PROCESSCONTROL | TABLEOFCONTENTS

PROCESSCONTROL | TABLEOFCONTENTS
339_Layout 1 7/8/14 11:36 AM Page 339
Panel Meters/
Indicators
pages 342-349, 352-353
Control Enclosures
pages 350-351
Annunciators/
Alarm Modules
page 354
Signal Conditioners/
Isolating Transmitters
page 355
Relays
pages 356-361
Current Transformers/
Switches
pages 362-365
Signal Converters
page 366
Power Supplies
pages 367-368
Power Supplies/
Transformers
page 369
Fan Speed
Controls
page 370
Intrinsically Safe
Barriers
pages 371-372
Timers
page 373
Timer Controllers
pages 374-377
Time Delay Relays
page 378
Ground/Continuity
Controls
page 379
Particulate (Dust or
Broken Bag)
Transmitters/Sensors
pages 380-382
Vibration Controls
page 383
Conveyor Controls
page 384
Data Loggers,
Indicating
pages 385-386
Data Loggers,
Miniature
page 387
Data Loggers,
Wireless
pages 388-389
Data Loggers,
USB
pages 390-391
Chart Recorders
page 392
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
PROCESSCONTROL | TABLEOFCONTENTS
TYPICAL
APPLICATIONS
pages 340-341
339
Typical Applications
PROCESS CONTROL
340_Layout 1 7/8/14 11:35 AM Page 340
Monitor the test environment for accurate laboratory tests.
The Love Controls® Model LCR20 dual pen circular chart recorder can be used to
monitor the humidity and temperature in an environmental chamber. The 10Ž chart
size makes it easy to see the blue and red pen markings on the chart paper. The
recorder takes in most common thermocouples and process inputs for both channels.
It is recommended that the LCR20 be used with a Dwyer® RHP series humidity /
temperature transmitter for best results.
Dust Collector Timer Controller shows filter condition in dust
collector.
This portable dust collector can be rolled from job to job in an industrial building. An
operator places the large diameter collection hose where it is needed and dust is
collected by filters located inside the access doors on the units side. The top mounted
blower draws air through the filters. To monitor the pressure drop across the filters,
the manufacturer supplies a Magnehelic® differential pressure gage. When the
pressure drop due to dust build up on the filter indicates that cleaning is necessary,
the DCT500A Dust Collector Timer Controller is manually activated to initiate a
cleaning cycle which involves solenoid valves releasing pulses of air. This process
removes the dust from the filters where it drops into a storage bin. A Dwyer® Minihelic®
differential pressure gage can be used instead of the Magnehelic® gage, and, if
automatic cleaning is required, a Photohelic® differential pressure switch/gage can
provide the electrical contact to actuate the cleaning cycle when the pressure drop
reaches the preset limit.
Button Datalogger monitors food and beverage temperature in
refrigerated transport vehicles.
Bag house cleaning system uses Dust Collector Timer Controller to
initiate optimum cleaning cycle.
When transporting temperature-sensitive products such as meat, produce, beer and
wine over long distances, it is necessary to verify that the storage compartment has
not exceeded the critical preservation temperature at any time. Dwyer® BDL Button
Dataloggers offer a low cost way to measure and record storage temperatures
throughout transport. By placing several •buttonsŽ throughout the storage
compartment and setting an appropriate measurement interval, transportation
services can retrieve data at the completion of delivery to assure their customers of
adequate preservation temperatures.
A Dwyer® DCT1000 Dust Collector Timer Controller with attachable DCP pressure
sensing module monitors and controls the dust levels and corresponding pressure
drop across the filter bags. The DCT1000/DCP control automatically activates the
cleaning cycle when the DCT1000's pre-programmed set points have been exceeded.
This on-demand control system alleviates excessive air compressor usage by
preventing unnecessary cleaning which lowers energy and maintenance costs.
340
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
341_Layout 1 7/8/14 11:34 AM Page 341
PROCESS CONTROL
Typical Applications
Detect broken filters in dust collectors.
Monitoring belt conveyor for proper operation.
The Dwyer® Series DPM Particulate Monitor and PMS Particulate Sensor combine
to make a particulate monitoring system for the exhaust stream of dust collectors.
The amount of particulate leaking out of the dust collector is measured using low
maintenance induction technology and shown on a display for easy viewing. The DPM
has programmable thresholds of leakage for switch output indication of dust collector
problems such as broken or leaking filters. Proper use of the system will allow the
user to catch breaking filters early. Advantages of the system are maintaining
regulatory compliance, maximizing product recovery, optimizing filtration efficiency,
preventing fines and plant shutdowns, and reducing the amount of pollutants
released.
A Proximity’ Series NSS Speed Switch is used to monitor the speed of a product
belt conveyor indicating proper operation. Common applications include grain, feed,
aggregate, mining, and textiles. Belt slippage or a slowdown in belt speed indicates
problems that could lead to product waste or could generate sparks leading to a fire
or explosion. The belt•s speed is monitored via the rotational speed of the shaft at the
end of the belt. The NSS is a non-contact magnetic actuated system allowing easy
installation and long operational life. A magnetic disc is installed on the rotating shaft
and the sensor is mounted across from it. The sensor picks up the rotation of the disc
to detect the rotational speed of the belt. Inside the sensor is a programmable switch
that can be set for any speed. In this application as the speed decreases and hits the
set point the switch is activated for indication of a problem. Proper usage of an NSS
can help with predictive maintenance and decrease down-time.
Providing remote indication of pressure, humidity or temperature.
Monitor the status of your fan or pump.
The Series DPML, DPMP and DPMW Digital LCDPanel Meters provide remote
indication in the designated engineering units for pressure, humidity and temperature
measurements. The panel meters can take in a voltage or current input signal from
transmitters such as the Dwyer Series TTE, Series 626 or Series RHP.The jumper
selection allows the user to choose the appropriate engineering units.
The Dwyer Series SCS Current Switches monitor the input current into a fan or pump
motor starter in order to monitor the status of the equipment. As the current passes
through the core of the switches, it generates enough energy to power up the switch
eliminating the need for extra power wires. The solid core models are typically used
on new installations, while the split core models are able to mount on existing or new
installations.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
341
PROCESS CONTROL
342_Layout 1 7/8/14 11:33 AM Page 342
Series
SPPM
Smart Programmable Panel Meter
Fully Field Configurable, 16-Bit Color Touch Screen Display
RoHS
1/2 [12.45]
3 [76.45]
2-3/8
[60.44]
1-29/32
[48.26]
SMART PROGRAMMABLE PANEL METER
15/16
[23.62]
(COUNTRY OF ORIGIN)
DATE CODE
9/32
[7.11]
1/16
[1.52]
21/32
[16.51]
23/32
[18.29]
Panel Meters/
Indicators
1-11/16
[42.55]
SPPM-24 and SPPM-24-C
3-17/32
[89.51]
3-1/2
[89.10]
2-9/32
[57.60]
1/4
[6.71]
29/32 [23.40]
19/32
[15.20]
1-11/16
[43.22]
2-1/4
[56.80]
3/16
[5.07]
3/4
[19.06]
9/16
1-3/8
[14.00]
5/16 [35.12]
[7.70]
3-5/16
[84.10]
SPPM-28 and SPPM-28-C
3-3/32
[78.50]
29/32
[23.30]
The Series SPPM Smart Programmable Panel Meter is a configurable, full-color
touch-screen display that can be used in a variety of applications. Utilizing a USB
connection, the panel meter can be configured with downloadable software, using any
computer running Windows® based software. Available with either a 2.4˝, 2.8˝ or 3.5˝
screen that features remarkable graphics that can easily be customized to read and/or
graph pressure, temperature, humidity, gas concentration, or many other parameters. Up
to two transmitters or transducers can feed the panel meter’s user scalable inputs (voltage
models only).
Input
Voltage
Voltage
Voltage
Current
Current
Current
ACCESSORIES
A-SPPM-TC, Thermocouple Input Board
SPPM-CA, Mini USB to full USB cable
SPPM-HSG24, 2.4 Display Housing
SPPM-HSG28, 2.8 Display Housing
Additional configurations available via online software.
Sample Programmable Display Configurations
11/16
[17.80]
1/16
[1.90]
35
27/32
[21.26]
2-5/32
[55.01]
SPPM-35 and SPPM-35-C
Scan here
to watch
product video
2-1/8
[53.81]
5/8
[16.16]
SPPM-HSG
3-1/2
[88.85]
5/32 [3.90]
3/8 [9.80]
3-25/32
[96.00]
Description
Model
SPPM-24 Smart Programmable Panel Meter with 2.4 display
SPPM-28 Smart Programmable Panel Meter with 2.8 display
SPPM-35 Smart Programmable Panel Meter with 3.5 display
SPPM-24-C Smart Programmable Panel Meter with 2.4 display
SPPM-28-C Smart Programmable Panel Meter with 2.8 display
SPPM-35-C Smart Programmable Panel Meter with 3.5 display
19/32 [15.19]
SPPM SPECIFICATIONS
Inputs: Current: 0 to 50 mA, scalable
(factory set from 4 to 20 mA); Voltage:
0 to 40 VDC, scalable (factory set from
0 to 10 V).
Accuracy: 0.1%.
Resolution: 0.3 to 9.8 mV (depending
on input range).
Power Supply: 4 to 30 VDC max or
via USB.
Current Consumption: 190 mA max.
Display: 2.4, 2.8 or 3.5 TFT full color
touch screen.
Display Resolution: 320 x 240 pixels.
Sampling Rate: 3 samples/s.
Temperature Limits: 32 to 104°F (0 to
40°C).
Warm Up: 30 s.
Mounting: Panel mount.
Electrical Connection: Screw
terminals, pin connection, or USB.
Software Requirements: Compatible
with Windows® XP, Windows® 2000,
Windows® 7 and Windows Vista®.
Weight: 2.8 oz (79.4 g).
Approvals: CE, RoHS.
31/32
[24.81]
3/32
[2.70] 23/32
[17.95]
SPPM-HSG SPECIFICATIONS
Service: Indoor or outdoor.
Material: Painted aluminum or glass.
Enclosure Rating: NEMA 4X (IP66).
A-SPPM-TC SPECIFICATIONS
Probe Measurement Range:>K-type:
-328 to 2462°F (-200 to 1350°C); Jtype:-328 to 2174°F (-200 to 1190°C);
T-type:-328 to 734°F(-200 to 390°C).
Temperature Limits: 14 to 104°F (-10
to 40°C).
Resolution: 1.0°F(0.5°C).
Power Requirements: Powered by
USBport through SPPM panel meter.
Accuracy: ±2.0°F(±1.0°C).
Weight: 0.9 oz (25.5 g).
Agency Approvals: RoHS.
Windows® and Windows Vista® are registered trademarks of Microsoft Corporation
342
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
343_Layout 1 7/8/14 11:33 AM Page 343
LCD Digital Panel Meters
1/8 DIN, Loop Powered, Large 3-1/2 Digit Display
RoHS
P Models
V
A
KW
PF
3-25/32
[96]
°F
°C
PSI
%
1-1/8
[28.5]
13/64
[5]
Model
DPMA-401
DPMA-402
DPMA-404
DPMA-501
DPMA-502
DPMA-504
DPMA-401P
DPMA-402P
DPMA-404P
DPMA-501P
DPMA-502P
DPMA-504P
Input
Current
Current
Current
Voltage
Voltage
Voltage
Current
Current
Current
Voltage
Voltage
Voltage
Segments
Amber Segments
Red Segments
Green Segments
Amber Segments
Red Segments
Green Segments
Amber Segments
Red Segments
Green Segments
Amber Segments
Red Segments
Green Segments
Engineering Units
°F, °C, %, PSI
5/64
[1.9]
MOUNTING BRACKET
OUTLINE REAR VIEW
4-29/64
[113]
(R.010 MAX)
4 PLCS [.25 mm]
SPECIFICATIONS
Input: DPMA-4XX(P): 4 to 20 mA;
DPMA-5XX(P): 0 to 200 mVDC, 0 to 5
VDC or 0 to 10 VDC.
Input Impedance: DPMA-4XX(P):
300 nominal; DPMA-5XX(P): 390K
nominal.
Accuracy: ±(0.05% FS + 1 count).
Power Supply: DPMA-4XX(P):
Powered by control loop; DPMA5XX(P): 12 VDCor 24 VDC.
BacklightPower Supply: 24 VDC @
35 mA typical.
Span and Zero: Adjustable. (±1999
counts).
Display: 3-1/2 digits, 7 segments,
1 (25.4 mm) H.
Decimal Points: 3-position, user
selectable.
Engineering Units: DPMA-XXX: °F,
°C, %, psi; DPMA-XXXP: V, A, KW, PF.
Polarity: Automatic, •-Ž displayed.
Operating Temperature: 32 to 122°F
(0 to 50°C).
Storage Temperature: -4 to 158°F
(-20 to 70°C).
Mounting: Snap-in panel mount or
clamp (gasket included).
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 4 oz (113.4 g).
Agency Approvals: RoHS.
V, A, KW, PF
APPLICATIONS
Used to display process values from pressure, humidity, temperature, voltage,
current, watt, or power factor transmitters.
ACCESSORIES
DPM-12P, Regulated 120 VAC to 12 VDC Power Supply
DPM-24P, Regulated 120 VAC to 24 VDC Power Supply
Series
DPMW
LCD Digital Panel Meters
3-1/2 Digits, Window Mount
17/64
[6.9]
RoHS
P Models
V
A
KW
PF
2-3/8
[60.5]
°F
°C
PSI
%
[Ø.140]
[Ø3.6 mm]
2 PLCS
The Series DPMW LCD Digital Panel Meter is designed with a 3-1/2 digit, highcontrast LCD display. The colored segments are available in red, amber, or green - ideal
for viewing at a distance. The Series DPMW features user selectable engineering units,
selectable decimal point position and adjustable span and zero. The meter accepts a 4 to
20 mA input signal from pressure, level, flow, temperature, voltage, current, watt, or power
factor transmitters. A 24 VDC power supply is required to illuminate the colored segments.
The Series DPMW can be quickly installed in a window cutout.
Model
DPMW-401
DPMW-402
DPMW-403
DPMW-401P
DPMW-402P
DPMW-403P
Segments
Amber Segments
Green Segments
Red Segments
Amber Segments
Green Segments
Red Segments
1-59/64
[49]
Engineering Units
°F, °C, %, PSI
V, A, KW, PF
ACCESSORY
DPM-24P, Regulated 120 VAC to 24 VDC Power Supply
1/8
[3]
2-5/16
[58.7]
PANEL CUTOUT FOR
WINDOW MOUNTING
13/32
[10.2]
SPECIFICATIONS
Input: 4 to 20 mA.
Input Impedance: 300 nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: Powered by control
loop.
Backlight Power Supply: 24 VDC@
35 mA typical.
Span and Zero: Adjustable. (± 1999).
Display: 3-1/2 digits, 7 segments,
0.45 (11.4 mm) H.
Decimal Points: 3-position, user
selectable.
Engineering Units: DPMW-XXX: °F,
°C, %, psi; DPMW-XXXP: V, A, KW,
PF.
1/8
[3]
63/64
[25.1]
29/32
[23.1]
1-9/16
[39.7]
Polarity: Automatic, •-Ž displayed.
Operating Temperature: 32 to 122°F
(0 to 50°C).
Storage Temperature: -4 to 158°F
(-20 to 70°C).
Mounting: Window mount.
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
343
Panel Meters/
Indicators
Series DPMA Adjustable LCD Digital Panel Meter offers a 3-1/2 digit display for
easy viewing in a standard 1/8 DIN package. Unit accepts 4 to 20 mA, 0 to 5 VDC, or 0 to
10 VDC inputs with a wide bipolar span and zero adjustment. Standard features include
field selectable engineering units and decimal point positions. Choose from red, amber, or
green segments for easy viewing at a distance. A 24 VDC power supply is required for the
operation of the backlight.
1-59/64
[49]
63/64
[25]
1-49/64
PANEL CUTOUT
[45]
FOR SNAP IN MOUNTING
3-5/8
[92]
15/32
[12]
1-57/64
[48]
3-15/32
[88] REAR HOUSING
PROCESS CONTROL
Series
DPMA
PROCESS CONTROL
344_Layout 1 7/29/14 3:25 PM Page 344
LCD Digital Panel Meters
Series
DPMP
& DPML
3-1/2 & 4-1/2 Digit LCD, User Selectable Engineering Units, Panel Mount
P Models
V
A
KW
PF
DPMP
2-35/64
[64.5]
DPMP
°F
°C
PSI
%
Panel Meters/
Indicators
1/8
[3]
2-13/32
[61]
1-9/64
[29]
P Models
V
A
KW
PF
2.390 [60.6]
REAR HOUSING
2-35/64
[64.5]
DPML
RoHS
PANEL CUTOUT FOR
WINDOW MOUNTING
63/64
[25.1]
1
[25.4]
1-5/8
[41.1]
DPML
°F
°C
PSI
%
1-9/64
[29]
2.390 [60.6]
REAR HOUSING
The Series DPMP &DPML LCD Digital Panel Meters provide easy viewing on the 31/2 or 4-1/2 digit LCD display. The display segments are available in a choice of amber,
black, red or green. The meter features user-selectable engineering units, adjustable span
and zero and field-selectable decimal point position. The snap-in bezel mount eliminates
mounting hardware for quick installation. A 24 VDC power supply is required for the
operation of the backlight.
APPLICATIONS
Used to display process values from pressure, humidity, temperature, voltage,
current, watt, or power factor transmitters.
Model
DPMP-401
DPMP-402
DPMP-403
DPMP-501
DPMP-502
DPMP-503
DPMP-401P
DPMP-402P
DPMP-403P
DPMP-501P
DPMP-502P
DPMP-503P
Input
Current
Current
Current
Voltage
Voltage
Voltage
Current
Current
Current
Voltage
Voltage
Voltage
Segments
Amber
Green
Red
Amber
Green
Red
Amber
Green
Red
Amber
Green
Red
Engineering
Units
°F, °C, %, PSI
°F, °C, %, PSI
°F, °C, %, PSI
°F, °C, %, PSI
°F, °C, %, PSI
°F, °C, %, PSI
V, A, KW, PF
V, A, KW, PF
V, A, KW, PF
V, A, KW, PF
V, A, KW, PF
V, A, KW, PF
Digit*
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
3-1/2
SPECIFICATIONS
Input: DPMX-4XX(P): 4 to 20 mA;
DPMX-5XX(P): 0 to 200 mVDC, 0 to 5
VDC, or 0 to 10 VDC.
Input Impedance: DPMX-4XX(P):
300 nominal; DPMX-5XX(P): 390
nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: DPMX-4XX(P):
Powered by control loop; DPMX5XX(P): 12 VDC or 24 VDC.
Backlight Power Supply: 24 VDC @
35 mA typical.
Span and Zero: Adjustable (±1999
Counts).
Display: DPMP: 3-1/2 digits, 7
segments, 0.45 (11.4 mm) H; DPML:
4-1/2 digits, 7 segments, 0.45 (11.4
mm) H.
Decimal Points: DPMP: 3-position,
user selectable; DPML:4-position, user
selectable.
Engineering Units: DPMX-XXX: °F,
°C, %, psi; DPMX-XXXP: V, A, KW, PF.
Polarity: Automatic, •-Ž displayed.
Operating Temperature: 32 to 122°F
(0 to 50°C).
Storage Temperature: -4 to 158°F
(-20 to 70°C).
Mounting: Snap-in bezel mount.
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.
ACCESSORIES
DPM-12P, Regulated 120 VAC to 12 VDC Power Supply
DPM-24P, Regulated 120 VAC to 24 VDC Power Supply
*Note: For 4-1/2 digit display change P to L.
Example: DPML-401
Model
DPMF
Flush Mount LCD Digital Panel Meter
3-1/2 Digit LCD, Surface Mount
RoHS
2-3/8
[59.94]
1-1/8
[29.03]
1
[25.40]
2-3/16
[55.56]
The Model DPMF Flush Mount LCD Digital Panel Meter offers high performance
and low cost in a compact package. This meter is designed with a 3-1/2 digit, high contrast
LCD display. The unit is powered by a 4 to 20 mA DC control loop input. Standard features
include adjustable span and zero, and field-selectable decimal point position. The flat pack
of the panel meter allows for the instrument to be mounted to any flat surface.
Model DPMF, Flush Mount LCDDigital Panel Meter
344
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Input: 4 to 20 mA DC.
Input Impedance: 300 nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: Powered by control
loop.
Span and Zero: Adjustable (±1999
counts).
Display: 3-1/2 digits, 7 segments, 0.5
(12 mm) H.
Decimal Points: 3-position, user
selectable.
Ø1/8
[Ø2.5]
Polarity: Automatic, •-Ž displayed.
Operating Temperature: 32 to 122°F
(0 to 50°C).
Storage Temperature: -4 to 158°F (-20
to 70°C).
Mounting: Surface mount.
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 1.2 oz (34.5 g).
Agency Approvals: RoHS.
345_Layout 1 7/8/14 11:31 AM Page 345
PROCESS CONTROL
Series
DPMX
Extra Large Digital Panel Meter
3-1/2 Digit LED Display, 2.3” Segment Height, Process Inputs
1-31/32 [50.04]
10-19/32 [269.24]
10-19/32 [261.11]
4
[101.60] 4-5/32
[105.66]
2-43/64
3-7/64 [67.87]
[78.99]
29/32
[22.86]
FEATURES
€ Large display
€ Inputs for most processes
€ Protective metal casing
Model
DPMX-1
DPMX-2
DPMX-3
DPMX-1-LV
DPMX-2-LV
DPMX-3-LV
Segments
Blue
Green
Red
Blue
Green
Red
Power Supply
90 to 250 VAC
90 to 250 VAC
90 to 250 VAC
10.5 to 30 VAC/VDC
10.5 to 30 VAC/VDC
10.5 to 30 VAC/VDC
Series
LCI132
SPECIFICATIONS
Inputs:
Set voltage: ±200 mVDC, ±2 VDC, ±20 VDC;
Adjustable voltage: 200 mVDC, 5 VDC, 10 VDC;
Adjustable current: 0(4) to 20 mA DC.
Input Impedance:
Set voltage: >1 M (>10 M on 200 mV range);
Adjustable voltage: 392 k;
Adjustable current: 300 nominal.
Accuracy: ±(1% F.S. + 1 count).
Power Supply: 90 to 250 VAC @ 12 VA or 10.5 to 30 VAC/DC @ 6VA (depending
on model).
Display: 3-1/2 digits, 2.3 H, 7 segment LED.
Sampling Rate: 3 readings per second.
Operating Temperature: 14 to 122°F (-10 to 50°C).
Storage Range: -40 to 167°F (-40 to 75°C).
Warm Up: 10 minutes.
Mounting: 180° gimbal mounting with 30° stops or bezel mount.
Process Indicator
1/32 DIN, Fully Programmable
2-49/64
[70.25]
Program
Keys
1-57/64
[48.2]
7/16
[11.11]
61/64
[24.2]
53/64
[21.03]
1/4 [6.35] MAXIMUM
PANEL THICKNESS
Process Display
The LCI132 Series process indicators offer flexibility, and value in a low cost,
compact 1/32 DIN package. This family of indicators offers input availability for most types
of process measurement.
The LCI132 has a 7.62 mm (0.3 inch) high display. The shallow depth of these full size panel
meters allows installation in panels only 70 mm (2.76˝) deep with room to spare.
Inputs are available for Process (0 to 10V, 4 to 20 mA), AC Volts, AC Amps, DC Volts, and
DC Amps.
SPECIFICATIONS
LCI132-0X
Range:
Input Volts (DC): ±200 V, ±20 V, ±10 V;
Input Amperes: ±100 mV, ±20 mA;
Resolution: Input Volts (DC):0.1 V, 0.01 V, 1 mV;
Input Amperes: 0.1 mV, 0.01 mA;
Input Impedance:Volts: 1 M , mV: 100 M , mA: 12.1 .
FEATURES
€ Large display
€ Easy to program
€ Inputs for most processes
€ IP65 (NEMA 4X) front
LCI132-1X
Range AC: Input Volts: 600.0, 100.0;
Input Amperes: 5.000, 1.000;
Range DC: Input Volts: -199.9, ±600.0, ±100.0;
Input Amperes: -1.999, +5.000, ±1.000;
Resolution: Input Volts:0.1 V;
Input Amperes: 1 mA
Input Impedance:Volts: 3 M (106), Amps:12 m (10-3).
Model
LCI132-00
LCI132-01
LCI132-10
LCI132-11
Input
±100 VDC; ±20 VDC
±10 VDC; ±200 VDC; ±20 mA DC
±100 VAC; 600 VAC; 5A (DC) 1A (AC)
-199.9 to +600 VDC;
±100 VDC -1.999 to 5A (DC)
±1A (DC)
Supply Voltage
120/240 VAC
24/48 VAC
120/240 VAC
24/48 VAC
Accuracy at 23ºC ±5ºC
100/600 VDC 1/5 A DC; 600V/5A AC: ±(0.2% reading + 3 digits). 100 V / 1A AC:
±(0.4% reading + 4 digits).
Temperature Coefficient: 100 ppm/°C.
Warm Up: 5 minutes.
Power Supply and Fuses (DIN 41661) (Not supplied):
LCI132-X0: 85…265 VAC 50/60 Hz and 100-300 VDC: Fuse: 0.1A/ 250V.
LCI132-X1: 21-53 VAC 50/60Hz and 10.5-70 VDC: Fuse 0.5A/ 250V.
Display
Range: -1999 to 9999 (DC) 0 to 9999 (AC).
Type: 4 red digits 10 mm.
Reading Rate: 4/s.
Overflow Indication: OVR.
Environmental
Operating Temperature: -10 to 60°C.
Storage Temperature: -25 to 85°C.
Relative Humidity (non condensed): < 95% @ 40°C.
Panel Sealing: NEMA 4X (IP66).
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
345
Panel Meters/
Indicators
The Series DPMX Digital Panel Meter can easily be viewed from across a room or in
dark areas. The 2.3˝ LED segments are available in red, green, or blue. These panel meters
come equipped with a universal power supply and user selectable process inputs to fit most
applications. The Series DPMX includes a mounting bracket that can be adjusted up to
180°.
PROCESS CONTROL
346_Layout 1 7/8/14 11:31 AM Page 346
Series
APM
Analog Panel Meter
Multi-Pump Alternation Control, Open-Channel Flow, Rate and Totalizer
RoHS
1-49/64
[45.0]
3-5/8
[92.0]
NO NC
C NO NC
C
Panel Meters/
Indicators
5-3/64
[128.0]
4-49/64
[121.0]
4-11/64
[106.0]
2-7/16
[62.0]
The Series APM has a unique, rugged, NEMA 4X front panel design that makes it nearly
impenetrable in typical applications. The weatherproof, UV resistant, large, dual line
display allows for more information making it easier to read and even simpler to program.
The intensity of the display can be adjusted allowing this meter to be utilized in dark rooms
as well as outdoors, due to its sunlight readable display. It features up to eight visual alarm
set points to trigger certain events and three function keys which can be programmed to
provide direct menu access. With up to four relays available, the APM features latching,
non-latching, sampling, pump alteration control, and a failsafe action. Offering
programmable delay time, this meter prevents recognition of false maximum or minimum
reading which may be caused by the start-up or unusual process events. The APM provides
three security passwords that restrict modification of programmed settings. This unit has
the ability to obtain non-linear input signals and linearize them with simple to use math
functions such as square-root extractor, weirs and flumes exponential linearizer, horizontal
round tank linearizer or general purpose 32-point linearizer. Unit accepts 0 to 20 mA, 4 to
20 mA, 0 to 5V, or ±10V inputs and requires 85-265 VAC or 12/24 VDC power supply.
Choose from RS-232, RS-422/485 serial communication options or any available expansion
modules, accessories, and enclosures.
The APM is a 1/8 DIN digital panel meter specifically designed for displaying flow rate
and total from a flow meter with an analog output such as 4 to 20 mA or 0 to 10V. The
APM is particularly well-suited for flow applications and can be programmed for a wide
variety of display configurations. The upper line can display either flow rate, total or grand
total, and the lower line can display either flow rate, total, grand total, or engineering units.
It is possible to display flow rate and total at the same time, a very unique feature on a 1/8
DIN digital panel meters.
FEATURES
€ Three levels of password protection
€ Math functions for flow & round horizontal tanks
€ 32-point linearization, square root or programmable exponent
€ Multi-pump alternation control
€ Rate displayed as units per second, minute, hour, or day
€ Total, grand total or non-resettable grand total
€ Two or four relays & isolated 4 to 20 mA output options
€ External 4-relay & digital I/O expansion modules
€ RS-232, RS-422/485 serial communication options
OPEN CHANNEL FLOW CAPABILITY
Series APM when utilized with an ultrasonic level transmitter, such as the Mercoid
Series ULT, provides an economical way to measure open channel flow.
DIFFERENTIAL PRESSURE FLOW
The APM can display flow rate and total by extracting the square root from the 4 to
20 mA signal from a differential pressure transmitter, such as the Dwyer 629, that is
being used with a flow element such as Dwyer orifice plate Series OP or TE. The
user-selectable, low-flow cut-off feature gives a reading of zero when the rate is
below a user selectable value.
PUMP CONTROL
With the two or four contact output option the APM can be used as a programmable
pump controller when used with a Dwyer level transmitter. The unit also has
programmable on and off points for up to four pumps, quadraplex pumping systems
with alternation capability. When using the 4-relay model with the four external relay
accessory, the APM can do 8 contacts for any combination of pump control and 8
programmable alarms.
346
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
1-9/32
[15.0]
4-11/16
[119.0]
SPECIFICATIONS
Input: 0 to 20 mA, 4 to 20 mA, 0 to 5V, or ±10V inputs; A 85-265 VAC or 12/24
VDC.
Input Impedance: 50 to 100 .
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable
exponent accuracy range: 10-100% of calibrated span.
Power Requirements: 85 to 265 VAC 50/60 Hz, 90 to 265 VDC, 20 W max or 12
to 24 VDC ±10%, 15 W max.
Display: Dual-line 6-digit display, 0.60 in and 0.46 in.
Decimal Points: Five positions, user selectable.
Temperature Limits:
Operating: -40 to 149°F (-40 to 65°C);
Storage: -40 to 185°F (-40 to 85°C).
Enclosure Rating: NEMA 4X, IP65 front.
Electrical Connections: Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Output Signal: 4 to 20 mA.
Power Consumption:
85 to 265 VAC models: 200 mA @ 24 VDC;
12 to 24 VDC models: 100 mA @ 24 VDC;
Second supply with output 2 models: 40 mA @ 24 VDC.
Switch Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external;
rated 3A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for
inductive loads.
Time Delay: 0 to 999.9 seconds, on & off relay time delays; programmable and
independent for each relay.
Shipping Weight: 9.5 oz (269 g).
Agency Approvals: CE, RoHS, UL.
Model
APM-100
APM-101
APM-120
APM-121
APM-140
APM-141
APM-200
APM-201
APM-220
APM-221
APM-240
APM-241
Power
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
Output 1
None
None
2 relays
2 relays
4 relays
4 relays
None
None
2 relays
2 relays
4 relays
4 relays
Output 2
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
Accessories: See page 349 (Series PMA)
Enclosures: See page 350 (Series PME)
347_Layout 1 7/15/14 3:41 PM Page 347
PROCESS CONTROL
Series
MPM
Multi Panel Meter
1/8 DIN, Dual-Line 6-Digit Display, Multi-Pump Alternation Control
RoHS
1-49/64
[45.0]
3-5/8
[92.0]
NO NC
Panel Meters/
Indicators
C NO NC
C
5-3/64
[128.0]
4-49/64
[121.0]
4-11/64
[106.0]
2-7/16
[62.0]
The Series MPM has a unique, rugged, NEMA 4X front panel design that makes it nearly
impenetrable in typical applications. The weatherproof, UV resistant, large, dual line
display allows for more information, making it easier to read and simpler to program. The
intensity of the display can be adjusted allowing this meter to be utilized in dark rooms as
well as outdoors, due to its sunlight readable display. It features up to eight visual alarm
set points to trigger certain events and three function keys, which can be programmed to
provide direct menu access. With up to four relays available, the MPM features latching,
non-latching, sampling, pump alteration control, and a fail-safe action. Offering
programmable delay time, this meter prevents recognition of false maximum or minimum
reading which may be caused by the start-up or unusual process events. The MPM provides
three security passwords that restrict modification of programmed settings. The MPM has
the ability to obtain non-linear input signals and linearize them with simple to use math
functions such as square-root extractor, weirs and flumes exponential linearizer, horizontal
round tank linearizer or general purpose 32-point linearizer. Unit accepts 0 to 20 mA, 4 to
20 mA, 0 to 5V, or ±10V inputs and requires 85 to 265 VAC or 12/24 VDC power supply.
Choose from RS-232, RS-422/485 serial communication options or any available expansion
modules, accessories and enclosures.
FEATURES
€ Three levels of password protection
€ Math functions for flow & round horizontal tanks
€ 32-point, square root or exponential linearization
€ Multi-pump alternation control
€ Two or four relays & isolated 4 to 20 mA output options
€ External 4-relay & digital I/O expansion modules
€ RS-232, RS-422/485 serial communication options
PUMP CONTROL
Providing two or four contact output options, the MPM can be used as a
programmable pump controller when used with any Dwyer level transmitter. The
relay capabilities of this meter expand its usefulness beyond simple indication to
provide the user with alarm and pump control.
1-9/32
[15.0]
4-11/16
[119.0]
SPECIFICATIONS
Input: 0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V or ±10 V.
Input Impedance: 50 to 100 .
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable
exponent accuracy range: 10 to 100% of calibrated span.
Power Requirements: 85 to 265 VAC 50/60 Hz, 90 to 265 VDC, 20 W max or 12
to 24 VDC ± 10%, 15 W max.
Display: Dual-line 6-digit display, 0.60 & 0.46.
Decimal Points: 5-position, user selectable.
Temperature Limits:
Operating: -40 to 149°F (-40 to 65°C);
Storage: -40 to 185°F (-40 to 85°C).
Enclosure Rating: NEMA 4X, IP65 front.
Electrical Connections: Removable screw terminal blocks accept 12 to 22 AWG
wire; RJ45 for external relays, digital I/O, and serial communication adapters.
Output Signal: 4 to 20 mA.
Switch Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external;
rated 3A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for
inductive loads.
Power Consumption:
85 to 265 VAC models: 200 mA @ 24 VDC;
12 to 24 VDC models: 100 mA @ 24 VDC;
Second supply with output 2 models: 40 mA @ 24 VDC.
Time Delay: 0 to 999.9 seconds, on & off relay time delays programmable and
independent for each relay.
Shipping Weight: 9.5 oz (269 g).
Agency Approvals: CE, RoHS, UL.
Model
MPM-100
MPM-101
MPM-120
MPM-121
MPM-140
MPM-141
MPM-200
MPM-201
MPM-220
MPM-221
MPM-240
MPM-241
Power
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
Output 1
None
None
2 relays
2 relays
4 relays
4 relays
None
None
2 relays
2 relays
4 relays
4 relays
Output 2
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
Accessories: See page 349 (Series PMA)
Enclosures: See page 350 (Series PME)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
347
PROCESS CONTROL
348_Layout 1 7/8/14 11:29 AM Page 348
Series
PPM
Pulse Panel Meter
1/8 DIN, Dual-Line 6-Digit Display, Flow Rate and Totalizer
RoHS
1-49/64
[45.0]
3-5/8
[92.0]
NO NC
C NO NC
C
Panel Meters/
Indicators
5-3/64
[128.0]
4-49/64
[121.0]
4-11/64
[106.0]
2-7/16
[62.0]
The Series PPM has a unique, rugged, NEMA 4X front panel design that makes it nearly
impenetrable in typical applications. The weatherproof, UV resistant, large, dual line
display allows for more information, making it easier to read and simpler to program. The
intensity of the display can be adjusted allowing this meter to be utilized in dark rooms as
well as outdoors, due to its sunlight readable display. It features up to eight visual alarm
set points to trigger certain events and three function keys which can be programmed to
provide direct menu access. With up to four relays available, the PPM features latching,
non-latching, sampling, pump alteration control, and a failsafe action. Offering
programmable delay time, this meter prevents recognition of false maximum or minimum
reading which may be caused by the start-up or unusual process events. The PPM provides
three security passwords that restrict modification of programmed settings. This unit has
the ability to obtain non-linear input signals and linearize them with a general purpose 32point linearizer. Choose from RS-232, RS-422/485 serial communication options or any
available expansion modules, accessories, and enclosures.
The PPM displays flow rate and total simultaneously, with a programmable relay and 4 to
20 mA option for flow rate or flow total. The PPM is a 1/8 DIN digital panel meter
specifically designed for displaying flow rate and total from a pulsed input provided by
open collector, NPN, PNP, TTL, switch contact, sine wave, or square wave.
FEATURES
€ Three levels of password protection
€ Gate function for rate display of slow pulse rates
€ Rate displayed as units per second, minute, hour, or day
€ K-factor calibration or scale with up to 32-point linearization
€ Total, grand total or non-re-settable grand total
€ Two or four relays & isolated 4 to 20 mA output options
€ External 4-relay & digital I/O expansion modules
€ RS-232, RS-422/485 serial communication options
FLOW RATE
The PPM is particularly well-suited for flow applications because its six-digit, dualline display can be programmed for a wide variety of display configurations. For
instance, the upper line can display either flow rate, total or grand total, and the
lower line can display flow rate, total, grand total, or engineering units. Among other
things, this makes it possible to display either flow rate and total, or total and grand
total at the same time, a very unique feature on 1/8 DIN digital panel meters.
1-9/32
[15.0]
4-11/16
[119.0]
SPECIFICATIONS
Input: Field selectable: Pulse or square wave 0 to 5V, 0 to 12V, or 0 to 24V @ 30
kHz; TTL; open collector 4.7 kΩ pull-up to 5V @ 30 kHz; NPN or PNP transistor,
switch contract 4.7 kΩ pull-up to 5V @ 40 Hz.
Input Impedance: 50 to 100 .
Accuracy: ±0.03% of calibrated span ±1 count.
Power Requirements: 85 to 265 VAC 50/60 Hz, 90 to 265 VDC, 20 W max or 12
to 24 VDC ± 10%, 15 W max.
Display: Dual-line 6-digit display, 0.60 and 0.46.
Decimal Points: 5-positions, user selectable.
Temperature Limits:
Operating: -40 to 149°F (-40 to 65°C);
Storage: -40 to 185°F (-40 to 85°C).
Enclosure Rating: NEMA 4X, IP65 front.
Electrical Connections: Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Output Signal: 4 to 20 mA.
Switch Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external;
rated 3A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for
inductive loads.
Power Consumption:
85 to 265 VAC models: 200 mA @ 24 VDC;
12 to 24 VDC models: 100 mA @ 24 VDC;
Second supply with output 2 models: 40 mA @ 24 VDC.
Time Delay: 0 to 999.9 seconds, on & off relay time delays programmable and
independent for each relay.
Shipping Weight: 9.5 oz (269 g).
Agency Approvals: CE, RoHS, UL.
Model
PPM-100
PPM-101
PPM-120
PPM-121
PPM-140
PPM-141
PPM-200
PPM-201
PPM-220
PPM-221
PPM-240
PPM-241
Power
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
85 to 265 VAC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
12 to 24 VDC
Output 1
None
None
2 relays
2 relays
4 relays
4 relays
None
None
2 relays
2 relays
4 relays
4 relays
Output 2
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
None
4 to 20 mA
Accessories: See page 349 (Series PMA)
Enclosures: See page 350 (Series PME)
348
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
349_Layout 1 7/8/14 11:29 AM Page 349
PROCESS CONTROL
Series
PMA
Panel Meter Accessories
For PPM, APM, MPM, and LTI Series Panel Meters
PMA-01 RS-232 Serial Adapter
PMA-02 Meter Copy Cable
SPECIFICATIONS
Compatibility: EIA-232.
Connectors: PC compatible 9-pin D subminiature
connector (DB9) and RJ11 (adapter to meter).
Cable: 3 ft (0.9 m) standard CAT5e cable provided
with adapter.
Distance: Adapter to panel meter: 6 ft (1.8 m) max;
Adapter to computer: 50 ft (15 m) max; Serial interface
cable not provided.
Power: Powered by panel meter M-LINK connection.
Status Indication: Separate LEDs for power (P),
transmit (TX), and receive (RX).
PMA-02
PMA-03 RS-422/485 Serial Adapter
SPECIFICATIONS
Compatibility: EIA-422 and EIA-485.
Connectors: Removable screw terminal connector
and RJ11 (adapter to meter).
Cable: 3 ft (0.9 m) standard CAT5e cable provided
with adapter.
Distance: Adapter to panel meter: 6 ft (1.8 m) max;
Adapter to computer: 3937 ft (1200 m) max.
Power: Powered by panel meter M-LINK
connection.
Status Indication: Separate LEDs for power (P),
transmit (TX), and receive (RX).
PMA-03
PMA-06 USB to RS-232 Non-Isolated Converter
PMA-04, PMA-05 RS-232 to RS-422/485 Converters
SPECIFICATIONS
Compatibility: EIA-232, EIA-422, and EIA-485.
Connectors: Screw terminal connector and DB9.
Distance: RS-232 connection: 50 ft (15 m) max; RS422/485 connection: 3937 ft (1200 m) max.
Number of Units: Up to 31 RS-485 compatible devices.
Power: 9 to 12 VDC; 115 VAC/12 VDC adapter included.
Isolation: PMA-04: 1500 VAC between data lines; 700
VDC input/output-to-power; PMA-05: 1500 VAC between
data lines only.
PMA-04, Isolated
PMA-05, Non-Isolated
PMA-07, PMA-08 USB to RS-422/485 Converters
SPECIFICATIONS
Compatibility: USB 1.1, USB 2.0, EIA-422, and EIA-485.
Connectors: Screw terminal connector and USB Type B.
Drivers: Windows® 98/2000/ME/XP operating systems,
Linux 2.4 & greater.
Distance: USB connection: 10 ft (3 m) max; RS-422/485
connection: 3937 ft (1200 m) max.
Number of Units: Up to 31 RS-485 compatible devices.
Power: USB port.
Isolation: PMA-07: 1500 VAC between data lines, 700
VDC input/output-to-power; PMA-08: 1500 VAC between
data lines only.
SPECIFICATIONS
Compatibility: USB 1.1, USB 2.0, EIA-232.
Connectors: PC compatible 9-pin D subminiature
connector (DB9) and USB type A.
Drivers: Windows® 98/2000/Me/XP operating systems.
Distance: USB connection: 10 ft (3 m) max;
RS-232 connection: 50 ft (15 m) max.
Power: USB port.
PMA-07, Isolated
PMA-08, Non-Isolated
PMA-06
PMA-09 Snubber
PMA-10 DIN Rail Mounting Kit for Two Expansion Modules
SPECIFICATIONS
Rail: 6 in (15.24 cm) long.
Mounting Clips: 4 plastic mounting clips with adhesive
strips.
Total Capacity: 2 expansion modules.
SPECIFICATIONS
Capacitance Value: 0.01 F.
Resistor Value: 470 Ω.
Voltage: 250V.
PMA-10
PMA-09
PMA-11 4 Relay Expansion Module
PMA-12 4 Digital Inputs and 4 Digital Outputs Module
SPECIFICATIONS
Relays: Four form A (SPST); Rated 3 A @ 30 VDC
and 125/250 VAC for resistive loads 1/14 HP @
125/250 VAC for inductive loads.
Cable: Standard CAT5e cable; provided with module.
Connectors: RJ45.
Tightening Torque: Screw terminal connectors: 5 lb-in
(0.56 Nm).
Enclosure: ABS-94HB material, UL94HB.
Overall Dimensions: 2.286 in x .924 in x 3.624 in
(58.06 mm x 23.47 mm x 92.05 mm) (w x h x d).
Power: Panel meter M-LINK connection.
Weight: 2.4 oz (68 g).
PMA-11
Panel Meters/
Indicators
PMA-01
SPECIFICATIONS
Cable: 3 ft (0.9 m) standard modular cable.
SPECIFICATIONS
System: Up to 2 modules for a total of 8 inputs, outputs.
Digital Input Logic: High: 3 to 5 VDC; Low: 0 to 1.25
VDC.
Digital Output Logic: High: 4.75 to 5 VDC; Low: 0 to 0.4
VDC.
Current: Source: 10 mA max.; Sink: 1.5 mA min..
Cable: Standard CAT5e cable; Provided with module.
Connectors: RJ45.
Tightening Torque: Screw terminal connectors: 5 lb-in
(0.56 Nm).
Enclosure: ABS-94HB material, UL94HB.
Power: Panel meter M-LINK connection.
Weight: 2.2 oz (62 g).
PMA-12
Windows® is a registered trademark of Microsoft Corporation
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
349
PROCESS CONTROL
350_Layout 1 7/8/14 11:28 AM Page 350
Series
PME
Panel Meter Enclosures
For 1/8 DIN Meters
Low-Cost Plastic Enclosure
Low-Cost Plastic Enclosure
SPECIFICATIONS
Material: Thermoplastic polyester.
Ratings: NEMA 4X (IP66).
Dimensions: 5.9 in x 7.9 in x 6.3 in (150 mm x
200 mm x 160 mm).
Weight: 1.75 lb (0.79 kg).
Control Enclosures
SPECIFICATIONS
Material: Thermoplastic polyester.
Ratings: NEMA 4X (IP66).
Dimensions: 5.9 in x 7.9 in x 6.3 in (150 mm x
200 mm x 160 mm).
Weight: 1.75 lb (0.79 kg).
PME-01, For 1 Meter
PME-02, For 2 Meter
Plastic Enclosures
Plastic Enclosures
SPECIFICATIONS
Material: Thermoset polyester.
Ratings: NEMA 4X (IP66).
Dimensions: PME-11: 8.8 in x 6.7 in x 4.3 in (224
mm x 170 mm x 110 mm); PME-12, -13: 11.8 in x
7.9 in x 7.0 in (300 mm x 201 mm x 178 mm).
Weight: PME-11: 1.45 lb (0.66 kg); PME-12, -13:
3.15 lb (1.43 kg).
PME-11, For 1 Meter
PME-12, For 2 Meters
PME-13, For 3 Meters
SPECIFICATIONS
Material: Thermoset polyester.
Ratings: NEMA 4X (IP66).
Dimensions: 15.8 in x 11.8 in x 7.0 in (400 mm x
300 mm x 178 mm).
Weight: 5.50 lb (2.49 kg).
PME-14, For 4 Meter
PME-15, For 5 Meters
PME-16, For 6 Meters
Plastic Enclosures
Plastic Enclosures
SPECIFICATIONS
Material: Thermoplastic.
Ratings: NEMA 4X (IP66).
Dimensions: PME-21: 7.7 in x 6.4 in x 5.1 in (196
mm x 163 mm x 130 mm); PME-22: 9.7 in x 6.4 in x
5.1 in (246 mm x 163 mm x 130 mm); PME-23: 11.7
in x 8.4 in x 5.1 in (297 mm x 213 mm x 130 mm).
Weight: PME-21: 1.60 lb (0.70 kg); PME-22: 2.20 lb
(1.00 kg); PME-23: 3.00 lb (1.40 kg).
PME-21, For 1 Meter
PME-22, For 2 Meters
PME-23, For 3 Meters
SPECIFICATIONS
Material: Thermoplastic.
Ratings: NEMA 4X (IP66).
Dimensions: 13.7 in x 12.4 in x 7.1 in (348 mm x
315 mm x 181 mm).
Weight: 5.00 lb (2.30 kg).
PME-24, For 4 Meter
PME-25, For 5 Meters
PME-26, For 6 Meters
Stainless Steel Enclosures
Stainless Steel Enclosures
SPECIFICATIONS
Material: 304 SS.
Ratings: NEMA 4X (IP66).
Dimensions: 13.5 in x 12.9 in x 6.0 in (343 mm x
329 mm x 152 mm).
Weight: 13.90 lb (6.30 kg).
SPECIFICATIONS
Material: 304 SS.
Ratings: NEMA 4X (IP66).
Dimensions: PME-31: 7.5 in x 6.9 in x 4.0 in (191
mm x 176 mm x 102 mm); PME-32: 9.5 in x 6.9 in x
3.5 in (241 mm x 176 mm x 89 mm); PME-33: 11.5 in
x 8.9 in x 4.0 in (292 mm x 227 mm x 102 mm).
Weight: PME-31: 3.80 lb (1.70 kg); PME-32: 5.10 lb
(2.30 kg); PME-33: 7.90 lb (3.60 kg).
PME-31, For 1 Meter
PME-32, For 2 Meters
PME-33, For 3 Meters
PME-34, For 4 Meter
PME-35, For 5 Meters
PME-36, For 6 Meters
Steel Enclosures
Steel Enclosures
SPECIFICATIONS
Material: Steel.
Ratings: NEMA 4X (IP66).
Dimensions: PME-41: 7.5 in x 6.9 in x 4.0 in (191
mm x 176 mm x 102 mm); PME-42: 9.5 in x 6.9 in x
3.5 in (241 mm x 176 mm x 89 mm); PME-43: 11.5 in
x 8.9 in x 4.0 in (292 mm x 227 mm x 102 mm).
Weight: PME-41: 3.80 lb (1.70 kg); PME-42: 5.10 lb
(2.30 kg); PME-43: 7.90 lb (3.60 kg).
PME-41, For 1 Meter
PME-42, For 2 Meters
PME-43, For 3 Meters
Note: Make sure panel meter dimensions fit enclosure size.
350
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Material: Steel.
Ratings: NEMA 4X (IP66).
Dimensions: 13.5 in x 12.9 in x 6.0 in (343 mm x
329 mm x 152 mm).
Weight: 13.90 lb (6.30 kg).
PME-44, For 4 Meter
PME-45, For 5 Meters
PME-46, For 6 Meters
351_Layout 1 7/21/14 2:02 PM Page 351
PROCESS CONTROL
Series
A-900
&
A-901
1/4 DIN Control Enclosures
Weatherproof, Durable, Pre-Cut Mounting Hole
4-1/4
[107.95]
10-32 UNF-2B
TYP 8 PLCS
3-39/64
[91.68]
A-900
Control Enclosures
7-3/4
3-39/64 4-1/4
[91.68] [107.95] [195.33]
5
[127.51]
5
[127.51]
7-3/4
[195.33]
Top View
Bottom View
1-1/2
[38.10]
1-3/4
[44.45]
4-1/8
[106.17]
A-901 UNIT
(4-1/2 [114.30] STANDOFFS)
4 PLCS
Side View
A-901
Models A-900 and A-901 are the perfect instrument housing for indoor or outdoor
applications. Protects controls from dirt, dust, oil and water. Unit is rated weatherproof
type NEMA 4X (IP66) and has a fully gasketed cover. Standard features include a lockable
latch to prevent tampering and flush mounting hardware.
The Model A-900 comes standard with a 1/4 DIN cut out in the front cover. Controller will
mount with front face exposed for easy access to the programming buttons. Love and
Mercoid controllers feature weatherproof NEMA 4X (IP66) rated front panels and gaskets
enabling the control to be weatherproof protected when installed in the A-900 even though
the front face is exposed. Wiring an installed control is easy due to the hinged cover and
spacious clearance for the control to swing out with front cover. The lockable latch prevents
unauthorized removal of the control from the enclosure.
The Model A-901 comes standard with a clear plastic front window and mounting hardware
to install the control inside the box. Controller mounts just behind the window assuring
easy viewing. Mounting the control inside the enclosure protects the control face from
corrosive atmospheres or from being covered in oil, dirt and dust. The lockable latch
prevents unauthorized removal of the control and removes access to the control
programming buttons. The Mounting hardware is attached to the rear of the enclosure
and includes a bracket with a 1/4 DIN cutout and standoffs long enough for Love and
Mercoid controls to fit. Control programming buttons are easily accessible by just opening
the front cover.
FEATURES
€ UV stabilized for outdoor use
€ Snap latch with lockable hasp
€ Continuous cover hinge
€ Fiberglass material is easily punched or drilled for conduit connections
€ Includes feet and screws for flush mounting to a wall
€ Compatible with Love 2500, 2600, 4B, 4C, MPCJR and MPC
SPECIFICATIONS
Service: Indoor or outdoor.
Rating: NEMA 1, 2, 3, 3R, 4, 4X, 12 and 13.
Materials:
Body: UV stabilized fiberglass reinforced polyester;
Snap latch: 304 SS;
Hinge: SS;
Mounting feet and screws: 304 SS;
Window: UV stabilized polycarbonate;
Cover gasket: Neoprene.
Agency Approvals: UL.
Enclosure Rating: NEMA 4X(IP66).
Control Temperature Limits:
When using the enclosures with controls that have 10A relay outputs the extra heat
generation decreases the maximum ambient temperature value that the control can
be used at inside the enclosure. Other outputs on our controls are not a concern.
For Models: 25XX3, 26XX3, 26X3X, 26X33, MPC, MPCJR
Ambient
Temperature
77°F (25°C)
104°F (40°C)
131°F (55°C)
Model
A-900
A-901
ACCESSORY
A-600, R/C snubber
Maximum Current
A-901
A-900
10 Amps 10 Amps
10 Amps 9 Amps
7.5 Amps 6 Amps
Description
Weatherproof enclosure, Type 4X.
Control direct panel mounts in the front of the enclosure.
Weatherproof enclosure, Type 4X.
Clear plastic window with rear panel for mounting the
control inside the enclosure.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
351
PROCESS CONTROL
352_Layout 1 7/21/14 2:01 PM Page 352
Model
LPI
Loop Powered Indicators
Square Root Function and User Defined Curves 4-Digit LED
1/2˝ NPT
9/16
[14.2]
Panel Meters/
Indicators
I
2-15/64
[56.7]
Bottom of Cover
The micropressure based Model LPI Loop Powered Indicator accepts a 4 to 20
mA input signal and displays the associated process variable such as pressure, level, flow,
temperature or relative humidity. Local or remote indication of process variable can be
viewed on the bright red four-digit LED. The user can quickly modify the instrument
configuration via three push buttons. Program input/output scaling, engineering units,
offset, decimal point position, and password protection. The Series LPI contains several
linearizations which can be applied to the display including straight linear, square root, x
3/2, x 5/2, or a user defined 19 segment linearization curve. The indicator is housed in a
NEMA 4X (IP66) polycarbonate enclosure with a 1/2˝ female NPT side port.
Model LPI-111, Loop Powered Indicator with plastic enclosure
Series
BPI
1-11/64
[29.7]
3-11/32
[84.9]
N
SPECIFICATIONS @ 68°F (20°C)
Input: 4 to 20 mA.
Maximum Input Current: 100 mA for 1 minute.
Accuracy: ±0.02% of full scale.
Stability: Zero: 0.002%/°C; Span: 100 ppm/°C.
Power Requirements: 2-wire 4 to 20 mA loop powered.
Display: 4-digit, 7.6 mm (high) red LED.
Maximum Display Range: -1999 to 9999.
Ambient Operating Temperature: -4 to 167°F (-20 to 75°C).
Storage Temperatures: -58 to 185°F (-50 to 85°C).
Weight: 6.0 oz (170 g).
Front Panel Protection: NEMA 4X (IP66).
Agency Approvals: CE.
Battery Powered Temperature Indicator
RTD or T/C Input, 4-Digit Display, Selectable °F or °C
9/16
[14.2]
1/2˝ NPT
1-11/64
[29.7]
3-11/32
[84.9]
2-15/64
[56.7]
The Series BPI Battery Powered Indicator accepts RTD or Thermocouple input and
provides local or remote display of temperature measurements. Quickly navigate the menu
system to customize for each application. Three push buttons allow the user to select input
type, engineering units (°F or °C), offset temperature, decimal point position, and password
protection. The indicator is housed in a polycarbonate NEMA 4X (IP66) enclosure for
additional protection from the environment.
Measuring Ranges
Sensor Range °F (°C)
K
-328 to 2498 (-200 to 1370)
J
-148 to 2192 (-100 to 1200)
T
-346 to 752 (-210 to 400)
N
-292 to 2372 (-180 to 1300)
R
14 to 3200 (-10 to 1760)
S
14 to 3200 (-10 to 1760)
E
-328 to 1832 (-200 to 1000)
F
-148 to 1112 (-100 to 600)
Pt100
-148 to 1472 (-100 to 800)
Ni120
-148 to 1472 (-100 to 800)
352
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Inputs: Thermocouple or RTD depending on model.
Accuracy: Thermocouple input: ±0.1% of FS, ±0.5°C (plus sensor); RTD: ±0.2°C
±0.1% of reading (plus sensor error).
Power Requirements: 3.6 V AA lithium metal battery, included, user replaceable.
Battery Life: > 2 years.
Display: 4-digit LCD.
Resolution: 0.1°C.
Ambient Operating Temperature: 14 to 158°F (-10 to 70°C).
Storage Temperature: -4 to 185°F (-20 to 85°C).
Weight: 6.0 oz (170 g).
Front Panel Protection: NEMA 4X (IP66).
Agency Approvals: CE.
Model
BPI-101
BPI-102
Input
3-wire Pt100 or Ni120
K, J, T, N, R, S, E, or F thermocouples
353_Layout 1 7/9/14 12:23 PM Page 353
PROCESS CONTROL
Series
BGM
Bar Graph Meter
Clear Relative Position & High Resolution In One
3-51/64
[96.39]
25/32
[19.81]
1-13/32
[35.56]
XXXX
XX.X
55/64
[21.72]
21/64
[8.33]
17/64
[6.92]
55/64
[21.84]
TARE
XX.X
MENU
XX.X
XX.X
5-45/64
[144.78]
51/64
[20.07]
PEAK
XX.X
19/32
[14.99]
Horizontal
XX.X
Vertical
BGM H 0 0 N W D AE AO
BGM
H
V
Enclosure
0
Rating
4
0
Relays
2
N
Voltage
E
Retransmission
W
Power Supply
S
D
D
Signal
A
Input
B
AE
Scale Label*
AF
AH
AI
AM
AZ
Scale Range*
AO
AQ
AT
AV
AW
AX
AZ
BA
Example
Series
Orientation
L1
L2
SETPT/
RESET
Vertical
The Series BGM Digital Bar Graph Meter is extremely durable and can replace a wide
range of analog meters. The 4-digit display will significantly reduce the potential for
human error in reading by eliminating errors commonly produced by the viewing angle
when reading analog meters. This series has a key pad that allows for easy access of
features without complex menu structures. With the combined ability to create a wide
range of custom faceplate and the optional NEMA 4X bezel, the Series BGM can be used
in a variety of applications. The LED bar graph adds a visual indicator of the measured
value so that it can be visually analyzed, preventing accidents or system failures from
happening.
BGM-H00-NWD-AE-AO
Bar Graph Meter
Horizontal
Vertical
None
NEMA 4X•
None
2 Relay Outputs
None
Voltage Retransmission
120 VAC 50/60 Hz
5 to 12 VDC
10 to 30 VDC
0 to ±10 VDC
4 to 20 mA
0 to 5 VDC
Feet
FPM
Inches w.c.
Inch/sec
Level
Tank Level
0 to 5
0 to 10
0 to 20
0 to 30
0 to 40
0 to 50
0 to 75
0 to 100
Panel Meters/
Indicators
VALLEY
>
21/64
[8.33]
21/32
[16.51]
SPECIFICATIONS
Inputs: 0 to ±10 VDC or 4 to 20 mA.
Accuracy: ±0.05% FS.
Power Requirements: 120 VAC 50/60 Hz, 5 to 12 VDC, or 10 to 30 VDC model
dependent.
Power Consumption:
120 VAC: 2.4 W @ 20 mA max;
5 to 12 VDC: 1.2 W @ 100 mA max;
10 to 30 VDC: 1.5 W @ 50 mA max.
Display:
LEDDisplay: 4 red colored digits, 0.3 height;
LED Graph: 31 element bar, 0.2 W x 3.1 L (5.08 mm W x 78.74 mm L).
Decimal Point: 3 positions, user selectable.
Temperature Limits:
Operating: -13 to 176°F (-25 to 80°C);
Storage: -67 to 176°F (-55 to 80°C).
Enclosure Rating: NEMA 1 or NEMA 4X• , model dependent IP65 front.
Electrical Connections: Removable screw terminal blocks.
Outputs: 2 SPST relay outputs (optional).
Switch Rating: 1 A @ 200 V.
Enclosure Material:
Bezel: Black epoxy enameled steel;
Window: Acrylic;
Case and Mounting Bracket: 304 SS.
Time Delay: 0.5 sec.
Weight: 40 oz (1.13 kg).
ACCESSORY
A-BGM-RPM, Remote Programmer Module
*Note: Contact factory for additional options.
• NEMA4Xoption requires A-BGM-RPMfor programming.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
353
Annunciator/Alarm Modules
PROCESS CONTROL
354_Layout 1 7/8/14 11:25 AM Page 354
Series
SC1
Process/Temperature Alarm Switch Module
Two Form C (SPDT) Switches, Small Size, Mounts Easily on 35 mm DIN Rail
0.886˝
[22.5]
3.88˝
[98.5]
ALL DIMENSIONS IN INCHES (MILLIMETERS)
DIN EN 50022-35
(NOT SUPPLIED)
1.40˝
[35.3]
2.95˝
[75]
ADAPTOR
BRACKET
FOR SURFACE
MOUNTING
(OPTIONAL)
3.88˝
[98.5]
The Series SC1090 Limit/Alarm Switch Modules are on-off or limit switches with field
selectable inputs. Input type can be either a process signal, thermocouple, or RTD based on
the model. Input type, scale range, and output type selection are made through easily accessible
switches without the need to open the product. Each unit has two form C (SPDT) relays
which can operate independently, or be logically connected to operate as a DPDT output. A
two color LED indicator indicates the status of each output relay. These units mount easily
on a standard 35 mm DIN rail. Low Voltage (SCLXXXX) units are also available.
Model
SC1090
SC1290
Input
4 to 20 mA, 10 to 50 mA, 0 to 20 mA,
0 to 10 V, -10 to 10 mV
Thermocouple Type J, K, R, S, T, E
SC1490
RTD Pt1000 Ni100, Ni120, Cu10,
Ni-Fe1000, N-Fe2000
SCL1090 4 to 20 mA, 10 to 50 mA, 0 to 20 mA,
0 to 10 V, -10 to 10 mV
SCL1290 Thermocouple Type J, K, R, S, T, E
SCL1490 RTD Pt1000 Ni100, Ni120, Cu10,
Ni-Fe1000, N-Fe2000
Power
Supply
85 to 265
VDC/VAC
85 to 265
VDC/VAC
85 to 265
VDC/VAC
12 to 24
VDC/VAC
12 to 24
VDC/VAC
12 to 24
VDC/VAC
SPECIFICATIONS
Input: See table.
Power Supply:
SCmodels:85 to 265 VDC/VAC, 50
to 400 Hz;
SCL models:12 to 24 VDC/VAC, 50
to 400 Hz.
Isolation: 1500V rms between outputs,
input, and power.
Set Points: Adjustable 0 to 100% of
span.
Deadband: Adjustable 0.25% to 100%
of span.
Drift: ±0.02%/°C typical ±0.05%/°C
maximum.
Ambient Temperature Range:
Operating: 32 to 131°F (0 to 55°C);
Storage: -40 to 176°F (-40 to 80°C).
Excitation Current: (SC1490) Cu10
= 5 mA; Plt 100, Ni 100, Ni 120 =
500A; Plt 500, NiFe 1000 = 100
A; Plt 1000 = 50 A.
Lead Compensation Error: (SC1490)
0.02%/.
Open Lead Protection: (SC1490)
upscale only.
Input Impedance:
SC1090:Voltage input = 1 M,
current input = 10;
SC1290:3 M.
Sensor Burnout Protection:
Selectable.
Relay Output: Form C, SPDT, one per
set point, 5A @ 250 VAC, resistive.
Latch Circuit Reset: Automatic at
power up. Manual with reset switch on
front of module.
Indicators: One dual color LED per set
point. Red = relay on, green = relay off.
Wiring Terminals: Screw driven
compression type.
ACCESSORY
A-360, Aluminum DINRail 1 m
Series
AN2
Indicating Alarm Annunciator
Up to 8 Inputs, Integral Power Supply
37/64 [14.68]
3-29/32
[99.22]
4-5/32
[105.57]
3-9/16
[90.49]
3-1/2
[88.9]
4-7/32
[107.16]
1-31/32
[50]
2-7/32
[56.36]
The Series AN2 Indicating Alarm Annunciator provides visible and audible alarms
for up to eight inputs. The annunciator also has two SPDT relay outputs that can be used
to initiate external alarms, buzzers, or paging devices. The Integral 24 VDC power supply
can power most level, temperature, pressure, and flow switches. Audible alarm conditions
can be acknowledged, reset, or silenced either via the front panel push buttons or the rear
terminal block. The Series AN2 can be set to any common ISA sequences including FirstOut.
Number of
Model
Outputs
Power Supply
AN24-1 4
85 to 265 VAC
AN24-2 4
12 to 36 VDC
AN28-1 8
85 to 265 VAC
AN28-2 8
12 to 36 VDC
354
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Inputs: NO or NCswitches, open
collector transistor (open circuit voltage
= 3.3 VDC); Logic levels: LO = 0 to 0.9
VDC, HI = 2.4 to 28 VDC (100 K
input impedance).
Outputs: Two SPDT relay (3 A @ 250
VAC or 30 VDC, resistive; 1/14 HP @
125/250 VAC, inductive).
Temperature Limits: -40 to 149°F (-40
to 65°C).
Power Requirements: 85 to 265 VAC
50/60 Hz, 90 to 265 VDC; 12 to 36
VDC, 12 to 24 VAC(depending on
model).
4
[101.6]
4-13/16
[22.24]
Power Consumption: 20 W (6 W on
low voltage models).
Mounting: 1/8 DIN.
Housing Material: ULrated 94V-0
high impact plastic.
Enclosure Rating: NEMA 4X (IP66)
front panel.
Weight: 9.6 oz (272 g).
Agency Approvals: CE, UL.
355_Layout 1 7/8/14 11:25 AM Page 355
PROCESS CONTROL
Series
SC4
®
Iso Verter II Signal Conditioning Modules
Accepts Virtually All Standard Process Signals
0.886
[22.5]
1.400
[35.5]
3.880 [98.5]
Linearized and isolated RTD and Thermocouple transmitters are part of the Series
SC4000 Iso Verter® II Signal Conditioning Modules. These modules completely isolate the
input from the output and from ground. Compatible with industry standard 35 mm DIN
Rail mount transmitters and isolators, these modules are easily applied in new or existing
installations.
The SC4380 Process Signal Converter/Isolator accepts virtually all standard
process signals as an input, and isolates and retransmits the signal in either the same units
or virtually any other standard process signal. The SC4380 can be field programmed for
reverse or direct action and can receive and transmit single sided or bipolar* signals. Low
Voltage units (SCL) are also available.
The SC4151 RTD Transmitters each offer a fixed scale range input (selected when
ordered) and a linearized, isolated, field selectable 4 to 20 mA or 0 to 10 VDC output.
Output is selected by simple switch settings. Low Voltage units (SCL) are also available.
The SC4130 Thermocouple Transmitter offers a fixed scale range input (selected
when ordered) and a linearized, isolated, field selectable 4 to 20 mA or 0 to 10 VDC output.
Output is selected by simple switch settings.
Low Voltage units (SCL) are also available.
Note: The term •bipolarŽ refers to an input or output that crosses zero volts. Certain
devices have ranges that run from minus to plus voltages (eg. -1 to +5 VDC, -10 to
+10 VDC, etc.). The SC4380 Iso Verter® II can be set up to accept a bipolar signal
input or provide a bipolar output.
ACCESSORY
A-360, Aluminum DINRail 1 m
SPECIFICATIONS
Isolation: 1500 VAC RMS.
Linearity: 0.1% of full-scale.
Drift: ±0.02%/°C typical, ±0.05%/ °C maximum.
Power Supply: SC: 85 to 265 VDC/VAC 50 to 400 Hz; SCL: 12 to 24 VDC/VAC 50
to 400 Hz.
Output Loads: Current: 600 max voltage: 500 min (20 mA maximum).
Input Characteristics: SC4380: Voltage: 1 M impedance; Current: 10 ;
SC4151: RTD Search current < 500 A; SC4130: 3 M impedance.
Case Size: 0.866 W (22.5 mm) x 2.950 H (75.0 mm) 3 3.880 D (98.5 mm).
Mounting: Mounts on industry standard 35 mm DIN Rail (DIN EN50022-35).
To Order Use Range Code as Suffix:
SC4130 & SCL4130
Model SC4130 Range Codes Model SCL4130 Range Codes
A = J, -100 to 200°C
A = J, -100 to 200°C
C = J, 0 to 100°C
C = J, 0 to 100°C
D = J, 0 to 500°F
D = J, 0 to 500°F
E = J, 0 to 250°C
E = J, 0 to 250°C
F = J, 0 to 750°C
F = J, 0 to 750°C
G = J, 0 to 1000°F
G = J, 0 to 1000°F
H = K, -150 to 350°F
H = K, -150 to 350°F
J = K, -100 to 200°C
J = K, -100 to 200°C
K = K, 0 to 500°F
K = K, 0 to 500°F
L = K, 0 to 250°C
L = K, 0 to 250°C
M = K, 0 to 1000°F
M = K, 0 to 1000°F
N = K, 0 to 500°C
N = K, 0 to 500°C
P = K, 0 to 2000°F
P = K, 0 to 2000°F
R = K, 0 to 1000°C
R = K, 0 to 1000°C
S = T, -300 to 250°F
S = T, -300 to 250°F
T = T, -200 to 200°C
T = T, -200 to 200°C
SC4151 & SCL4151
Model SC4151 Range Codes
A = DIN, -100 to 200°C
B = DIN, 0 to 100°C
C = DIN, 0 to 150°C
D = DIN, 0 to 200°F
E = DIN, 0 to 200°C
F = DIN, 0 to 400°F
G = DIN, 0 to 250°C
H = DIN, 0 to 500°F
J = DIN, 0 to 500°C
K = DIN, 0 to 1000°F
Model SCL4151 Range Codes
A = DIN, -100 to 200°C
B = DIN, 0 to 100°C
C = DIN, 0 to 150°C
D = DIN, 0 to 200°F
E = DIN, 0 to 200°C
F = DIN, 0 to 400°F
G = DIN, 0 to 250°C
H = DIN, 0 to 500°F
J = DIN, 0 to 500°C
K = DIN, 0 to 1000°F
SC4380 & SCL4380 Operating Ranges
Inputs
Current
0 to 5 mA
0 to 10 mA
0 to 10 mA
0 to 20 mA
0 to 50 mA
0 to 100 mA
1 to 5 mA
4 to 20 mA
10 to 50 mA
Voltage
0 to 100 mV
0 to 200 mV
0 to 500 mV
0 to 1 V
0 to 5 V
0 to 10 V
1 to 5 V
2 to 10 V
Outputs
Current
0 to 1 mA
0 to 5 mA
0 to 20 mA
1 to 5 mA
4 to 20 mA
Voltage
0 to 1 V
0 to 5 V
0 to 10 V
1 to 5 V
2 to 10 V
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
355
Signal Conditioners/
Isolating Transmitters
2.950
[75]
PROCESS CONTROL
356_Layout 1 7/8/14 11:24 AM Page 356
Series
861SSR
DIN/Panel Mountable Solid State Relay
10 Amp, SPST-NO Operation, Internal Heat Sink
RoHS
45/64
[17.78]
19/32
[15.24]
19/64
[7.62]
13/64
[5.08] 3-1/2
[88.90]
GREEN
LED
3-19/32
[91.44]
1-51/64
[45.72]
1-13/32
[35.56]
Relays
2-19/32
[66.04]
3/32
[2.54]
ø13/64
[ø5.08]
19/32
[15.24]
Series 861SSR DIN/Panel Mountable Solid State Relay features an internal heat
sink, bistable clips for DIN rail or panel mounting and an LED indicator light. It is a
completely solid state relay - it has NO moving parts. The DSSR provides reliable switching
and long-life operation in applications where high inrush currents or induced currents can
affect mechanical state relay operation. The compact housing also minimizes panel space.
AC Operated
Model
861SSR210-AC-1
DC Operated
Model
861SSR210-DC-1
Input Voltage Range
90 to 280 VAC
Rated Current Load
10 amp
Input Voltage Range
3 to 32 VDC
Rated Current Load
10 amp
ACCESSORY
A-360, Aluminum DINRail 1 m
Series
62
45/64
[17.78] 1-13/32
[35.56] 2-37/64
[65.53]
SPECIFICATIONS
Operating and Load Voltage Range:
24 to 280 VAC.
Sensor Current: 10 amps max.
Electrical Connection: Screw
terminals.
Switching Operation: SPST normally
open.
Switching Type: Zero cross.
3/32
[2.54]
Temperature Limits: -22 to 176°F
(-30 to 80°C).
Voltage Loss: 1.6 VAC max.
Output Leakage Current: 10 mA max.
Housing: Lexan 943.
Weight: 4.1 oz.
Agency Approvals: CE, RoHS, cUL,
UL.
FEATURES
€ Internal heat sink
€ No contact bounce
€ No mechanical delay
€ DIN and panel mountable
€ 17 mm wide modular design
Hockey Puck Solid State Relay
10 or 25 Amp, SPST-NO Operation
RoHS
1-3/32
[27.94]
1
LED
OUTPUT
2
SOLID STATE RELAY
HSSR-XXA-XX
4
INPUT
(INPUT VOLTAGE)
3
1-45/64
[43.18]
1
[25.40]
DATE CODE
1-51/64
[45.72]
Series 62 Hockey Puck Style Solid State Relay features a terminal cover and LED
status indicator. The optically coupled circuitry isolates the input terminals from the output
terminals to give the relay 100% pure solid state performance.
AC Operated
Model
6210AXXSZS-AC90
6225AXXSZS-AC90
DC Operated
Model
6210AXXSZS-DC3
6225AXXSZS-DC3
356
Input Voltage Range
90 to 280 VAC
90 to 280 VAC
Rated Current Load
10 amp
25 amp
Input Voltage Range
3 to 32 VDC
3 to 32 VDC
Rated Current Load
10 amp
25 amp
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Operating and Load Voltage Range:
24 to 280 VAC.
Electrical Connection: Spade lug.
Switching Operation: SPST normally
open.
Switching Type: Zero cross.
FEATURES
€ Hockey puck design
€ Finger-safe cover
€ LED status indicator
€ Optically coupled circuitry
1-13/32
1 [35.56]
[25.40]
2-19/64
[58.42]
Temperature Limits: -40 to 176°F
(-40 to 80°C).
Voltage Loss: 1.6 VAC max.
Output Leakage Current: 10 mA max.
Housing: Polyamide 6.
Weight: 3.5 oz.
Agency Approvals: CE, RoHS, cUR,
UR.
357_Layout 1 7/8/14 11:24 AM Page 357
Electromechanical Relay
30 Amp, SPDT and DPDT Operation
1-5/8
[41.40]
19/64
[7.62] 1-15/64
1-1/16
[31.50]
[26.92]
R 5/64
[R 1.80]
5/64
[2.03]
SPDT
FEATURES
€ Compact size
€ 30 amp rating
€ Quick-connect terminals
€ Flange mounting
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
24 VAC 50/60 Hz
120 VAC 50/60 Hz
DC Operated Model
9AS5D5224
92S11D22D12
92S11D22D24
Input Voltage
24 VDC
12 VDC
24 VDC
1-3/32
[27.94]
2-3/64
[51.85]
2-11/16
[68.07]
2-11/32
[59.44]
SPDT
The 9 Electromechanical Relay is small in size, features Class F insulation for a max
coil temperature of 155°C, quick-connect terminals for simple connection, and is panel
mountable. The relays are compact and impervious to shock and vibration. The EMR is
perfect for motor control, power supplies, lighting, and compressor loads.
AC Operated Model
9AS5A5224
9AS5A52120
92S11A22D24
92S11A22D120
1
[25.25]
0.25 X 0.033 [6.35 X 0.84] QUICK CONNECT
TEMINALS WITH SOLDER HOLE
Ø3/32
FOR
#8
SCREWS
[Ø2.29]
1-39/64
1-11/32 3/16
1-3/16 [40.89]
[34.29] [4.83]
[29.97]
Coil
Resistance
500
3000
250
1600
Coil
Resistance
576
86
1600
Series
725
DPDT
SPECIFICATIONS
Operating and Load Voltage Range: 12-277 VAC; 5-110 VDC.
Electrical Connection: Quick-connect tab terminals. SPDT 0.187 coil
terminal/0.25 contact terminal; DPDT 0.25 coil terminal/0.25 contact terminal.
Switching Operation: SPDT or DPDT.
Electrical Rating: SPDT: NO 30 A @ 240 VAC / 28 VDC; NC 10 A @ 240 VAC /
28 VDC; DPDT: 30 A @ 240 VAC 20 A @ 28 VDC.
Temperature Limits: Storage: -40 to 185°F (-40 to 85°C); Operation: -40 to 131°F
(-40 to 55°C).
Voltage Loss: 2.5 VA (VAC); 1W (VDC).
Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical).
Housing: Polyester resin.
Weight: 1.16 oz (45 g) (SPDT); 3 oz (85 g) (DPDT).
Agency Approvals: CE, RoHS, cUL, UL, (EMR-XXXX-DPDT), cUR, UR (EMRXXXX-SPDT).
ACCESSORIES
16-9ADIN1, Din Adaptor
A-360, Aluminum DINRail 1 m
Power Relay
SPST-NO Operation, 30 Amp or DPST-NO Operation, 25 Amp
RoHS
3/16
[4.90] 5/16
[8.00]
1-19/64
[33.10]
1/4
[6.30]
2-3/32
[53.20]
The Series 725 Power Relays are designed to switch high current loads in the most
demanding of applications. By having a high dielectric strength from the coils to the
contacts, the relay is able to withstand severe voltage surges and spikes as commonly seen
in inductive loads. Flag and LED indicators show the relay status and if there is power to
the coil. A push-to-test button allows for manual testing of the relay operation without
providing an electrical trigger. Integral mounting ears allows the relay to be panel
mounted or DIN rail mounted without the need for an external socket. For quicker wiring
installation, the Series 725 is available with quick connect tabs or screw terminals.
ACOperated Model
725AXXBC3ML-24A
725AXXBC3ML-120A
725AXXBC3ML-240A
725AXXSC3ML-120A
725AXXSC3ML-240A
725BXXBC3ML-24A
725BXXBC3ML-120A
725BXXBC3ML-240A
725BXXSC3ML-24A
725BXXSC3ML-120A
725BXXSC3ML-240A
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
DC Operated Model
725AXXBC3ML-24D
725AXXSC3ML-24D
725BXXBC3ML-24D
725BXXSC3ML-24D
Input Voltage
24 VDC
24 VDC
24 VDC
24 VDC
Rated
Current Load
30 Amp
30 Amp
30 Amp
30 Amp
30 Amp
25 Amp
25 Amp
25 Amp
25 Amp
25 Amp
25 Amp
Rated
CurrentLoad
30 Amp
30 Amp
30 Amp
30 Amp
Electrical
Connections
Quick connect
Quick connect
Quick connect
Screw
Screw
Quick connect
Quick connect
Quick connect
Screw
Screw
Screw
Electrical
Connections
Quick connect
Screw
Quick connect
Screw
1-31/32
[50.00]
2-21/64
[59.10]
2-43/64
[67.70]
1-19/64
[33.10]
1-15/16
[49.40]
SPECIFICATIONS
Operating and Load Voltage Range: 24 to 240 VAC 50/60 Hz; 24 VDC.
Operating Range (% of Nominal): 75 to 110%.
Electrical Connection: Silver alloy quick-connect terminals/screw terminals.
Switching Operation: SPST-NO or DPST-NO.
Electrical Rating: SPST-NO: 30 A @ 277 VAC 50/60Hz or 30 VDC; DPST-NO: 25
A @ 277 VAC 50/60Hz or 30 VDC.
Temperature Limits: Storage: -4 to 131°F (-20 to 55°C); Operation: -58 to 212°F
(-50 to 100°C).
Power Consumption: 2.5 VA or 1.9 W.
Cycle Life: 100,000 cycles (electrical); 5,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 4.2 oz (120 g).
Agency Approvals: CE, CSA, RoHS, cUR, UR.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
357
Relays
DPDT
1-61/64
[49.53]
RoHS
PROCESS CONTROL
Series
9
PROCESS CONTROL
358_Layout 1 7/29/14 3:39 PM Page 358
Series
199
Open Style Power Relays
DPDT, 40 Amp Rating (AC or DC)
RoHS
2-5/16
[58.80]
2-1/2
[63.50]
Relays
3-1/8
[79.40]
The Series 199 Open Style Power Relays are designed for high AC and DC current
applications up to 40 Amps. These mercury-free DPDT relays are available in a variety of
trigger voltages and coil resistances to fit most common applications. The riveted housing
construction increases the durability and reduces the effects of vibration on the relay.
ACOperated Model
W199AX-13
W199AX-14
W199AX-15
DC Operated Model
W199X-13
Input Voltage
24 VAC, 50/60 Hz
120 VAC, 50/60 Hz
240 VAC, 50/60 Hz
Input Voltage
24 VDC
Series
750H
Coil Resistance
12
290
1200
Coil Resistance
290
SPECIFICATIONS
Operating and Load Voltage Range: 24 to 240 VAC, 24 VDC.
Operating Range (% of Nominal): 85 to 110% (AC operated); 80 to 110% (DC
operated).
Electrical Connection: AgSnO screw terminals.
Switching Operation: DPDT.
Electrical Rating: 40 A @ 300 VAC/28 VDC; 5 A @ 480/600 VAC.
Temperature Limits: Storage: -67 to 212°F (-55 to 100°C); Operation: -67 to
131°F (-55 to 55°C).
Power Consumption: 10 VA, 4 W.
Cycle Life: 100,000 cycles (electrical); 1,000,000 cycles (mechanical).
Housing: Plastic phenolic.
Weight: 8 to 11 oz (227 to 312 g).
Agency Approvals: CE, CSA, RoHS, cUL, UL, cUR, UR.
Hermetically Sealed Relay
12 Amp, DPDT Operation (8-pin) or 3PDT Operation (11-pin)
RoHS
1-29/64
[37.00]
1-1/2
[38.00]
1-3/32 [27.94]
2-63/64
[76.00]
1-39/64
[40.89]
1-7/16
[36.58]
1-63/64
[50.30]
3-5/32
[80.00]
1-37/64
[40.00]
5/32
[3.81]
1-11/32
[34.20]
The Series 750H Hermetically Sealed Electromechanical Relay is designed to be
used in Class I Division 2 hazardous area locations. Gold flashed contacts provide
protection against oxidation in low current / voltage applications. 8-pin and 11-pin sockets
are available to allow quick and easy installation for both surface and DIN rail mounting.
ACOperated
Model
750XBXH-24A
750XBXH-120A
750XCXH-24A
750XCXH-120A
Input
Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
24 VAC 50/60 Hz
120 VAC 50/60 Hz
Coil
Resistance
72 Ω
1700 Ω
72 Ω
1700 Ω
Number of Pins
8-pin
8-pin
11-pin
11-pin
ACCESSORIES
70-750DL11-1, Socket for 750H series relay (11-pin)
70-750DL8-1, Socket for 750H series relay (8-pin)
70-ASMM-24, Protection modules, MOV suppressor, 24 VAC/VDC
70-ASMM-120, Protection modules, MOV suppressor, 24 VAC/VDC
16-750/788CBJ-1, Coil bus jumpers
358
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Operating and Load Voltage Range: 24 to 120 VAC.
Operating Range (% of Nominal): 85 to 110% (AC operated); 80 to 110% (DC
operated).
Electrical Connection: Silver alloy plug-in contacts.
Switching Operation: DPDT (8-pin models) or 3PDT (11-pin models).
Electrical Rating: 12 A @ 120/240 VAC (50/60 Hz) or 28 VDC.
Temperature Limits: Storage: -40 to 185°F (-40 to 85°C); Operation: -40 to 131°F
(-40 to 55°C).
Power Consumption: 1.2 VA; 0.9 W.
Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical).
Housing: Metal.
Weight: 4.6 oz (130 g).
Enclosure Rating: Class 1 Div. 2.
Agency Approvals: CE, RoHS, cUL*, UL*, cUR, UR.
*When used with listed sockets.
359_Layout 1 7/8/14 11:22 AM Page 359
PROCESS CONTROL
Series
782H
Hermetically Sealed Ice Cube Relays
5 Amp, 4PDT Operation, Class 1 Div II Rated
RoHS
1-9/32
[32.54]
CHINA
T-CODE T4A
BOTTOM VIEW
Relays
1/64
[0.51]
QUALIFIED FOR CLASS 1
DIVISION 2. GROUPS A, B, C, D
HAZARDOUS LOCATIONS
WHEN USED WITH APPROVED
SOCKETS. USE HOLD DOWN
CLIP WHEN SOCKET MOUNTED
1-5/32
[29.36]
31BN
WARNING: DO NOT DISCONNECT
WHEN CIRCUIT IS LIVE UNLESS
AREA IS KNOWN TO BE
NON-HAZARDOUS
782XDXH21XXX VXC
D932ADL
1/4
[6.35]
CONTACTS
5 AMP 120/240 VAC, 30 VDC
IND. CONT. EQ.
FOR USE IN
HAZARDOUS LOCATIONS
29/32
[23.10]
Picture shown with socket accessory
(sold separately)
The Series 782H Hermetically Sealed Ice Cube Relay is suitable for switching up
to four circuits in a hazardous environment. It features a hermetically sealed housing and
a safety seal to withstand a wash-down. The plug-in socket is easy to mount and remove
from crowded DIN rails.
Coil Resistance
4430
Coil Resistance
650
ACCESSORY
70-782D14-1, Socket for 782H Series Relay
Hazardous Rated Solid State Relays
15 Amp Rating, SPST-NO, Internal Heat Sink
2-9/16 [65.00]
1-23/64
[34.60]
9/64
[3.40]
11/16
[17.60]
5/8
[16.00]
INPUT
Caution!
High Temperature
24-280 VAC
OUTPUT
861HSSRXXX-XX-X
INPUT: (VOLTAGE)
10A
1-25/32
[45.30]
2-5/8
[66.80]
(VOLTAGE)
3-41/64
[92.40]
3-35/64
[90.00]
861HSSRXXX-XX-X
Patent Pending
CERTIFIED FOR
CLASS 1
DIVISION 2
HAZARDOUS
LOCATIONS
GROUPS 1, B, C, & D
Derating
1-13/32
[35.60]
RoHS
Derating
Series
861H
DIN RAIL
Input Voltage
120 VAC 50/60 Hz
Input Voltage
24 VDC
#14 AWG COPPER WIRE MAXIMUM
RATED AT 75°C
7.1 lb-in TORQUE MAXIMUM
ACOperated Model
782XDXH21-120A
DCOperated Model
782XDXH21-24D
SPECIFICATIONS
Operating and Load Voltage Range: 120 VAC, 24 VDC.
Electrical Connection: Silver alloy plug-in contacts.
Switching Operation: 4PDT.
Electrical Rating: 5 A @ 120/240 VAC 50/60 Hz or 30 VDC.
Temperature Limits:
Storage: -40 to 185°F (-40 to 85°C);
Operation: -40 to 158°F (-40 to 70°C).
Power Consumption: 1.2 VA; 0.9 W.
Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical).
Housing: Metal.
Weight: 1.6 oz (45 g).
Agency Approvals: CE, CSA, RoHS, cUL, UL, cUR, UR.
9/16
[14.30]
The Series 861H Hazardous Rated Solid State Relay provides reliable switching
and long life operation in some of the most demanding applications, such as medical
equipment, mining, oil and gas. It integrates an internal heat sink and internal snubber
into a compact housing to save space in the panel. In order to reduce installation time,
integral tabs can be used to snap the relay onto a DIN rail or surface mount to a wall inside
the panel. LED indicator lights give the user quick visual indication of the switch status.
The 861H is intrinsically safe rated for Class 1, Division 2 Groups A, B, C and D.
Model
861HSSR210-AC-1
861HSSR210-DC-1
861HSSR115-DD
Input Voltage
90 to 280 VAC
3 to 32 VDC
3.5 to 32 VDC
Load Voltage
24 to 280 VAC
24 to 280 VAC
3 to 50 VDC
Rated Current
10 amp
10 amp
15 amp
SPECIFICATIONS
Electrical Connection: Screw terminals.
Switching Operation: SPST normally open.
Switching Type: AC/DC: Zero cross; DD: DC switching.
Temperature Limits:
Storage: -40 to 212°F (-40 to 100°C);
Operation: -22 to 176°F (-30 to 80°C).
Voltage Loss: AC/DC: 1.6 VAC max; DD: 0.5 VDC max.
Output Leakage Current: AC/DC: 10 mA max; DD: 0.25 mA max.
Housing: Polycarbonate.
Hazardous Classification: Class 1 Division 2; Hazardous Locations: Groups A, B,
C and D.
Weight: 4.1 oz (127.1 g).
Agency Approvals: RoHS, cUR, UR.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
359
SPDT Ice Cube Relays
20 Amp, SPDT Operation
RoHS
1-19/32
[40.60]
1-3/32
[27.09]
(VOLTAGE)
RoHS
WIRING DIAGRAM
NEMA - IEC
OBSERVE POLARITY
DC COILS VIEWED
FROM PIN END
Relays
35/64
[14.00]
When used with socket
Current limited 10
Reading at relay or
Socket whichever is less
Series
781
COIL: XXX VXC
20A, 277 VAC 50/60Hz, 28 VDC
CSA 1DA, 277 VAC, RES
1/2HP. 110-120 V 50/60Hz
1HP. 220-250VAC 50/60Hz
8300 PILOT DUTY
PROCESS CONTROL
360_Layout 1 7/8/14 11:22 AM Page 360
Picture shown with socket accessory
(sold separately)
The Series 781 Electromechanical Ice Cube Relay is a full-featured SPDT relay
that can be used to handle loads up to 20 amps for AC or DC circuits. It features a flag
status indicator and a LED status lamp to let the user know when the relay is activated. In
order to differentiate between AC and DC actuated models, the push-to-test button is colorcoded. For testing the operation, a removable lock-down lever holds the test button in place.
The clear plastic housing gives a view of the contacts, and there is a removable I.D tag for
labeling the circuit.
ACOperated Model
781XAXM4L-24A
781XAXM4L-120A
781XAXM4L-240A
DCOperated Model
781XAXM4L-24D
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
Input Voltage
24 VDC
Coil Resistance
180
4430
15720
Coil Resistance
750
Series
782
SPECIFICATIONS
Operating and Load Voltage Range: 24 to 240 VAC; 24 VDC.
Electrical Connection: Silver alloy plug-in contacts.
Switching Operation: SPDT.
Electrical Rating: 20 A @ 120 / 277 VAC (50/60Hz) or 28 VDC.
Temperature Limits:
Storage: -40 to 185°F (-40 to 85°C);
Operation: -40 to 131°F (-40 to 55°C).
Power Consumption: 0.9 VA; 0.7W.
Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 1.02 oz (29 g).
Agency Approvals: CE, CSA, RoHS, cUL, UL, cUR, UR.
ACCESSORY
70-781D5-1A, Socket for 781 Series Relay
DPDT Ice Cube Relays
15 Amp, DPDT Operation
RoHS
53/64
[21.00]
19/64
[7.37]
IND. CONT. EQ.
ALTERNATE NEMA OR
IEC NUMBERS,
VIEWED FROM PIN
SIDE
When used with socket 70-458-1,
70-7820-1 or 70-78208-1
Current limited to reading of
relay or socket whichever is less
1-3/32
[27.90]
15A, 120 VAC 50/60Hz RES
12A, 277 VAC 50/60Hz RES
10A 277 VAC RES. (CSA)
12A, 28 VDC
1/2 HP 120 VAC
1 HP 250 VAC
8300 PILOT DUTY
1/64
[0.50]
1-17/32
[39.10]
3/16
[4.75]
Picture shown with socket accessory
(sold separately)
The Series 782 Electromechanical Ice Cube Relay is a full-featured DPDT relay
that can be used to switch two different devices with a single trigger. With a rating of 15
amps, the relay can be used to stop and start small fans, motors, and pumps directly. It
features a flag status indicator and a LED status lamp to let the user know when the relay
is activated. In order to differentiate between AC and DC actuated models, the push-totest button is color-coded. For testing the operation, a removable lock-down lever holds the
test button in place. The clear plastic housing gives a view of the contacts, and there is a
removable I.D tag for labeling the circuit.
ACOperated Model
782XBXM4L-24A
782XBXM4L-120A
782XBXM4L-240A
DCOperated Model
782XBXM4L-24D
360
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
Input Voltage
24 VDC
Coil Resistance
180
4430
15720
Coil Resistance
650
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Operating and Load Voltage Range: 24 to 240 VAC; 24 VDC.
Electrical Connection: Silver alloy plug-in contacts.
Switching Operation: DPDT.
Electrical Rating: 15 A @ 120 VAC 50/60Hz; 12 A @ 277 VAC 50/60 Hz or 28
VDC (UL); 10 A @ 277 VAC 50/60 Hz (CSA).
Temperature Limits:
Storage: -40 to 185°F (-40 to 85°C);
Operation: -40 to 131°F (-40 to 55°C).
Power Consumption: 1.2 VA; 0.9W.
Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 1.3 oz (36 g).
Agency Approvals: CE, CSA, RoHS, cUL, UL, cUR, UR.
ACCESSORY
70-782D8-1A, Socket for 782 Series Relay
361_Layout 1 7/8/14 11:21 AM Page 361
PROCESS CONTROL
Series
783
3PDT Ice Cube Relays
15 Amp, 3PDT Operation
3/16
[4.75]
RoHS
1-37/64
[40.00]
1-7/32
[30.80]
1/64
[0.51]
LISTED 367C
IND. CONT. ED.
When used with socket 70-78301
Current limited to rating at relay
or socket whichever is less
1-3/32
[27.90]
(VOLTAGE)
Relays
17/64
[6.57]
Picture shown with socket accessory
(sold separately)
The Series 783 Electromechanical Ice Cube Relay is a full featured 3PDT relay
that can control up to 3 devices with a single trigger. It features a flag status indicator and
a LED status lamp to let the user know when the relay is activated. In order to differentiate
between AC and DC actuated models, the push-to-test button is color-coded. For testing
the operation, a removable lock-down lever holds the test button in place. The clear plastic
housing gives a view of the contacts, and there is a removable I.D tag for labeling the circuit.
The Series 783 can handle loads up to 15 amps.
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
Input Voltage
24 VDC
Coil Resistance
103
2770
Coil Resistance
400
Series
784
Temperature Limits: Storage: -40 to
185°F (-40 to 85°C); Operation: -40 to
131°F (-40 to 55°C).
Power Consumption: 1.5 VA; 1.4 W.
Cycle Life: 200,000 cycles (electrical);
10,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 2.1 oz (60 g).
Agency Approvals: CE, CSA, RoHS,
cUL, UL, cUR, UR.
ACCESSORIES
70-783D11-1A, Socket for 783 Series Relay
70-ASMM-24, Protection Modules, MOV Suppressor, 24 VAC/VDC
70-ASMM-120, Protection Modules, MOV Suppressor,120 VAC/VDC
70-ASMD-250, Protection Modules, Protection Diode, 6 to 250 VDC
16-750/788CBJ-1, Coil Bus Jumpers
4PDT Ice Cube Relays
15 Amp, 4PDT Operation
RoHS
1-3/32
[27.90]
17/64
[6.60]
1/64
[0.50]
When used with socket 70-78401.
Current limited to rating of relay
or socket whichever is less.
1-19/32
[40.60]
784XDXM4L
COIL: XXX VXC
367G IND. CONT. EQ.
ACOperated Model
783XCXM4L-24A
783XCXM4L-120A
DCOperated Model
783XCXM4L-24D
SPECIFICATIONS
Operating and Load Voltage Range:
24 to 120 VAC; 24 VDC.
Electrical Connection: Silver alloy
plug-in contacts.
Switching Operation: 3PDT.
Electrical Rating: 15 A @ 120 VAC
50/60 Hz; 12 A @ 277 VAC 50/60 Hz or
28 VDC.
RoHS
(VOLTAGE)
1-17/32
[39.10]
3/16
[4.75]
15A, 120 V 50/60 Hz (30A MAX) 1Ø
12A, 28 VDC
12A, 277 V 50/60 Hz (20A MAX) 1Ø
1/2 HP 120 VAC, 3/4 HP 250 VAC 1Ø
8300 PILOT DUTY
Picture shown with socket accessory
(sold separately)
The Series 784 Electromechanical Ice Cube Relay is a full featured 4PDT relay
that can be used to handle loads up to 15 amps for AC or DC circuits. Utilizing the same
trigger, this relay can be used in underground parking garage applications to signal audible
and visual alarms for high levels of carbon monoxide, while opening the dampers and
starting the exhaust fans. It features a flag status indicator and a LED status lamp to let
the user know when the relay is activated. In order to differentiate between AC and DC
actuated models, the push-to-test button is color-coded. For testing the operation, a
removable lock-down lever holds the test button in place. The clear plastic housing gives a
view of the contacts and there is a removable I.D tag for labeling the circuit.
SPECIFICATIONS
Operating and Load Voltage Range:
24 to 120 VAC; 24 VDC.
Electrical Connection: Silver alloy
plug-in contacts.
Switching Operation: 4PDT.
Electrical Rating: 15 A @ 120 VAC
50/60Hz; 12 A @ 277 VAC 50/60 Hz or
28 VDC.
ACOperated Model
784XDXM4L-24A
784XDXM4L-120A
DCOperated Model
784XDXM4L-24D
ACCESSORIES
70-784D14-1, Socket for 784 Series Relay
70-ASMM-24, Protection Modules, MOV Suppressor, 24 VAC/VDC
70-ASMM-120, Protection Modules, MOV Suppressor,120 VAC/VDC
70-ASMD-250, Protection Modules, Protection Diode, 6 to 250 VDC
16-750/788CBJ-1, Coil Bus Jumpers
Input Voltage
24 VAC 50/60 Hz
120 VAC 50/60 Hz
Input Voltage
24 VDC
Coil Resistance
84.5
2220
Coil Resistance
388
Temperature Limits: Storage: -40 to
185°F (-40 to 85°C); Operation: -40 to
131°F (-40 to 55°C).
Power Consumption: 1.5 VA; 1.5 W.
Cycle Life: 200,000 cycles (electrical);
10,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 2.8 oz (80 g).
Agency Approvals: CE, CSA, RoHS,
cUL, UL, cUR, UR.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
361
PROCESS CONTROL
362_Layout 1 7/21/14 1:55 PM Page 362
Series
MCS
Miniature Current Switch
Low Cost, Solid or No Core, LED Confirmation, Adjustable Set Point
RoHS
63/64˝
[25.15]
CurrentTransformers,
Switches
Ø5/32˝
[Ø3.94]
1-21/32˝
[42.25]
1/8˝
[3.18]
2-1/32˝
[51.73]
2-31/64˝
[63.03]
SolidCore
NoCore
The Series MCS Miniature Current Switches are ideal for monitoring the current
usage in fuse boxes and small control panels. Both models have adjustable set points and
LED indication to show there is power to the unit and when the switch activates. Set points
can be adjusted using the potentiometer next to the LED’s.
Due to the size of the switch, it is only offered in solid core and no core versions. The no
core version has terminal blocks which can accept currents up to 1A directly into the unit.
Minimum
Set Point Set Point
Case
Model
Adjustable 0.50
MCS-111050 Solid Core
Adjustable 0.01
MCS-111001 No Core
(Terminal Connection)
Series
CCS
LED
Red/Green
Red/Green
SolidCore
NoCore
SPECIFICATIONS
Amperage Range:
MCS-111050: 0.5 to 50A continuous;
MCS-111001: 0.01 to 1A continuous.
Output Rating: Isolated, N.O. 0.3 A @ 130 V DC/AC.
Power Requirements: None, self-powered.
Hysteresis: 1%.
Response Time: <200 ms.
Temperature Limits: 32 to 122°F (0 to 50°C).
Humidity Limits: 10 to 95% RH (non-condensing).
Enclosure Rating: UL 94V-0 flammability rated ABS, insulation class 600 V.
Weight: 0.5 oz (14.5 g).
Agency Approvals: CE, RoHS, cUL, UL.
Current Switches
Solid or Split Core, LED Visual Confirmation, Fixed or Adjustable Set Point
2-29/32
[74.00]
63/64
[25.00]
33/64
[13.00]
1-9/64
[29.00]
55/64
[22.00]
2-31/64
[63.00]
Ø3/4
[Ø19.00]
3-1/2
[89.00]
Solid Models
The Series CCS Current Switches are ideal for monitoring the operating status of
fans, pumps, and motors. These self-powered switches can be hung or tied directly to cables
or wires. For use on existing installations, split core models can be installed without
disconnecting cables. LED indicators provide a visual confirmation that the current is
flowing through the core. Both fixed and adjustable set points are available. The adjustable
models utilize a potentiometer to easily adjust the set point.
Set Point
Fixed
Adjustable
Fixed
Adjustable
Adjustable
Adjustable
Minimum
Set Point
0.50
1.00
1.00
1.50
1.00
1.50
Dry Contact
Output
Yes
No
Yes
No
Yes
Yes
Model
CCS-121050
CCS-111100
CCS-221100
CCS-211150
CCS-131100
CCS-231150
Case
Solid core
Solid core
Split core
Split core
Solid core
Split core
362
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
LED
Red
Red/Green
Red
Red/Green
Red/Green
Red/Green
3-1/2
[89.00]
2X Ø13/64
[Ø5.00]
1-17/64
45/64
[32.00]
[18.00]
33/64
[13.00]
2-7/16
[62.00]
2X
Ø13/64
[Ø5.00]
43/64
[17.00]
2-3/4
[70.00]
19/32
[15.00]
2-33/64
[64.00]
55/64
[22.00]
55/64
[22.00]
Split Models
4-1/64
[102.00]
SPECIFICATIONS
Amperage Range: 0 to 200 A AC.
Maximum Switch Rating:
For dry contact models: 0.3 A @ 135 VAC/DC;
For non-dry contact models: 1 A @ 240 VAC.
Power Requirements: None, self-powered.
Temperature Limits: -22 to 158°F (-30 to 70°C).
Humidity Limits: 0 to 95% (non-condensing).
Isolation Voltage: 2000 V.
Frequency: 40 to 400 Hz.
Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing.
Approvals: CE, cUL, UL.
363_Layout 1 7/8/14 11:20 AM Page 363
PROCESS CONTROL
Series
SCS
Current Switches
Optional Relay Output, Solid or Split Core Case
1-27/32
[47.0]
RoHS
63/64
[24.9]
1-9/16
[39.6]
2-9/16
[65.0]
2-35/64
[64.5]
2-45/64
[68.6]
Current Transformers/
Switches
1-5/64
[27.4]
Models
SCS-111100 AND SCS-120025
2-9/16
1-1/16
[65.0]
[26.9]
2-35/64
[64.5]
1-5/64
[27.4]
Model
SCS-111100-R
1-1/16
2-9/16
[26.9]
[65.0]
2-45/64
[68.6]
Models
Models
SCS-220015, SCS-220150, AND SCS-211125 SCS-220150-R AND SCS-211125-R
The Series SCS Low Cost Current Switches are ideal for monitoring whether fans,
pumps, or motors are operating. The current flowing through the core of the device powers
the circuit without an external power supply. All models have a built in solid state output
and are easy to install. Optional LED’s and 10 Amp relay modules are available. The Series
SCS is available in both split and solid core configurations.
Model
SCS-120025
SCS-111100
SCS-111100-R
SCS-220015
SCS-220150
SCS-211125
SCS-220150-R
SCS-211125-R
Case
Solid
Solid
Solid
Split
Split
Split
Split
Split
Amperage
Range
.25 to 200 A
1 to 135 A
1 to 135 A
.15 to 200 A
1.5 to 200 A
1.25 to 135 A
1.5 to 200 A
1.25 to 135 A
Set Point
0.25 Fixed
Adjustable
Adjustable
0.15 Fixed
1.5 Fixed
Adjustable
1.5 Fixed
Adjustable
Switch
Mode
Under
Over/Under
Over/Under
Under
Under
Over/Under
Under
Over/Under
Snap-on
Relay
No
No
Yes
No
No
No
Yes
Yes
SPECIFICATIONS
Output: Isolated, 1A @30 VAC/DC max, NO.
External Relay: SPST N.O., 10A at 260 VAC (5A at 30 VDC).
Power Requirements: None, self-powered.
Temperature Limits: 5 to 140°F (-15 to 60°C).
Isolation Voltage: 600 VAC RMS.
Frequency: 50/60 Hz.
Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing.
Agency Approvals: CE, RoHS, cUL, UL.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
363
PROCESS CONTROL
364_Layout 1 7/21/14 1:52 PM Page 364
Series
CCT40/50
Current Transformers
Solid or Split Core, Field Selectable Range
2-29/32
[74.00]
63/64
[25.00]
Current Transformers/
Switches
33/64
[13.00]
1-9/64
[29.00]
55/64
[22.00]
2-31/64
[63.00]
Ø3/4
[Ø19.00]
3-1/2
[89.00]
2X Ø13/64
[Ø5.00]
45/64
[18.00]
33/64
[13.00]
2-7/16
[62.00]
19/32
[15.00]
Power Requirements
Self Powered
Self Powered
Self Powered
Self Powered
Self Powered
Self Powered
15 to 42 VDC,
Loop Powered
CCT50-200 100/150/200 A 4 to 20 mA 15 to 42 VDC,
Loop Powered
4 to 20 mA 15 to 42 VDC,
CCT40-100 10/20/50 A
Loop Powered
CCT50-100 100/150/200 A 4 to 20 mA 15 to 42 VDC,
Loop Powered
Output
0 to 5 V
0 to 5 V
0 to 5 V
0 to 5 V
0 to 10 V
0 to 10 V
4 to 20 mA
Series
CCT60/70
Case
Solid core
Solid core
Split core
Split core
Solid core
Solid core
Solid core
2-33/64
[64.00]
55/64
[22.00]
4-1/64
[102.00]
Solid Models
Range
Model
CCT40-202 10/20/50 A
CCT50-202 100/150/200 A
CCT40-102 10/20/50 A
CCT50-102 100/150/200 A
CCT40-203 10/20/50 A
CCT50-203 100/150/200 A
CCT40-200 10/20/50 A
43/64
[17.00]
2-3/4
[70.00]
55/64
[22.00]
3-1/2
[89.00]
The Series CCT40/50 Current Transformers are a low cost alternative for measuring
power and monitoring the operation of fans, pumps, or other equipment. For use on existing
installations, split core models can be installed without disconnecting cables. Each model
offers three jumper selectable ranges and a choice of three different outputs.
2X
Ø13/64
[Ø5.00]
1-17/64
[32.00]
Split Models
SPECIFICATIONS
Amperage Range: Field selectable; up to 200 A (depending on model).
Output: 0 to 5 V, 0 to 10 V, or 4 to 20 mA (depending on model).
Power Requirements: Self powered or 15 to 42 VDC loop powered (depending on
model).
Accuracy: 1%.
Temperature Limits: -22 to 158ºF (-30 to 70ºC).
Humidity Limits: 0 to 95% (non-condensing).
Response Time: 250 ms to 90%.
Isolation Voltage: 2000 V.
Frequency: 10 to 400 Hz.
Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing.
Approvals: CE, cUL, UL.
Solid core
Split core
Split core
True RMS Current Transformers
Solid or Split Core, Field Selectable Range
2-29/32
[74.00]
63/64
[25.00]
33/64
[13.00]
1-9/64
[29.00]
55/64
[22.00]
2-31/64
[63.00]
Ø3/4
[Ø19.00]
3-1/2
[89.00]
Solid Models
The Series CCT60/70 True RMS Current Transformers are a low cost alternative
for providing true RMS outputs on distorted AC waveforms. True RMS outputs are ideal
for nonlinear loads or noisy circuits. For existing installations, split core models can be
installed without disconnecting cables. Each model offers three jumper selectable ranges
to reduce the risk of ordering the wrong model.
Model
CCT60-200
CCT70-200
CCT60-100
CCT70-100
364
Range
10/20/50 A
100/150/200 A
10/20/50 A
100/150/200 A
Case
Solid core
Solid core
Split core
Split core
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
3-1/2
[89.00]
2X Ø13/64
[Ø5.00]
45/64
[18.00]
33/64
[13.00]
2-7/16
[62.00]
2X
Ø13/64
[Ø5.00]
1-17/64
[32.00]
19/32
[15.00]
43/64
[17.00]
2-3/4
[70.00]
2-33/64
[64.00]
55/64
[22.00]
55/64
[22.00]
4-1/64
[102.00]
Split Models
SPECIFICATIONS
Amperage Range: Up to 200 A (depending on model).
Output: 4 to 20 mA, true RMS.
Power Requirements: 24 VDC nominal.
Accuracy: 1%.
Temperature Limits: -22 to 158ºF (-30 to 70ºC).
Humidity Limits: 0 to 95% (non-condensing).
Response Time: 250 ms to 90%.
Isolation Voltage: 2000 V.
Frequency: 10 to 400 Hz.
Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing.
Approvals: CE, cUL, UL.
365_Layout 1 7/21/14 1:43 PM Page 365
PROCESS CONTROL
Series
LTT
SSR Monitors
Monitors SSRs for Loss of Line, Open Load, Shorted SSR, Loss of DC Power
2.500
Current Transformers/
Switches
1.550
Love Controls LTT Series SSR Monitors allow easy monitoring of the operation of
your SSR switches. This handy device compares the input status with the output status.
An alarm operates a relay contact to tell you if the load circuit has opened or if the SSR
has shorted. The LTT mounts easily on most SSRs with no additional hardware. Protect
your system today.
Model
LTT12-0
LTT24-0
LTT24-1
FEATURES
€ Monitors SSRs for loss of line, open load, shorted SSR, loss of DC power
€ Mounts on standard SSRs over the connection terminals
€ Designed to fit under finger safe cover
€ LED status indicator
€ Normally closed dry relay contact 200 VDC @ 0.5A max.
Series
LTTJ
Description
Solid State Relay Monitor, 10 to 19 VDC Trigger,
100 to 660 VAC Load
Solid State Relay Monitor, 20 to 32 VDC Trigger,
100 to 660 VAC Load
Solid State Relay Monitor, 20 to 32 VDC Trigger,
100 to 660 VAC Load with Driver Circuit Test
Current Transformers
0 to 10 VDC Analog Output, Fully Adjustable Output, Over Voltage Protection
Ø.500
1.650
1.150
1.600
Love Controls Series LTTJ Current Transformers allow easy monitoring of the
current flowing to your load. This easy to use device provides a 0 to 10 VDC signal into
both low and high impedance circuits, and is easily scalable to your needs.
Available in a number of different ranges, the Series LTTJ can be easily mounted on most
Series LTP Solid State Relays for convenient wiring. Some models feature an LED for
visual confirmation that current is flowing through the device.
FEATURES
€ 0 to 10 VDC analog output
€ Impedance matching for high or low impedance inputs
€ Fully adjustable output
€ Over voltage protection
Model
LTTJ-010
LTTJ-020
LTTJ-030
LTTJ-040
LTTJ-050
LTTJ-060
LTTJ-070
LTTJ-080
LTTJ-090
LTTJ-100
LTTJ-103
LTTJ-305
LTTJ-305I
LTTJ-103S
LTTJ-305S
1.550
Description
Current Transformer Calibrated to 10 VDC at 10 Amps
Current Transformer Calibrated to 10 VDC at 20 Amps
Current Transformer Calibrated to 10 VDC at 30 Amps
Current Transformer Calibrated to 10 VDC at 40 Amps
Current Transformer Calibrated to 10 VDC at 50 Amps
Current Transformer Calibrated to 10 VDC at 60 Amps
Current Transformer Calibrated to 10 VDC at 70 Amps
Current Transformer Calibrated to 10 VDC at 80 Amps
Current Transformer Calibrated to 10 VDC at 90 Amps
Current Transformer Calibrated to 10 VDC at 100 Amps
Current Transformer Adjustable from 10 to 30 Amps,
5-10 VDC Output
Current Transformer Adjustable from 30 to 50 Amps,
5-10 VDC Output
Current Transformer Adjustable from 30 to 50 Amps,
LED Output
Current Transformer Adjustable from 10 to 30 Amps,
NPN Transistor Output
Current Transformer Adjustable from 30 to 50 Amps,
NPN Transistor Output
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
365
PROCESS CONTROL
366_Layout 1 7/21/14 12:01 PM Page 366
Series
SCT
Current Transformer
Optional Auxillary, Relay Output, Split Core
1-1/16
[26.9]
2-9/16
[65.0]
3/8
[9.6]
3BYE
IND. CONT. CO.
Class 2
C223444
(800) 872-9141
www.dwyer-inst.com
Isolation 600 VAC (UL)
300 VAC (CE)
Read instructions
before installing
Model SCT10-100
Analog Current Transducer
2-45/64
[68.6]
Signal Converters
RoHS
2-9/16
[65.0]
2-45/64
[68.6]
13/64
[5.3]
3-1/4
[82.4]
Mounting Bracket
43/64
[17]
Snap On Relay
The Series SCT Current Transformers continuously measure the current consumption
of pumps, fans, boilers, solar panels and chillers for use in energy monitoring. Current or
voltage outputs can be scaled using a slider switch to select between three factory set ranges.
Split core configuration allows the current transformer to be installed on new and existing
installations. Snap-on mounting bracket allows for quick installation of replacement
transformers. An optional 10 A command relay can snap onto the current switch, which
eliminates the need to mount an additional relay.
Model
SCT10-100
SCT10-102
SCT20-103
Range
30/60/120 A
30/60/120 A
20/100/150 A
Output
4 to 20 mA
0 to 5 VDC
0 to 10 VDC
Power
Requirements
24 VDC
Self-powered
Self-powered
Max. Continuous
Operating Current
120 A
120 A
150 A
SPECIFICATIONS
Amperage Range: 30/60/120 A or 20/100/150 A (depending on model).
Continuous Operating Current: 120 A or 150 A (depending on model).
Output: 4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC (depending on model). Optional
relay NO SPST; 10 A @ 260 VAC, 5 A @ 30 VDC.
Power Requirements: Self-powered or 24 VDC (depending on model).
Accuracy: ±2% from 10 to 100% of selected range.
Temperature Limits: 5 to 140°F (-15 to 60°C).
Humidity Limits: 0 to 95% non-condensing.
Response Time: 2 s.
Isolation Voltage: 600 VAC RMS.
Frequency: 50/60 Hz.
Enclosure Rating: UL, V-O flammability rated, type 66 nylon.
Agency Approvals: CE, RoHS, cUL, UL.
ACCESSORIES
SCT-RLY-12, 12 VAC Trigger Voltage Relay Module
SCT-RLY-24, 24 VAC Trigger Voltage Relay Module
Model
MN-1
™
Mini-Node Communication Signal Converter
Converts RS-485 to USB, Integral USB Connector, No External Power
GREEN LED
YELLOW LED
27/32
[21.43]
3-13/64
[81.36]
57/64
[22.62]
The Model MN-1 Mini-Node’ Communication Signal Converter is a low cost device
that converts half duplex RS-485 serial communications signals into a signal that can be
read by any computer with a USB port. The integral USB connector and RJ-45 connector
reduces set up time by eliminating extra wiring. The Model MN-1 is powered via the USB
connection which eliminates the need for an external power source. The compact size is
great for field installation, control panels, and lab testing.
Model MN-1, Mini-Node’ USB to RS-485 Converter
366
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Power Requirements: No external power required.
Power Consumption: 0.4 W.
Isolated Voltage: 3000 VDC.
Input Impedance: 96 k.
USB Connector: B-type (female).
RS-485 Connector: RJ-45.
Baud Rate: 75, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600,
and 115200 bps.
Compatibility: Full compliance with USB V.2.0 specification.
367_Layout 1 7/8/14 11:18 AM Page 367
Power Supply
Economical and reliable power supply is suitable for powering all Dwyer pressure,
temperature or air velocity transmitters. Inexpensive, open-frame design allows
convenient access to input/output solder terminals. Auxiliary inputs are selectable for
operation from power sources found worldwide. Compact size eases enclosure
installations.
Model
A-699
Model A-700, (0.5 Amp)
Model A-700-2, (2 Amp)
Model A-700-4, (4.8 Amp)
Control Transformer
SPECIFICATIONS
AC Input: 120 VAC, 60 Hz.
AC Output: 24 VAC.
Maximum Current output: 400 mA (typically). 10 VA max.
Electrical Connections: Primary, 6-1/2 leads; Secondary, 6 to 32 screw
terminals. (Manufactured for Dwyer Instruments, Inc.)
Weight: 1 lb, 4 oz.
UL and CSA listed Class 2 step down transformer is mounted on a 4-1/4˝ square
plate stand-off for direct installation in standard 4˝ x 4˝ x 1-1/2˝ junction boxes. The A-699
is suitable for powering all Dwyer 4-wire transmitters and Model 660 Air Velocity Monitor.
Model
KF-CC-304
Model A-699, Control Transformer
USB Dual Power
Charge Two USB Devices at Once!
2-5/16
[58.93]
DC
POWER
PLUG
2 X USB PORTS
1-47/64
[44.01]
FLIP-OUT
STANDARD
AC PLUG
1-37/64
[40.22]
4-11/16
[119.17]
The USB Dual Power charger keeps you plugged-in and powered-up at home and on the
road. Featuring a robust charging capacity of 1.5 amps, two USB ports for the simultaneous
charging of two devices, and a pocket-friendly 2-in-1 design for both wall charging and auto
charging, the USB Dual Power is the ultimate charging accessory for USB-powered portable
electronics!
FEATURES
€ Provides 1.5 amps of charging power
€ Charge two USB devices at once
€ Use at home or in the car
€ Built-in safety fuse to protect your devices
€ Sleek, pocket-friendly design
€ LEDlight indicates ready power source
SPECIFICATIONS
Input: 100 to 240 VAC 50/60 Hz 0.15 A 12 to 24 VDC.
Output: Terminal Voltage Current:
USBport 1: 5.0 V = 1.5 A;
USB port 2: 5.0 V = 1.5 A;
USB port 1 + 2: 5.0 V = 750 + 750 mA.
Agency Approvals: CE.
KF-CC-304, USB Dual Power
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
367
Power Supplies
SPECIFICATIONS
AC Input: 100/120/220/230-240 VAC ±10%, 47-63 Hz.
DC Output: 24 to 28 VDC regulated.
Maximum Current Output: A-700: 0.5 A @ 60 Hz, 0.45 A @ 50 Hz; A-700-2: 2 A
@ 60 Hz, 1.8 A @ 50 Hz; A-700-3: 4.8 A @ 60 Hz, 4.5 A @ 50 Hz.
Operating Temperature: 32 to 122°F (0 to 50°C).
External Fuse Required: 0.5 Amp for 100 to 120 VAC, 0.25 Amp for 220 to 240
VAC.
Dimensions: 4-7/8H x 4W x 1-5/8D
Weight: 2 lb.
PROCESS CONTROL
Series
A-700
PROCESS CONTROL
368_Layout 1 7/8/14 11:17 AM Page 368
Model
BPS-005
Low Cost DC Power Supply
Regulated 0.5 A, 1 A Fuse Protection
RoHS
Power Supplies
3
[76.20]
2-13/32
[61.19]
2-1/16
[52.28]
SNAPTRACK
The Model BPS-005 Low Cost DC Power Supply is a regulated .5 A power supply
that accepts 24 VAC input and provides an adjustable 1.5 to 29 VDC output. Output voltage
adjustments are made using the on-board potentiometer while measuring the output with
a multimeter. A compact snap track design allows the power supply to be surface mounted
within a panel.
SPECIFICATIONS
Input: 24 VAC/VDC 50/60 Hz.
Output: 24 VDC (full wave rectified and regulated) adjustable 1.5 to 29 VDC, 0.5 A
max.
Maximum Current Output: 0.5 A.
Over-Current Protection: 1 A fuse.
Operating Temperature: 32 to 130°F (0 to 55°C).
Humidity Limits: 95% (non-condensing).
Weight: 0.4 lb.
AgencyApproval: RoHS.
Model BPS-005, Low Cost DCPower Supply
Model
BPS-015
19/32
[14.97]
Low Cost DC Power Supply
1.5A, Fuse Protection
1-15/16
[49.02]
11/16
[17.27]
4-1/16
[103.12]
2-19/64
[58.17]
SNAPTRACK
The Model BPS Building Automation Power Supply is used to convert 24 VAC to a
regulated DC power source for transmitters with 4 to 20 mA outputs. The output voltage
can be field adjusted from 1.5V to 27V using a potentiometer. The 3A fuse protects the
power supply from over-current conditions. The snap-on bracket can be quickly surface
mounted to any flat surface.
Model BPS-015, Power Supply
368
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Input: 24 VAC/VDC 50/60 Hz.
Output: 24 VDC (full wave rectified and regulated) adjustable 1.5 to 27 VDC.
Maximum Current Output: 1.5A (de-rated to 400 mA for non-isolated circuits).
TemperatureLimits: 32 to 130°F (0 to 55°C).
Humidity Limits: 95% (non-condensing).
Weight: 0.4 lb.
369_Layout 1 7/8/14 11:16 AM Page 369
PROCESS CONTROL
Series
APT
AC Power Transformers
40 VA to 100 VA, Single or Dual Hub, Circuit Breaker, UL Class 2
RoHS
Power Supplies/
Transformers
A
C
Model
APT-40-0SN
APT-40-1SN
APT-40-1DN
APT-50-1SN
APT-50-1SB
APT-50-1DB
APT-75-1SB
APT-75-1DB
APT-100-1SB
APT-100-1DB
1/2 NPT Male
B
D
E
The Series APT AC Power Transformers provide isolated step-down to 24 VAC with
models offering VA ratings of 40, 50, 75, or 96 VA’s. These low-cost transformers are
offered in single or dual 1/2˝ NPT threaded hub mounts with 8-1/2˝ 18 AWG wire leads,
to meet the installation requirements of a variety of building automation and control panel
applications. All models are UL Class 2 listed.
Model
APT-40-0SN
APT-40-1SN
APT-40-1DN
APT-50-1SN
APT-50-1SB
APT-50-1DB
APT-75-1SB
APT-75-1DB
APT-100-1SB
APT-100-1DB
Rating
40 VA
40 VA
40 VA
50 VA
50 VA
50 VA
75 VA
75 VA
96 VA
96 VA
Input Voltage
24 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
Mounting
Foot Mount with Single Hub
Foot Mount with Single Hub
Foot Mount withDual Hub
Foot Mount with Single Hub
Foot Mount with Single Hub
Foot Mount withDual Hub
Foot Mount with Single Hub
Foot Mount withDual Hub
Foot Mount with Single Hub
Foot Mount withDual Hub
A in (mm)
1-61/64 (49.5)
1-61/64 (49.5)
1-61/64 (49.5)
1-13/16 (46.0)
1-13/16 (46.0)
1-13/16 (46.0)
2-13/64 (56.0)
2-13/64 (56.0)
2-13/32 (61.0)
2-13/32 (61.0)
Current Protection
Inherent
Inherent
Inherent
Internal Fuse
Button Circuit Breaker
Button Circuit Breaker
Button Circuit Breaker
Button Circuit Breaker
Button Circuit Breaker
Button Circuit Breaker
D in (mm)
2-43/64 (68.0)
2-43/64 (68.0)
2-43/64 (68.0)
2-61/64 (75.0)
3-31/64 (88.5)
3-31/64 (88.5)
3-7/8 (98.5)
3-7/8 (98.5)
4-5/64 (103.5)
4-5/64 (103.5)
E in (mm)
2-7/8 (73.0)
2-7/8 (73.0)
2-7/8 (73.0)
3-1/32 (77.0)
3-1/32 (77.0)
3-1/32 (77.0)
3-1/32 (77.0)
3-1/32 (77.0)
3-1/32 (77.0)
3-1/32 (77.0)
Wiring
Diagram B
Diagram A
Diagram A
Diagram A
Diagram A
Diagram A
Diagram A
Diagram A
Diagram A
Diagram A
Weight
1.96 lb (0.89 kg)
1.98 lb (0.90 kg)
2.03 lb (0.92 kg)
2.43 lb (1.10 kg)
2.77 lb (1.26 kg)
2.77 lb (1.26 kg)
3.53 lb (1.60 kg)
3.57 lb (1.62 kg)
3.97 lb (1.80 kg)
4.01 lb (1.82 kg)
Diagram B
RED
BROWN
120VAC
24VAC
BLACK
C in (mm)
2-11/64 (55.0)
2-11/64 (55.0)
2-11/64 (55.0)
2-1/2 (63.5)
2-1/2 (63.5)
2-1/2 (63.5)
2-1/2 (63.5)
2-1/2 (63.5)
2-1/2 (63.5)
2-1/2 (63.5)
SPECIFICATIONS
Input Voltage: See model chart.
Input Frequency: 50/60 Hz.
Output Voltage: 24 VAC.
Output VA Rating: 40, 50, 75, or 96 VA.
Mounting: Slotted foot mount with single, or dual 1/2 NPT hub.
Current Protection: See model chart.
Electrical Connections: 8.5 (210 mm) 18 AWG leads.
Weight: See model chart.
Agency Approvals: CE, RoHS, cUL, UL.
Diagram A
WHITE
B in (mm)
1-25/32 (45.2)
1-25/32 (45.2)
1-25/32 (45.2)
1-31/32 (50.2)
1-31/32 (50.2)
1-31/32 (50.2)
1-31/32 (50.2)
1-31/32 (50.2)
1-31/32 (50.2)
1-31/32 (50.2)
BLUE
BROWN
24VAC
24VAC
RED
BLUE
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
369
PROCESS CONTROL
370_Layout 1 7/29/14 3:41 PM Page 370
Model
FC-1000
Electronic Fan Speed Control
Low Cost, 0-10 VDC Input, Selectable Hard Start
1-3/8
[34.93]
13/16
[20.64]
3/16
[4.76]
4
[101.6]
4X Ø1/4
[Ø6.35]
3/4 [19.05] 2X 7/16
[11.11]
Fan Speed Controls
2X Ø7/8
[Ø22.23]
4-3/8
[111.13]
5-1/4
[133.35]
5-1/8
[130.18]
2X 4-1/4
[107.95]
2X 1/2 [12.7]
2-7/8
[73.03]
The Model FC-1000 Electronic Fan Speed Control provides precise speed
modulation of small AC motors. Popular 0 to 10 VDC input works with most process
controllers, eliminating the need for more expensive dampers, damper actuators and
linkages while improving overall energy efficiency of the system. This inexpensive unit
enables variable control of ventilation fans, condenser fans and interfacing with VAV box
controllers.
Model FC-1000, Electronic Fan Speed Control
Model
KFD0
SPECIFICATIONS
Line Voltage Range: 120 to 277 VAC,
60 Hz.
Input Signal Voltage: 0 to 10 VDC.
Low Voltage Input: 24 VAC, class 2.
Input Signal Impedance: 10K .
Full Load Amp Rating: 9.8 @120
VAC, 9.3 @ 208 VAC, 8.0 @ 240 VAC,
6.9 @ 277 VAC.
Locked Rotor Amp Rating: 24.0.
Temperature Limits: -40 to 131°F
(-40 to 55°C).
1/2
[12.7]
Electrical Connections: Line voltage:
10-32 screw terminals. Signal and low
voltage input: 1/4 quick connects.
Transient Protection: 320 V surge
suppression. Exceeds IEEE C62.41
standards.
Housing Materials: Cold rolled steel.
Enclosure Rating: NEMA 1.
Mounting: Vertical only; four holes
provided for #10 screws.
Weight: 1 Ib, 11 oz (.77 kg).
Agency Approval: UR.
Galvanic Barrier
Loop Powered, Intrinsically Safe Isolators
4-37/64 [116.46]
25/32 [20.00]
4-3/8 [111.20]
The Model KFD0 Loop Powered, Galvanic Barrier provides complete isolation for
communication with Dwyer® intrinsically-safe transmitters approved for use in hazardous
areas. Galvanic barrier eliminates the need for a high integrity earth ground required
when using shunt type diode type safety barriers. Unlike most other isolators, the Model
KFD0 does not require external power and has a low current draw. The housing is designed
to easily mount on most standard DIN rails.
Model
Dwyer Series
Approval
KFD0-SCS-EX1.55 FM for Class I, Zone 1,
HHT-IX
Groups IIC, IIB, IIA; Class I, II, III, Div. 2,
Groups A, B, C, D, F, G
Model
Vo (V)
KFD0-SCS-EX1.55 23.1
Io (mA)
38.2
Group
IIC (A, B)
IIB (C)
IIA (D, F, G)
F
0.042
0.267
0.267
mH
0.5
2.5
2.5
SPECIFICATIONS
Hazardous Area Input:
Signal range: 4 to 20 mA (linear transmission 1 to 22 mA);
Available transmitter voltage: 16 V for supply voltage > 21 V.
Safe Area Output:
Signal range: 4 to 20 mA;
Transmitter voltage: 30 VDC.
Response Time: 20 s at 0, and 600 s at 800 load.
Maximum Power Dissipation:150 mW @ 20 mA and V <24 V.
Temperature Limits: -4 to 140°F (-20 to 60°C).
Temperature Drift: 0.5 A/°C.
Weight: 4.2 oz (120 g).
Agency Approvals: CE, FM.
Model KFD0-SCS-EX1.55, Loop powered galvanic barrier
ACCESSORY
A-360, Aluminum DINRail 1 m
370
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
371_Layout 1 7/21/14 11:46 AM Page 371
PROCESS CONTROL
Series
MTL5041/
5045
Galvanic Barrier
Intrinsically Safe Isolators for Hazardous Locations
41/64
[16.27]
Intrinsically Safe
Barriers
4-11/32
[110.33]
HAZARDOUS
AREA TERMINAL
4-3/32
[103.98]
SAFE AREA
TERMINAL
MTL5041
The MTL5041/5045 Galvanic Barrier provide total intrinsically safe isolation for
communication with Dwyer® pressure transmitters approved for location in hazardous
areas. Galvanic barrier eliminates the need for a high integrity earth ground required
when using shunt diode type safety barriers. DIN rail mounting and plug-in signal and
power connectors simplify installation and maintenance
Compatible Models: 637, 638, 608, 2700, 2800, 2900, SBLTX, PBLTX, IS626
MTL5041/5045
Galvanic
Approval
Barrier
MTL5041 FM for Class I, II, II; Div. 1 Groups C, D, F,G
MTL5041 UL for Class I; Div. 1 Groups A, B, C, D
Class II Div. 1 Groups E, F, G ClassIII Div 1
MTL5041 FM for Class I, II, III; Div. 1 Groups B, C, D, E, F, G
MTL5041 FMfor Class I, II, III; Div. 1 Groups A, B,C, D, E,F,G
MTL5045 FMfor Class I, II, III; Div. 1 Groups C, D, E,F,G
MTL5045 FMfor Class I, II, III; Div. 1 Groups C, D, E,F,G
Dwyer
Series
638
IS626, SBLTX,
PBLTX
637
608
2900
2700/2800
FM
F
mH
Group
0.13
4.2
A &B
0.30
12.6
C
1.04
33.6
D
BASEEFA (ATEX)
Group F
mH H/
IIC
0.083 3.05 55
IIB
0.85
9.15 210
IIA
2.15
244 444
Region
(Authority)
Standard
USA (FM) (UL) 3600,
3610 entity
3611, 3810
UL913
UL1604
Canada (CSA) CAN/CSA
E60070,
IEC60079,
C22.2
UK (BASEEFA) EN 50014,
EN 50020
UK (BASEEFA) EN 50039
Systems
Approved For
AIS/I,II,III/1/Entity ABCDEFGSCI-942; NI/I/@/ABCD/T4
[I/0] AEx[ia]IIC-SCI-942
Entity; NI/1/2/IIC/T4;
Ta=140°F (60°C)
Class I,Div.2, Gps A, B, C, D;
Ex nA [iA] IIC T4
Class I, Xone 2, Aex nA IIC
T4
EEx ia IIC
EEx ia IIC
Certificate/
File no.
3010737
SPECIFICATIONS
Hazardous Area Input:
Signal range: 0 to 24 mA (including over-range);
Transmitter voltage:16.5 V at 20 mA.
Safe Area Output:
Signal range: 4 to 20 mA;
Safe-area load resistance: 0 to 1k;
Safe-area output resistance:> 2 M.
Power Requirement:20 to 35 VDC.
Response Time:Settles to within 10% of final value within 250 s.
Current Consumption (20 mA signal):
70 mA at 24 VDC;
85 mA at 20 VDC;
55 mA at 35 VDC.
Maximum Power Dissipation(20 mA signal): 1.2 W at 24 VDC.
Isolation: 250 V rms between input, output and power supply terminals.
Transfer Accuracy at 68°F (20°C): Better than 20 A(typically 5 A).
LED Indicator: Green:Power indication.
Temperature Limits:
Operating:-4 to 140°F (-20 to 60°C);
Storage:-40 to 176°F (-40 to 80°C).
Temperature Drift:<1 A/°C.
Humidity: 5 to 95% RH.
Mounting: 1.4 (35 mm) top hat rail to:
EN 50022-35 x 7.5;
BS 5584;
35 x 27 x 7.3 DIN46277.
Terminals: Accommodate up to 2.5 mm2 stranded or single-core.
Safety Description:28 V, 300, 93 mA; Um=250 rms or dc.
Weight: 3.9 oz (110 g).
Agency Approvals: See table.
1345550
BAS01ATEX7217
Ex01E2219
ACCESSORY
A-360, Aluminum DINRail 1 m
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
371
PROCESS CONTROL
372_Layout 1 7/8/14 11:15 AM Page 372
Zener Barrier
Series
MTL7706/
7787
Intrinsically Safe Barriers for Hazardous Locations
SAFE AREA
TERMINAL
HAZARDOUS
AREA TERMINALS
Intrinsically Safe
Barriers
1/2
[12.70]
3-35/64
[90.09]
4-5/32
[105.57]
MTL7787
The MTL7706/7787 is an intrinsically safe (IS) shunt-diode barrier that can be used to
communicate with and provide isolations for certain Dwyer® transmitters approved for use
in hazardous areas. These barriers limit the amount of energy allowed to pass into the
hazardous area, which inhibit ignition in flammable atmospheres.
Compatible Models:637, 608, SBLTX, PBLTX, IS626
Zener
Approval
Barrier
MTL7706 ULfor Class I; Div. 1 Groups A, B, C, D
CL II; Div. 1 Groups E, F, G; CL III Div. 1
FM
Group F
mH
A &B 0.083 4.2
BASEEFA (ATEX)
Group F
mH
IIC
0.083 4.2
Region
(Authority)
Standard
USA (FM) (UL) 3600,
3610 entity
3611, 3810
UL698,
UL913
UL1604
Canada (CSA) CAN/CSA
E60070,
IEC60079,
C22.2
UK (BASEEFA) EN 50014,
EN 50020
UK (BASEEFA) EN 50039
Systems
372
MTL7787
MTL7706
MTL7706 FMfor Class I, II, III; Div. 1 Groups B,
C, D, E,F,G
MTL7706 FM for Class I, II, III; Div. 1 Groups A,
B, C, D, E, F, G
Dwyer
Series
IS626
SBLTX
PBLTX
637
608
SPECIFICATIONS
Transmitter Voltage: 16.2 V at 20 mA with 250 load (negative w.r.t. earth); 11.0 V
at 20 mA with 500 load (negative w.r.t. earth).
Safe Area Output:4 to 20 mA.
Load Resistance: 0 to 500 .
Power Requirement:20 to 35 VDC w.r.t. earth.
Accuracy:±2 A under all conditions.
LED Indicator: Green:Power indication.
Temperature Limits:
Operating:-4 to 140°F (-20 to 60°C);
Storage:-40 to 176°F (-40 to 80°C).
Humidity: 5 to 95% RH.
Terminals: Accommodate up to 2.5 mm2 stranded or single-core.
Safety Description:28 V, 300, 93 mA.
Weight: 4.9 oz (140 g).
Agency Approvals: See table.
FM
Group F
mH
A &B 0.083 3.05
BASEEFA (ATEX)
Group F
mH
IIC
0.083 3.05
Certificate/
Approved For
File no.
AIS/I,II,III/1/Entity ABCDEFG- 3010737
SCI-942; NI/I/@/ABCD/T4
[I/0] AEx[ia]IIC-SCI-942
Entity; NI/1/2/IIC/T4;
Ta=140°F (60°C)
Class I,Div.2, Gps A, B, C, D;
Ex nA [iA] IIC T4
Class I, Xone 2, Aex nA IIC
T4
EEx ia IIC
1345550
EEx ia IIC
Ex01E2219
BAS01ATEX7217
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
ACCESSORY
A-360, Aluminum DINRail 1 m
373_Layout 1 7/8/14 11:13 AM Page 373
PROCESS CONTROL
Series
LCT216
Digital Timer/Tachometer/Counter
3 Controls in 1 Device, DIP Switch Configuration
3-23/64
[85.22]
1-7/8
[47.63]
DIP SWITCH
3-1/8
[79.50]
1-7/8
[47.63]
Model
LCT216-100
LCT216-110
Output Type
Transistor
Relay
Series
LCT316
Timers
The Series LCT216 combines a versatile timer, counter, and tachometer in one device.
The bright, easy-to-read display shows both the desired set point and the current process
value as well as the operating mode that the control is functioning in. The fourteen preprogrammed timer functions are easy to set up and cover most applications. The counting
functions include one stage or two stage counting along with batch, total, or dual counting
modes. The Series LCT216 can also be used as a tachometer to measure rotational speeds.
For quick set up, many of the programming parameters can be set with external dip
switches located on the side of the unit.
1-3/4
[44.45]
SPECIFICATIONS
Operating Temperature Range: 32 to 122°F (0 to 50°C).
Humidity Conditions: 35 to 85%RH (non-condensing).
Control Output Ratings: (Out 1) Relay: SPST 5A at 250 VAC; Transistor: NPN
open collector 100 mA / 30 VDC residual voltage = 1.5 VDC max; (Out 2) Relay:
SPST 5A at 250 VAC, Transistor: NPN open collector 100 mA / 30 VDC residual
voltage = 1.5 VDC max.
Weight: 4 oz (114 g).
Reset Time: 0.001 seconds minimum.
Inputs: Dry contact, PNP, or NPN.
Timing Functions: 14 pre-programmed timing functions.
Supply Voltage: 100 to 240 VAC 50 / 60 Hz.
Power Consumption: Less than 10 VA.
Internal Power Supply: 12 VDC ±10%, 100 mA.
Display: Two-line 6 digit negative transmissive LCD display.
Agency Approvals: CE, cUL, UL.
Low Cost Digital Timer
Quick Installation, Digital Input, Audible Alarm
1-1/8
[28.57]
1-11/32
[33.99]
3
[76.20]
The Series LCT316 Low Cost Digital Timer provides accurate countdown timing for
a variety of applications. The timer can be triggered remotely using the digital input
terminals or locally via the set button. Time intervals can be set up to 999 minutes or
seconds. The Series LCT316 has an internal buzzer to alert when the time interval has
expired.
Model
LCT316-100
LCT316-200
LCT316-300
LCT316-400
Supply Power
115 VAC
230 VAC
12 VAC/DC
24 VAC/DC
2-7/16
[61.91]
SPECIFICATIONS
Operating Temperature Range: 32 to 158°F (0 to 70°C).
Control Output Ratings: Relay, SPST NO, 16A at 250 VAC resistive.
Weight: 5.6 oz (158.8 g).
Status Light: LED shows time and operation.
Inputs: Digital input for start and reset.
Supply Voltage: 115 VAC, 230 VAC, 12 VAC/DC, 24 VAC/DC depending on
model.
Power Consumption: 4 VA.
Agency Approvals: CE, cUR, UR.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
373
PROCESS CONTROL
374_Layout 1 7/21/14 1:36 PM Page 374
Series
DCT500A
Low Cost Timer Controller
Compact, Easy to Use; 4, 6 or 10 Channels
75
100
25
200
150
R31
175
CONNECT JUMPER TO LAST
CHANNEL USED
TIME ON
350
1 2 3 4 5 6 7 8 9 10
400
150
R29
100
1 SEC 200
HIGH
LIMIT
300
250
125
50
50
mSEC
450
DWYER INSTRUMENTS
MICHIGAN CITY, IN
TIME OFF
500
COM
LOW
LIMIT
POWER
ON
Timer Controllers
05-443179-00
VER 0
INDUSTRIAL CONTROL EQUIPMENT
LINE INPUT RATING 120 VAC +10%-15%
50/60 HZ SINGLE PHASE. THIS UNIT MUST BE
ENCLOSED. USE NEC CLASS 1 WIRING RATED
60C/75C. USE 14-22 GA COPPER ONLY FOR LINE
AND LOAD CONNECTIONS. TORQUE TERMINALS
TO 5 IN. LB. REPLACE FUSE WITH TYPE 3AG FAST
ACTING 3 AMP 250V ONLY. FAILURE TO COMPLY
WITH THESE REQUIREMENTS WILL VOID
MANUFACTURES WARRANTEE.
FVN 1.0.0
D16
4-1/4
[107.95]
4-7/8
[123.8]
WIRE STRIP GAUGE
0.250 IN. MAX
DO NOT USE SLOW BLOW FUSES
LINE VOLTAGE
102 VAC TO 132 VAC MAX
50-60 HZ
L1 L2 SOL 1
COM
2 3
6-1/4 [158.75]
Ideal for pneumatic conveying systems, the Series DCT500A Low Cost Timer
Controller is designed to provide continuous or on-demand cleaning for receivers and pulse
jet systems. Available in either 4, 6 or 10 channels, each unit is the same size, minimizing
enclosure space and reducing overall system installation cost.
The DCT500A is simple and easy to use. Time-On and Time-Off settings are selected using
two potentiometers. High Limit and Low Limit control inputs are provided for use with
on demand systems. The new enhanced board circuitry of the DCT500A synchronizes the
on-time pulse to the power line to achieve a pulse stability of ±1 msec.
For added safety, the control circuitry including the control inputs are isolated from the
line voltage.
To meet your system requirements, an optional weatherproof enclosure is available. For
on demand systems, a Dwyer Series A3000 Photohelic® gage or Series 1800 Pressure
Switch may be used with the DCT500A.
Model
DCT504A
DCT506A
DCT510A
Description
Timer Controller
Timer Controller
Timer Controller
No. of Channels
4
6
10
Series
DCT500ADC
4
5 6
7
8
1/16
[1.59]
9 10
OUTPUTS (300 VA MAX)
1/2
[12.70]
6-3/4 [171.45]
SPECIFICATIONS*
Output Channels: 4, 6, & 10
channels.
Power Requirements: 102 to 132
VAC 50 or 60 Hz.
Power Consumption: 2.5 W.
Solenoid Supply: 3 A max per
channel.
Fuse: Type 3 AG, 3 A @ 250 VAC.
Temperature Limits: -40 to 140°F
(-40 to 60°C).
1-21/64
[33.73]
Storage Temperature Limits:
-40 to 176°F (-40 to 80°C).
On Time: 50 ms to 500 ms.
On Time Accuracy: ±10 ms.
On Time Stability: ±1 ms.
Off Time: 1 second to 180 seconds.
Off Time Accuracy: ±5% of setting.
Weight: 9 oz (255 g).
Agency Approval: CE, cUL, UL.
*Additional specifications on IOM.
OPTIONS
L, Mounting Bracket for Field Retrofits:
8-1/4 x 6-1/4 (209.55 mm x 158.75 mm
WP, Weatherproof Housing:
Standard Models
Models with Option -L Mounting Bracket
Low Cost Timer Controller
For Low Voltage Applications
TIME ON
TIME OFF
SEC
mSEC
4-1/4
[107.95]
4-7/8
[123.83]
F1
1/16
[1.59]
6-1/4 [158.75]
6-3/4 [171.45]
Ideal for pneumatic conveying systems, the Series DCT500ADC Low Cost Timer
Controller is designed to provide continuous or on-demand cleaning for 10-35 volt powered
receivers and pulse jet systems. Available in either 4, 6 or 10 channels, each unit is the
same size, minimizing enclosure space and reducing overall system installation cost.
The DCT500ADC is simple and easy to use. Time-On and Time-Off settings are selected
using two potentiometers. High Limit and Low Limit control inputs are provided for use
with on demand systems.
For added safety, the control circuitry including the control inputs are isolated from the
line voltage.
To meet your system requirements, an optional weatherproof enclosure is available. For
on demand systems, a Dwyer Series A3000 Photohelic® gage or Series 1800 Pressure
Switch may be used with the DCT500ADC.
Model
DCT504ADC
DCT506ADC
DCT510ADC
374
Description
Timer Controller
Timer Controller
Timer Controller
No. of Channels
4
6
10
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS*
Output Channels: 4, 6, & 10
channels.
Power Requirements: 10 to 35 VDC.
Power Consumption: 0.6 W.
Solenoid Supply: 3 A max per
channel.
Fuse: Type 3 AG, 3 A @ 250 VAC.
Temperature Limits: -40 to 140°F
(-40 to 60°C).
1/2
[12.70]
1-3/16
[30.16]
Storage Temperature Limits:
-40 to 176°F (-40 to 80°C).
On Time: 50 ms to 500 ms.
On Time Accuracy: ±10 ms.
On Time Stability: < ±1 ms.
Off Time: 1 s to 180 s.
Off Time Accuracy: ±5% of setting.
Weight: 9 oz (255 g).
Agency Approval: CE.
*Additional specifications on IOM.
OPTIONS
L, Mounting Bracket for Field Retrofits:
8-1/4 x 6-1/4 (209.55 mm x 158.75 mm)
WP, Weatherproof Housing:
Standard Models
Models with Option -L Mounting Bracket
375_Layout 1 7/21/14 12:59 PM Page 375
PROCESS CONTROL
Series
DCT600
Timer Controller
With Universal Power For Both 120 and 220 VAC
4-1/4
[107.95]
4 thru 10 channel boards
6-1/4 [158.75]
Timer Controllers
4-7/8
[123.8]
1/16
[1.59]
6-3/4 [171.45]
1/2
[12.7] 1-23/64
[34.53]
6-1/4
[158.75]
6-7/8
[174.62]
8-1/4 [209.55]
8-3/4 [222.25]
1-3/16
[30.16]
22 and 32 channel board
The Series DCT600 Timer Controller is a timing system for pulse-jet type dust
collectors or pneumatic conveying systems in either continuous or on-demand cleaning
applications. It provides either 4, 6, 10, 22 or 32 channels. The DCT600 was designed for
ease of installation in your dust collector system. For installations requiring fewer channels
than available on the board, a shorting plug (DCT604 & DCT610) or dip switches (DCT622
& DCT632) allows selection of the last used channel. Time-on and time-off settings are
selected using two potentiometers. High-limit and low-limit control inputs are provided for
use with on-demand systems. Units can also work in continuous clean mode. The new
enhanced board circuitry of the DCT600 synchronizes the on-time pulse to the power line
to achieve a pulse stability of ±1 msec. For safety, the control circuitry including the control
inputs and the last channel jumper is isolated from the power line.
Model
DCT604
DCT606
DCT610
DCT622
DCT632
Description
Timer Controller
Timer Controller
Timer Controller
Timer Controller
Timer Controller
No. of Channels
4
6
10
22
32
1/16
[1.59]
1/2
[12.7]
SPECIFICATIONS*
Output Channels: 4, 6, 10, 22 and 32 channels available.
Power Requirements: 85 to 270 VAC.
Power Consumption: 1.2 W.
Solenoid Supply: 300 VA.
Fuse: Type 3 AG, 3 A @ 250 VAC.
Temperature Limits: -40 to 140°F (-40 to 60°C).
Storage Temperature Limits: -40 to 176°F (-40 to 80°C).
On Time: 50 ms to 500 ms.
On Time Accuracy: ±5% of setting.
On Time Stability: ±1 ms.
Off Time:1 s to 180 s.
Off Time Accuracy: 5% of setting.
Weight: 9 oz (255 g).
Agency Approvals: CE, cUL, UL.
*Additional specifications on IOM.
OPTIONS
WP, Weatherproof Housing
4 thru 10 channel only
22 & 32 channels
L, Mounting Bracket for Field Retrofits (4, 6 or 10 channel boards only): 8-1/4 x 61/4 (209.55 mm x 158.75 mm)
Note: L mounting bracket available with 4, 6, or 10 channel models only.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
375
PROCESS CONTROL
376_Layout 1 7/21/14 12:28 PM Page 376
Series
DCT1000
Dust Collector Timer Controller
Modular Design, User Friendly, Up to 22 Channels
2-3/4
[69.85]
Timer Controllers
6-1/4
[158.75]
6-7/8
[174.62]
8-1/4
[209.55]
Simplify your on-demand cleaning requirements with the Series DCT1000 Dust
Collector Timer Controller. Relying on one timer board for on demand and continuous
cleaning applications, the DCT1000 eliminates external devices such as pressure switches,
relays and timers.
Offering a universal power supply, the DCT1000 accepts 85-270 VAC/VDC at either 50 or
60 Hz for both domestic and overseas requirements. The units modular design allows for
use as a continuous cleaning control or on-demand cleaning control using the optional plugin pressure module. A 4 to 20 mA process output is integral to the plug-in pressure module,
eliminating the need to purchase an expensive process transmitter. Mounting holes are
standard to other dust collector controllers used in the industry, allowing you to use the
DCT1000 for existing installations.
In addition, the DCT1000 is the same size for 6, 10 and 22 channels. One board size allows
the standardization on one enclosure. Latching relays and jumper wires are eliminated for
large installations requiring channel expanders. Each channel expander connected is
automatically detected.
1-13/16
[46.04]
8-3/4
[222.25]
SPECIFICATIONS
DCT1000 Timer Controller:
Output Channels: 6, 10, & 22
channels. Expandable to 255 channels
using DCT1122 & DCT1110 channel
expander boards.
Power Requirements: 85 to 270 VAC,
50 or 60 Hz.
Power Consumption: 5 W.
Solenoid Supply: 3 A max per
channel.
Fuse: 3 A @ 250 VAC. Low voltage
control circuitry is isolated from the line
voltage for system safety.
Temperature Limits: -40 to 140°F (-40
to 60°C).
Storage Temperature Limits: -40 to
176°F (-40 to 80°C).
On Time: 10 ms to 600 ms, 10 ms
steps.
On Time Accuracy: ±10 ms.
Off Time: 1 s to 255 s, 1 s steps.
1/16
[1.59]
Off Time Accuracy: ±1% of the value
or ±50 ms, whichever is greater.
Weight: 1 lb 3.0 oz (538.6 g).
Agency Approvals: cUL, UL.
DCP Pressure Module:
Pressure Ranges: 10 in w.c. or 20 in
w.c.
Temperature Limits: -40 to 140°F (-40
to 60°C).
Pressure Limit: 10 psi (68.95 kPa).
Pressure Limit (differential): 10 psi
(68.95 kPa).
Accuracy: ±1.5% FS @ 73°F (22.8°C).
Output Signal: 4 to 20 mA.
Alarm Contacts: 1.5 A inductive load,
3 A resistive load @ 30 VAC or 40
VDC.
Process Connections: Two barbed
connections for use with 1/8 (3.18
mm) or 3/16 (4.76 mm) ID tubing.
Weight: 5.5 oz (155.9 g).
OPTIONS
WP, Weatherproof Housing Only
WPP, Weatherproof Housing with Pressure Ports
WPPS, Weatherproof Housing with Pressure Ports, Three Position Rotary Switch
Installed
EXPL, Explosion-proof Housing
Multiple Boards, Stacked in enclosure
ACCESSORIES
DCA, Channel expander cable available in 1 ft, 2 ft, and 4 ft lengths
DPMA-402, Process Indicator
Model
DCT1022
DCT1010
DCT1006
DCT1122
DCT1110
DCP200A
DCP100A
376
Description
Master Controller
Master Controller
Master Controller
Channel Expander
Channel Expander
PressureModule
PressureModule
No. of Channels
22
10
6
22
10
D.P. Range
20 in w.c.
10 in w.c.
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
DCT in optional NEMA
4/4X weatherproof
enclosure.
DCT in optional
Explosion-proof
Enclosure.
Master Board
Stacked with
Channel Expander.
Model DCAC02
Cable Connection:
For connecting
multiple boards.
377_Layout 1 7/21/14 12:22 PM Page 377
PROCESS CONTROL
Series
DCT1000DC
Dust Collector Timer Controller
For Low Voltage Applications
2-3/4
[69.85]
PROCESS (IN H2O)
LAST OUTPUT
TIME OFF (SEC)
TIME ON (M SEC)
SETUP STATUS
UP
RUN
ALARM
RESET
DOWN
HIGH LIMIT
LOW LIMIT
HIGH ALARM
LOW ALARM
CYCLE DELAY (MIN)
MANUAL
SELECT
OVERRIDE
DOWN TIME CYCLES
(MIN)
AUTO ALARM RESET
(SEC)
6-1/4
[158.75]
Timer Controllers
6-7/8
[174.62]
1/16
[1.59]
8-1/4
[209.55] 8-3/4
[222.25]
Simplify your on-demand cleaning requirements with the Series DCT1000DC Dust
Collector Timer Controller. Relying on one timer board for on demand and continuous
cleaning applications, the DCT1000DC eliminates external devices such as pressure
switches, relays and timers.
The DCT1000DC accepts 10 to 30 VDC power. The units modular design allows for use as
a continuous cleaning control or on-demand cleaning control using the optional DCP plugin pressure module. A 4 to 20 mA process output is integral to the DCP pressure module,
eliminating the need to purchase an expensive process transmitter. A solenoid fault light
on the DCT1000DC notifies the operator when a solenoid valve fails to activate properly.
The DCT1000DC is the same size for 6, 10 and 22 channels. One board size allows the
standardization on one enclosure.
SPECIFICATIONS
DCT1000DC Timer Controller:
Output Channels: 6, 10, & 22
channels.
Power Requirements: 10 - 30 VDC.
Solenoid Supply: 3 A maximum per
channel.
Fuse: 3 A @ 250 VAC.
Temperature Limits: -40 to 140°F (-40
to 60°C).
Storage Temperature Limits:
-40 to 176°F (-40 to 80°C).
On Time: 10 ms to 600 ms, 10 ms
steps.
On Time Accuracy: ±10 ms.
Off Time: 1 s to 255 s, 1 s steps.
Off Time Accuracy: ±1% of the value
or ±50 ms, whichever is greater.
Weight: 1 lb 3.0 oz (538.6 g).
DCP Pressure Module:
Pressure Ranges: 10 in w.c. or 20 in
w.c.
Temperature Limits: -40 to 140°F (-40
to 60°C).
Pressure Limit: 10 psi (68.95 kPa).
Pressure Limit (differential): 10 psi
(68.95 kPa).
Accuracy: ±1.5% FS @ 73°F (22.8°C).
Output Signal: 4 to 20 mA.
Alarm Contacts: 1.5 A inductive load, 3
A resistive load @ 30 VAC or 40 VDC.
Process Connections: Two barbed
connections for use with 1/8 (3.18 mm)
or 3/16 (4.76 mm) ID tubing.
Weight: 5.5 oz (155.9 g).
Agency Approvals: CE.
DCT in optional NEMA 4/4X
weatherproof enclosure.
DCT in optional
explosion-proof enclosure.
OPTIONS
WP, Weatherproof Housing Only
WPP, Weatherproof Housing with Pressure Ports
WPPS, Weatherproof Housing with Pressure Ports, Three Position Rotary Switch
Installed
EXPL, Explosion-proof Housing
ACCESSORY
DPMA-402, Process Indicator
Model
DCT1022DC
DCT1010DC
DCT1006DC
DCP200A
DCP100A
Description
Master Controller
Master Controller
Master Controller
Pressure Module
Pressure Module
No. of Channels
22
10
6
D.P. Range
20 in w.c.
10 in w.c.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
377
PROCESS CONTROL
378_Layout 1 7/15/14 3:02 PM Page 378
Series
SVT
Solenoid Valve Enclosure with Timer
Compact Size, NEMA 4X Enclosure
9-55/64
[250.49]
Time Delay Relays
5-3/16
[131.80]
2-7/16
[61.77]
9-5/8
[244.48]
Scan here to watch product video
The Series SVT Solenoid Valve Enclosure with Timer is a compact, reliable and
economic package designed for small to medium filtration systems. It combines a timer board
and solenoid valve enclosure into one package, eliminating the need for separate enclosures
and wiring. The SVT is available with 2, 4 or 6 valves. For larger systems expansion modules
can be daisy chained to the SVT for a max of 60 outputs. The SVT is available in either 90 to
240 VAC or 240 VDC/VAC supply voltages allowing it to be used in low or high voltage
applications. On-demand cleaning or down time cleaning functions can be selected with a simple
dip-switch. Time-on and time-off settings are selected using two potentiometers.
Number of
Supply
Description
Solenoids
Model
Voltage
Solenoid Valve Enclosure with Timer 2
SVT-2
90 to 240 VAC
Solenoid Valve Enclosure with Timer 3
SVT-3
90 to 240 VAC
Solenoid Valve Enclosure with Timer 4
SVT-4
90 to 240 VAC
Solenoid Valve Enclosure with Timer 6
SVT-6
90 to 240 VAC
SVT-2-DC Solenoid Valve Enclosure with Timer 2
24 VDC/VAC
SVT-3-DC Solenoid Valve Enclosure with Timer 3
24 VDC/VAC
SVT-4-DC Solenoid Valve Enclosure with Timer 4
24 VDC/VAC
SVT-6-DC Solenoid Valve Enclosure with Timer 6
24 VDC/VAC
Expansion Module
3
SVTE-3
Any
ExpansionModule
4
SVTE-4
Any
Expansion Module
6
SVTE-6
Any
Note: SVTE modules are powered from the main enclosure and can be used with either
the 90 to 240 VAC or the 24 VDC/VAC Model SVT•s.
Series
820
SPECIFICATIONS
Service: Compatible gases, filtered and oil free.
Wetted Materials: Pilot body: Brass; Spring: 302 SS; O-ring: NBR.
Temperature Limits: 14 to 140°F (-10 to 60°C).
Pressure Limit: 145 psi (10 bar).
Power Requirements: 90 to 240 VAC, 50 or 60 Hz or 24 VAC/VDC ±10%.
Power Consumption: 25 VA.
Fuse: 0.5 A delayed.
Electrical Connection: 2 DIN A 43652 connectors.
Enclosure Rating: NEMA 4X (IP66).
Enclosure Material: Polyamide with carbon fiber, polycarbonate, TPE rubber.
Process Connection: 1/4 OD push to connect.
Mounting Orientation: Any position.
On-Time: 150 ms to 700 ms.
Off-Time: 4 s to 210 s.
Agency Approvals: CE.
DIN Rail Mountable Time Delay Relay
15 Amp, SPDT/DPDT Operation
RoHS
11/16
[17.60]
2-9/16
[65.00] 1-11/32
[34.20]
5/8
[16.00]
2-21/32
[67.50]
1-25/32
[45.30]
The Series 820 DIN Rail Mountable Time Delay Relays can be configured in accordance
with 10 different timing functions. Bright red and green LED’s indicate whether the input has
been triggered and if the output is active. For greater accuracy, there are 10 time scales and a
fine adjustment potentiometer that allows adjustment down to 0.1 seconds. Integral mounting
ears allow the Series 820 to mount directly to a DIN rail.
Model
821TD10H-UNI
822TD10H-UNI
378
Contact Configuration
SPDT
DPDT
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
3-35/64
[90.00]
SPECIFICATIONS
Operating and Load Voltage Range: 12 to 240 VAC / VDC.
Electrical Rating: 15 A @ 240 VAC, 24 VDC.
Timing Rating:
Functions available: A, B, C, D, E, F, G, H, I, J (10 for total);
Time ranges: 0.1 sec to 10 days.
Electrical Connection: Screw terminals.
Switching Operation: SPDT or DPDT.
Temperature Limits:
Storage: -22 to 158°F (-30 to 70°C);
Operation: -4 to 131°F (-20 to 55°C).
Power Consumption: 3 VA (AC) or 1.7 W (DC).
Housing: Plastic polycarbonate.
Weight: 2.3 oz (65 g).
Agency Approvals: CE, RoHS, cUL, UL.
379_Layout 1 7/21/14 8:55 AM Page 379
PROCESS CONTROL
Series
TDRSOX/
SRX
Time Delay Relay
12 Amp, DPDT Operation
RoHS
Digital Switch Position
II
III
IV
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
CONTACTS:
1/3HP 120VAC
1/2HP 240VAC
12A, 120-24DVAC/30VDC
TDRSOXP-XXXV
N DELAY/INTERVAL
XXXVAC/VDC
TIMING RANGE
0.1 SEC TO 10 HRS
ON
D
TDRSXXP-XXXV
OUTPUT
INPUT
On Delay
Interval
Digital Switch Position
I
OFF
ON
1-47/64
[44.00]
Off
On
I
II
III
IV
Function
Time
Time
Time
3-25/64 [86.00]
2-9/16
[65.00]
TIME DELAY RELAY
8-PIN SHOWN
11-PIN AVAILABLE
The Series TDRSOX/SRX Time Delay Relay combines the functionality of a timer
and a relay in a compact socket mount enclosure. For quick set up, the timer features DIP
switches that allow the user to choose between two function modes and eight timing scale
ranges. TDRSOX models offer On Delay and Interval function modes, and TDRSRX models
offer Off Delay and Retriggerable One Shot function modes. The timing scale ranges can
be set from .1 seconds to 10 hours. The dual LEDs allow the user to know when power is
present at the coil and when the output is energized.
Model
TDRSOXP-24V
TDRSOXP-120V
TDRSRXP-24V
TDRSRXP-120V
Input Voltage
24 VDC / VAC
120 VDC / VAC
24 VDC / VAC
120 VDC / VAC
Timing Range
0.1 s to 10 h
0.1 s to 10 h
0.1 s to 10 h
0.1 s to 10 h
ACCESSORIES
70-750DL8-1, Socket for 750H and TDRSOX/SRX Series Relay
70-ASMM-24, Protection Modules, MOV Supressor, 24 VAC/VDC
70-ASMM-120, Protection Modules, MOV Supressor, 120 VAC/VDC
16-750/788CBJ-1, Coil Bus Jumpers
Series
TR-7
MADE IN CHINA
ON DELAY
43/64
[17.00]
IN
OUT
INTERVAL
IN
OUT
SPECIFICATIONS
Operating and Load Voltage Range: 24, 120 VDC/VAC.
Electrical Rating: 12 A, 120 to 240 VAC/30 VDC.
Switching Voltage: 120 to 240 VAC, 50/60 Hz; 30 VDC; 1/3 HP @ 120 VAC; 1/2 HP
@ 240 VAC; B300 pilot duty.
FunctionsAvailable:
A, C (On delay, interval);
D, E (Off delay, one shot).
Timing Rating: Time Ranges: 0.1 sec to 10 hr.
Electrical Connection: Silver alloy contacts.
Switching Operation: DPDT.
Temperature Limits:
Storage: -22 to 185°F (-20 to 85°C);
Operation: -4 to 131°F (-20 to 55°C).
Power Consumption: 5 VA; 2.5 W.
Weight: 3 oz (85g).
Agency Approvals: RoHS, cUL, UL, cUR, UR.
SAFE-T-GROUND
Explosion-proof, Intrinsically Safe, Ground Continuity Control
8-1/16 [204.77]
5-25/32
[146.91] 4-31/64 7/16
[113.79] [11.11]
6-5/8 [168.28]
TR-7L
Model TR-7 Safe-T-Ground provides continuous monitoring of a truck’s ground
connection throughout loading operations. Static electricity is often brought in by tank
trucks entering the loading area. The Safe-T-Ground Model TR-7 instantly stops loading
operations if a tank truck loses its ground.
To safeguard loading operations, the Safe-T-Ground circuit can be wired into your pump
control – and to an audible alarm or signal light.
Complete Model Chart
Example
TR-7 B
L TR-7-BL, Ground continuity control, 120 VAC, 36
coiled cable, alligator clamp, with indicating lights
Explosion-proof and intrinsically safe
120 VAC(standard)
220/240 VAC
Construction TR-7
Power
Supply
U
Option
Cable
B
Connection
Cable
X
Length
L
Options
Stud (standard)
Battery (alligator) clamp
36 coiled, extends to 16´ (standard)
72 coiled, extends to 32´
Red and green indicating lights
3/4 NPT CONDUIT
OPENING (TYP.)
SPECIFICATIONS
Housing: 356-T6 cast aluminum alloy
(copper-free), explosion-proof … Class
I, Group D.
Size: 6-5/8˝ W x 10-3/8˝ H x 5-5/8˝ D.
Power Requirements: 105-125 VAC,
60 Hz. 7.75 watts - with light, 1.75
watts - without lights. Optional 220-240
VAC, 50/60 Hz.
Electrical Rating, Relay: DPDT, 10
amps, 125 VAC, 60 Hz contact rating.
Wiring: Terminal strip.
Conduit Connection: 3/4˝ NPT
Installation: 7/16 mounting lugs,
integrally cast.
Contactor: (Grounding clamp) molded
polyethylene with beryllium copper
contact clips. 16-2 type SO coiled
cable; retracts to 3 , extends to 16 .
Grounding Studs: 2 supplied. Order a
pair for each truck.
Shipping Weight: 20 lb with contactor
and cord.
Agency Approvals:UL.
Options: Integral pilot lights; 30 coiled
cable; Temporary contactor
assemblies, clamp connectors, and
other supply voltages.
Model TR-7
Model TR-7-L (Integral Pilot Lights)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
379
Ground/Continuity Controls
SELECTING FUNCTION
Function
When used with socket 70-750DL8-1 or
70-750E8-1 or 70-464-1
Current limited to rating at relay or socket
whichever is less.
1-27/64
[36.00]
SELECTING TIME RANGE
Time Range
0.1sec-1sec
1sec-10sec
10sec-100sec
0.1min-1min
1min-10min
10min-100min
0.1hr-1hr
1hr-10hr
PROCESS CONTROL
380_Layout 1 7/8/14 11:10 AM Page 380
Series
DPM
Particulate Monitor & Control
Real-Time Leak Gage, Adjustable Alarm Points
6-5/16
[160.34]
Particulate (Dust or
Broken Bag) Sensors
4-3/8
[11.13]
Together the DPM Particle Monitor and the PMS Particle Sensor:
€ Prevent false readings from:
- Moist and conductive dusts
- Corrosive gases and condensate
- Dust buildup
€ For baghouses, cartridge filters, bin vents, and cyclones
€ Protect downstream blowers, oxidizers, HEPAs, etc.
€ Keep a clean workplace and be a good neighbor
Model
DPM-A111
DPM-A112
DPM-A113
DPM-A121
DPM-A122
DPM-A123
DPM-AHZ111
DPM-AHZ112
DPM-AHZ113
DPM-AHZ121
DPM-AHZ122
DPM-AHZ123
System Rating
Weatherproof/NEMA 4X (IP66)
Weatherproof/NEMA 4X (IP66)
Weatherproof/NEMA 4X (IP66)
Weatherproof/NEMA 4X (IP66)
Weatherproof/NEMA 4X (IP66)
Weatherproof/NEMA 4X (IP66)
Intrinsically Safe*
Intrinsically Safe*
Intrinsically Safe*
Intrinsically Safe*
Intrinsically Safe*
Intrinsically Safe*
Range
5.0 pA - 5000 pA
5.0 pA - 5000 pA
5.0 pA - 5000 pA
0.5 pA - 5000 pA
0.5 pA - 5000 pA
0.5 pA - 5000 pA
5.0 pA - 5000 pA
5.0 pA - 5000 pA
5.0 pA - 5000 pA
0.5 pA - 5000 pA
0.5 pA - 5000 pA
0.5 pA - 5000 pA
*DPM models listed intrinsically safe are to be used with corresponding intrinsically safe PMS models
making an intrinsically safe control loop. The PMS model can then be installed in a hazardous location
according to approval ratings listed. The DPM itself is not intrinsically safe and must be installed outside
the hazardous location.
380
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
4-3/8
[111.13]
SPECIFICATIONS
Inputs: From PMS sensor.
Output Ratings:
Alarm relays: 2 form A (SPST) rated 5 A@ 240 V res. (must provide an 8 A
(max) fuse in series with relay load);
Analog: 4 to 20 mA (option RC).
Power Requirements: 115 VAC 50/60 Hz, 230 VAC 50/60 Hz, or 24 VDC.
Power Consumption: 6 watts max.
Accuracy: Standard: ±5% of range, Optional: ±1% of range.
Display: LCD.
Display Resolution: Standard: 5 pA; Optional: 0.5 pA.
Memory Backup: For set point storage only.
Temperature Limits: -13 to 160°F (-25 to 70°C).
Weight: 4.5 lb (2.0 kg).
Enclosure: Cast aluminum, weatherproof, NEMA 4X (IP66).
Loop Power Supply (Isolated): 17 VDC loop supply provided by DPM control unit
for PMS sensor.
Agency Approvals: CE &CSA.*
Input Power
115 VAC 50/60 Hz
230 VAC 50/60 Hz
24 VDC
115 VAC 50/60 Hz
230 VAC 50/60 Hz
24 VDC
115 VAC 50/60 Hz
230 VAC 50/60 Hz
24 VDC
115 VAC 50/60 Hz
230 VAC 50/60 Hz
24 VDC
OPTION
Analog Output (4-20 mA), add -RC to the end of the model number
6-19/64
[159.94]
4-11/32
[110.33]
MOUNTING
6-19/64
[159.94]
The DPMParticle Monitor and PMS Particulate Sensor combine to provide a basic
baghouse and cartridge filter leak detector designed for general maintenance planning
and process protection. It is easy to use and reliable. Leakage is gauged in real-time, onthe-spot, without prior baseline data and without signal tuning. Simply apply power and
the general condition of the filter is quickly determined. An alarm point is set by simply
moving an indicator up and down the gage with the convenient, lockable key pad. For more
precise alarm setup the large display provides both a logarithmic analog bar graph and an
absolute digital readout. The log scale enables the user to observe both the baseline bleed
through and the high peaks that are caused by filter cleaning cycles and developing leaks.
Observation of both baseline and peaks is essential to setting proper alarms. The digital
readout in absolute units ensures correct interpretation of the readings and provides
accurate historical comparisons.
The DPM Particle Monitor is housed in a rugged cast aluminum enclosure. An LCD
displays particulate levels in bar-graph and digital forms. A lockable membrane keypad is
provided for setup and adjustment.
4-11/32
[110.33]
MOUNTING
381_Layout 1 7/8/14 11:09 AM Page 381
PROCESS CONTROL
Particulate Sensor
Series
PMS
Reliable Operation, Minimal Maintenance
6-3/32
[154.78]
FLANGE
2-15/16
[74.61]
CONDUIT ENTRY
NPT MOUNT
PMS Particulate Sensor
€ More effective control than•broken bag detectorsŽ.
€ Protect downstream blowers, oxidizers, HEPAs, etc.
€ For baghouses, cartridge filters, bin vents, and cyclones.
€ Repeatable in all applications (conductive and moist dusts).
How To Order:
Determine model number from model chart using example as a guide.
Select desired length of Particulate Sensor cable from cable model chart.
Process Connection
Maximum Process
Temperature
Maximum Process
Pressure
Insertion Length
(Recommended at Least 1/2
Duct Diameter)
1
2
3
4
T1
T2
T3
T4
P1
P2
Model
Description
Model
CAB-30
10 foot sensor cable
CAB-10
CAB-40
20 foot sensor cable
CAB-20
Consult factory for custom cable lengths up to 300 feet.
L1.5
L03
L05
L10
L15
L20
L30
L36
L48
L60
L72
3
[76.2]
MOUNT
3
[76.2]
MOUNT
QUICK CLAMP
1˝ MALE NPT
FlangeMount
The PMS Particulate Sensor employs a field-proven combination of passive-induction
and protected-probe technologies. As particles flow near and around the probe, minute
currents are dynamically induced into the probe by flowing particulate. A DSP processes
the signal into an absolute output that is reasonably linear to mass. Protective layers over
the probe work in combination with induction-sensing to ensure reliable operation with all
types of particulate including moist powders and highly conductive dusts. Maintenance is
minimal and there is no need for an air purge. For durability, the sensors are passive and
free of electronics. The PMS Particulate Sensor is designed to be used with the DPM
Particle Monitor in order to be intrinsically safe.
PMS A1
1 T1 P1 L1.5
PMS
A1
AHZ1
2-15/16
[74.61]
OPTIONAL HIGH
PRESSURE / TEMPERATURE
SEALING GLAND
DO NOT LOOSEN
NPTMount
INSERTION
LENGTH
3-29/32
[99.22]
INSERTION
LENGTH
2-15/16
[74.61]
Example
Series Designator
Enclosure Rating
3-13/16
[96.84]
NIPPLE
INSERTION
LENGTH
Quick ClampMount
SPECIFICATIONS
Service: Air and compatible gases, any type particulate.
Wetted Materials: T1 and T2: 316SS and PFA; T3 and T4:316SS and ceramic.
Temperature Limits:
Ambient: Maximum -40 to 392°F (-40 to 200°C) (max must be calculated for each
application);
Process: See model chart.
Pressure Limits:
Standard: Full vacuum to 10 psi (0.69 bar);
Optional: 100 psi (6.89 bar).
Output Signal: pA.
Electrical Connection: Low noise coaxial.
Process Connection: See model chart.
Enclosure:
Standard: Painted cast aluminum, weatherproof, NEMA 4X (IP66);
Optional: Intrinsically safe, CSA (must use with proper DPM model).
Weight: Varies depending on length of probe and type of mount.
Agency Approvals: CE, CSA
PMS-A11T1P1-L1.5:PMS Particulate Sensor, Weatherproof, NEMA 4X (IP66),
1/2 NPT Connection, 250°F Max Temp., 10 psi Max Pressure, 1.5 Probe.
PMS Particulate Sensor
Weatherproof, NEMA 4X (IP66)
Intrinsically Safe, CSA & CEA Approvals, Class I, II, and III. Division I & II, All
Groups, NEMA 4X (requires Quick Clamp connection or flange mount)
1/2 NPT
1 NPT with 1.5 Quick Clamp Connection
2 150# ANSIFlange
2 150# ANSI Flange with Process Mating Flange and Installation Kit
250°F (121°C)
450°F (232°C)
800°F (426°C) - requires flange mount
1200°F (649°C) - requires flange mount
10 psi
100 psi - requires flange mount
1.5 Probe
3 Probe
5 Probe
10 Probe
15 Probe
20 Probe
30 Probe
36 Probe
48 Probe
60 Probe
72 Probe
Description
30 foot sensor cable
40 foot sensor cable
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
381
Particulate (Dust or
Broken Bag) Sensors
5-3/64
[128.19]
3-13/16
[96.84]
NIPPLE
PROCESS CONTROL
382_Layout 1 7/8/14 11:09 AM Page 382
Series
PMT
Particulate Transmitter
Particulate (Dust or
Broken Bag) Transmitters
2-Wire Loop Powered
5-3/64
[128.19]
6-3/32
[154.78]
INSERTION
LENGTH
3-13/16
[96.84]
NIPPLE
FLANGE
2-15/16
[74.61]
INSERTION
LENGTH
2-15/16
[74.61]
CONDUIT ENTRY
OPTIONAL HIGH
PRESSURE / TEMPERATURE
SEALING GLAND
DO NOT LOOSEN
3-29/32
[99.22]
3-13/16
[96.84]
NIPPLE INSERTION
LENGTH
2-15/16
[74.61]
3 [76.2]
MOUNT
3 [76.2]
MOUNT
QUICK CLAMP
1˝ MALE NPT
NPTMount
The Series PMT Particulate Transmitter is a reliable dust collector emissions monitor
and leak detector. The loop powered design is ideal for direct connection to existing PLCs
or other baghouse diagnostic control systems. Adjustable linear or logarithmic output
scaling enables trending both the baseline emissions and the high peak emissions that are
caused by filter cleaning cycles and developing leaks. Observation of both baseline and
peaks is essential to setting proper alarms. The PMT Particulate Transmitter employs a
field-proven combination of induction and protected-probe technologies. As particles flow
near and around the probe, minute currents are dynamically induced into the probe. The
signal is processed into an absolute output relative to the amount of particulate and thus
leakage. Protective-layers over the probe work in combination with induction-sensing to
ensure reliable operation with all types of particulate including moist powders and highly
conductive dusts. Maintenance is minimal and there is no need for an air purge
The Series PMT Particulate Transmitter:
€ For baghouses, cartridge filters, bin vents, and cyclones
€ Simple, low cost 2-wire installation for PLCs
€ Prevent false readings from:
- Moist and conductive dusts
- Corrosive gases and condensate
- Dust buildup
€ Protect downstream blowers, oxidizers, HEPAs, etc.
€ Repeatable in all applications (conductive and moist ducts)
Example
Series Designator
Enclosure Rating
PMT A1
1 T1 P1 1
PMT
A1
AHZ2
Process Connection
1
2
3
4
Maximum Process
T1
Temperature
T2
Maximum Process
P1
Pressure
Range
1
2
3
Insertion Length
(Recommended
at Least
1/2 Duct Diameter)
382
L1.5
L1.5
L03
L05
L10
L15
L20
L30
L36
FlangeMount
Quick ClampMount
SPECIFICATIONS
Service: Air and compatible gases, any type particulate conductive or nonconductive.
Wetted Materials: 316 SS and PFA.
Air Velocity Range: 300 ft/min and higher.
Minimum Detection: Standard: 10.0 pA; Optional: 5.0 pA and 0.5 pA.
TemperatureLimits:
Ambient: -15 to 160°F (-25 to 70°C);
Process: Standard: -40 to 250°F (-40 to 120°C);
Optional: -40 to 450°F (-40 to 232°C).
Pressure Limit: 10 psi (0.69 bar).
Power Requirement: 18 to 28 VDC (24V nominal).
Output Signal: 4 to 20 mA.
Loop Resistance: 300 max.
Current Consumption: Powered from 4 to 20 mA loop.
Electrical Connection: Terminal block.
Process Connection: See model chart.
Enclosure Rating: Weatherproof, NEMA 4X (IP 66).
Mounting Orientation: Any.
Weight: Varies with length of probe and type of mount.
Agency Approvals: CE, CSA.
PMT-A11T1P11-L1.5:PMT Particulate Transmitter, Weatherproof/NEMA 4X (IP66), 1/2 NPT
Connection, 250°F Max Temp., 10.0 psi Max Pressure, 10.0 pA -1.5 Probe.
PMT Particulate Transmitter (1-piece configuration, Sensor included in price)
Ordinary/General Purpose Locations, CE Approval, NEMA 4X (IP66), CSA
Hazardous Location, CSA Approval, Class I, Division II, Groups A-D. Class II, Groups F, G
1/2 NPT
1 NPT with 1.5 Quick Clamp Connection
2 150# ANSIFlange
2 150# ANSI Flange with Process Mating Flange and Installation Kit
250°F (120°C)
450°F (232°C)
10 psi
10.0 pA - 5000 pA
5.0 pA - 5000 pA
0.5 pA - 5000 pA (required for low levels or EPA leak detection)
1.5 Probe
3 Probe
5 Probe
10 Probe
15 Probe
20 Probe
30 Probe
36 Probe
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
383_Layout 1 7/9/14 12:27 PM Page 383
PROCESS CONTROL
Series
VBS
Vibration Switch
Adjustable Switch and Delay Settings, Continuous 4 to 20 mA Output
M12X1
4 PIN CONNECTION
Analog
Out
4...
20
mA
1-1/16˝
[26.87]
mm/s
RMS Set
inch/s
2-7/8˝
[73.05]
18...
32
VDC
sec
Delay Set
sec
pnp
500 mA
CKING
10
15
POWER
VBS-X
Scan here
to watch
product video
M8 CONNECTION
[316 SS]
The Series VBS Vibration Switch is small, compact, and uses two easy set up dials that
adjust the maximum RMS velocity set point and false trip time delay. The Series VBS is
intended to continuously monitor the changes in a machine’s vibration level. The VBS
takes real-time RMS vibration input and provides an analog output of velocity as well as a
switching output when an alarm value is exceeded.
FEATURES
€ Easy set-up and operating concept
€ 4 to 20 mA output
€ No software required
€ Adjustable switch and delay set point
1-1/32˝
[25.91]
APPLICATIONS
Vibration monitoring for:
€ Motors
€ Pumps
€ Fans
€ Engines
€ Compressors
€ Centrifuges
€ Generators
€ Turbo chargers
€ Gear boxes
€ Conveyors
Model
VBT-1
SPECIFICATIONS
Housing Material: PBT, PC, FPM, and
316 SS.
Temperature Limit: -22 to 221°F (-30 to
105°C).
Accuracy: < ±3%.
Measuring Range: 0 to 50 mm/s.
Connections: M12 connector.
Enclosure Rating: NEMA 6 (IP67).
Electrical Rating: 18 to 32 VDC.
Mounting Orientation: All.
Nonlinearity: < ±0.25% of span.
Switch Output Range:
VBS-1: 0 to 25 mm/s Vrms;
VBS-2: 0 to 50 mm/s Vrms.
Analog Output Range: 10 to 1000 Hz.
Output Signal: 4 to 20 mA.
Switch Type: PNP NO (500 mA max).
Switch Time Delay: 1 to 60 s.
Repeatability: < 0.5%.
Weight: 0.25 lb (0.114 kg).
Agency Approval: CE.
Model VBS-1, Vibration Switch 0 to 25 mm/s Vrms Range
Model VBS-2, Vibration Switch 0 to 50 mm/s Vrms Range
Vibration Transmitter
Continuous 4 to 20 mA Output Signal
M12 CONNECTOR
Ø7/8˝
[22.00]
2-1/2˝
[63.25]
Scan here
to watch
product video
1/4˝-28 UNF
The Model VBT-1 Vibration Transmitter continuously detects the vibration in a
system and monitors for unusual operating conditions and potential failure. The vibration
is converted into an analog signal at the current output. The VBT requires no setup, and
there is no software required for configuration. The 2-wire loop power operation, combined
with standard M12 micro cable connector and interchangeable mounting studs (1/4˝-28
UNF/M8 (2) or the 1/4˝-28 UNF), makes for a fast and reliable installation.
FEATURES
€ Easy set-up and operating concept
€ 4 to 20 mA output
€ No software required
€ Stainless steel housing
7/8˝
[22.23]
APPLICATIONS
Vibration monitoring for:
€ Motors
€ Pumps
€ Fans
€ Engines
€ Compressors
€ Centrifuges
€ Generators
€ Turbo chargers
€ Gear boxes
€ Conveyors
SPECIFICATIONS
Housing Material: 316 SS.
Temperature Limit: -22 to 221°F (-30 to 105°C).
Accuracy: < ±3%.
Connections: M12 connector.
Enclosure Rating: NEMA6 (IP68).
Electrical Rating: 9.6 to 32 VDC.
Mounting Orientation: Any position.
Nonlinearity: < ±0.25% of span.
Frequency Range: 10 to 1000 Hz.
Output Signal: 4 to 20 mA.
Repeatability: < 0.5%.
Weight: 0.28 lb (0.125 kg).
Agency Approval: CE.
Model VBT-1, Vibration Transmitter
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
383
Vibration Controls
2-1/2˝
[63.67]
PROCESS CONTROL
384_Layout 1 7/15/14 2:45 PM Page 384
Model
CBAS
Belt Alignment Switch
Adjustable Activation Angles, Two Micro Switches
ø2-3/8
[ø60.33]
TOUCH
PULLEY
Conveyor Controls
5-9/16
[141.29]
75°
2-9/16
[65.09]
2-9/16
[65.09]
3-11/32
[84.93]
5-21/64
[135.33]
5-49/64
[70.25]
2X 3/4˝ NPT
3/16 [4.76]
1/4 [6.35]
51/64 [20.24]
1-15/32 [37.31]
The Model CBAS Belt Alignment Switch is a rugged and reliable conveyor belt
alignment switch. The compact die cast aluminum enclosure is designed for easy
installation. The switch cover allows for simple access to wiring terminals and CAM
adjustments. Belt alignment switches are typically used in pairs with one switch on each
side of the conveyor belt mounted near the first and/or last pulley of a conveyor. Each CBAS
is equipped with two micro switches, allowing one actuation angle for small belt deviations
and a second actuation angle for extreme belt deviations. The actuation angles are factory
set at 20 degrees and 35 degrees, each actuation angle can be easily adjusted in the field
to fit any application.
Model CBAS-1, Conveyor Belt Alignment Switch
Model
CPS
10-9/16
[268.29]
3-43/64
[93.27]
9/32
[7.14]
29/32 [25.02]
1-63/64
2X 13/32
[50.4]
[10.32]
MOUNTING
HOLES
SPECIFICATIONS
Temperature Limits: -4 to 140°F (-20
to 60°C).
Enclosure: Die cast aluminum.
Enclosure Rating: NEMA 6 (IP67).
Switch Type: 2 SPDT.
Electrical Rating: 10 amp @ 125/250
VAC; 1/2 amp @ 125 VDC.
Electrical Connection: 3 screw type,
common, NO, NC.
2X 1-1/2
[38.1]
5-1/8
[130.18]
2X 2-11/64
[55.17]
Electrical Conduit: Two 3/4 female
NPT.
Activation Angles: 20° and 35°
(adjustable).
Activation Force: 0.8 to 1.2 lb. (0.36
to 0.54 kg).
Control Type: Automatic reset.
Weight: 6.4 lb (2.9 kg).
Cable Pull Switch
For Emergency or Normal Shut-Off
63/64
[25]
5-1/8
[130.18]
8-7/16
[214.31]
3-7/16
[87.31]
2X 3/4˝
NPT
3-15/16
[100.01]
2-9/16
[65.09]
RESETTING
LEVER
Model CPS-1, Cable Pull Switch
384
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
LOCK POSITION
OPERATING
DIRECTION
31/64
[12.3]
2-49/64
[70.25]
29/32 9/32
[23.02] [7.14]
2X 1-1/2
[38.1]
1-31/32
51/64 [50]
[20.24]
6-1/16
[153.99]
The Model CPS Cable Pull Switch is designed to provide a switching system to isolate
the power to the conveyor system or other similar process equipment in event of a shutdown condition. A steel wire is placed along the side of the conveyor and attached to the
cable pull switch. When the cable is pulled at any point along the conveyor it will trip the
cable pull switch causing the conveyor to shut down. To restart the conveyor the CPS must
be manually reset. The CPS has a universal design for bi-directional activation and utilizes
a highly visible red flag to indicate the switch status. The compact design makes it ideal
for easy installation.
30°
1-31/32 [50]
2-21/64
[59.13]
1/8 [3.18]
2-15/64 [5.95]
61/64
[24.21]
3-23/64
[85.33]
3-15/16
[100.01]
1-1/8
[28.58]
1/4
19/32 [6.35]
[15.03]
SPECIFICATIONS
Temperature Limits: -4 to 140°F (-20
to 60°C).
Enclosure: Die cast aluminum.
Enclosure Rating: NEMA 6 (IP67).
Switch Type: 2 SPDT.
Electrical Rating: 10 amp @ 125/250
VAC; 1/2 amp @ 125 VDC.
Electrical Connection: 3 screw type,
common, NO, NC.
1-37/64
[40.08]
5-1/8
[130.18]
2-9/16
[65.09]
2X 2-11/64
[55.17]
ø13/32
[10.32]
MOUNTING
HOLES
Electrical Conduit: Two 3/4 female
NPT.
Activation Angles: 30 degrees.
Activation Force: 11 ±2.25 lb. (5 ±1
kg).
Control Type: Manual reset.
Weight: 6.4 lb (2.9 kg).
385_Layout 1 7/15/14 2:42 PM Page 385
Universal Input Data Logger
Internal Temperature Sensor, Optional Internal Humidity Sensor
and Display, Universal Inputs
RoHS
PROCESS CONTROL
Series
UDL
3-1/16
[77.79]
2-5/8
[66.68]
The Series UDL Universal Input Data Loggers are available with 0, 2, or 4 universal
inputs. Each universal input can be individually configured to accept a thermocouple, RTD,
thermistor, voltage, or current input. All Series UDL data loggers have an internal
temperature sensor and a digital input which can be used as a trigger to start logging or as
a pulse counter for interfacing with flowmeters or other sensors with a pulse output. Optional
features include an internal humidity sensor, an LCD display, and an external humidity and
temperature sensor. The Series UDL loggers interface to the USB port of a PC. The unit
includes software, USB connection cable and installed battery.
Model
UDL-000
UDL-100
UDL-010
UDL-110
UDL-002
UDL-102
UDL-012
UDL-112
UDL-004
UDL-104
UDL-014
UDL-114
Sensors Included
Internal temperature sensor
Internal temperature sensor w/ display
Internal temperature/RH sensor
Internal temperature/RH sensor w/ display
Internal temperature sensor, 2 universal inputs
Internal temperature sensor, 2 universal inputs w/ display
Internal temperature sensor/RH, 2 universal inputs
Internal temperature sensor/RH, 2 universal inputs w/ display
Internal temperature sensor, 4 universal inputs
Internal temperature sensor, 4 universal inputs w/ display
Internal temperature sensor/RH, 4 universal inputs
Internal temperature sensor/RH, 4 universal inputs w/ display
Data Loggers, Indicating
4-13/16
[122.24]
4-1/4
[107.95]
1-1/4
[31.75]
SPECIFICATIONS
Inputs: RTD, thermocouple, thermistor, current, voltage, slidewire.
Range: Internal temperature: -22 to 158°F (-30 to 70°C); Internal RH: 0 to 100%;
External temperature: -22 to 158°F (-30 to 70°C); External RH: 0 to 100%.
Accuracy: Internal temperature: ±1°F (± 0.5°C); External temperature: ±1°F
(±0.5°C) over 30 to 122°F (0 to 50°C), ±2°F (±1°C) over -30 to 32°F (-30 to 0°C)
and 122 to 158°F (50 to 70°C); Internal/external RH: ±2.0% RH over 10% to 90%,
±4.0% RH over 0 to 10% and 90 to 100% RH.
Memory Size: 0 or 2 universal inputs: 62,000 readings; 4 universal inputs:
128,000 readings.
Resolution: All universal inputs: 16 Bit; Internal & external temperature: 12 Bit;
Internal & external RH: 8 Bit.
Sampling Method: Stop when full or continuous logging (wrap when full).
Sampling Rate: Selectable from 1 s to 24 hrs.
Computer Requirements: Windows® 98, Windows® 2000, Windows® ME,
Windows NT®, Windows® XP, and Windows Vista® operating system with 16 MB
RAM, one free USB port.
Power Requirements: 3.6 V AA lithium metal battery, installed functional, user
replaceable.
Battery Life: 6 years (approx.).
Alarms: Programmable high/low.
Interface: USB port (cable included).
Housing Material: ABS plastic.
Weight: 5.8 oz (165 g).
Agency Approval: CE, RoHS.
ACCESSORIES
DL500-LITE*, Lite Version Windows® Operating System Software
DL500**, Full Version Windows® Operating System Software Key
UDL-RH, Remote Humidity Probe
UDL-PS, Power Supply
*Free download from website
**Need lite version also
Windows®, Windows NT®, and Windows Vista® are registered trademarks of
Microsoft Corporation.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
385
PROCESS CONTROL
386_Layout 1 7/8/14 11:07 AM Page 386
Model
GDL
Graphical Display Data Logger
Measure Temperature, Humidity and Dew Point, Instant Display
Data Loggers, Indicating
3-1/16
[77.79]
4
[101.6]
The Model GDLGraphical Display Data Logger can record and instantly display
trends for temperature, humidity and dew point. The display can show measurement trends
in text or graphic format. Other features include a logging summary which details the sample
rate and memory status. Recording starts immediately with the push of a button or at a
user specified date and time. With the Windows® based software, the user can select the
sampling interval, high/low alarm settings, logging channels and recording start time. Over
40,000 data points can be downloaded by way of a PC’s USB port. Measured data stays
secure with a recording session counter and password-protected calibration. The Model
GDL comes with batteries, software and a USB cable.
Model GDL, Graphical Display Data Logger
1-1/2
[38.1]
SPECIFICATIONS
Memory Size: 43,344 temperature;
21,672 temperature, RH and dew
point.
Temperature Range:15 to 150°F (-10
to 65°C).
Temperature Accuracy: ±1°F
(±0.5°C).
Temperature Resolution: 0.01°F
(0.01°C).
Humidity Range: 0 to 99% RH.
Humidity Accuracy: ±2% RH, from 10
to 90% RH.
Humidity Resolution: 0.01% RH.
Sampling Method: Stop on memory
full or continuous recording.
Sampling Rate: 1 s to 18 hrs, 1 s
increments.
Computer Requirements: Windows®
98 and above (software included).
Power Requirements: (3) AA alkaline
batteries, installed functional, user
replaceable.
Alarms: Programmable high/low.
Interface: USB port (cable included).
Weight: 7 oz (20 g).
Agency Approvals: CE.
Windows® is a registered trademark of Microsoft Corporation
Model
GDL-T
Graphical Display Data Logger
3 External Temperature Sensors, 1 Internal Temperature Sensor
1-1/2
[38.08]
3-7/8
[98.30]
GDL-T
3
[76.06]
TEMP 1
TEMP 2
TEMP 3
DISPLAY
-
The Model GDL-T Four Temperature Graphical Display Data Logger provides
local, real time data and graphical trends on a large LCD. Front panel buttons allow users
to see all four temperatures, graph display, logging summary, sample rates, memory used
and memory left. This device can record up to 87,000 data points and download them to
your PC for further analysis. Applications include refrigeration/freezers, medical storage
facilities, greenhouses/florists, wine storage, and many more. Software, USB cable, digital
manual, and batteries are included with this product.
Model GDL-T, Four Temperature View Data Logger
UNITS
START
VIEW
+
SPECIFICATIONS
Memory Size: 21,760 points for 4
temperatures, 29,010 points for 3
temperatures, 43,520 points for 2
temperatures, 87,040 for single
temperature.
Internal Temperature Range: 15 to
150°F (-10 to 65°C).
External Probe Temperature Range:
-40 to 160°F (-40 to 70°C).
Temperature Accuracy: ±1°F (0.5°C).
Temperature Resolution: 0.1°F/C.
Operating Temperature: 15 to 150°F
(-10 to 65°C).
Time Accuracy: ±100 ppm @ 75°F.
Sampling Rate: User selectable 1
second to 18 hours.
Computer Requirements: Windows®
98SE, Windows® ME, Windows® 2000,
Windows® XP, Windows Vista®, and
Windows® 7 operating systems.
Compatible with 32 and 64 bit systems.
System Requirements: 5 MB of free
space, 800 x 600 screen resolution, 1
USB port.
Power Requirements: (3) AA alkaline
batteries, installed functional, user
replaceable.
Battery Life: 1 year continuous use, 2
years average use. Automatically
powers off in 1 hour if not logging data.
Alarms: Visual over and under alarm
indicator for all 4 channels.
Interface: USB port. USB cable is
included.
Weight: 7.0 oz (200 g).
Agency Approvals: CE.
Windows® is a registered trademark of Microsoft Corporation
386
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
387_Layout 1 7/21/14 12:09 PM Page 387
Button Data Logger
Self-Powered, Compact Size, USB Interface
The Series BDL Button Data Logger records temperatures and humidity in applications
where size and cost effectiveness are key. The BDL is housed in a SS case and is water
resistant, making it durable in hostile environments where excessive moisture is present.
The BDL is self-powered and features a USB interface. Sample rate and high/low alarms
are user selectable through the Windows®-based application. The included software displays
downloaded data graphically with trace and zoom functions. The logger is very small which
enables it to be inserted into small items and packages. The Series BDL-K Logger Kit
includes 2 buttons, 2 magnets, an interface cable, and a plastic button holder.
Model
BDL-1
BDL-2
BDL-K1
BDL-K2
Input Type
Temperature
Temperature/Humidity
Temperature
Temperature/Humidity
Kit
No
No
Yes
Yes
ACCESSORIES
DL500-LITE*, Lite Version Windows® Operating System Software
DL500**, Full Version Windows® Operating System Software Key
BDL-SIL, Weatherproof Silicone Housing (5 pk)
BDL-WALL, Wall Mounting Bracket (5 pk)
BDL-CLIP, Plastic Button Holder (5 pk)
*Free download from website
**Must also have lite version
Series
MTL
20/30
SPECIFICATIONS
Range: BDL-1: -40 to 185°F
(-40 to 85°C); BDL-2: -4 to 185°F
(-20 to 85°C), 0 to 100% RH.
Memory Size: BDL-1: 2048 readings;
BDL-2: 4096 temperature and 4096
humidity readings (low resolution),
2048 temperature and 2048 humidity
readings (high resolution).
Accuracy: BDL-1: ±1.5°F (±1°C) from
-22 to 158°F (-30 to 70°C); BDL-2:
±0.9°F (±0.5°C) from 14 to 158°F
(-10 to 70°C), ±5% RH.
Resolution: BDL-1: 8 bit; BDL-2: 8 or
11 bit.
Sampling Method: Stop on memory
full or continuous recording.
1/4
[6.35]
Sampling Rate: BDL-1: Selectable
from 1 to 255 min; BDL-2: Selectable
from 1 s to 24 hrs.
Computer Requirements: Windows®
98, Windows® 2000, Windows® ME,
Windows NT®, Windows® XP, and
Windows Vista® operating system with
16 MB RAM, one free USB port.
Power Requirements: 3 V lithium
metal battery, internal, nonreplaceable.
Battery Life: BDL-1: 10 years
(approx); BDL-2: 5 years (approx).
Alarms: Programmable high/low.
Interface: USB port (cable included).
Housing Material: 305 SS.
Weight: 0.14 oz (4 g).
Agency Approvals: CE, RoHS.
Windows®, Windows NT®, and Windows Vista® are registered
trademarks of Microsoft Corporation.
Miniature USB Data Logger
Measure Temperature, Humidity, and Dew Point
3
[76.2]
1-39/64
[30.88]
The Series MTL Miniature USB Data Logger measures and records accurate readings
for temperature or temperature/humidity/dew point in a wide range of applications.
Sampling intervals and high/low alarm settings are user selectable through the included
easy to use Windows® based software. On models ordered with an integral display, the
temperature and humidity readings alternate on the display. The series MTL can be
software configured to begin measuring based on a time delayed-start or by push-button.
The logger can store up to 43,344 readings and can be set to stop on memory full or for
continuous recording. Stored data is downloaded by plugging the unit into a PC’s USB
port (cable included). The loggers provide measurements for many environment conditions,
which make them ideal for refrigeration systems, laboratories, and medical storage
facilities.
Model
MTL-20
MTL-30
MTL-20-LCD
MTL-30-LCD
Input Type
Temperature
Temperature/Humidity/Dew Point
Temperature
Temperature/Humidity/Dew Point
Display
No
No
Yes
Yes
SPECIFICATIONS
Temperature Range: MTL20: -40 to
185°F (-40 to 85°C); MTL30: -40 to
160°F (-40 to 70°C), 0% to 99% RH
(non condensing).
Accuracy: MTL20: ±1°F (±0.5°C);
MTL30: ±1°F (±0.5°C), ±2% RH from
10% to 90% RH.
Resolution:
Non-LCD models: 0.01°F (0.01°C),
0.01% RH;
LCD models: 0.1°F (0.1°C), 0.1%
RH.
Memory Size: 43,344 temperature;
21,672 each temperature and RH.
39/64
[15.48]
Sampling Mode: Stop on memory full
or memory rollover for continuous
recording.
Sampling Rate: 1 s to 18 hrs.
Computer Requirements: Windows®
based application software included.
Power Requirements: 3 V CR2032
lithium metal battery, installed
functional, user replaceable.
Alarms: Programmable high/low.
Interface: USB port (cable included).
Weight: 1 oz (28 g).
Agency Approvals: CE.
Windows® is a registered trademark of Microsoft Corporation
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
387
Data Loggers, Miniature
Ø43/64
[Ø17.07]
RoHS
PROCESS CONTROL
Series
BDL
PROCESS CONTROL
388_Layout 1 7/8/14 11:06 AM Page 388
Series
WTDL
Wireless Temperature/Humidity Data Logger
Transmission up to 400 Feet, Text/Email Alarm Updates
1-17/64
[32.00]
WHITE
BODY
PROBE
ATTACHMENT
4-61/64
[125.72]
1 2 3 4
Data Loggers, Wireless
O
ON 13
3/8
[9.40]
180° HORIZONTAL
ROTATION
90° VERTICAL
ROTATION
27/64
[10.67]
WTDL-30
WTDL-10/20
.300
Ø.137 X 2
2.753
.760
.600
2.753
3.575
5.296
.120
3.780
Wireless Transceiver
The Series WTDL Temperature/Humidity Data Logger is perfect for applications
which require real time monitoring or areas that are not as accessible to periodically retrieve
the data. The data loggers can transmit up to 500 feet indoors and up to 2000 feet outdoors.
The distance can be increased by using additional receivers. Wireless data is transmitted
on a 2.4 GHz frequency allowing it to be used anywhere in the world. A network of data
loggers can be separated into a smaller subnet. These subnets can all be controlled by a
single PC. The Series WTDL data loggers also feature a user programmable alarm. This
alarm can be configured to show an on screen alarm, send a text message (standard SMS
rates apply) or an email if an alarm condition is met.
Model
WTDL-10
WTDL-20
WTDL-30
Description
Temperature data logger
Temperature data logger with humidity output
Temperature data logger with probe attachment
ACCESSORIES
Model WTDL-RX, Wireless transceiver, USB cable, software CD, software
manual, A/C adapter
TLH-5903, Replacement Battery
3.580
MINI USB
PORT
1.570
SPECIFICATIONS
Temperature Range: WTDL-10/WTDL-20: -4 to 176°F (-20 to 80°C); WTDL-30:
-328 to 500°F (-200°C TO 260°C) for probe.
Humidity Range: WTDL-20: 0 to 95% RH.
Temperature Accuracy: WTDL-10/WTDL-20: 0.9°F (0.5°C) from 32 to 122°F (0 to
50°C); WTDL-30: 0.18°F (0.1°C) from -4 to 176°F (-20 to 80°C), 0.9°F (0.5°C)
outside of specified range.
Humidity Accuracy: WTDL-20: ±3.0% RH, ±2% typical at 77°F (25°C).
Temperature Resolution: 0.018°F (0.01°C).
Humidity Resolution: WTDL-20 only: 0.1% RH.
RF Carrier Frequency: 2.45 GHz.
Band: ISM band 2.405-2.48 GHz.
Maximum Power Output: +0 dBm typical.
Wireless Transmission Range: 2000´ (610 m) outdoors, line of sight; 500´ (152
m) indoors.
Receiver Sensitivity: -95 dBm typical.
Memory Size: WTDL-10/WTDL-30: 30,000 Readings; WTDL-20: 15,000 readings
per channel, software configurable memory wrap.
Sampling Method: Stop on memory full or continuous recording.
Sampling Rate: 2 sec to 24 hrs.
TemperatureLimits: -4 to 176°F (-20 to 80°C).
Humidity Limits: 0 to 95% RH.
Computer Requirements: Windows® Xp Sp3, Windows Vista®, Windows® 7.
Computer Interface: WTDL-RX.
Power Requirements: 3.6 V TL-5104 lithium metal battery, installed functional,
user replaceable.
Battery Life: 2 years (approx.).
Housing Material: ABS plastic.
Weight: 0.25 lb (113.4 g).
FCC Approval: FCC ID# OA3MRF24J40MA.
Agency Approvals: CE.
Windows® and Windows Vista® are registered trademarks of Microsoft Corporation
388
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
389_Layout 1 7/9/14 8:49 AM Page 389
Wireless Wi-Fi Data Logger
Measures Temperature/Humidity, Integral LCD
RoHS
PROCESS CONTROL
Series
DW-WIFI
3-7/8
[97.30]
Data Loggers, Wireless
1
[26.36]
2-3/4
[71.30]
The Series DW-WIFI Wireless Wi-Fi Data Logger measures and records up to 1,000,000
temperature and / or humidity readings and shares the data with any PC or server on the
same Wi-Fi network. Software settings allow the user to set the high and low alarms, the
sampling rate, and the temperature scale. If the Wi-Fi connection is lost, the sensor will
continue to store any records until it can regain communication with the network. Stored
data can be viewed at any time after the communications have been restored. Each data
logger includes a wall bracket that allows the data logger to be mounted to any wall or flat
surface. Configuration and logging software available for download on our website.
Model
DW-WIFI-T
DW-WIFI-TH
Input
Range
InternalTemperature
-4 to 140°F (-20 to 60°C)
Internal Temperature/Humidity -4 to 140°F (-20 to 60°C),
0 to 100%RH
DW-WIFI-TP
Remote TemperatureProbe
-40 to 257°F (-40 to 125°C)
DW-WIFI-TC
Remote Thermocouple
-454 to 2372°F (-270 to 1300°C)
(probe dependent)
DW-WIFI-T-HA Internal Temperature
-4 to 140°F (-20 to 60°C)
DW-WIFI-TH-HA Internal Temperature/Humidity -4 to 140°F (-20 to 60°C),
0 to 100%RH
DW-WIFI-TP-HA Remote TemperatureProbe
-40 to 257°F (-40 to 125°C)
SPECIFICATIONS
Memory Size: 1,000,000 readings; 500,000 each for DW-WIFI-TH(-HA).
Sampling Mode: Continuous recording.
Sampling Rate: Selectable from 10 s to 12 hrs.
Transmission Rate: Selectable from 1 min to 24 hrs.
Temperature Limits: -4 to 140°F (-20 to 60°C).
Power Requirements: 3.7 V lithium ion battery, installed functional, factory
replaceable (cable for charging included).
Alarms: Programmable high/low.
Interface: Wi-Fi connection.
Probe Length:
DW-WIFI-TP: 11.8 (30 cm);
DW-WIFI-TC: 59 (150 cm).
Weight: 7.2 oz (204 g).
Agency Approvals: CE, RoHS.
Accuracy (typ.)
±1.0°F (±0.5°C) @ 14 to 122°F (-10 to 50°C)
±0.6°F (±0.3°C) @ 41 to 140°F (5 to 60°C)
±2.5% RH @ 20 to 80%RH
±1.2°F (±0.6°C) @ 14 to 158°F (-10 to 70°C)
±3.0°F (1.5°C)
Display Resolution
0.1°F (0.1°C)
0.5°F (0.5°C)
1.0%RH
0.1°F (0.1°C)
0.1°F (0.1°C)
±0.2°F (±0.1°C) @ 14 to 140°F (-10 to 60°C)
±0.4°F (±0.2°C) @ 41 to 140°F (5 to 60°C)
±2.5%RH @ 10 to 90% RH
±0.2°F (±0.1°C) @ 14 to 158°F (-10 to 70°C)
0.1°F (0.01°C)
0.5°F (0.5°C)
1.0%RH
0.01°F (0.01°C)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
389
PROCESS CONTROL
390_Layout 1 7/8/14 2:20 PM Page 390
Series
DW-USB
Compact USB Data Logger
RoHS
Measure Temperature, Humidity, Dew Point, Current, Voltage, or Carbon Monoxide
LED
1-3/64
[26.59]
Y
4-51/64
[121.73]
1-1/16
[26.99]
Data Loggers, USB
X
Ø1-3/32
[27.76]
ModelDW-USB-CASE
ModelDW-USB-X
Model
DW-USB-1
DW-USB-2, -2-HA
DW-USB-3
DW-USB-4
DW-USB-5, -5-LR
DW-USB-6
The compact design of the DW-USB Series data loggers allows the user to monitor
temperature, humidity, dew point, voltage, current, or carbon monoxide almost anywhere.
The user can select the sampling rate, start time, high/low alarm settings, and temperature
unit parameters with easy to install Windows®-based application. Stored data is downloaded
by simply plugging the module into a PC’s USB port with no cable required. Alarm status
and low battery is indicated via built-in flashing LED’s. When the protective cap is fitted,
the data logger resists moisture to IP67 standards. These features make the data logger
ideal for calibration labs, pharmaceutical plants, environmental chambers, and storage
warehouses.
ACCESSORY
Model DW-USB-CASE, Waterproof case for DW-USB-1
Model
DW-USB-1
DW-USB-2
DW-USB-2-HA
DW-USB-3
DW-USB-4
DW-USB-5
DW-USB-5-LR
DW-USB-6
Input Type
Temperature
Temperature/Humidity/Dew Point
High Accuracy Temperature/Humidity/Dew Point
Voltage
Current
Carbon Monoxide
Low Range Carbon Monoxide
Thermocouple
Overall
Length (X)
3-55/64
4-1/16
4-27/64
4-27/64
4-59/64
4-21/32
Overall
Length (Y)
3-55/64
4-1/16
4-27/64
4-27/64
4-59/64
4-21/32
Body/Clip
Standard
Vented
Standard
Standard
Vented
Standard
SPECIFICATIONS
Memory Size: 16,382 temperature;
16,382 each temperature and RH;
32,764 readings for voltage, current,
and thermocouple; and 32,510 for
carbon monoxide.
Sampling Mode: Stop on memory full.
Sampling Rate: Selectable from 10 s
to 12 hrs (DW-USB-1, DW-USB-2, DWUSB-2-HA), 1 s to 12 hrs (DW-USB-3,
DW-USB-4, DW-USB-5, DW-USB-5LR:) and 10 s to 5 min (DW-USB-6).
Range
-31 to 176°F (-35 to 80°C)
-31 to 176°F (-35 to 80°C), 0 to 100% RH
-31 to 176°F (-35 to 80°C), 0 to 100% RH
0 to 30 VDC
4 to 20 mA
0 to 1000 ppm
0 to 300 ppm
J-type: -202 to 1652°F (-130 to 900°C);
K-type: -328 to 2372°F (-200 to 1300°C);
T-type: -328 to 662°F (-200 to 350°C)
Accuracy
±2°F (±1°C)
±1°F (±0.5°C), 3% RH
±0.6°F (±0.3°C), 2% RH
±1%
±1%
±6%
±4%
±1.5°F (±1°C)
Cap
Standard
Standard
Black Tip Term Block
Blue Tip Term Block
Red Tip CO Sensor
Standard
LED
Clear/Red
Clear/Clear
Red/Green
Red/Green
Red/Green
Red/Green
Computer Requirements: Windows®
98, Windows® 2000, Windows® XP,
Windows NT®, Windows® 7 or Windows
Vista® 32-bit or 64-bit operating
systems.
Power Requirements: 3.6 V 1/2 AA
lithium metal battery, included, user
replaceable.
Housing: ABS plastic blend.
Alarms: Programmable high/low.
Interface: USB port.
Weight: 1.5 oz (43 g).
Agency Approvals: CE, RoHS.
Resolution
1°F (0.5°C)
1°F (0.5°C), 0.5% RH
1°F (0.5°C), 0.5% RH
50 mVDC
0.05 mA
0.5 ppm
0.5 ppm
0.9°F (0.5°C)
Windows®, Windows NT®, and Windows Vista®
are registered trademarks of Microsoft Corporation.
Model
DW-USB-LITE
Mini Temperature Data Logger
Single Channel, USB Interface
32/32
[18.26]
2-11/16
[69.26]
The Model DW-USB-LITE Data Logger is a low cost temperature data logger that
measures and stores up to 4080 temperature readings over a measurement range 14 to
122°F. The stand-alone device has a fixed 30-min sample rate and a battery life of 1 month
with continuous use. High/low alarm settings are user programmable through easy to
install Windows® based software (included). The DW-USB-LITE features a visual LED
alarm indicator. Stored data is downloaded by directly plugging the data logger into a PC’s
USB port and running the software, no cable required. Downloaded data can then be
graphed, printed and exported to other applications.
Model DW-USB-LITE, Mini Temperature Data Logger
SPECIFICATIONS
Temperature Range: 14 to 122°F
(-10 to 50°C).
Temperature Accuracy: ±4.5°F
(±2.5°C).
Temperature Resolution: 2°F (1°C).
Memory Size: 4080 readings.
Sampling Mode: Continuous.
Sampling Rate: 30 min (fixed).
3/8
[22.23]
Computer Requirements: Windows®
98, Windows® 2000, Windows® XP, and
Windows Vista® (software included).
Power Requirements: 3 V CR1620
lithium metal battery, installed nonfunctional, user replaceable.
Alarms: Programmable high/low.
Interface: USB.
Weight: 1 oz (30.0 g).
Agency Approvals: CE.
Windows®, Windows NT® and Windows Vista®
are registered trademarks of Microsoft Corporation.
390
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
391_Layout 1 7/9/14 8:47 AM Page 391
Compact USB Data Logger With Display
Integral LCD Display, LED Status Indication
RoHS
LCD
SCREEN
Y
1-1/16
[26.99]
1-3/64
[26.59]
LED
X
Overall Length (X)
4-31/32
4-31/32
5-19/64
The Portable Series DW-USB-LCD USB Data Loggers displays and records
temperature, humidity and dew point. The easy-to-read LCD display shows the current
temperature or humidity along with the minimum and maximum reading since last reset.
For applications that require more accuracy, a high accuracy temperature and humidity
model is available. Thermocouple models can accept any J, K, or T type thermocouple with
a mini-plug connector. Series DW-USB-LCD data loggers include a Windows® based software
which allows selection of the sampling rate, start time, high/low alarm settings, and
temperature unit application. For quick downloading of data, the data logger can be plugged
directly into a PC’s USB port with no cable required. Downloaded data can then be graphed,
printed, or exported to other spreadsheet applications.
Model DW-USB-2-LCD, Temperature, humidity, and dew point USB data logger with
display
Model DW-USB-2-HA-LCD, High accuracy temperature, humidity, and dew point
USB data logger with display
Model DW-USB-6-LCD, Thermocouple USB data logger with display
ACCESSORIES
1818-0074, Immersion temperature probe
1818-0078, Penetration temperature probe
1818-0082, Surface temperature probe
1818-0085, Air duct temperature probe
1718-0077, Remote temperature probe handle
Model
DW-DATAPAD
LED
FUNCTION
BUTTON
Data Loggers, USB
Model DW-USB-X
Model
DW-USB-2-LCD
DW-USB-2-HA-LCD
DW-USB-6-LCD
PROCESS CONTROL
Series
DW-USBLCD
Model DW-USB-X-LCD
Base Length (Y)
4-57/64
4-57/64
5-15/64
Body/Clip
Cap
Vented
No clip Transparent
Vented
No clip Transparent
Plug in bottom No clip Transparent
LED
Red/Green
Red/Green
Red/Green
SPECIFICATIONS
Range: DW-USB-2-LCD: Temperature: -31 to 176° F (-35 to 80°C), Humidity: 0 to
100% RH; DW-USB-2-HA-LCD: Temperature: -31 to 176° F (-35 to 80°C);
Humidity: 0 to 100% RH; DW-USB-6-LCD: K-type: -328 to 2372°F (-200 to
1300°C), J-type: -202 to 1652°F (-130 to 900°C), T-type: -328 to 662°F (-200 to
350°C).
Accuracy: DW-USB-2-LCD:Temperature ±1°F (±0.5°C), Humidity ±3.0%; DWUSB-2-HA-LCD:Temperature ±0.6°F (±0.3°C), Humidity ±2.0%; DW-USB-6-LCD:
±2°F (±1°C).
Resolution: Temperature: 1°F (0.5°C), Humidity: 0.5% RH.
Memory Size: Thermocouple models: 32510 readings; Temperature/humidity
models: 16382 readings.
Sampling Mode: Continuous with data rollover.
Sampling Rate: Selectable from 10 seconds to 12 hours for temperature/humidity
models; 1 second to 12 hours for thermocouple models.
Display: 2.5 digit LCD.
Computer Requirements: Windows® 2000, Windows® XP, Windows® 7, Windows
VISTA® 32-bit or 64-bit operating systems.
Power Requirements: 3.6 V 1/2 AA lithium metal battery, included, user
replaceable.
Housing: ABS plastic blend.
Alarms: Programmable high/low.
Interface: USB port.
Weight: Temperature/humidity models 1.6 oz (45.4 g); Thermocouple models 1.8
oz (51 g).
Agency Approval: CE, RoHS.
Handheld Portable Data Viewer
Works With DW-USB Data Logger
RoHS
3/4 [19.00]
4-7/32 [107.00]
2-11/16 [68.00]
The Model DW-DATAPAD Handheld Portable Data Viewer configures and reads
data from up to 500 DW-USB data loggers. A 2.8˝ full color TFT touch screen display is
easy to read and simplifies navigation through the configuration menus. Data that has been
downloaded to the viewer can be displayed as a trend graph or a statistical summary. Stored
data can also be transferred to a computer using the provided micro-USB cable and the
included Windows® based software. A rechargeable lithium battery is provided that has
an average life of 5 to 8 hours under constant use.
The DW-DATAPAD is compatible with the following DW-USB data loggers: DW-USB-1,
DW-USB-1-HT, DW-USB-1-LCD, DW-USB-2, DW-USB-2-HA, DW-USB-2-HA-LCD, DW-USB2-LCD, DW-USB-6, DW-USB-6-LCD, and DW-USB-LITE.
Model DW-DATAPAD, Handheld Portable Data Viewer for Dwyer USB Data Loggers
SPECIFICATIONS
Data Recording Capacity: Internal flash memory, greater than 8.5 million
readings.
Battery life: 5 to 8 hours (constant use).
Operating Temperature Range: 0 to 50°C (32 to 122°F).
Power Requirements: CA374170 lithium ion battery, installed functional, factory
replaceable.
Display: 2.8 full color TFT touch screen LCD display.
Resolution: 240 X 320.
Interface: Touch screen and single front-panel push-button power switch.
Connections: 1 USB type A socket (top of unit) for data logger connection. 1
micro-USB (bottom of unit) for connection of unit to PC via supplied USB cable.
Compatible Data Loggers: DW-USB-1, DW-USB-1-HT, DW-USB-1-LCD, DWUSB-2, DW-USB-2-HA, DW-USB-2-HA-LCD, DW-USB-2-LCD, DW-USB-6, DWUSB-6-LCD, and DW-USB-LITE.
Weight: 3.9 oz (111 kg).
Agency Approvals: CE, RoHS.
Windows® is a registered trademark of Microsoft Corporation.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
391
PROCESS CONTROL
392_Layout 1 7/8/14 11:04 AM Page 392
Series
LCR10
Circular Chart Recorder
Single Pen, Clockwise or Counter-clockwise Rotation
11-29/32
[302.41]
12-5/8
[320.68]
3-35/64
[90.10]
Chart Recorders
14
[355.60]
13-3/16
[334.95]
The Series LCR10 Circular Chart Recorder offers a wide range of features in an easy
to use package. The large 10˝ (254 mm) Circular chart allows easy reading of your data.
Available in clockwise and counter clockwise rotation, the LCR10 is compatible with
Honeywell and Partlow circular charts. The LCR10 can be easily programmed for any of
six different thermocouple types, 100 Ω platinum DIN RTD’s, or process inputs (0 to 5
VDC or 4 to 20 mA). Inputs may be scaled to a min of 100 units (or degrees) to a max of
the sensor scale or -1999 to +9999.
Model
LCR10-101
LCR10-111
LCR10-201
LCR10-211
Rotation
Counter Clockwise
Counter Clockwise
Clockwise
Clockwise
Output
No
Yes
No
Yes
ACCESSORIES
LCR200, Chart paper, 0 to 200°F, 24 hour, CCW
LCR2007, Chart paper, 0 to 200°F, 7 day, CCW
LCR110C, Chart paper, 0 to 110°C, 24 hour, CCW
LCR-R, Red chart pens, package of 6
LCR-B, Blue chart pens, package of 6
Series
LCR20
12-5/8
[320.68]
14
[355.60]
SPECIFICATIONS
Ranges: Thermocouple:Type J, K, T, R, S, B; RTD: 100 platinum DINcurve
(0.00385 per per °C); Process: 0 to 5 VDC, 250 impedance, 4 to 20 mA
across 250 .
Chart Size: 10 (254 mm).
Accuracy: ±0.5% of span (100 division span).
Output Relay: Form C (DPDT), 1A @ 240 VAC resistive.
Chart Speed: Programmable 4, 8, 12, 24, 48, 72, 168 hour rotation (168 hours=7
days).
Ambient Operating Temperature/RH: 32 to 140°F (0 to 60°C); 0-90% RH
(non-condensing).
Power Requirements: 110/220 VAC ±10%.
Battery Backup: 9 V alkaline battery, installed functional, user replaceable.
Power Consumption: 15 VA max.
Housing Material: Fire retardant polyphenylene ether and polystyrene PPE & PS
with acrylic window.
Mounting: ±20 degrees of vertical, ±10 degrees of horizontal.
Weight: 7 lb (3.2 kg).
Agency Approval: CE.
Dual Pen Circular Chart Recorder
Dual Pen, Adjustable Rotation Speeds, Selectable Recording Times
11-29/32
[302.41]
12-5/8
[320.68]
3-35/64
[90.10]
14
[355.60]
13-3/16
[334.95]
The LCR20 Dual Pen Circular Chart Recorder offers a wide range of features in an
easy to use package. The large 10˝ (254 mm) circular chart allows easy reading of your
data. Available in clockwise and counter-clockwise rotation, the LCR20 is compatible with
Honeywell and Partlow circular charts. The LCR20 has one pen input that can be easily
programmed for any of six different thermocouple types, 100 ohm platinum DIN RTD’s,
or process inputs (0 to 5 VDC or 4 to 20 mA). Inputs may be scaled to a min of 100 units
(or degrees) to a max of the sensor scale or -1999 to +9999.
Model
LCR20-101
LCR20-111
LCR20-201
LCR20-211
Rotation
Counter Clockwise
Counter Clockwise
Clockwise
Clockwise
Output
No
Yes
No
Yes
ACCESSORIES
LCR200, Chart paper, 0 to 200°F, 24 hour, CCW
LCR2007, Chart paper, 0 to 200°F, 7 day, CCW
LCR110C, Chart paper, 0 to 110°C, 24 hour, CCW
LCR-R, Red chart pens, package of 6
LCR-B, Blue chart pens, package of 6
392
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
12-5/8
[320.68]
14
[355.60]
SPECIFICATIONS
Ranges Input 1: Thermocouple:Type J, K, T, R, S, B; RTD: 100 platinum DIN
curve (0.00385 ohms per per °C); Process: 0 to 5 VDC, 250 impedance, 4 to
20 mA across 250 .
Ranges Input 2: Thermocouple:Type J, K, T, R, S, B; RTD: 100 platinum DIN
curve (0.00385 ohms per per °C); Process: 0 to 5 VDC, 250 impedance, 4 to
20 mA across 250 .
Chart Size: 10 (254 mm).
Accuracy: ±0.5% of span (100 division span).
Output Relay: Form C (DPDT), 1A @ 240 VAC resistive.
Chart Speed: Programmable 4, 8, 12, 24, 48, 72, 168 hour rotation (168 hours = 7
days).
Ambient Operating Temperature/RH: 32 to 140°F (0 to 60°C); 0 to 90% RH
(non-condensing).
Power Requirements: 110/220 VAC ±10%.
Battery Backup: 9 V alkaline battery, installed functional, user replaceable.
Power Consumption: 15 VA max.
Housing Material: Fire retardant polyphenylene ether and polystyrene PPE & PS
with acrylic window.
Mounting: ±20 degrees of vertical, ±10 degrees of horizontal.
Weight: 7 lb (3.2 kg).
Agency Approval: CE.