Honeywell T8602D Installation instructions
Add to my manuals
12 Pages
Honeywell T8602D offers precise temperature control for your home's heating and cooling systems. It features a user-friendly interface with a large backlit display for easy viewing, even in dim light. Program up to 4 daily periods with different temperatures for each, providing customized comfort levels throughout the day. The T8602D also includes a filter change reminder and the ability to display outdoor temperature (requires additional sensor).
advertisement
T8602D Chronotherm® IV
Programmable Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The T8602 Chronotherm® IV Programmable Thermostat provides electronic control of 24 Vac single-stage heating and cooling systems or 750 mV heating and 750 mV cooling. Refer to Table 1 for a general description of the thermostat. All T8602 Thermostats are powered by batteries.
T8602
D
System
Heat-Cool
Changeover
Manual or
Automatic
Selectable
Table 1. Description of T8602 Thermostats.
System
Selection
Heat-Off-Cool or
Heat-Off-Cool-Auto
Fan
Selection Comments
On-Auto System and fan selections are done by keyboard.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Location
Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 50.8 mm x 101.6 mm (2 in. x 4 in.) wiring box.
Position wallplate horizontally on the wall or on a
50.8 mm x 101.6 mm (2 in. x 4 in.) wiring box.
1. Position and level the wallplate (for appearance only). The thermostat will function properly even when not level.
2. Use a pencil to mark the mounting holes. See Fig.
2.
3. Remove the wallplate from the wall and drill two
4.76 mm (3/16 in.) holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 5.56 mm (7/32 in.) holes. Gently tap anchors
(provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
® U.S. Registered Trademark
Copyright © 2003 Honeywell International Inc. • • All Rights Reserved
69-1510-4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
NO
YES
NO
1.5 METERS
(5 FEET)
NO
M10856
WIRES
THROUGH WALL
WALL
ANCHORS (2)
WIRING
Fig. 2. Mounting the wallplate.
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 through 6 for typical hookups.
A letter code is located near each terminal for identification.
CAUTION
Electrical Hazard.
WALL
Fig. 1. Typical location of thermostat.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 7.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
MOUNTING
HOLES
MOUNTING
SCREWS
M15044
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
THERMOSTAT
G W RC
2
Y R OT
3
OT
COMPRESSOR
CONTACTOR
HEAT
RELAY
FAN
RELAY
OUTDOOR
TEMPERATURE
SENSOR
L1
(HOT)
L2
1
1
COOLING
TRANSFORMER
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
L1
(HOT)
L2
HEATING
TRANSFORMER
2 JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
ONE TRANSFORMER SYSTEM.
3 AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
M10855
Fig. 3. Typical hookup in heat and cool system with two transformers.
69-1510-4 2
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Y G O
THERMOSTAT
B W R RC OT
3
OT
COMPRESSOR
CONTACTOR
COOL
DAMPER
2
HEAT
RELAY
OUTDOOR
TEMPERATURE
SENSOR
FAN
RELAY
HEAT
DAMPER
2
1
1
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
L1
(HOT)
L2
2 CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
3 AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
M10347A
Fig. 4. Typical hookup in heat and cool system with one transformer.
PILOTSTAT
CONTROL
(IF USED)
MILLIVOLT HEATING-24Vac
COOLING WALLPLATE
W G R RC Y O
TH
TH/
PP
PP
LIMIT
CONTROL
CHANGEOVER
RELAY
MILLIVOLTAGE
GENERATOR
MILLIVOLTAGE
GAS CONTROL
FAN
RELAY
COOLING
CONTACTOR
L1
(HOT)
L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
M2942
Fig. 6. Typical hookup in millvoltage heating and
24 Vac cooling circuit.
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM).
PILOTSTAT
CONTROL
(IF USED)
MILLIVOLT HEATING-ONLY
WALLPLATE
W R
TH
TH/
PP
LIMIT
CONTROL
PP MILLIVOLTAGE
GAS CONTROL
MILLIVOLTAGE
GENERATOR
M2931
Fig. 5. Typical hookup in millivoltage heating circuit.
M4826
Fig. 7. Correct wiring technique.
Mounting Thermostat
1. Engage tabs at the top of the thermostat and wallplate. See Fig. 7.
2. Press lower edge of case to close and latch.
NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove top last.
A.
ENGAGE TABS
AT TOP OF
THERMOSTAT
AND WALLPLATE.
3
B.
PRESS LOWER
EDGE OF CASE
TO LATCH.
M14628
Fig. 8. Mounting thermostat on wallplate.
69-1510-4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Using Thermostat Keys
The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures,
• display present setting,
• configure Installer Setup,
• check Self-Test,
• display outdoor temperature (select models),
• set the system operation,
• set the fan operation.
See Fig. 9 for the location of the keys.
INCREASE TIME SETTING
OR SCROLL FORWARD
THROUGH INSTALLER SETUP
AND SYSTEM TEST
SET WAKE TIMES
AND SETPOINTS
SET CURRENT
DAY AND TIME
SET LEAVE TIMES
AND SETPOINTS
SET RETURN TIMES
AND SETPOINTS
RETURN TO
NORMAL
OPERATIONS
ENTER
INDEFINITE
OR TIMED
HOLD MODE
Run
Program
Set Current
Day/Time
Time
Wake
Set Program
Leave Return Sleep
SET CURRENT OR
PROGRAM DAY
CHANGE BETWEEN
DAYLIGHT SAVINGS
AND STANDARD TIME
Hold Temp Day
Daylight
Time
Copy
Heat/Cool
Settings
System Fan
COPY ONE PROGRAMMED
DAY TO ANOTHER DAY
DECREASE TIME SETTING OR
SCROLL BACKWARD THROUGH
INSTALLER SETUP AND SYSTEM TEST
Fig. 9. T8602D key locations and descriptions.
INCREASE TEMPERATURE
SETTING OR SCROLL
FORWARD THROUGH
INSTALLER SETUP OPTIONS
DECREASE TEMPERATURE
SETTING OR SCROLL
BACKWARD THROUGH
INSTALLER SETUP OPTIONS
DISPLAY INFORMATION
SUCH AS PRESENT
SETTINGS AND OUTDOOR
TEMPERATURE
SET SLEEP TIMES
AND SETPOINTS
SELECT FAN
OPERATION
SELECT SYSTEM
OPERATION
CHANGE BETWEEN
HEATING AND COOLING
SETPOINTS
M14624
SETTINGS
System and Fan Settings
The System default setting is Heat and the Fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 10. The fan settings can be set for each program period individually. The system selection is for all the program periods.
System settings control the thermostat operation as follows:
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between heating and cooling operation, depending on the indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Fan operates with equipment.
Time
Run
Program
Hold Temp
Set Current
Day/Time
Day
Daylight
Time
Copy
Wake
Heat/Cool
Settings
Set Program
Leave Return
System
Sleep
Fan
System
Fan
M14625
Fig. 10. Thermostat System and Fan key locations.
NOTE: Always press the keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.
69-1510-4 4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Temperature Settings
Refer to Table 2 for the default program settings. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owner’s Guide, form 69-0940, for complete instructions on changing the program.
Wait Set Program Set Day/Time Temporary Setting
Recovery
Hold for
AM
Filter Em Ht Aux Ht
PM
Days
Mon Tue Wed Thu Fri Sat Sun
Wake Leave Return Sleep
Repl Batt
DST
Room Outdoor
Heat Cool
System
Em Heat
Off
Cool
Auto
Fan
On
Auto
M14559 Table 2. Default Program Settings.
Period
Wake
Leave
Time
6:45 AM
8:45 AM
Heat
Setpoint
20°C
4.5°C
Return 5:00 PM
Sleep 10:00 PM
20°C
4.5°C
Cool
Setpoint
25°C
37°C
25°C
37°C
Fan
Setting
Auto
Auto
Auto
Auto
Fig. 11. Display of all LCD segments.
INSTALLER SETUP
NOTE: For most applications, the thermostat factorysettings do not require changing. Review the factory settings in Table 2 and, if no changes are necessary, go to Installer Self-Test section.
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, system changeover and outdoor temperature display. Installer Setup numbers are listed in
Table 3. The table includes all the configuration options and the factory-settings for the T8602.
A combination of key presses is required to use the
Installer Setup feature.
— To enter the installer setup, press and hold the information i key with the increase and decrease keys until the first number is displayed.
All display segments appear for approximately three seconds before the number is displayed. See Fig. 11 and 12.
— To advance to the next Installer Setup, press the Time
∆ key.
— To change a setting, use the increase or decrease key.
— To scroll the Installer Setup numbers backward, press the Time ∇ key.
— To exit the Installer Setup, press Run Program.
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)
FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)
M14618
Fig. 12. Display of Installer Setup number and setting.
CAUTION
Electric Heat Configuration Hazard.
Can cause equipment damage.
Configure electric heat system to 1 in Installer
Setup number 2 to prevent system running without fan.
IMPORTANT
Only configured numbers are shown on the device. Example: If thermostat does not have a
System key, Installer Setup Number 12 will not be displayed. Review Table 3 factory settings and mark any desired changes in the Actual
Setting column. When Installer Setup is complete, review the settings to confirm that they match the system.
5 69-1510-4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Select
Not Used.
Fan operation.
Not Used.
Heating cycle rate.
Not Used.
System setting adjustment
Adaptive
Intelligent
Recovery™ control.
Not Used.
Clock format.
Not Used.
Outdoor temperature display
(select models).
Not Used.
Minimum off time for the compressor.
Temperature range stops in heating.
Temperature range stops in cooling.
Not Used.
Installer Setup
Number (Press
Time ∆ key to change)
1
2
(Number 2 must be set to 1 to extend fan operation.)
3
4
5 thru 11
12
Table 3. Thermostat Installer Setup Options.
Factory Setting
Display
—
0
—
6
—
1
Description
—
Conventional applications where equipment controls fan operation in heat mode.
—
6—6 cph used for conventional heat.
—
Manual changeover
Other Choices
(Press or key to change)
Display Description
—
1
—
Heat pump or electric heat applications where thermostat controls fan operation in heat mode.
9
—
1, 3, or
—
0 or 2
—
1—1 cph used for radiant
floor heat, gravity system.
3—3 cph used for hot water systems or high efficiency furnaces.
9—9 cph used for electric heat systems.
—
0—Auto changeover
2—Auto only
13
14 thru 15
16
17 thru 23
24
25 thru 32
33
34
35
36
1
—
0
—
0
—
5
32.0
7.0
—
Conventional recovery
(system starts recovery at programmed time).
—
12-hour clock format.
—
No outdoor temperature is displayed.
—
5 minute minimum off time for the compressor.
Highest setting for heating setpoint.
Lowest setting for cooling setpoint.
—
—
1
—
1
—
Adaptive Intelligent
Recovery™ control is activated (system starts early so setpoint is reached by start of program period).
—
24-hour clock format.
—
Outdoor temperature is displayed. Needs a
C7089B1000 Outdoor
Temperature Sensor to operate.
—
0 thru 4 Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor.
4.5 to
31.5
7.5 to
37.0
—
Temperature range (0.5°C increments) of heating setpoint settings.
Temperature range (0.5°C increments) of cooling setpoint settings.
—
Actual
Setting
—
—
—
—
—
—
—
—
69-1510-4 6
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Select
Temperature display adjustment.
Furnace Air
Filter Timer.
Humidifier
Pad Monitor.
Ultraviolet
(UV) Air
Treatment
System Lamp
Monitor.
Table 3. Thermostat Installer Setup Options. (Continued)
Installer Setup
Number (Press
Time ∆ key to change)
37 0
Factory Setting
Display Description
No difference in displayed temperature and actual room temperature.
43
44
45
0
0
0
Off
Off
Off
1, 2, 3,
4
Other Choices
(Press or key to change)
Display
1.5 thru
-1.5
1, 2, 3
1
Description
.5—Display adjusts to
0.5°C higher than actual room temperature.
1.0—Display adjusts to
1.0°C higher than actual room temperature.
1.5—Display adjusts to
1.5°C higher than actual room temperature.
-.5—Display adjusts to -
.5°C lower than actual room temperature.
-1.0—Display adjusts to -
1.0°C lower than actual room temperature.
-1.5—Display adjusts to -
1.5°C lower than actual room temperature.
1 – 10 days
2 – 30 days
3 – 60 days
4 – 120 days
(Time counted when heat, cool or fan is running.)
1 – 90 days
2 – 180 days
3 – 365 days
(Time counted by calendar days in heat mode.)
1 – 365 days
(Times counted by calendar days in any mode.)
Actual
Setting
IMPORTANT
Review the settings to confirm that they match the system. Press Run Program to exit the
Installer Setup. The thermostat has saved the
Installer Setup changes and initiated a reset in order to operate using the new settings. Be sure to set the current day and time immediately.
7 69-1510-4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Setting Current Day and Time
1. Press Set Current Day/Time.
NOTE: On initial powerup or after an extended power loss, 1:00 pm flashes on the display until a key is pressed.
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat operation. Refer to Table 4 for a list of the available system tests.
Set Current
Day/Time
Run
Program
Hold Temp
Set Current
Day/Time
Day
Time
Wake
Set Program
Leave Return Sleep
Heat/Cool
Settings
System Fan
Daylight
Time
Copy
Mon
Set Day/Time
PM
2. Press Day until the current day is displayed.
NOTE: Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday,
Thu=Thursday, Fri=Friday, Sat=Saturday.
M14619
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed during Installer System Test.
Avoid cycling compressor quickly.
To start the system test:
Press and hold the increase and decrease keys at the same time until 10 appears. All segments of the display will be displayed before the 10 appears.
See Fig. 13 and 14.
Set Day/Time
Tue
PM
Day
Run
Program
Set Current
Day/Time
Time
Wake
Set Program
Leave Return Sleep
Heat/Cool
Settings
System Fan Hold Temp Day
Daylight
Time
Copy
M14620
3. Press Time ∆ or Time ∇ until the current time is displayed.
NOTE: Tapping the Set Current Day/Time changes the time in one hour increments.
Time
Set Day/Time
AM
Run
Program
Hold Temp
Set Current
Day/Time
Day
Time
Wake
Set Program
Leave Return Sleep
Heat/Cool
Settings
System Fan
Daylight
Time
Copy
Tue
M14621
NOTE: If the current time is Daylight Savings Time, press Daylight Time until DST is displayed.
Table 4. Tests Available In Installer System Test.
Test
Number
10-19
30-39
40-49
60 0 to
60 19
70-79
System Test Description
Heating equipment can be turned on and off.
Cooling equipment can be turned on and off.
Fan equipment can be turned on and off.
Keyboard keys test.
Thermostat information, including date code and software versions, is displayed.
Daylight
Time
Run
Program
Set Current
Day/Time
Hold Temp Day
Daylight
Time
Time
Wake
Heat/Cool
Settings
Set Program
Leave Return
System
Sleep
Fan
Copy
4. Press Run Program.
Tue
Set Day/Time
AM
DST
M14622
Wait Set Program Set Day/Time Temporary Setting
Recovery
Hold for
AM
Filter
Mon
Em Ht Aux Ht
PM
Days
Tue Wed Thu Fri Sat Sun
Wake Leave Return Sleep
Repl Batt
DST
Room Outdoor
Heat Cool
System
Em Heat
Off
Cool
Auto
Fan
On
Auto
M14559
Fig. 13. Display of all LCD segments.
Run
Program
Run
Program
Set Current
Day/Time
Time
Wake
Set Program
Leave Return Sleep
Heat/Cool
Settings
System Fan Hold Temp Day
Daylight
Time
Copy
Wake
Tue
69-1510-4
AM
DST
Room
System
Heat
Fan
Auto
M14623
8
M14612
Fig. 14. Display of test number.
Refer to Table 5 for the directions and results of the specific tests.
NOTE: Press Time ∆ to advance to the next test and
Time ∇ to go back to the previous test. Press
Run Program to exit the System Test
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
Table 5. Installer System Test Options.
Keys to
Press
Test
Number
Heating Equipment System Test
Time ∆ 10 Enter heating equipment system test.
11
Description
Heat comes on. When Installer Setup number 2 is 1, the system fan is also energized.
10 Heat and system fan turn off.
Cooling Equipment System Test
Time ∆ 30 Change from heating to cooling equipment system test.
31
30
Cool and system fan come on.
Cool and system fan turn off.
Fan Equipment System Test
Time ∆ 40
41
Change from cooling to fan equipment system test.
Fan comes on.
40 Fan turns off.
Key Operation System Test
Time ∆ 60 2 Change from fan to key operation system test.
NOTE: Press any key and the displayed numbers will change. Press Time ∇ to go to the previous test and Time ∆ to go to the next test. The Run Program key does not exit this test. Press Time ∆ or Time ∇ and then the Run
Program key to exit.
9 69-1510-4
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
THERMOSTAT INFORMATION
1. Press the Time ∆ key to access the thermostat information.
4. Press the increase key again to display the software revision number.
(Example: 001 = Revision number 1).
M14613
2. Press the increase key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year.
(Example: 027 = February 1997).
M14616
5. Press the increase key again to display the
EEPROM identification code.
(Example: 314 = EEPROM ID 314).
M14614
3. Press the increase key again to display the software identification code.
(Example: 02 = software ID code 2).
M14617
6. Press the Run Program key to exit the system test.
The system test times out after four minutes without any key presses.
CHECKOUT
Outdoor Temperature Sensor
(Select Models)
Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading.
M14615
69-1510-4 10
T8602D CHRONOTHERM® IV PROGRAMMABLE THERMOSTATS
TROUBLESHOOTING GUIDE
Symptom
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example:
Cannot set the heating higher or the cooling lower.)
Heating will not come on.
Table 6. Troubleshooting Guide.
Possible Cause
Thermostat is not being powered.
Action
• Check if batteries are present and installed correctly.
— If batteries are present and installed correctly, replace thermostat.
Enter Installer Setup number 37 and reconfigure the display.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
Bad thermostat location.
Enter Installer Setup number 14 and reconfigure the display.
Relocate the thermostat.
The upper or lower temperature limits were reached.
Check the temperature setpoint:
• Heating limits are 4.5 to 32°C
• Cooling limits are 7 to 37°C
The setpoint temperature range stops were configured.
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint stops.
Cooling will not come on.
Heating or cooling come on momentarily and shut off.
No power to the thermostat.
System selection is not set to
Cool.
Cool setpoint is above room temperature.
Heat or cool circuit is opening up or becoming high impedance.
• Check for 24 Vac between R and W terminals (check for
750 mV on PowerPile ® Systems).
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit breaker.
— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in the Off position—set to the On position.
— check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Wait up to five minutes for the system to respond.
Thermostat minimum off time is activated.
System selection is not set to
Heat.
Heating setpoint is below room temperature.
No power to the thermostat.
Thermostat minimum off time is activated.
Set system selection to Heat.
Check heating setpoint. Set heating setpoint to desired temperature.
• Check for 24 Vac between R or RC and Y terminals
— If missing 24 Vac:
— check if the circuit breaker is tripped—reset the circuit breaker.
— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in the Off position—set to the On position.
— check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off time (if required).
Set system selection to Cool.
Check cooling setpoint. Set cooling setpoint to desired temperature.
Add resistor in parallel with load or install interface relay.
11 69-1510-4
Table 6. Troubleshooting Guide. (Continued)
Symptom Possible Cause Action
System on indicator
(flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
Fan operation set for 0 (conventional heat) when it should be set for 1 (electric heat).
Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint.
Enter Installer Setup number 2 and reconfigure the fan operation.
Wait a minute after seeing the on indicator and then check the registers.
Outdoor temperature not displayed a
Outdoor temperature display is incorrect a
Heating or cooling equipment is not operating.
Option not activated.
Verify operation of heating or cooling equipment in self-test.
Enter Installer Setup number 24 and set to 1. Thermostat must have OT terminals and a C7089B1000 Sensor installed.
Outdoor sensor is connected incorrectly.
Wrong sensor.
Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor.
Replace sensor with C7089B1000 Sensor.
a Select models.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
69-1510-4 G.H. Rev. 03-03
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
www.honeywell.com/yourhome
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 application
- 1 Installation
- 1 When Installing this Product...
- 1 Location
- 1 Wallplate Installation
- 2 Wiring
- 3 Mounting Thermostat
- 4 Using Thermostat Keys
- 4 Settings
- 5 Temperature Settings
- 5 Installer setup
- 8 Setting Current Day and Time
- 8 Installer System test
- 10 Thermostat Information
- 10 Checkout
- 10 Outdoor Temperature Sensor (Select Models)
- 11 Troubleshooting Guide