LP FlameBlock Fire-Rated OSB Sheathing FAQ

Add to my manuals
16 Pages

advertisement

LP FlameBlock Fire-Rated OSB Sheathing FAQ | Manualzz

T E C H N I C A L G U I D E

S T R U C T U R A L P E R F O R M A N C E

A N D F I R E R E S I S T A N C E

I N T H E S A M E P A N E L

L P ® F L A M E B L O C K ® F I R E - R A T E D O S B S H E A T H I N G :

B U I L D O N O U R S T R E N G T H ,

C O U N T O N O U R F I R E   R E S I S T A N C E

TABLE OF CONTENTS

Product Description

Product Specifications

2

3–4

Applications & Assemblies 5–12

LP® FLAMEBLOCK® FIRE-

RATED OSB SHEATHING

FEATURES A PROPRIETARY

NON-COMBUSTIBLE,

FIBERGLASS-REINFORCED

PYROTITE® TREATMENT.

Product Installation

Instructions 13

Warranty 14

LP & Sustainability 15

LOOK BENEATH THE

IGNITION-RESISTANT

PYROTITE TREATMENT

AND YOU’LL FIND

THE STRENGTH AND

CONSISTENCY OF LP® OSB.

PRODUCT DESCRIPTION

LP® FlameBlock® Fire-Rated OSB Sheathing is a code-compliant oriented strand board (OSB) panel with a fire-resistant Pyrotite® treatment covering one or both sides. The Pyrotite treatment consists of a layer of fiberglass-reinforced magnesium oxide cement tightly bonded to the OSB surface. In addition to providing burnthrough resistance and a Class A Flame Spread rating, this layer reinforces the OSB substrate, resulting in full standard load/span ratings and shear design values for each thickness category. LP FlameBlock panels install with standard tools, methods and fasteners, and are highly resistant to cracking or damage from impact.

2

SIZE/LENGTH

LP FlameBlock sheathing is available in standard thickness and performance categories, including Struct-1 performance grade, and in nominal dimensions of 4´ x 8´, 4´ x 9´, and 4´ x 10´.

COMMON APPLICATIONS

• Roof decks, for vertical continuity of firewalls

• Exterior walls located near property lines

• Load-bearing party walls

• Exterior walls in Type III buildings

• Exterior walls and eaves in wildfire zones

CODE COMPLIANCE AND FIRE PERFORMANCE

• ICC certified (ESR-1365, Click here for online listing ) for a range of roof deck and wall applications in various building categories

• Class A Flame Spread Rating (ASTM E84, UL723, Click here for online listing)

• Meets requirements for 15-minute thermal barriers

• CALFIRE/OSFM code-approved (CBC Chapter 7A) for use in exterior walls, eaves and soffits in California WUI Zones

• Relevant Listings/Assemblies:

• Roof Decking to Satisfy Vertical Continuity Requirements for Fire Walls

• Bearing And Non-Bearing Exterior Walls For

Type III Construction

– UL Listing BXUV.U349

– UL Listing BXUV.W408

– UL Listing BXUVC.W324

• Load-Bearing Common Walls

– UL Listing BXUV.U350

– UL Listing BXUVC.W325

• Load-Bearing 1-Hour Fire-Rated Exterior Walls For Type V Construction

– Intertek Listing LPB/WA-60-01

– UL Listing BXUV.U348

3

4

WEATHER RESISTANCE

With LP FlameBlock sheathing’s water-resistant adhesives and durable Pyrotite treatment, each panel carries an Exposure 1 classification, so it can withstand exposure to moisture during normal construction delays. As with similarly classified panels, installation of building wrap is required for weather protection during construction.

STABILITY

LP FlameBlock sheathing won’t cup, warp, split or delaminate. You can count on consistent quality, without core voids and knots. Each panel is uniform, strong, dense, and easy to work with. LP FlameBlock sheathing is designed to be installed with standard tools (carbide saw blades recommended) and fasteners, using the same procedures and safety precautions applicable to LP OSB. See installation instructions on page 14 for details.

WARRANTY

20-Year Transferable Limited Warranty. For full warranty information, please visit LPCorp.com.

DISPOSAL AND WASTE

The use of LP FlameBlock sheathing in fire-rated bearing walls reduces overall material usage and waste when compared to gypsum-plussheathing applications. Panels contain no harmful chemicals.

STRUCTURAL PERFORMANCE

The fiberglass reinforcement within the Pyrotite treatment of LP FlameBlock sheathing increases the shear capacity, bending performance, and impact resistance of the underlying OSB substrate. Structural design properties are identical to those of standard, PS2-certified wood structural panels in the same thickness category, with no deductions as a result of the treatment. (See Figure 1 and Figure 2.) Structural performance and compliance with other PS2 standards are certified by P.E.I., an independent ISO-certified testing laboratory.

FIGURE 1. RECOMMENDED UNIFORM ROOF LIVE LOADS FOR LP FLAMEBLOCK FIRE-RATED SHEATHING (C) AND RATED SUBFLOOR

WITH STRENGTH AXIS PERPENDICULAR TO SUPPORTS (C)

Panel Span

Rating

Performance

Category **

Rated Sheathing (c)

Maximum Span (in.)

With Edge Support (a) Without Edge Support

24/16

32/16

40/20

48/24

7/16

15/32, 1/2

19/32, 5/8

23/32, 3/4

60/32

60/48

7/8

1-1/8

Rated Subfloor (c)

16 oc 19/32, 5/8

20 oc

24 oc

32 oc

19/32, 5/8

23/32, 3/4

7/8

24

32

40

48

60

60

24

32

48

48

24

32

36

40

48 oc 1-3/32, 1-1/8 60 48

(a) Tongue and groove edges, panel edge clips (one midway* between each support, except two equally spaced between supports 48 in. on center or greater), lumber blocking, or other.

(b) 10 psf dead load assumed

24

28

32

36

40

48

12 16

Allowable Live Loads (psf) (b)

Spacing of Supports Center-to-Center (in.)

20 24 32 40 48 60

-

-

12

185

190

325

-

-

270

-

-

-

-

16

100

100

180

305

-

150

240

-

65

120

205

280

-

-

20

65

100

160

295

40

94

151

175

305

305

24

40

60

100

185

30

60

95

165

165

32

30

50

100

30

45

100

100

40

30

60

35

70

70

48

25

40

290 160 100 65 40

(c) Applies to panels 24 in. or wider applied over two or more spans.

*No established tolerance.

**Performance Category replaces the fractional nominal thickness used in PS2 and is consistent with the panel thickness used in the U.S. model building codes.

32

35

60

FIGURE 2. ALLOWABLE SHEAR (POUNDS PER FOOT) FOR PANEL SHEAR WALLS WITH FRAMING OF DOUGLAS-FIR, LARCH, OR

SOUTHERN PINE (a) OR WIND OR SEISMIC LOADING (b,f,g,h,i) (See also 2006 IBC Table 2306.4.1)

Structural 1

Grades

Rated

Sheathing

7/16

15/32

15/32

7/16

15/32

15/32

5/8

Minimum Nail

Penetration in

Framing (in.)

1-3/8

1-1/2

1-3/8

1-1/2

Panels Applied Direct to Framing

Nail Size

(Common or

Galvanized Box)

8d

10d

8d

10d

6

Nail Spacing at Panel Edge (in.)

4 3 2 (e)

255 395 505 670 (c)

280 430 550 730

340 510 665 (e) 870

240 350 450 585 (c)

260 380 490 640

310 460 600 (e) 770

340 510 665 (e) 870

Panels Applied Over

1/2˝ or 5/8˝ Gypsum Sheathing

Nail Size

(Common or

Galvanized

Box)

6

Nail Spacing at Panel Edges (in.)

4 3 2 (e)(d)

10d

10d

280 430 550 (e) 730

-

-

-

-

-

-

-

-

-

-

-

-

260 380 490 (e) 640

5

6

A P P L I C A T I O N S A N D A S S E M B L I E S

ROOF DECKING TO SATISFY VERTICAL CONTINUITY REQUIREMENTS FOR FIRE WALLS

REFERENCE DOCUMENTS: 2009 AND 2012 IBC SECTION 706.6 AND ESR 1365, SECTION 4.2A

Examples: Roof decks over interior or exterior fire walls in single family, multifamily and townhomes.

Framing: As required by the pertinent fire wall and roof assemblies and in accordance with local building code.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment facing the interior, fastened to supports with minimum 1 7 ⁄

8

˝ 6d nails, spaced 6˝ o.c. on the perimeter and 12´ o.c. in the field, for a distance of 4 feet on both sides of the wall. Minimum Class B roof covering installed per design.

Interior: Per building design

Min. 7/16

LP FlameBlock,

Pyrotite facing the interior

Fire wall with the adjacent trusses and code-compliant roof deck

4´ 4´

REFERENCE DESIGN: INTERTEK LPB/WPPS 60-01

BTC/WA 60-01

Click here for online listing.

Fire Rating: 1 hour from both sides

BEARING WALL - MAXIMUM LOADING OF 2,145 LBS. PER STUD

Examples: Single and multifamily buildings close to lot lines.

Framing: Nominal 2˝ x 6˝ framing, spaced 16˝ o.c., with two top plates and one bottom plate. Mineral wool insulation, nominal 2.5 pcf and 5 1 ⁄

2

˝ thick, pressure fit in the cavities between studs. Mineral wool insulation is required for 1-hour fire rating from exterior side.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment facing the exterior, fastened to studs with minimum 1 7 ⁄

8

˝ 6d nails, spaced 6˝ o.c. on perimeter and 12˝ in the field. Horizontal joints are to be staggered with those of interior GWB. Code-compliant building wrap installed per manufacturer’s instructions. Wood, wood composite, fiber cement, stucco or steel exterior facing options per Intertek listing, installed per manufacturers instructions.

Interior: Any classified 5⁄8˝ Type X GWB, applied vertically and nailed to studs with minimum 1 7 ⁄

8

˝ drywall nails or code-compliant screws, spaced

8˝ o.c. Wallboard joints must be covered with tape and joint compound, and fastener heads covered with joint compound.

5-1/2˝ 2.5 pcf Mineral

Wool Insulation

5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

2x6 wood stud

16˝o.c.

Exterior Facings *

* Installed per Manufacturer’s Instructions

1. Steel Siding

2. T-1-11 Siding

3. Fiber Cement Board

4. Wood Strand or Fiber Panel

6. Diamond Wall Insulating Stucco

HORIZONTAL SECTION

DESIGN No - Intertek Labs - BTC/WA 60-01

1-HOUR RATED EXTERIOR FIRE WALL

Bearing Wall - Max. Loading 2145 lbs. per stud

Min. 7/16 Category

LP FlameBlock with

Pyrotite surface facing out

7

8

A P P L I C A T I O N S A N D A S S E M B L I E S

REFERENCE DESIGN: BXUV.U348/BXUVC.W323

Click here for online listing.

Fire Rating: 1 hour from interior side only

Finish Rating: 23 minutes

BEARING WALL

Examples: Multifamily/senior living and commercial Type V property where a fire rating from the exterior is not required.

Framing: Nominal 2˝ x 4˝ framing, spaced 16˝ o.c. or 2˝ x 6˝ framing, spaced 24˝ o.c., with two top plates and one bottom plate. Faced or unfaced mineral fiber insulation, nominal 3.0 pcf, or fiberglass insulation, nominal 0.9 pcf, pressure fit in the cavities between wall framing.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment facing wall cavity, fastened to studs with minimum 1 7 ⁄

8

˝ 6d nails, spaced

6˝ o.c. on perimeter and 12˝ in the field. Code-compliant building wrap installed per manufacturer’s instructions. Wide range of exterior facings accepted, installed per manufacturer’s instructions.

Interior: Any classified 5⁄8˝ Type X GWB, applied vertically and nailed to studs with minimum 1 7 ⁄

8

˝ drywall nails or code-compliant screws, spaced

7˝ o.c. Wallboard joints covered with tape and joint compound. Fastener heads covered with joint compound.

FIRE SIDE

Min. 3-1/2˝ 3.0 pcf Mineral Fiber or

0.9 pcf Fiberglass

Insulation

5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

Nominal 2˝ Wood Framing

Exterior Facings *

* Installed per Manufacturer’s Instructions

1. Vinyl Siding

2. Particle Board Siding

3. T-1-11 Plywood

4. Cementitious Stucco

5. Brick

6. Any approved exterior cladding.

HORIZONTAL SECTION

Design No. - BXUV.U348/BXUVC.W323

Bearing Wall Rating - 1 Hr

(EXPOSED TO FIRE ON INTERIOR FACE ONLY)

Min. 7/16 Category

LP FlameBlock 1-Side

Pyrotite surface facing wall cavity

REFERENCE DESIGN: BXUV.U349/BXUVC.W324

Click here for online listing.

Fire Rating: 2 hours from interior side only

Finish Rating: 55 minutes

BEARING WALL

Examples: Type III buildings (5 & 6 stories) mixed use/multifamily residential buildings with adequate fire separation distance.

Framing: Nominal 2˝ x 4˝ framing, spaced 16˝ o.c. or 2˝ x 6˝ framing, spaced 24˝ o.c., with two top plates and one bottom plate, OR minimum

No. 20 MSG corrosion-protected steel studs, minimum 3 1 ⁄

2

˝ deep. Maximum spacing 16˝ o.c., attached to floor and ceiling tracks with minimum

1⁄2˝ Type S-12 steel screws or bolted or welded per AISI specifications. Faced or unfaced glass fiber insulation, nominal 0.25 pcf and 3 1 ⁄

2

˝ thick, or mineral wool insulation, 3.0 pcf and 3 1 ⁄

2

˝ thick, pressure fit in the cavities between studs.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment on both sides, fastened to studs with minimum 1 7 ⁄

8

˝ 6d nails (screws when steel studs are used), spaced 6˝ o.c. on perimeter and 12˝ in the field. Code-compliant building wrap installed per manufacturer’s instructions. Wide range of exterior facings accepted, installed per manufacturer’s instructions.

Interior: Two layers of any classified 5⁄8˝ Type X GWB, applied vertically with joints staggered. Base layer nailed to studs with minimum 1 7 ⁄

8

˝ drywall nails or code-compliant screws, 7˝ o.c. Face layer fastened to studs and bearing plated with 8d cement-coated drywall nails or screws, spaced 8˝ o.c. Face layer wallboard joints covered with tape and joint compound. Fastener heads covered with joint compound. For securement to steel studs and track, Type S or S-12 steel screws, 1˝ for base layer and 1 5 ⁄

8

˝ long for face layer, with spacing same as that for nails.

FIRE SIDE

3-1/2˝ Fiberglass

Insulation

2 Layers 5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

Wood or Steel framing

Exterior Facings *

* Installed per Manufacturer’s Instructions

1. Vinyl Siding

2. Particle Board Siding

3. T-1-11 Plywood

4. Cementitious Stucco

5. Brick

6. Any approved exterior cladding.

HORIZONTAL SECTION

Design No. - BXUV.U349/BXUVC.W324

2 HOUR RATED EXTERIOR WALL

(EXPOSED TO FIRE ON INTERIOR FACE ONLY)

Min. 7/16 Category

LP FlameBlock with

Pyrotite on both faces

9

A P P L I C A T I O N S A N D A S S E M B L I E S

REFERENCE DESIGN: BXUV.W408

Click here for online listing.

Fire Rating: 2 hours from interior side, 1 hour from exterior side

Finish Rating: 50 minutes on interior face, 17 minutes on exterior face

BEARING WALL

Examples: Type III buildings (5 & 6 stories) mixed use/multifamily residential buildings.

Framing: Nominal 2˝ x 4˝ framing, spaced 16˝ o.c. or 2˝ x 6˝ framing, spaced 24˝ o.c., with two top plates and one bottom plate. Faced or unfaced glass fiber insulation, nominal 0.25 pcf and 3 1 ⁄

2

˝ thick, or mineral wool insulation, 3.0 pcf and 3 1 ⁄

2

˝ thick, pressure fit in the cavities between studs.

Mineral wool insulation is required for 1-hour fire rating from exterior side.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment on both sides, fastened to studs with minimum 1 7 ⁄

8

˝ 6d nails, spaced 6˝ o.c. on perimeter and 12˝ in the field. Code-compliant building wrap installed per manufacturer’s instructions. Wood, wood composite, stucco, and fiber cement exterior facing options per UL listing, installed per manufacturer’s instructions.

Interior: Two layers of any classified 5⁄8˝ Type X GWB, applied vertically with joints staggered. Base layer nailed to studs with minimum 1 7 ⁄

8

˝ drywall nails or code-compliant screws, 7˝ o.c. Face layer fastened to studs and bearing plated with 8d cement-coated drywall nails or screws, 8˝ o.c. Face layer wallboard joints covered with tape and joint compound. Fastener heads covered with joint compound.

Notes:

A: When nominal 4˝ brick is installed as the exterior facing, fiberglass insulation may be used in the wall cavities while maintaining the 1-hour fire rating from the exterior. See report LP10288-05 for more information.

B: Fire resistance rating may be increased to 2 hours from both sides of the wall by addition of one layer of 5/8˝ Type X exterior gypsum or 7/8˝

3-coat stucco to the exterior face of the LP FlameBlock panels. See reports LP10288-05 and 10288-09 .

3-1/2˝ 3.0 pcf Mineral

Wool Insulation

(2) 5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

INTERIOR FACE

Nominal 2˝ Wood Framing

10

Exterior Facings *

*Req’d for 1 Hr. from Exterior Face

1. Min. 11/32˝ Exterior Wood Siding

2. Min. 7/16˝ Exterior OSB Lap Siding

3. Min. 3/8˝ Cementitious Stucco

4. Min. 7/16˝ Fiber Cement Siding

5. Brick

HORIZONTAL SECTION

Design No. - UL BXUV.W408

2-HOUR RATED EXTERIOR WALL

(EXPOSED TO FIRE ON INTERIOR FACE ONLY)

Bearing Wall Rating - 1 Hr

(EXPOSED TO FIRE ON EXTERIOR FACE ONLY)

Min. 7/16 Category

LP FlameBlock with

Pyrotite on both faces

REFERENCE DESIGN: BXUV.U350/BXUVC.W325

Click here for online listing.

Fire Rating: 2 hours from both sides

Finish Rating: 23 minutes

BEARING WALL

STC RATINGS: CONFIGURATION A: 62 CONFIGURATION B: 62

Examples: Walls between living units, 2-hour chase walls, or between living units and corridors/stairs.

3-1/2˝ 3.0 pcf Mineral

Wool Insulation

Framing: Nominal double row of 2˝ x 4˝ framing, spaced 16˝ o.c. or 2˝ x 6˝ framing, spaced 24˝ o.c., with two top plates and one bottom plate, with studs effectively fire stopped. Opposite stud rows spaced a minimum of 1˝ apart (allowing for wall sheathing, if applicable), and opposing studs staggered 8˝ o.c.

Faced or unfaced fiberglass insulation, nominal

0.25 pcf and 3 1/2˝ thick, or mineral wool insulation, nominal 3.0 pcf and 3 1⁄2˝ thick, pressure fit in the cavities between studs.

Living Space Side:

Configuration A – Minimum 7/16 category LP

FlameBlock with Pyrotite treatment facing the stud cavities, fastened to studs with minimum 17⁄8˝ 6d nails, spaced 6˝ o.c. on perimeter and 12˝ in the field. 5⁄8˝ Type X GWB, applied vertically and fastened to wall studs, with joints staggered with those of FlameBlock sheathing.

3-1/2˝ 3.0 pcf Mineral

Wool Insulation

5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

Nominal 2˝ Wood Framing

Min. 7/16 Category

LP FlameBlock 1-Side

Pyrotite surface facing wall cavity

HORIZONTAL SECTION

DESIGN No. - UL BXUV.U350/BXUVC.W325

2-HOUR INTERIOR PARTY WALL

STC Rating = 62

Configuration A

5/8˝ Type X GWB

Wallboard Joints and Nailheads covered with tape and joint compound

Configuration B (Required for STC rating:

Resilient channel of 25 MSG galvanized steel, installed horizontally and spaced vertically 24˝ o.c., secured to studs with min. 11⁄4˝ diamondshaped point, double lead Phillips head steel screws.) 5⁄8˝ Type X GWB, applied vertically and fastened with minimum 1˝ self-drilling, selftapping Type S or S-12 steel screws.

Nominal 2˝ Wood

Framing

Nominal 2˝ Wood Framing

Resilient channel

Concealed Space Side:

Configuration A – No sheathing required. Fire blocking per code requirements.

Configuration B – Minimum 7/16 category LP

FlameBlock with Pyrotite treatment facing the stud cavities, fastened to studs with minimum

17⁄8˝ 6d nails, spaced 6˝ o.c. on perimeter and

12˝ in the field. Fire blocking per code requirements.

Min. 7/16 Category

LP FlameBlock 1-Side

Pyrotite surface facing wall studs

HORIZONTAL SECTION

DESIGN No. - UL BXUV.U350/BXUVC.W325

2-HOUR INTERIOR PARTY WALL

STC Rating = 62

Configuration B

11

12

A P P L I C A T I O N S A N D A S S E M B L I E S

REFERENCE DOCUMENTS: CALIFORNIA WUI ZONE EXTERIOR WALL TEST PROTOCOL 12-7A-1

Click here for online listing.

Cal-Fire/OSFM Listing Nos 8140-2027:0005 and 8140-2027:0006

Western Fire Center Test Report No. 10023.1

Examples: Single and multifamily homes in areas designated as high wildfire hazard.

Exterior: Minimum 15/32 category LP FlameBlock with Pyrotite treatment facing the exterior, fastened to studs with minimum 1 7 ⁄

8

˝ 6d nails, spaced 6˝ o.c. on perimeter and 12˝ in the field. Exterior cladding of LP SmartSide Precision Series lap or panel siding, cedar shingles of nominal

½˝ butt thickness or less, or plain bevel wood siding of cedar and other species in various widths. Cladding material installed in accordance with manufacturer’s instructions.

Framing and Insulation: Per building design and in accordance with California Building Code

Interior Finish: Per building design and in accordance with California Building Code

Wall cavity insulation per design (optional)

16˝o.c.

1/2˝ GWB

Wallboard Joints and Nailheads covered with tape and joint compound or other interior finish per design (optional)

2x4 Wood framing

FIRE SIDE

Exterior Facings *

*

Installed per Manufacturer’s Instructions

1. LP SmartSide lap or panel siding

2. Cedar sidewall shingles with 1/2˝ butt-end thickness

3. Plain bevel solid wood siding, Cedar or other species

HORIZONTAL SECTION

Cal-Fire Listings 8140-2027:0005 and :0006

Fire Rating from the Exterior Only

Min. 7/16 Category

LP FlameBlock with

Pyrotite surface facing out

REFERENCE DOCUMENTS: CALIFORNIA WUI ZONE TEST PROTOCOL 12-7A-3

Click here for online listing.

Cal-Fire/OSFM Listing No. 8160-2027:0007

Western Fire Center Test Report No. 10085

Examples: Closed soffit in single and multifamily homes in areas designated as high wildfire hazard.

Exterior: Minimum 7/16 category LP FlameBlock with Pyrotite treatment facing the exterior, fastened to supports with minimum 1 7 ⁄

8

˝ 6d nails, spaced 6˝ o.c. on perimeter and 12˝ in the field. Exterior cladding (soffit ceiling) of cedar or redwood T&G cladding boards of nominal 5⁄8˝ thickness and greater. Cladding material installed in accordance with manufacturer’s instructions.

Framing and Insulation: Per building design and in accordance with California Building Code.

Cedar or Redwood v-ceiling or T&G cladding, minimum nominal

5/8˝ thickness and nominal

4˝ width, fastened to underside of LP FlameBlock

VERTICAL SECTION

California WUI 12-7A-3

Soffit Assembly

Min. 15/32 Category

LP FlameBlock with

Pyrotite layer facing exterior, fastened to nominal 2˝ framing members

REFERENCE DESIGN: CALIFORNIA WUI ZONE GUIDELINES FOR UNDER EAVE CONSTRUCTION

(IGNITION-RESISTANT CONSTRUCTION)

Click here for CBC 707A.4 information.

2013 California Building Code Section 707A.4

Examples: Open eaves in single and multifamily homes in areas designated as high wildfire hazard.

Roof Decking: Minimum 15/32 category LP FlameBlock with Pyrotite treatment facing downward and coated with exterior-grade paint.

Framing: Exposed rafter tails and cross-blocking of minimum nominal 2˝ lumber.

Roof covering per design

Min. 15/32 Category

LP FlameBlock installed on exposed rafter supports of minimum nominal 2˝ lumber with Pyrotite layer facing downward and coated with exterior-grade paint

13

I N S T A L L A T I O N I N S T R U C T I O N S

14

GENERAL REQUIREMENTS

• Comply with local safety regulations when installing roof, wall, or subfloor sheathing.

• Comply with the following manufacturer’s instructions and with APA’s Engineered Wood Construction Guide Form E30U (September 2007) or the current equivalent.

STORAGE AND HANDLING

• Store panels in clean, dry areas off the ground. If possible, store indoors. If stored outside, cover with plastic sheets, tarps or the LP FlameBlock

Fire-Rated OSB Sheathing unit cover. Keep cover open and away from the sides and bottom of panels to allow for air circulation.

• Additional protective measures may be necessary during extended adverse weather conditions.

ROOF INSTALLATION

• Place the skid-resistant side up with the white fire-resistant surface facing down and wear skid-resistant shoes when installing LP FlameBlock

Fire-Rated OSB Sheathing as roof sheathing on either side of a partition wall in multi-family residential buildings, or in any application where reducing the spread rate of an interior fire is the intent of the code requirement. Install LP FlameBlock Fire-Rated OSB Sheathing with the white

Pyrotite side facing upwards when used under EPDM roof membranes and in other applications where reducing the spread rate of fire from an exterior source is the intent.

• Install with the long dimension or strength axis of the panel across supports and with the panel continuous over two or more spans.

• Provide 1⁄8˝ space at panel ends and edges. Use a spacer tool (i.e. 10d box nail) to ensure accurate and consistent spacing.

• Panel end joints shall occur over framing. Stagger end joints in each succeeding row.

• For panels in the 7/16 and 15/32 category, provide additional panel stiffness by installing panel edge clips mid-span on all unsupported edges.

• Nail 6˝ o.c. along supported panel ends and edges and 12˝ o.c. at intermediate supports. Fasten panels 3⁄8˝ from panel edges. Use 8d common nails for panels up to 1˝ thickness. For panels over 1˝ use 8d ring-shank or 10d common nails. Other code-approved fasteners may be used.

• Cover roof sheathing as soon as possible with roofing felt or shingle underlayment for protection against excessive moisture prior to roofing.

If any edge swelling occurs prior to roof underlayment installation, the exposed wood substrate side of panels with raised joints should be sanded flat.

• Remove wrinkles and flatten surface of shingle underlayment before installing shingles. High performance shingle underlayment is recommended for better results.

• Heavier weight and/or textured shingles are recommended to better mask imperfections in roofing assembly.

• When installed as roof deck in open eaves, the exposed underside of panels, as well as any exposed edges, must be coated with exterior-grade paint.

NOTE: Check with your local building department before deciding on an installation method.

WALL INSTALLATION

• LP FlameBlock Fire-Rated OSB Sheathing panels should be installed as specified in the relevant fire-rated assembly. In the absence of a listed firerated assembly, panels should be installed vertically, with the horizontal joints blocked.

• When installing LP FlameBlock Fire-Rated OSB Sheathing in walls, consult approved construction plans to determine the proper orientation of the white, fire-resistant panel surface.

• Provide 1⁄8˝ space between panel ends and edges. Use a spacer tool (i.e. 10d box nail) to ensure accurate and consistent spacing.

• At minimum, nail 6˝ o.c. along supported panel ends and edges and 12˝ o.c. at intermediate supports. Fasten panels 3⁄8˝ from panel edges.

Use 6d common nails for panels up to 1˝ thickness. For panels over 1˝ use 8d ring-shank or 8d common nails. Other code-approved fasteners may be used.

NOTE: For shear walls, use the fastener type and spacing specified in approved construction documents.

I T ’ S M O R E T H A N O U R P R O D U C T S . I T ’ S T H E W A Y W E D O B U S I N E S S .

At LP Building Products, we’re proud to offer integrated building solutions that work together to save you time and money. And proud that our products offer so many benefits.

But something else sets us apart: the way we do business. We believe that “sustainability” means acting in a way that protects the environment, embraces social responsibilities, and builds economic prosperity today and for future generations.

We invite you to discover more about LP’s environmental programs, industry-leading employee safety accomplishments, community involvement and financial results by visiting our website at LPCorp.com.

15

LP® FlameBlock® Fire-Rated OSB Sheathing helps you meet fire codes while reducing dead load and wall thickness versus common alternatives. It offers higher design values than FRT plywood at the same thickness and provides a better substrate for securely fastening exterior facing. Choose LP FlameBlock sheathing for your next project.

D R I V I N G I N N O V A T I O N

I N F I R E - R E S I S T A N T

C O N S T R U C T I O N

For more information about LP FlameBlock Fire-Rated OSB Sheathing, including our Technical Guide, call 1-888-820-0325 or visit LPCorp.com/FlameBlock

LPCorp.com/FlameBlock

Phone: 1-888-820-0325

Fax: 1-877-523-7192

Email: [email protected]

© 2015 Louisiana-Pacific Corporation. All rights reserved. The UL mark is a registered trademark of Underwriters Laboratories, Inc.

Pyrotite is a registered trademark of Barrier Technology, Inc.

All other trademarks are owned by Louisiana-Pacific Corporation.

Specifications subject to change without notice.

Printed in USA. LPFB0070 12/15

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement