IQlogic+
GB.TBIQ3.170815
Installation, IQlogic+, modules TBIQ-3
GOLD
1. General
The IQlogic+ is used for extra functions for which the
inputs and outputs are not included as standard in the air
handling unit’s control unit.
1
-
2
+
3
-
4
+
5
-
6
7
-
+
8
+
9 10 11 12
- S - S
2. Installation
3. Data
Connection port
2 x RJ 12 6/6
Supply voltage (Via modular contact) 24V DC
Relay contacts
2 A/AC3
5 A/AC1
Ambient temp.
normal
-40 °C - +55 °C, 10 - 95 % RH
Enclosure class
IP 20 to EN 60529
CE-approved to
EN 61000-6-2, EN 61000-6-3
Swegon reserves the right to alter specifications.
7 89A
IQlogic+
COM POWER
BCDE
P1
34 5 6
Function selector switch
0ReCO2, TBIQ-3-1
1 Coil heat exchangers, TBIQ-3-1 (- 2015)
2 Plate heat exchanger, TBIQ-3-1 (PX, Version E)
3 Plate heat exchanger, TBIQ-3-1 (PX, Version E2/F, Standard defrosting)
3 Plate heat exchanger, TBIQ-3-3 (PX, Version E2/F, RECOfrost defrosting)
3 External supervision, TBIQ-3-2
4Humidification, TBIQ-3-1
5 AQUA Link (see separate instructions), TBIQ-3-1
5 GOLD RX/HC (see separate instructions), TBIQ-3-2
6 External supervision, TBIQ-3-2
7 All Year Comfort (see separate instructions), TBIQ-3-2
8 Booster unit, TBIQ-3-2
9Preheating, TBIQ-3-2
A Xzone heating (see separate instr. TBLZ-1-50), TBIQ-3-2
External communication, I/O module no. A, TBIQ-3-1
B Xzone cooling (see separate instr. TBLZ-1-50), TBIQ-3-2
External communication, I/O module no. B, TBIQ-3-1
C Coil heat exchangers, TBIQ-3-2 (2016 -)
External communication, I/O module no. C, TBIQ-3-1
D Spare
E Extra control sequence 1 and Season Heating, TBIQ-3-2
F Extra control sequence 2, TBIQ-3-2
Function
selector
switch
C NO
13 14
F 012
Install the IQlogic+ at an appropriate place, for example at
an unoccupied spot on a DIN rail inside the air handling
unit’s electrical equipment cubicle .
Connect the communication cable, supplied with the unit,
to one of the connections on the module. It is not important which connection is used. The reason why there are
two connections is to make it possible to connect several
IQlogic+.
Connect the other end of the communication cable to one
of the connections of the control unit, marked COM (the
exact connection is specified under the relevant function).
Heat/Cool
C NO
15 16
Com 1
Com 2
+
- +
17 18 19 20
G G0
21 22
A TBIQ-3-2 is shown.
Terminal number
1 –*
0–10 V, OUT 1
2+
3 –*
0–10 V, OUT 2
4+
5 –*
0–10 V, IN 1
6+
7 –* 0–10 V, IN 2
8+
9–
Digital sensor 1
10s
11– Digital sensor 2
12s
13
14
15
16
17 → 18–
19 →
20 –
21+
22 –*
Relay 1
Relay 2
Digital, IN 1
Digital, IN 2
24 V AC input, for
Heat/Cool power supply
www.swegon.com
1
GB.TBIQ3.170815
Outdoor air damper/External damper
4. Function
4.1 ReCO2
GOLD Control unit
The function can be activated in the hand-held micro terminal of the GOLD unit or via a communication interface.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+module to one of the contacts in the air handling
unit's IQLogic control unit marked COM6-11.
28
*
30
1
-
If several damper actuators are used, they must
be connected in parallel.
Connection wire no. 9
must not be connected
in parallel, which means
3
-
4
+
5
-
6
7
-
S
8
S
IQlogic+
BCDE
P1
COM POWER
F 012
that only one actuator
can be monitored.
2
+
7 89A
The module controls the outdoor air dampers.
1 2 8 9
34 5 6
The IQlogic+ is used for the ReCO2 function (function selector switch set to position 0).
Com 1
C NO
9 10
Com 2
+
11 12
* The conductors for supplying 24 V AC power can be connected to
Terminals 28 (P) and 30 (G0) on the air handling unit control unit.
Applicable to size 100/120 GOLD units only:
If the total load on Terminals 28-30 is higher than 16 VA, use Terminals
201 (G) and 202 (G0). Terminals 201-202 can be loaded with a total of
max, 48 VA.
2
www.swegon.com
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
White
Yellow
Brown
Green
Valve actuator
4.2.1 CX, version E, fixed-speed controlled pump
(delivered before or during 2015)
The IQlogic+ is used for the coil heat exchanger function.
4
+
5
-
6
7
-
S
8
S
IQlogic+
7 89A
* Digital temperature
sensors require correct
polarity when you
connect them.
COM POWER
BCDE
P1
Com 1
Com 2
+
11 12
C NO
9 10
Circulation pump
Pump alarm
Brown
White
4.2.2 CX, version E/F, pressure controlled pump
(delivery during 2016/2017)
The IQlogic+ is used for the coil heat exchanger function.
White
Yellow
White
Yellow
Brown
Green
Valve
actuator
Temp.
sensor*
White
One IQlogic+ module is installed, as standard, in all GOLD
CX air handling units. The IQlogic+ module’s function
selector switch is set to position C.
1
-
2
+
3
-
4
+
5
-
6
+
7
-
8
+
9 10 11 12
- S - S
7 89A
2**
34 5 6
A limiting sensor is connected to the module. Readings
from the temperature sensor (insertion type) prevent the
water circulating through the extract air coil from reaching
such low temperatures that freezing is likely.
Pressure sensor
Yellow green
3**
1**
C NO
13 14
A pressure sensor measures the pressure in the liquid
circuit and ensures correct flow.
COM POWER
BCDE
P1
F 012
4**
IQlogic+
The module controls the circulation pump of the pipework
package and the valve actuator on the coil heat exchanger.
Cable for BUS communication is connected to any of
the contacts in the air handling unit IQlogic control unit
marked COM6-11.
3
-
204
Cable for BUS communication is connected to any of
the contacts in the air handling unit IQlogic control unit
marked COM6-11.
A manometer initiates an alarm in the event of low pressure.
2
+
Temp.
sensor*
F 012
A limiting sensor is connected to the module. Readings
from the temperature sensor (strap-on type) prevent the
water circulating through the extract air coil from reaching
such low temperatures that freezing is likely.
1
-
203
One IQlogic+ module is installed, as standard, in all GOLD
CX air handling units. The IQlogic+ module’s function
selector switch is set to position 1.
The module controls the circulation pump of the pipework
package and the valve actuator on the coil heat exchanger.
Brown
White
34 5 6
4.2 Coil heat exchanger
Heat/Cool
C NO
15 16
Black
Grey
Manometer
Com 1
+
- +
17 18 19 20
Com 2
G G0
21 22
Brown
Green
Circulation pump
* Digital temperature sensors require correct polarity when you connect
them.
** There are three cable variants. These variants depend on the brand of
pressure sensor.
HUBA and Grundfos brands have different coloured cables. For Siemens
each cable is numbered 1 - 3.
HUBA and Siemens brands are voltage fed with 24 VAC via the terminal
next to the IQlogic+-module, while Grundfos is voltage fed with 24 VDC
from the GOLD unit’s control card via the cable adapter.
HUBA
Siemens
Grundfos
1 = Brown
2 = Green
3 = White
-
1=1
2=2
3=3
-
2 = Light grey
4 = Black
NOTE! Check the make of pressure sensor carefully before connecting!
Swegon reserves the right to alter specifications.
www.swegon.com
3
GB.TBIQ3.170815
One IQlogic+ module is installed, as standard, in all GOLD
CX air handling units. The IQlogic+ module’s function
selector switch is set to position C.
Insertion-type
sensor*
Transformer
Dark blue
The module controls the circulation pump of the pipework
package and the valve actuator on the coil heat exchanger.
Dark blue
Dark blue
Black
Dark blue
4.2.3 CX, version F, pressure-controlled pump
(delivery starting autumn 2017)
The IQlogic+ is used for the coil heat exchanger function.
1
-
A limiting sensor is connected to the module. Readings
from the temperature sensor (insertion type) prevent the
water circulating through the extract air coil from reaching
such low temperatures that freezing is likely.
GND +24V B
A
A pressure sensor measures the pressure in the liquid
circuit and ensures correct flow.
U
G
G0
Y
U
G0
2
+
3
-
4
+
5
-
6
+
8
+
9 10 11 12
- S - S
IQlogic+
Y
Black
7 89A
COM POWER
BCDE
P1
F 012
Cable for BUS communication is connected to any of
the contacts in the air handling unit IQlogic control unit
marked COM6-11.
7
-
34 5 6
C NO
13 14
Heat/Cool
C NO
15 16
Com 1
+
- +
17 18 19 20
Com 2
G G0
21 22
Jumper
Circulation pump
Valve actuator
Pressure sensor
* Digital temperature sensors require
correct polarity when you connect them.
4
www.swegon.com
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
4.3 Plate heat exchanger
4.3.1 PX, Version E
(delivered as from week no. 46 of 2014)
IQlogic+ is used for the plate heat exchanger function.
Damper
actuator
Pink
Grey
Red
Black
One IQlogic+ module is installed, as standard, in all GOLD
PX air handling units. The IQlogic+ module’s function selector switch is set to position 2.
1
-
201
The module controls the by-pass and shut-off damper
actuators on the plate heat exchanger.
3
-
4
+
5
-
6
7
-
S
IQlogic+
7 89A
* Digital temperature sensors require
correct polarity. Be
careful when you
wire the conductors.
COM POWER
BCDE
P1
34 5 6
Com 1
Com 2
+
11 12
C NO
9 10
Damper
actuator
Pink
Grey
Black
Red
One IQlogic+ module is installed, as standard, in all GOLD
PX air handling units. The IQlogic+ module’s function
selector switch is set to position 3.
1
-
202
2
+
3
-
4
+
5
-
6
7
-
S
8
S
201
The module controls the by-pass and shut-off damper
actuators on the plate heat exchanger.
IQlogic+
7 89A
COM POWER
BCDE
P1
F 012
Cable for BUS communication is connected to any of
the contacts in the air handling unit IQlogic control unit
marked COM6-11.
34 5 6
Com 1
Com 2
+
11 12
C NO
9 10
4.3.3 PX, Version E2/F, RECOfrost defrosting
(delivered as from week no. 47 of 2014)
IQlogic+ is used for the plate heat exchanger function with
the RECOfrost defrosting function.
Grey Damper
Pink actuator
Black
Red
Grey Damper
Pink actuator
Black
Red
One IQlogic+ module is installed, as standard, in all GOLD
PX air handling units. The IQlogic+ module's function
selector switch P1 is set to position 3.
Grey Damper
Pink actuator
Black
Red
The module controls the by-pass and shut-off damper
actuators on the plate heat exchanger.
1
-
2
+
3
-
4
+
5
-
6
+
7
-
8
9 10 11 12
- + - +
+
13 14 15 16
- + - +
17 18 19 20
- S - S
21 22 23 24
- S - S
201
202
34 5 6
C NO
27 28
C NO
29 30
C NO
31 32
C NO
33 34
COM POWER
BCDE
P2
F 012
C NO
25 26
7 89A
BCDE
P1
F 012
7 89A
IQlogic+
34 5 6
Cable for BUS communication is connected to any of
the contacts in the air handling unit IQlogic control unit
marked COM6-11.
8
S
202
The cable for BUS communication is connected to one
of the ports in the air handling unit’s IQlogic control unit
marked COM6-11.
4.3.2 PX, Version E2/F, Standard defrosting
(delivered as from week no. 47 of 2014)
IQlogic+ is used for the plate heat exchanger function with
the Standard defrosting function.
