Type Differential pressure transducer

Type Differential pressure transducer
Homepage > Prodotti > Sistemi di regolazione
> Sistema di regolazione EASYLAB - LABCONTROL > Sensori
> Type Differential pressure transducers
Type Differential pressure transducer
FOR THE DIFFERENTIAL PRESSURE RECORDING AND CONTROL IN COMBINATION WITH
EASYLAB
Differential pressure transducers based on the static measurement principle for the room or duct pressure control in combination
with EASYLAB controllers TCU3 or LABCONTROL controllers TCU-LON-II
Suitable for air and non-aggressive media
For use in laboratories, clean rooms in the pharmaceutical and semiconductor industries, operating theatres, intensive care
units, and offices with very demanding control requirements
Constructions with calibration certificate to meet GMP requirements
APPLICATION
Application
Differential pressure transducer for the LABCONTROL system
For the room or duct pressure control in combination with EASYLAB controllers
TCU3 or with TCU-LON-II
For the room and duct pressure monitoring in combination with monitoring systems
TPM
For use in laboratories, clean rooms in the pharmaceutical and semiconductor
industries, operating theatres, intensive care units, and offices with very demanding
control requirements
DESCRIPTION
Variants
699: Measuring range ± 50 or ± 100 Pa
699-LCD: Measuring range ± 50 or ± 100 Pa, with differential pressure display
GB404: Measuring range ± 100 Pa
GB604-CAL: Measuring range ± 100 Pa, with calibration certificat to meet GMP
requirements (Good Manufacturing Practice)
Choose a sufficient measuring range above/below the setpoint pressure
Maintenance
Zero point correction once per year is recommended
TECHNISCHE INFORMATION
Function, Technical data, Specification text, Order code, Related products
FUNCTION
Functional description
Static differential pressure transducers function according to the static differential pressure measurement principle. The
sensor is a cylinder that consists of two chambers (one for positive pressure and one for negative pressure) separated by
a diaphragm. If there is equal pressure in both chambers, the diaphragm is in the middle between the chambers and is
not deformed. If there is a pressure difference, the diaphragm deforms towards the chamber with the negative pressure.
The degree by which the diaphragm deforms is a measure for the differential pressure. This is why the voltage signal is
proportional to the differential pressure.
Principle of operation – room pressure control
① Controller EASYLAB TCU3 or LABCONTROL TCU-LON-II
In a lab, the room pressure transducer is typically linked to the supply air controller; in a clean room, it is linked to the
extract air controller.
TECHNICAL DATA
Static differential pressure transducer 699
Supply voltage
24 V AC ± 15 % or 13.5 – 33 V DC
Power rating
1 VA
Output signal
0 – 10 V DC, 1 mA max.
Media
non-aggressive gases
Measuring range
± 50 Pa factory set, can be changed to ± 100 Pa
Measurement
± 2 % of full scale
accuracy
Overload protection
for negative pressure measurement: –400 Pa at P1, for positive pressure measurement 10000 Pa at
P1
Connections for tubes
Ø 6.2 mm (for flexible tubes 6 mm)
Operating temperature
0 – 70 °C (non-condensing)
IEC protection class
III (protective extra-low voltage)
Protection level
IP 54 (with cover)
EC conformity
EMC according to 2004/108/EC
Dimensions (B × H × T)
92 × 75 × 48 mm
Weight
0.1 kg
Static differential pressure transducer GB604
Supply voltage
24 V AC, 24 V DC ± 10 % (switching is possible)
Power rating
1.8 VA
Output signal
0 – 10 V DC; 2 mA max.
Media
non-aggressive gases
Measuring range
± 100 Pa
Measurement accuracy
± 0.5 % of full scale
Maximum operating pressure
70 kPa
Connections for tubes
for flexible tubes 4 mm
Operating temperature
–20 to 65 °C
IEC protection class
III (protective extra-low voltage)
Protection level
IP 54
EC conformity
EMC according to 2004/108/EC
Dimensions (B × H × T)
122 × 120 × 58 mm
Weight
0.3 kg
SPECIFICATION TEXT
Differential pressure transducer for the LABCONTROL system, for the measurement of room or duct pressure.
When the transducer is connected to a room controller, the supply air or extract air flow is controlled based on the differential
pressure.
ORDER CODE
Order example: PT-GB604-CAL
Measuring range ±100 Pa, with calibration certificate
Type
PT
Differential pressure transducer
Variants
699
Measuring range ±50 or ±100 Pa
699-LCD
GB604
Measuring range ±50 or ±100 Pa, with pressure display
Measuring range ±100 Pa
GB604-CAL
Variants
VARIANTS
Measuring range ±100 Pa, with calibration result
699
Application
Differential pressure transducer for the LABCONTROL system
For the room or duct pressure control in combination with EASYLAB controllers TCU3 or with TCU-LON-II
For the room and duct pressure monitoring in combination with monitoring systems TPM
Variants
699: Measuring range ± 50 or ± 100 Pa
699-LCD: Measuring range ± 50 or ± 100 Pa, with differential pressure display
Special characteristics
Supply voltage: A.C. or D.C. voltage (ideal for EASYLAB with EM-TRF-USV)
Adjustable measuring ranges
Short circuit proof and with reverse voltage protection
Parts and characteristics
Plastic casing
Connections for tubes
Push button for zero point reset
Adjustable measuring ranges
699-LCD: Differential pressure display
Construction features
Fixing points at the outside, for mounting to a wall or ceiling
Materials and surfaces
Transparent plastic casing
GB604
Application
Differential pressure transducer for the LABCONTROL system
For the room or duct pressure control in combination with EASYLAB controllers TCU3 or with TCU-LON-II
For the room and duct pressure monitoring in combination with monitoring systems TPM
Variants
GB604: Measuring range ± 100 Pa
GB604-CAL: Measuring range ± 100 Pa, with calibration certificat to meet GMP requirements (Good Manufacturing
Practice)
Special characteristics
Supply voltage: A.C. or D.C. voltage, switching between A.C. and D.C. is possible
Parts and characteristics
Plastic casing
Zero point potentiometer
Construction features
Fixing points at the inside, for mounting to a wall or ceiling
Capacitive stainless steel measuring cell
Materials and surfaces
Plastic casing, light grey
Differential pressure transducer 699
Differential pressure transducer GB 604 MF
Homepage > Prodotti > Sistemi di regolazione
> Sistema di regolazione EASYLAB - LABCONTROL > Sensori
> Type Differential pressure transducers
Home Contatto Stampa Condizioni generali di vendita e consegna Privacy Disclaimer
18/09/2017 © TROX Italia
S.p.A.
Homepage > Prodotti > Sistemi di regolazione
> Sistema di regolazione EASYLAB - LABCONTROL > Sensori
> Type Differential pressure transducers
Installation details
INSTALLATION DETAILS
Installation and commissioning
Choose a suitable installation location (reference room with stable pressure)
Ensure sufficient cross section and careful placing of the measuring tubes
Connect the differential pressure transducer to the controller or monitoring system
Supply voltage from the EASYLAB TCU3 controller or TCU-LON II (supply voltage for the differential pressure
transducer must be equal to the supply voltage provided by the controller)
Cosider the warm-up time of the sensor
Do not install the sensor near sources of interference such as transformers, senders, motors, or heat sources
Choose a stable installation location as shocks or vibration may distort the output signal
Installation should be vertical, with connections pointing downwards; this installation position corresponds to the
factory setup for calibration; it also prevents the ingress of condensate from the pressure tubes.
Zero point correction required
699, Terminal connections
Ο: Ground
+: Supply voltage
↗: Actual value signal
Home Contatto Stampa Condizioni generali di vendita e consegna Privacy Disclaimer
18/09/2017 © TROX Italia
S.p.A.
Homepage > Prodotti > Sistemi di regolazione
> Sistema di regolazione EASYLAB - LABCONTROL > Sensori
> Type Differential pressure transducers
GB604, Terminal connections
1
2
3
4
~, +: Supply voltage
⊥, -: Ground, neutral
+: Actual value signal
–: Actual value signal, ground
Home Contatto Stampa Condizioni generali di vendita e consegna Privacy Disclaimer
18/09/2017 © TROX Italia
S.p.A.
Homepage > Prodotti > Sistemi di regolazione
> Sistema di regolazione EASYLAB - LABCONTROL > Sensori
> Type Differential pressure transducers
TROX Italia S.p.A.
Online-Services
Service-Hotlines
TROX Academy
Telefono
Your contact partner
Online fault report
+39 02-98 29 74.1
Telefax
+39 02-98 29 74 60
Via Mecenate 90
20138 Milano
ITALY
Home Contatto Stampa Condizioni generali di vendita e consegna Privacy Disclaimer
18/09/2017 © TROX Italia
S.p.A.
Was this manual useful for you? yes no