Honeywell Thermostat V4062C User's Manual

Add to my manuals
8 Pages

advertisement

Honeywell Thermostat V4062C User's Manual | Manualzz

APPLICATION

The V4062 Gas Valve Actuator in combination with a V5055 or V5097 Gas Valve provides three-position control of the gas supply to commercial and industrial burners.

FEATURES

• When energized, the V4062 Actuator opens the V5055/

V5097 Gas Valve to the low-fire position. The actuator opens the valve to the fully open position when the line voltage contacts are made.

• When used with the V5055, V5097 or VE5000 Gas

Valve, the combination is rated for final safety shutoff service.

• Although the V4062 can be used with all V5055 or

V5097 Valve models, the V5055/V5097B with characterized guide is recommended for optimum control and low-fire repeatability

V4062A,B,D

HI-LO-OFF Fluid Power

Gas Valve Actuator

PRODUCT DATA

• The standard model has an opening time of

26 seconds at 60 Hz, or 32 seconds at 50 Hz. A fastopening model is available, with timings of

13 seconds at 60 Hz, or 16 seconds at 50 Hz.

• Maximum closing time is one second, which meets code, standard, insurer requirements.

• Damper shaft models are available with or without spring return; shaft extends out both sides and rides in Delrin bushings; used with standard damper crank arm (part no. 7616BR).

• Red OPEN indicator attached to the actuator stem shows when the valve is even slightly open; yellow

SHUT indicator on the valve stem shows only when the gas valve is fully closed.

• Ambient temperature range is -40

°

to 150

°

F (-40

°

to

66

°

C) for 60 Hz models; -10

°

to 158

°

F (23

°

to 70

°

C) for

50 Hz and 50/60 Hz models.

• Models available with factory adjusted, fieldadjustable, single-pole-double throw (spdt) auxiliary switch rated at 1/2 hp (0.37 kW). Auxiliary switch can be added in the field.

• Low-fire position is adjustable with adjusting wrench, part no. 135796 (included with the actuator).

• Standard enclosure meets NEMA 1 (IP30) general purpose requirements.

• V4062/V5055C,E and V4062/V5097C,E combinations available with a proof-of-closure switch and double valve seal (valve seal overtravel interlock) to meet specific code/standard/insurer requirements.

• Model available to be used with series 60 floating type controller.

• Model available with adjustable maximum flow switch.

Contents

Application ..........................................................................

1

Features ..............................................................................

1

Specifications ......................................................................

2

Ordering Information ...........................................................

2

Installation ...........................................................................

4

Wiring ..................................................................................

5

Adjustments ........................................................................

6

Operation ............................................................................

7

Service and Checkout ........................................................

8

® U.S. Registered Trademark

Copyright © 1998 Honeywell Inc. • All Rights Reserved 60-2099-8

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

SPECIFICATIONS

IMPORTANT:

The specifications given in this publication do not include normal manufacturing tolerances.

Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

Models:

V4062A HI-LO-OFF Gas Valve Actuator.

V4062B HI-LO-OFF Gas Valve Actuator, high pressure.

V4062D HI-LO-OFF Gas Valve Actuator with proof-ofclosure switch. Use with V5055/V5097C,E (double seal) gas valves for valve seal overtravel interlock. Do not use V4062 with V5034 Valve body.

Electrical Ratings:

Standard V4062A,D Actuators (Table 1):

60 Hz, 26 second opening.

50 Hz, 32 second opening.

Voltage

Frequency

120V /60 Hz

100V

50/60 Hz

200V

50/60 Hz

Table 1. Standard V4062A,D Actuators.

W

Opening

Va W

Holding

Va

59.5

129 19.0

28.0

53.0/42.7

105/80 20.0/17.2

33/29

72.01/52.5

160/110 18.4/16.2

28/24

Fast-opening V4062A,D Actuators (Table 2):

60 Hz, 13 second opening.

50 Hz, 16 second opening.

Table 2. Fast-opening V4062A,D Actuators.

