Stride SE2 Unmanaged Insert
®
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860, USA
Stride® SE2 Series Industrial
Unmanaged Ethernet Switches
Note: For additional product details, a user manual,
SE2-USER-M, is available as a downloadable PDF file from the
Online Documentation area of the AutomationDirect website.
General Specifications
Operating Mode
Store and forward wire speed switching, non-blocking
Devices Supported
All IEEE 802.3 compliant devices are supported
MAC Addresses
Packet Forwarding Rate
RJ45
GbE
Fiber
SE2-MC2U-C1-T
1
–
1 SC
SE2-MC2U-T1-T
1
–
1 ST
1-800-633-0405
SE2-SW5U
5
SE2-SW5U-T
–
–
–
–
Input power
(max.)
3.4 W
–
5
–
SE2-SW5U-1C1-T
4
–
1 SC
SE2-SW5U-1T1-T
4
–
1 ST
–
–
–
–
–
2 SC
–
2 ST
8
2 GbE
SFP*
10W
–
–
8W
8
SE2-SW8U-T
SE2-SW8U-2C1-T
6
SE2-SW8U-2T1-T
SE2-SW8UG-T
–
SE2-SW10UG-2P-T
–
SE2-SW16U-T
16
Operating Temp
4.5 W
-10 to +60­°C
(+14 to +140°F)
3.4 W
-40 to +85 °C (-40 to +185 °F)
Vibration, Shock & Freefall
IEC60068-2-6, -27, -32
-10 to +60­°C
(+14 to +140°F)
UL/cUL 6101-1 and 61010-2-201,
Class 1, Div. 2, Groups A, B, C, D, (UL file #E200031)
CE
* Broadcast storm threshold value is 2 packets/100ms for 10 Mbps port or 2 packets/10ms for 100 Mbps
and 1000 Mbps ports.
** DIP switch II is unused on the 10/100 models.
Front Panel LEDs
LED
PWR1 LED
PWR2 LED
Yes
ACT/LNK LED
Speed LED
10/100 Models
Shielded RJ45
IEEE 802.3i, 802.3u, 802.3x for 10/100 Ethernet
IEEE 802.3ab, 802.3z for Gigabit Ethernet
Auto-Crossover
Speed LED
10/100/1000
Models
Yes, allows you to use straight-through or crossover wired cables
Auto-Sensing Operation
Yes, full and half duplex
Auto-Negotiating Speed
Yes
Flow Control
State
Description
On
Power 1 connected and operational
Off
Power 1 no voltage
On
Power 2 connected and operational
Off
Power 2 no voltage
On
Indicates that there is a proper Ethernet connection (Link) between the port and another
Ethernet device, but no communications activity is detected.
Indicates that there is a proper Ethernet connection (Link) between the port and another
Ethernet device, and that there is communications activity.
Indicates that there is not a proper Ethernet connection (Link) between the port and
another Ethernet device. Make sure the cable has been plugged securely into the ports
at both ends.
Blinking
Off
RJ45 Ports
Ethernet Compliance
Metal case, IP30
ANSI/ISA 12.12.01-2015 & CSA 22.2 No. 213-15 (Class I, Div.2) (file #E200031);
Agency Approvals
-40 to +75°C
(-40 to +167°F)
Refer to Models table
Port Type
RoHS (Pb free) and WEEE compliant
Hazardous Locations
Redundant Input Terminals
Power Consumption
FCC CFR47 Part 15, EN55022/CISPR22, Class A
Packaging and Protection
Class 2 Power Supply: 12-48 VDC, 18-30 VAC 50/60 Hz
Reverse Power Protection
No corrosive gases permitted
RoHS and WEEE
4.6 W
–
5 to 95% RH
IEC61000-4-2 (ESD): +/- 6kV (contact), +/- 8kV (air)
IEC61000-4-3 (RS): 10V/m (80MHz ~ 2GHz)
IEC61000-4-4 (EFT): Power Port +/- 2kV; Data Port: +/- 1kV
IEC61000-4-5 (Surge): Power Port: +/- 1kV/DM, +/- 2kV/CM;
Data Port +/- 1kV (+/- 2kV for 16 and 18 port models)
IEC61000-4-6 (CS): 10V (150kHz ~ 80MHz)
EMS
Power Details
Input Voltage
< 10 µs
Storage Temperature Range
Humidity
(non-condensing)
Environmental Air
EMI Emissions
-40 to +75°C
(-40 to +167°F)
* Optional SFP modules sold separately. Use only Gigabit speed SFPs with
SE2-SW10UG-2P-T.
Power Input
DIP switch enabled for Gigabit Ethernet switches (DIP switch II ON)**
Latency
-40 to +75°C
(-40 to +167°F)
SE2-SW5UG-T
SE2-SW8U
Jumbo Frame Support
On
A 100 Mbps (100BaseT) connection is detected.
Off
A 10 Mbps (10BaseT) connection is detected.
On
A 1000 Mbps (1000BaseT) connection is detected
Off
A 100 or 10 Mbps (100BaseT or 10BaseT) connection is detected
SC/ST Fiber Port: (100BaseFX multimode)
Automatic
Optimal Fiber Cable
Cable Requirements
Twisted pair (Cat5e or better) (shielded recommended)
Center Wavelength
Max. Cable Distance
100 meters
Multimode
SFP Ports
Nominal Max. Distance
Eye Safety (laser)
SFP (pluggable) ports accept Mini-GBIC (SFP) transceivers
with a speed of 1000 Mbps or 100 Mbps
See SFP datasheet for optional fiber transceiver specifications
1
50/125 or 62.5/125 µm
1300 nm
Links up to 4 km typ.
> Transmitter power (dBm): -21 min, -17 typ, -14 max
> Receiver sensitivity (dBm): -34 typ, -31 max
4 km
IEC 60825-1, Class 1; FDA 21 CFR 1040.10 and 1040.11
www.AutomationDirect.com
RJ45
10/100
DIP switch enabled (DIP switch I ON)
Broadcast Storm Protection*
Stride SE2 Unmanaged Models
Part Number
8K for SE2-SWxG-T, SE2-SW16U-T
2K
0.75 Mpps - SE2-MC2U-x, SE2-SW5U & SE2-SW5U-x
1.2 Mpps - SE2-SW8U-x
7.4 Mpps - SE2-SW5UG-T
14.9 Mpps - SE2-SW8UG-T & SE2-SW10UG-2P-T
5.7 Mpps - SE2-SW16U-T
20mm (0.79”)
CLEARANCE
Dimensions:
Dimensions
B
A
Part No.
Weight kg [lb]
SE2-MC2U-x
SE2-SW5Ux
Width (A)
Depth (B)
0.25 [0.55]
29.6 [1.17]
0.30 [0.66]
45.6 [1.80]
0.50 [1.10]
53.6 [2.11]
0.70 [1.54]
80.0 [3.15]
SE2-SW8U
SE2-SW8U-T
SE2-SW8U-2C1-T
Height (C)
mm [inches]
68.0 [2.68]
114.5 [4.51]
106.0 [4.17]
135.0 [3.31]
SE2-SW8U-2T1-T
C
SE2-SW8UG-T
SE2-SW10UG-2P-T
SE2-SW16U-T
Power Wiring:
Safety Standards:
C
UL
R
The switch can be powered from the same DC source that is used to power your
other devices. To maintain the UL listing, this must be a Class 2 power supply.
A DC voltage in the range of 12 to 48 VDC needs to be applied between the
P1+ terminal and the P1- terminal as shown below. The chassis screw terminal
should be tied to panel or chassis ground. To reduce down time resulting from
power loss, the switch can be powered redundantly with a second power supply
as shown below. A recommended DC power supply is AutomationDirect.com
part number PSL-24-030.
RoHS
US
RoHS Compliant
Redundant DC Power
These devices are open-type and are meant to be installed in an enclosure
which is only accessible with the use of a tool and suitable for the environment when installed in Class 1, Division 2 Hazardous Locations. The switch
can be snapped onto a standard 35 mm x 7.5 mm height DIN rail (Standard:
CENELEC EN50022) and can be mounted either vertically or horizontally.
Allow 20mm (0.79”) clearance between an SE2 switch and other equipment
on the DIN rail.
DIN rail mounting steps:
1. Hook top back of unit over the DIN rail.
2. Push bottom back onto the DIN rail until it snaps into place.
DIN rail removal steps:
A. Push the unit down to free the bottom of the DIN rail.
B. Rotate the bottom of the unit away from the DIN rail.
C. Unhook top of unit from DIN rail.
Removal
Mounting
1
C
A
B
Required terminal
screw torque is
4.5 to 5.0 lb-in
(0.51 to 0.57 N·m).
Wire Size Range
24 – 12 AWG
Wire Strip Length
7mm
Note: Signal output rated voltage is <30V.
WARNING: EXPLOSION HAZARD
Additional Help and Support
•
For additional product support, specifications, and
installation, a User Manual, SE2-USER-M, is available
as a downloadable PDF file from the Online Documentation area
of www.AutomationDirect.com
• For additional technical support and questions, call our Technical
Support team @ 770-844-4200.
AVERTISSEMENT: RISQUE D’EXPLOSION
• Avant de deconnecter l’equipement, couper le courant ou s’assurer que l’emplacement est
designe non dangereux.
• La substitution de composants peut rendre ce materiel inacceptable pour les emplacements de
Classe I, Division 2.
Copyright 2017, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
Optional Dual DC Supplies
Note: The following AutomationDirect PLC Ethernet
Modules are not compatible with the Stride Ethernet
Switches and Media Converter with fiber optic connections
because the modules have a speed of 10BaseF (fiber optic)
only: Ethernet Communications Module, p/n H2-ECOM-F
& H4-ECOM-F; Ethernet Base Controller Module, p/n H2EBC-F & H4-EBC-F; Ethernet Remote Master Module, p/n
H2-ERM-F & H4-ERM-F.
Cet appareillage est utilisable dans les emplacements de Classe I, Division 2, Groupes A, B, C et D,
ou dans les emplacements non dangereux seulement.
• Substitution of any component may impair suitability for Class I, Division 2.
+ –
The RJ45 Ethernet port connector bodies on the switch are metallic
and connected to the Chassis GND terminal. Therefore, shielded cables
may be used to provide further protection. To prevent ground loops, the
cable shield should be tied to the metal connector body at one end of the
cable only. Electrical isolation is also provided on the Ethernet ports for
increased reliability.
WARNING: The following information applies when operating this device in hazardous locations:
+ –
The switch provides connections to standard Ethernet devices such as
PLCs, Ethernet I/O, industrial computers and much more. Use dataquality (not voice-quality) twisted pair cable rated Cat5e (or better) with
standard RJ45 connectors. Straight-through or crossover RJ45 cable can
be used for all devices the switch is connected to as all the ports are
capable of auto-mdi/mdix-crossover detection.
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or nonhazardous
locations only.
• Do not disconnect equipment while the circuit is live or unless the area is known to be free of
ignitable concentrations.
Chassis
GND
(panel)
Communication Ports Wiring:
2
P1+ P1- P2+ P2-
2
www.AutomationDirect.com
1-800-633-0405
Installation – DIN Rail Mounting: