HP 3 Phase Parallel Uninterruptible Power Systems - Data
HP 3 Phase Parallel Uninterruptible Power Systems
Data sheet
Efficiency, modularity, and redundancy give HP 3
Phase Parallel Uninterruptible Power Systems the ability
to grow with your data centre needs, with lower energy
costs and cooling needs than conventional large
uninterruptible power systems.
Can you meet your power
protection needs?
This pre-racked uninterruptible power system (UPS)
provides 36 kilowatts (kW) of power or 24 kW with
N+1 redundancy. Housed in a single HP 10000
G2 Series 42U rack, the system can be expanded
to 60 kW with N+1 simply by installing up to three
additional RP12000/3 UPS Modules. Digital
Signal Processing (DSP), UPS paralleling, and new
Online On Demand hybrid technology answer the
call for increased density, redundancy, efficiency,
and flexibility.
Online On Demand combines the efficiency of a lineinteractive UPS, up to 97 per cent, with the stability
of a double conversion online UPS when power
Power protection in your data centre has always
been a critical requirement to maintain system uptime fluctuates beyond acceptable limits. Hot-swappable
batteries and electronics modules and an automatic
and keep a dynamic business running. Today, the
bypass reduce downtime for maintenance.
increased densities in data centres drive the need for
uninter­ruptible power with increased power density,
power efficiency, and flexibility. The HP RP36000/3 Key features and benefits
Uninterruptible Power System provides all three.
The new HP RP36000/3 Uninterruptible Power
Systems are designed to provide high power output
with industry-leading efficiency for mission-critical
enterprise solutions and data centres.
Performance
•Supports up to 60,000 volt-amperes (VA)/60,000
watts in a single 42U rack
•Offers unity power factor, which means volt
amperage out equals wattage output
•Delivers industry-leading 97 per cent efficiency,
even at output loads as low as 40 per cent, with
Online On Demand hybrid technology
•Uses UPS paralleling for redundancy and expansion
•Delivers extra long battery life with Enhanced
Battery Management (EBM)
•Extends battery run time with optional Extended
Runtime Modules (ERMs)
•Enables longer run time with Digital Signal
Processing technology (DSP)
Management
•Includes UPS Management Module for remote
configuration and graceful shutdown of critical
servers without the need for a dedicated
management server
•Includes hot-swappable electronics and batteries
•Is backed by a limited three-year warranty and
HP pre-failure warranty on the batteries
•Offers N+1 redundancy with UPS paralleling
technology
•Allows up to six UPS modules to work together
to increase load capacity and N+1 fault tolerance
•In the event of a failure, the load shifts to remaining
modules to provide 100 per cent UPS protection
Options
•Allows you to attach up to four 3U Extended
Runtime Modules to each UPS for increased run
time in the event of a power failure
•Supports output modules with dual L15-30
receptacles that can be connected to each UPS
module for a total of 12 L15-30 connections
•Fully compatible with the HP Power Distribution
Rack to provide power and scalability to rows
of equipment
Ideal environments
Large data centres
The HP 3 Phase Parallel UPS can provide you with
additional power protection for multiple racks of
­critical equipment in the event of a power outage,
with better efficiency than many site-level UPS systems.
2
Small to mid-size data centres
When hundreds of kilowatts of power are not
necessary, the HP 3 Phase Parallel Uninterruptible
Power System provides power protection for an
entire row of racks. Its unique modular design allows
your system to grow with demand. Hot-swappable
electronics and batteries reduce downtime.
Collocation facilities
The HP 3 Phase Parallel UPS can provide power
protection to one or more racks and can be
managed by administrators separately from the
collocation facilities.
Recommended options
RP12000/3 UPS Module AF436 (NA) and AF437 (INTL)
Based on the R12000/3, this UPS is specially
designed to attach directly to the bus bar in the
RP36000/3, allowing it to expand to 60 kW with
N+1 redundancy.
HP Power Distribution Rack
The HP Power Distribution Rack (PDR) improves
power management in the data centre by moving
power ­distribution to the row level. Decentralising
power improves cable management, decreases diag­
nostic time for problems, and saves installation costs
by reducing the size and number of long power
feeds required to reach from large wall-mounted
distribution units. Capable of high amperage inputs,
the HP PDR can power several high-density racks
with shorter cable runs than conventional site-level
power distri­bution systems. Fully redundant inputs
and outputs provide dependable power while
protecting valuable IT equipment. Individual branch
circuit monitoring and redundant management
modules provide the status and power consumption
of each attached rack.
HP Power Distribution Units AF504A, AF503A,
AF508A, and AF507A
The monitored vertical rack-mount power distribution
units (PDUs) units can connect directly to the optional
UPS output modules and provide three-phase moni­
tored power, as well as full-rack power utility ranging
from 8.6 kilovolt-amperes (kVA) up to 22 kVA. Avail­
able PDUs include full-rack models with 39 receptacles
or with 78 receptacles.
HP 3 Phase Modular Power Distribution Units
AF512A and AF513A
These high-output, 8.6 kVA (North America/Japan)
and 11 kVA (international) modular PDUs have a
unique modular architecture designed specifically
for data centre customers who want to increase
power distribution and space efficiencies in the rack.
Modular PDUs consist of two building blocks: the
Control Unit (core) and the optional Extension Bars
(sticks). The Control Unit is 1U/0U, and the optional
Extension Bars mount directly to the frame of the
rack in multiple locations.
RP36000/3 (base unit)
RP12000/3 (optional UPS expansion
module)
Power rating (non-redundant)
36 kW / 36 kVA
12 kW / 12 kVA
Power rating N+1
24 kW / 24 kVA
60 kW / 60 kVA maximum configuration
Efficiency
>97%
>97%
Heat dissipation
<1113 W / 3800 BTU/hr at 100% rated load
<371 W / 1266 BTU/hr at 100% rated load
Cooling
Fan-cooled, temperature microprocessor monitored; front air entry,
rear exhaust
Fan-cooled, temperature microprocessor monitored; front air entry,
rear exhaust
Altitude before derating
1000 meters (3300 ft ASL)
1000 meters (3300 ft ASL)
Input connection
Hard-wired from facility power
Connects to power bus bar
Input voltage
208 VAC and 400 VAC models
208 VAC and 400 VAC models
Voltage range
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
Frequency range
50 or 60 Hz, ±5 Hz (auto-sensing)
50 or 60 Hz, ±5 Hz (auto-sensing)
Input current distortion
<5% with IT loads (PFC power supplies)
<5% with IT loads (PFC power supplies)
Input power factor
>.99 with IT loads (PFC power supplies)
>.99 with IT loads (PFC power supplies)
Inrush current
Load dependent
Load dependent
Input requirements
Hard-wired, three-phase, wye (5 wire, 4 pole)
Hard-wired, three-phase, wye (5 wire, 4 pole)
Bypass source
Same as input (single-feed)
Same as input (single-feed)
Generator compatibility
Fast sync slew rate for generator synchronisation
Fast sync slew rate for generator synchronisation
Technical specifications
General characteristics
Input characteristics
Output characteristics
Output connection
Hard-wired from power bus bar or uses optional output modules
Hard-wired from power bus bar or uses optional output modules
Rated output voltage
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
Output configuration
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
Output frequency (nominal)
50 or 60 Hz auto-detection on startup
50 or 60 Hz auto-detection on startup
Frequency regulation
0.1 Hz free-running
0.1 Hz free-running
Load power factor range
Lagging: 0.7
Leading: 0.9
Lagging: 0.7
Leading: 0.9
Total output voltage distortion
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
Battery type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Battery run time (internal)
>5 minutes at 100% load
>5 minutes at 100% load
Battery string voltage
240 VDC
240 VDC
Battery test
Automatic battery test standard
Manual battery test from front display
Automatic battery test standard
Manual battery test from front display
Battery recharge profile
Enhanced Battery Management three-stage charging technology
Enhanced Battery Management three-stage charging technology
Battery cut-off voltage
Variable from 1.67 VPC at <5 min run time to 1.75 VPC at >90 min
run time
Variable from 1.67 VPC at <5 min run time to 1.75 VPC at >90 min
run time
Battery low condition
Announced with alarm
Announced with alarm
Extended battery capability
Yes, add up to four additional 3U battery enclosures per
RP12000/3 UPS Module
Yes, add up to four additional 3U battery enclosures per
RP12000/3 UPS Module
Battery characteristics
3
Technical specifications (continued)
RP36000/3 (base unit)
RP12000/3 (optional UPS expansion module)
Dimensions (HxDxW) UPS
78.7 x 39.7 x 24 inches 2,000 x 1,015 x 597 mm (HP 10000
G2 42U Rack)
10.3 (6U) x 17.4 x 26.0 inches 267 x 442 x 660 mm
Total chassis weight without
batteries or electronics
653 lb (296 kg)
100 lb (46 kg)
Total chassis weight with batteries
or electronics
1274 lb (578 kg)
307 lb (140 kg)
ERM weight
170 lb (77 kg)
170 lb (77 kg)
Software compatibility
UPS ships with HP UPS Management Module
UPS ships with HP UPS Management Module
Control panel LCD
Two lines by 20 characters, four menu-driven interface buttons, four
status-at-a-glance LEDs 1 per UPS Module
Two lines by 20 characters, four menu-driven interface buttons, four
status-at-a-glance LEDs 1 per UPS Module
Multi-language
English standard
English standard
Configuration changes
User-capable, firmware auto-configures
User-capable, firmware auto-configures
REPO port
Yes
Yes
Warranty (parts/labour/onsite)
3-year/1-year/1-year (Power bus bar is 3-year parts only)
3-year/1-year/1-year (Power bus bar is 3-year parts only)
Serviceability features
Hot-swappable batteries, hot-swappable electronics module,
Automated internal maintenance bypass, auto-configure firmware,
Flash firmware upgradeable
Hot-swappable batteries, hot-swappable electronics module,
Automated internal maintenance bypass, auto-configure firmware,
Flash firmware upgradeable
HP Care Packs
Installation Care Packs available for additional RP12000/3
UPS Modules
Installation Care Packs available for additional RP12000/3
UPS Modules
Physical characteristics
Communications and user interface
Warranty and serviceability
Certifications
Safety
208V model: UL1778, cUL 400V model: CE
208V model: UL1778, cUL 400V model: CE
EMI
208V model: FCC Part 15 Class A 400V model: EN62040-2 Class A
208V model: FCC Part 15 Class A 400V model: EN62040-2 Class A
Surge protection
ANSI C62.41, Cat B-3
ANSI C62.41, Cat B-3
Hazardous materials (RoHS)
EU Directive 2002/95/EC Category 3 (4 of 5)
EU Directive 2002/95/EC Category 3 (4 of 5)
HP Financial Services
For more information
HP Financial Services provides innovative financing
and financial asset management programmes to
help you cost-effectively acquire, manage, and
ultimately retire your HP solutions. For more infor­
mation, contact your local HP representative, or
visit www.hp.com/go/hpfinancialservices.
For more information about HP power distribution
products, contact your local HP representative or
visit www.hp.com/products/ups.
Get connected
www.hp.com/go/getconnected
Current HP drivers, support & security alerts
delivered directly to your desktop
Technology for better business outcomes
To learn more, visit www.hp.com/products/ups
© Copyright 2007, 2010 Hewlett-Packard Development Company, L.P. The information contained herein
is subject to change without notice. The only warranties for HP products and services are set forth in
the express warranty statements accompanying such products and services. Nothing herein should be
construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or
omissions contained herein.