Phase Reversal DIN Rail Mounting 3 Phase Voltage
V
M olta
on ge
ito
rs
Section 7
Voltage Monitors
Voltage Monitors
Selection Guide..................................................................................................................... 7.2
3 Phase Voltage Monitors
WVM........................................................ 7.4
DLMU...................................................... 7.6
HLMU...................................................... 7.8
PLMU....................................................... 7.10
PLM......................................................... 7.12
TVW......................................................... 7.14
TVM......................................................... 7.16
Low Volts, Phase Reversal
PLR.......................................................... 7.18
Phase Reversal
PLS.......................................................... 7.20
DIN Rail Mounting 3 Phase Voltage Monitors
CM-MPS
CM-PAS
CM-PSS
CM-PVS
CM-PFS
CM-PFE
CM-PVE
CM-PBE
Note:
Product pages are not included in
this catalog.
Go to: www.ssac.com/s7.pdf
Click on the Product Name
(ie: CM-MPS) to open the catalog
page.
[Adobe Acrobat Reader is required]
1 Phase Voltage Monitor
HLV............................................................. 7.22
KVM......................................................... 7.25
DIN Rail Mounting 1 Phase Voltage Monitors
CM-ESS.1............................. see Note above
CM-ESS.2............................. see Note above
CM-EFS................................ see Note above
CM-ESS.M...............................see Note above
DIN Rail Mounting Motor Insulation Monitors
Selection Guide..................... see Note above
CM-MSE................................ see Note above
CM-MSS................................ see Note above
CM-MSN............................... see Note above
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.1
1TRC 001 009 C0202
Selection Guide
Voltage Monitors
e
ag rs
t
l
Vo nito
o
M
Single Phase
Three Phase
For detailed product
specifications, refer to
catalog pages.
Series
Functions and Features Page
WVM
7.4
DLMU
7.6
PLM PLMU PLR PLS
7.12 7.10 7.18 7.20
HLMU
7.8
TVM
7.16
General Features
DIN Rail Mounting
w/a
•
w/s w/s w/s w/s
w/a
Surface Mounting
•
•
w/s w/s w/s w/s
•
•
8-Pin Plug-In
•
•
•
•
Screw Terminals
•
•
•
Quick Connects
•
TVW
7.14
HLV
7.22
KVM
7.25
•
w/a
•
w/a
•
•
•
•
Output
DPDT Relay(s)
•
•
SPDT Relay
•
•
•
•
•
•
•
•
•
SPST-NO
Line V Connection
Wired Phase-to-Phase
•
•
•
•
•
•
•
•
•
Universal Voltage
•
•
•
Phase-to-Neutral
•
•
Single Phase
•
•
Trip Point(s) Adjustable
•
•
•
•
•
•
v
•
Trip Point(s) Fixed
•
•
•
•
•
Supply Voltage Required
Protection
•
•
•
•
•
Phase Loss :
Motor Operating
•
•
•
•
Motor Start Up Only (!)
•
Undervoltage
•
•
•
•
•
Overvoltage
•
•
•
Unbalance (Asymmetry)
•
•
•
•
Rapid Recycling
•
•
•
Phase Sequence
•
•
•
•
•
•
Time Delays & Reset
Trip Delay
•
•
•
•
Restart Delay
•
•
•
Automatic Restart
•
•
•
•
•
•
Manual Reset
•
Indicator LED(s)
Output ON/OFF
•
•
•
•
•
Supply ON/OFF
•
•
•
Fault(s)
•
•
•
•
Timing
•
•
•
•
in
4.4 x 6.9 x 2.4
1.97 x 2.95 x 4.33
1.78 x 2.39 x ≤ 3.2
Dimensions
111.8 x 175.3 x 61
50 x 75 x 110
45.2 x 60.7 x ≤ 81.3
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
3 x 2 x 1.64
76.7 x 51.3 x 41.7
•
•
•
2.0 x 2.0 x ≤ 1.5
50.8 x 50.8 x ≤ 38.1
•
•
3 x 2 x 1.5
2 x 2 x 1.21
76.7 x 51.3 x 38.1 50.8 x 50.8 x 30.7
w/a = with adaptor; w/s = with socket v = Line Voltage adjustable on some models
! Phase loss protection for resistive and non-rotating loads. Motor protection can be affected by regenerated voltages.
7.2
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
0702Sel
12.05.06
mm
•
•
V
M olta
on ge
ito
rs
Selection Guide
Voltage Monitors
Three Phase
Series
Functions and Features
CMMPS
CM-
PAS
CM-
PVS
Single Phase
CM-
PSS
CM-
PFS
CM-
PBE
CM-
PFE
CM- CM-EFS CM-ESS.2CM-ESS.M
PVE
CM-ESS.1
Product pages are not included in this catalog. Go to: www.ssac.com/sg71.pdf. Click on the Product Name (i.e. CM-MPS)
General Features
DIN Rail Mounting
•
•
•
Surface Mounting
w/a
w/a
w/a
8-Pin Plug-In
Screw Terminals
•
•
•
Quick Connects
•
w/a
•
w/a
•
w/a
•
w/a
•
w/a
•
w/a
•
w/a
•
w/a
•
•
•
•
•
•
•
•
Output
DPDT Relay(2 SPDT)
•
•
•
•
•
•
ESS.2
SPDT Relay
•
•
ESS.1
SPST-NO •
•
2 SPDT (Independent)
•
Normal Status
Energized Energized Energized Energized Energized Energized Energized Energized Selectable De-energized
Line V Connection
Wired Phase-to-Phase
•
•
•
380 or 400
•
•
•
Universal Voltage (500VAC Max)
•
•
•
200-500
208-440
Phase-to-Neutral
•
•
Single Phase
Trip Point(s) Adjustable
•
•
•
Trip Point(s) Fixed
•
•
•
•
Supply Voltage Required
•
•
Selectable
•
•
•
•
•
Protection
Phase Loss:
•
•
•
•
•
•
•
•
Motor Operating
•
•
Motor Start Up Only (!)
•
•
•
•
•
•
Undervoltage
•
•
•
•
•
Overvoltage
•
•
•
•
Unbalance (Asymmetry)
•
•
Voltage Window
Phase Sequence
•
•
•
•
•
•
24-240 VAC 24 - 240 VAC 24 - 240 VAC
•
ESS.2
•
•
•
•
•
•
•
•
•
•
•
0703Sel
Time Delays & Reset
Trip Delay
•
•
•
•
•
•
Restart Delay
•
h
•
•
Automatic Restart
•
•
•
•
•
•
•
•
Latching Output
•
ESS.2
h
h
•
•
•
•
h
•
•
Indicator LED(s)
Output ON/OFF
Supply ON/OFF
Fault(s)
Timing
•
•
•
•
•
•
•
•
Dimensions
•
•
•
•
12.05.06
in
mm
•
•
•
•
•
•
•
•
0.89 x 3.07 x ≤ 3.98
22.5 x 78 x ≤ 101
•
ON
ON
ON
ON
•
•
OFF
OFF
OFF
OFF
•
0.89 x 3.07 x 3.09
22.5 x 78 x 78.5
•
•
•
•
0.89 x 3.07 x ≤ 3.98
22.5 x 78 x ≤ 101
w/a = with adaptor; w/s = with socket; h = hysteresis
! Phase loss protection for resistive and non-rotating loads. Motor protection can be affected by regenerated voltages.
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.3
1TRC 001 009 C0202
3 Phase Voltage Monitor
WVM Series
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
The WVM Series provides protection against premature equipment (motor) failure caused by voltage faults on
the 3 Phase Line. The WVM’s microcontroller design provides reliable protection even if regenerated voltages
are present. It combines dependable fault sensing with a 10 fault memory and a 6 LED status display. Part
instrument, part control, the WVM protects your equipment when you’re not there and displays what happened
when you return. The WVM is fully adjustable and includes time delays to prevent nuisance tripping and
improve system operation. Time delays include a 0.25 to 30 s adjustable trip delay, an adjustable 0.25 to 64
m (in 3 ranges) restart delay, plus a unique 3 to 15 s true random start delay. The random start delay prevents
voltage sags caused by simultaneous restarting of numerous motor loads after a power outage.
Operation
ANSI Device #27/47/59
The output relay is energized when all conditions
are acceptable and the WVM is reset. A restart
and/or random start delay may occur before the
output relay is energized.
Field Adjustment: Select the line voltage listed
on the motor’s name plate. This automatically sets
the over and under voltage trip points. Consult the
equipment’s manufacturer specifications for the
correct trip delay, unbalance percentage, and restart/
reset operation and restart delay. Make connection
to all three line phases as shown in the connection
diagram. Apply power. If the relay fails to energize,
view the LEDs for the cause, and correct the problem.
If the phase sequence is incorrect, swap any two
wires. No further adjustment should be required to
achieve maximum equipment protection.
Read Memory: Fault(s) stored in the memory
are indicated when the yellow LED is flashing. To
read memory, rotate selector from Manual to Read
Memory. The last fault will be displayed. Repeat this
operation to read the second to the last fault. Repeat
until up to 10 faults are noted.
Memory Reset: To clear the memory of all
faults stored, rotate selector to Clear Memory
for 5 seconds. The yellow LED will turn off.