Voltage

Frequency

Opening

W

59.5

Va

129 120V/60 Hz

220V/50 Hz

220V/50 Hz

84.0

82.0

196

180

220-240V

50/60 Hz a

74.5

143.5

220-240V

50/60 Hz b a b

61.9

230V, 50 Hz power supply.

230V, 60 Hz power supply..

112

W

Holding

19.0

17.0

16.5

13.7

11.2

Va

28.0

27.0

26.4

24.8

20.5

Fast-opening V4062B Actuators (Table 3):

60 Hz, 13 second opening.

50 Hz, 16 second opening.

Table 3. Fast-opening V4062B Actuators.

Voltage

Frequency

Opening

W

220-240V /50/60 Hz a

76.5

220-240V /50/60 Hz b a b

64.4

230V, 50 Hz power supply.

230V, 60 Hz power supply.

Va

150.6

118.2

W

13.3

11

Holding

Va

28.8

23.2

Pressure Ratings Of Valve-Actuator Combinations:

See Table 4.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386 (612) 951-1000

In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

60-2099—8 2

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

Table 4. Pressure Ratings of Valve-Actuators Combinations.

V4062A,D Actuator a

Differential b

Closeoff c

V4062B Actuator

Differential b

Closeoff c

Valve psi mbar psi bar psi mbar psi bar

V5055A,C; V5097A,C 3/4 to 3 in.

V5055A,C 4 in.

V5055B, V5097B 3/4 to 3 in.

V5055B 4 in.

5

3

5

3

340

200

340

200

15

15

15

15

1

1

1

1

15

5

15

5

1000

340

1000

340

15

15

15

15

V5055D,E 3/4, 1, 1-1/4, 1-1/2 in.;

V5097D 3/4 in. to 2 in.

5 340 75 5 25 1700 75 5 b c

V5055D,E; V5097D,E 2, 2-1/2, 3 in.

a

5 340 45 3 15 1000 45 3

Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal overtravel interlock.

Maximum operating pressure differential.

Maximum closeoff pressure without seal leakage. this is the maximum allowable pressure drop to which a valve may be subjected while fully closed, and is independent of the valve body rating.

1

1

1

1

Auxiliary Switch And Proof-Of-Closure Switch Ratings:

See Table 5.

Table 5. Auxiliary Switch and Proof-of-Closure

Switch Ratings (1/2 hp [0.37 kW] a

Load

Full Load

120V

9.8A

).

240V

4.9A

a

Locked Rotor 58.8A

29.4A

Maximum total connected power to both switches (if used) is 1800 VA.

Mounting:

Mounts directly to V5055/V5097 Valve with two setscrews positioned 90 degrees apart.

Valve and actuator can be mounted in any position

(multipoise).

NOTE: 220 to 240 Vac, 50/60 Hz models must be mounted vertically.

Mounting Dimensions:

See Fig. 1.

Low-Fire Adjustment:

0.17 inch to 0.64 inch (with respect to V5055/V5097B

Valve) valve stem travel.

NOTE: The low-fire position of the V5055/V5097A,C,D and

E Valves differ from the V5055/V5097B. Check the valve flow curves and match the low-fire position to the burner design and valve application.

Nominal Opening Time:

Standard Models: 26 sec at 60 Hz; 32 sec at 50 Hz.

Fast-opening Models: 13 sec at 60 Hz; 16 sec at 50 Hz.

Closing Time:

1 sec maximum

Damper Shaft:

3/8 in. sq (9.5 mm) for use with 7616BR Damper Crank

Arm (not included). Models available with or without damper shaft return spring.

Maximum Damper Shaft Rotation:

52 angular degrees.

Maximum Force:

At 2-11/16 in. (68.3 mm) radius for 7616BR Damper

Crank Arm (ordered separately).

NOTE: Damper shaft drives damper crank arm in one direction only; optional return spring is available on damper shaft to turn damper crank arm in opposite direction. See Table 6.

Table 6. Actuator Torque (With and

Without Return Spring).

