HygroFlex transmitter version 4: instruction manual
Document title
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 1 of 61
HygroFlex
Humidity Temperature Transmitter
Instruction Manual
Version 4
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 2 of 61
Document title
Contents
Re-attaching the ribbon cable (cover with optional display and keypad) .........................21
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 3 of 61
Document title
About the version number:
This manual is valid for all instruments with firmware version 4.x, where 4.x can be 4.0, 4.1, etc.
(see Function Menu, SYS STATUS). Changes to the last digit of the version number reflect minor firmware changes that do not affect the manner in which the instrument should be operated.
Note: Both instrument configuration and adjustment of the HygroClip probes require a PC with the optional ROTRONIC HW4 software version 1.2.2 or higher. Instructions for using the software are not included in this manual. These instructions are shipped separately on the software CD ROM.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 4 of 61
Document title
1 Overview
The HygroFlex are 3-wire humidity temperature transmitters available with a wide variety of probes for use in many different industrial and scientific applications. The HygroFlex series uses a microprocessor based design to achieve unparalleled accuracy, reliability and versatility.
The HygroFlex is available in 3 different models:
HygroFlex 1: Basic industrial transmitter with analog outputs
Relative humidity and temperature
-
Compatible with any ROTRONIC HygroClip digital probe
1)
-
Relative humidity and temperature analog outputs
-
Test connector for communication with the HygroPalm indicator
2)
-
Software-based calibration (HygroClip probes only)
-
Internal service connector (RS232) for configuration with PC (unit system, output range)
-
Two linear analog outputs, signal type (mA, V) configurable by means of jumpers
-
Optional LC display and keypad
4)
3)
1) ROTRONIC analog probes are also accepted with some restrictions
2) Allows the HygroPalm to read the transmitter or to calibrate a digital probe
3) 0..1V, 0..5V, 0..10V, 0..20 mA, 4..20 mA
4) Allows direct calibration of digital probes by the transmitter and direct access to other functions
HygroFlex 2: Networkable industrial transmitter with digital outputs
Relative humidity, dew point (or other) and temperature
-
Compatible with any ROTRONIC HygroClip digital probe
1)
-
Optional analog input for second probe
2)
-
Relative humidity, temperature, dew point, wet bulb, mixing ratio, enthalpy, etc
3)
-
Test connector for communication with the HygroPalm indicator
4)
-
Software-based calibration (HygroClip probes only)
-
RS232 and RS485 serial ports or Ethernet (TCP/IP) and RS-485 ports
-
Optional LC display and keypad
6)
5)
1) ROTRONIC analog probes are also accepted with some restrictions
2) Pressure probe or ROTRONIC HygroClip digital probe – some restrictions apply
3) Uses either a fixed barometric pressure value or the measurements from an analog pressure probe for those parameters that require pressure as a computational input. The fixed pressure value can be changed with the optional HW4 software.
4) Allows the HygroPalm to read the transmitter or to calibrate a digital probe
5) The optional HW4 software offers a reliable networking solution and the possibility of exporting live data to practically any OPC client applications.
6) Allows direct calibration of digital probes by the transmitter and direct access to other functions
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 5 of 61
Document title
HygroFlex 3: Networkable industrial transmitter with digital and analog outputs
Relative humidity, dew point (or other) and temperature
-
Compatible with any ROTRONIC HygroClip digital probe
1)
-
Optional input for second probe
2)
-
Relative humidity, temperature, dew point, wet bulb, mixing ratio, enthalpy, etc
3)
-
Test connector for communication with the HygroPalm indicator
4)
-
Software-based calibration (HygroClip probes only)
-
RS232 and RS485 serial ports or Ethernet (TCP/IP) and RS-485 ports
5)
-
Three linear analog outputs, signal type (mA, V) configurable by means of jumpers
6)
-
Optional LC display and keypad
7)
1) ROTRONIC analog probes are also accepted with some restrictions
2) Pressure probe or ROTRONIC HygroClip digital probe – some restrictions apply
3) Uses either a fixed barometric pressure value or the measurements from an analog pressure probe for those parameters that require pressure as a computational input. The fixed pressure value can be changed with the optional HW4 software.
4) Allows the HygroPalm to read the transmitter or to calibrate a digital probe. IMPORTANT: there is no test connector on the HygroFlex 3 when it is equipped with the optional Ethernet (TCP/IP) port.
5) The optional HW4 software offers a reliable networking solution and the possibility of exporting live data to practically any OPC client applications
6) 0..1V, 0..5V, 0..10V, 0..20 mA, 4..20 mA - corresponding to relative humidity, temperature and computed parameter (or relative humidity of second probe)
7) Allows direct calibration of digital probes by the transmitter and direct access to other functions
HygroFlex 1 HygroFlex 2 HygroFlex 3
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Document title
2 General description
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 6 of 61
2.1 Power requirements
The HygroFlex is available with a choice of two basic internal power modules:
- Standard power module for operation with 12 to 35 VDC (maximum 300 mA) or with 12 to 24 VAC.
- Optional power module for operation with voltages within the range of 90 to 264 VAC (50/60 Hz).
Starting with PCB number 66.0738.0502 all models are equipped with a SMD power fuse
(250 VAC 1 A) – see page 19.
2.2 Probes and probe Inputs
Model
number of probe inputs probe types (see below) number of digital input channels number of analog input channels analog input A/D resolution
HygroFlex 1
1
ROTRONIC Digital
ROTRONIC Analog
1
2
10-bit
HygroFlex 2 HygroFlex 3
1 (standard) or 2 (optional)
ROTRONIC Digital
ROTRONIC Analog
Third-Party Analog
1 (input 1) + 1 (input 2 - optional)
2 (input 1) + 1 (input 2 - optional)
10-bit
Unless otherwise specified when ordering, all probe inputs are factory programmed to accept a HygroClip digital probe and the voltage powering the probe is set to 5 VDC.
Prior to using any analog probe, the corresponding input should be re-programmed. This can be done with the
HW4 software after connecting the internal service connector to a PC COM port (see separate software manual).
IMPORTANT:
HygroClip EX probes require 15 VDC power supply. These probes, as well as any third party analog probe requiring a supply voltage of more than 5 VDC, can be supplied with 15 VDC by moving the jumper B20 to B19 – see page 12: selection of the probe supply voltage.
A matching adapter cable is required to connect analog probes.
2.2.1 HygroClip digital probes
The HygroFlex is primarily designed for use with the ROTRONIC HygroClip digital humidity temperature probes. These probes permit to take full advantage of all the features and functions of the HygroFlex such as the software based calibration.
The ROTRONIC HygroClip digital probes are highly accurate and are calibrated entirely by means of software (no adjustment potentiometers). Because calibration and other data are stored in the probe non-volatile memory, the probes are fully interchangeable. When a probe requires calibration or has to be repaired, it can be replaced with another probe in a few seconds. The ROTRONIC
HygroClip digital probes are available in different configurations so as to meet the requirements of each application:
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Document title
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 7 of 61
HygroClip IW for surface mount (area monitoring) max. 85
°C (185°F) – wire mesh filter
observe temperature limits of transmitter electronics
HygroClip IC-1 (100mm) / IC-3 (250mm) for through-wall installation max. 200
°C (392°F) - wire mesh filter
HygroClip IM-1 (120mm) / IM-3 (270mm) for through-wall installation in high humidity applications max. 200
°C (392°F) - wire mesh filter
HygroClip IE-1 (G ½”) / IE-2 (NPT ½”) for compressed air (max. 50 bar / 725 PSI) max. 85
°C (185°F) – sintered steel filter
to avoid errors, temperature should be the same on both sides of the mounting wall
HygroClip IC-05 for measurement in tight spaces max. 100
°C (212°F)
Probe Extension Cable AC1616/xxx
with built-in signal booster
xxx = 002 to 200 from 2 to 200 m (about 6.5ft to 656ft) max. temperature 85
°C (185°F)
HygroClip ID-EX-xxx (intrinsically safe)
for through-wall installation
xxx = 002 to 100 from 2 to 100 m cable length (about 6.5ft to 328ft) max. temperature at sensors: 200
°C (392°F) probe length 250 mm - sintered steel filter
HygroClip IW-EX-xxx (intrinsically safe) for surface mount (area monitoring) xxx = 002 to 100 from 2 to 100 m cable length (about 6.5ft to 328ft) max. temperature 40°C (104°F) probe length 150mm sintered steel filter
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Document title
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 8 of 61
ZB1 Zenner Barrier for ID-EX and IW-EX
AC1617xxx Connecting Cable for ZB1
with built-in signal booster
xxx = 002 to 100
2 to 100m (about 6.5ft to 328ft)
Depending on the model and options, the HygroFlex transmitters can be used with one or two analog probes. Both the scale and unit of the analog input signals can be defined by software. For example, an analog pressure probe may used to provide the local value of barometric pressure for the computation of parameters such as the wet bulb temperature, mixing ratio or enthalpy.
Use of analog probes is subject to the following restrictions and limitations: a) ROTRONIC analog humidity-temperature probes with the standard temperature output signal of
– 0.5…2.0 V = -50…200
°C: because the HygroFlex cannot read a negative voltage signal, temperature measurement is generally limited to values above freezing. b) Third-party analog probes: single channel probes (one signal), output signal within the range of
0 to 2.5 VDC, supply voltage: 15 VDC or less, maximum current consumption: 10 mA. (see page 16 – selection of the probe supply voltage). c) Resolution is limited by the 10-bit A/D converter used for the analog inputs. This converter provides a theoretical maximum of 1024 counts for an input voltage span of 2.5 VDC. In theory, this gives a resolution of 2.5 / 1024 = 0.00244 V. In practice, it is not possible to get 100% of the counts from an A/D converter and the actual resolution should be about 0.0027 V (typical). For example, if a probe with a temperature signal of 0..1 V = 0…100
°C is being used, the signal resolution will be about 100 x 1 x 0.0027 = 0.27
°C
2.3 Analog outputs (HygroFlex 1 and 3)
Model HygroFlex 1
analog outputs
- relative humidity
- temperature
HygroFlex 3
Any three of:
- relative humidity
- temperature
- computed parameter
- user defined calculation see note below
1)
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 9 of 61
Document title
Model
output signals configurable with jumpers
D/A output resolution options
2)
0…1 V
0…5 V
0…10 V
0…20 mA
4…20 mA
HygroFlex 1
humidity: 12-bit temperature: 16-bit floating analog current outputs
(galvanic separation)
HygroFlex 3
0…1 V
0…5 V
0…10 V
0…20 mA
4…20 mA
Out 1: 12-bit
Out 2: 16-bit
Out 3: 12-bit floating analog current outputs
16-bit D/A resolution for Out1 allows
0.1 resolution with a span of more than 200 units.
