HOLLYSYS PLC - LM MICRO SERIES LM3106-CDT

HOLLYSYS PLC - LM MICRO SERIES LM3106-CDT
LM3106-CDT CPU MODULE with 24 points I/O (14DI, 10DO), DC Powered
Local I/O
Digital I/O
Analog I/O
Maximum number of expansion modules
I/O Channel Status Indicator
14 In (24VDC), 10 Out (transistor)
None
4 modules
HOLLYSYS PLC - LM MICRO SERIES
Memory
User program memory
Storage type
Input storage zone
Output storage zone
Mid-variables (M) zone
Global (N) zone
Power-loss retain zone
60,000 words
Flash RAM
256 words
256 words
4000 words
12,000 words
3,000 words, 10 years
Terminal Block Cover
PLC Status Indicator,
Run, Stop, Com, Error
Sliding switch to control the Operational Mode,
RUN/STOP
Connection to Expansion Module
Analog Potentiometer Adjustment
RS-232 Communication Port
DIN Rail Snap-Clip
Holes for Backplane or Wall Mounting
Terminal Block (Spring-cage connection)
Instructions
Basic
Expandable
Boolean execution speed
Timer
Counter
Programming languages
Instructions
340
47
0.37Ɨs per instruction
Unlimited number of timers, 1ms ~ 49 days
Unlimited number of counters, 15 bits counting range
Compliance with IEC61131-3 international standards, supporting 6 programming
languages, LD, IL, FBD, SFC, ST, CFC
Enhanced Features
High-speed input counter
Mono-phase counters: 3 In (100KHz)
Bi-phase counters: 2 In (100KHz)
Pulse catch input
External interrupt input
Pulse output
Analog potentiometer adjustment
Real-time clock
Password protection
4
4
2 (20KHz)
2 potentiometer adjustment, value range: 0~255
Yes, 10 days power loss protection
Yes
Communications
Number of comm ports:
Communication protocol
Max. Baud Rate
1 RS-232 (non-isolated)
MODBUS RTU or G3 proprietary or FreePort protocol
Up to 38, 400 baud
Power Specifications
Input power supply
Line voltage-permissible range
Input current (max load)
Auxillary 24 VDC external output power
Voltage range
24V DC Power
21 ~ 27 VDC
1.3 A at 24 VDC
24V DC Power
22.8 ~ 25.2 VDC
Current limit
+24 VDC (for expansion bus)
+24 VDC (for external)
+5 VDC(for expansion bus)
Short-circuit protection
300 mA
300 mA
800 mA
400 mA, 24 VDC output
Input Specifications
Input type
Number of DC inputs
Input voltage
Voltage-permissible range
Logic 1 signal
Logic 0 signal
Optical isolation (galvanic)
Input delay
Isolation group
Sink / Source
14
24 VDC
0 ~ 30 VDC
15 ~ 30 VDC at 3 mA
0 ~ 5 VDC at 1 mA
500 VAC for 1 minute
< 0.6 ms (Rated input voltage)
2 groups (8 in/ 6 in)
Output Specifications
Basic Features
• Selectable operational mode control via sliding switch
(RUN / STOP)
• 2 adjustable analog potentiometer.
• Real-time clock.
• 60,000 words of program storage memory.
• 3,000 words of power-loss retain memory zone.
• Sync pulse establishing high-speed data transmission
between CPU and expansion modules.
• RS-232 communication/programming port with a maximum
baud rate of 38400bps
• 24VDC Input power providing 5VDC and 24VDC to all
modules.
• Auxiliary 24VDC external output power supply.
Transistor, Solid-state MOSFET
10
20.4 ~ 28.8 VDC
24 VDC
1A
1 mA
<4A
< 0.2 Ƅ
< 8 A for 100 ms, max.
No
500 VAC for 1 minute
Isolation group
Output delay (off to on / on to off)
2 groups ( 5 out / 5 out)
Normal output < 1ms, High-speed pulse output < 10—s
Physical Specifications
Size of module
Weight
Ambient operating environment
125 mm (L) × 90 mm (W) × 70 mm (H)
310 g
0° to 55° C, horizontal mounting
0° to 45° C, vertical mounting
Relative humidity
Storage environment
Mechanical shock
Sinusoidal vibration
5% ~ 95% non-condensing, no corrosive gas
-40° to +70° C, 25° to 55° C 95% humidity
15 G (147m/S2), 11 ms pulse, 6 shocks in each of 3 axes
0.30 mm peak-to-peak 10 to 57 Hz; 2 G panel mount, 1G DIN rail mount, 57 Hz to
150 Hz; 10 sweeps each axis, 1 octave/minute
IP20
CE approved (EMC and LVD)
24VDC Input
Power Supply
10x Digital Output (24VDC)
1V-
1V+
0.0
0.1
0.2
0.3
0.4
2V-
2V+
1M
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
LM3106-CDT : 14x DI 10x DO (Transistor)
Output type
Number of DC outputs
Permissible range
Rated value
Output current logic 1 signal
Output current logic 0 signal
Max. current per common/group
ON state resistance (contact)
Surge current
Overload protection
Optical isolation (galvanic)
Mechanical protection
Agency approvals
Key Specifications
• 14 digital inputs, (sink/source selectable) of which:
• 3 of the inputs can be use as 100 KHz high-speed
mono-phase counters or 2 of the inputs can be use as
100 KHz high-speed bi-phase counters.
• 4 of the input can be use as pulse catch inputs.
• 4 of the input can be use as interrupt inputs.
• 10 digital transistor output, of which:
• 2 of the output can be use as 20 KHz high-speed pulse
output (PTO or PWM).
• Expandable with a maximum of 4 additional I/O or
communication modules.
0.5
0.6
0.7
1.0
1.1
VI-
VI+
1.5
VO-
Terminal Points: 18+19
*
2M
1.0
1.1
1.2
14x Digital Input (24VDC)
1.3
1.4
VO+
Auxiliary
24VDC
External
Output Power
Supply
Top
Terminal
Block
Top Terminal Description
1VDO load drive supply -24VDC GND
terminal
1V+
DO load drive supply +24VDC terminal
Q0.0
Digital output #0
Q0.1
Digital output #1
Q0.2
Digital output #2
Q0.3
Digital output #3 / high-speed pulse
output
Q0.4
Digital output #4
2VDO load drive supply -24VDC GND
terminal
2V+
DO load drive supply +24VDC terminal
Bottom
Terminal
Block
1M
Q0.5
Q0.6
Digital output #5
Digital output #6
*
2M
Q0.7
Digital output #7
I1.0
Q1.0
Digital output #8
I1.1
Q1.1
Digital output #9 / high-speed pulse
output
EARTH GROUND
I1.2
Digital input #5
Digital input #6 / high-speed input counter / external
interrupt input / pulse catch input
Digital Input #7 / external interrupt input / pulse catch
input
Not in used
DI common terminal of group #2 (connect to 24VDC +/terminal corresponding to source/sink DI)
Digital Input #8 / external interrupt input / pulse catch
input
Digital Input #9 / external interrupt input / pulse catch
input
Digital Input #10
I1.3
Digital Input #11
VIVI+
-24VDC power supply GND terminal
+24VDC power supply terminal
I1.4
I1.5
VOVO+
Digital Input #12
Digital Input #13
Auxiliary -24VDC GND terminal
Auxiliary +24VDC power supply terminal
I0.0
I0.1
I0.2
I0.3
I0.4
I0.5
I0.6
I0.7
Bottom Terminal Description
DI common terminal of group #1 (connect to 24VDC +/terminal corresponding to source/sink DI)
Digital input #0 / high-speed input counter
Digital input #1 / high-speed input counter control
Digital input #2 / high-speed input counter
Digital input #3 / high-speed input counter control
Digital input #4
Was this manual useful for you? yes no