2
+
F 012
Two limiting sensors are connected to the module. Readings from the temperature sensor (strap-on type) prevent
the foil, in the extract air passages of the heat exchanger
cube, from reaching such low temperatures that freezing
is likely.
Temp.
Brown sensor 2*
White
Brown
White
Temp.
sensor 1*
+ 35 36
+ 37 38
Com 1
+ 39 40
Com 2
+ 41 42
+ 43 44
P1
Swegon reserves the right to alter specifications.
www.swegon.com
5
GB.TBIQ3.170815
4.4 External monitoring
4.4.1 External operation
IQlogic+ is used for external monitoring by means of analogue and digital signals (function selector switch set to
position 3 and/or 6) in cases when communication with
the air handling unit cannot be used. The module can for
example be used if the air handling unit will be controlled/
monitored via a microprocessor substation or a PLC system. The function is activated in the air handling unit's
terminal or via a communications interface.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
Dig. output 1Closes between terminals 13 and 14
when the control system, in the terminal,
indicates Selected function*, active.
Factory-preset function:
Inactive.
Dig. output 2Closes between terminals 15 and 16
when the control system, in the terminal,
indicates Selected function*, active.
Factory-preset function:
Inactive.
* Indication is obtainable for two of the functions
below:
All GOLD
AHU in operation/AHU in automatic operation/ AHU
in manual operation/AHU in low speed mode/AHU
in high speed mode/A-alarm/B-alarm/Damper relay/
Heat exchanger/Heat exchanger, defrosting/Re-heat/
Re-heat capacity reduction/Heating Boost/Morning
Boost/Intermittent night operation/Airflow, down
regulation/Extra regulation sequence 1/2, heating/
Extra regulation sequence 1/2, cooling/Cooling/
Cooling Boost/Summer night cool/ Supply air fan in
operation/Extract air fan in operation Internal fire
alarm/External fire alarm 1/External fire alarm 2/
External fire alarm 1 or 2/Any fire alarm/External
fire alarm 1 with priority/External fire alarm 2 with
priority//Internal fire alarm tripped with priority/
Preheating
Dig. input 1To be connected to terminals 17 and 18.
The following can be selected via the
hand-held terminal:
- Alarm resetting. Resets possible alarms on
closure.
- Stop AYC heated water Blocks heated
water regulation and pump operation
when the input is interrupted.
- Stop AYC chilled water Blocks chilled
water regulation and pump operation
when the input is interrupted.
Factory-preset function: Inactive.
6
www.swegon.com
Dig. input 2 To be connected to terminals 19 and 20.
The following can be selected via the hand-held terminal:
- Alarm resetting. Resets possible alarms on
closure.
- Stop AYC heated water Blocks heated
water regulation and pump operation
when the input is interrupted.
- Stop AYC chilled water Blocks chilled
water regulation and pump operation
when the input is interrupted.
Factory-preset function: Inactive.
Digital sensor 1 Spare
Digital sensor 2 Spare
Analog
output 1
Indicates present supply airflow, from
0 to air handling unit’s max. speed (%).
Connect to Terminals 1 (-) and 2 (+).
Analog
output 2
Indicates present extract airflow, from
0 to air handling unit’s max. speed (%).
Connect to Terminals 3 (-) and 4 (+).
Analog. input 1 Connect to Terminals 5 (-) and 6 (+).
The following selection can be made via the hand-held micro terminal:
- Set point displacement (temperature).
- Set point displacement, supply air (flow).
- Set point displacement, extract air (flow).
Factory-preset function:
Inactive.
Analog. input 2 Connect to Terminals 7 (-) and 8 (+).
The following selection can be made via the hand-held micro terminal:
- Set point displacement (temperature).
- Set point displacement, supply air (flow).
- Set point displacement, extract air (flow).
Factory-preset function:
Inactive.
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
4.4.2 External BMS, I/O-module
IQlogic+ modules for external communication can be used
by the monitoring system (BMS), when several inputs/
outputs are required and no microprocessor substation is
installed in the fan room.
The IQlogic+ modules are controlled completely separately
by BMS and do not affect the GOLD unit's internal control
system.
Swegon reserves the right to alter specifications.
3
-
4
+
5
-
6
7
-
S
8
S
7 89A
IQlogic+
BCDE
P1
34 5 6
The outputs of the module(s) can be viewed and the
outputs can be controlled externally via communication
protocol (see the relevant protocol for BACnet, Modbus
and Exoline). All the inputs/outputs can also be viewed in
the GOLD unit's hand-held terminal and, if required, all
the outputs can be controlled from the test menu.
The function can be activated in the AHU's hand-held
terminal or via a communication interface.
Connect the cable for BUS communication between the
IQlogic+ module and the air handling unit's IQlogic control
unit, from an optional COM1 or COM2 contact on the
IQlogic+ module to one of the contacts in the air handling
unit's IQlogic control unit marked COM1-3.
2
+
COM POWER
F 012
Requires Program Version 1.20 or a later version.
Up to three IQlogic+modules (TBIQ-3-1) can be used (function selector switch set to position A, B or C).
There are one AI, one AO, one DI, one DO and two inputs
for temperature sensor on every IQlogic+ module. The
temperature sensor should be of Swegon manufacture.
These are available as insertion-type sensors, strap-on sensors and duct sensors.
1
-
Com 1
C NO
9 10
Com 2
+
11 12
Function selector switch. Position A, B or C.
Wiring terminal number
1 –
0–10 V, OUT
2+
3 –
0-10 V, IN
4+
5–
Digital sensor 1
6s
7– Digital sensor 2
8s
9
Relay
10
11 → Digital, IN
12–
www.swegon.com
7
GB.TBIQ3.170815
4.5 Humidification
Steam humidifier
The IQlogic+ is used for the steam humidifier function
(function selector switch set to position 4).
1
-
Select Humidification in the air handling unit’s hand-held
micro terminal or via a communication interface.
The relay output is used for controlling the steam humidifier, on/off.
Digital input can be used for external alarms. Select normally open or normally closed contact function in the AHU
hand-held micro terminal.
Use the analogue output for variably modulating 0 – 10 V
to the steam humidifier.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
2
+
3
-
4
+
5
-
6
7
-
S
8
S
BCDE
P1
COM POWER
F 012
7 89A
IQlogic+
34 5 6
Com 1
Com 2
+
11 12
C NO
9 10
Start Stop*
Alarms**
+ 0-10 V In
Steam humidifier (not Swegon)
* Normally-open contact starts the humidifier.
** Select the normally-open contact function in the AHU hand-held
micro terminal.
Evaporative humidification
The IQlogic+ is used for the evaporative humidification
function (function selector switch set to position 4).
Select Humidification in the air handling unit’s hand-held
micro terminal or via a communication interface.
The relay output is used for controlling the humidifier’s
solenoid valve or circulation pump, on/off.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
1
-
2
+
3
-
4
+
5
-
6
7
-
S
8
S
BCDE
P1
COM POWER
F 012
7 89A
IQlogic+
34 5 6
Com 1
C NO
9 10
Com 2
+
11 12
Supply voltage
Solenoid valve or circulation
pump, evaporative humidifier
(not Swegon)
8
www.swegon.com
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
4.6 AQUA Link
1
-
2
+
3
-
4
+
5
-
6
7
-
S
8
S
7 89A
IQlogic+
COM POWER
BCDE
P1
F 012
34 5 6
The IQlogic+ is used for the AQUA Link function (function
selector switch set to position 5).
Select AQUA Link in the air handling unit’s hand-held
micro terminal or via a communication interface.
The relay output is used for controlling the circulation
pump.
The digital input can be used for external alarms. Select
normally open, normally closed or contactor function in
the AHU’s hand-held micro terminal or via a communication interface.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
Com 1
Com 2
+
11 12
C NO
9 10
Circulation pump
Pump alarm
4.7 All Year Comfort
2
+
3
-
4
+
5
-
6
+
7
-
8
+
9 10 11 12
- S - S
7 89A
IQlogic+
COM POWER
BCDE
P1
C NO
13 14
F 012
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
1
-
34 5 6
The IQlogic+ is used for the All Year Comfort function
(function selector switch set to position 7).
See the Guide to the All Year Comfort Functions and
Installation of the TBLZ-2-59 control box.
Heat/Cool
C NO
15 16
Com 1
4.8 Booster unit
The IQlogic+ is used for the Booster unit function (function
selector switch set to position 8), where type BOOSTER
displacement units with damper motor are used. Relay 1
on the module is energised when the supply air temperature is higher than the room temperature, relay 2 operates
inversely compared to Relay 1, i.e. that when relay 1 is
energised Relay 2 is de-energised and vice versa.
Com 2
+
- +
17 18 19 20
G G0
21 22
G 24 VAC
G0
Swegon
MM ASM115SF901
01
02
Actuator for
BOOSTER
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
Swegon reserves the right to alter specifications.
www.swegon.com
9
GB.TBIQ3.170815
4.9 Preheating
The anti-frost sensor (if required) for the water air heater is
equipped with RJ 45 connector.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
The IQlogic is used for the preheating function (function
selector switch set to position 9).
The function can be activated in the hand-held micro terminal of the GOLD unit or via a communication interface.
The module controls the air heater for water or the electric
air heater.
To wire the TBLA/TCLA air heater, water, for the
GOLD, or electric air heater of a type other than
Swegon standard
The valve actuator is fitted with a quick-fit connector on
the control cable.
Wire the circulation pump cable, if required, to the relay
output.
+
1
-
3
-
5
-
6
+
R1
RD
7
-
8
+
T1
GR
9 10 11 12
- S - S
7 89A
IQlogic+
COM POWER
BCDE
P1
34 5 6
C NO
13 14
Control of the circulation pump
4
+
Jack for wall
mounting, 019611
F 012
The following applies to the size 100/120 GOLD
units only:
If the total load on Terminals 31-32 is higher
than 16 VA, then Terminals 201 (G) and 202
(G0) must be used. Terminals 201-202 can be
loaded with a total of max. 48 VA.
* Digital temperature sensors require correct
polarity when you connect them.
2
+
Temp. sensor*
for pre-heat
Heat/Cool
C NO
15 16
Com 1
+
- +
17 18 19 20
Com 2
G G0
21 22
32 (G0) IQlogic control unit
31 (G) IQlogic control unit
Pump alarm
(Requires GOLD program version 1.10 or a later version)
Blue
Orange
Black
Red
Green
Yellow
Brown
White or
Resistor/air heater/air cooler type, 2.2 kΩ
Brown
Insertion-type/strap-on sensor
White
0-10 V DC output signal
0-10 V DC control signal
G0 24 V AC
Valve actuator
G 24 V AC
grey
10
www.swegon.com
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
To wire a standard air heater for the GOLD, TBLE/
TCLE
The control cable of the standard, type TBLE/TCLE coils are
fitted with a quick-fit connector.
Connect the cable for BUS communication between the
IQLogic+ module and the air handling unit's IQLogic control unit, from an optional COM1 or COM2 contact on the
IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
Temp. sensor,* for preheated air
Jack for wall
mounting, 019611
Electric
air heater
Swegon
Standard
with 8-pin
control cable
1
-
2
+
3
-
4
+
5
-
6
+
7
-
8
+
9 10 11 12
- S - S
IQlogic+
COM POWER
BCDE
P1
34 5 6
C NO
13 14
F 012
7 89A
Applicable to size 100/120 GOLD units
only:
If the total load on Terminals 31-32 is
higher than 16 VA, use Terminals 201
(G) and 202 (G0). Terminals 201-202
can be loaded with a total of max, 48
VA.
* Digital temperature sensors require
correct polarity. Be careful when you
wire the conductors.
T1
GR
R1
RD
Heat/Cool
C NO
15 16
Com 1
Com 2
+
- +
17 18 19 20
G G0
21 22
32 (G0) IQlogic control unit
31 (G) IQlogic control unit
Swegon reserves the right to alter specifications.
www.swegon.com
11
GB.TBIQ3.170815
4.10 Extra control sequence and Season
Heating
The valve actuator is fitted with a quick-fit connector on the
control cable.
Wire the circulation pump cable, if required, to the relay output.
The IQlogic+ is used for the extra control sequence 1 and Season
Heating (function selector switch set to position E) and for the
extra control sequence 2 (function selector switch set to position
F). Used also as a regulation output to SMART Link
The anti-frost sensor (if required) for the water air heater is
equipped with RJ 45 connector.
Connect the cable for BUS communication between the IQLogic+
module and the air handling unit's IQLogic control unit, from
an optional COM1 or COM2 contact on the IQLogic+ module to
one of the contacts in the air handling unit's IQLogic control unit
marked COM1-3.
The function can be activated in the hand-held micro terminal of
the GOLD unit or via a communication interface.
The module controls the air heater/air cooler for water or the
electric air heater.
To wire the TBLA/TCLA/TBKA/TCKA air heater/air cooler,
water, for the GOLD, or electric air heater of a type other
than Swegon standard
The connection applies when both extra regulation sequence
and Season Heating are in use.
1
-
2
+
The following applies to the size 100/120
GOLD units only:
If the total load on Terminals 31-32 is higher
than 16 VA, then Terminals 201 (G) and 202
(G0) must be used. Terminals 201-202 can
be loaded with a total of max. 48 VA.
3
-
4
+
5
-
6
+
7
-
8
9 10 11 12
- S - S
+
COM POWER
BCDE
P1
34 5 6
C NO
13 14
F 012
7 89A
IQlogic+
Heat/Cool
C NO
15 16
Control of the circulation pump
When the Season Heating function is activated.
Optional normally open/normally closed contact.
Com 1
+
- +
17 18 19 20
Com 2
G G0
21 22
32 (G0) IQlogic control unit
31 (G) IQlogic control unit
Pump alarm
(Requires GOLD program version 1.10 or a later version)
Blue
Orange
Black
Red
Green
Yellow
Brown
White or
Resistor/air heater/air cooler type, 2.2 kΩ
Brown
Insertion-type/strap-on sensor
White
0-10 V DC output signal
0-10 V DC control signal
Valve actuator
G0 24 V AC
G 24 V AC
grey
12
www.swegon.com
Swegon reserves the right to alter specifications.
GB.TBIQ3.170815
To wire a standard air heater for the GOLD, TBLE/TCLE
The connection applies when both extra regulation sequence and Season
Heating are in use.
The control cable of the standard, type TBLE/TCLE coils are fitted with a quickfit connector.
Connect the cable for BUS communication between the IQLogic+ module and
the air handling unit's IQLogic control unit, from an optional COM1 or COM2
contact on the IQLogic+ module to one of the contacts in the air handling
unit's IQLogic control unit marked COM1-3.
Electric
air heater
Swegon
Standard
with 8-pin
control cable
Applicable to size 100/120 GOLD
units only:
If the total load on Terminals 58-59
and 60-61 is higher than 16 VA,
use Terminals 201 (G) and 202 (G0).
Terminals 201-202 can be loaded with
a total of max, 48 VA.
1
-
2
+
3
-
4
+
5
-
6
+
7
-
8
+
9 10 11 12
-
S
-
S
COM POWER
BCDE
P1
F 012
7 89A
IQlogic+
34 5 6
C NO
13 14
Heat/Cool
C NO
15 16
When the Season Heating
function is activated.
Optional normally open/
normally closed contact.
Com 1
Com 2
+
- +
17 18 19 20
G G0
21 22
32 (G0) IQlogic control unit
31 (G) IQlogic control unit
Connection for GOLD SD and TBBD mixing section
Applies only if extra regulation sequence is in use.
See separate instructions for the TBBD mixing section.
Swegon reserves the right to alter specifications.
www.swegon.com
13
GB.TBIQ3.170815
14
www.swegon.com
Swegon reserves the right to alter specifications.