1)
Any of the 3 analog outputs of the HygroFlex 3 can be set to correspond to humidity [probe
1 or 2] or temperature [probe 1 or 2] or calculated parameter [probe 1 or 2] or user defined calculation or optional analog probe signal (such as pressure). The HygroFlex is set at the factory as specified when ordering. These settings can be changed at any time with the optional HW4 software.
2)
The output signals are set at the factory according to the type and range specified when ordering. A label located on the transmitter housing shows the type of output signal for each unit.
The analog output signals are linear and are consistent with the requirements of most data/signal processing instrumentation (panel meter, controller, computer card, etc.).
2.4 Optional display and keypad
The LC display shows which probe input is being displayed (small indicator on top of the display) and up to 2 parameters measured by the probe, with the associated engineering unit. When relevant, the message line provides additional information.
Probe Input Indicator
(1-2) from left to right
Humidity and Temperature
Calculated Value and Temperature
Calculated Value and Humidity
Parameter or
Trend Indicators
S S
8.8:8.8
8.8:8.8
Engineering
Units
Message Line
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Document title
Keypad
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 10 of 61
MENU : Press this key to activate the function menu. The different menu items appear on the LCD message line. Press this key again to exit the menu
UP / DOWN: Press one of these keys to select the probe input for the display and functions. When the function menu is active, use these keys to navigate the menu, make a selection or to change a number on the display.
ENTER: When the menu is active, press this key to confirm a selection.
To prevent unauthorized or accidental changes, access from the keypad to the calibration functions can be blocked out when configuring the HygroFlex with the HW4 software. This also prevents access to the calibration functions with the
HygroPalm calibrator.
2.5 Serial interface (HygroFlex 2 and 3)
Both the HygroFlex 2 and 3 have an external receptacle (located on the connector plate) that provides both a RS-232 and a RS-485 interface. A special connector matching this receptacle is shipped with the HygroFlex.
Serial interface settings
The HygroFlex transmitter is compatible with the ROTRONIC HW4 software (version 1.2.2 or higher) and backward compatible with the ROTRONIC HW3 software. Each software uses a different communications protocol and different settings regarding the parity, number of data bits and number of stop bits. When interrogated, the HygroFlex automatically recognizes which software and which protocol is being used. This allows using the HygroFlex with either HW3 or
HW4 without requiring a manual configuration of the HygroFlex serial settings.
When used with HW4, the HygroFlex automatically sets its serial interface as follows: none
Data bits
Stop bits
: 8
: 1
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 11 of 61
Document title
When used with HW3, the HygroFlex automatically sets its serial interface as follows:
Parity :
Data bits : 7
Stop bits : 1
Note: the HygroFlex will automatically set its serial interface to the above settings when interrogated by a third-party software that uses the same ASCII commands as HW3 to request data. On models with the optional Ethernet interface, the internal module must be re-configured as indicated in document IN-E-TCPIP-Conf_10.doc (also available in PDF format).
IMPORTANT
: The HygroFlex can be configured by the user with a Baud rate of 57600. The factory default Baud rate of 19200 is compatible with both HW3 and HW4. The Baud rate of 57600 is compatible only with HW4.
RS-232 interface
This interface is used to read measurement data, adjust any HygroClip probe connected to the
HygroFlex and to configure the HygroFlex. The RS-232 allows direct connection of the HygroFlex to the COM port of a PC (up to 150 m / 490 ft separation)
The HW4 software (version 1.2.2 or higher) should be installed on the PC.
RS-485 interface
This interface is used to connect together a number of HygroFlex transmitters (as well as other
ROTRONIC devices) so as to form a RS-485 multi-drop. This is useful when the number of PC ports is limited and provides savings on cabling costs. The RS-485 interface has the same functionality as the RS-232 interface (measurement data, adjustment of HygroClip probes and device configuration).
In a RS-485 multi-drop, the master is automatically the device that is connected to a COM port,
USB port or network port (Ethernet) of the PC. Any ROTRONIC device that is equipped with both a
RS-232, USB or Ethernet interface and a RS-485 interface can be used as the master. The other devices in the RS-485 multi-drop are slaves. Any HygroFlex 2 or HygroFlex 3 transmitter can be used either as a slave or a master, without special configuration other than giving a unique RS-485 address to each device and setting each device to use the same Baud rate.
2.6 Optional Ethernet (TCP/IP) interface (HygroFlex 2 and 3)
As an option, both the HygroFlex 2 and HygroFlex 3 can be ordered with the combination of an
Ethernet (TCP/IP) interface and a RS-485 serial interface. The HW4 software accepts connection to the PC by means of an Ethernet network.
Note
: when equipped with this option, the HygroFlex 3 does not have a Test connector.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 12 of 61
Document title
3 Optional configuration and communication software
Depending on the model of HygroFlex, the ROTRONIC HW4 software (version 1.2.2 or higher) offers additional functionality such as:
- Networking (unlimited number of masters, up to 64 units per multi-drop)
- Instrument
- Adjustment of the ROTRONIC HygroClip digital probes
- Data logging to a PC disk file
- Graphic functions (both on and off-line)
- Alarm functions (on-screen display, reports, notification by e-mail, etc.)
See also Accessories for the HygroFlex – HCA (HygroClip Alarm)
HW4 is compatible with Windows XP, NT4 with SP6a or higher. For more details see separate instruction manual provided with the software.
The HygroFlex is backward compatible with the ROTRONIC HW3 software (Windows 98 or NT)
4 How to configure the HygroFlex
The HygroFlex is configured by the factory as specified when the instrument was ordered. The configuration can be modified by the user and this requires connecting the HygroFlex to a PC with the ROTRONIC HW4 software installed (version 1.2.2 or higher).
Depending on the model of HygroFlex, the following can be configured by the user with Device
Manager in HW4 (where relevant, the factory default is indicated in bold):
- Device name
- RS-485 address [0]
- Device write protection with password [disabled]
- Fixed barometric pressure value used in some psychrometric calculations [1013.25 hPa]
- Dew or frost point calculation below freezing [frost point]
- Language and unit system
- Probe input type (HygroClip probe, analog pressure probe, other analog probe)
- Input name
- Calculated parameter (HygroClip probe only)
- Barometric pressure (fixed value or read from an input) [fixed]
- Alarm threshold (low and high) for humidity, temperature, calculated parameter or other.
See also Appendix 9 – Accessories for the HygroFlex – HCA (HygroClip Alarm).
- Parameter or custom calculation associated with each analog output and output scale
- Custom calculation (example: difference between two parameters such as dew point)
- Optional display configuration (resolution, trend indicators, parameters to be displayed)
- Keypad: restricted menu access [not restricted]
- Baud rate (serial interface) [19200]
For more details see separate instruction manual provided with the software.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 13 of 61
Document title
4.1 Internal service connector (HygroFlex configuration)
All HygroFlex models have an internal RS-232 service connector (MTA) located on the main PCB
(see PCB connections). Cable AC1623 is required to connect the HygroFlex MTA connector to
COM port of a PC.
Use of the MTA service connector is limited to configuring the instrument (unit system, output range, display, etc.). Both the HygroFlex 2 and HygroFlex 3 can also be configured via one of the external digital ports.
Instrument configuration requires a PC with the HW4 software installed. Instructions for configuring the HygroFlex are provided in the software manual.
4.2 Resolution of the analog signals (HygroFlex 3)
The HW4 software allows defining the range of the analog output signals of the HygroFlex 3. When selecting a range, it is important to consider the fact that the resolution of the analog output signal depends on the span of the selected range.
The HygroFlex 3 uses two 12-bit D/A converters to generate the analog output signals for relative humidity (output #1) and for the computed parameter (output #3). In theory, a 12-bit D/A converter can distinguish between 4,096 values (or counts). This number of counts, together with the span of the signal (%RH, °C, etc.), determines the resolution of the analog output signal.
Because of the tolerance in the analog components associated with the D/A converter, the number of counts that are effectively used tends to be less than the theoretical maximum. Typically, only about 90% of the counts (3,680) may be effectively used.
In addition, the analog output signal may be a partial range. For example, 4…20 mA is a partial range of 0…20 mA. With a 4…20 mA output signal, the number of useful D/A counts is further reduced by 20% (1 - 16/20) and only 72% of the count (2,950 counts) may be effectively available.
Taking the example of a 4…20 mA output, the span of the analog signal should not exceed 140 to
150 units (for example –50 to 100°C dew point) to maintain a resolution of 0.1 unit. With analog signal such as 0…5V or 0…20 mA, a maximum span of 180 units could be used.
The above examples are based on a resolution of 0.05 units as this prevents the analog output signal from bouncing around by ± 0.1 units.
For the temperature analog output signal, the HygroFlex 3 uses a 16-bit D/A converter. This is more than sufficient to offer 0.1 resolution for any temperature range and any type of analog signal available with the HygroFlex 3.
Note: an optional 16-bit D/A converter is available for analog output 1. In that case the computed parameter is assigned to output 1 and relative humidity to output 3.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 14 of 61
Document title
4.3 Baud rate compatibility requirements
Depending on the model, devices from ROTRONIC use one of the following Baud rates as the factory default:
• 57600 bps: HygroLog NT data logger and docking stations
• 19200 bps: HygroPalm and HygroLab indicators, HygroFlex and M33 transmitters, HygroClip
Alarm programmable alarm card, HygroClip DI interface, HygroStat MB Thermo-Hygrostat
The factory default Baud rate of the HygroFlex is compatible both with both the ROTRONIC HW4 and HW3 software and is the recommended Baud rate for the HygroFlex.
IMPORTANT:
• All devices connected to a RS-485 multi-drop network (master and slaves) must use the same Baud rate
• Models with the optional Ethernet (TCP/IP) interface: after using HW4 – Device Manager to change the Baud rate, you should also change the configuration of the internal Ethernet module to the new Baud rate (see separate HW4 manual).
Devices and internal Ethernet modules with mismatched Baud rate will not communicate together.
• The Baud rate configuration of a ROTRONIC device can be changed with the Device
Manager
function (Digital Interface tab) available from within the HW4 software.
• The Baud rate of a Digi Module can be changed only from the module web interface. See separate document IN-E-TCPIP-Conf_10.doc (also available in PDF format).
4.4 Ethernet local area network
ROTRONIC devices with an Ethernet (TCP/IP) interface presently use an internal module manufactured by Digi International (Digi Connect ME for a wired connection, Digi Connect WI-ME for a wireless connection). Both types of module feature a web interface that is used to configure the module.
IMPORTANT:
The TCP/IP settings of models with an Ethernet (TCP/IP) interface should be configured to be compatible with the local area network. Detailed instructions are provided separately in document IN-E-TCPIP-Conf_10.doc (also available in PDF format).
