armitage shanks markwik21 concealed thermostatic shower

armitage shanks markwik21 concealed thermostatic shower
ARMITAGE SHANKS
MARKWIK21 CONCEALED
THERMOSTATIC SHOWER MIXER
page 1 of 15
Dimensions are nominal measurements only.
SPECIFICATIONS
Recommended use
Healthcare
Colour availability
Chrome
Pressure rating
Maximum continuous operating pressure 1000 kPa static, 500 kPa dynamic.
For best performance and longer life we recommend 100-500kPa.
Balanced hot/cold water pressure is preferred but will work on unbalanced pressure up to a ratio of 5:1
Temperature rating
Maximum continuous working temperature 40-41°C
Suitable Hot Water
Units
Storage tank: Yes a 20 kPa minimum pressure
Gravity Feed: Yes a 20 kPa minimum pressure
Water Efficiency
WELS approval not applicable for thermostatic products
Standards
AS 4032.1: 2005 Thermostatic Valves
Continuous Flow: Yes a 20 kPa minimum pressure
To see the complete Armitage Shanks range
go to www.reece.com.au/bathrooms
CLEANING RECOMMENDATIONS
When cleaning chromed products use only a mild detergent, rinse & wipe dry with a soft cloth. Ideally clean after each use to
maintain appearance.
Never use abrasive, scouring powders or scrapers. Never use cleaning agents containing alcohol, ammonia, hydrochloric acid,
sulphuric acid, nitric acid, phosphoric acid or organic solvents. Use of incorrect cleaning products / methods may result in
chrome damage which is not covered by the manufacturer’s guarantee.
TM
WaterMark
AS 4032.1 WMK 25821
SAI Global
Disclaimer: Products in this specification manual must by regulation be installed by licensed and registered
trade people. The manufacturer/distributor reserves the right to vary specifications or delete models from
their range without prior notification. Dimensions and set-outs listed are correct at time of publication
however the manufacturer/distributor takes no responsibility for printing errors.
Tech Page Version 1
Pressure & temperature ranges of the incoming water supplies should comply with the limits specified
in table.1 (section 4.3).
page 2 of 15
ARMITAGE SHANKS
MARKWIK21
CONCEALED
SHOWER MIXER
note:
maximum recommended
static pressure in asTHERMOSTATIC
3500.1.2 is 500 kpa.
Important Note
to avoid exceeding this pressure, install a suitable pressure reducing valve - prv (or pressure limiting
valve
- plv)
both hot
& cold
incomingofwater
supply
a suitable
location
for a comes
prv on
Mixer must
beon
installed
to the
requirements
AS/NZS
3500systems.
by a qualified
plumber.
Your mixer
to the
youhot
already factory
supply
mayand
be tested.
on the We
colddoinlet
the heating
assembled
not to
recommend
theappliance.
dismantling of any internal part of the mixer. The mixers are factory tested and
sealed so
as to giveon
theboth
bestinlets
performance.
supply
pressures
should be reasonably balanced.
INSTALLATION
INSTRUCTIONS
similarly,
if the water
supply temperature ranges do not conform to table.1 then suitable temperature
controlling devices should be installed to achieve this.
5
INSTALLATION GUIDE
Before connection, flush water through pipe-work to remove
all debris etc. to prevent damage to the valve mechanism.
tHen ensure Water supplies Have been isolateD.
65 max
max / min
Mounting location
Decide on a suitable location for mounting the mixing
valve on the wall. give consideration to the mounting
depth as shown here.
the plaster guard (blue moulding) is marked at the top
end with minimum & maximum to help the installer
achieve the correct depth. the dimensions are shown
from the centre line of the outlet pipe to the finished
surface (which could be tiles).
the back support (white polystyrene moulding) can be
left in position to support the brass valve & act as a
levelling guide. use a spirit level for accuracy.
The profile of either the back support or the large side
of the plaster guard can be used as a guide for
marking out the size & shape of the aperture required
in the finished wall for the sealing of the trim kit.
43 min
G1/2
1
Fig. 5a
1. all 4 ports on this valve are threaded ½” female.
Inlet ports
the Hot water supply to the valve should be on the
left & ColD water supply on the right.
hot
Outlet ports
the valve has two outlet ports. the installer can decide
which port to use & fit the supplied ½” plug into the other port.
purchase 3x ½” male connectors suitable for
the type of pipe being used to plumb the installation.
use an appropriate approved thread sealing medium.
6
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
G1/2
G1/2
Fig. 5b
cold
page 3 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
In-line service valves
IMPORTANT: The inline service valves supplied with this product must be fitted into the
pipe-work. see section 10 for more details.
Consider a suitable location for the service valves. During installation, the service valve
can be held with grips or use an adjustable spanner on the flats of the valve body.
Orientate the service valve such that the filter cap & isolating screw are easily accessible
for future maintenance.
Fit pipes to both sides of the service valves & make good all the joints.
.
note: When the isolator screw slot is parallel to the valve body, the valve is open &
permits water to flow. To close the valve, rotate the isolator screw 90°. Valves can be left
closed until after the trim kit has been fitted.
Plaster guard removal
To remove the plaster guard, undo the two screws
shown here. Use a “long reach” flat blade screw driver.
Valve fixation
If the pipe-work does not sufficiently support the valve,
then two suitable screws can be fitted into the two
holes shown.
BLUE
marking
RED
marking
The two smaller threaded holes are
required for attaching the trim kit.
Blanking plug
a ½” blanking plug is supplied with a copper sealing washer. blank off the outlet port not
being used. Above, the top port is shown with the plug fitted. With the seal in place, use a
10mm hexagonal key to tighten plug into the port being blanked.
Check valve housings
the top surfaces of the check valve housings are marked reD on the left side & blue on
the right side. the markings signify the Hot & ColD water supply sides respectfully.
With the valve secured, pipe-work attached, & blanking plug fitted, the plaster guard
can be reattached to the valve to protect it from subsequent decorating tasks.
DO NOT apply heat near this product. Heat generated by
soldering could damage plastic parts and seals.
Check that all joints are securely tightened, test for leaks.
7
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
Fig. 5c
page 4 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
Tiling
2. If the finished wall is to be tiled, then the tiling template
should be used, apply a thin layer of silicon sealant on the
wall surrounding the plaster guard as shown.
slide the tiling template over the plaster guard & press it
firmly against the wall. Wipe away any excess silicone.
allow silicone time to set.
2
3. Affix tiles to wall & trim neatly
- close to the tiling template.
4. undo the two screws
shown here. use a “long
reach” flat blade screw
driver.
5. to remove the plaster
guard gently pull it away
from the wall. the plaster
guard & the two small
screws can be discarded.
Fig. 5d
6
5
3
6. Carefully trim away the
tiling template “flush” with
the finished tiled surface
using a sharp craft knife.
Fig. 5e
4
Fig. 5f
7. Carefully slide the chrome shroud onto
the central cartridge boss. if necessary
lubricate the o-ring with water containing
a little washing–up liquid. press shroud
until it bottoms out on the shoulder.
5.1 Fitting trim kit
7
8
8. the black mouldings shown should already
be assembled. ensure the large seal is in position at the rear. align the centre hole of the
assembly with the chromed shroud & gently
push towards the wall. ensure centre o-ring
stays in position. next align this assembly
with trimmed tiling template. manipulate the
large seal into the tiling template. press this
assembly against the finished tiled wall.
9
Fig. 5g
8
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
9. Fit the long screws supplied into
the holes as shown. tighten screws
using a flat blade screw driver.
page 5 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
10. align the hole in the chromed escutcheon
plate to the projecting chromed shroud &
carefully press it against the finished wall.
10
11 to 13 see below.
13
12
11
4
Fig. 5h
5.2 Handle fixation
NOTE: Handle screw is already fitted to the grey spindle-extension on the shower valve.
undo this screw using a 4mm hexagonal key. ensure spindle-extension remains seated on
the thermostatic cartridge.
Fit the handle as follows:
rotate the spindle-extension fully clockwise until it stops (excessive force is not required).
Handle spline can be engaged onto spindle to assist rotation if necessary. the spindle is
now in the “off” position.
11. orientate the handle as shown above & locate it onto the spindle.
12. Locate fixing screw into the centre of the handle & tighten.
13. Finally snap the index button into the handle.
open tHe isolating valves & CHeCk For Water FloW.
6
OPERATION
hot
warm
Fig.6 showing the handle control
positions.
as the handle is rotated anticlockwise
from the off position the
delivered water progresses from cold
through warm to the preset maximum
temperature of approximately 41°C.
cold
off
9
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 6 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
7
COMMISSIONING AND AUDITS
The following procedure should be conducted after installation to ensure the product is functioning
correctly.
7.1
7.1
Purpose
of commissioning
The Purpose
of Commissioning:
• To confirm the correct designation of product versus application.
• To confirm the correct supply water conditions for the product / installation.
• To adjust the mixed temperature if necessary to suit the water supply conditions of the installation.
• To check the product is performing properly.
• To start an audit log and record appropriate data.
This product is factory set at 40 ± 1°C with supplies of circa; 300 KPa balanced pressure and
temperatures of 15°C cold & 65°C hot (i.e. an inlet ∆t of 50C° & a hot / mix ∆t of 24C°)
For supply requirements, see 4.0 Water Supply Conditions.
7.2
7.2
Commissioning
Process
decision
tree FC1)
Commissioning
Process
(see(see
decision
tree FC1)
• Establish that the supply conditions are within the requirements outlined above. If not investigate.
• When conditions are acceptable record them, together with hot and cold temperatures. Establish ∆t.
Check the outlet mix temperature is within 40 ± 2°C, if not (probably due to ∆t > 5C° difference to
factory setting) adjust appropriately. (see 9.1)
• If mixed temperature is correct undertake an 'in field' cold water isolation (CWI) test: (see 7.5 )
Pass – restore supply and record mixed temperature,
Fail – See 7.5 in-field 'Cold Water Isolation' test.
For more information on spare parts contact Armitage Shanks
Customer care, see details on back page.
10
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 7 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
7.2
cont. Commissioning process (decision tree FC1)
check the supply conditions
pressure 100 - 500 KPa & temperature <20 ºC & >55º
YES
NO
NOTE:
Factory settings are:
Inlet ∆t = H - C = 65-15 = 50°C
Hot/Mix ∆t = 65-41 = 24°C
record supply conditions
and ∆t for the hot & cold
investigate
NO
follow setting
or maintenance
instructions
MWT 41ºC (+0/- 2ºC)
re-set mixed to
41ºC +0/-2°C
YES
undertake in-field cold water
isolation test - see 7.5
Achieved 41±2°C?
NOTES:
MWT - Maximum Working
Temperature
Commissioning; Supply Conditions
should be recorded
YES
pass
accept
Figure 7a
record mixed temperature
11
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
NO
fail test
page 8 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
7.3
7.3
AuditChecks
Checks
TMV‘s
Audit
onon
TMV's
The purpose of a performance audit of a product is:
 To check the product continues to perform properly.
 To flag the need for the product to be adjusted due to supply condition changes or mechanism
ageing.
 To ultimately identify the need for product maintenance.
Note - Additionally these audits facilitate regular verification of the supply conditions.
(See decision tree FC3)
Audit of Supplies To Fittings (FC3)
cold <20ºC
in 2 minutes
YES
hot>55ºC
in 1 minute
supply pressures
are appropriate
NO
record stable state supply
temperature (5 - 20ºC)
NO
investigate system issue
>65ºC
NO
YES
record stable state supply
temperature (55 - 65ºC)
YES
YES
is supply temperature
same as previous audit?
YES
implications to terminal fittings
NO
NO
insignificant change
∆t difference <5ºC
∆t>5ºC
temporary change
of known cause
NO
is supply temperature
same as previous audit?
long term or permanent
change - consider
recommissioning of thermo
fitting(s)
YES
no action
no action.
retest when
conditions normalise
go to field test audit 7.4
or commissioning 7.2
Figure 7b
12
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
follow
commissioning
instructions see
YES
page 9 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
7.4
Audit procedure (see decision tree FC2)
Fitting Field Test Audit (FC2)
 Verify the water supplies conditions are
similar to when the product was
commissioned i.e. inlet ∆t as previous + / 5C°
water supplies same as
previous audit or
∆t change >5ºC
Note: If inlet ∆t change is > 5C° consider the
cause of the change, If it is seen as a long
term or permanent change, re-commission
the product. If however, it is only a temporary
change, retest when normal conditions
resume.
undertake the cold
water isolation test
see 7.5
 If inlet ∆t differs from the commissioning ∆t by
< 5C° carry out field 'cold water isolation'
(CWI) test (see 7.5 in field
Cold Water Isolation test failure).
 Pass - restore the cold supply and move on to
check the mix temperature.
pass
Note: If the product fails CWI test, refer to 7.5
and then re-commission the valve.
restore cold
 Mixed Temperature is as commissioned ±2C°,
Accept and record the temperature.
Note: If mixed Deviation > ±2C° (1st
instance) reset mix as instructions and redo
the test from start. See 9.1 Adjustment of
the mix temperature.
fail
see 9
check mixed
temperature
 2nd & subsequent instances follow
maintenance instructions.