V4062

Model

-40

°

F to 20

°

F

(-40

°

C to -7

°

C) lb N

5 22.2

20

°

F to 150

°

F

(-70

°

C to 66

°

C) lb

20

N

89.0

Without return spring

With return spring 5 22.2

10 44.5

3 60-2099—8

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

B

1

A

6-3/4 (171.5)

3-23/32

(94.5)

VALVE

27/32

(21.4)

1-9/32

(32.5)

KNOCKOUT

FOR 1/2 INCH

CONDUIT (4)

5 (127.0)

VALVE

1 ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.

VALVE SIZE

INCH

3/4

1

1-1/4

1-1/2

2

2-1/2

3

4

IN.

DIM A

11-1/8

11-1/8

11-1/8

11-1/8

11-1/4

11-3/4

11-3/4

14-1/8

V5055

MM

282.6

282.6

282.6

282.6

285.8

298.5

298.5

358.8

IN.

DIM B

MM

2-3/4

2-3/4

2-3/4

2-3/4

2-7/8

3-3/8

3-3/8

5-13/16

69.9

69.9

69.9

69.9

73.0

85.7

85.7

147.6

IN.

DIM A

MM

V5097

IN.

DIM B

MM

11-1/8

11-1/8

11-1/8

11-1/8

11-3/4

11-3/4

11-3/4

283

283

283

283

298

298

298

2-3/4

2-3/4

2-3/4

2-3/4

3-3/8

3-3/8

3-3/8

70

86

86

86

70

70

70

M10981

Fig. 1. Approximate mounting dimensions of V4062 Actuators in in. (mm).

Ambient Operating Temperature Rating:

-40

°

to 150

°

F (-40

°

to 66

°

C) for 60 Hz models;

-10

°

to 158

°

F (-23

°

to 70

°

C) for 50 Hz and 50/60 Hz models.

Approvals:

Underwriters Laboratories Inc. Listed: File No. MH1639,

Guide No. YIOZ.

Factory Mutual: Approved.

International Approval Services (Joint Venture of the

American Gas Association [AGA] and the Canadian

Gas Association [CGA]): Certified 60 Hz models only.

Industrial Risk Insurers Acceptable.

Some V4062 Actuators are approved as Class A valves in accordance with EN161:

When used with V5055 Valves: Pin: CE-0063AR1359.

When used with VE5000 Series Valves: Pin: CE-

0063AP3075.

Accessories:

133568 Auxiliary Switch Bag Assembly.

133569 Proof-of-Closure Switch Bag Assembly. (Must be used with a V5055/V5097C or E with double seal).

135796 Wrench (included with the actuator).

7616BR Damper Crank Arm (damper arm and clip).

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3. Installer must be a trained experienced, flame safeguard control technician.

4. After installation is complete, check out product operation as prided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause serious injury or death.

Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

IMPORTANT

1. All wiring must comply with all applicable electrical codes, ordinances, and regulations. All wiring must be NEC Class 1.

2. Voltage and frequency of the power supply connected to this control must agree with those marked on the device.

3. Loads connected to the auxiliary switch and/or proof-of-closure switch, if used, must not exceed the ratings given in the Specifications section.

4. When replacing a V6034 Actuator with a V4062, the

V5034 Valve body must be changed to a V5055

Valve.

5. Do not attempt to use the V4062 Actuator with the

V4055/V5034 Adapter. Differences in stem travel can prevent correct low fire adjustment.

Install Valve

The actuator is installed directly on the V5055/V5097 body after the valve is installed in the gas supply line. Refer to the instructions packed with the V5055/V5097 Gas Valve for installation details. When installing the valve, assure that:

1. Sufficient clearance is allowed for actuator installation and service.

2. Ambient temperatures at the valve location do not exceed actuator ratings.

3. Position of the valve permits damper hookup if one is controlled.

Install Accessory Switches (If Needed)

An spdt switch can be installed to operate an auxiliary load up to 1/2 hp (0.37 kW). The switch can be adjusted to operate at any point in the valve stroke.

A proof-of-closure switch can also be installed with a V5055/

V5097C or E Valve (with double seal) on any V4062 Actuator to provide a valve seal overtravel interlock. The spdt proof-ofclosure switch is installed to make or break a circuit when the valve is in the closed position. The switch is not adjustable.

60-2099—8 4

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

NOTE: Mark the actuator or valve to indicate any changes made.

To install the switches, proceed as follows:

1. Remove the actuator faceplate (two screws).

2. Remove the silver-colored barrier to expose the actuator stem.

3. Insert the auxiliary switch in the position indicated in

Fig. 2. Fasten with two screws through the actuator base.

4. Insert the proof-of-closure switch in the position shown in Fig. 2. The proof-of-closure switch mounts against the side of the actuator housing. The mounting holes are spaced to allow mounting the switch only in the correct position. Fasten with two screws through the actuator base.

5. If only one switch is used, install the narrow barrier included with the switch in the unused space.

6. Mount the actuator before making wiring connections and adjustments to the auxiliary switch.

133568

AUXILIARY

SWITCH (OR MAX

FLOW LIMIT SWITCH,

FACTORY INSTALLED)

133569

PROOF-OF-

CLOSURE SWITCH

AUXILIARY

SWITCH OR MAX

FLOW LIMIT SWITCH

ADJUSTMENT

SCREW

LOW-FIRE

ADJUSTMENT CAM

Fig. 2. V4062 Actuator with cover removed.

M7338A

Mount Actuator On Valve

Check the final position of the V5055/V5097 Valve body to be sure that the actuator will be in the proper position when mounted on the valve. This is especially important when the actuator is used to drive a damper.

If two smaller size valves are mounted very close together, as in an Industrial Risk Insurers type valve train, it may be necessary to mount the actuators off center to provide adequate clearance.

Slip the bottom collar of the actuator over the valve bonnet assembly. Rotate the actuator to the desired position and use a 5/32-inch Allen wrench to securely tighten the two setscrews (50 to 60 lb-in. [5.7 to 6.8 N•m]). Connect the damper linkage, if used. Refer to the instructions packed with the damper crank arm.

Mount and Adjust 7616BR Damper Crank

Arm (If Used)

The damper crank arm provides a maximum travel of

2-5/16 in. (58.7 mm) through a stroke of 52 degrees. See

Fig. 3. If the V4062 has a damper shaft return spring, dampers go to the closed position when power is interrupted by the programmer. Refer to the instructions packed with the

7616BR Damper Crank Arm for complete installation information.

WIRING

Wiring must comply with all applicable electrical codes, ordinances, and regulations. Wiring to the actuator and to the controller must be NEC Class 1.

Connect the power from the flame safeguard control to terminals 1 and 2 on the V4062 terminal strip, and connect the firing rate controller to terminals 3 and 4. Refer to Fig. 4 for typical connection. Fig. 5 shows the wiring for connecting the Max Flow Limit Switch to the actuator. For other typical system hookups, refer to the instructions packed with the device used to control the valve.

When all wiring connections are complete, replace the actuator faceplate.

CAUTION

Equipment Damage Hazard.

Can cause equipment damage or improper and dangerous operation.

Label all wires prior to disconnection when servicing valves. Wiring errors can cause improper and dangerous operation.

52 DEGREE

ANGULAR

ROTATION

2-5/16 (58.7)

MAXIMUM

TRAVEL

7616BR

DAMPER

ARM

SHAFT

2-11/16 (68.3)

RADIUS M7322

Fig. 3. 7616BR Damper Crank Arm can be attached to actuator shaft to drive a damper at same time valve is opened.

5 60-2099—8

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

3

4

4

L1

HOT

1

L2

1

3 2

AUXILIARY

SWITCH

C

NC

NO

C

NC

NO

FIRING

RATE

2

CONTROLLER

L2

FLAME SAFEGUARD

PROGRAMMER–MAIN

VALVE CONNECTIONS

5

PROOF-OF-

CLOSURE SWITCH 5

6 6

1 POWER FROM FLAME SAFEGUARD CONTROL.

2 ACTUATOR OPENS TO LOW-FIRE POSITION WHEN FIRING RATE

CONTROLLER SWITCH IS OPEN AND LINE VOLTAGE IS SUPPLIED

TO TERMINALS L1 AND L2. ACTUATOR OPENS FULLY WHEN THE

FIRING RATE CONTROLLER SWITCH IS CLOSED AND POWER IS

SUPPLIED TO TERMINALS L1 AND L2.

