Galaxy VM Modbus Register Map
Modbus Register Map:Galaxy VM (3:3 50-225kVA 400/480V)
Part number: 990-9692
Notes:
1. 16-bit registers are transmitted MSB first (i.e. big-endian).
2. INT32 and UINT32 are most-significant word in n+0, least significant word in n+1 (i.e. big-endian).
3. Function codes 3 and 4 are supported
4. Modbus serial RTU and Modbus over TCP is supported.
5. Signed numbers are twos-compliment
6. Status bits are atomic within a single Modbus register. User should not look for consistency across multiple registers, only within a single register.
7. For ASCII strings less than the maximum length, the unused characters are filled with nulls.
8. Single-register reads of reserved or undefined registers will return an error. Block reads which begin with a valid register will not return an error but will return zeros for undefined registers.
9. Strings are two characters per register, first character in high-order byte, second character in low-order byte. Printable ASCII only.
10. Bit #0 is least significant bit.
11. Data Type column: "INT16"=signed 16-bit integer, "UINT16" = unsigned 16-bit integer, "INT32" = signed 32-bit integer, "UINT32" = unsigned 32-bit integer, "ENUM" is a UINT16 value which maps
to a defined list of states, "ASCII" = the printable ASCII subset from 0x20 - 0x7E. BOOLEAN= a single bit, 0 or 1.
12. "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to "Register 40001" in Modicon terminology, which is address zero when transmitted over the wire.
For detailed modbus configuration settings, please refer to the Display or AP9635 User’s Guide.
Scale
Modicon Standard
Register Number
Status Data
40002
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
0x0001
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
40003
40004
0x0002
0x0003
2
3
Length
# registers
Data Point
UPS Status
UPS operation mode - Battery
Battery is below minimum acceptable runtime
Bypass
UPS operation mode - Battery Test
Reserved
Reserved
Reserved
Reserved
Reserved
Battery fault
Reserved
Reserved
Reserved
Informational alarm present
Warning alarm present
Critical alarm present
1
Alarm Register
1
Data Type
Multiply
Reading
By:
Divide
Reading
By:
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Valid Response
1=UPS operation mode - Battery
1=Battery is below minimum acceptable runtime
1=UPS is in Bypass
1=UPS operation mode - Battery Test
1=Battery fault
1=Informational alarm present
1=Warning alarm present
1=Critical alarm present
1=Lost local network management interface - to - UPS
communication
1=Main Controller is unable to communicate with the
display
0 Lost local network management interface - to - UPS communication
BOOLEAN
1 Display communication is lost
BOOLEAN
2
3
4
5
6
7
8
9
10
11
12
13
14
15
BOOLEAN
1=Parallel communication error on PBUS cable 1
BOOLEAN
BOOLEAN
1=Parallel communication error on PBUS cable 2
Parallel communication error on PBUS cable 1
Parallel communication error on PBUS cable 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Communication cable termination fault
General parallel system error
Lost parallel redundancy
Reserved
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Alarm Register
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
1
1=Communication cable termination fault
1=General parallel system error
1=Lost parallel redundancy
Scale
Modicon Standard
Register Number
40005
40006
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
0x0004
0x0005
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Reserved
UPS operation mode - Requested Static Bypass
UPS operation mode - Forced Static Bypass
UPS operation mode - Maintenance Bypass
Started a self-test
UPS operation mode - Off
UPS operation mode - Initialize
Reserved
Reserved
Reserved
Reserved
Input phase sequence error
Input frequency fault
Input voltage error
Selftest - Failed
Reserved
Alarm Register
Reserved
Reserved
Reserved
Bypass frequency fault
Bypass phase sequence error
Reserved
Reserved
Reserved
Overload on UPS
Overload on Static bypass switch
Ambient temperature out of range
EPO Switch Activated
Ground fault detected
Reserved
Bypass voltage error
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Alarm Register
System locked in bypass operation
Batteries are discharging
Reserved
Reserved
Reserved
Charge power is reduced
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Battery condition is weak
Battery condition is poor
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
RESERVED
1
Alarm Register
Reserved
Reserved
Reserved
Ambient temperature high
Overload on UPS due to high ambient temperature
Output frequency fault
Output voltage error
1
4
5
40007
0x0006
6
40008
0x0007
7
Data Point
Length
# registers
0
1
2
3
4
5
6
Data Type
Multiply
Reading
By:
Divide
Reading
By:
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
2
Valid Response
1=UPS operation mode - Requested Static Bypass
1=UPS operation mode - Forced Static Bypass
1=UPS operation mode - Maintenance Bypass
1=UPS operation mode - Off
1=UPS operation mode - Initialize
1=Input phase sequence error
1=Input frequency fault
1=Input voltage is out of range
1=Self test has failed
1=Bypass frequency fault
1=Bypass phase sequence error
1=Overload on UPS
1=Overload on Static bypass switch
1=Ambient temperature out of range
1=EPO Switch activated
1=Ground fault detected
1=Bypass input voltage is out of range
1=System locked in bypass operation
1=Batteries are discharging
1=Charge power is reduced
1=Battery condition is weak
1=Battery condition is poor
1 = Ambient temperature is high
1 = Overload on UPS due to high ambient temperature
1=Output frequency fault
1=Output voltage is outside its defined limits
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
7
8
9
10
11
12
13
14
15
40009
0x0008
8
40010
0x0009
9
40011
0x000A
0x000B
11
40015
0x000E
14
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Data Type
1
Alarm Register
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Unit Unit Breaker (UIB) open
Unit Ouput Breaker (UOB) open
Maintenance Bypass Breaker (MBB) closed
System Isolation Breaker (SIB) open
Static Switch Input Breaker (SSIB) open
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Alarm Register
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
0
1
2
3
4
5
6
7
Divide
Reading
By:
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Valid Response
1=Unit Unit Breaker (UIB) open
1=Unit Ouput Breaker (UOB) open
1=Maintenance Bypass Breaker (MBB) closed
1=System Isolation Breaker (SIB) open
1=Static Switch Input Breaker (SSIB) open
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
8 Static bypass switch fault
BOOLEAN
9
10
11
12
13
14
15
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
0
1
2
3
4
5
6
7
8
9
10
Multiply
Reading
By:
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
RESERVED
10
40012
Data Point
Length
# registers
Static bypass switch warning
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
RESERVED
3
Alarm Register
Reserved
Reserved
Reserved
High Battery Temperature Level
Low Battery Temperature Level
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
3
1=Static bypass switch has a critical fault that prevents it
from operating
1=Static bypass switch has an error with severity level
warning
1=Battery temperature above alarm setting
1=Battery temperature below alarm setting
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
11
12
13
14
15
40016
0x000F
15
40017
0x0010
16
40018
0x0011
0x0012
18
40020
0x0013
19
Battery breaker BB1 open
Battery breaker BB2 open
Reserved
Reserved
Reserved
RESERVED
1
Alarm Register
UPS operation mode - Static bypass standby
UPS operation mode - Inverter standby
Reserved
Reserved
General UPS settings error
UPS configuration error
Synchronization error
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fan fault
Inverter is Off due to a request by the user
Restricted air flow
Surveillance fault
Charger status
Inverter status
PFC status
Battery status
Reserved
Alarm Register
Technical check recommended
Start-up recommended
Warranty expiring soon
Reserved
Air filter check recommened
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
RESERVED
1
Alarm Register
Reserved
Reserved
Reserved
Reserved
Reserved
Not enough UPS ready to turn on inverter
Parallel UPS 1 not present
Parallel UPS 2 not present
Parallel UPS 3 not present
Parallel UPS 4 not present
Parallel UPS 5 not present
Parallel mixed operation mode
Reserved
Reserved
Reserved
Reserved
1
17
40019
Data Point
Length
# registers
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Data Type
Multiply
Reading
By:
Divide
Reading
By:
Valid Response
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Battery breaker BB1 open
1=Battery breaker BB2 open
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=UPS operation mode - Static bypass standby
1=UPS operation mode - Inverter standby
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=General UPS settings error
1=UPS has general configuration error
1=Synchronization error-system is free running
1=UPS has one or more faulty fans. Fan redundancy is
lost.
1= Inverter is Off due to a request by the user
1=Restricted air flow
1=Surveillance fault exists in UPS
1=Faulty
1=Faulty
1=Faulty
1=Faulty
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Technical check recommended
1= Secure start-up recommended
1=Warranty expiring soon
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Warning alarm in Prallel UPS 1
1=Warning alarm in Prallel UPS 2
1=Warning alarm in Prallel UPS 3
1=Warning alarm in Prallel UPS 4
1=Warning alarm in Prallel UPS 5
1=Not enough UPS ready to turn on inverter
1=Parallel UPS 1 not present
1=Parallel UPS 2 not present
1=Parallel UPS 3 not present
1=Parallel UPS 4 not present
1=Parallel UPS 5 not present
1=Parallel mixed operation mode
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
4
1=Air filter check recommened
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
40021
0x0014
20
40022
0x0015
21
40023
40024
40025
0x0016
0x0017
0x0018
Data Point
Length
# registers
RESERVED
1
Alarm Register
System operation mode - Off
System operation mode - Forced static bypass
System operation mode - Requested static bypass
System operation mode - Maintenance bypass
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Alarm Register
Input missing phase error
Bypass missing phase error
External sync voltage error
External sync phase sequence error
External sync frequency fault
External sync missing phase error
Reserved
Reserved
Display firmware incompatibility detected
NMC 1 firmware incompatibility detected
NMC 2 firmware incompatibility detected
Reserved
Inverter output is not in phase with bypass input
Reserved
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Alarm Register
Modular battery cabinet 1 fault
Modular battery cabinet 2 fault
Modular battery cabinet 3 fault
Modular battery cabinet 4 fault
Modular battery cabinet 5 fault
Modular battery cabinet 6 fault
Modular battery cabinet 7 fault
Modular battery cabinet 8 fault
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Alarm Register
Modular battery cabinet 1 breaker 1 open
Modular battery cabinet 1 breaker 2 open
Modular battery cabinet 2 breaker 1 open
Modular battery cabinet 2 breaker 2 open
Modular battery cabinet 3 breaker 1 open
Modular battery cabinet 3 breaker 2 open
1
0
1
2
3
4
5
22
23
24
Data Type
Multiply
Reading
By:
Divide
Reading
By:
Valid Response
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1 = System operation mode - Off
1 = System operation mode - Forced static bypass
1 = System operation mode - Requested static bypass
1 = System operation mode - Maintenance bypass
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Input is missing a phase
1=Bypass input is missing a phase
1=External sync voltage is out of range
1=The phase rotation on external sync is wrong
1=External sync frequency is out of range
1=External sync is missing a phase
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Modular battery cabinet 1 fault
1=Modular battery cabinet 2 fault
1=Modular battery cabinet 3 fault
1=Modular battery cabinet 4 fault
1=Modular battery cabinet 5 fault
1=Modular battery cabinet 6 fault
1=Modular battery cabinet 7 fault
1=Modular battery cabinet 8 fault
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1=Modular battery cabinet 1 breaker 1 open
1=Modular battery cabinet 1 breaker 2 open
1=Modular battery cabinet 2 breaker 1 open
1=Modular battery cabinet 2 breaker 2 open
1=Modular battery cabinet 3 breaker 1 open
1=Modular battery cabinet 3 breaker 2 open
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
5
1=Display firmware incompatibility detected
1=NMC 1 firmware incompatibility detected
1=NMC 2 firmware incompatibility detected
1=Inverter output is not in phase with bypass input
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
6
7
8
9
10
11
12
13
14
15
Data Point
Length
# registers
Modular battery cabinet 4 breaker 1 open
Modular battery cabinet 4 breaker 2 open
Modular battery cabinet 5 breaker 1 open
Modular battery cabinet 5 breaker 2 open
Modular battery cabinet 6 breaker 1 open
Modular battery cabinet 6 breaker 2 open
Modular battery cabinet 7 breaker 1 open
Modular battery cabinet 7 breaker 2 open
Modular battery cabinet 8 breaker 1 open
Modular battery cabinet 8 breaker 2 open
0x1000
0x1009
0x1011
0x101A
0x1023
0x1029
0x1031
0x1037
0x1043
4096
4105
4113
4122
4131
4137
4145
4151
4163
Display/NMC Model Number
Display/NMC Serial Number
Display/NMC Firmware Revision APP
Display/NMC Hardware Revision
Display/NMC Date of Manufacture
RESERVED
UPS Serial Number
UPS Firmware Version
Product Name
Dynamic Data
44353
44355
44357
44359
44360
44368
44369
0x1100
0x1102
0x1104
0x1106
0x1107
0x110F
0x1110
4352
4354
4356
4358
4359
4367
4368
2
2
2
1
8
1
1
1
1
1
1
44370
44371
44372
44373
44374
44375
44376
44377
44378
44379
44380
44381
0x1111
0x1112
0x1113
0x1114
0x1115
0x1116
0x1117
0x1118
0x1119
0x111A
0x111B
0x111C
4369
4370
4371
4372
4373
4374
4375
4376
4377
4378
4379
4380
44609
44610
44611
44612
0x1200
0x1201
0x1202
0x1203
4608
4609
4610
4611
Frequency (input)
Voltage L1-2 (input)
Voltage L2-3 (input)
Voltage L3-1 (input)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Divide
Reading
By:
9
8
9
9
6
8
6
12
40
1
1
1
1
1
1
1
1
1
1
1
1
Valid Response
1=Modular battery cabinet 4 breaker 1 open
1=Modular battery cabinet 4 breaker 2 open
1=Modular battery cabinet 5 breaker 1 open
1=Modular battery cabinet 5 breaker 2 open
1=Modular battery cabinet 6 breaker 1 open
1=Modular battery cabinet 6 breaker 2 open
1=Modular battery cabinet 7 breaker 1 open
1=Modular battery cabinet 7 breaker 2 open
1=Modular battery cabinet 8 breaker 1 open
1=Modular battery cabinet 8 breaker 2 open
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Static Data
44097
44106
44114
44123
44132
44138
44146
44152
44164
RESERVED
Runtime remaining
Estimated charge time
Estimated charge %
RESERVED
Battery Temperature (for classic battery solution)
Charger Mode
Float Charging
Boost Charging
Reserved
Reserved
Reserved
Equalization Charging
Not Charging
Test In Progress
Cyclic Charging
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Battery Power
RESERVED
Battery Voltage
Battery Current
Modular Battery cabinet 1 temperature
Modular Battery cabinet 2 temperature
Modular Battery cabinet 3 temperature
Modular Battery cabinet 4 temperature
Modular Battery cabinet 5 temperature
Modular Battery cabinet 6 temperature
Modular Battery cabinet 7 temperature
Modular Battery cabinet 8 temperature
Data Type
Multiply
Reading
By:
ASCII
ASCII
ASCII
ASCII
ASCII
ASCII
ASCII
ASCII
UINT32
UINT32
UINT16
1
1
1
1
1
1
Seconds
Seconds
%
UINT16
1
1
°C
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INT16
1=Charger mode is float charging
1=Charger mode is boost charging
1=Charger mode is eqalization charging
1=Charger mode is Off
1=Test is in progress
1=Charge mode is cyclic charging
0,1
10
kW
UINT16
INT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
0,1
0,1
1
1
1
1
1
1
1
1
10
10
1
1
1
1
1
1
1
1
Vdc
amps
°C
°C
°C
°C
°C
°C
°C
°C
UINT16
UINT16
UINT16
UINT16
0,1
1
1
1
10
1
1
1
Hz
Vrms
Vrms
Vrms
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
6
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
Data Point
Length
# registers
Data Type
Multiply
Reading
By:
Divide
Reading
By:
Valid Response
44613
44614
44615
44616
44617
44618
44619
44620
44621
44622
44623
44624
44625
44626
44627
44629
44631
44633
44634
44635
0x1204
0x1205
0x1206
0x1207
0x1208
0x1209
0x120A
0x120B
0x120C
0x120D
0x120E
0x120F
0x1210
0x1211
0x1212
0x1214
0x1216
0x1218
0x1219
0x121A
4612
4613
4614
4615
4616
4617
4618
4619
4620
4621
4622
4623
4624
4625
4626
4628
4630
4632
4633
4634
Current L1 (input)
Current L2 (input)
Current L3 (input)
Active power L1 (input)
Active power L2 (input)
Active power L3 (input)
Apparent power L1 (input)
Apparent power L2 (input)
Apparent power L3 (input)
Total active power (input)
Total apparent power (input)
Voltage L1-N (input)
Voltage L2-N (input)
Voltage L3-N (input)
Maximum RMS Current L1 (input)
Maximum RMS Current L2 (input)
Maximum RMS Current L3 (input)
Power factor L1 (input)
Power factor L2 (input)
Power factor L3 (input)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0,1
0,1
0,1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
amps
amps
amps
kW
kW
kW
kVA
kVA
kVA
kW
kVA
Volts
Volts
Volts
amps
amps
amps
Unitless
Unitless
Unitless
44865
44866
44867
44868
44869
44870
44871
44872
44873
44874
44875
44876
44877
44878
44879
44880
44881
44882
44883
44885
44887
44889
44890
44891
0x1300
0x1301
0x1302
0x1303
0x1304
0x1305
0x1306
0x1307
0x1308
0x1309
0x130A
0x130B
0x130C
0x130D
0x130E
0x130F
0x1310
0x1311
0x1312
0x1314
0x1316
0x1318
0x1319
0x131A
4864
4865
4866
4867
4868
4869
4870
4871
4872
4873
4874
4875
4876
4877
4878
4879
4880
4881
4882
4884
4886
4888
4889
4890
Frequency (bypass)
Voltage L1-2 (bypass)
Voltage L2-3 (bypass)
Voltage L3-1 (bypass)
Current L1 (bypass)
Current L2 (bypass)
Current L3 (bypass)
Active power L1 (bypass)
Active power L2 (bypass)
Active power L3 (bypass)
Apparent power L1 (bypass)
Apparent power L2 (bypass)
Apparent power L3 (bypass)
Total active power (bypass)
Total apparent power (bypass)
Voltage L1-N (bypass)
Voltage L2-N (bypass)
Voltage L3-N (bypass)
Maximum RMS Current L1 (bypass)
Maximum RMS Current L2 (bypass)
Maximum RMS Current L3 (bypass)
Power factor L1 (bypass)
Power factor L2 (bypass)
Power factor L3 (bypass)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
0,1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0,1
0,1
0,1
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
Hz
Vrms
Vrms
Vrms
amps
amps
amps
kW
kW
kW
kVA
kVA
kVA
kW
kVA
Volts
Volts
Volts
amps
amps
amps
Unitless
Unitless
Unitless
45121
45122
45123
45124
45125
45126
45127
45128
45129
45131
45133
45135
45136
45137
45138
45139
45140
45141
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1406
0x1407
0x1408
0x140A
0x140C
0x140E
0x140F
0x1410
0x1411
0x1412
0x1413
0x1414
5120
5121
5122
5123
5124
5125
5126
5127
5128
5130
5132
5134
5135
5136
5137
5138
5139
5140
UPS Power Rating
Frequency (output)
Voltage L1-2 (output)
Voltage L2-3 (output)
Voltage L3-1 (output)
Current L1 (output)
Current L2 (output)
Current L3 (output)
Maximum RMS current L1 (output)
Maximum RMS current L2 (output)
Maximum RMS current L3 (output)
Active power L1 (output)
Active power L2 (output)
Active power L3 (output)
Apparent power L1 (output)
Apparent power L2 (output)
Apparent power L3 (output)
RESERVED
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
3
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT32
UINT32
UINT32
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
1
0,1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
kVA
Hz
Vrms
Vrms
Vrms
amps
amps
amps
amps
amps
amps
kW
kW
kW
kVA
kVA
kVA
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
7
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
Data Point
Length
# registers
45144
45145
45146
45147
45148
45149
45150
45151
45152
45153
45154
45155
45156
45157
45158
45159
0x1417
0x1418
0x1419
0x141A
0x141B
0x141C
0x141D
0x141E
0x141F
0x1420
0x1421
0x1422
0x1423
0x1424
0x1425
0x1426
5143
5144
5145
5146
5147
5148
5149
5150
5151
5152
5153
5154
5155
5156
5157
5158
Total active power (output)
Total apparent power (output)
Total Output Percent load
Power factor L1 (output)
Power factor L2 (output)
Power factor L3 (output)
Current crest factor L1 (output)
Current crest factor L2 (output)
Current crest factor L3 (output)
Voltage L1-N (output)
Voltage L2-N (output)
Voltage L3-N (output)
Neutral current (output)
Current THD L1 (output)
Current THD L2 (output)
Current THD L3 (output)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
45377
0x1500
5376
RESERVED
1
45378
0x1501
5377
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Switch gear status
Unit Input Breaker (UIB)
Unit Output Breaker (UOB)
(Maintenance Bypass Breaker (MBB)
System Isolation Breaker (SIB)
Static Switch Input Breaker (SSIB)
Battery Breaker 1 (for classic battery solution)
Battery Breaker 2 (for classic battery solution)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Data Type
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
Multiply
Reading
By:
Divide
Reading
By:
1
1
0,1
0,1
0,1
0,1
0,1
0,1
0,1
1
1
1
1
0,1
0,1
0,1
1
1
10
10
10
10
10
10
10
1
1
1
1
10
10
10
Valid Response
kW
kVA
%
power factor
power factor
power factor
crest factor
crest factor
crest factor
Volts
Volts
Volts
amps
%
%
%
Bit mask
For each bit,
0 = open, 1 =closed
1
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
45379
45380
0x1502
0x1503
5378
5379
UPS Operation Mode
Number of Active Alarms
1
1
ENUM
UINT16
1
1
45381
0x1504
5380
Highest alarm severity
1
UINT16
1
1
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
8
0 = Reserved
1 = Normal operation
2 = Battery Operation
3 = Battery Test
4 = Requested Static Bypass
5 = Forced Static Bypass
6 = Maintenance Bypass
7 = Off
8 = Emergency Static Bypass
9 = Static Bypass Standby
10 = Inverter Standby
11 = Power Saving Mode
12 = SPoT Mode
13 = ECO Mode
14 = ECOnversion
Number of active alarms in the system
0 = none
1 = informational
2 = warning
3 = critical
Scale
Modicon Standard
Register Number
Absolute Starting Absolute Starting
Register Address, Register Address,
(Decimal)
(Hexa-decimal)
Bit
Data Point
Length
# registers
Data Type
Multiply
Reading
By:
Divide
Reading
By:
Valid Response
45382
45383
45386
45390
45395
45397
0x1505
0x1506
0x1509
0x150D
0x1512
0x1514
5381
5382
5385
5389
5394
5396
System Mode
RESERVED
NMC/UPS Time
NMC/UPS Date
Input kWh
Output kWh
1
3
4
5
2
2
ENUM
1 = Inverter
2 = Requested Static Bypass
3 = Forced Static Bypass
4 = Off
5 = Reserved
6 = Maintenance Bypass
7 = ECO Mode
8 = ECOnversion
ASCII
ASCII
UINT32
UINT32
1
1
1
1
hh:mm:ss format
mm/dd/yyyy format
kWh
kWh
46401
46402
46403
46404
46405
46406
46407
46408
46409
46410
46411
0x1900
0x1901
0x1902
0x1903
0x1904
0x1905
0x1906
0x1907
0x1908
0x1909
0x190A
6400
6401
6402
6403
6404
6405
6406
6407
6408
6409
6410
Current L1 (parallel system mains input)
Current L2 (parallel system mains input)
Current L3 (parallel system mains input)
Current L1 (parallel system bypass input)
Current L2 (parallel system bypass input)
Current L3 (parallel system bypass input)
Current L1 (parallel system output)
Current L2 (parallel system output)
Current L3 (parallel system output)
Total apparent power (parallel system output)
Total Percent load (parallel system)
1
1
1
1
1
1
1
1
1
1
1
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
1
1
1
1
1
1
1
1
1
1
0,1
1
1
1
1
1
1
1
1
1
1
10
amps
amps
amps
amps
amps
amps
amps
amps
amps
kVA
%
Configuration
Data
48193
48196
0x2000
0x2003
8192
8195
RESERVED
Number of Battery Modules
3
1
UINT16
1
1
48449
0x2100
8448
Low Battery Alarm Threshold
1
1
UINT16
1
1
48450
0x2101
8449
Battery Type
ENUM
1
1
ENUM
1
1
ENUM
UINT16
1
1
1
1
1
48451
0x2102
8450
Battery Solution
1
48452
48453
0x2103
0x2104
8451
8452
Deep Discharge Allowed
Total Battery Capacity
1
1
48705
0x2200
8704
Nominal Output Voltage
ENUM
1
1
ENUM
1
1
ENUM
1
1
ENUM
1
1
ENUM
1
1
1
48706
0x2201
8705
Transfer to Static Bypass Disable
1
48707
0x2202
8706
Flywheel Present
1
48708
0x2203
8707
Automatic Battery Disconnect
1
48709
END OF MAP
0x2204
8708
High Efficiency Mode
Galaxy VM (3:3 50-225kVA 400/480V) Modbus Register Map
9
Seconds
0=VRLA
1=Open Cell
0=None
1=Classic
2=Modular
3=Unknown
0=No
1=Yes
Ah
0=380V
1=400V
2=415V
3=480V
0=Disable
1=Enable
0=No
1=Yes
0=No
1=Yes
0=Disable
1=ECO mode
2=ECOnversion
Was this manual useful for you? yes no