Memory Overload: The 11th fault causes the
first to be removed from memory. Only the 10
most recent faults are retained.
Random Start Delay: A new 3 to 15 s random start
delay is selected by the microcontroller when a fault
is corrected and when the operating voltage (L1, L2,
L3) is applied to the WVM. A random start delay does
not occur when the reset is manual.
Automatic Restart: Upon fault correction, the output
will re-energize after a random start delay.
Automatic Restart Upon Fault Trip: When a fault is
sensed for the full trip delay, the output de- energizes
and a restart delay is initiated. This delay locks out
the output for the delay period. Should the fault be
corrected by the end of the restart delay, the output
will re-energize after a random start delay. A restart
delay will also occur when operating voltage (L1, L2,
L3) is applied to the WVM.
Manual Reset: After a fault condition is corrected,
the WVM can be manually reset. There are two
methods; a customer supplied remote switch, or the
onboard selector switch.
Protects Against: Phase
Loss & Reversal; Over,
Under & Unbalanced
Voltages; Short Cycling
10 Fault Memory & Status
Displayed on 6 LED Readout
Switch Selectable Automatic
Restart, Delayed Automatic Restart, & Manual Reset
Isolated 10 A SPDT Relay
Contacts
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Approvals:
Listed
Connection
F = Fuses
NO = Normally Open
NC = Normally Closed
RS = Optional Remote Reset Switch
7.4
1TRC 001 009 C0202
Remote Reset: Reset (Restart) is accomplished
by a momentary contact closure across terminals 1
& 2. The output will immediately energize. Remote
switch requirements are ≥ 10 mA at 20 V DC and the
reset terminals are not isolated from line voltage. A
resistance of ≤ 20KΩ across terminals 1 & 2 will
cause immediate automatic restart.
Automatic Restart Upon Fault Correction:
(P/N includes an R)
When a fault is sensed for the full trip delay, the output
relay de-energizes. Upon correction of the fault, a
restart delay begins. At the end of this delay, the
output will re-energize after a random start delay. If
a fault occurs during restart timing, the restart time
delay will be reset to zero, and the output will not
energize until the restart delay is completed.
-60 Option: Add the suffix -60 to any automatic
restart part number to remove the Random Start
Delay feature. See example P/N‘s below.
WVM
Series
X
3 Phase Line Voltage
–6 - 200 ... 240 V AC
–8 - 355 ... 425 V AC
–9 - 400 ... 480 V AC
–0 - 500 ... 600 V AC
X
X
X
Reset Method
Unbalance Trip Delay
–1 - 2 ... 10% –1 - 0.25 ... 30 s –A - Switch Selectable:
Automatic Restart Upon Fault Trip
–R - Switch Selectable:
Automatic Restart Upon Fault
Correction
X
Restart Delay
–L - 0.25 ... 64 s
–N - 6 ... 300 s
–H - 0.25 ... 64 m
Example P/Ns: WVM011AL,
WVM911AL-60 (No Random Restart Delay)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
WVM02B01 12.13.06
CAUTION:
2 amp max fast acting
fuses must be installed
externally in series with
each input. (3)
Relay contacts are isolated.
Dashed lines are internal
connections.
Manual Reset (Onboard): Rotate selector switch
from the Manual Reset position to Auto Restart
w/ Delay then back again to Manual Reset within 3
seconds. The output will immediately energize.
V
M olta
on ge
ito
rs
3 Phase Voltage Monitor
WVM Series
Motor Protector
Technical Data
Line Voltage
Type
Operating Voltage
240 V AC
380 V AC
480 V AC
600 V AC
3 phase Delta or Wye with no connection to neutral
Adjustment Range
200 ... 240 V AC
355 ... 425 V AC
400 ... 480 V AC
500 ... 600 V AC
50 ...60 Hz
Frequency
Reset on Balance
Overvoltage, Undervoltage, &
Selected
Unbalance
%
Reset %
Voltage Unbalance
Overvoltage Trip Point
109 ... 113% of adjusted voltage
2
1.8
3
2.7
Reset Voltage
-2% of trip point
4
3.6
Undervoltage Trip Point
88 ... 92% of adjusted voltage
5
4.5
Reset Voltage
+2% of trip point
6
5.4
Voltage Unbalance
Adjustable from 2 ... 10%
7
6.3
Trip Delay
Adjustable from 0.25 ... 30 s +/-15%
8
7.2
Phase Loss
≥ 15% unbalance
9
8.1
Response Time ≤ 200 ms
10
9
Random Start Delay Range
3 ... 15 s
Reset (Restart) Delay
Low Range
0.25 ... 64 s +/-15%
Normal Range
6 ... 300 s +/-15%
High Range
0.25 ... 64 m +/-15%
Fault Memory
Type
Nonvolatile RAM
Capacity
Stores last 10 faults
Status Indicators
6 LEDs provide existing status & memory readout
Note: 50% of operating line voltage must be applied to L1 & L2 for operation of status indicators
Output
Type
Electromechanical relay
Form
Isolated single pole double throw (SPDT)
Rating
10 A resistive @ 250 V AC; 6 A inductive (0.4 PF) at 250 V AC
Protection
Surge
IEEE 62.41-1991 Level B
Isolation Voltage
≥ 2500 V RMS input to output
Mechanical
Mounting
Surface with 2 or 4 #8 (M4 x 0.7) screws
Termination
Screw terminals with captive wire clamps for up to #12 AWG ( 3.2 mm2) wire
Environmental
Operating/Storage Temperature
-40°C ... +65°C / -40°C ... +85°C
Weight
≅ 25 oz ( 709 g)
Accessories
Mechanical View
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
3-phase fuse
block/disconnect
P/N: P0700-241
2 AMP fuse
P/N: P0600-11
WVM02B01 09.15.04
P/N: P1011-38
P/N: P0500-153
35mm DIN Rail Adaptor
The P1011-38 provides an easy
method of mounting the WVM
Series on 35mm DIN rail. The
P1011-38 adaptor includes four
mounting screws. 7 x 4.5 x .33 in.
(177.8 x 114.3 x 8.4 mm)
Clear Tamperproof Cover
The P0500-153 protects against unauthorized adjustment
of the trip points. It prevents the resetting of manual units by
the equipment’s operator. It isolates line-level connection
points preventing contact during troubleshooting
operations. Alignment dimples allow drilling (5 places) for
limited access to adjustment knobs and the reset switch.
Included are (2) spacers, (5) hole plugs. 7.5 x 4.7 x 2.6 in.
(190.5 x 119.4 x 66 mm)
Inches (Millimeters)
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.5
1TRC 001 009 C0202
Universal 3 Phase Voltage Monitor
DLMU Series (DPDT)
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
ANSI Device #27/47/59
Preliminary Data Sheet - Available 2nd Quarter 2007
The DLMU Series is a universal voltage, 3 Phase Voltage Monitor. It continuously measures the voltage of each
of the three phases with microcontroller accuracy and compares the value to preset trip points. It separately
senses Phase Reversal, Over, Under and Unbalanced voltages including Phase Loss and over or under frequency.
Protection is assured during periods of large average voltage fluctuations, or when regenerated voltages are
present. The unit trips within 200 ms when phase loss is detected. Adjustable time delays are included to prevent
nuisance tripping and short cycling of sensitive equipment. The 10A isolated DPDT output relay contacts trip
when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage unbalance, and
time delays are knob adjustable. The phase loss set point and the acceptable frequency range are fixed. Both
Delta and Wye systems can be monitored; no connection to neutral is required.
Operation
Upon application of line voltage, the output is deenergized and the restart delay begins. If all the three
phase voltages are within the acceptable range, the
Protects Against: Phase output energizes at the end of the restart delay. The
Loss, Phase Reversal, Over, Under and Unbalanced microcontroller circuitry automatically senses the vol
Voltages, Over/Under tage range, and selects the correct operating frequency
(50 or 60hz). The over and under voltage trip points
Frequency
are set at +/- 10% of the adjusted line voltage. When
35 mm DIN Rail or Surface the measured value of any phase voltage exceeds the
Mounting
acceptable range limits (lower or upper) the trip delay
DPDT Isolated 10 A Relay
begins. At the end of the trip delay the output relay de Contacts
energizes. If the phase voltage returns to an acceptable
LED Indicates, Relay, Faults,
value before the trip delay expires, the trip delay is
& Time Delays
reset and the output remains energized. Under, over,
Universal Line Voltage
and unbalanced voltages plus over or under frequency
240 ... 480 V AC in One Unit
must be sensed for the complete trip delay before the
600 V AC Version Available
unit trips. The unit trips in 200 ms when phase loss or
3 Wire Connection for reversal are sensed. The unit will not energize if a fault
Delta or Wye Systems
is sensed as the line voltage is applied.
ASME A17.1 rule 210.6
Reset: Reset is automatic upon correction of the volNEMA MG1 14:30, 14:35
tage or frequency fault or phase sequence.
IEEE C62.41-1991 Level B
Approvals:
Connection
Accessories
Restart Delay Options:
L= Lockout or minimum OFF time. The restart
delay begins when the output trips. The unit cannot
be re-energized until the restart delay is complete.
This provides a minimum off time or lockout time
to allow equipment sensitive to short cycling, time
to reset. If the fault is corrected after the restart
delay is complete the output energizes immediately.
The restart delay also occurs when line voltage is
applied/reapplied.
R= Restart Delay on fault correction. The restart
delay begins when line voltage is reapplied or
when a voltage fault is corrected. This option is
normally selected when staggered restarting of
multiple motors on a power system is required.
N= No Restart Delay. 0.6 second initialization
delay on application of line voltage applies.
Restart Notes:
All restart options remain reset when the following
conditions are detected:
1.) Phase Loss (phase unbalance greater than 25%)
2.) Average Line Voltage less than 120VAC
3.) Phase Reversal
The restart delay begins when the condition is
corrected.
LED Operation
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes
red during the trip delay then glows red when the
output de-energizes. It flashes red/green if phase
reversal is sensed If a fault is sensed during the
restart delay, the LED will glow red during that
portion or the full restart delay.
3-phase fuse
block/disconnect
P/N: P0700-241
2 Amp Fuse
P/N: P0600-11
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
See accessory pages for
specifications.
LED Flashing Table
L1, L2, L3 = Line Voltage Input
NO = Normally Open Contact NC = Normally Closed Contact
C = Common, Transfer Contact
Red
Trip Delay
ON/OFF 120 FPM
CAUTION: 2 amp max. fast acting fuses are recomGreen ON/OFF 60 FPM
Restart Delay
mended to protect the equipment‘s wiring. They are not
Phase Reversal Red/Green Alternate 120 FPM
required to protect the DLMU.
FPM = Flashes per minute
Ordering Table
X
Output
–D - DPDT
X
X
X
Voltage Unbalance
Restart Function
Trip Delay
–A - Adjustable 2 ... 10%
–A - Adjustable 1...30 s
–L - Lockout,
Fixed: Specify Unbalance
Fixed: Specify delay
Min Off Time
2 ...10% in 1% increments
1 ... 30 s in 1 s increments,
–R - Staggered Restarting
using two digits [ 04 ]
using two digits [ 20 ]
–N - No Restart Delay
Example P/N:
DLMUDLAAA = 200 ... 480 V, DPDT, Lockout Function Delay, Adjustable Unbalance, Trip and Restart Delay
DLMUDRAAA = 200 ... 480 V, DPDT, Restart Delay on fault correction, Adjustable Unbalance, Trip and Restart Delay
DLMUDNAAN = 200 ... 480 V, DPDT, No Restart Delay, Adjustable Unbalance and Trip Delay
DLMUDL0420A = 200 ... 480 V, DPDT, Lockout Function, 4% Unbalance, 20 s Trip Delay, Adjustable Restart Delay
7.6
1TRC 001 009 C0202
X
Restart Delay
–A - Adjustable
0.6 ...300 s
–N - No Restart
Delay
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]grossautomation.com
11.21.06
X
Line Voltage
–U - 200 ... 480 V AC
–H - 500 ... 600 V AC
DLMU2B01
DLM
Series
Universal 3 Phase Voltage Monitor
DLMU Series
Motor Protector
V
M olta
on ge
ito
rs
Technical Data
Line Voltage
Type
Operating Voltage
3 phase Delta or Wye with no connection to neutral
Range Voltage Adjustment Range Line Frequency Line Voltage Max.
240
200 ... 240 V AC
50 or 60 Hz
380
340 ... 420 V AC
50 Hz
400 ... 480 V AC
60 Hz
550 V AC
480
600
500 ... 600 V AC
50 or 60 Hz
600 V AC
600 V AC
Line Frequency
50 or 60 Hz Automatically detected
Phase Loss
≥ 25% Unbalance
Response Time
≤200ms
Undervoltage and Voltage Unbalance
Type
Voltage detection with delayed trip & automatic reset
Trip
Overvoltage:
Voltage
109 to 113% of the adjusted line voltage
Reset Voltage
≅ -3% of the trip voltage
Trip
Undervoltage:
Voltage
88 ... 92% of the adjusted line voltage
Reset
Voltage
≅ +3% of the trip voltage
Trip Set Point
Voltage Unbalance:
Adjustable 2 ... 10%; or specify fixed unbalance of 2 ... 10% in 1% increments
Reset on Balance
≅ -0.7% Unbalance
Active
Trip Delay
On
Over/Undervoltage, Voltage Unbalance, Over/Under Frequency
Range
Adjustable from 1 ... 30 s; or specify fixed delay 1 ... 30 s in 1 s increments
Tolerance
± 15%
Restart Delay
Range
Adjustable from 0.6 ... 300 s; if no restart delay is selected a 0.6 s initialization delay applies
Tolerance
± 15% Trip / Reset
Over/Under Frequency
±4%; Reset ±3%; 50 or 60 Hz
Phase Sequence
A, B, C, L1, L2, L3
Response Time -Phase Reversal & Phase Loss
≤200 ms
Reset
Automatic
Output
Type
Isolated Electromechanical Relay
Form
Double pole double throw (DPDT)
Rating
10 A resistive at 240 V AC; 8 A resistive at 277 V AC; N.O-1/4 hp at 120 V AC; 1/3 hp at 240 V AC
Life
Mechanical -- 1 x 106
Electrical -- (at 10 A) -- DPDT = 1 x 303
Protection
Surge
IEEE C62.41-1991 Level B
Isolation Voltage
≥ 2500 V RMS input to output
Mechanical
Mounting
Surface mount with 2 #8 (M4 x 0.7) screw or snap on 35mm DIN Rail
Note: 0.25 in.(6.35 mm) spacing between units or other devices is required
Package
4.33 x 2.95 x 1.97 in. (110 x 75 x 50 mm)
Termination
Screw terminals with captive wire clamps for up to #14 AWG (2.5 mm2) wire
Environmental
Operating Temperature
-40°C ... +60°C
Storage Temperature
-40°C ... +85°C
Humidity
95% relative, non-condensing
Weight
≅ 8.6 oz (244 g)
200 ... 480 V AC
Mechanical View
DLMU2B01
08.21.06
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.7
1TRC 001 009 C0202
Universal 3 Phase Voltage Monitor
HLMU Series (DPDT)
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
The HLMU Series is a universal voltage, encapsulated, 3 Phase Voltage Monitor. It continuously measures the
voltage of each of the three phases with microcontroller accuracy and compares the value to preset trip points.
It separately senses Phase Reversal, Over, Under and Unbalanced voltages including Phase Loss and over or
under frequency. Protection is assured during periods of large average voltage fluctuations, or when regenerated voltages are present. The unit trips within 200 ms when phase loss is detected. Adjustable time delays are
included to prevent nuisance tripping and short cycling of sensitive equipment. The 10A isolated DPDT output
relay contacts trip when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage
unbalance, and time delays are knob adjustable. The phase loss set point and the acceptable frequency range
are fixed. Both Delta and Wye systems can be monitored; no connection to neutral is required.
Restart Delay Options:
ANSI Device #27/47/59
L= Lockout or minimum OFF time. The restart
delay begins when the output trips. The unit cannot
be re-energized until the restart delay is complete.
This provides a minimum off time or lockout time to
allow equipment sensitive to short cycling, time to
reset. If the fault is corrected after the restart delay
is complete, the output energizes immediately.
The restart delay also occurs when line voltage is
applied/reapplied.
R= Restart Delay on fault correction. The restart
delay begins when line voltage is reapplied or
when a voltage fault is corrected. This option is
normally selected when staggered restarting of
multiple motors on a power system is required.
N= No Restart Delay. 0.6 second initialization
delay on application of line voltage applies.
Restart Notes:
All restart options remain reset when the following
conditions are detected:
1.) Phase Loss (phase unbalance greater than 25%)
2.) Average Line Voltage less than 120VAC
3.) Phase Reversal
The restart delay begins when the condition is
corrected.
Operation
Upon application of line voltage, the output is deenergized and the restart delay begins. If all the three
phase voltages are within the acceptable range, the
output energizes at the end of the restart delay. The
Protects Against: Phase microcontroller circuitry automatically senses the vol Loss, Phase Reversal,
tage range, and selects the correct operating frequency
Over, Under & Unbalanced Voltages, Over/Under (50 or 60hz). The over and under voltage trip points
are set at +/- 10% of the adjusted line voltage. When
Frequency
the measured value of any phase voltage exceeds the
Encapsulated Circuitry
acceptable range limits (lower or upper) the trip delay
DPDT Isolated 10 A Contacts
begins. At the end of the trip delay the output relay deLED Indicates Relay Status, energizes. If the phase voltage returns to an acceptable
Faults, & Time Delays
value before the trip delay expires, the trip delay is
Universal Line Voltage
reset and the output remains energized. Under, over,
200 ... 480 V AC in One Unit
Compact, Encapsulated and unbalanced voltages plus over or under frequency
must be sensed for the complete trip delay before the
Design
unit trips. The unit trips in 200 ms when phase loss or
Finger-Safe Terminal reversal are sensed. The unit will not energize if a fault
Blocks, up to 12 AWG
is sensed as the line voltage is applied.
ASME A17.1 rule 210.6
Reset: Reset is automatic upon correction of the volNEMA MG1 14:30, 14:35
tage or frequency fault or phase sequence.
IEEE C62.41-1991 Level B
Connection
Approvals:
LED Operation
Accessories
CAUTION: 2
amp max. fast
acting fuses are
recommended
to protect the
equipment‘s
wiring. They
are not required
to protect the
HLMU.