3 INTERNAL JUMPER.

4 FOR LOW-FIRE ADJUSTMENT AFTER BURNER IS IN OPERATION.

DISCONNECT FIRING RATE CONTROLLER LEADWIRE FROM

TERMINAL 4.

5 SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN VALVE IS

SHUT (DE-ENERGIZED).

6 SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN VALVE IS

SHUT (DE-ENERGIZED).

M7339

Fig. 4. Typical hookup for V4062 Actuator.

7800 SERIES

RELAY

MODULE

L2

9

PUMP

VALVE

3

1

4

2

TRAVEL

LIMIT

SWITCH

PUMP

MOTOR

NO

NC

ADJUSTABLE

MAX

FLOW

LIMIT

SWITCH

C

M12798

FIELD WIRING

INTERNAL WIRING

Fig. 5. Connecting Max Flow Limit Switch to the actuator.

ADJUSTMENTS

Low-Fire Adjustment

The low-fire position is adjustable from 0.16 in. to 0.64 in.

(with respect to V5055/V5097B Valve) valve stem travel. A dial on the low-fire cam (Fig. 6) indicates the low-fire setting.

Because the cam rotates as the valve opens, scales are marked on the dial so the low-fire setting can be observed with the valve in any position. One scale is visible when the actuator is closed, and the other is visible when it is open.

These scales are not independent; the same setting applies to both. The low-fire setting is adjusted either before the actuator is installed or after the entire system is operational.

Refer to form 70-8311 for valve flow (capacity) curves.

IMPORTANT:

When using the V4062 with a V5055/V5097C or E

Valve (with double seal), match low-fire minimum position to burner and application. Too low a position could result in loss of burner flame. This low-fire position should also be checked at periodic maintenance intervals.

For most effective use of the V4062/V5055 or V4062/V5097, be sure to select a valve body size closely corresponding to burner capacity. An oversized valve might not allow the lowfire rate to be adjusted to the desired minimum setting.

The V4062 Actuator is shipped from the factory with the lowfire setting at MAX to provide a valve gas flow of approximately 50 to 60 percent, which is adequate for safe lightoff until the final setting can be determined.

LOW-

FIRE

CAM

DIAL

SETSCREW

MAX

E

D

A

MIN

MAX

C

B

DUAL

LOW-FIRE

SETPOINT

INDICATORS

(SHOWN AT

MAX WITH

VALVE OPEN)

M7340

Fig. 6. Low-fire position can be adjusted from 0.16 in. to

0.64 in. (with respect to V5055/V5097B) valve stem travel.

60-2099—8 6

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

Recommended Procedure

To adjust the low-fire setting without energizing the actuator, proceed as follows:

1. Remove the wiring compartment cover.

2. Manually rotate the cam and dial assembly downward so that the setscrew is accessible from the front of the actuator.

3. Loosen the setscrew on the low-fire cam using the special wrench (supplied taped to the inside of the actuator cover).

4. Set the cam to the predetermined low-fire setting for the burner being used.

5. Tighten the setscrew in the cam.

6. Replace the wiring compartment cover.

Alternate Procedure

To adjust the low-fire setting after the burner is in operation, use the following instructions:

1. Remove the wiring compartment cover.

2. Check to be sure the low-fire adjustment is set at MAX to assure a safe lightoff. (Low-fire adjustment is preset at the factory in the MAX position.)

3. Disconnect the firing rate controller leadwire from terminal 4 on the actuator to keep the valve in the lowfire position (Fig. 4).

4. Start the system and establish the main burner flame.

5. Loosen the setscrew in the cam (Fig. 5) with the special wrench. Keep the wrench seated in the setscrew. Rotate the cam slightly downward (by moving the wrench toward the actuator base) to open the bleed valve. The actuator will start to close.

6. When the valve reaches the desired low-fire position, quickly tighten the setscrew and remove the wrench. If the desired low-fire setting is missed, loosen the setscrew and rotate the cam in the opposite direction to the desired setpoint.

7. Shut down the burner, and then restart. Repeat several times to be sure the low-fire setting is suitable for correct burner lightoff. Readjust, if necessary.

8. Disconnect power and reconnect the controller leadwire removed in step 3.

9. Replace the wiring compartment cover.

Adjust Auxiliary Switch (If Used)

The auxiliary switch can be adjusted to operate at any point in the actuator stroke. After installing the switch in the actuator, turn the adjustment screw (Fig. 2) clockwise to cause the switch to operate earlier in the stroke or turn counterclockwise to cause the switch to operate later in the stroke.

NOTE: The proof-of-closure switch is not adjustable.

Adjust Max Flow Limit Switch (Fig. 2)

The Max Flow Limit Switch is adjustable throughout the actuator stroke. With the switch installed in the actuator, turn the adjusting screw clockwise to cause the switch to operate earlier in the stroke (less flow) or counterclockwise to cause the switch to operate later in the stroke (more flow).

OPERATION

To function as intended, the V4062 must be connected to a properly sized valve. Too large a valve will not properly control the gas flow.

When the actuator is energized, it drives to the adjustable low-fire position. Depending on the demand of the controller, the valve remains at low-fire or moves to the high-fire position. When the firing rate controller calls for no heat, the actuator returns the valve to the low-fire position. When power to the actuator is interrupted, the valve completely closes.

Fig. 4 shows the V4062 in a typical flame safeguard control system.

7 60-2099—8

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

SERVICE AND CHECKOUT

CAUTION

Equipment Damage Hazard.

Unskilled technicians can damage the equipment.

Only experienced, trained flame safeguard control service technicians should service or replace this control.

Service

The actuator is not field repairable, except for replacing the auxiliary switch or valve-closed indication switch. See

Installation section for procedure. Do not disassemble the valve actuator. If the actuator should fail to operate properly, replace it.

Checkout

After the installation is complete, cycle the valve several times with the manual fuel shutoff cock closed before testing the system in actual operation.

V4062A1156 Fluid Power Gas Actuator

The V4062A1156 Fluid Power Gas Valve Actuator was modified to provide modulation between high-and low-fire positions when used with a Series 60 controller, such as the

W964 Aquatrol® System and two auxiliary relays.

The V4062A1156 will not operate properly wired similarly to other V4062 models. See Fig. 7 for suggested wiring procedure.

Ratings:

Voltage: 120V, 60 Hz.

Nominal Opening Time: 26 seconds.

Closing Time: one second maximum.

See Specifications section for further specifications.

INDOOR

SENSOR

1 R1

RELAY

COIL

OUTDOOR

SENSOR

W964

C B A

1

R1

RELAY

CONTACT

3 4 1

2

C

NC

NO

AUX.

SWITCH

5

R2

RELAY 2

CONTACT

V4062

R2 2

RELAY

COIL

L2

TO MAIN VALVE

TEMINAL ON

PROGRAMMER

1 2

V4055

L1

L2

1 R1 – NORMALLY CLOSED RELAY CONTACT.

2 R2 – NORMALLY OPEN RELAY CONTACT.

Fig. 7. Suggested wiring diagram.

M7341

Home and Building Control

Honeywell Inc.

Honeywell Plaza

P.O. Box 524

Minneapolis MN 55408-0524

Honeywell Latin American Region

480 Sawgrass Corporate Parkway

Suite 200

Sunrise FL 33325

Home and Building Control

Honeywell Limited-Honeywell Limitée

155 Gordon Baker Road

North York, Ontario

M2H 3N7

Honeywell Europe S.A.

3 Avenue du Bourget

1140 Brussels

Belgium

Honeywell Asia Pacific Inc.

Room 3213-3225

Sun Hung Kai Centre

No. 30 Harbour Road

Wanchai

Hong Kong

Printed in U.S.A. on recycled paper containing at least 10% www.honeywell.com