G6D-4B/G3DZ-4B
Terminal Relay
G6D-4B/G3DZ-4B
CSM_G6D-4B_G3DZ-4B_DS_E_4_1
Space-saving Vertical Terminal Relays with 4
Outputs
• Space saving size: 28 × 90 × 45 mm (W × H × D)
• Lineup includes models with G6D Relays and models with
G3DZ Power MOS FET Relays.
• Easy wiring with separate I/O terminal construction.
• LED operation indicator.
• Built-in diode absorbs coil surge.
• Special socket used for easy Relay replacement.
• Mounts either on DIN track or with screws.
• Relay Removal Tool.
Ordering Information
■ List of Models
Output
Relay outputs
Contact
configuration
Model
Four SPST-NO G6D-4B
relays
Power MOS FET
relay outputs
G3DZ-4B
Rated voltage
12 VDC
24 VDC
12 VDC
24 VDC
■ Accessories (Order Separately)
Replacement Relays
Applicable
Terminal Relay
G6D-4B
Model
G6D-1A-ASI
Rated voltage
12 VDC
24 VDC
G3DZ-4B
G3DZ-2R6PL
12 VDC
24 VDC
1
G6D-4B/G3DZ-4B
Specifications
■ Ratings
■ Characteristics
Relay Specifications
Model
G6D-4B
Item
Relay output
Coil Ratings (per G6D Relay)
Contact resistance (See
note 2.)
100 mΩ max.
Rated Rated Coil resis- Must
Must
Max.
Power
voltage current
tance
operate release voltage
con(V)
(mA)
(Ω)
voltage voltage
(V) sumption
(V)
(V)
(mW)
Must operate time (See
note 3.)
10 ms max.
Release time (See note
3.)
15 ms max.
DC 12 18.7
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between
coil and contacts
24 10.5
720
70%
10%
max.
min.
(See
note 1.)
2,880
130%
Approx.
200
Note: 1. The must operate voltage is 75% max. when the Terminal
Relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil
temperature of 23°C.
4. The maximum voltage is the maximum value of the
allowable voltage range for the relay coil operating power
supply. There is no continuous allowance.
5. The rated current includes the terminal's LED current.
Contact Ratings (per G6D Relay)
Item
Load
750 VAC, 50/60 Hz for 1 min between
contacts of same polarity
Impulse withstand voltage 4,000 V (1.2 × 50 µs)
(between coil and
contacts)
Vibration
Destruction
resistance
10 to 55 to 10 Hz, 0.75-mm single
amplitude (1.5-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.75-mm single
amplitude (1.5-mm double amplitude)
Shock
Destruction
resistance Malfunction
500 m/s2
Endurance Mechanical
20,000,000 operations min. (at 18,000
operations/hr)
Electrical
100,000 operations min. (3 A at 250 VAC,
(See note 3.) resistive load)
100,000 operations min. (3 A at 30 VDC,
resistive load) (at 1,800 operations/hr)
Resistive load (cosφ = 1)
Rated load
3 A at 250 VAC, 3 A at 30 VDC
Rated carry current
3A
Max. switching voltage 250 VAC, 30 VDC
100 m/s2
Minimum permissible
load (reference value)
(See note 4.)
10 mA at 5 VDC
Ambient operating/
storage temperature
−25 to 55°C (with no icing)
Power MOS FET Relay Specifications
Ambient operating
humidity
45 to 85%
Input (per G3DZ Power MOS FET Relay)
Weight
Approx. 70 g
Max. switching current 3 A
Max. switching power
(reference value)
750 VA, 90 W
Input
Must
Rated Operating
Must
voltage
voltage
operate release impedance
(V)
voltage voltage
level
level
DC 12
24
9.6 to 14.4 9.6 VDC
VDC
max.
1 VDC
min.
19.2 to
19.2 VDC
28.8 VDC max.
Rated
current
2 kΩ±20%
8.0 mA
±20%
4 kΩ±20%
8.2 mA
±20%
Note: The rated current includes the terminal's LED current.
Output (per G3DZ Power MOS FET Relay)
Load voltage
3 to 264 VAC
3 to 125 VDC
Load current
100 µ to 0.3 A
Inrush current
resistance
6 A (10 ms)
Note: 1.
2.
3.
4.
The above values are initial values.
Measurement condition: 1 A at 5 VDC
Ambient temperature: 23°C
This value is measured at 120 operations/min.
Model
Item
Must operate time
G3DZ-4B
Power MOS FET relay outputs
10 ms max.
Release time
15 ms max.
Output ON resistance
2.4 Ω max.
Leakage current at OFF
state
10 µA max. (at 125 VDC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between
input and output terminals
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single
amplitude (1.5-mm double amplitude)
Shock resistance
500 m/s2
−25 to 55°C (with no icing)
Note: There is no output polarity for the G3DZ.
Ambient operating/
storage temperature
Ambient operating
humidity
45% to 85%
Weight
Approx. 65 g
2
G6D-4B/G3DZ-4B
Engineering Data
■ Reference Data
G6D-4B
Endurance
100
50
30
10
AC resistive load
DC resistive load
5
500
Endurance (×104 operations)
Switching voltage (V)
Maximum Switching Power
3
300
100
50
250 VAC/30 VDC resistive load
30
10
1
5
0.5
3
0.3
0.1
0
3
5
30 50 100
10
250
0
500
1
2
3
4
5
6
Switching voltage (V)
7
8
9
10
Switching current (A)
G3DZ-4B
Inrush Current Resistance
Non-repetitive
Inrush current (A. Peak)
Load current (A)
Load Current vs. Ambient
Temperature
1
0.8
0.6
(
Keep the inrush current to half the rated
value if inrush current occurs repetitively.
8
6
4
0.4
0.3
0.2
0
−30 −20
2
0
20
40
55 60
80
)
10
0
100
5
10
30 50 100
300 500 1,000 3,000 5,000
Note: Measurement values taken from
production line samples have been plotted
in graphs to provide this data. Use this
data only as a guide.
Relays are mass-produced, so
allowances must be made for a certain
amount of variation in measurement data.
Energizing time (ms)
Ambient temperature (°C)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Relays
G6D-4B
G3DZ-4B
Mounting Holes
13, M3 Phillips screws
Two, 4-dia. holes or M3.5 screw holes
1
2
3
Terminal Arrangement/
Internal Connections
(Top View)
+
COM
4
−
1
−
2
−
3
−
4
Ry4
Ry3
90 max.
(94)
Ry2
80±0.2
1
Ry1
2
3
5
6
7
8
11
20±0.2
28 max.
4
80±0.3
9
10
12
6
35 max.
45 max.
20±0.3
Note: 1. Do not reverse the coil polarity.
2. There is no output polarity for the
G6D-4B and G3DZ-4B.
3
G6D-4B/G3DZ-4B
■ Accessories (Order Separately)
Relay Mounting Products (Order Separately)
Safety Precautions
Refer to Safety Precautions for All Relays.
Mounted Relays
Relays and SSRs cannot be mounted together.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement