Typical Specifications: Standard Options*:

Typical Specifications: Standard Options*:
The D1000
D1000-R_
Cabinet
Range Hood
Air
Flow
D1030-­‐F_
D1030-­‐F_ (NFPA101)
D1030-­‐R_
D1030-­‐R_ (NFPA101)
D1030-­‐I_-­‐DF
D1030-­‐I_-­‐DF (NFPA101)
D1030-­‐I_-­‐WF
D1030-­‐I_-­‐WF (NFPA101)
D1036-­‐F_
D1036-­‐F_ (NFPA101)
D1036-­‐R_
D1036-­‐R_ (NFPA101)
D1036-­‐I_-­‐DF
D1036-­‐I_-­‐DF (NFPA101)
D1036-­‐I_-­‐WF
D1036-­‐I_-­‐WF (NFPA101)
Width
30"
30"
30"
30"
30"
30"
30"
30"
36"
36"
36"
36"
36"
36"
36"
36"
Fan Type
INTERNAL
INTERNAL
INTERNAL
INTERNAL
In-­‐Line Duct Fan
In-­‐Line Duct Fan
Exterior Wall Fan
Exterior Wall Fan
INTERNAL
INTERNAL
INTERNAL
INTERNAL
In-­‐Line Duct Fan
In-­‐Line Duct Fan
Exterior Wall Fan
Exterior Wall Fan
Model: D1030-R
Spec & Submittal
Version 2.3
Venting
CFM (at hood) DUCT LENGTH (max)
FRONT (recirc)
140 CFM
N/A
FRONT (recirc)
500 CFM
N/A
REAR EXPELLING
250 CFM
N/A
REAR EXPELLING
500 CFM
N/A
Vertical Duct
470 CFM
35 FEET
Vertical Duct
510 CFM
35 FEET
Vertical Duct
150 CFM
20 FEET
Vertical Duct
550 CFM
20 FEET
FRONT (recirc)
140 CFM
N/A
FRONT (recirc)
500 CFM
N/A
REAR EXPELLING
250 CFM
N/A
REAR EXPELLING
500 CFM
N/A
Vertical Duct
470 CFM
35 FEET
Vertical Duct
510 CFM
35 FEET
Vertical Duct
150 CFM
20 FEET
Vertical Duct
550 CFM
20 FEET
Volts = 115 :: Hz = 60 :: Amps = 5 :: Light Bulb = 60A15/TF :: Elec. Cutoff = 50A-­‐208VAC Relay :: Gas Cutoff = 110VAC Solenoid
110VAC Supply Cable
Power Disconnect
Cable
Typical Specifications:
- Hood shall be D1000 Series by DENLAR Fire Protection
- Unit shall be wall mounted so that the bottom of the
mounting bracket sits 24” to 30” above the cooktop
- Unit shall be of stainless steel construction (#18 & #20
GA, polished 304) w/ no sharp edges and brushed finish
D1000-R_-NFPA101
- Unit shall have fire suppression system factory installed
- Activation of the mechanical fire suppression system
shall be by 212 or 280 degree fusible link (30” vs 36”)
- Wet chemical extinguishing agent: Low PH Amerex 660
(pressurized potassium citrate / potassium acetate mix)
- Unit shall have centrifugal fan with air delivery of 380 to
610 cfm, fan speed controller will be infinitely variable
Cabinet
Fan Box (NFPA101 rev)
Range Hood
- Unit shall be ETL listed, tested to UL300A stanfards, fan
motor shall be permanantly lubricated and meet UL507
Air
Flow
- Unit shall include a fuel shut-off device for gas & electric
110VAC Supply Cable
Power Disconnect
Cable
appliances, activated at suppression system discharge
- Unit shall also automatically disconnect range element
once a certain pre-set temperature in reached
- Unit shall have multiple alarm contacts pre-installed
(local, remote & trouble alarms) and an audible buzzer
- Lighting shall be by 60w shatter-proof bulb
Standard Options*:
MPK - Manual Pull Station Kit
NSF - Upgrade to Natl. Sanitation Foundation Compliance
ADA - Handicapped Accessible Control Box
CLBX - THE CLOCKBOX (Key-lock, Range Element Timer)
NFPA101 - Upgrade to NFPA Life Safety Code Compliance
*Custom Powdercoat Finishes Are Available
1
System Anatomy :: D1030-R
Suppression Tank
Safety Key
Mounting Bracket
S.S. Drip Cup
D1000 System
Front Grill / Charcoal Filter (F model only)
S.S. Grease Baffle
Top View
Front Grille (charcoal filter)
S.S. Drip Cup
S.S. Grease Baffle
Suppression Piping
Fusible Links
Mounting Bracket
D1000 System
Bottom View
The D1000
2
Model: D1030-R
Spec & Submittal
Version 2.3
Integrated Fire Suppression System
Cut-Away View From Bottom
Nozzle Type:
40 degree Conical Spray
Number of Nozzles:
4 protecting the appliance
1 located in the plenum
Chemical Agent:
AMEREX 660
-low PH wet chemical
Bottle Volume:
approx. 1.5 liters
The D1000
3
Model: D1030-R
Spec & Submittal
Version 2.3
22 1/8"
0"
29 7/
29 7/8"
22 1/
0"
System & Components
5 13/16"
6 9/16"
5 13/16"
35 7/8"
25 1/8"
6 9/16"
5 13/16"
6 9/16"
29 7/8"
D1030: Outer Shell
29 7/8"
7 5/8"
3 5/16"
10 1/2"
35 7/8"
19 3/8"
The D1000
Model: D1030-R
Spec & Submittal
Version 2.3
4
D1000: Standard Mounting Plate
D1000: NFPA101 Mounting Plate
*
D1030FC: 30” Top Cover for R unit
*
5
Indicates OPTIONAL component
The D1000
Model: D1030-R
Spec & Submittal
Version 2.3
D1000-G: Controlled
GAS Solenoid Valve
Included:
6 ft shielded control wire
-plug & play connection
D1000-E: Electric Range
Element Disconnect
Included:
6 ft shielded control wire
-plug & play connection
*
D1000-MPK:
Manual Pull
Station Kit
Included:
18 ft braided metal rope
3 corner pulley’s
*
6
Indicates OPTIONAL component
The D1000
Model: D1030-R
Spec & Submittal
Version 2.3
*
D1000-ADA:
Handicapped
Accessible
Control Box
Included:
8ft shielded control wire
-plug & play connection
*
D1000-CLBX:
CLOCKBOX II Range
Element Timer /
Lock-Out System
Included:
20ft shielded control wire
-plug & play connection
*
7
Indicates OPTIONAL component
The D1000
Model: D1030-R
Spec & Submittal
Version 2.3
NFPA101 Calibration :: D1030-R_-NFPA101
The NFPA101 Upgrade to the DENLAR D1000 is intended to offer total compliance to a 2012 Amendment
to The NFPA Life Safety Code section 18.3.2.5.3. The “NFPA101” calibration packages the following options
into one simple upgrade: +500cfm of Air Delivery, a Manual Pull Station Kit and The CLOCKBOX.
Fan Stack :
Front View
Fan Stack : Bottom View
NOTE: The NFPA LSC
(101) requires 500cfm of
airflow in a 300A hood
& suppression system.
This amount of airflow,
through a recirculating
hood, will creates inefficiencies within the system
resulting in additional
noise production.
D1030-R_-NFPA101
Exploded View
Rear Duct Access Panel
(on R model only)
NFPA101 Fan Stack (F & R models)
Mounting Bracket
NFPA101 Fan Collar (F & R models)
Pull Station
Pass-through
Front Grill / charcoal filter
(on F model only)
Safety Key
D1000 System
Suppression Tank
S.S. Grease Baffle
S.S. Drip Cup
The D1000
8
Model: D1030-R
Spec & Submittal
Version 2.3
D1000 Electrical Diagram - Complete Schematic
The D1000
9
Model: D1030-R
Spec & Submittal
Version 2.3