200 Series Mounting Base Options
200 Series
Mounting Base
Options
System Sensor mounting bases and kits provide a variety
of installation options for detectors in any application.
Features
• Bases enable quick and secure detector plug-in
• SEMS screws provide easy wiring connection
• Support for 12-24 AWG provides installation flexibility
• Multiple accessory options provide mounting flexibility
• Sounder bases are ULC listed as an audible signal appliance
To meet local code and application requirements, System Sensor offers relay, isolator, and sounder base options for
200 Series detectors. Relay bases provide one form C contact
relay for control of auxiliary functions, such as door closure and
elevator recall. Isolator bases allow loops to continue to operate
under fault conditions and automatically restore when the fault is
removed. Sounder bases are available in a combination temporal 3
and continuous tone model (B200SRA) or an addressable model
(B200SA) that can be activated by the fire alarm control panel based
on the event.†
200 Series Bases provide a variety of mounting options to meet your
installation challenges. Bases come in flanged or flangless versions
for mounting to a variety of junction boxes. See the 200 Series
Junction Box Selection Guide on the next page for junction box
options. Surface mounting boxes are also available.
Agency Listings
Model
Listings
B501A
ULC, FM
B200SA
ULC, FM
B200SRA
ULC, FM
B210LPA
ULC, FM
B224RBA
ULC, FM
B224BIA
ULC, FM
Consult your fire alarm control panel manufacturer for compatibility
with the addressable model of the sounder base.
† Specifications – 200 Series Bases
Physical Specifications
Diameter
B501A: 104 mm (4.1"); B210LPA: 155 mm (6.1"); B224BIA, B224RBA, B200SRA, B200SA: 175 mm (6.875")
Wire Gauge
B224BIA, B224RBA, B200SRA, B200SA, B210LPA, B501A: 24 to 12 AWG
Temperature Range
0°C to 49°C (32°F to 120°F ); B501A, B210LPA: –20°C to 66°C (–4°F to 150°F )
Humidity Range
10% to 93% RH non-condensing
B224RBA/B224BIA Electrical Ratings
B200SRA/B200SA Electrical Ratings
Operating Voltage
15 to 32 VDC (powered by SLC)
External Supply Voltage 16 to 33 VDC (VFWR)
Standby Current
170/450 µA max.
Standby Current
500 µA max.
Set Time (B224RBA only)
Short Delay: 60 to 100 msec
Long Delay: 6 to 10 sec
Reset Time (B224RBA only) 20 msec max.
Relay Characteristics
2 coil latching relay
Sound Output
High Volume: Greater than 87 dBA,
(B224RBA only)
1 Form C contact
Low Volume: Greater than 85 dBA minimum
UL/ULC Rating: measured in a ULC anechoic room at 10
0.5 A @ 125 VAC feet, 24 Volts (in continuous tone)
0.9 A @ 125 VDC Alarm Current
35 mA max.
3 A @ 30 VDC
200 Series Junction Box Selection Guide
Model
Single
Gang
3.5"
Octagonal
4"
Octagonal
4"
Square
4"
Square*
50
mm
60
mm
70
mm
75
mm
B501A
No
Yes
No
No
Yes
Yes
Yes
Yes
No
B200SRA/B200SA
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
B210LPA
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
B224RBA
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
B224BIA
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
†
†
* with 3.0" mud ring
†
B200SA is not compatitble with the 200 Series junction boxes
Note: Box depth contingent on base and wire size. Refer to National Code or applicable local codes for appropriate recommendations.
Ordering Information, 200 Series Bases
Model
B501A
B200SRA
Description
4" Flangeless Mounting Base
Standard Sounder Base (Compatible with B501BHA Series)
B200SA
Intelligent Addressable Sounder Base
B210LPA
6" Flanged Mounting Base
B224RBA
Relay Base
B224BIA
Isolator Base
200 Series Accessories
SMB600
Surface Mounting Kit (flanged)
F110
Accessory Flange Ring for 6" Base
F210
Accessory New Smaller Flange Ring for 6” Base
RA100ZA
Remote LED Annunciator
M02-04-01
Detector Test Magnet
M02-09-00
Test Magnet with Telescoping Handle
XR2B
Detector Removal Tool (T55-127-000 included)
XP-4
Extension Pole for XR2B (5 to 15 ft.)
T55-127-000
Detector Removal Head
BCK-200B
Black Detector Kit
WCK-200B
White Detector Kit
B200SA Addressable Sounder Base
Product Overview
When used with compatible fire alarm control panels, the B200SA
sounder base provides unmatched flexibility to configure the output
to various events. When combined with System Sensor SpectrAlert®
Advance notification appliances, the B200SA can serve as a
component for general evacuation signaling, improving aesthetics
and reducing system costs.
Features:
• S
imple addressing scheme - base adopts the same address as
attached sensor
• Synchronizable with SpectrAlert Advance notification appliances
• Four standard tone patterns at two selectable volumes
• Custom tone capability
• Support for Temporal-4 CO annunciation
• Remote silence capability
6-6581 Kitimat Rd • Mississauga, ON L5N 3T5
Phone: 800-SENSOR2 • Fax: 905-812-0771
www.systemsensor.ca
©2012 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
CMDS00600-1 • 1/12