Liebert Ship-Ahead Input/Output Cabinet NXL Installation manual


Add to my manuals
20 Pages

advertisement

Liebert Ship-Ahead Input/Output Cabinet NXL Installation manual | Manualzz

Liebert

®

NXL

Ship-Ahead Input/Output Cabinet

Installation Manual – 250-400kVA, 60Hz

AC Power

For Business-Critical Continuity™

C

ONTACTING

L

IEBERT FOR

S

UPPORT

To contact Liebert Services for information or repair service in the United States, call

1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts.

For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Emerson Network Power Liebert Services, the authorized distributor is responsible for providing qualified, factory-authorized service.

For LGS to assist you promptly, please have the following information available:

Part numbers: _________________________________________________________________

Serial numbers:________________________________________________________________

Rating: _______________________________________________________________________

Date purchased: _______________________________________________________________

Date installed:_________________________________________________________________

Location: ______________________________________________________________________

Input voltage/frequency:________________________________________________________

Output voltage/frequency: ______________________________________________________

Battery reserve time:___________________________________________________________

Product Warranty Registration

To register for warranty protection, visit the Service and Support section of our Web site at: www.liebert.com

Click on Product Registration and fill out the form.

TABLE OF CONTENTS

1.0

M ECHANICAL I NSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

1.1

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.2

Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.3

Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.4

Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2.0

E LECTRICAL I NSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

2.1

External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.2

Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.0

I NSTALLATION D RAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

FIGURES

Figure 1

Input/output conduit detail drawing, 250-300kVA Liebert NXL UPS . . . . . . . . . . . . . . . . . . . . . . 9

Figure 2 Input/output conduit detail drawing, 400kVA Liebert NXL UPS . . . . . . . . . . . . . . . . . . . . . . . . . 10

Figure 3 Top cable entry routing and installation order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Figure 4 Bottom cable entry routing and installation order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Figure 5 Floor mount brackets—standard and optional layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Table 1

Table 2

Table 3

Table 4

Table 5

Table 6

TABLES

Current ratings—rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Current ratings—bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Current ratings—output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Current ratings—battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Recommended conduit and cable sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

i

ii

I

MPORTANT

S

AFETY

I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of your Liebert NXL ™ Input/Output Cabinet. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.

!

!

WARNING

Risk of electrical shock. Can cause personal injury or death.

Check for voltage with both AC and DC voltmeters before working within the cabinet. Check for voltage with both AC and DC voltmeters before making contact.

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.

Extreme caution is required when performing installation.

Special safety precautions are required for procedures involving handling, installation of the

UPS system. Observe all safety precautions in this manual before handling or installing the cabinet. Observe all precautions in the Operation and Maintenance Manual, SL-25425, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system.

WARNING

Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.

Exercise extreme care when handling the cabinet to avoid equipment damage or injury to personnel.

Locate center of gravity symbols and determine unit weight before handling each cabinet.

Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.

Slots at the base of the modules cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.

Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.

!

WARNING

Risk of electrical shock and fire. Can cause equipment damage, personal injury or death.

The area around the cabinet should be kept free of puddles of water, excess moisture and debris.

Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the DC connections.

All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes.

One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.

1

Mechanical Installation

1.0

M

ECHANICAL

I

NSTALLATION

1.1

Introduction

This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL Input/Output Cabinet.

This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures.

NOTICE

All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation.

NOTICE

Three-phase input supply required.

The standard Liebert NXL UPS is suitable for connection to three-phase, four-wire (+ Earth)

TN-C, TN-S, IT-G, IT-IG or, three-phase, three-wire plus ground, IT-UG.

If using with IT Power system, a 4-pole disconnect device must be included as part of building installation.

1.2

Preliminary Checks

Before installing the cabinet, please carry out the following preliminary checks:

• Visually examine the cabinet for transit damage, both internally and externally. Report any damage to the shipper immediately.

• Verify that the correct equipment is being installed.

• Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.

1.3

Environmental Considerations

1.3.1 UPS Room

The cabinet intended for indoor installation and should be located in a cool, dry, clean-air environment.

When bottom entry is used, the conduit plate must be installed.

NOTE

The UPS is suitable for mounting on concrete or other non-combustible surface only.

1.4

Positioning

The Liebert NXL Input/Output Cabinet is structurally designed to withstand lifting from the base.

!

CAUTION

Risk of unit tipping over. Can cause equipment damage and personal injury.

Floor mount brackets must remain attached to the frame until the unit is being placed in its final, installed position. (The final installation will always require the unit to be bolted to another Liebert NXL product.) Failure to comply with these instructions could result in equipment damage and/or injury to personnel.

2

Mechanical Installation

1.4.1 Moving the Cabinets

The Liebert NXL Input/Output Cabinet can be handled with a forklift or similar equipment.

When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.

Handling the cabinet with straps is not authorized.

1.4.2 Clearances

Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully open. Installation must leave a distance of 24" (610mm) between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.

Space must be reserved on the left side of the I/O cabinet. The UPS Rectifier/Inverter cabinet can be mounted only on the left side of the I/O cabinet.

1.4.3 Floor Installation/Anchoring

If the equipment is to be located on a raised floor, it should be mounted on a pedestal designed to accept the equipment point loading. Refer to the base view to design this pedestal.

3

Electrical Installation

2.0

E

LECTRICAL

I

NSTALLATION

This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.

!

WARNING

Risk of electrical shock. Can cause injury or death.

Check for voltage with both AC and DC voltmeters before working within the cabinet.

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the cabinet or preparing the cabinet for installation.

2.1

External Protective Devices

For safety, circuit breakers must be installed in the input AC supply and external battery system.

Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed.

External overcurrent protection must be provided. See Tables 1 through 4 for overload capacity.

Dual Input

When wiring the cabinet with a separate rectifier and bypass input, each input must be protected separately.

Size the breakers according to the input currents shown in Tables 1 and 2.

2.2

Power Cables

The UPS will require both power and control cabling. All control cables, whether shielded or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected

The cable design must comply with the voltages and currents in Tables 1 through 4, follow local wir-

ing practices and take into consideration the environmental conditions (temperature and physical support equipment and methods), room temperature and conditions of installation of the cable and system’s overload capacity.

For cable entry terminal, refer to Figure 1.

!

WARNING

Risk of electrical shock. Can cause injury or death.

Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the input/bypass supply to the power distribution panel.

Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.

NOTICE

For dual input operation, ensure that any busbars between the bypass and the rectifier input are removed.

When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given

in Table 4.

4

Electrical Installation

The following are guidelines only and are superseded by local regulations and codes of practice where applicable:

• Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non-

linear loads. Refer to the values in Tables 2 and 3.

• The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.

• Consideration should be given to the use of smaller, paralleled cables for heavy currents, as this can ease installation considerably.

2.2.1 Power Cable Connection Procedure

Equipment Ground

The equipment ground busbar is located as shown in Figure 1. The grounding conductor must be

connected to the ground busbar and bonded to each cabinet in the system.

All cabinets and cabling should be grounded in accordance with local regulations.

NOTICE

Proper grounding reduces problems in systems caused by electromagnetic interference.

!

WARNING

Risk of fire and electrical shock. Can cause equipment damage, personal injury or death.

Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur.

All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Liebert

Services. See the back page of this manual for contact information.

The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice.

Once the equipment has been positioned and secured, connect the power cables as described in the following procedure.

Refer to the appropriate cable connection drawing in Figure 3 or 4.

1. Verify that the equipment is isolated from its external power source. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.

2. Open exterior and interior panels on the front of the I/O.

3. Connect the ground and any necessary main bonding jumper to the equipment ground busbar located in the I/O section.

4. Make power connections and tighten the connections to the proper torque according to one of the two procedures below, depending on the type of installation:

NOTE

Ensure correct phase rotation.

• Top Cable Entry (see Figure 3)

• Bottom Cable Entry (see Figure 4)

5

!

!

Top Cable Entry

When making the power connections, the recommended order of pulling and installing cables is to start from the top connections to the bottom connections. The cables must be routed

around the fault braces (see Detail in Figure 3). This is to prevent the cables from contacting

other busbars. The recommended conduit layout is shown in Figure 1.

Bottom Cable Entry

When making the power connections, the recommended order of pulling and installing cables is to start from the bottom connections to the top connections. The cables must be routed

around the fault braces (see Detail in Figure 3. This is to prevent the cables from contacting

other busbars. The recommended conduit layout is shown in Figure 1.

NOTE

For a Single Input configuration, linking busbars must be installed between the bypass and the rectifier input.

WARNING

Risk of electrical shock. Can cause injury or death.

If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their termination.

WARNING

Risk of electrical shock. Can cause injury or death.

When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first.

NOTE

If fault bracing brackets were removed during installation, they MUST be replaced.

5. Close and secure the interior and exterior doors.

Table 1

UPS Rating

Current ratings—rectifier input

Voltage, VAC kVA kW Input Bypass Output

250 225 480

300 270 480

400 360 480

480

480

480

480

480

480

Nominal

Current

313

376

500

Table 2 Current ratings—bypass input

UPS Rating kVA kW

250

300

400

225

270

360

Input

480

480

480

Voltage, VAC

Bypass Output

480

480

480

480

480

480

Maximum

Current

392

469

625

Nominal

Current

301

361

481

External

100% Breaker

Trip, Amps

400

500

700

10 Minute

Overload

376

451

601

External

80% Breaker

Trip, Amps

500

600

800

External Breaker

Trip, Amps

400

500

700

Table 3 Current ratings—output

UPS Rating kVA kW

250

300

400

225

270

360

Input

480

480

480

Voltage, VAC

Bypass Output

480

480

480

480

480

480

Nominal

Current

301

361

481

10 Minute

Overload

376

451

601

Electrical Installation

External Breaker

Trip, Amps

400

500

700

6

Electrical Installation

Table 4 Current ratings—battery

UPS Rating kVA kW

250

300

400

225

270

360

Nominal VDC

480

480

480

Maximum Battery

Current at EOD

615

737

981

External Breaker

Trip, Amps

700

800

1000

Table 5

Notes on Tables

1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input current is controlled by the current limit setting which is adjustable. Values shown are for maximum setting of 125%. Standard factory setting is 125%.

2. Recommended bypass external overcurrent protection is based on 125% overload capacity for 10 minutes.

3. All recommended external overcurrent protections are based on 80% rated breakers.

4. Nominal battery voltage is shown at 2.0 volts / cell.

Recommended conduit and cable sizes

Rectifier Input

UPS Rating

Voltage

(VAC) kVA kW Input Bypass Output

250 225

300 270

400 360

480

480

480

480

480

480

480

480

480

Nominal Selection

Top Cable Entry Input

Wire & Conduit

Ph, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, G THW / RNC

(2) 2.5C 3-250kcmil,

#1/0AWG

(2) 3C 3-350kcmil,

#1/0AWG

(2) 3C 3-500kcmil,

#1/0AWG

(2) 2.5C 3-250kcmil,

#1/0AWG

(2) 3C 3-350kcmil,

#1/0AWG

(2) 3.5C 3-500kcmil,

#1/0AWG

Bypass Input

UPS Rating Voltage (VAC) kVA kW Input Bypass Output

250 225

300 270

400 360

480

480

480

480

480

480

480

480

480

Nominal Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

Output

UPS Rating Voltage (VAC) kVA kW Input Bypass Output

250 225

300 270

400 360

480

480

480

480

480

480

480

480

480

Nominal Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry Input

Wire & Conduit

Ph, N, G THW / RNC

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

Battery

Nominal Selection

UPS Rating Voltage (VAC) kVA kW Input Bypass Output

Top Cable Entry Input

Wire & Conduit

Wires, G THW / FMC

Bottom Cable Entry Input

Wire & Conduit

Wires, G THW / RNC

250 225

300 270

400 360

480

480

480

480

480

480

480

480

480

(2) 2.5C 2-350kcmil,

#1/0AWG

(2) 2.5C 2-500kcmil,

#1/0AWG

(3) 2.5C 2-500kcmil,

#4/0AWG

(2) 2.5C 2-350kcmil,

#1/0AWG

(2) 3C 2-500kcmil,

#1/0AWG

(3) 3C 2-500kcmil,

#4/0AWG

If the UPS is used in a four-wire system, the neutral ground jumper must be removed.

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, G THW / RNC

(3) 2C 3-#2/0AWG,

#1/0AWG

(3) 2.5C 3-#4/0AWG,

#1/0AWG

(3) 2.5C 3-250kcmil,

#1/0AWG

(3) 2C 3-#2/0AWG,

#1/0AWG

(3) 2.5C 3-#4/0AWG,

#1/0AWG

(3) 2.5C 3-250kcmil,

#1/0AWG

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

(2) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(2) 3C 3-350kcmil,

2-#4/0AWG, #1/0AWG

(2) 3.5C 3-500kcmil,

2-350kcmil, #1/0AWG

(2) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(2) 3.5C 3-350kcmil,

2-#4/0AWG, #1/0AWG

(2) 4C 3-500kcmil,

2-350kcmil, #1/0AWG

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Wires, G THW / FMC

(3) 2C 2-#4/0AWG,

#1/0AWG

(3) 2C 2-250kcmil,

#1/0AWG

(4) 2C 2-250kcmil,

#4/0AWG

Bottom Cable Entry Input

Wire & Conduit

Wires, G THW / RNC

(3) 2C 2-#4/0AWG,

#1/0AWG

(3) 2C 2-250kcmil,

#1/0AWG

(4) 2.5C 2-250kcmil,

#4/0AWG

7

Table 6 Recommended lug sizes

Cable Size

T&B Series 54000

One Hole

T&B Series 54000

Two Hole

#8 AWG

#6 AWG

#4 AWG

#2-3 AWG

#1 AWG

#1/0 AWG

#2/0 AWG

54930BE

54905BE

54906BE

54942BE

54947BE

54950BE

54951BE

54850BE

256-30695-868

256-30695-733

54811BE

54857BE

256-30695-593

54862BE

#3/0 AWG

#4/0 AWG

250kcmil

300kcmil

350kcmil

400kcmil

500kcmil

600kcmil

54965BE

54970BE

54913BE

54914BE

54915BE

54916BE

54918BE

54920BE

54864BE

54866BE

54868BE

54870BE

54872BE

54874BE

54876BE

54878BE

750kcmil 54922BE 54880BE

Use the T&B crimping tools recommended for these types of lugs.

Electrical Installation

8

Installation Drawings

3.0

I

NSTALLATION

D

RAWINGS

Figure 1 Input/output conduit detail drawing, 250-300kVA Liebert NXL UPS

DC

(2) 3" CONDUIT

BYPASS

(2) 3.5" CONDUIT

INPUT

(2) 3" CONDUIT

OUTPUT

(2) 3.5" CONDUIT

OUTPUT

(2) 3.5" CONDUIT

INPUT

(2) 3" CONDUIT

BYPASS

(2) 3.5" CONDUIT

DC

(2) 3" CONDUIT

LOW VOLTAGE

1.5" CONDUIT

DC POSITIVE

DC NEGATIVE

SEE NOTE 6

TOP VIEW

A

LOW VOLTAGE

(14) 1" CONDUIT

LOW VOLTAGE

1.5" CONDUIT

BOTTOM VIEW

SHOWN IN EXTENDED

POSITION

76.8

( 1950 )

BYPASS

NEUTRAL

GROUND BUS

(TOP ENTRY)

BYPASS INPUT

RECTIFIER INPUT

OUTPUT

INNER PANEL

REMOVED

FOR CLARITY

GROUND BUS

(BOTTOM ENTRY)

OUTPUT

NEUTRAL

D

B

C

59.4

(1509)

56.4

(1432)

52.9

(1343)

49.4

(1255)

46.4

(1178)

43.4

(1102)

40.4

(1026)

34.4

(874)

37.4

(950)

31.4

(797)

28.4

(721)

25.4

(645)

21.9

(556)

.0

( 0 )

FRONT RIGHT SIDE VIEW

( 14 )

TYP

.87

( 22 )

1.75

( 44 )

TYP

(BOTTOM

ENTRY)

.98

( 25 )

1.75

( 44 )

TYP

1.75

( 44 )

TYP

.87

( 22 ) 1.10

( 28 )

1.75

( 44 )

TYP

(TOP

ENTRY)

( 14 )

TYP

DETAIL A

DETAIL B

O

.56

( 14 )

TYP

NOTES:

1. ALL DIMENSIONS ARE IN inches (mm).

2. 24" MINIMUM CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.

3. KEEP CABINET WITHIN 15 DEGREES OF VERTICAL.

4. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE ACCESS

PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE AND REPLACE.

1.75

( 44 )

TYP

(BOTTOM

ENTRY)

5. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.

6. THESE BRACKETS CAN BE REMOVED DURING INSTALLATION BUT MUST BE

REPLACED AFTER INSTALLATION.

7. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUITS.

.88 X .56 SLOT

6 PLACES

EACH BAR

8. ALUMINUM AND COPPER-CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.

9. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

1.75

( 44 )

TYP

DETAIL C

DETAIL D

1.75

( 44 )

TYP

(TOP

ENTRY)

O

.56

( 14 )

TYP

9

Installation Drawings

Figure 2 Input/output conduit detail drawing, 400kVA Liebert NXL UPS

DC

(2) 3" CONDUIT

BYPASS

(2) 3.5" CONDUIT

INPUT

(2) 3" CONDUIT

OUTPUT

(2) 3.5" CONDUIT

OUTPUT

(2) 3.5" CONDUIT

INPUT

(2) 3" CONDUIT

BYPASS

(2) 3.5" CONDUIT

DC

(2) 3" CONDUIT

LOW VOLTAGE

1.5" CONDUIT

LOW VOLTAGE

(14) 1" CONDUIT

TOP VIEW BOTTOM VIEW

LOW VOLTAGE

1.5" CONDUIT

BYPASS

NEUTRAL

DC POSITIVE

DC NEGATIVE

GROUND BUS

LOCATION

(TOP ENTRY)

B

SEE NOTE 6

BYPASS INPUT

A

RECTIFIER INPUT

OUTPUT

INNER PANEL

REMOVED

FOR CLARITY

GROUND BUS

(BOTTOM ENTRY)

OUTPUT

NEUTRAL

D

C

34.4

( 874)

28.4

( 721)

21.9

( 556)

31.4

(797)

O .56

(14)

TYP

FRONT

.87

( 22)

.98 (25)

( 44 )

TYP

(BOTTOM

ENTRY)

RIGHT SIDE VIEW

1.75

( 44 )

TYP

(TOP

ENTRY) (44)

TYP

DETAIL A

DETAIL B

( 14 )

TYP

NOTES:

1. ALL DIMENSIONS ARE IN inches (mm).

2. 24" MINIMUM CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.

3. KEEP CABINET WITHIN 15 DEGREES OF VERTICAL.

4. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE ACCESS

PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE AND REPLACE.

5. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.

6. THESE BRACKETS CAN BE REMOVED DURING INSTALLATION BUT MUST BE

REPLACED AFTER INSTALLATION.

7. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUITS.

8. ALUMINUM AND COPPER-CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.

9. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL

CODES.

1.75

( 44 )

TYP

( 14 )

TYP

1.75

( 44 )

TYP

(BOTTOM

ENTRY)

.88 X .56 SLOT

6 PLACES

EACH BAR

( 44 )

TYP

DETAIL C

.0

( 0 )

DETAIL D

10

46.4

(1178)

49.4

(1255)

( 44 )

TYP

(TOP

ENTRY)

( 14 )

TYP

Figure 3 Top cable entry routing and installation order

FAULT BRACE

BYPASS INPUT

FAULT BRACE

RECTIFIER INPUT

FAULT BRACE

OUTPUT

FRONT VIEW

DC (POSITIVE)

DC (NEGATIVE)

GROUND (TOP ENTRY)

BYPASS NEUTRAL

BYPASS INPUT

RECTIFIER INPUT

FAULT BRACE

BYPASS INPUT

FAULT BRACE

RECTIFIER INPUT

FAULT BRACE

OUTPUT

OUTPUT

GROUND

(BOTTOM ENTRY)

OUTPUT NEUTRAL

Installation Drawings

OUTPUT CONDUIT

INPUT CONDUIT

BYPASS CONDUIT

DC CONDUIT

DC (POSITIVE)

DC (NEGATIVE)

BYPASS NEUTRAL

BYPASS INPUT

(PHASE C)

RECTIFIER INPUT

(PHASE C)

OUTPUT (PHASE C)

OUTPUT NEUTRAL

SIDE VIEW

Recommended order of installation for cables:

1. DC Power

2. Bypass Neutral

3. Bypass Input Power (Phases A-B-C)

4. Rectifier Input Power (Phases A-B-C)

5. Output Power (Phases A-B-C)

6. Output Neutral

7. Ground

The cables must be routed around the fault braces. This is to prevent the cables from coming in contact with other busbars.

11

Installation Drawings

Figure 4 Bottom cable entry routing and installation order

FAULT BRACE

BYPASS INPUT

FAULT BRACE

RECTIFIER INPUT

FAULT BRACE

OUTPUT

DC (POSITIVE)

DC (NEGATIVE)

GROUND (TOP ENTRY)

BYPASS NEUTRAL

FAULT BRACE

BYPASS INPUT

BYPASS INPUT

FAULT BRACE

RECTIFIER INPUT

RECTIFIER

INPUT

FAULT BRACE

OUTPUT

OUTPUT

GROUND (BOTTOM ENTRY)

OUTPUT NEUTRAL

FRONT VIEW

DC (POSITIVE)

DC (NEGATIVE)

BYPASS NEUTRAL

BYPASS INPUT

(PHASE C)

RECTIFIER INPUT

(PHASE C)

OUTPUT (PHASE C)

OUTPUT NEUTRAL

OUTPUT CONDUIT

INPUT CONDUIT

BYPASS CONDUIT

DC CONDUIT

SIDE VIEW

Recommended order of installation for cables:

1.) Output Neutral

2.) Output Power (Phases A-B-C)

3.) Rectifier Input Power (Phases A-B-C)

4.) Bypass Input Power (Phases A-B-C)

5.) Bypass Neutral

6.) DC Power

7.) Ground

The cables must be routed around the fault braces. This is to prevent the cables from coming in contact with other busbars.

12

Installation Drawings

Figure 5 Floor mount brackets—standard and optional layout

20.7

(525mm)

27.4"

(695mm)

27.4"

(695mm)

BOTTOM VIEW (Standard)

7.7"

(197mm)

4.7"

(120mm)

DETAIL AREA

FLOOR MOUNTS

36.8"

(935mm)

27.4"

(695mm)

KEEP BRACKETSATTACHED

WARNING

BOTTOM VIEW (Optional)

Brackets MUST remain attached to the frame until the unit is being placed in its final installed position. (The final installation will always require the unit to be bolted to another Liebert NXL product.) Failure to comply with these instructions could result in equipment damage and/or injury to personnel.

NOTES:

1. All dimensions are in inches (mm).

2. 24" minimum clearance above unit required.

3. Keep cabinet within 15 degrees of vertical.

4. Top and bottom cable entry available through removable access plates.

Remove, punch to suit conduit size and replace.

5. Unit bottom is structurally adequate for forklift handling.

6. Control wiring and power wiring must be run in separate conduits.

7. Aluminum and copper-clad aluminum cables are not recommended.

8. All wiring is to be in accordance with national and local electrical codes.

9. Optional bottom view can be used to bolt input / output cabinet to floor

and allow the UPS to be positioned. This option requires the

cabinet to be bolted to the floor.

10. Brackets can be removed after the ups has been bolted to the

input / output cabinet.

13

14

Installation Drawings

Ensuring The High Availability

0f Mission-Critical Data And Applications.

Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems.

Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 2008 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert is a registered trademark of Liebert Corporation.

All names referred to are trademarks or registered trademarks of their respective owners.

SL-25440_REV0_05-08

Emerson Network Power.

The global leader in enabling Business-Critical Continuity.

AC Power Embedded Computing

Connectivity Embedded Power

DC Power Monitoring

Technical Support / Service

Web Site www.liebert.com

Monitoring

800-222-5877 [email protected]

Outside the US: 614-841-6755

Single-Phase UPS

800-222-5877 [email protected]

Outside the US: 614-841-6755

Three-Phase UPS

800-543-2378 [email protected]

Environmental Systems

800-543-2778

Outside the United States

614-888-0246

Locations

United States

1050 Dearborn Drive

P.O. Box 29186

Columbus, OH 43229

Europe

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD) Italy

+39 049 9719 111

Fax: +39 049 5841 257

Asia

7/F, Dah Sing Financial Centre

108 Gloucester Road, Wanchai

Hong Kong

852 2572220

Fax: 852 28029250

Outside Plant

Power Switching & Controls

Precision Cooling

EmersonNetworkPower.com

Racks & Integrated Cabinets

Services

Surge Protection

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.

©2008 Emerson Electric Co.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals