DOWNLOAD DuraLife Shielded Datasheet
DuraLife®-W FPL Shielded
UL 2-Hour Fire Certified FIRE RESISTIVE ALARM CABLES
FHIT & FHITC.28B Electrical Circuit Integrity System
SPECIFICATIONS
UL 2196 CERTIFIED / ULC-S139 COMPLIANT / UL 1424 LISTED. FHIT & FHITC
SYSTEMS NO. 28B. LOW SMOKE, ZERO HALOGEN DESIGN (LSOH).
WET RATED.
Shielded - 18AWG, 16AWG, 14AWG; 2-conductor; Electrical Circuit Integrity System.
NEC Type FPL; for use in electrical circuit protective systems.
DURALIFE APPLICATIONS
• Hospitals and Healthcare Facilities
• High Rises
• Sports Arenas
• Critical or Federal Buildings
• Bridges, Tunnels and Transit
COMPLIANCE:
• UL 1424 Listed FPL for Power-Limited Fire Alarm Circuits; 300V / 90°C classified
• UL Certified to UL 2196 2-hour fire rating in FHIT.28B
• ULC Certified under FHITC.28B.
• CSA Std. C22.2 No. 208-14. CSA Type FAS90, 300V FT1.
• Meets National Fire Protection Code (NFPA 70 & 72) fire alarm survivability circuit requirements
• Meets National Fire Protection Code (NFPA 130 & 502) fire alarm survivability circuit requirements.
• Suitable for 2-hr. certified fire-resistive applications in EMT conduit.*
• Fire certified for Power-Limited system use at 50V (18AWG) & 72V (16AWG, 14AWG) phase-to-phase utilization voltages
• UL Listed File No. E-241484. UL Fire Directory R-21213.
• Suitable for use in wet locations.
* DuraLife® FPL products are not approved for use in RMC or IMC conduit systems
HARDWARE SYSTEM CERTIFIED: (Refer to DuraLife®-W Installation Guide for Item Details)
• Enclosure Set-screw Fittings --- Hubbell-Raco
• Copper Off-Set Fixed Lug Connector with set
screw; --- Penn Union (16AWG - 14AWG)
• Mechanical Connector --- Ceramic Wire Nut;
Proheat (18AWG, 16AWG, 14AWG)
• Pulling Lubricant --- Polywater J, LZ
• EMT Conduit --- Wheatland Tube FasTrak Plus*
• EMT Couplings --- Hubbell-Raco or Halex
• Enclosure Compression Fittings --- Cooper Crouse-Hinds
• NEMA 1 Splice Enclosure/Pull Box --- Cooper B-Line
(Pull box size up to 12x12x4 for 16AWG and 14AWG.
Splice box size must be 8x8x4.)
*Certified assemblies, no substitute of any kind can be made
CONSTRUCTION:
• Oxygen-free bare copper (OFHC) conductors, solid and stranded; proprietary ceramifiable silicone rubber insulation; color-code
black and red insulation on leads, aluminum/aramid shield, and 22AWG solid TC drain
• Low smoke - zero halogen FRPE outer jacket. Black jacket color available at an additional charge
• Standard construction is 3 twists per foot.
• Patented
Certifications & EMT Fill Listings
9-17
CERTIFICATIONS
18 AWG
16 AWG
14 AWG
Solid Conductor



Stranded Conductor
—
—

FILL RATES
18 AWG
16 AWG
14 AWG
¾” EMT Horizontal and Vertical
Up to 2 cables
1 cable
1 cable
1” EMT Horizontal and Vertical
—
Up to 2 cables
Up to 2 cables
1 ¼” EMT Horizontal
—
Up to 4 cables
Up to 4 cables
1 ¼” EMT Vertical
—
Up to 3 cables
Up to 3 cables
1 ½” EMT Horizontal
—
Up to 6 cables
Up to 6 cables
1 ½” EMT Vertical
—
Up to 4 cables
Up to 4 cables
2” EMT Horizontal
—
Up to 10 cables
-
2” EMT Vertical
—
Up to 8 cables
Up to 10 cables
© 2017
DuraLife®-W FPL Shielded
UL 2-Hour Fire Certified FIRE RESISTIVE ALARM CABLES
FHIT & FHITC.28B Electrical Circuit Integrity System
PACKAGING:
Available on 1,000 ft. and 5,000 ft. standard length reels. Smaller reels available from distributors.
RADIX WIRE-II DURALIFE™ -W E241484 2/C 18 AWG SHLD FPL 90C / (UL) 2196 CLASSIFIED FIRE-RESISTIVE CABLE FOR USE IN ELECTRIC CIRCUIT
INTEGRITY SYSTEM #28B. SEE UL FIRE RESISTANCE DIRECTORY R21213 CSA LL13427 FAS90 300V FT1 (MONTH/YEAR) CI - NYC certified fire alarm cable
RADIX P/N
#COND
AWG
NOMINAL INSUL
THICKNESS
(INCH)
NOMINAL JACKET
THICKNESS (INCH)
NOMINAL
O.D.
MIN. - MAX.
SPEC. RANGE
NET WEIGHT
(LBS PER MFT)
COPPER
LBS/MFT
CAPACITANCE
(pF/Ft.)
IMPEDANCE
CIS18A0102
2
18 SOLID
0.032”
0.035”
0.326”
+/-0.020”
51
9.8
19.2
94.7
RADIX WIRE-II DURALIFE™ -W E241484 2/C 16 AWG SHLD FPL 90C / (UL) 2196 CLASSIFIED FIRE-RESISTIVE CABLE FOR USE IN ELECTRIC CIRCUIT
INTEGRITY SYSTEM #28B. SEE UL FIRE RESISTANCE DIRECTORY R21213 CSA LL13427 FAS90 300V FT1 (MONTH/YEAR) CI - NYC certified fire alarm cable
RADIX P/N
#COND
AWG
NOMINAL INSUL
THICKNESS
(INCH)
NOMINAL JACKET
THICKNESS
(INCH)
NOMINAL
O.D.
MIN. - MAX.
SPEC. RANGE
NET WEIGHT
(LBS PER MFT)
COPPER
LBS/MFT
CAPACITANCE
(pF/Ft.)
IMPEDANCE
CIS16A0102
2
16 SOLID
0.032”
0.035”
0.340”
+/-0.020”
60
16.4
21.6
85.2
RADIX WIRE-II DURALIFE™ -W E241484 2/C 14 AWG SHLD FPL 90C / (UL) 2196 CLASSIFIED FIRE-RESISTIVE CABLE FOR USE IN ELECTRIC CIRCUIT
INTEGRITY SYSTEM #28B. SEE UL FIRE RESISTANCE DIRECTORY R21213 CSA LL13427 FAS90 300V FT1 (MONTH/YEAR) CI - NYC certified fire alarm cable
AWG
NOMINAL INSUL
THICKNESS
(INCH)
NOMINAL JACKET
THICKNESS
(INCH)
NOMINAL
O.D.
MIN. - MAX.
SPEC. RANGE
NET WEIGHT
(LBS PER MFT)
COPPER
LBS/MFT
CAPACITANCE
(pF/Ft.)
IMPEDANCE
2
14/7
0.032”
0.035”
0.380”
+/-0.020”
78
25.2
25.9
69.4
2
14 SOLID
0.032”
0.035”
0.365”
+/-0.020”
75
24.8
25.0
75.1
RADIX P/N
#COND
CIS14A0702
CIS14A0102
CERTIFICATION LISTINGS:
18AWG solid OFHC; 2-conductor vertical straight-through w/ couplings in 3/4” EMT conduit; 72” max. support spacing, pull box, 2 cables
18AWG solid OFHC; 2-conductor horizontal straight-through w/ couplings in 3/4” EMT conduit; 48” max. support spacing
18AWG solid OFHC; 2-conductor horizontal straight-through w/ pull box in 3/4” EMT conduit; 48” max. support spacing
18AWG solid OFHC; 2-conductor horizontal w/ mechanical splice in 3/4” EMT conduit; 48” max. support spacing
18AWG solid OFHC; 2-conductor vertical w/ mechanical splice in 3/4” EMT conduit; 72” max. support spacing
16AWG solid OFHC; 2-conductor vertical straight-through w/ couplings in 1” EMT conduit; 72” max. support spacing, pull box, 2 cables
16AWG solid OFHC; 2-conductor horizontal straight-through w/ couplings in 3/4” EMT conduit; 48” max. support spacing
16AWG solid OFHC; 2-conductor horizontal straight-through w/ pull box in 3/4” EMT conduit; 48” max. support spacing
16AWG solid OFHC; 2-conductor horizontal w/ mechanical splice in 3/4” EMT conduit; 48” max. support spacing
14AWG 7-strand OFHC; 2-conductor vertical straight-through w/ couplings in 1” EMT conduit; 72” max. support spacing, pull box, 2 cables
14AWG 7-strand OFHC; 2-conductor horizontal straight-through w/ couplings in 3/4” EMT conduit; 48” max. support spacing
14AWG 7-strand OFHC; 2-conductor horizontal straight-through w/ pull box in 3/4” EMT conduit; 48” max. support spacing
14AWG 7-strand OFHC; 2-conductor horizontal w/ mechanical splice in 3/4” EMT conduit; 48” max. support spacing
14AWG solid OFHC; 2-conductor vertical straight-through w/ couplings in 1” EMT conduit; 72” max. support spacing, pull box, 2 cables
14AWG solid OFHC; 2-conductor horizontal straight-through w/ couplings in 3/4” EMT conduit; 48” max. support spacing
14AWG solid OFHC; 2-conductor horizontal straight-through w/ pull box in 3/4” EMT conduit; 48” max. support spacing
14AWG solid OFHC; 2-conductor horizontal w/ mechanical splice in 3/4” EMT conduit; 48” max. support spacing
Note: 18AWG, 16AWG, and 14AWG cables may be installed within the same raceway when not
exceeding the number of cables associated with the 14AWG installation.
All dimensions listed above are nominal
Information included in this catalog is intended as a guideline only. for applications that require
tight tolerances. Please contact the Radix factory for dimensional verification. Information herein is
believed to be accurate as of publication date; however, if an error exists it is unintentional and
Radix Wire is not responsible for any claim traceable to such error.