7.5
In-field 'Cold Water
Isolation´(CWI) test.
Locate the cold inline isolating valve
(see fig 10a, section 10).
Using a flat-blade screw driver, the
screw can be rotated 90° anti-clockwise
to isolate the cold water supply.
same as at
commissioning
±2.0ºC
accept
& record
mixed temp.
Before commencing the CWI test, ensure:
1. The water supply conditions are met either:
A. For commissioning a new product
deviation from
previous >+2.0ºC
1st instance
reset, follow
setting instructions
Figure 7c
2nd instance
follow maintenance
instructions (section 9)
B. Or the inlet ∆t is within ±5°C to when the
product was commissioned (see 7.4)
NOTE It is important that the hot temperature is
go to commissioning FC1 (7.2)
greater than 55°C
.
2. Mixed water outlet temperature is correct (see table 2, section 8)
.
13
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 10 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
To perform a CWI test, operate the product by rotating the lever fully to the right.
Then conduct the following procedure:
1. Record the steady state temperature of both hot and cold water supplies. Note the ∆t.
2. Record the temperature of the mixed water at the outlet.
3. Isolate the cold water supply (by rotating the isolating screw 90° & monitor the flow of water
from the outlet.
If the flow ceases, CWI test passed:
1. Restore the cold water supply by rotating the isolator screw 90° clockwise.
2. Re-check the temperature of the stabilised mixed water at the outlet to ensure it is still correct.
Accept & record mixed temperature.
If there is an ongoing flow of water from the mixed water outlet, then 5 seconds after CWI collect the
discharging water into a measuring vessel for 60 seconds. To pass the CWI test the volume of
collected water should be less than 120ml.
If the product fails CWI test, see FC2 (see section 7.4). Follow product maintenance (see section 9)
and servicing (see section 8) instructions.
8
SERVICING
The need for servicing is normally identified as a result of the regular performance auditing.
Application
Maximum mixed water
temperature during
normal operation
Washbasin
Permitted maximum stabilised
temperature recorded during site
testing – excluding transient spikes
43ºC
41ºC
Table 2 A guide to maximum temperature sets
8.1
FREQUENCY OF REGULAR SERVICING
The purpose of servicing regularly is to monitor any changes in performance due to changes in either the
system or the product. This may highlight the need to adjust either the supply system or the product.
These products should be audited 6 to 8 weeks and again 12 to 15 weeks after commissioning. The
results are to be compared against original commissioning settings.
If there are no significant changes at the mixed temperature outlet then a 6 monthly servicing cycle may
be adopted. Otherwise, servicing checks should be carried out more frequently
(e.g. every 4 months).
Follow the recommended auditing and maintenance procedures detailed in sections 7 & 9.
During servicing, note the following:
1. Repeat the procedure of recording and checking supply temperatures. (The same type of measuring
equipment should be used)
2. If the temperature has changed significantly from the previously recorded valves, the
following should be checked:
a. All in-line or integral valve filters are clear of obstruction.
b. All in-line or integral check valves are clean and working properly to prevent backflow.
c. Any isolating valves are fully open.
d. The thermostat is free of debris
3. When satisfied with the mixed outlet temperatures re-record the temperatures.
14
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 11 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
9
MAINTENANCE
When installed in a healthcare application, we recommend that the commissioning and maintenance
procedures, detailed under 7 & 8, be carried out.
9.1
Adjustment of the mix temperature
• Note: Cartridge is factory pre-set at 40±1°C at 300 KPa
1. prise out the cover button on the handle & unscrew the retaining screw using a 4mm
hexagonal key. move the lever to the fully on (max) position & then remove the handle.
Refer to section 5.2 Handle fixation.
2. remove the face plate & black mouldings (see section 5.1). slide off the cylindrical
chrome shroud & grey spindle extension to expose the thermostatic cartridge.
3. remove the upper anti clockwise stop ring (slide off spindle).
4. rotate spindle (use lever handle if necessary) to achieve correct mix temperature.
(40±1ºC) rotate clockwise to reduce and anti-clockwise to increase.
5. Refit the upper stop ring against cartridge stop face.
Note: 1. this is the normal maximum temperature range for the product and as such there is a
wide zone of spindle movement that gives this mix temperature. For best performance you
should refit the stop at the first point of anticlockwise rotation that achieves the desired setting.
Note: 2. if you are unable to achieve 40 - 41°C Max and you have the correct Δt’s it may
be due to fine debris. See 9.2 Removal and inspection of cartridge.
6. upon successful completion of the temperature adjustment, conduct the Cold Water
isolation (CWi) test (see 7.5) to ensure product is working properly.
7. Refit the spindle extension, cylindrical shroud & face plate kit (see section 5.1). Refit the
handle (see section 5.2).
8. record the mix temperature.
upper rotation
stop
(anticlockwise)
rotation
stops
upper
stop ring
lower
stop ring
Fig. 9a cartridge rotation
stops & rings
cartridge
stop face
15
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 12 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
9.2
Removal and inspection of cartridge
After checking that supply conditions are within the specified parameters, if the fitting malfunctions or should the test results fail to fall within the specified limits consider replacing the
cartridge with a new one. See 9.3 Important notes on debris.
1. remove the face plate (see section 5.1 & 5.2). slide off the cylindrical
chrome shroud & grey spindle extension to expose the thermostatic cartridge.
2. Isolate the fitting by closing the isolating valves (see section 10).
3. unscrew the cartridge from the body with a 36mm a/F deep socket. inspect cartridge
for damage. expect a small quantity of trapped water to escape when the cartridge is
unscrewed.
4. replace cartridge if necessary and reassemble cartridge into body.
5. the replacement cartridge should be tightened to a torque of 15nm.
(to re-secure the cartridge we recommend the use of Loctite 2400 or equivalent applied to the
thread of the cartridge)
6. reinstate the supplies.
7. After fitting the new cartridge start the test procedure from the section on commissioning.
• Redo the Cold Water Isolation (CWI) test (See 7.5).
• Once satisfied with the CWI test, re-check and if necessary, adjust the maximum mix temperature,
(See 9.1).
• Refit the spindle extension, cylindrical shroud & face plate (see section 5.1).
• Refit the handle (see section 5.2).
• Record the mix temperature.
36
sequential
cartridge
cartridge
extension
Fig. 9b cartridge removal
NOTE: During servicing (or replacing): the thermostatic
cartridge fitted in this product does NOT require lubrication.
16
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
shroud
page 13 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
9.3
Important notes on debris
Although this product is protected by built-in filters, debris can still find its way to the thermostat housing
area. this can happen during servicing for example. remove cartridge (see section 9.2) and carry out
an inspection.
9.4
Thermostatic Cartridge Ageing
Following many years of normal service you may notice the following:
1. the need to carry out more frequent adjustment of mixed temperature.
2. the thermostatic element may not pass the CWi test.
these issues could be due to the ageing of the thermostat which loses some expansion capability over
time.
these are the principle objectives of testing, as they serve to indicate to maintenance staff the declining
performance capability of the thermostatic cartridge.
For this reason the audit testing flow chart highlights that 2nd Instance CWI test failure or 2nd instance
mixed deviation even with stable ‘as commissioned’ supply conditions and correct inlet supply ∆t’s, is
potentially the first indication of the need to replace the cartridge.
10
INLINE SERVICE VALVES
The service valves contain filter & isolating valve functions.
isolation valves facilitate 4 activities:
1) Cleaning strainers & check valves
2) servicing the cartridge
3) Disinfection
4) audit cold water failure testing
Strainers
Each service valve is fitted with a strainer (filter/mesh) to catch any waterborne debris
To ensure trouble free operation of the fitting, the strainer elements should be checked and
cleaned in accordance with the commissioning and servicing guide (see section 8).
to access the strainer element, simply close the isolating valve and unscrew the strainer cap.
The strainer element should be washed with clean water and refitted.
use a 22mm spanner on the strainer cap. reopen the isolating valves upon completion.
expect a small quantity of trapped water to escape when the strainer cap is opened.
Circlip
flow regulator
check valve
to operate the
isolating valve rotate 90°
(illustrated closed)
strainer cap
strainer screen
direction
of flow
Fig.10a operating the isolating valve
isolating valve
Fig.10b exploded view of isolating valve
17
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 14 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
11
INTEGRAL COMBINED CHECK VALVES
& FLOW REGULATORS
To access the combined check valves & flow regulators (CV15FR):
1. remove the face plate (see section 5.1 & 5.2) to expose the shower valve. the Cv15Fr valve
housings (x2) are integral to the shower valve as shown figure 11.
17
2
Combined
check valve &
flow regulator
Fig. 11 check valve housings
2. isolate the product, see section 10.
3. use a 17mm spanner (or socket) to undo the Cv15Fr valve housings.
note: expect a small quantity of trapped water to escape when these
housings are opened.
4. slide the Cv15Fr valves out from the bottom of the housings.
5. Check/clean/replace the Cv15Fr valves. observe arroW marking.
6. Refit the CV15FR valve housings into the shower valve.
Reopen the isolating valves upon completion of task & refit face plate etc…
To achieve a suitable flow rate where supply pressures are very low it may be necessary to remove the
combined flow regulator (item 14a figure 12) and replace with a single check valve (item 14b figure 12).
PRODUCT MUST BE FITTED WITH CHECK VALVES, DO NOT REMOVE THESE.
NOTE: The flow regulator fitted in each maintenance carrier is nominally rated 5L/min. Therefore mixer is flow regulated to max 10L/min
For more information on spare parts contact Armitage Shanks
Customer care, see details on back page.
18
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
page 15 of 15
ARMITAGE SHANKS
MARKWIK21 CONCEALED THERMOSTATIC SHOWER MIXER
12
pos.
1
2
3
4
5
SPARE PARTS
part no.
a 962 017 aa
a 961 456 aa
a 961 464 nu
a 961 467 aa
a 860 967 aa
6
7
8
9
10
11
a 962 173 nu
a 962 074 nu
a 860 321 nu
a 963 344 nu
a 961 935 nu
a 962 280 nu
12
13
14a
14b
17
20
a 860 968 nu
a 963 431 nu
F 961 081 nu
a 962 594 nu
a 963 510 nu
a 860 969 nu
Cv-Fr
simple check valves
18
16
14
13
19
12
10
15
18
14
13
11
12
20
17
9
4
2
8
1
7
6
Fig.12 spare parts
9
5
3
For more information on spare parts contact Armitage Shanks
Customer care, see details on back page.
19
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
YEAR
IT Y
E
5
TE
QU
AL
G UARA
N
REECE PRODUCT QUALITY GUARANTEE
You have purchased a quality product from Reece Pty Ltd
ABN 84 004 097 090 (“Reece”). This product is covered by a
5 year replacement product warranty and a 12 month warranty
over spare parts and labour.
This warranty does not include faults caused by:
5 YEAR WARRANTY
This warranty covers faults in the product construction, material
and assembly. Products which are within 5 years from the
date of purchase, found upon inspection by an authorised
Reece representative, to be defective in construction, material
or assembly, will be repaired or exchanged with an equivalent
product free of charge. Replaced items become Reece’s
property. This warranty also covers any spare parts included
under “Manufacturer’s Provisions” below.
• Installation or part installation by the purchaser or any person
other than a LICENSED PLUMBER
All replacement products will be available for collection without
charge to the customer at the nearest Reece branch to the
customer’s location, or elsewhere as agreed between the
customer and Reece.
Manufacturer’s Provisions
The following spare parts are covered by a 10 year warranty:
• Mixer Cartridge
Labour and Spare Parts
The labour for the replacement of products and spare parts
to which this warranty applies will be supplied by Reece or
relevant supplier using licensed plumbers engaged by Reece or
relevant supplier within 1 year from the date of purchase.
Spare parts other than those listed in the Manufacturer’s
Provisions above, which are within 1 year from the date of
purchase found upon inspection by an authorised Reece
representative to be defective in construction, material or
assembly, will be replaced free of charge.
• Unsuitable or improper use
• Incorrect installation or installation not in accordance with
the instructions provided
• Normal wear and tear
• Inadequate or complete lack of maintenance
• Chemical, electrochemical or electrical influences
• Harsh detergents or abrasive cleaners used on
product finishes
EXCLUSIONS
To the fullest extent permitted by law, Reece excludes all liability
for damage or injury to any person, damage to any property,
and any indirect consequential or other loss or damage.
CLAIM PROCEDURE
For all warranty queries customers are to contact the branch
where the product was purchased. These details can be found
on your purchase invoice.
Our goods come with guarantees that cannot be excluded
under the Australian Consumer Law. You are entitled
to a replacement or refund for a major failure and for
compensation for any other reasonably foreseeable loss or
damage. You are also entitled to have the goods repaired or
replaced if the goods fail to be of acceptable quality and the
failure does not amount to a major failure.
Warranty Conditions
This warranty will apply only under all of the
following conditions:
• The item has been installed by a licensed plumber
• Failure is due to a fault in the manufacture of the product
• Proof of purchase (including the date of purchase)
is provided
• The installation of the product is in accordance with the
instructions provided
MIXERS.C.5YR
This warranty does not cover products purchased as an
ex-display without being fully checked and tested for sale by
the manufacturer.
Don’t risk it, use a licensed plumber.™
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement