Linear fittings Fluorescent fitting with easy disconnect EVS

Linear fittings Fluorescent fitting with easy disconnect EVS
Linear fittings
Fluorescent fitting with easy disconnect
EVS - Zones 1, 2 & 21, 22
Features
– Easy disconnect without wiring to remove the gear tray
– All components mounted on hinged and removable gear
tray for easy maintenance
– Double central locking for ingress protection
– Automatic switch off on opening
– Including accessories (cable gland, plugs & fixing brackets)
Specifications
– Main body constructed of glass reinforced polyester for
high impact strength
– UV protected polycarbonate diffuser to resist harsh
environments
– Rated voltage 220 -240Vac/Vdc 50-60Hz
– EOL (End of life) the ballast prevents the lamp cap at the
end of lamp life cycle from overheating
– Instant start
– Wiring configuration: 5 wires
– 3x entries M20
– 2x emergency versions (type: “EM” version 3h battery
duration or “EMA” with 3h with automatic test and
blackstart capabilities)
Certifications
Standards
Approved to:
EN 60079-0 : General requirements
EN 60079-1 : Flameproof enclosure “d”
EN 60079-31 : Enclosure “t”
EN 60079-7 : Increased safety “e”
EC Type examination
Directive 94/9/EC - (2014/34/UE)
certificate to:
LCIE 11 ATEX 3065X
IEC Ex LCI 11.0053X
Ex II 2 G
Ex de IIC T4 Gb for -40°C to +60°C
Ex II 2 D
Ex tb IIIC T85°C Db IP66 for -40°C to +60°C
EMC Directive
EN 55015 : Conducted emission test and
(2004/108/CE) -
radiated emission test
April 2016 (2014/30/UE)
EN 61547 : CEM immunity
EN 61000-3-2 : Harmonic current Emissions Class C
EN 61000-3-3 : Limitation of voltage changes and flickers
Low voltage Directive
EN 60598-1 : Luminaire general requirements
(2006/95/CE) - April 2016
and tests, including dielectric strength and
(2014/35/UE)
isolation resistance
Glow wire test:
960ºC
Operating
-20°C to +55ºC EVS,
temperature:
-10°C to +50ºC EVS EM & EVS EMA
IP test:
IP66 IEC 60529
Impact protection index:
IK10 according to IEC 62262
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017 3/3
3
Linear fittings
Fluorescent fitting with easy disconnect
EVS - Zones 1, 2 & 21, 22
2 x M8 hole 20mm depth
137 mm
C
B
3
A
EVS
170 mm
Dimensional drawing
Technical specifications
3ODQFRPPHUFLDO
Tol.
Class
Material
Processing
Drawn by
Description
Scale
Rev
Checked by
Approved by
CUSTOMER
DTS
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
Type - For
non armored cable
armored cable
Wiring Configuration
Light
Rating W
Current A
@ 230V
Dimensions mm
A
B
C
Weight kg
5 wires: Equipped with 1 cable gland & 2 plugs
EVS120-0000
EVS120-D000
5 wires*
1 x 18
0.09
785
432
400
5.81
EVS140-0000
EVS140-D000
5 wires*
1 x 36
0.17
1 370
900
700
8.60
EVS165-0000
EVS165-D000
10.40
5 wires*
1 x 58
0.26
1 670
900
700
EVS220-0000
EVS220-D000
5 wires*
2 x 18
0.17
785
432
400
5.81
EVS240-0000
EVS240-D000
5 wires*
2 x 36
0.33
1 370
900
700
8.60
EVS265-0000
EVS265-D000
5 wires*
2 x 58
0.5
1 670
900
700
10.40
5 wires through**
1 x 18
0.09
785
432
400
5.81
5 wires through**
1 x 36
0.17
1 370
900
700
8.60
10.40
3ODQFRPPHUFLDO
Tol.
Class
Material
Processing
Drawn by
Description
Scale
Rev
Checked by
Approved by
CUSTOMER
DTS
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
5 wires through: Equipped with 2 cable glands & 1 plug
EVS120-B000
EVS120-E000
EVS140-B000
EVS140-E000
3ODQFRPPHUFLDO
Tol.
Class
Material
Processing
Drawn by
Description
Scale
Rev
Checked by
Approved by
CUSTOMER
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
DTS
EVS165-B000
EVS165-E000
5 wires through**
1 x 58
0.26
1 670
900
700
EVS220-B000
EVS220-E000
5 wires through**
2 x 18
0.17
785
432
400
5.81
EVS240-B000
EVS240-E000
5 wires through**
2 x 36
0.33
1 370
900
700
8.60
EVS265-B000
EVS265-E000
5 wires through**
2 x 58
0.5
1 670
900
700
10.40
Note. * For armored cable with 1 continuity plate. ** For armored cable with 2 continuity plates.
Technical information
Lamps
Fluorescent Lamp (order separately)
T8 bi-pin tube, lampholder G13, diameter
26mm - white industry 4 000°K.
Dielectrical class I
CRI 80
Power factor
0.98
Photometric curve
See page 6/9
Rated voltages
Electronic ballast: 220-240Vac/Vdc 50/60Hz.
EOL (End of life) the ballast prevents the
lamp cap at the end of lamp life cycle from
overheating
3/4
Grounding system
TNS, TNC, TT, IT neutral system
Terminal block (spring)
Jumped bar x2 terminal blocks 4mm² (rigid
wire), 2.5mm² (flexible wire)
Terminals supplied L1, L2, L3, N, PE (looping
possible with one additional cable gland)
Cable entries
Three entries M20
For non- armoured cable: included two
M20 nylon plugs (EX-M20) and one M20
nylon cable gland, diameter 6-12mm
(EXCGM20S)
For armoured cable: included continuity
plate - two M20 nylon plugs (EX-M20) and
one M20 nickel plated brass cable gland,
diameter 6-12/ 8.5-16mm (EXN04MMC1)
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017
Housing
Fiberglass reinforced polyester housing for
high impact strength, UV protected polycarbonate diffuser to resist harsh environments,
Painted steel gear tray & Stainless steel
316L insert
Fixing (included with product)
V015 - 2x Two zinc-plated steel brackets for
ceiling mounting
Linear fittings
Emergency Fluorescent fitting with easy disconnect - 3h
EVS EM - Zones 1, 2 & 21, 22
Technical specifications
Type - For
non armored cable
armored cable
Wiring Configuration
Light
Rating W
Battery
h
Current A
@ 230V
Dimensions mm
A
B
C
Weight kg
3 wires: Equipped with 1 cable gland & 2 plugs
EVS120EME-0000
EVS120EME-C000
3 wires*
1 x 18
3h
0.09
785
432
400
8.40
EVS140EM-0000
EVS140EM-C000
3 wires*
1 x 36
3h
0.17
1 370
900
700
11.02
EVS165EM-0000
EVS165EM-C000
3 wires*
1 x 58
3h
0.26
1 670
900
700
13.40
3ODQFRPPHUFLDO
Tol.
Class
Material
Processing
Drawn by
Description
Scale
Rev
Checked by
Approved by
CUSTOMER
DTS
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
EVS220EME-0000
EVS220EME-C000
3 wires*
2 x 18
3h
0.17
785
432
400
8.40
EVS240EM-0000
EVS240EM-C000
3 wires*
2 x 36
3h
0.33
1 370
900
700
11.02
EVS265EM-0000
EVS265EM-C000
3 wires*
2 x 58
3h
0.50
1 670
900
700
13.40
Note. * For armored cable with 1 continuity plate.
For dimensional drawing, please refer to page 3/4
Electrical Features
Lamps
Power factor
EVS
EMseparately)
terminals wiring
Fluorescent
Lamp
(order
EM terminals
wiring
diagram
0.98.diagram
T8 bi-pin tube, lampholder G13, diameter
26mm - white industry 4 000°K
Battery
Battery NiCd 7,2V
4Ah in flameproof case (Ex d)
Lumen output in emergency mode (1 lamp lit)
2 hours: 40% for EVS120, EVS220, 33% for
EVS140, EVS240, 10% for EVS165, EVS265
3 hours: 24% for EVS120, EVS220, 18% for
EVS140, EVS240, 8% for EVS165, EVS265
Monitored by one LED
Rated voltages
Electronic ballast: 220-240Vac/Vdc 50/60Hz
EOL (End of life) the ballast prevents the
lamp cap at the end of lamp life cycle from
overheating.
Closed loop option
d loop option
Terminal block
Terminal block (screws plug in terminal block)
4mm² (rigid wire), 2,5mm² (flexible wire)
Terminals supplied L1, L2, L3, N, PE (looping
possible with one additional cable gland)
Cable entries
Three entries M20
For non- armoured cable: included two M20
nylon plugs (EX-M20) and one M20 nylon
cable gland, diameter 6-12mm (EXCGM20S)
For armoured cable: included continuity
plate - two M20 nylon plugs (EX-M20) and
one M20 nickel plated brass cable gland,
diameter 6-12/ 8.5-16mm (EXN04MMC1)
Housing
Fiberglass reinforced polyester housing for
high impact strength, UV protected polycarbonate diffuser to resist harsh environments
Stainless steel 316L insert
Painted steel gear tray
Fixing
V015 - 2x Two zinc-plated steel brackets for
ceiling mounting (included with product)
Switched option
Switched option
Emergency function diagrams
Wiring provided by DTS - Maintained Mode
2
1
E
N
L1
2
1
Switch between 1/2 - Non Maintained Mode *
E
N
L12
1
E
N
L1
2
1
1
0
0
1
E
N
L1
Mains Supply
Tube
Battery
Mains Supply
Tube
Battery
ON
Lit
Charging
ON
OFF
Charging
OFF
Only emergency tube lit
Discharging
OFF
Only emergency tube lit
Discharging
* This table corresponds to the position 0 “open”.
If the switch is on position 1 “close”, refer to the table on the left
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017 3/5
3
Linear fittings
Emergency Fluorescent fitting with automatic test
& blackstart capabilities. EVS EMA - Zones 1, 2 & 21, 22
Technical specifications
Type - For
non armored cable
armored cable
Wiring Configuration
Light
Rating W
Battery
h
Current A
@ 230V
Dimensions mm
A
B
C
Weight kg
8.80
5 wires: Equipped with 1 cable gland & 2 plugs
3
EVS120EMA-0000
EVS120EMA-D000
5 wires*
1 x 18
3h
0.09
785
432
400
EVS140EMA-0000
EVS140EMA-D000
5 wires*
1 x 36
3h
0.17
1 370
900
700
11.02
EVS220EMA-0000
EVS220EMA-D000
5 wires*
2 x 18
3h
0.17
785
432
400
8.80
EVS240EMA-0000
EVS240EMA-D000
5 wires*
2 x 36
3h
0.33
1 370
900
700
11.02
3ODQFRPPHUFLDO
Tol.
Class
Material
Processing
Drawn by
Description
Checked by
Approved by
CUSTOMER
Scale
Rev
DTS
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
Note. * For armored cable with 1 continuity plate.
For dimensional drawing please refer to page 3/4
Electrical Features
Lamps
Fluorescent Lamp (order separately)
T8 bi-pin tube, lampholder G13, diameter
26mm - white industry 4 000°K
Rated voltages
Electronic ballast: 220-240Vac/Vdc 50/60Hz
EOL (End of life) the ballast prevents the
lamp cap at the end of lamp life cycle from
overheating
Battery
Cable entries
Battery NiCd 6V 4Ah in flameproof case
Three entries M20
(Ex“d“) for EVS120, EVS220
For non- armoured cable: included two
Battery NiCd 6V 7Ah in flameproof case
M20 nylon plugs (EX-M20) and one M20 nylon
(Ex“d“) for EVS140, EVS240
cable gland, diameter 6-12mm (EXCGM20S)
Lumen output in emergency mode (1 lamp lit)
For armoured cable: included continuity
EVS EM A terminals
EVS EM wiring
A terminals
diagram
wiring diagram
3h: 40% for EVS120, EVS220
plate - two M20 nylon plugs (EX-M20) and one
33% for EVS140, EVS240
M20 nickel plated brass cable gland, diameter
Monitored
by two LED
6-12/ 8.5-16mm (EXN04MMC1)
Closed loop option
Closed loop option
Terminal block (spring)
Jumped bar x2 terminal blocks
E Bs Bs
E Bs Bs
4mm² (rigid wire),
2,5mm² (flexible
wire) N
Terminals supplied L1, L2, L3, LS, N, E, BS
(looping possible with one additional cable
gland)
Power factor
0.98
Preventive maintenance mode
Wiring provided by DTS - Maintained Mode
Switch between LS/L1 - Non Maintained Mode
N
Battery charge - daily
Emergency lamp during 1min - weekly
Battery charge capacity during 1hr - quaterly
Clear system test display
Switched option Switched option
Battery charge monitored by 2 LED
Switched option Switched option
Closed loop option
Closed loop option
E Bs Bs
Fixing (included with product)
V015 - 2x Two zinc-plated steel brackets for
ceiling mounting
N Ls Ls L1 NL1 NL2LsL3Ls E L1 L1 L2 L3 E
EVS EM AEmergency
terminals
EVS EM wiring
A terminals
diagram
wiring
diagram
function
diagrams
E Bs Bs
Housing
Fiberglass reinforced polyester housing
for high impact strength, UV protected
polycarbonate diffuser to resist harsh
environments
Stainless steel 316L insert
Painted steel geartray
N Ls Ls L1 NL1 NL2LsL3LsE L1 L1 L2 L3 E
E
Bs Bs
E
Bs Bs
N
N Ls Ls L1 NL1 NL2LsL3LsE L1 L1 L2 L3 E
0
1
1
0
Mains Supply
ON
Switched option Switched option
OFF
Tube
Battery
Mains Supply
Tube
Battery
Lit
Charging
ON
OFF
Charging
Only emergency
Discharged
OFF
Only emergency
Discharged
tube lit
E
Bs Bs
E
Bs Bs
N
Healthy
(test OK)
Emergency or
Indicator
Lamp Fault
(must be
replaced)
Test in
Progress
(waiting end
of test)
Fault
(replace
battery)
tube lit
Switched option
Switched
option
This table corresponds
to the
position
1 “closed”.
N Ls Ls L1 NL1 NL2 LsL3LsE L1 L1 L2 L3 E
Emergency function diagram - Blackstart mode
0
EVS EM A terminals wiring diagram
0
1
The EMA product contains 2 blackstart terminals.1 The blackstart
mode consists in disconnecting the battery and
Switch between BS terminals
Closed loop option
so switching off the fitting. This mode is mainly used during maintenance. As soon as the maintenance is done, the
This table corresponds to the position
0 “open”.
main power ON and the blackstart terminals connected, the emergency fitting is ready to be used as the battery is not
E Bs Bs
discharged.
N
N Ls Ls L1 L1 L2 L3 E
0
1
3/6
Mains supply
Tube
Battery
ON
Lit
Disconnected - not charged
Switched option
OFF
OFF
Disconnected - not charged
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017
E
Bs Bs
N
N Ls Ls L1 L1 L2 L3 E
Linear fittings
Accessories
EVS - Zones 1, 2 & 21, 22
Lamps
Bi-pin T8 fluorescent lamps
2
ø36
ø20
Specifications:
Lumen output lm
Lampholder
G13 - ø 26mm
TL18W
18
1 250
G13
Colour temperature: White industry 4 000°K
TL36W
36
3 350
G13
CRI: > 80
TL58W
58
5 200
G13
18
100
70
30
Power W
25
M8
lm/W: 65 to60¡
93
maxi
2 x ø9
20
M8
Average
operating life: 12 000 hours
ø9
30
100
Type
α
41
ø9
~70
Fixing accessories*
60
25
,
2 Ø 8.5
20
ø9
160
200
25
M
ø36
ø20
Brackets
100
Hook
Specifications
V015
2 x pair of zinc plated steel for ceiling mounting (Included with product)
V016
stainless steel 316L brackets for ceiling mounting
25
18
60¡
maxi
α
2
Specifications
V024
2x Zinc plated steel suspension hook
M8
M8
60
Type
41
ø9
~70
ø36
ø20
,
2 Ø 8.5
100
25
2 x ø9
100
70
30
5
20
30
ø9
18
30
Type
60¡
maxi
α
Mounting bracket clip
Specifications
V014
2x Rapid ceiling mounting with stainless steel clip
60
ø9
160
200
ø9
41
~70
Fixing bracket and flange
Type
25
M8
M8
25
,
2 Ø 8.5
Type
Specifications
V018
2x zinc plated steel pole mounted brackets for ø1”¼ & 1”½
V019
2x zinc plated steel pole mounted brackets for ø2”
V021
2x Stainless steel 316L pole mounted brackets for ø1”¼ & 1”½
V022
2x Stainless steel 316L pole mounted brackets ø2”
* Screws and locknuts supplied
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017 3/7
3
Linear fittings
Spare parts
EVS - Zones 1, 2 & 21, 22
3
V001
V004
V008
V005
Spare parts
Type
Specifications
V00120W
20W diffuser with gasket for EV. range
V00140W
40W diffuser with gasket for EV. range
V00165W
65W diffuser with gasket for EV. range
V0041X20WS
Gear tray 1x18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS120
V0041X40WS
Gear tray 1X36W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS140
V0041X65WS
Gear tray 1X58W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS165
V0042X20WS
Gear tray 2X18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS220
V0042X40WS
Gear tray 2x36W with electronic ballast 220- 240Vac/Vdc 50-60Hz for EVS240
V0042X65WS
Gear tray 2x58W with electronic ballast 220- 240Vac/Vdc 50-60Hz for EVS265
V0041X20WEMS
Emergency gear tray 1x18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS120EM
V0041X40WEMS
Emergency gear tray 1x36W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS140EM
V0042X20WEMS
Emergency gear tray 2x18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS220EM
V0042X40WEMS
Emergency gear tray 2x36W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS240EM
V0041X65WEMS
Emergency gear tray 1x58W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS165EM
V0042X65WEMS
Emergency gear tray 2x58W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS265EM
V0041X20WEMAS
Emergency gear tray + auto test 1X18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS120EMA
V0041X40WEMAS
Emergency gear tray + auto test 1X36W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS140EMA
V0042X20WEMAS
Emergency gear tray + auto test 2X18W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS220EMA
V0042X40WEMAS
Emergency gear tray + auto test 2X36W with electronic ballast 220-240Vac/Vdc 50-60Hz for EVS240EMA
V005S
Connection pack: XIN, terminal, track, connector
V008
Bi-pin G13 lampholder
V011
Battery pack Ni-Cd 7.2v -4Ah for EVS120EME, EVS220EME, EVS140EM, EVS240EM
V01120WEMEA
Battery for EVS120EMA, EVS220EMA
V01140WEMEA
Battery for EVS140EMA, EVS240EMA
V02520x40W
Brass continuity plate for EV. 120, EV. 220, EV. 140, EV. 240
V02565W
Brass continuity plate for EV. 165, EV. 265
EXCGM20S-01
Kit M20 Exe IIC nylon cable gland for non armoured cable diameter 6-12mm and locknut
EXN04MMC1-01
Kit M20 Ex-d IIC Ex-e II Ex-td double compression nickel plated cable gland for armoured cable diameter inner 6-12 outer 8.5-16mm locknut, sealing gasket
3/8
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 03/2017
Was this manual useful for you? yes no