Kidde PI2010 User's Guide

Add to my manuals
16 Pages

advertisement

Kidde PI2010 User's Guide | Manualzz

PI2010 For model: PI2010

Smoke Alarm User’s Guide

AC Wire-in Single and/or Multiple Station (up to 24 Devices)

Photoelectric/Ionization Smoke Alarm with 9 Volt Battery

Back Up and “HUSH” Control to temporarily silence nuisance alarms.

Thank you for purchasing this smoke alarm. It is an important part of your family’s home safety plan. You can trust this product to provide the highest quality safety protection. We know you expect nothing less when the lives of your family are at stake. Kidde alarms and accessories

CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms. Connection of Kidde products to a non-specified manufacturer’s interconnect system, or connection with non-specified equipment from another manufacturer into an existing Kidde system could result in nuisance alarming, failure to alarm, or damage to one or all of the devices in the interconnect system. Refer to the User’s Guide supplied with each Kidde product for interconnect compatible models, brands, and devices. Refer to the wiring instructions in section 3 for NFPA initiating device limits.

For your convenience, write down the following information. If you call our Consumer Hotline, these are the first questions you will be asked.

Smoke Alarm Model Number

(located on back of alarm):

Date Code (located on back of alarm).

National Fire Protection Association

(NFPA) and the manufacturer recommends replacing this alarm ten years from the date code:

Date of Purchase:

Where Purchased:

820-0905 REV. D 06/09

1475-7205-00

The ion portion of this alarm detects products of combustion using the ionization technique. It contains 0.9 microcurie of Americium

241, a radioactive material (see section 9).Distributed under U.S.

NRC License No. 32-23858-01E. Manufactured in compliance with

U.S. NRC safety criteria in 10 CFR 32.27. The purchaser is exempt from any regulatory requirements. Do not try to repair the smoke alarm yourself. Refer to the instructions in section 12 for service.

WARNING! BATTERY DOOR WILL NOT CLOSE UNLESS A

BATTERY IS PRESENT. REMOVAL OF THE SMOKE ALARM

BATTERY AND DISCONNECTING OR LOSS OF AC POWER

WILL RENDER THE SMOKE ALARM INOPERATIVE.

ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm

(maximum 80mA for originating unit with 24 devices interconnected).

IMPORTANT! READ ALL INSTRUCTIONS BEFORE

INSTALLATION AND KEEP THIS MANUAL NEAR THE ALARM

FOR FUTURE REFERENCE.

CONTENTS OF THIS MANUAL

1 -- RECOMMENDED LOCATIONS FOR SMOKE ALARMS

2 -- LOCATIONS TO AVOID

3 -- INSTALLATION INSTRUCTIONS

4 -- OPERATION AND TESTING

5 -- NUISANCE ALARMS

6 -- MAINTENANCE

7 -- LIMITATIONS OF SMOKE ALARMS

8 -- GOOD SAFETY HABITS

9 -- NRC INFORMATION

10 -- NFPA PROTECTION STANDARD 72

11 -- CALIFORNIA STATE FIRE MARSHAL REQUIRED INFORMATION

11 -- SERVICE AND WARRANTY

1. RECOMMENDED LOCATIONS FOR ALARMS

• Locate the first alarm in the immediate area of the sleeping rooms.

Try to monitor the exit path as the sleeping rooms are usually farthest from the exit. If more than one sleeping area exists, locate additional alarms in each sleeping area (See figure 3).

• Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and heat.

• Locate at least one alarm on every floor level.

• Locate an alarm in every sleeping room.

• Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or humidifiers).

• Locate an alarm in every room where someone sleeps with the door closed.

The closed door may prevent an alarm not located in that room from waking the sleeper.

• Smoke, heat, and combustion products rise to the ceiling and spread horizontally.

Mounting the smoke alarm on the ceiling in the center of the room places it closest to all points in the room. Ceiling mounting is preferred in ordinary residential construction.

FIGURE 1

• For mobile home installation, select locations carefully to avoid thermal barriers that may form at the ceiling. For more details, see MOBILE HOME INSTALLATION below.

• When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see figure 1).

• Put smoke alarms at both ends of a hallway or large room if the hallway or room is more than 30 ft (9.1 m) long. For large rooms, one smoke alarm is recommended for every 500 square feet of floor space.

FIGURE 2

• In homes that are not well insulated, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may

FIGURE 3

ANYWHERE ALONG

THIS BOLD SURFACE

12”

(300mm) create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. If you are not sure about the insulation in your home,

FIGURE 4 or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. In such homes, install the smoke alarm with the top edge of the alarm

at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see figure 1).

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft (0.9m) of the highest point (measured horizontally). NFPA

72 states: “Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally shall be located on the high side of the room.” NFPA 72 states: “A row of detectors shall be spaced and located within 3 ft (0.9m) of the peak of the ceiling measured horizontally” (see figure 2).

• Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the highest portion of the ceiling or on the sloped portion of the ceiling within 12” (305mm) vertically down from the highest point (see figure 4).

Mobile Home Installation

Modern mobile homes have been designed and built to be energy efficient. Install smoke alarms as recommended above (refer to

RECOMMENDED LOCATIONS and Figures 1 and 2). In older mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 4” (10cm) and a maximum of 12” (30.5cm) below the ceiling (see figure 1).

If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection, install at least one alarm close to the sleeping rooms. For additional protection, see

SINGLE FLOOR PLAN in figure 2.

WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER

RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE,

BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING

USE.

2. LOCATIONS TO AVOID

• In the garage. Products of combustion are present when you start

• Less than 4” (10cm) from the peak of an “A” frame type ceiling.

• In an area where the temperature may fall below 40ºF or rise above

100ºF, such as garages and unfinished attics; this should also include electrical boxes exposed to these environments.

• In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.

• In very humid areas. Moisture or steam can cause nuisance alarms.

• In insect-infested areas.

• Smoke alarms should not be installed within 3 ft (.9m) of the following: the door to a kitchen, the door to a bathroom containing a tub or shower, forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air flow areas.

• Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence feature or be a photoelectric type.

• Near fluorescent lights. Electronic “noise” may cause nuisance alarms.

• Smoke alarms are not to be used with detector guards unless the combination (alarm and guard) has been evaluated and found suitable for that purpose.

3. INSTALLATION INSTRUCTIONS

WIRING REQUIREMENTS

• This smoke alarm should be installed on a U.L. listed or recognized junction box. All connections should be made by a qualified electrician and all wiring used shall be in accordance with articles 210 and 300.3(B) of the U.S. National Electrical Code

ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdiction in your area. The multiple station interconnect wiring to the alarms must be run in the same raceway or cable as the AC power wiring. In addition, the resistance of the interconnect wiring shall be a maximum of 10 ohms.

• The appropriate power source is 120 Volt AC Single Phase supplied from a non-switchable circuit which is not protected by a ground fault interrupter.

WARNING: This alarm cannot be operated from power derived from a square wave, modified square wave or modified sine wave inverter. These types of inverters are sometimes used to supply power to the structure in off grid installations, such as solar or wind derived power sources. These power sources produce high peak voltages that will damage the alarm.

WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS

CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT

BEFORE WIRING THE ALARM.

• For alarms that are used as single station, DO NOT CONNECT

THE RED WIRE TO ANYTHING. Leave the red wire insulating cap

in place to make certain that the red wire cannot contact any metal parts or the electrical box.

• When alarms are interconnected, all interconnected units must be powered from a single circuit.

• A maximum of 24 Kidde/Lifesaver devices may be interconnected in a multiple station arrangement. The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon monoxide, etc.). With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.

• When mixing models which have battery backup (Kidde models: 1275, 1276, 1285, 1296, i12040, i12060, i12080, i4618,

PE120, PI2000, PI2010, RF-SM-ACDC, KN-SM-FM-I, KN-COSM-

IB, HD135F, KN-COB-IC, KN-COP-IC, KN-COPF-I and FireX models: AD, ADC, FADC) with models without battery backup,

(Kidde models: 1235, i12020, KN-COSM-I, 120X, SM120X,

CO120X, SL177) be advised that the models without battery backup will not respond during an AC power failure.

• The maximum wire run distance between the first and last unit in an interconnected system is 1000 feet.

• Figure 4 illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to operate, or a shock hazard.

• Make certain alarms are wired to a continuous (non-switched) power line. NOTE: Use standard UL listed household wire (as required by local codes) available at all electrical supply stores and most hardware stores.

FIGURE 4 INTERCONNECT WIRING DIAGRAM

WIRES ON ALARM HARNESS CONNECTED TO

Black

White

Red

Hot Side of AC Line

Neutral Side of AC Line

Interconnect Lines (Red Wires) of

Other Units in the Multiple

BATTERY INSTALLATION

See Maintenance (section 6) for battery installation

CAUTION! IF BATTERY REMINDER FINGER IS NOT HELD

DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY,

THE BATTERY DOOR WILL NOT CLOSE, THE AC QUICK

CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE

ALARM WILL NOT ATTACH TO THE TRIM RING (SEE SECTION

6, FIGURE 8).

MOUNTING INSTRUCTIONS

CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT

REMOVABLE!

1. Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm in the direction indicated by the “OFF” arrow on the alarm cover.

2. After selecting the proper smoke alarm location as described in section 1 and wiring the AC QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to the electrical box (see figure 6).

3. Pull the AC QUICK CONNECTOR through the center hole in the trim ring and mount the ring, making sure that the mounting screws are positioned in the small ends of the keyholes before tightening the screws.

4. Plug the AC QUICK CONNECTOR into the back of the alarm

(see figure 5), making sure that the locks on the connector snap into place. Then push the excess wire back into the electrical box through the hole in the center of the trim ring.

5. If you have finished all the WIRING, BATTERY INSTALLATION

AND TRIM RING MOUNTING STEPS, you can install the alarm on the trim ring. Note: The alarm will mount to the trim ring in

4 positions (every 90 degrees).

6. Install the alarm on the trim ring and rotate the alarm in the direc-

tion of the “ON” arrow on the cover until the alarm ratchets into place (this ratcheting function allows for aesthetic alignment).

7. Turn on the AC power. The green AC Power On Indicator should be lit when the alarm is operating from AC power.

TAMPER RESIST FEATURE: To make your smoke alarm tamper

A

Posts

A

FIGURE 5

FIGURE 6

FIGURE 7 resistant, a tamper resist feature has been provided. Activate the tamper resist feature by breaking off the four posts in the square holes in the trim ring (see figure 6). When the posts are broken off, the tamper resist tab on the base is allowed to engage the mounting bracket. Rotate the alarm onto the trim ring until you hear the tamper resist tab snap into place, locking the alarm on the trim ring. Using the tamper resist feature will help deter children and others from removing the alarm from trim ring. NOTE:

To remove the alarm when the tamper resist tab is engaged, press down on the tamper resist tab, and rotate the alarm off of the trim ring (see figure 7).

After installation, TEST your alarm by pressing and holding the test button for several seconds. This should sound the alarm.

4. OPERATION AND TESTING

OPERATION: The smoke alarm is operating once AC power is applied, a fresh battery is installed and testing is complete. When products of combustion are sensed, the unit sounds a loud 85db pulsating alarm until the air is cleared.

HUSH CONTROL: The “HUSH” feature has the capability of temporarily desensitizing the alarm circuit for approximately 10 minutes. This feature is to be used only when a known alarm condition, such as smoke from cooking activates the alarm. The smoke alarm is desensitized by pushing the “HUSH” button on the smoke alarm cover. If the smoke is not too dense, the alarm will silence immediately and the red LED will flash every 10 seconds for approximately 10 minutes. This indicates that the alarm is in a temporarily desensitized condition. The smoke alarm will automatically reset after approximately 10 minutes, and sound the alarm if smoke is still present. The “HUSH” feature can be used repeatedly until the air has been cleared of the condition causing the alarm.

NOTE: DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL

FEATURE AND SOUND A CONTINUOUS ALARM.

CAUTION: BEFORE USING THE ALARM HUSH FEATURE,

IDENTIFY THE SOURCE OF THE SMOKE AND BE CERTAIN A

SAFE CONDITION EXISTS.

LED INDICATORS: This smoke alarm is equipped with red and green LED indicators. The red LED is located under the test button and has several modes of operation. The green LED is located under the “Hush” button and indicates the presence of AC power.

Standby Condition: The red LED will flash every approximately every 45 seconds to indicate that the smoke alarm is operating properly. The green LED will be steady on, indicating the presence of AC power.

Alarm Condition: When the alarm senses products of combustion and goes into alarm, the red LED will flash rapidly (once every second). The rapid flashing LED and temporal alarm will continue until the air is cleared.

Hush Condition: The red LED will flash every 10 seconds as long as the alarm is in Hush mode.

Low Battery Condition: The red LED flash will be accompanied by an audible chirp. Replace the battery when this condition occurs.

SMOKE SENSING CHAMBER OPERATION: This alarm will “chirp” if any of the components in the smoke sensing chamber fail. This chirp will occur between the flashes of the red LED indicator light.

(If the chirp occurs at the same time as the red LED flash, see section 6 for low battery information).

WHEN UNITS ARE INTERCONNECTED, only the red LED of the alarm “which senses the smoke” or “is being tested” (the originating unit) will flash rapidly. All other units in the interconnect system will sound an alarm but their red LED’s will NOT flash rapidly.

TESTING: Test by pushing the test button on the cover and hold it down for a minimum of 5 seconds. This will sound the alarm if the electronic circuitry and horn and battery are working. In an interconnected installation all interconnected alarms should sound when the test button on any one of the interconnected alarm is pressed. If no alarm sounds, the unit has defective batteries or other failure. DO NOT use an open flame to test your alarm, you could damage the alarm or ignite combustible materials and start a structure fire.

TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION.

Erratic or low sound coming from your alarm may indicate a defective alarm, and it should be returned for service (see section

12).

NOTE: WEEKLY TESTING IS REQUIRED.

5. NUISANCE ALARMS

Smoke alarms are designed to minimize nuisance alarms. Cigarette smoke will not normally set off the alarm, unless the smoke is blown directly into the alarm. Combustion particles from cooking may set off the alarm if the alarm is located close to the cooking area. Large quantities of combustible particles are generated from spills or when broiling. Using the fan on a range hood which vents to the outside (non-recirculating type) will also help remove these combustible products from the kitchen.

The Model PI2010 has a “HUSH” control that is extremely useful in a kitchen area or other areas prone to nuisance alarms. For

more information refer to section 4, OPERATION AND TESTING.

If the alarm does sound, check for fires first. If a fire is discovered, get out and call the fire department. If no fire is present, check to see if one of the reasons listed in section 2 may have caused the alarm.

6. MAINTENANCE

ALARM REMOVAL

IF TAMPER RESIST FEATURE HAS BEEN ACTIVATED, REFER TO

TAMPER RESIST FEATURE DESCRIPTION IN SECTION 3 FOR

PIN REMOVAL INSTRUCTIONS.

To replace the battery, remove the alarm from the trim ring by rotating the alarm in the direction of the “OFF” arrow on the cover. To disconnect the AC power harness, squeeze the locking arms on the sides of the Quick Connector while pulling the connector away from the bottom of the alarm (see section 3, figure 5).

BATTERY INSTALLATION AND REMOVAL

To replace or install the batteries you must first remove the alarm from the trim ring by following the ALARM REMOVAL instructions at the beginning of this section. After alarm has been removed, you can open the battery door and install or replace the battery.

Battery installation instructions are provided on the inside of the battery door.

When installing the battery, press the battery reminder finger down into the battery compartment and install the battery (see figure 5).

CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD

DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY,

THE BATTERY DOOR WILL NOT CLOSE, THE AC QUICK

CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE

ALARM WILL NOT ATTACH TO THE TRIM RING.

The Model PI2010 Smoke Alarm is powered by a 9V alkaline bat-

Battery

Reminder

Finger

FIGURE 8

tery (lithium batteries may also be used). A fresh battery should last for one year under normal operating conditions. This alarm has a low battery monitor circuit which will cause the alarm to

“chirp” approximately every 45 seconds for a minimum of seven

(7) days when the battery gets low. Replace the battery when this condition occurs.

USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE

ALARM REPLACEMENT.

Alkaline Type: ENERGIZER 522; DURACELL MN1604, MX1604,

GOLD PEAK 1604A PANASONIC 6AM6, 6AM-6,

6AM-6PI, 6AM6X, and 6LR61(GA)

Lithium Type: ULTRALIFE U9VL-J

After installing or changing the battery, reinstall your alarm. Test your alarm by using the test button and check that the green LED is on.

NOTE: WEEKLY TESTING IS REQUIRED.

CLEANING YOUR ALARM

YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR

To clean your alarm, remove it from the mounting bracket as outlined in the beginning of this section. You can clean the interior of your alarm (sensing chamber) by using compressed air or a vacuum cleaner hose and blowing or vacuuming through the openings around the perimeter of the alarm. The outside of the alarm can be wiped with a damp cloth. After cleaning, reinstall your alarm and test your alarm by using the test button and check that the green LED is on. If cleaning does not restore the alarm to normal operation the alarm should be replaced.

7. LIMITATIONS OF SMOKE ALARMS

WARNING: PLEASE READ CAREFULLY AND THOROUGHLY

• NFPA 72 states: Fire-warning equipment for residential occupancies are capable of protecting about half of the occupants in potentially fatal fires. Victims are often intimate with the fire, too old or too young, or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be possible. For these people, other strategies such as protection-in-place or assisted escape or rescue would be necessary.

• Smoke alarms are devices that can provide early warning of possible fires at a reasonable cost; however, alarms have sensing limitations. Ionization sensing alarms may detect invisible fire particles

(associated with fast flaming fires) sooner than photoelectric alarms.

Photoelectric sensing alarms may detect visible fire particles (associated with slow smoldering fires) sooner than ionization alarms. Home fires develop in different ways and are often unpredictable. For maximum protection, Kidde recommends that both Ionization and

Photoelectric alarms be installed.

• A battery powered alarm must have a battery of the specified type, in good condition and installed properly.

• AC powered alarms (without battery backup) will not operate if the

AC power has been cut off, such as by an electrical fire or an open fuse.

• Smoke alarms must be tested regularly to make sure the batteries and the alarm circuits are in good operating condition.

• Smoke alarms cannot provide an alarm if smoke does not reach the alarm. Therefore, smoke alarms may not sense fires starting in chimneys, walls, on roofs, on the other side of a closed door or on a different floor.

• If the alarm is located outside the sleeping room or on a different floor, it may not wake up a sound sleeper.

• The use of alcohol or drugs may also impair one’s ability to hear the smoke alarm. For maximum protection, a smoke alarm should be installed in each sleeping area on every level of a home.

• Although smoke alarms can help save lives by providing an early warning of a fire, they are not a substitute for an insurance policy.

Home owners and renters should have adequate insurance to protect their lives and property.

8. GOOD SAFETY HABITS

DEVELOP AND PRACTICE A PLAN OF ESCAPE

• Make a floor plan indicating all doors and windows and at least two

(2) escape routes from each room. Second story windows may need a rope or chain ladder.

• Have a family meeting and discuss your escape plan, showing everyone what to do in case of fire.

• Determine a place outside your home where you all can meet if a fire occurs.

• Familiarize everyone with the sound of the smoke alarm and train them to leave your home when they hear it

• Practice a fire drill at least every six months, including fire drills at night. Ensure that small children hear the alarm and wake when it sounds. They must wake up in order to execute the escape plan.

Practice allows all occupants to test your plan before an emergency.

You may not be able to reach your children. It is important they know what to do.

• Install and maintain fire extinguishers on every level of the home

and in the kitchen, basement and garage. Know how to use a fire extinguisher prior to an emergency.

• Current studies have shown smoke alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.

• There are situations where a smoke alarm may not be effective to protect against fire as noted by the NFPA and UL. For instance:

- Smoking in bed.

- Leaving children unsupervised.

- Cleaning with flammable liquids, such as gasoline.

- Fires where the victim is intimate with a flaming initiated fire; for example, when a person’s clothes catch fire while cooking.

- Fires where the smoke is prevented from reaching the detector due to a closed door or other obstruction.

- Incendiary fires where the fire grows so rapidly that an occupant’s egress is blocked even with properly located detectors.

9. NRC INFORMATION

The ionization portion of this smoke alarm uses a very small amount of a radioactive element in the sensing chamber to enable detection of visible and invisible combustion products. The radioactive element is safely contained in the chamber and requires no adjustments or maintenance. This smoke alarm meets or exceeds all government standards. It is manufactured and distributed under license from the U.S. Nuclear Regulatory Commission.

10. NFPA REQUIRED PROTECTION

The National Fire Protection Association’s Standard 72 provides the following information:

Smoke Detection - Where required by applicable laws, codes, or standards for the specified occupancy, approved single- and multiple-station smoke alarms shall be installed as follows: (1) In all sleeping rooms Exception: Smoke alarms shall not be required in sleeping rooms in existing one- and two-family dwelling units.

(2) Outside of each separate sleeping area, in immediate vicinity of the sleeping rooms. (3) On each level of the dwelling unit, including basements Exception: In existing one- and two-family dwelling units, approved smoke alarms powered by batteries are permitted.

Smoke Detection - Are More Smoke Alarms Desirable? The required number of smoke alarms might not provide reliable early

warning protection for those areas separated by a door from the areas protected by the required smoke alarms. For this reason, it is recommended that the householder consider the use of additional smoke alarms for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms. The installation of the smoke alarms in the kitchen, attic (finished or unfinished), or garage is normally not recommended, as these locations occasionally experience conditions that can result in improper operation.

This equipment should be installed in accordance with the

National Fire Protection Association’s Standard 72 (NFPA,

Batterymarch Park, Quincy, MA 02269).

NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE

COMPANY OF YOUR SMOKE ALARM INSTALLATION.

11. CAUTION (AS REQUIRED BY THE CALIFORNIA

STATE FIRE MARSHAL)

“Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows. A smoke alarm installed in each separate sleeping area (in the vicinity of, but outside of the bedrooms), and heat or smoke alarms in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages”.

12. SERVICE AND WARRANTY

If after reviewing this manual you feel that your smoke alarm is defective in any way, do not tamper with the unit. Return it for servicing to: KIDDE, 1016 Corporate Park Dr., Mebane, NC 27302.

1-800-880-6788 (See Warranty for in-warranty returns).

TEN YEAR LIMITED WARRANTY

Kidde warrants to the original purchaser that the enclosed smoke alarm

(but not the battery) will be free from defects in material and workmanship or design under normal use and service for a period of ten years from the date of purchase. The obligation of Kidde under this warranty is limited to repairing or replacing the smoke alarm or any part which we find to be defective in material, workmanship or design, free of charge to the customer, upon sending the smoke alarm with proof of date of purchase, postage and return postage prepaid, to Warranty Service

Department, Kidde, 1016 Corporate Park Dr., Mebane, NC 27302.

This warranty shall not apply to the smoke alarm if it has been damaged, modified, abused or altered after the date of purchase or if it fails to operate due to improper maintenance or inadequate AC or DC electrical power.

THE LIABILITY OF KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY

CORPORATIONS ARISING FROM THE SALE OF THIS SMOKE ALARM OR

UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY

CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND,

IN NO CASE, SHALL KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY

CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES

RESULTING FROM THE FAILURE OF THE SMOKE ALARM OR FOR BREACH

OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE

LOSS OR DAMAGE IS CAUSED BY THE COMPANY’S NEGLIGENCE OR

FAULT.

Since some states do not allow limitations on the duration of an implied warranty or do not allow the exclusion or limitation of incidental or consequential damages, the above limitations or exclusions may not apply to you. While this warranty gives you specific legal rights, you may also have other rights which vary from state to state.

Also, Kidde makes no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose, with respect to the battery.

The above warranty may not be altered except in writing signed by both parties hereto.

QUESTIONS OR FOR MORE INFORMATION

Call our Consumer Hotline at 1-800-880-6788 or contact us at our website at www.kidde.com

Kidde 1016 Corporate Park Drive, Mebane, NC 27302

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Frequently Answers and Questions

What is the power source for this smoke alarm?
The appropriate power source is 120 Volt AC Single Phase supplied from a non-switchable circuit which is not protected by a ground fault interrupter.
Can I use this smoke alarm with a detector guard?
Smoke alarms are not to be used with detector guards unless the combination (alarm and guard) has been evaluated and found suitable for that purpose.
What is the maximum number of devices that can be interconnected?
A maximum of 24 Kidde/Lifesaver devices may be interconnected in a multiple station arrangement.
What is the NFPA interconnect limit?
The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon monoxide, etc.).
How far should the smoke alarm be mounted from the ceiling?
When mounting the alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall.
Download PDF