3-phase fuse
block/disconnect
P/N: P0700-241
2 Amp Fuse
P/N: P0600-11
DIN rail P/Ns:
017322005 (Steel)
←
→
C103PM (Al)
DIN rail adaptor
P/N: P1023-20
See accessory pages for
specifications.
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes red
during the trip delay then glows red when the output
de-energizes. It flashes red/green if phase reversal is
sensed. If a fault is sensed during the restart delay,
the LED will glow red during that portion or the full
restart delay.
LED Flashing Table
L1, L2, L3 = Line Voltage Input
NO = Normally Open Contact NC = Normally Closed Contact
C = Common, Transfer Contact
Red
Trip Delay
ON/OFF 120 FPM
Green ON/OFF 60 FPM
Restart Delay
Phase Reversal Red/Green Alternate 120 FPM
FPM = Flashes per minute
Note: Relay contacts are isolated, 277 V AC max.
X
X
Line Voltage
Output
–U - 200 ... 480 V AC –D - DPDT
X
X
X
Restart Delay
Trip Delay
Voltage Unbalance
–A - Adjustable 2 ...10%
–A - Adjustable 1...30 s –A - Adjustable
Fixed: Specify Unbalance
Fixed: Specify delay
0.6 ...300 s
2 ...10% in 1% increments,
1 ... 30 s in 1 s
–N - No Restart
using 2 digits [04]
increments, using
Delay
Example P/N:
2 digits, [05]
HLMUDLAAA = 200 ... 480 V, DPDT, Lockout Restart, Adjustable Unbalance, Trip and Restart Delay
HLMUDNAAN = 200 ... 480 V, DPDT, No Restart Delay, Adjustable Unbalance and Trip Delay
HLMUDRAAA = 200 ... 480 V, DPDT, Staggered Restart, Adjustable Unbalance, Trip and Restart Delay
HLMUDL0405A = 200 ... 480, DPDT, Lockout Restart, Fixed Unbalance 4%, Fixed Trip Delay 5 Seconds, Adjustable Restart
7.8
1TRC 001 009 C0202
X
Restart Function
–L - Lockout, Min Off Time
–R - Staggered Restarting
–N - No Restart Delay
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
HLM02B01
HLM
Series
12.05.06
Ordering Table
Universal 3 Phase Voltage Monitor
HLMU Series (DPDT)
Motor Protector
V
M olta
on ge
ito
rs
Technical Data
Line Voltage
Type
Operating Voltage
Cover Detail
3 phase Delta or Wye with no connection to neutral
Knobs & Dials
200 ... 480 V AC
Range Voltage Adjustment Range Line Frequency
(Fully adjustable
240
200 ... 240 V AC
50 or 60 Hz
Part Numbers)
380
340 ... 420 V AC
50 Hz
480
400 ... 480 V AC
60 Hz
Line Voltage Max.
550 V AC
Line Frequency
50 or 60 Hz Automatically detected
Phase Loss ≥ 25% Unbalance
Response Time ≤200ms
Undervoltage and Voltage Unbalance
Type
Voltage detection with delayed trip & automatic reset
Overvoltage:
Trip Voltage 109 to 113% of the adjusted line voltage
Reset Voltage ≅ -3% of the trip voltage
Undervoltage:
Trip Voltage 88 ... 92% of the adjusted line voltage
Reset Voltage ≅ +3% of the trip voltage
Trip Set Point Adjustable 2 ... 10%; or specify fixed unbalance of 2 ... 10% in 1% increments
Voltage Unbalance:
Reset on Balance ≅ -0.7% Unbalance
Active
On Over/Undervoltage, Voltage Unbalance, Over/Under Frequency
Trip Delay
Range Adjustable from 1 ... 30 s; or specify fixed delay 1 ... 30 s in 1 s increments
Tolerance
± 15%
Restart Delay
Range Adjustable from 0.6 ... 300 s; if no restart delay is selected a 0.6 s initialization delay applies
Tolerance ± 15% Trip / Reset ±4%; Reset ±3%; 50 or 60 Hz
Over/Under Frequency
Phase Sequence
A, B, C, L1, L2, L3
Response Time-Phase Reversal
& Phase Loss
≤200 ms
Reset
Automatic
Output
Type
Isolated Electromechanical Relay
Form
Double pole double throw (DPDT)
Rating
10 A resistive at 240 V AC; 8 A resistive at 277 V AC; N.O-1/4 hp at 120 V AC; 1/3 hp at 240 V AC;
Life
Mechanical -- 1 x 106
Electrical -- (at 10 A) -- DPDT = 1 x 303
Protection
Surge
IEEE C62.41-1991 Level B
Isolation Voltage
≥ 2500 V RMS input to output
Circuitry
Encapsulated
Mechanical
Mounting
Surface mount with one #10 (M5 x 0.7) screw
Note: 0.25 in.(6.35 mm) spacing between units or other devices is required
Package
3 x 2 x 1.5 in. (76.7 x 51.3 x 41.7 mm)
Termination
Screw terminal connection for up to 12 AWG (3.3 mm2) wire
Environmental
Operating Temperature
-40°C ... +60°C
Storage Temperature
-40°C ... +85°C
Humidity
95% relative, non-condensing
Weight
≅ 3.9 oz (111 g)
Mechanical View
-Hole for Mounting with One #10 (M4 x 0.7) Screw
HLM02B01 11.21.06
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.9
1TRC 001 009 C0202
3 Phase Voltage Monitor
PLMU Series
Universal Plug-in Monitor
e
ag rs
t
l
Vo nito
o
M
Description
The PLMU Series continuously measures the voltage of each of the three phases to provide protection for
three phase motors and sensitive loads. Its microcontroller senses under and over voltage, voltage unbalance,
phase loss, and phase reversal. Protection is provided even when regenerated voltages are present. Universal
voltage operation and standard base connection allows the PLMU to replace hundreds of competitive part
numbers.
Operation
ANSI Device #27/47/59
Protects Against: Phase Loss,
Phase Reversal, Overvoltage,
Undervoltage,
& Unbalanced Voltages
Octal Plug-in with SPDT
Isolated 10 A Contacts
Operates from 200 ... 480 V AC
LED Indicator Glows Green
when Voltages are
Acceptable, Red for Faults
Simple 3-Wire Connection for
Delta or Wye Systems
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Connection
Upon application of power, a 0.6 s random start delay
begins and the PLMU measures the voltage levels
and line frequency and selects the voltage range. The
output relay is energized and the LED glows green when
all voltages are acceptable and the phase sequence
is correct. LED flashes green during trip delay,
glows red when output de-energizes. Undervoltage,
overvoltage, and voltage unbalance must be sensed
for continuous trip delay before the relay de-energizes.
Re-energization is automatic upon fault correction.
The output relay will not energize if a fault condition is
sensed as three phase input voltage is applied. Line
voltage is selected with the knob, setting the over and
under voltage trip points. Voltage range is automatically
selected by the microcontroller.
2 Amp
Fast Acting
Fuses
Recommended For Safety
(Not Required)
F = Fuses
ØA = Phase A = L1
ØB = Phase B = L2
ØC = Phase C = L3NO = Normally Open
NC = Normally Closed
Relay contacts are isolated. Dashed lines are
internal connections.
Approvals:
Accessories
Panel mount kit
P/N: BZ1
Octal 8 pin socket
P/N: OT08PC
Faceplate View
Ordering Table
Voltage Unbalance
Adjustable 2 ... 10%
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
Trip Delay
Adjustable 0.25 ... 30 s
Part Number
PLMU11
Available with Fixed Unbalance and Trip Delay
PLMU2B01 06.08.04
3-phase fuse
block/disconnect
P/N: P0700-241
2 AMP fuse
P/N: P0600-11
See accessory pages for
specifications.
7.10
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
V
M olta
on ge
ito
rs
3 Phase Voltage Monitor
PLMU Series
Universal Plug-in Monitor
Technical Data
Line Voltage
Type
Line Voltage
Adjustable Voltage Ranges
(Automatic Range Selection)
Maximum Voltage Phase Sequence
Overvoltage, Undervoltage, &
Voltage Unbalance
Type
Overvoltage & Undervoltage
Undervoltage Trip Point
Reset Voltage
Overvoltage Trip Point
Reset Voltage
Voltage Unbalance Trip Point
Reset on Balance (%):
Selected Unbalance Reset Trip Delay Range
Severe Unbalance - 2X Selected Unbalance Random Start Delay
Phase Reversal & Phase Loss Trip Time
Phase Loss Set Point
Reset Type Output Type
Rating
Life
Protection
Surge
Isolation Voltage
Mechanical
Mounting*
Termination
Package
Environmental
Operating Temperature
Storage Temperature
Weight
Three phase Delta or Wye with no connection to neutral
200 ... 480 V AC +/-15%; 50 ... 60 Hz +/-2 Hz
200 ... 240 V AC, 50 ... 60 Hz
340 ... 420 V AC, 50 Hz
400 ... 480 V AC, 60 Hz
552 V AC
ABC
Voltage detection with delayed trip & automatic reset
88 ... 92% of adjusted line voltage
+2% of trip voltage
109 ... 113% of adjusted line voltage
-2% of trip voltage
Adjustable from 2 ... 10% or fixed 4 ... 10%
2
3
4
5
6
7
8
9
10
1.5 2.5
3.5 4.5 5.4 6.3 7.2
8.1
9
Adj. from 0.25 ... 30 s or fixed 2 ... 30 s +/-15%
0.25 ... 2 s; disabled when the trip delay is less than 2 s
≅ 0.6 s
≤ 150 ms
≥ 15% unbalance
Automatic
Energized when voltages are acceptable
10 A resistive @ 240 V AC; 1/4 hp @ 125 V AC; 1/3 hp @ 250 V AC; max. voltage 277 V AC
Mechanical -- 1 x 106 ; Electrical -- 1 x 105
IEEE C62.41-1991 Level B
≥ 2500 V RMS input to output
Plug-in socket rated 600 V AC
8 Pin octal plug
3.03 x 2.39 x 1.78 in. (77.0 x 60.7 x 45.2 mm)
*CAUTION: Select an octal socket rated for
600 V AC operation.
-40°C ... +60°C
-40°C ... +85°C
≅ 8.6 oz (244 g)
Mechanical View
PLMU2B01 06.08.04
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.11
1TRC 001 009 C0202
3 Phase Voltage Monitor
PLM Series
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
The PLM Series continuously measures the voltage of each of the three phases. The PLM Series uses a new
microcontroller circuit design that senses Undervoltage, Voltage Unbalance, Phase Loss, and Phase Reversal.
Protection is assured when regenerated voltages are present. Both Delta and Wye systems can be monitored;
no connection to neutral is required.
Operation
US Pat #6541954
ANSI Device # 47/27
Protects Against: Phase
Loss, Phase Reversal,
Undervoltage, & Unbalanced Voltages
8 Pin Plug-in Base
Adjustable Low Voltage
Trip Point
Factory Fixed Unbalance
and Trip Delay
Line Voltages 200...480 V AC,
in 3 Ranges
SPDT Isolated 10 A Relay
Contacts
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
The output relay is energized and the LED glows
green when all voltages are acceptable and the phase
sequence is correct. Under and unbalanced voltages
must be sensed for a continuous trip delay period
before the relay de-energizes. Reset is automatic upon
correction of the fault condition. The output relay will
not energize if a fault condition is sensed as power is
applied. The LED flashes red during the trip delay, then
glows red when the output de-energizes. The LED
flashes green/red if phase reversal is sensed.
Field Adjustment:
Set voltage adjustment knob at the desired
operating line voltage for the equipment. This
adjustment automatically sets the undervoltage
trip point. Apply power. If the PLM fails to
energize, (LED glows red) check wiring of all 3
phases, voltage, and phase sequence. If phase
sequence is incorrect, the LED flashes green/
red. To correct this, swap any two line voltage
connections at the mounting socket. No further
adjustment should be required.
Connection
2 Amp
Fast Acting
Fuses
are
Recommended
For Safety
(Not Required)
Approvals:
Accessories
Panel mount kit
P/N: BZ1
3-phase fuse
block/disconnect
P/N: P0700-241
2 AMP fuse
P/N: P0600-11
DIN rail P/Ns:
C103PM (Al)
017322005 (Steel)
Relay contacts are isolated.
Dashed lines are internal connections.
F = Fuses NO = Normally Open
NC = Normally Closed
Ordering Table
PLM
Series
X
Line Voltage
V AC
–6 - 240
–8 - 380 V AC
–9 - 480 V AC
X
Voltage Unbalance (Fixed) –Specify:
4, 5, 6, 7, or 8%
X
Delay (Fixed)
Trip
–Specify from 2 ... 20 s in
1 s increments
(Insert 0 before 1 ... 9)
PLM02B01 02.10.05
Octal
8 pin socket
P/N: OT08PC
Example P/N: PLM6405, PLM9410
See accessory pages for
specifications.
7.12
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
V
M olta
on ge
ito
rs
3 Phase Voltage Monitor
PLM Series
Motor Protector
Technical Data
Line Voltage
Type
Operating Voltage:
Line Frequency
Phase Sequence
Power Consumption
Low Voltage and Voltage Unbalance
Type
Low Voltage: Trip Voltage
Reset Voltage
Voltage Unbalance: Trip Unbalance
Reset on Balance Trip Delay:
Range Tolerance
Phase Reversal and Phase Loss
Response Time -Phase Reversal
Phase Loss
Phase Loss
Reset
Output
Type
Form
Rating
Life
Protection
Surge
Isolation Voltage
Mechanical
Mounting*
Package
Environmental
Operating Temperature
Storage Temperature
Weight
3 phase Delta or Wye with no connection to neutral
Model
Adj. Line Voltage Range Line Voltage Max.
240
200 ... 240 V AC
380
360 ... 430 V AC
480
400 ... 480 V AC
50 ... 100 Hz
ABC
≅ 2W for 240 V units
270 V AC
480 V AC
530 V AC
≅ 3W for 380 ... 480 V units
Voltage detection with delayed trip & automatic reset
88 ... 92% of adjusted line voltage
Plus 3% of trip voltage
Factory fixed from 4 ... 8%
-0.7% unbalance typical
Factory fixed from 2 ... 20 s
+/-15%
≤ 200 ms
≤ 200 ms
> 35% unbalance
Automatic
Electromechanical relay
Isolated single pole double throw (SPDT)
10 A resistive at 240 V AC, 277 V AC Max.
1/2 Hp at 240 V AC; 1/4 Hp at 120 V AC
Mechanical -- 1 x 107; Electrical --1 x 105
IEEE C62.41-1991 Level B
≥ 2500 V RMS input to output
8 pin plug-in socket rated 600 V AC
3.2 x 2.39 x 1.78 in. (81.3 x 60.7 x 45.2 mm)
*CAUTION: Select an octal socket rated
for 600 V AC operation.
-40°C ... +60°C
-40°C ... +85°C
≅ 4.4 oz (125 g)
Mechanical View
PLM02B01 02.10.05
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.13
1TRC 001 009 C0202
Compact 3 Phase Voltage Monitor
TVW Series The NetTM
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
Provides protection for motors and other sensitive loads. Continuously measures the voltage of each of
the three phases using a new microcontroller circuit design that senses under and overvoltage, voltage
unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are
present. Includes a trip delay to prevent nuisance tripping and a restart delay to prevent short cycling after
a momentary power outage.
Operation
US Patent 6541954
ANSI Device # 27/47/59
Protects Against: Phase
Loss, Phase Reversal, Under,
Over, and Unbalanced
Voltages, Short Cycling
Fixed Trip Points and Delays
Adjustable Voltages from
208 ... 480 V A C
in 4 Ranges
Monitor 600 V AC Lines by
Connecting VRM Accessory
Isolated 10 A, SPDT Relay
Contacts
Bi-color LED Indicator
Shows: Output Status,
Faults, Time Delays, Phase
Reversal and Set Point
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Upon application of line voltage, the restart delay
begins. The output is de-energized during restart delay.
Under normal conditions, the output energizes after the
restart delay. Undervoltage, overvoltage, and voltage
unbalance must be sensed for the complete trip delay
period before the output de-energizes. The restart
delay begins as soon as the output de-energizes. If
the restart delay is completed when a fault is corrected,
the output energizes immediately. The output will
not energize if a fault is sensed as the input voltage
is applied. If the voltage selector is set between two
voltage marks (e.g. between 220 and 230 V), the LED
will flash red rapidly. The TVW provides fault protection
at the lower of the two line voltages (e.g. 220 V).
Reset: Reset is automatic upon correction of a fault.
LED Operation
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes
red during the trip delay then glows red when the
output de-energizes. It flashes red/green if phase
reversal is sensed. If the voltage selector knob is
between settings, it rapidly flashes red.
LED Flashing Table
Trip Delay
Red
ON/OFF 115 FPM
Restart Delay
Green
ON/OFF 57 FPM
Phase Reversal Red/Green Alternate 115 FPM
Voltage Selector
Red
ON/OFF 460 FPM
Between Marks
(7.5 FPS)
FPM = Flashes per minute
FPS = Flashes per second
Mechanical View
Connection
Approvals:
Relay contacts are
isolated. Dashed
lines are internal
connections.
F = 2 A Fast Acting Fuses are recommended, but
not required.
Female quick connect
P/Ns:
P1015-13 (AWG 10/12)
P1015-64 (AWG 14/16)
P1015-14 (AWG 18/22)
3-phase fuse
block/disconnect
P/N: P0700-241
2 Amp Fuse
P/N: P0600-11
See accessory pages for
specifications.
7.14
1TRC 001 009 C0202
L1 = Phase A L2 = Phase B L3 = Phase C
NO = Normally Open NC = Normally Closed
C = Common, Transfer Contact
Inches (Millimeters)
Ordering Table
X
X
Trip Delay
Restart Delay
–Specify Fixed Delay –Specify Fixed Delay
In Seconds (S)
In Seconds (S)
[0.2 ... 1]
[0.4 ... 1]
In 0.1 s Increments
In 0.1 s Increments
[1 ... 100]
[1 ... 100]
In 1 s Increments
In 1 s Increments
In Minutes (M)
[1 ... 999]
In 1 M Increments
Example P/N: TVW645S10S = 208, 220, 230 & 240 V AC, 4% Voltage Unbalance,
5 Second Trip Delay, 10 Second Restart Delay
TVW960.2S1M = 430, 440, 460 & 480 V AC, 6% Voltage Unbalance,
0.2 Second Trip Delay, 1 Minute Restart Delay
TVW
Series
X
X
Line Voltage
Voltage Unbalance
Specify Fixed
Wide Range
– 5 - 208 ... 240 V AC
Percentage
Selectable
– 4, 5, 6, 7, 8,
– 6 - 208, 220, 230 &
9, or 10
240 V AC
– 8 - 380, 400 & 415 V AC
– 9 - 430, 440, 460 & 480 V AC
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
TVW02B01 11.30.06
Accessories
V
M olta
on ge
ito
rs
Compact 3 Phase Voltage Monitor
TVW Series The NetTM
Motor Protector
Technical Data
Line Voltage
Type
Input Voltage/Tolerance
Line Frequency
Phase Sequence
Power Consumption
Overvoltage, Undervoltage, &
Voltage Unbalance
Overvoltage & Undervoltage
Undervoltage Trip Point
Reset Voltage
Overvoltage Trip Point
Reset Voltage
Trip Variation vs Temperature
Voltage Unbalance Reset On Balance
Trip Delay Range
Restart Delay Range
Phase Reversal &
Phase Loss Response
Phase Loss
Output
Type
Rating
208 ... 240 V AC (55°C) 380 ... 480 V AC Life
Protection
Surge
Dielectric Breakdown 208 ... 240 V AC
380 ... 480 V AC
Mechanical
Mounting
Termination
Environmental
Storage Temperature
Humidity
Weight
Three phase Delta or Wye with no connection to neutral
208 ... 480 V AC in 4 ranges/-30% ... +20%
50 ... 100 Hz
ABC
Approx. 2 W for 240 V units
Approx. 3 W for 480 V units
Voltage detection with delay trip & automatic reset
88 ... 92% of the selected line voltage
≅ +3% of trip voltage
109 ... 113% of the selected line voltage
≅ -3% of trip voltage
≤ +/-2%
Factory fixed, from 4 ... 10%
≅ -0.7% unbalance
Fixed, from 0.2 ... 100 s, +/-15% or +/-0.1 s, whichever is greater
Fixed, from 0.4 s ... 999 m, +/-15% or +/-0.1 s, whichever is greater
≤ 200 ms; automatic reset
≥ 25% unbalance
Isolated SPDT relay contacts
10 A resistive @ 125 V AC, 5 A @ 250 V AC, 1/4 hp @ 125 V AC
10 A resistive @ 240 V AC, 1/4 hp @ 125 V AC,
1/3 hp @ 250 V AC; max. voltage 277 V AC
Mechanical--1 x 106; Electrical --1 x 105
IEEE C62.41-1991 Level B
≥ 1500 V RMS input to output terminals
≥ 2500 V RMS input to output terminals
Operating Temperature
Surface mount with one #8 (M5 x 0.8) screw
0.25 in. (6.35 mm) male quick connect terminals
-40°C ... +85°C
95% relative, non-condensing
≅ 2.8 oz (79 g)
Accessory
Connection
VRM Voltage Reduction Module
Mechanical View
575 V AC
→ 460 V AC
P/N: VRM6048
The VRM6048 Accessory Module
allows the TVW9XXX to monitor a 3-Phase
550 ... 600 V AC Line.
Voltage:
INPUT
600 V AC
575 V AC
550 V AC
TVW02B01 08.26.04
Package:
Circuitry
Mounting:
Termination:
*OUTPUT
480 V AC
460 V AC
440 V AC
Molded Housing with Encapsulated Surface Mount with One #10 (M5 x 0.8)
Plastic Screw. May be DIN Rail Mounted Using P1023-20 Adaptor
Screw Terminals with Captive Wire Clamps for up to No.12 AWG Wire.
VRM Module
P/N: VRM6048
Voltage Monitor
TVW9XXXX
* The VRM6048 must be connected as shown. If the
TVW9XXX is disconnected, the VRM output voltage
equals the input voltage.
Adjustment: If the measured line voltage is 575 V
AC, connect as shown and adjust the TVW9XXX for
460 V AC operation.
Operating:
Storage:
Humidity:
Inches (Millimeters)
-40°C to +70°C
-40°C to + 85°C
95% Relative, Non-Condensing Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.15
1TRC 001 009 C0202
Compact 3 Phase Voltage Monitor
TVM Series The NetTM
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
Provides protection for motors and other sensitive loads. Continuously measures the voltage of each of
the three phases using a new microcomputer circuit design that senses under and over voltage, voltage
unbalance, phase loss, and phase reversal. Protection is provided even when regenerated voltages are
present. Includes a trip delay to prevent nuisance tripping and a restart delay to prevent short cycling after
a momentary power outage.
Operation
US Patent 6541954
ANSI Device #27/47/59
Protects Against: Phase
Loss, Phase Reversal,
Under, Over, and
Unbalanced Voltages,
Short Cycling
Fixed Trip Points and
Delays
Fixed Voltages from 208
.. 480 V AC
Isolated 10 A, SPDT
Relay Contacts
Bi-color LED Indicator
Shows: Output Status,
Faults, Time Delays and
Phase Reversal
ASME A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
Upon application of line voltage, the restart delay
begins. The output relay is de-energized during restart
delay. Under normal conditions, the output energizes
after restart delay. Undervoltage, overvoltage, and
voltage unbalance must be sensed for continuous
trip delay period before the output is de-energized.
The output will not de-energize if a fault is corrected
during the trip delay. The restart delay begins as soon
as the output relay de-energizes. If the restart delay is
completed when the fault is corrected, the output relay
will energize immediately.
The output relay will not energize if a fault or phase
reversal is sensed as three phase input voltage is
applied.
Reset: Reset is automatic upon correction of a fault.
Connection
LED Operation
The LED flashes green during the restart delay, then
glows green when the output energizes. It flashes
red during the trip delay then glows red when the
output de-energizes. It flashes red/green if phase
reversal is sensed.
LED Flashing Table
Red
Trip Delay
ON/OFF 115 FPM
Green
Restart Delay
ON/OFF 57 FPM
Phase Reversal Red/Green Alternate 115 FPM
FPM = Flashes per minute
Mechanical View
Approvals:
Relay contacts are isolated. Dashed lines are
internal connections.
F = 2A Fast Acting Fuses are recommended,
but not required.
L1 = Phase A L2 = Phase B L3 = Phase C
NO = Normally Open NC = Normally Closed
C = Common, Transfer Contact
Female quick
connect P/Ns:
P1015-13 (AWG 10/12)
P1015-64 (AWG 14/16)
P1015-14 (AWG 18/22)
3-phase fuse
block/disconnect
P/N: P0700-241
2 Amp Fuse
P/N: P0600-11
See accessory pages for
specifications.
7.16
1TRC 001 009 C0202
Ordering Table
TVM
Series
X
Line Voltage
–208 A - 208 V AC
–220 A - 220 V AC
–230 A - 230 V AC
–240 A - 240 V AC
–380 A - 380 V AC
–400 A - 400 V AC
–415 A - 415 V AC
–440 A - 440 V AC
–460 A - 460 V AC
–480 A - 480 V AC
Example P/N:
X
Voltage Unbalance
Specify Fixed
Percentage
–4, 5, 6, 7, 8,
9, or 10
X
Trip Delay
–Specify Fixed Delay
In Seconds (S)
[0.2 ... 1]
In 0.1 s Increments
[1 ... 100]
In 1 s Increments
X
Restart Delay
–Specify Fixed Delay
In Seconds (S)
[0.4 ... 1]
In 0.1 s Increments
[1 ... 100]
In 1 s Increments
In Minutes (M)
[1 ... 999]
In 1 M Increments
TVM240A45S10S
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
TVM02B01 01.20.05
Accessories
Inches (Millimeters)
V
M olta
on ge
ito
rs
Compact 3 Phase Voltage Monitor
TVM Series The NetTM
Motor Protector
Technical Data
Line Voltage
Type
Input Voltage
Line Frequency
Phase Sequence
Power Consumption
Overvoltage, Undervoltage, &
Voltage Unbalance
Overvoltage & Undervoltage
Undervoltage Trip Point
Reset Voltage
Overvoltage Trip Point
Reset Voltage
Trip Variation vs Temperature
Voltage Unbalance Reset On Balance
Trip Delay Range
Restart Delay Range
Phase Reversal &
Phase Loss Response
Phase Loss
Output
Type
Rating
208 ... 240 V AC (55°C) 380 ... 480 V AC Life
Protection
Surge
Dielectric Breakdown 208 ... 240 V AC
380 ... 480 V AC
Mechanical
Mounting
Termination
Environmental
Storage Temperature
Humidity
Weight
Three phase Delta or Wye with no connection to neutral
208 ... 480 V AC (See Ordering Table)
50 ... 100 Hz
ABC
Approx. 2 W for 240 V units
Approx. 3 W for 480 V units
Voltage detection with delay trip & automatic reset
88 ... 92% of the selected line voltage
≅ +3% of trip voltage
109 ... 113% of the selected line voltage
≅ -3% of trip voltage
≤ +/-2%
Factory fixed, from 4 ... 10%
≅ -0.7% unbalance
Fixed, from 0.2 ... 100 s, +/-15% or +/-0.1 s, whichever is greater
Fixed, from 0.4 s ... 999 m, +/-15% or +/-0.1 s, whichever is greater
≤ 200 ms; automatic reset
≥ 25% unbalance
Isolated SPDT relay contacts
10 A resistive @ 125 V AC, 5 A @ 250 V AC, 1/4 hp @ 125 V AC
10 A resistive @ 240 V AC, 1/4 hp @ 125 V AC,
1/3 hp @ 250 V AC; max. voltage 277 V AC
Mechanical--1 x 106; Electrical --1 x 105
IEEE C62.41-1991 Level B
≥ 1500 V RMS input to output terminals
≥ 2500 V RMS input to output terminals
Operating Temperature
Surface mount with one #8 (M5 x 0.8) screw
0.25 in. (6.35 mm) male quick connect terminals
-40°C ... +85°C
95% relative, non-condensing
≅ 2.8 oz (79 g)
Connection
Accessory
VRM Voltage Reduction Module
Mechanical View
575 V AC
→ 460 V AC
P/N: VRM6048
The VRM6048 Accessory Module
allows the TVM9XXX to monitor a 3-Phase
550 ... 600 V AC Line.
Voltage:
INPUT
600 V AC
575 V AC
550 V AC
TVM02B01 01.20.05
Package:
Circuitry
Mounting:
Termination:
*OUTPUT
480 V AC
460 V AC
440 V AC
Molded Housing with Encapsulated Surface Mount with One #10 (M5 x 0.8)
Plastic Screw. May be DIN Rail Mounted Using P1023-20 Adaptor
Screw Terminals with Captive Wire Clamps for up to No.12 AWG Wire.
VRM Module
P/N: VRM6048
Voltage Monitor
TVM9XXXX
* The VRM6048 must be connected as shown. If the
TVM9XXX is disconnected, the VRM output voltage
equals the input voltage.
Adjustment: If the measured line voltage is 575 V
AC, connect as shown and adjust the TVM9XXX for
460 V AC operation.
Operating:
Storage:
Humidity:
Inches (Millimeters)
-40°C to +70°C
-40°C to + 85°C
95% Relative, Non-Condensing Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.17
1TRC 001 009 C0202
3 Phase Voltage Monitor
PLR Series
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
The PLR Series provides a cost effective means of preventing 3 phase motor startup during adverse voltage
conditions. Proper A-B-C sequence must occur in order for the PLR’s output contacts to energize. In addition,
the relay will not energize when an undervoltage or phase loss condition is present. The PLR protects a motor
against undervoltage operation. The adjustment knob sets the undervoltage trip point.
Operation
US Patent No. 6541954
ANSI Device # 27/32
Protects Against: Phase
Loss (On Startup), Phase
Reversal, Undervoltage
Used Where Moderate Voltage Unbalance Protection is Not Required
Direct Replacement for Most Popular 3 Phase Monitors
8 Pin Octal Base Connection
SPDT Isolated 5 A Relay Contacts
AMSE A17.1 rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B
The output relay is energized and the LED glows when
all voltages are acceptable and the phase sequence
is correct. Undervoltage must be sensed for a
continuous dropout delay period before the relay deenergizes. Reset is automatic upon correction of the
fault condition. The output relay will not energize if a
fault condition is sensed as power is applied.
Connection
Field Adjustment: Turn the adjustment knob fully
counterclockwise and apply three-phase power.
The LED should be ON. Increase adjustment until
the LED goes OFF. Decrease adjustment until LED
glows again. If nuisance tripping occurs, decrease
the adjustment slightly.
NOTE: When properly adjusted and operating in
an average system, a voltage unbalance of 10% or
more is required for phase loss detection. When a
phase is lost while the motor is running, a voltage
will be induced into the open phase nearly equal in
magnitude to the normal phase-to-phase voltage.
This condition is known as regeneration. When
regenerated voltages are present, the voltage
unbalance during single phasing may not exceed
10% for some motors. The PLR Series may not
provide protection under this condition. For systems
that require superior phase loss protection, select
the PLMU Series.
Approvals:
2 Amp
Fast Acting
Fuses
Recommended
For Safety
(Not Required)
Accessories
Panel mount kit
P/N: BZ1
Octal
8-pin socket
P/N: OT08PC
3-phase fuse
block/disconnect
P/N: P0700-241
2 AMP fuse
P/N: P0600-11
F = Fuses
ØA = Phase A = L1
ØB = Phase B = L2
ØC = Phase C = L3
NO = Normally Open
NC = Normally Closed
Relay contacts are isolated. Dashed lines are
internal connections.
Ordering Table
Voltage
95 ... 140 V AC
190 ... 270 V AC
340 ... 450 V AC
380 ... 500 V AC
Part Number
PLR120A
PLR240A
PLR380A
PLR480A
PLR02B01 06.07.04
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
See accessory pages for
specifications.
7.18
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
V
M olta
on ge
ito
rs
3 Phase Voltage Monitor
PLR Series
Motor Protector
Technical Data
Line Voltage
Type
3 phase Delta or Wye with no connection to neutral
Nominal Voltage
Undervoltage Dropout Adjustment Range
120 V AC
85 ... 130 V AC
240 V AC
170 ... 240 V AC
380 V AC
310 ... 410 V AC
480 V AC
350 ... 480 V AC
Frequency
50 ... 60 Hz
Phase Sequence
ABC
Response Times
Pull-in
≤ 400 ms
Drop-out
≤ 100 ms
Hysterisis
Pull-in/Drop-out
≅ 2%
Output
Type
Electromechanical relay, energized when all voltages are acceptable
Form
Single pole double throw (SPDT)
Rating
5 A resistive at 240 V AC: 1/4 Hp at 120 V AC
Maximum Voltage
250 V AC
Protection
Surge
IEEE C62.41-1991 Level B
Isolation Voltage
120 & 240 V AC
≥ 1500 V RMS input to output
380 & 480 V AC
≥ 2500 V RMS input to output
Mechanical
Mounting
Plug-in socket
Termination
8 pin, octal plug
Environmental
Operating Temperature
0°C ... +55°C
Storage Temperature
-40°C ... +85°C
Weight
≅ 6 oz (170 g)
Line Voltage Max.
143 V AC
270 V AC
480 V AC
530 V AC
Mechanical View
Inches (Millimeters)
PLR02B01 06.07.04
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.19
1TRC 001 009 C0202
Reverse Phase Relay
PLS Series
Motor Protector
e
ag rs
t
l
Vo nito
o
M
Description
The PLS Series is a low cost phase sensitive control that provides an isolated contact closure when the proper
A-B-C phase sequence is applied. Protects sensitive 3 phase equipment and equipment operators from
reverse rotation. Designed to be compatible with motor overloads or other 3 phase equipment protection
devices. Protection for equipment control centers where frequent reconnection or electrical code makes
reverse rotation protection essential. Examples include, mobile refrigerated containers, construction equipment,
hoists, pumps, conveyors, elevators and escalators.
Operation
The internal relay and LED are energized when the
phase sequence is correct. The output relay will not
energize if the phases are reversed. Reset is automatic
upon correction of the fault.
Protects Against Phase
Reversal
Low Cost Protection, One
Unit for All Sized Motors
3 Wire Connection for
Delta or Wye Systems
Octal Base Connection- Industry Standard Wiring
SPDT Isolated Relay
Contacts
Factory Calibrated--No
Adjustments Required
Approvals:
Connection
2 Amp
Fast Acting
Fuses
Recommended
For Safety
(Not Required)
Accessories
F = Fuses
ØA = Phase A = L1
ØB = Phase B = L2
ØC = Phase C = L3
NO = Normally Open
NC = Normally Closed
Panel mount kit
P/N: BZ1
Octal
8 pin socket
P/N: OT08PC
Relay contacts are isolated. Dashed lines are
internal connections.
3-phase fuse
block/disconnect
P/N: P0700-241
2 AMP fuse
P/N: P0600-11
Ordering Table
Voltage
120 V AC
208/240 V AC
380/415 V AC
440/480 V AC
Part Number
PLS120A
PLS240A
PLS380A
PLS480A
PLS02B01 06.09.04
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
See accessory pages for
specifications.
7.20
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
V
M olta
on ge
ito
rs
Reverse Phase Relay
PLS Series
Motor Protector
Technical Data
Line Voltage
Type
Frequency
Phase Sequence
Response Times
Pull-in
Drop-out
Output
Type
Form
Rating
120 & 240 V AC 380 & 480 V AC Maximum Voltage
Protection
Isolation Voltage
120 & 240 V AC 380 & 480 V AC Mechanical
Mounting
Termination
Environmental
Operating Temperature
Storage Temperature
Weight
3-phase Delta or Wye with no connection to neutral
Nominal Voltage
Minimum Voltage
120 V AC
95 V AC
208/240 V AC
175 V AC
380/415 V AC
310 V AC
440/480 V AC
380 V AC
50 ... 60 Hz
ABC
Maximum Voltage
135 V AC
255 V AC
430 V AC
500 V AC
≤ 300 ms
≤ 50 ms
Electromechanical relay, energized when the phase sequence is correct
Isolated SPDT
10 A resistive at 240 V AC
8 A resistive at 240 V AC
250 V AC
≥ 1500 V RMS input to output
≥ 2500 V RMS input to output
Plug-in socket
8 pin, octal plug
-40°C ... +55°C
-40°C ... +85°C
≅ 6 oz (170 g)
Mechanical View
Inches (Millimeters)
PLS02B01 06.09.04
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.21
1TRC 001 009 C0202
Single Phase Undervoltage Monitor
HLV Series
30 A SPDT Relay Output
e
ag rs
t
l
Vo nito
o
M
Description
The HLV Series is a single phase undervoltage monitor designed to protect sensitive equipment from brownout
or undervoltage conditions. Time delays are included to prevent nuisance tripping and short cycling. The 30 A,
1 hp rated SPDT relay contacts allow direct control of motors, solenoids and valves. The output relay can be
ordered with isolated SPDT contact to allow monitoring of one voltage and switching a separate voltage. Two
undervoltage trip point ranges allow monitoring of 110 to 120 VAC or 208 to 240 VAC systems.
Connection
US Patent 6708135
Protects against undervoltage
in Single Phase Systems
30 A SPDT N.O. Output
Contacts
100 ... 240 VAC Input Voltage
70 ... 220 VAC Adjustable Undervoltage Trip Point in
2 Ranges
Restart Delays from 3 ... 300 s
Trip Delay 1 ... 20 s Fixed
Isolated or Non Isolated Relay
Contacts
Approvals:
NO = Normally Open
NC = Normally Closed
C = Common
T1 = Undervoltage Trip Point
T2 = Restart Delay
Quick connect to
Operation
PI
TP
V
C-NO
C-NC
screw adaptor
P/N: P1015-18
Female quick
connect P/Ns:
P1015-64 (AWG 14/16)
P1015-13 (AWG 10/12)
Mounting bracket
P/N: P1023-6
DIN rail P/Ns:
Dashed lines are internal
connections.
Dashed lines are internal
connections.
Function
Accessories
I = Relay contacts are
isolated.
N = Relay contacts
are non-isolated.
IV
tr = Restart Delay
td = Trip Delay
PI = Pull-in 105% or trip point
TP = Trip Point
V = Monitored Voltage
IV = Input voltage
C-NO = Normally Open Contacts
C-NC = Normally Closed Contacts
Upon application of input voltage the output relay remains de-energized. When the input voltage value is
above the pull-in voltage, the restart delay begins. At
the end of the restart delay, the output relay energizes. When the input voltage falls below the trip point,
the trip delay begins. If the input voltage remains
below the pull-in voltage for the entire trip delay the
relay de-energizes. If the input voltage returns to a
value above the pull-in voltage, during the trip delay,
the trip delay is reset and the relay remains energized.
If the input voltage falls below the trip point voltage
during the restart delay, the delay is reset and the
relay remains de-energized. Reset is automatic upon
correction of an undervoltage fault.
Reset: Removing input voltage resets the output
relay and the time delays.
017322005 (Steel)
←
→
C103PM (Al)
DIN rail adaptor
P/N: P1023-20
A
X
Undervoltage Range
– 4 - 70 ... 120 VAC
– 6 - 170 ... 220 VAC
X
Output Connection
– I = Isolated SPDT
– N = Non-Isolated
SPDT
X
Restart Delay
– 2 - Onboard Adjustment
3...300 s
X
Trip Delay
– Fixed 1 ... 20 s in
1 s increments
Example P/N’s: HLVA4N25 = 70 ... 120 VAC Trip Point Range, Non-Isolated SPDT, Adjustable Restart Delay, Trip Delay fixed at 5 seconds
HLVA6I220 =170 ... 220 V Trip Point Range, Isolated SPDT, Adjustable Restart Delay, Trip Delay fixed at 20 seconds
7.22
1TRC 001 009 C0202
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
HLV02B01
HLV
Series
12.05.06
See accessory pages for
specifications.
Single Phase Undervoltage Monitor
HLV Series
30 A SPDT Relay Output
V
M olta
on ge
ito
rs
Technical Data
Input
Min and Max RMS Voltage
70 ... 264 VAC
Line Frequency
50 ... 60 Hz
Power Consumption
AC ≤ 4 VA
Undervoltage Sensing
Type
Peak Voltage Sensing
Ranges
(4)
70 ... 120 VAC
(6)
170 ... 220 VAC
Pull-In Voltage
105% or Trip Point Voltage
Trip Point Accuracy
± 3% of Trip Point
Time Delay
Restart Delays
3 ... 300 s adjustable
Trip Delay
1 ... 20 s fixed in 1 s increments
Repeat Accuracy
+/-0.5% or 20 ms, whichever is greater
Tolerance (Factory Calibration) +/-5%
Reset Time
≤ 150 ms
Time Delay vs. Temp. & Voltage ≤ +/-10%
Output
Type/Form
Electromechanical relay/SPDT
Ratings:
SPDT-N.O
SPDT-N.C.
General Purpose 125/240 V AC
30 A
15 A
Resistive
125/240 V AC
30 A
15 A
28 V DC
20 A
10 A
Motor Load
125 V AC
1 hp*
1/4 hp**
240 V AC
2 hp**
1 hp**
Life
Mechanical -- 1 x 106
Electrical -- 1 x 105, *3 x104, **6,000
Protection
Surge
IEEE C62.41-1991 Level A
Circuitry
Encapsulated
Isolation Voltage
≥ 1500 V RMS input to output; isolated units
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting
Surface mt. with one #10 (M5 x 0.8) screw
Package
3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1 mm)
Termination
0.25 in. (6.35 mm) male quick connects
Environmental
Operating Temp.
-40°C ... +60°C
Storage Temp.
-40°C ... +85°C
Humidity
95% relative, non-condensing
Weight
≅ 3.9 oz (111 g)
Mechanical View
HLV02B01
02.10.06
T1 = Undervoltage Trip Point
T2 = Restary Delay
Inches (Millimeters)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.23
1TRC 001 009 C0202
e
ag rs
t
l
Vo nito
o
M
7.24
1TRC 001 009 C0202
Notes
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
V
M olta
on ge
ito
rs
KVM Series
Single Phase
Undervoltage Monitor
Description
The KVM Series is a single phase undervoltage monitor designed to protect sensitive equipment against
brownout undervoltage conditions. The compact design and encapsulated construction make the KVM an
excellent choice for OEM equipment.
Operation
Function
The output relay is energized and the LED glows
green when the input voltage is above the reset
voltage threshold. If the input voltage drops below the
undervoltage set point, the output relay and LED will
de-energize. The output relay will remain de-energized
as long as the input voltage is below the reset voltage.
Reset is automatic when the input voltage returns to a
normal range.
Connection
TP = Undervoltage Set Point
R = Reset Point
Mechanical View
Economical
Single Phase
Brownout/Undervoltage
Protection
Isolated 8 A SPDT Relay
Contacts
Input Voltages of 0 to 132 or
0 to 264 V AC
Adjustable Low Voltage Trip
Point
LED Indicator
V = Voltage L = LED S = Undervoltage Set Point
NO = Normally Open NC = Normally Closed
C = Common, Transfer Contact
Dashed lines are internal connections.
Approvals:
Undervoltage Set Point (Adjustable)
78 ... 99 V AC
156 ... 199 V AC
Inches (Millimeters)
Maximum Line Voltage
132 V AC
264 V AC
Part Number
KVM4
KVM6
Technical Data
Line Voltage
Type Input Voltage/Frequency
Power Consumption
Power Off Reset Time
Undervoltage Detection
Undervoltage Set Point
Undervoltage Reset Point
Accessories
Quick connect to
screw adaptor
P/N: P1015-18
Female quick
connect
P/N:
P1015-64 (AWG 14/16)
DIN rail P/N‘s:
017322005 (Steel)
C103PM (Al)
←
→
KVM01B01 06.10.04
DIN rail adaptor
P/N: P1023-20
See accessory pages for
specifications.
Repeatability
Voltage Sensing Accuracy
Output
Type/Form
Rating
Life LED Indicator
Protection
Surge
Circuitry
Isolation Voltage
Insulation Resistance
Mechanical
Mounting
Package
Termination
Environmental
Operating/Storage Temperature
Humidity
Weight
Single Phase
110 ... 120 V AC or 208 ... 240 V AC/50 ... 60 Hz
2.5W at 132 V AC; 4.5W at 264 V AC
< 150 ms
KVM4
KVM6
KVM4
KVM6
78 ... 99 V AC
156 ... 199 V AC
Fixed at 104 V AC
Fixed at 209 V AC
+/- 0.5% under fixed conditions
+/-1% over temperature range
+/-2% at 25°C
Electromechanical Relay/SPDT
8 A resistive at 120 V AC, 1/3 hp at 120/240 V AC
6
5
Mechanical; 1 x 10 ; Electrical; 1x10 Glows green when output energized
IEEE C62.41-1991 Level A
Encapsulated
> 1500 V RMS Input to Output
> 100 MΩ Minimum
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
0.25 in. (6.35 mm) male quick connect terminals
-25 to +55°C/-40 to +85°C
95% relative, non-condensing
2.6 oz (74 g)
Low Voltage Products & Systems
Gross Automation (877) 268-3700 · www.ssacsales.com · [email protected]
7.25
1TRC 001 009 C0202