Models with an Ethernet (TCP/IP) interface are shipped with a Device Configuration Certificate that provides information about the factory configuration settings of both the Ethernet module and device. See example below:
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 15 of 61
Document title
Setting
DHCP or Static Address
IP Address
Subnet Mask
Default Gateway
TCP Port
MAC Address
Firmware Release (device)
User Name (web interface)
Password (web interface)
Serial Port Configuration Profile
Basic Serial Settings
Parity
Value
Static
192.168.1.1
255.255.255.0
192.168.1.0
2101
00:40:9D:28:2D:2A
1.4 rotronic wlan
TCP Sockets
57600
8
None
1
None
4.5 RS-485 multi-drop network (HygroFlex 2 and 3)
Both the HygroFlex 2 and HygroFlex 3 feature a RS-485 connector. When the number of available
PC ports is limited, this connector can be used to connect together up to 64 HygroFlex (or other devices) in a multi-dropped arrangement. In principle, an unlimited number of such networks can be monitored with the HW4 software, but each RS-485 multi-drop network is limited to 64 devices.
The HygroFlex can be used either as a slave or a master, without special configuration. The master is automatically the device that is directly connected to the PC or LAN by means of a RS-232 port or TCP/IP port.
RS-485 Address
: the RS-485 address is used to identify the individual devices that are connected to a RS-485 multi-drop and must be unique to each device. This address is part of the HygroFlex communications protocol. The factory default for the RS-485 address is 00. In general, this address should not be changed manually (see note below). As far as HW4 is concerned, all masters can share the same RS-485 address. When the HW4 command “Search for RS-485 slaves” is being used, HW4 automatically changes from 00 to 01 the RS-485 address of any master that has slaves attached. As a result, all masters end up with the same RS-485 network address (01). In addition,
HW4 automatically changes the RS-485 address of the slaves in each multi-drop from 00 (factory default) to a unique address ranging from 02 to 64. The same address range (02 to 64) is used again when there is more than one multi-drop RS485 network.
Notes:
- We recommend using HW4 to give each HygroFlex a unique name for easier identification.
- In the situation where an RS-485 network is to be monitored by software other than HW4, you will have to use HW4 to give each device a unique RS-485 address prior to connecting to the network.
- If you change an instrument from master to slave, be sure to change the RS address of the instrument to 00 before establishing the RS-485 connection. Not doing so may prevent HW4 from detecting the instrument. After detecting the instrument, HW4 will automatically change the RS address to 02 or higher. Please note that HW4 may eventually change the address of any master with address 00.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 16 of 61
Document title
- All devices within a multi-drop should use the same Baud rate. See Baud rate compatibility requirements.
- Models with Ethernet (TCP/IP) interface: please note that the Baud rate of the HygroFlex and the Baud rate of the internal Ethernet module should be set to the same value.
4.6 Selection of the probe supply voltage (main PCB)
Starting with PCB number 66.0738.0602, the default factory setting for the probe supply voltage is 5 VDC.
IMPORTANT
: HygroClip EX probes require 15 VDC power supply. A third party analog probe may also require a supply voltage of more than 5 VDC (HygroFlex
2 and HygroFlex 3). Moving jumper B20 to B19 supplies all probes with 15 VDC
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 17 of 61
Document title
4.7 Analog signal configuration (HygroFlex 1 and 3 main PCB)
On the HygroFlex 1 and HygroFlex 3, the type of analog output signal can be selected by means of jumpers on the PCB:
B31
B32
B33
Res.
B34
HygroFlex 1: to configure the temperature range and unit, use this 3-pin service connector and connect to a PC with cable # AC1623.
HygroFlex 3: the transmitter can be configured by connecting the RS232 / RS485 output to a
PC.
For both transmitters, configuration requires the
HW4 software installed on the PC.
RS232 / RS485
Signal Jumpers to be closed
0…1 V B2, B3, B12, B13, B22, B23, B31
0…5 V B2, B4, B12, B14, B22, B24, B32
0…10 V B2, B5, B12, B15, B22, B25, B31, B32
0…20mA B1, B3, B11, B13, B21, B23, B33, B34
4…20mA B1, B3, B11, B13, B21, B23, B31, B33, B34
The scale of each analog output can be changed with the HW4 software (see separate instructions). On the HygroFlex 3, the parameter corresponding to the third output can also be changed by software (see software instructions).
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 18 of 61
Document title
5 Mechanical installation
Each HygroFlex transmitter is shipped in an individual box, separately from the probe. The shipping box has a label with the following information: instrument type, main specifications and serial number. An identical label is located inside of the transmitter enclosure.
5.1 Installation of the transmitter enclosure
Note: see appendix 8 for the optional metal enclosure
The HygroFlex is comprised of 5 parts: mounting bracket (1), electronics housing (2), main circuit board (3), connector plate (4) and front cover with or without optional display and keypad (5).
2
V-shaped slot
3
4
5
1
After unpacking the
HygroFlex, separate the mounting bracket from the back of the housing.
To attach the transmitter to a mounting surface:
1) Attach the wall plate in the position shown above to an appropriate surface using 4 screws.
2) Slide the electronics housing down on the wall plate to the mechanical stop
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 19 of 61
Document title
5.2 Front cover removal
The front cover is held in place by 4 small tabs molded into the electronics housing. To remove the cover, insert a screwdriver in the V-shaped slot on top of cover and press lightly to unlock prior to pulling the cover away from the electronics housing.
Note:
If the cover has the optional display and keypad, it is connected to the main circuit board by a ribbon cable. When removing the front cover, this cable can easily become detached. This is nothing to worry about since the cable can be just as easily re-attached.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 20 of 61
Document title
5.3 Front cover installation
To put the front cover back on the HygroFlex, proceed as shown below:
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 21 of 61
Document title
5.4 Re-attaching the ribbon cable (cover with optional display and
keypad)
Zero-insertion-force connectors are used for the ribbon cable that connects the cover and the main printed circuit board.
Ribbon cable
To unlock: grab both sides of outer frame up and pull up outer frame
(can be pulled out)
Zero-insertion-force connector
To lock: push down outer frame printed circuit board
To re-attach the ribbon cable, unlock the connector (see above). Each end of the ribbon cable has a contact side and a blue insulated side. When inserting the cable in the connector, position the contact side of the flat ribbon cable as indicated in picture 2. Slide the cable back into the connector as indicated in picture 1. Lock the connector in place and verify the cable is firmly held in place (picture 2).
Picture 1 Picture 2
Wrong!
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 22 of 61
Document title
Note: disconnecting and reconnecting the ribbon cable while the transmitter is powered may cause the display to remain blank. In that case, un-power and power again the transmitter.
5.5 Probe installation guidelines
Connect the probe to probe input 1 (main probe input). Except for probe model IW (area monitoring); probes are connected to the HygroFlex by means of a cable (attached to the probe).
Do not remove the dust filter or slotted cap from the probe. Both sensors can easily be damaged when not protected. For best results, please observe the following guidelines:
- Install the probe at a location where humidity, temperature and pressure conditions are representative of the environment or process to be measured. Avoid the following: (a) Close proximity of the probe to a heating element, a cooling coil, a cold or hot wall, direct exposure to sun rays, etc. (b) Close proximity of the probe to a steam injector, humidifier, direct exposure to precipitation, etc. (c) Unstable pressure conditions resulting from excessive air turbulence.
- If possible, choose a location that provides good air movement at the probe: air velocity of at least 1 meter/second (200 ft/ minute) facilitates adaptation of the probe to changing temperature.
- When installing the probe through a wall, immerse as much of the probe as possible in the environment to be measured.
OK
9 to 9.5" immersion
Small Diameter Duct
NG
Short Probe
NG
NG
OK
Position the probe so as to prevent the accumulation of condensation water at the level of the sensor leads. Install the probe so that the probe tip is looking downward. If this is not possible, install the probe horizontally.
Depending on the probe model, a probe holder (mounting flange with a compression fitting) can facilitate installation through a wall.
Future maintenance can be made easier by providing next to the probe a calibration access orifice.
During maintenance, this permits the insertion of a reference probe (calibrator).The calibration access orifice should have the same size as the orifice used to install the probe and can be equipped with a probe holder.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 23 of 61
Document title
6 Electrical installation
Before making the electrical connections, be sure to correctly identify each connector and terminal.
Applying power to any of the input or output terminals can severely damage the transmitter.
6.1 Main PCB connectors
All terminal blocks on the main PCB are of the plug-in type so that the connector plate can be pulled out if required.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
1- Main Probe Input (J2)
1 : Temperature (analog+)
2 : Humidity (analog +)
3 : GND
4 : Digital Input Output
5: +5 or +15 VDC ± 0.5 VDC
2 - Test (J4)
(for HygroPalm Calibrator)
1 : GND
2 : Digital Input Output
3 - Optional 2 nd
Probe Input (J3)
(except HygroFlex 1)
1 : Analog Input Signal (+)
2: GND
3 : Digital Input Output
4 : +5 or 15 VDC ± 0.5 VDC
4 - RS232/RS485 (J5)
(except HygroFlex 1)
1 : RI – (485)
2 : RI + (485)
3 : GND
4 : RX
5 : TX
5 - Analog Outputs (K2/ TB2)
(except HygroFlex 2)
1 : Out 1 (+)
2 : Out 2 (+)
3 : Out 3 (+) – HygroFlex 3 only
4 : GND (common)
6 - Power (K1/TB1)
(check label inside enclosure)
1 : AC N or DC –
2 : AC Ph or DC +
3 : GND (see note below)
MTA :
service / configuration connector connect to PC with cable AC1623
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 24 of 61
Document title
6.2 Optional Ethernet module (HygroFlex 2 and 3)
Optional Ethernet Module
6.3 Mains fuse
Starting with PCB number 66.0738.0602, all models are equipped with a SMD fuse (250 VAC / 1 A T) soldered on the main PCB.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 25 of 61
Document title
6.4 PCB number
The PCB number is located next to the power terminal block.
6.5 Connector plate
Standard connector plate (all models)
Note:
The drawing below shows the maximum number of connectors and cable grips. The actual number of connector depends on the model number (HygroFlex 1, 2 or 3).
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 26 of 61
Document title
Connector plate for models with the optional Ethernet interface
HygroFlex 2:
HygroFlex 3:
Grommet for Ethernet cable
Grommet for Ethernet cable
Note: the HygroFlex 3 with the optional Ethernet interface does not have an external test connector.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 27 of 61
Document title
6.6 Connector plate connectors - pin-out diagrams
Note: the contact side of the female connector is the same as the solder side of the matching male connector.
Probe 1 – TUCHEL T7 (7-pin female shown from contact side)
Pin # Function
E GND
1 Temperature – analog (+)
5
6
+ 5 or +15 VDC ±0.5 VDC, jumper-selectable, B19 / B20)
Humidity – analog (+)
Pin# on PCB connector J2
3
1
4
5
2
Test Connector (2-pin female shown from contact side)
Pin # Function Pin# on PCB connector J4
2
2 GND 1
Probe 2 (5-pin female shown from contact side) – optional
Pin # Function
2 + 5 or +15 VDC ±0.5 VDC, jumper-selectable, B19 / B20)
3 GND
Pin# on PCB connector J3
4
2
3
1
RS232 / RS485 (5-pin female shown from contact side)
Pin # Function
1 TXD
2 RXD
3 GND
Pin# on PCB connector J5
5
4
3
2
1
Analog Outputs (4-pin female shown from contact side) – optional
Pin #
1
Function
Output 1 (+)
2
3
Output 2 (+)
Output 3 (+)
4 GND
Pin# on PCB connector
1
2
3
4
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 28 of 61
Document title
RS232 connection (DB9 female connecting to a PC or terminal server)
Viewed opposite from solder side
Pin # Function
2 RX
3 TX
5 GND
6.7 Electrical diagrams (analog outputs)
Before making the electrical connections, be sure to correctly identify each connector and terminal.
Applying power to any of the input or output terminals can severely damage the transmitter.
12 to 35 VDC or 12 to 24 VAC supply voltage and voltage output signals
TB1 TB2
~
2
1
1
2
3
R
L
1)
R
L
1)
R
L
1)
1) minimum load:
1000 ohm
3
B18
4
Solder pad B18: see page 31
TB1 (2) 12…35 VDC (+) or 12…24 VAC neutral TB2 (1) Relative humidity (+)
TB1 (1) 12…35 VDC (-) or 12…24 VAC Ph TB2 (2) Temperature (+)
TB1 (3) Ground TB2 (3)
TB2 (4)
Calculated Parameter (+)
Common (-)
If so desired, close solder pad B18 (next to TB1) to connect signal ground and terminal 3 of the power terminal block TB1.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 29 of 61
Document title
~
90…264 VAC with optional power module and current output signals
TB1 TB2
2
1
2
3
1
3
B18
4
R
L
1)
R
L
1)
R
L
1)
1) maximum load :
500 ohm
wiring included.
Solder pad B18: see page 31
TB1 (2) 90…264 VAC Neutral TB2 (1) Relative humidity (+)
TB1 (1) Phase TB2 (2) Temperature (+)
TB1 (3) Ground TB2 (3)
TB2 (4)
Calculated Parameter (+)
Common (-)
If so desired, close solder pad B18 (next to TB1) to connect signal ground and terminal 3 of the power terminal block TB1.
Floating Current Outputs (option)
R
L
1)
1) maximum load : 500 ohm, wiring included
B18
Solder pad B18: see page 24
R
L
1)
R
L
1)
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 30 of 61
Document title
6.8 Cable grips
Cable grips (5 and 6) provide effective sealing only with cables having the proper outside diameter.
Preferably, use a cable with an outside diameter of 6 to 7 mm (0.236 to 0.275”) and with 18AWG wires. Seal any unused cable grip. On request, the connector plate is available with 1/2” conduit
adapters instead of cable grips.
We strongly recommend running the analog output signal cable separately from the power cable.
6.9 Grommet for the Ethernet cable (HygroFlex 2 and 3 option)
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 31 of 61
Document title
6.10 Grounding
Note that all input / output signal grounds - analog and digital - are tied together.
Ground the HygroFlex, especially if the electronics will be subjected to a low humidity environment
(35 %RH or less).
Starting with PCB version 66.0738.0402, there is no connection between signal ground and terminal 3 of the power terminal block
(TB1). If so desired, a connection can be established by closing solder pad B18, next to TB1. On previous versions of the PCB, the signal ground and terminal 3 of TB1 were always tied together.
6.11 RS-485 multi-drop network (HygroFlex 2 and 3)
Prior to connecting to the network
, configure each individual transmitter using the HW4 software (see separate instructions on the software CD ROM). With HW4 a Baud rate of either
19200 or 57600 may be used. As far as possible, use a Baud rate of 19200 for the HygroFlex and make sure that all devices in the multi-drop are set to the same Baud rate. Proceed as follows:
1) By default, all transmitters are shipped by the factory with RS address 0. If you plan on using HW4 for your network, the RS address does not have to be changed as
HW4 will do this automatically once the RS-485 network has been established.
2) For easier identification, you may also want to give each transmitter a unique descriptive name (maximum 30 characters).
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 32 of 61
Document title
Example: RS-232 / RS-485 Network
PC Unit 1
COM
Unit 2
2-cable connector
Unit 3
RJ45
2 wires
Unit 64
RS232 (3 wires) maximum 150 m (490 ft)
RS485 (2 wires) maximum 1,000 m (3,300 ft)
The RS232 connection between the HygroFlex and a PC requires 3 wires: RX, TX and GND.
Without a signal booster, the maximum cable length is limited to 150 m (490 ft). The RS485 connection requires two wires and should not exceed a total of 1,000m / 3,300 ft.
Each HygroFlex 2 or 3 is supplied with a special 5-pin connector that accommodates two cables
(see Connector Diagrams). On the first unit of a serial network, both the RS232 and RS485 wiring share this connector. Be sure to observe the polarity for each connection. Wall mounted RJ45 receptacles are a convenient means of connecting additional units to the RS-485 cable.
7 HygroFlex function menu
The functions of the HygroFlex can be accessed either with the optional display and keypad or by connecting a HygroPalm indicator to the Test connector of the HygroFlex
1
(see Remote Mode).
Some functions, including all calibration functions, can also be accessed with the HW4 software.
1
The HygroFlex 3 with the Ethernet interface option does not have a Test connector
To access the function menu from the HygroFlex keypad, press the MENU key. The first menu item appears on the message line of the LC display. Use the UP or the DOWN key to navigate the menu. When the desired menu item appears on the message line of the LC display, press the
ENTER key to select. Some menu items have sub-items. These can be selected with the UP,
DOWN and ENTER keys. To exit the menu and return to the normal display mode, press the
MENU key. The instrument also returns automatically to the normal display mode when no key is being pressed for some time (main menu: 10 sec., submenu: 30 sec.).
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 33 of 61
Document title
7.1 CALCULATE (HygroFlex 2 and 3)
Definition
This function is used to select the humidity parameter that is calculated and displayed by the instrument
1)
. Any selection made here has no effect on analog output #3 (computed parameter) of the HygroFlex 3. Use the HW4 software to change the computed parameter sent this output.
1) Does not apply to third-party analog probes.
The calculated parameter is selected individually for each probe connected to the instrument
1)
Prior to entering this function, select on the display the probe input to program.
.
The unit system (Metric or English) is factory programmed according to what was specified when the instrument was ordered. The unit system can be selected with the optional HW4 software (see separate instructions).
Selections
Parameter Metric English Flex 2 Flex 3
Dew Point / Frost Point
1)
°C °F
x x
Wet Bulb Temperature
°C °F
x x
Vapor Concentration g/m
3 gr/cuft
x x
Specific Humidity g/kg gr/lb
x x
Mixing Ratio g/kg gr/lb
x x
Vapor Concentration at Saturation
Partial Pressure of Water Vapor g/m
3 hPa gr/cuft
PSI or In Hg
x x x x
Saturation Pressure of Water Vapor
Pressure Constant
2)
(Barometric Pressure) hPa hPa
PSI or In Hg
PSI or In Hg
x x x x
1) The standard factory setting is frost point for values below freezing. This setting can be changed to dew point with the optional HW4 software
2) This selection shows the fixed value that is used for computing the parameters that require barometric pressure as an input. The fixed pressure value can be changed with the optional HW4
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 34 of 61
Document title software. Both the HygroFlex 2 and HygroFlex 3 can also be programmed to accept the input from a pressure probe (variable pressure value).
7.2 DISPLAY
Definition
This function is used to select which parameters are displayed by the optional display of the
HygroFlex 2 and HygroFlex 3. The display mode is specified globally for all humidity probes connected to the instrument.
HygroFlex 3: the display selection has no effect on the analog outputs.
Selections
- Measurement
Relative humidity and temperature or the parameter measured by any third party probe connected to the instrument.
- Calculated + Temperature
Calculated parameter (as selected under CALCULATE) and temperature. This selection is not available with third-party probes.
- Calculated + Humidity
Calculated parameter (as selected under CALCULATE) and relative humidity. This selection is not available with third-party probes.
- User Calc
User defined calculation such as the difference between temperature and dew point of any probe. The display shows only the calculated value. See the separate HW4 manual for instructions on how to program the HygroFlex 2 or 3 to compute a user specified parameter.
7.3 ADJUST M.PT
Definition
The Adjust M.PT function permits to calibrate and adjust a ROTRONIC HygroClip digital probe against a known reference environment. This function is designed to permit calibration at 2 temperature values and at up to 4 relative humidity values.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 35 of 61
Document title
Selections
The Adjust M.PT function offers the following selections:
RHS
: Humidity calibration using the ROTRONIC Humidity Standards
1)
Humidity
: Humidity calibration using any suitable reference environment
Temperature
: Temperature calibration using any suitable reference environment
1) For humidity calibration, ROTRONIC offers convenient, certified humidity standards to generate known humidity values (for more details, see Appendix 3 - Humidity Calibration).
Procedure
When two probes are connected to the transmitter, be sure to select (display) the HygroClip probe to be calibrated prior to entering the function.
When using the Adjust M.PT function, it is important to observe the following rules: a) Always calibrate temperature first (if temperature needs to be calibrated) b) When calibrating temperature (2 points), always calibrate at the low value first. The instrument is programmed to use the low temperature value to compute the offset and the high temperature value to compute the gain.
T-low < 40 °C (104°F) : used to compute the calibration offset
T-high ≥ 40 °C (104 °F) : used to compute the calibration gain
For best accuracy, we recommend using a T-low value close to 20°C (68°F). c) When calibrating relative humidity (2, 3 or 4 points) with the ROTRONIC humidity standards, always follow the sequence 35 %RH, 80 %RH, 10 %RH or 5 %RH, 0 %RH. When using a reference other than the ROTRONIC humidity standards, use reference conditions that are within the following brackets and observe the sequence:
>25 %RH…≤55 %RH
1)
>55 %RH
1)
≤ 1 %RH :
:
>1 %RH…≤25 %RH :
: used to compute the calibration offset used to compute the calibration gain sensor linearity adjustment sensor linearity adjustment
The HygroFlex is programmed to automatically recognize these brackets.
1) For best accuracy, we recommend using values close to 35 %RH and 80 %RH
When the probe is at equilibrium with the reference environment, activate the Adjust M.PT function and make the appropriate selections: a) RHS: press the ENTER key to select this item. The LC display shows the value read by the probe at the time the ENTER key was pressed. The letters “RHS” are displayed on the message line. Use the UP or the DOWN key to change the humidity value to match the mean value (at
23°C) written on the certificate supplied with the standard. For a faster change, keep the key pressed down. Press the ENTER key when done.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 36 of 61
Document title
Note: in the RHS mode, the software automatically compensates for the effect of temperature on the humidity standard. No additional correction is required. b) Humidity or Temperature: press the ENTER key to select. The LC display shows the value read by the probe at the time the ENTER key was pressed. The word “humidity” or
“Temperature” is shown on the message line. Use the UP or the DOWN key to change the humidity or temperature value to match the value of the reference environment. For a faster change, keep the key pressed down. Press the ENTER key when done.
After pressing the ENTER key, the message “sure?” should appear on the LC display. Press
ENTER to confirm. Next, the LC display will confirm that the probe adjustment has been successfully completed. At that time, press ENTER to exit or MENU to return to the function Adjust
M.PT and do another calibration point.
Carry on in the same manner for each calibration point, following the sequence described above.
Note: you can exit the function at any time (without calibrating the probe) by pressing the MENU key.
7.4 ADJUST 1PT
Definition
The Adjust 1PT function permits to do a 1-point adjustment (offset adjustment) of a ROTRONIC
HygroClip digital probe against a known reference environment. This function is limited to a simple offset adjustment that is applied across the entire measuring range. To prevent unauthorized or
accidental changes, lock the keypad (software configuration) to block out access to this function either from the keypad or from the HygroPalm calibrator.
Warning: a 1-point adjustment is no substitute for an adjustment at 2 or more points. Adjusting the probe at only one value can improve accuracy over a narrow range of conditions and may also be detrimental to accuracy at other conditions.
Selections
The Adjust 1PT function offers the following choices:
RHS
:
Humidity
:
Humidity calibration using the ROTRONIC Humidity Standards
Humidity calibration using any suitable reference environment
1)
Temperature
: Temperature calibration using any suitable reference environment
1) For humidity calibration, ROTRONIC offers convenient, certified humidity standards that generate known humidity values (for more details, see Appendix 3 - Humidity Calibration).
Procedure
When two probes are connected to the transmitter, be sure to select on the display the HygroClip probe to be calibrated prior to entering the function.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 37 of 61
Document title
When the probe is at equilibrium, activate the Adjust 1PT function and make the appropriate selections: a) RHS: press the ENTER key to select this item. The LC display shows the value of the standard
(for example 35.0%RH) on the top line and “Humidity RHS” on the message line. Verify that the value agrees with the standard being used. If necessary, change the value of the standard with the UP or the DOWN key. Press the ENTER key when done.
Note: the software automatically compensates for the effect of temperature on the humidity standard. No additional correction is required. b) Humidity or Temperature
1
: press the ENTER key to select. The LC display shows the value read by the probe at the time the ENTER key was pressed. The word “humidity” or
“Temperature” is shown on the message line. Use the UP or the DOWN key to change the humidity or temperature value to the value of the reference environment. For a faster change, keep the key pressed down. Press the ENTER key when done.
1
1-point temperature adjustment: limited by the firmware to -20…< 40°C (-4…<104°F)
After pressing the ENTER key, the message “sure?” should appear on the LC display. Press
ENTER to confirm. Next, the LC display will confirm that the probe adjustment has been successfully completed. At that time, press ENTER to exit.
Note: you can exit the function at any time (without calibrating the probe) by pressing the MENU key.
7.5 ADJUST REF
Definition
Note: this function is not available with the HygroFlex 1 (single probe input).
When two ROTRONIC HygroClip digital probes are connected to the HygroFlex, the Adjust REF function permits to do a 1-point adjustment (both humidity and temperature) of probe 1, using probe 2 as a reference. To prevent unauthorized or accidental changes, access from the keypad to
this function can be blocked out (software configuration).
Warning: a 1-point adjustment is no substitute for a full calibration (2 or more points). Doing a 1point adjustment can improve accuracy over a narrow range of conditions and may also be detrimental to accuracy at other conditions.
Procedure
Expose both probes to the same stable environment. Ventilation of the probes is highly recommended. Observe the readings from both probes for complete equilibration with the reference environment.
Press the ENTER key to enter the function. The display asks you to wait for a short time and then shows the temperature and humidity read by the reference probe at the time the ENTER key was pressed. Note that these values are not updated to the display as long as the function is active.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 38 of 61
Document title
The message line of the display shows which probe is the reference: for example REF = Probe 2 indicates that probe #2 is the reference.
Press the ENTER key to accept. After pressing the ENTER key, the message “sure?” should appear on the LC display. Press ENTER to confirm. Next, the LC display will confirm that the probe adjustment has been successfully completed. At that time, press ENTER to exit.
Note: you can exit the function at any time (without calibrating the probe) by pressing the MENU key.
7.6 PROBE
Definition
This function displays the version number and serial number of any ROTRONIC HygroClip digital probe connected to the instrument.
Procedure
Prior to entering the function, select the probe to be displayed (this is the same as the probe that was last displayed).
When entering the function, the version number of the probe is displayed first. Use the UP or the
DOWN key to display the serial number of the probe.
7.7 SETTINGS
Definition
This function is used to do the following:
• turn the trend indicators on or off
• change the symbol used for relative humidity
Procedure
Trend
: use the UP or the DOWN key to enable or disable the trend indicators.
The trend of humidity and temperature is shown on the display by an arrow (up or down) to the left of the measured value. Both arrows are shown to indicate stable conditions. Stable conditions are defined as rate of change of less than 0.02 %RH / min or °C / min.
Signal stability is first evaluated after 60 seconds into the measurement and is updated every 30 seconds.
HygroFlex 2 and 3: when the trend indicator is enabled, the symbol for the calculated parameter
(e.g. Dp for dew point) is no longer displayed to the left of the numerical value.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 39 of 61
Document title
Humi Unit:
use the UP or the DOWN key to change the symbol used for relative humidity
(depends on country and language).
7.8 SYS Status
Definition
This function displays the software version of the instrument, the RS232 configuration * (baud rate, parity, bits and stop bit), the network address *, any user defined description for the instrument * and the serial number of the instrument.
This information is for display only. Some parameters such as the network address can be changed with the HW4 software, after connecting the instrument to a PC.
* except HygroFlex 1
Procedure
When entering the function, the software version number is displayed first. Use the UP or the
DOWN key to display the other data.
7.9 OUTPUT
Definition
This function displays the numerical values sent to the analog outputs. The display shows the values at the time the menu key was pressed and these values are not updated to the display as long as the function is active. This allows the values to be correctly compared.
Note: the analog output signals keep being updated while this function is in use.
Procedure
When entering the function, analog output 1 is displayed first. Use the UP or the DOWN key to display the other outputs.
8 Error and status messages
The following is a list of coded messages (101, etc.) that the HygroFlex may show on the bottom line of the optional LC display or via PC interface.
Errors:
101
102 checksum error bad command
The checksum test did not pass during RS-communication.
An unknown command was received
103
104
105 disallowed command unknown probe input argument error
A command was received that is reserved for production and service
Reference was made to a non-existing analog or digital probe input
Error in the number of the arguments in the command or in the value of one of the arguments
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 40 of 61
Document title
106
107
HygroClip communication error calibration error
108
110
111
Warnings:
120
121
Status:
130 calibration error
(overflow) unknown reference probe
Temperature error no adjustment
No HygroClip probe is connected the probe was adjusted
The HygroClip probe does not answer or is not connected
The difference between the probe reading and the calibration point is larger than the maximum allowed by the
INI command.
Internal probe error (or the difference between the probe reading and the calibration value is too large)
The reference probe is not connected or the reference probe input does not exist
During humidity calibration, temperature should be within the limits of 0 and 80
°C (32 and 176°F)
Calibration
Calibration
9 Test connector for the HygroPalm indicator
NOTE
: The HygroFlex 3 equipped with the optional Ethernet interface does not have a Test connector.
Definition
The test connector permits to connect a HygroPalm indicator to the HygroFlex (the HygroPalm goes automatically into its Remote Control Mode). This is especially useful when the transmitter does not have the optional display and keyboard. Depending on the model of HygroPalm, the
Remote Control mode allows the following:
HygroPalm
1
Display the readings from any probe connected to the transmitter
x
Display the transmitter status
N/A
(configuration, serial number, etc.)
1-point adjustment of any ROTRONIC HygroClip digital probe connected to the transmitter, using the probe connected to the HygroPalm as a reference
Access the functions
1)
of the transmitter, primarily the
ADJUST M.PT function - see Functions.
1) except for CALCULATE and DISPLAY
N/A
HygroPalm
2
HygroPalm
3 x x x x x x
N/A N/A
x
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 41 of 61
Document title
Procedure
The Remote Control mode is automatically activated by connecting any probe input of the HygroPalm to the Test port of the transmitter
HygroPalm 1: remove the probe and replace it with cable # AC1621
HygroPalm 2 and 3: connect cable #AC1620 to the second probe input
As soon as the two instruments are connected, the HygroPalm detects the transmitter and this is indicated by a flashing star on each side of the LC display. At that time, the display of the HygroPalm shows data from the remote unit and can no longer be used to access local data from the
HygroPalm. Similarly, the function keys of the HygroPalm control the transmitter and not the HygroPalm itself. To exit the Remote Control mode, simply disconnect the two instruments.
Notes:
Using the Remote Control mode does not disturb the output signals (analog or digital) of the transmitter. The outputs keep being normally updated. The
HygroPalm cannot be turned off while in the Remote Control Mode.
9.1 Display the Probe Measurements
As soon as the Remote Control mode is initiated, the HygroPalm displays the measurements from the probe(s) connected to the transmitter. When two probes are connected to the transmitter, each probe can be displayed with the UP or DOWN key on the HygroPalm.
9.2 Functions (except ADJUST M.PT and ADJUST 1PT)
Press the MENU key of the HygroPalm to access the functions of the transmitter and use the UP and DOWN keys to navigate the function menu. Selections are confirmed by pressing the ENTER key.
Access to the functions depends on the model of HygroPalm. The functions CALCULATE and
DISPLAY are generally not accessible in the Remote Control mode. For more details see
HygroFlex Function Menu
9.3 Functions ADJUST M.PT and ADJUST 1PT
The functions ADJUST M.PT
1) and ADJUST 1PT
1) can be accessed only with the HygroPalm 3. In the remote mode, both the display and the keyboard of the HygroPalm act like if they were the display and keyboard of the transmitter. The definition of these functions and the procedure to be followed are the same as already described under HygroFlex Function Menu.
1) applies only to the ROTRONIC HygroClip digital probes
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 42 of 61
Document title
9.4 Function ADJUST REF
In the Remote Control Mode, the function Adjust REF can be used to do a 1-point adjustment of the ROTRONIC HygroClip probe(s)
1) connected to the transmitter against the probe connected to the HygroPalm indicator. The function adjusts both humidity and temperature simultaneously.
The following choices are available for the reference probe: a) REF = PALM: to access this function, a probe must be connected to one of the HygroPalm probe inputs. The other probe input of the HygroPalm is already used to connect to the TEST port of the transmitter. The reference is the probe connected to the HygroPalm.
HygroFlex 2 or 3 with second probe option: when 2 probes are connected to the HygroFlex, the probe that was displayed on the HygroPalm prior to entering the function menu will be adjusted. b) REF = FLEX (HygroFlex 2 or 3): this is available only when the HygroFlex has 2 probe inputs and the reference is always the probe connected to input 2 of the HygroFlex. Probe 1 will be adjusted (1-point) to match probe 2. Probe 2 cannot be adjusted against probe 1.
1) When no such probe is detected, the message “connect fail” will be displayed.
Press MENU and use the UP or the DOWN key to access Adjust REF from the function menu.
Press ENTER to select this function.
After pressing the ENTER key, the display of the HygroPalm shows the relative humidity and temperature data from the reference probe. When the HygroFlex has 2 probes, use the UP or the
DOWN key to select either REF = PALM or REF = FLEX. The data on the display is the data read by the reference probe at the time the ENTER key was pressed. This data is not updated while the function Adjust REF is active (see Notes below).
Press the ENTER key to accept the reference data. The message “sure?” should appear on the LC display. Press ENTER to do the 1-point adjustment of both humidity and temperature or press
MENU to abort and exit this process. When the message “Adjust OK” appears, press ENTER to exit.
Notes:
Expose both probes to be to the same stable environment. Ventilation of both probes is highly recommended. Observe the readings from both probes for complete equilibration (this can be done by entering and exiting a few times the function Adjust REF so as to check both probes prior to adjusting).
If the transmitter has its own display, it simply repeats the data or commands shown on the display of the HygroPalm.
10 Environmental limits
The HygroFlex can operate in the temperature range of –40...60
°C (-40…140°F) and should not be exposed to condensing humidity. Units with the optional LC display and keypad should not be used below -30
°C (-22°F).
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 43 of 61
Document title
The operating limits at the probe depend on the probe model and are specified separately for each probe.
11 Maintenance
11.1 On-site maintenance
a) Probe
Each HygroFlex transmitter has a test connector that is located on the connection plate.
The HygroPalm 2 and HygroPalm 3 portable indicators can be connected to this connector with cable AC1620. Using the probe of the HygroPalm as a reference, any
HygroClip digital probe connected to the transmitter can be read and adjusted at one humidity and temperature value. When adjusting against a reference probe, please make sure that both probes are exposed to the exact same environment and are at temperature and humidity equilibrium. Ventilation of both probes (same air stream) is highly recommended. b) Validation of the analog outputs
With the exception of the analog probe input and analog output circuits, the HygroFlex uses digital circuits that are by nature immune from drift. The HygroFlex uses analog circuits that are very stable. These circuits should not exhibit any noticeable drift for many years. If so desired, the analog input and output circuits can be validated by substituting a test connector for the probe. The test connector AC1618/50 simulates a HygroClip probe and generates digital and analog signals corresponding to 50%RH and 25
°C (77°F). The output signals can be read with a DVM (open the transmitter housing and disconnect the analog output plug-in terminal block).
11.2 Factory / metrology lab. maintenance
The HygroFlex should not require any routine maintenance other than validating the analog probe inputs (if used) and the analog outputs. Please, contact the factory if the analog outputs require an adjustment.
11.3 Maintenance of the ROTRONIC probes
Cleaning or replacing the dust filter
Most ROTRONIC probes come with one of the following types of dust filter: (a) protective metal base with a removable filter cartridge or (b) plastic slotted cap with built-in (not removable) filter element.
Depending on the conditions of measurement, the filter should be checked from time to time. If the probe has a removable filter cartridge, this can be easily removed for cleaning.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 44 of 61
Document title
If the probe has a plastic slotted cap with a built-in filter element, cleaning should be done without removing the filter from the probe. In that case, do not use detergents, solvents or other strong chemicals. Either brush the filter or use a little bit of clean water.
Corroded, discolored or clogged filters should be replaced. If the probe has a removable cartridge, simply replace the cartridge (leave the metal base on the probe).
If the probe has a plastic slotted cap with built-in filter element follow these instructions:
1) Unscrew the filter from the probe and pull it straight away, in the alignment of the probe, so as not the catch the humidity and temperature sensors.
2) Before putting on a new dust filter, check the alignment of both sensors with the probe. The wires that connect the sensors to the probe are very thin and bend easily. If necessary, correct the alignment by tapping the sensor very gently with a smooth object such as a small plastic rod. Do not use sharp pliers or tweezers as this could puncture the sensor and do not pull hard on the sensor.
Periodic calibration check
Long term stability of the ROTRONIC Hygromer humidity sensor is typically better than 1
%RH per year. For maximum accuracy, calibration of the probe should be verified every 6 to
12 months. Applications where the probe is exposed to significant pollution may require more frequent verifications.
Both the Pt 100 RTD temperature sensor and associated electronics are very stable and should not require any calibration after the initial factory adjustment.
For routine calibration checks, the probe should be verified at one or two values of humidity.
For more details, see Probe calibration Basics and Functions – ADJUST M.PT.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 45 of 61
Document title
12 Specifications
Operating Voltage
Operating limits at electronics
Measured parameters
1)
relative humidity
temperature standard optional w/o LC display with LC display
12 to 35 VDC / 300 mA max. or 12 to 24 VAC
90 to 264 VAC 50/60 Hz
0…99 %RH (non condensing)
-40...60
-30…60
°C (-40...140°F)
°C (-22…140°F) typical range indication range typical ranges pressure indication range range indication range
Calculated parameters
1) 2)
0…100 %RH
0.0 to 100.0 %RH
0…100
°C, -50…150°C, 0…200°C
0…100
-99.9 to 999.9
°C or °F
0…2000 hPa / 0…50 PSI / 0…100 InHg
0.000 to 9999 hPa/PSI/InHg
dew / frost point
enthalpy
4)
3)
wet bulb temperature
4) indication range
typical
-50…100
-99.9 to 999.9
°C or °F
°C / 0…200°F indication range typical range
0.0 to 100.0
°C / 32 to 212.0°F
-50…250 J/g or -50...150 BTU/lb
vapor concentration humidity indication range typical range indication range typical range
mixing indication range typical range indication range
vapor concentration at saturation typical range
-99.9 to 9999 J/g or BTU
0…500 g/m3 or 0…250 gr/cuft
0.000 to 9999 g/m3 or gr/cuft
0…500 g/kg or 0…4000 gr/lb
0.000 to 9999 g/kg or gr/lb
0…500 g/kg or 0…4000 gr/lb
0.000 to 9999 g/kg or gr/lb
0…500 g/m3 or 0…250 gr/cuft indication range
part. pressure of water vapor typical range
sat. pressure of water vapor indication range typical range
0.000 to 9999 g/m3 or gr/cuft
0…500 hPa / 0…10 PSI / 0…20 InHg
0.000 to 9999 hPa / PSI / InHg
0…500 hPa / 0…10 PSI / 0…20 InHg
System accuracy at 23
°C/73°F
Number of probe inputs indication range with HygroClip probe & 4-point calibration
HygroFlex 1
0.000 to 9999 hPa / PSI / InHg
± 1 %RH
± 0.2
1
°C / 0.4°F
HygroFlex 2 and 3 1 (standard) or 2 (optional)
Probe type
5) all models
HygroFlex 2 and 3
ROTRONIC HygroClip digital probe
ROTRONIC analog probe
Third-party analog probe
6)
6)
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 46 of 61
Document title
Analog outputs (scalable)
Analog signals (selectable)
HygroFlex 1
HygroFlex 3
HygroFlex 1 and 3 0…1V, 0…5V, 0…10V
Minimum load for voltage outputs
Maximum load for current outputs
Standard serial outputs HygroFlex 1
2: relative humidity and temperature
3: relative humidity, temperature and calculated parameter
0…20 mA, 4…20 mA
1000 ohm
500 ohm
7)
RS232 (internal service connector)
HygroFlex 2 and 3 RS232 / RS485 (external connector)
Optional Ethernet / serial output HygroFlex 2 and 3 TCP/IP and RS485
Electrical Connections power analog outputs cable grip and terminals cable grip and terminals
8)
8) output
probe
Optional LC display and keypad
Housing Material alphanumerical, 0.000…9999 keypad
ABS (standard)
metal
Housing Dimensions
Weight
Protection grade
207 x 150 x 59 mm (8.15 x 5.91 x 2.32”)
800 g (1.76 lb)
IP65 / NEMA 4
1) Specify engineering units and range when ordering (both can be changed by the user with optional HW4 software). See separate probe specifications regarding the different range limits
2) Not available with the HygroFlex 1. The accuracy of the computed parameter is limited by the accuracy of the measured parameters on which it is based
3) The standard factory setting is frost point for values below freezing. This setting can be changed to dew point with the optional HW4 software
4) A fixed value is used for the computations of this parameter. The fixed pressure value can be changed by the user with the optional HW4 software. The HygroFlex can also be programmed to accept the input from a pressure probe (variable pressure value)
5) Accuracy, repeatability and operating limits are specified separately for each model of probe
6) ROTRONIC analog probes: because the HygroFlex cannot read a negative input voltage, temperature measurement with probes having a standard output is generally limited to values above freezing. Thirdparty probe (pressure or other): linear voltage output signal within the range of 0..2.5 VDC, supply voltage
5 or 15 VDC, 10 mA (jumper selectable)
7) The span of the computed parameter should be determined under consideration of the D/A resolution of the corresponding analog output (12-bit is standard for output # 3). Depending on the desired signal resolution, a wide span may require the optional 16-bit D/A converter for analog output # 3
8) ½” conduit adapters or connectors also available
.
Recommended cable for cable grips: 7..9 mm diameter
( 0.275..0.354”) with 18 AWG wires. Cable for output signals should preferably be shielded.
9) This is a 5-pin connector that is shared by the RS232 and RS485 signals. A matching 2-cable connector is supplied with the transmitter
10) Supplied with the probe
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 47 of 61
Document title
Dimensions in mm
13 Probe calibration basics
Depending on whether or not the transmitter has a display and keypad, the following choices are available to calibrate the probe(s) used with the HygroFlex: a) Calibration using the transmitter display and keypad (see Functions) b) Calibration using a HygroPalm indicator (see Remote Control with the HygroPalm indicator) c) Calibration using a PC with the optional HW4 software (see separate software instructions).
This choice is available only with the HygroFlex 2 and HygroFlex 3. d) Calibration of the probe alone (removed from the transmitter), using a PC with the optional HW3 software and the T7-03-WIN calibration cable (see separate software instructions).
Note: the HygroFlex itself should not require any field calibration.
13.1 Temperature calibration
Note: the stability of the Pt100 RTD sensor used to measure temperature is such that temperature calibration in the field is seldom required.
In order to be able to correctly evaluate the accuracy of the temperature measurements provided by the probe, you should be able to meet the following requirements: a) Both the probe and a reference thermometer should be ventilated with the same stream of air. Any dust filter used to protect the sensors should be carefully removed from the probe.
If the probe has a protective slotted cap, this may be left on the probe. b) Air velocity at the sensor should be within the limits of 200 to 500 feet/minute (1 to 2.5 meters/second). Any comparison between two instruments at a velocity under 200 feet/minute may not be valid. Air velocity above 500 feet/minute may damage the unprotected humidity sensor.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 48 of 61
Document title c) The temperature of the air stream should be practically constant.
If you cannot meet the above requirements, you should not attempt to calibrate temperature.
13.2 Humidity calibration
ROTRONIC provides easy-to-use, certified humidity standards for customers who do not have access to a humidity generator. To use these standards, you will need a calibration device that is suitable for your probe.
Calibration device
The calibration device is a small airtight container that fits on the probe and seals around the humidity sensor. During calibration, a known reference humidity is produced inside the calibration device by means of a humidity standard (usually an aqueous salt solution).
The following calibration devices are available from ROTRONIC:
ER-15: for 15mm diameter probes
ER-05: for 5 mm diameter probes
EM-15 for probe type IE
ERV-15 for probe type IW
Certified humidity standards
The ROTRONIC certified standards are available in boxes of 5 glass ampoules of the same value, which can be stored indefinitely. Standards in the range of 5 to 95 %RH are nonsaturated aqueous salt solutions that are precisely titrated at our factory for the right concentration. The 0 %RH humidity standard is made of small granules of a highly porous ceramic that have been dried at a high temperature. A Material Safety Data Sheet is available for each standard. Since most standards are a salt solution, parts which have come in contact with the liquid should be cleaned after each use.
Each box of standards comes with a certificate that provides statistical information on the manufacturing batch of the standard. Information on the effect of temperature on each standard is provided on the cover of each box of standard. When calibrating either with the
HygroFlex or with the HW4 software, the effect of temperature on the standards is compensated by the software and no further correction is required. The value of the standards is not affected by altitude.
Instructions for using the standards
• Install the calibration device on the probe so that the receptacle (or solution holder) is under the probe. Check for a tight fit and remove the receptacle from the calibration device.
• Place one fiber disc (each box of standards includes 5 discs) in the receptacle of the calibration device. The purpose of this disc is to prevent accidental spilling of the solution inside the calibration device or on the humidity sensor.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 49 of 61
Document title
• Tap the top of the ampoule so that all liquid drops to the bottom of the ampoule. Snap off top and empty contents on fiber disc. Since the ampoule is made of glass, exercise proper caution (gloves, safety glasses) when snapping off the top.
• Put the receptacle back on the calibration device and make sure that the solution does not come in contact with the sensor: The solution inside the calibration device should never be on top of the sensors.
• Allow at least 60 minutes to insure that the calibration device, the solution and the sensor are in a state of equilibrium. This is verified by monitoring the display.
• After adjusting the probe, remove the receptacle from the calibration device. Throw away the wet disc (non reusable). Thoroughly wash and wipe dry the receptacle.
General recommendations
During calibration, temperature stability is the single most important requirement. If possible, calibrate the probe is room temperature (18 to 25
°C). Room temperature should be stable to
± 0.25°C or better during the period of time required for each calibration point. Do not calibrate close to an air vent or a heater, in direct exposure to sun rays, etc.
If using a humidity generator to calibrate the probe, make sure that the probe is as fully immersed in the generator as possible to minimize temperature effects.
14 Humidity Definitions
Relative humidity
Relative humidity is the ratio of two pressures: %RH = 100 x p/ps where p is the actual partial pressure of the water vapor present in the ambient and ps the saturation pressure of water at the temperature of the ambient.
Relative humidity sensors are usually calibrated at normal room temperature (above freezing).
Consequently, it generally accepted that this type of sensor indicates relative humidity with respect to water at all temperatures (including below freezing).
Ice produces a lower vapor pressure than liquid water. Therefore, when ice is present, saturation occurs at a relative humidity of less than 100 %. For instance, a humidity reading of 75 %RH at a temperature of -30°C corresponds to saturation above ice.
Dew point / Frost point temperature
The dew point temperature of moist air at the temperature T, pressure P b
and mixing ratio r is the temperature to which air must be cooled in order to be saturated with respect to water (liquid).
The frost point temperature of moist air at temperature T, pressure P b
and mixing ratio r is the temperature to which air must be cooled in order to be saturated with respect to ice.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 50 of 61
Document title
Wet bulb temperature
The wet bulb temperature of moist air at pressure Pb, temperature T and mixing ratio r is the temperature which the air assumes when water is introduced gradually by infinitesimal amounts at the current temperature and evaporated into the air by an adiabatic process at constant pressure until saturation is reached.
Vapor concentration
The vapor concentration (density of water vapor in a mixture) - or absolute humidity - is defined as the ratio of the mass of water vapor M v
to the volume V occupied by the mixture.
D v
= M v
/ V , expressed in grams/m3 or in grains/cu ft
This can be derived as follows from the equation PV = nRT: a) M v
= n x m m w w
, where : n = number of moles of water vapor present in the volume V
= molecular mass of water b) D v
= M v
/.V = n x m w
/ V = m w
x p / RT, where: m w
= 18.016 gram p = partial pressure of water vapor [Pa]
R = 8.31436 Pa x m3 / °K x mole
T = temperature of the gas mixture in °K
D v
[g / m3] = p / 0.4615 x T
1 gr (grain) = 0.0648 g (gram)
1 cu ft = 0.0283168 m3
D v
[gr / cu ft] = 0.437 x Dv [g / m3]
Specific humidity
The specific humidity (also known as mass concentration or moisture content of moist air) is the ratio of the mass M vapor M v v
of water vapor to the mass (M
is contained. v
+ M a
) of moist air in which the mass of water
Q = M v
/ (M v
+ M a
)
Q = p m w
/ (p m w
+ (P b
– p) m a
) m w m a p = partial pressure of water vapor [Pa] p = partial pressure of dry air [Pa]
P a b
= 18.016 gram
= 28.966 gram
= total or barometric pressure [Pa]
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 51 of 61
Document title
Q [g / kg] = 1000 p / (1.6078 P b
1 gr (grain) = 0.0648 g (gram)
1 lb = 0.4535923 kg
Q [gr / lb] = 7 x Q [g / kg]
– 0.6078 p)
Mixing ratio by weight
The mixing ratio r of moist air is the ratio of the mass M v
of water vapor to the mass M a with which the water vapor is associated: r = M v
/ M a
of dry air
M v
= n x m w
= m w
x p V / RT
M a
= n x m a
= m a
x p a
V / RT = m a
x (P b
– p) / RT, where: m w m a
= 18.016 gram
= 28.966 gram p = partial pressure of water vapor [Pa] p = partial pressure of dry air [Pa]
P a b
= total or barometric pressure [Pa]
R = 8.31436 Pa x m3 / °K x mole
T = temperature of the gas mixture in °K r = m w
p / m a
(P b
– p) r = 621.97 x p / (P b
– p) [g / kg]
1 gr (grain) = 0.0648 g (gram)
1 lb = 0.4535923 kg r [gr / lb] = 7 x r [g / kg]
Enthalpy
The enthalpy (or energy content) of moist air at pressure P b
(g/kg) is defined by: h [kJ / kg moist] = 1.00464 t + 0.001846 r x t + 2.5 r
, temperature t (°C) and mixing ratio r
Note: by convention, the enthalpy of dry air (r = 0) at 0°C is equal to zero. Negative values of enthalpy are possible and indicate that the energy content of the air / vapor mixture is less than the energy content of dry air at 0°C
1 lb = 0.4536 kg
1 BTU = 1.05507 kJ
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 52 of 61
Document title h [BTU / lb] = 0.4299 x h [kJ / kg] + 7.68
The value 7.68 is added to make the temperature of 0°F the reference for enthalpy expressed in
BTU / lb
15 Dew point accuracy
Both the HygroFlex 2 and the HygroFlex 3 use the relative humidity and temperature measurements to compute another parameter such as dew point, mixing ratio, enthalpy, etc. The accuracy of this conversion varies, depending on the humidity and temperature conditions. Typical accuracy for the dew point conversion is provided in the graph below:
Dew Point Accuracy
0
±1 °C
-10
±1.5 °C
-20
±2 °C
±2.5 °C
-30
-40
-50
-60
-40 -20 0 20 40 60 80 100 120
Temperature °C
The accuracy of the dew point conversion is less than the accuracy that is normally achieved with a chilled mirror instrument. This is especially true at low dew point values (dew point depression of more than -40…-50
°C) and at low temperatures. In many applications, repeatability is more critical than accuracy. Repeatability of the dew point conversion is typically 1/3 of the accuracy shown above.
Using a dew point conversion permits to measure conditions that cannot be measured with a chilled mirror instrument. Typically, the measuring head of a chilled mirror instrument is limited to a maximum of 70
°C and, therefore, cannot measure a dew point temperature above 70°C. In addition to the ability to operate at high temperature, the relative humidity probe offers significant advantages for industrial applications: less maintenance and higher tolerance to contaminants, no sampling system, no uncertainty between dew and frost and better response to fast changing conditions.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 53 of 61
Document title
16 ASCII communications protocol
The HygroFlex transmitter is compatible with two different communications protocols: ASCII and
HW4. When interrogated, the HygroFlex automatically recognizes which protocol is being used and does not require a manual configuration of its serial settings.
The following describes the ASCII communications protocol. This information is provided for users who for any reason are planning on using their own software.
Connections with a PC COM port
The exchange of data requires 3 wires: TXD (transmit), RXD (receive) and SG (signal ground).
When the ROTRONIC device requires power from the COM port (example: MOK-WIN probe calibration cable), the RTS and DTR wires are also used.
Settings required by the ASCII communications protocol
The ASCII communications protocol uses only 7-bit ASCII characters (ASCII 32 to 127). even
Data bits
Stop bits
: 7
: 1
Use these settings to configure a third-party software used to communicate with the HygroFlex
(see ASCII commands provided in this manual). Also use these settings to configure a device server (connection of a serial device to an Ethernet LAN). Set flow control to none and, if necessary, force incoming data to 7-bit ASCII.
Models with optional Ethernet interface
: the internal Ethernet module should be re-configured to use these settings. Detailed instructions are provided separately in document IN-E-TCPIP-
Conf_10.doc
(also available in PDF format).
Baud rate
Compatibility with the ASCII protocol requires the 19200 Baud rate (factory default).
IMPORTANT: Please note that all devices connected to an RS-485 multi-drop should use the same baud rate in order to communicate.
Data integrity
- 7-bit characters are sent with a parity bit. 8-bit characters are sent without parity bit.
- Strings (made of 7-bit characters) can be sent with or without checksum at the end of the string.
When the checksum is not known – for example: when sending a command - the checksum is replaced by the } character at the end of the string.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 54 of 61
Document title
ASCII communications protocol
Communication with the instrument is always initiated from the PC. Any ASCII string sent from the
PC should begin with the { character to start the synchronization. This should be followed by a
1-character product identification (see table below). The RS-485 address is next (this is a 2-digit number between 00 and 31 used to distinguish between the different instruments, probes, functions etc. that are connected to the PC). The address is followed by a command and by any values or parameters that may be required to carry out the command. Use a carriage return (CR) to terminate the command string.
Example: {M03RDD} + CR (asks instrument M03 to send measurement data)
When several instruments are connected together (RS485 network), commands directed to instruments other than the instrument that is physically connected to the COM port of the PC should be preceded with the | character (ASCII 124)
Example: |{U01RDD} + CR
The instrument answers with a string beginning with the { character, the product identification and the address, followed by the command that was received and any data field that may have been requested by the command. This is followed by a checksum.
The length of the string may vary, depending on how much data is included. Since the string itself does not include any information about its own length, a carriage return (CR) is always used to terminate the string.
Example: {M03RDD 0027.50;0023.76;0029.31;0022.77;#M (terminated with CR)
Note: Some instruments may insert the $ character at the second or third position of the string.
1-character product identification
ID Product Data request command
u HygroPalm 2 {u00RDD}+CR – assuming the address is 0
U HygroPalm 3 m HygroFlex 2
M HygroFlex 3 b HygroLab 2
B HygroLab 3
{U00RDD}+CR – assuming the address is 0
{m00RDD}+CR – assuming the address is 0
{M00RDD}+CR – assuming the address is 0
{b00RDD}+CR – assuming the address is 0
{B00RDD}+CR – assuming the address is 0
R M33 series {R00RDD}+CR – assuming the address is 0
A HygroClip Alarm
CR=Chr(13)
{A00RDD}+CR – assuming the address is 0
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Rotronic AG
Bassersdorf, Switzerland
Unit Document code
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 55 of 61
Document title
Special situations (single instrument)
Using address 99 in a data request causes any instrument with any address to answer. For this reason, address 99 should not be used when several instruments are connected to a network.
Address 99 can be useful when trying to communicate with a single instrument of unknown address. The address is returned as part of the answer string.
When the product ID is unknown, it can be replaced with a blank in the command. The product ID is returned as part of the answer string.
Example: { 99RDD}+CR
Examples
Data can be read from the instrument directly connected to the COM port of the PC (RS232) as well as from any instrument that is networked (RS485). The following examples are for the
HygroFlex. The same commands can be used for other instruments with similar capabilities by substituting the appropriate values for the product ID and address.
1) Read %RH and temperature from the HygroFlex 2 (with 2 probes) address 01, directly connected to the PC COM port (RS232):
Data request: {m01RDD}+CR
Answer: {m01RDD 0025.01;0016.89;0024.57;0019.84;#C
Note: 0025.01: humidity probe 1 (%RH)
0016.89: temperature probe 1 (°C as per instrument configuration)
0024.57: humidity probe 2 (%RH), etc.
2) Read %RH, temperature and computed parameter
Data request: {m01RDD0;}+CR
Answer: {m01RDD 0025.90;0015.82;-003.69;0024.47;0019.88;-001.00;S
Note: 0025.90: humidity probe 1 (%RH)
0015.82: temperature probe 1 (°C as per instrument configuration)
-003.69: dew point probe 1 (°C as per instrument configuration), etc.
3) Read %RH and temperature from the HygroFlex 3 (1 probe) with address 00, connected by
RS485 to the HygroFlex 2:
Data request |{M00RDD} +CR note: the | character (ASCII 124) preceding the command
Answer: {M00RDD 0020.41;0019.87;----.--;----.--;#E
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 56 of 61
Document title
Note: 0020.41: humidity probe 1 (%RH)
0019.87: temperature probe 1 (°C as per instrument configuration), etc
17 Metal enclosure option
As an option, the HygroFlex is available in an aluminum enclosure with a hinged cover - with or without display and keypad. The electrical connections are arranged like on the standard models.
The enclosure can be attached to a wall using the flanges located on each side of the enclosure.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 57 of 61
Document title
18 Accessories for the HygroFlex
Order Code Description
HW4-E HW4 software, Standard Edition ( single user)
HW4-P
HCA
HW4 Professional Edition (FDA/GAMP validation functions, multi user)
Programmable logic alarm and control card with 4 relay outputs. See note below.
HygroPalm 1 HygroPalm 1 indicator, limited to displaying the readings from the HygroFlex
HygroPalm 3 HygroPalm 3, field calibrator
AC1620
AC1621
AC1623
AC1624
AC1616
T7-03-B5
T7-03-WIN
AC1618/35
AC1618/50
AC1618/80
EA00-SCS
EA05-SCS
EA10-SCS
EA20-SCS
EA35-SCS
EA50-SCS
EA65-SCS
EA80-SCS
EA95-SCS
Cable HygroPalm 3 to HygroFlex
Cable HygroPalm 1 to HygroFlex
Cable service connector (MTA) to PC
RS232 cable (HygroFlex to PC)
Probe extension cable with signal amplifier, 2 to 200 meter (6 to 656 ft)
Adapter cable for optional 2nd probe. Cable length 3 meter (9.8 ft), 5 meter (16.4 ft) on request
Calibration cable HygroClip probe with T7 connector to PC. Terminated with a 25-pin SUB D connector. Converter 25-pin to 9-pin is supplied. Cable length 3 meter (9.8 ft). Includes 115
VAC / 9VDC adapter to power probe and cable electronics.
IMPORTANT
: this cable is compatible only with the HW3 software. probe simulator 35%RH / 77°F(25°C) probe simulator 50%RH / 77°F(25°C) probe simulator 80%RH / 77°F(25°C)
0%RH humidity std, SCS cert., pack of 5
5%RH humidity std, SCS cert., pack of 5
10%RH humidity std, SCS cert., pack of 5
20%RH humidity std, SCS cert., pack of 5
35%RH humidity std, SCS cert., pack of 5
50%RH humidity std, SCS cert., pack of 5
65%RH humidity std, SCS cert., pack of 5
80%RH humidity std, SCS cert., pack of 5
95%RH humidity std, SCS cert., pack of 5
ERV-15
ER-15
ER-05 calibration device for type ‘IW’ probes calibration device for 15mm diameter probes calibration device for 5mm diameter probes
EM-G calibration device for type ‘IE’ probes
HCA:
The HygroClip Alarm (HCA) is a programmable logic alarm and control card designed for use with other ROTRONIC products that have a RS-485 serial port. The HCA makes it possible to implement alarm functions that would not be available with either the HygroFlex alone or with the combination of the HygroFlex and a PC with the HW4 software. For example, the HCA makes it
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 58 of 61
Document title possible to trigger an alarm, or an action, based on the values measured by one or several devices and subject to the status of an external contact such as a switch or a push button. The HCA operates as a stand alone device or can be integrated in a network monitored by a PC with the
HW4 software. For more details, contact your local ROTRONIC representative or visit our website: www.rotronic-usa.com
19 Electrical Installation Guidelines
Power supply wiring
Heavy machinery and instrumentation should not share the same power supply wiring. If this cannot be avoided, noise filters and surge protectors should be used. Most UPS devices have those features already integrated.
General guidelines for signal cables
The following guidelines are derived from European Standard EN 50170 for the transmission of signals by copper wires. When planning an installation, the rules provided by EN 50170 should be followed under consideration of local circumstances to determine the position of machines and equipment.
All ROTRONIC HygroClip products are tested for Electromagnetic Compatibility according to following European standards:
- EN 61000-6-3 + EN 61000-6-1 (residential)
- EN 61000-6-4 + EN 61000-6-2 (industrial)
Whenever the level of electromagnetic interference is expected to be high, both the instruments and signal cables should be placed as far away as possible from the source of interference.
In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as indicated in the table below:
• Bus signals such as RS485
• Data signals for PCs, printers etc.
• shielded analog inputs
• unshielded direct current (<= 60V)
• shielded process signals (<= 25 V)
• unshielded alternate current (<= 25V)
• coaxial cables for CRT monitors
in common bundles or channels / conduits
• direct current from 60 V to 400 V
(unshielded)
• alternate current from 25V to 400 V
(unshielded)
in separated bundles or channels / conduits, without minimum distance
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
HygroFlex transmitter version 4: instruction manual
Rotronic AG
Bassersdorf, Switzerland
Unit
Instruction Manual
Document Type
Page 59 of 61
Document title
• direct and alternate current > 400 V
(unshielded)
• Telephone lines
• lines leading into EX-rated areas
in separated bundles or channels / conduits, without minimum distance
Lightning protection
Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that are suitable for underground installation.
RS-485 Cable
Using a symmetrical transmission method in combination with low capacity/ low attenuation twisted pair cables, allows extremely reliable long distance connections. The use of a high grade shielded cable avoids cross talk between the transmitted signals and also reduces the potential of external interference. For the RS-485 cable, we recommend using a cable Cat. 5e ANSI/ TIA /EIA-568-A-5.
In general the RS-485 cable should be shielded and comply with the following specifications:
-
Cable capacitance
- Line
<=300pF/m or 90 pF/ft
Ω ±15 Ω
140
-
Signal lines Twisted pair
In addition, we recommend terminating each end of the RS-485 cable with a 240 Ohm resistor.
RS485 Network
240
Ω
Addr. 1
RS485 device connectors
Addr. n
Note: all instruments connected to the network should use the same baud rate
240
Ω
Voltage potential issues
The existence of a voltage-potential between instruments that are interconnected can be a source on concern in large installations, installations with different mains power supply and in inter-building networking.
As a first measure, the shield of a signal cable should be connected at both ends. In the case of a data cable, a low-resistance potential equalization cable may also have to be used. This cable
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 60 of 61
Document title should be run parallel and as near as possible to the data cable, preferably in the same conduit.
The shield of the data cable should under no circumstances be used as equalization cable! The conductors of the potential equalization cable should ideally be stranded in order to be effective also in case of high- frequency interference.
The following point should also be observed:
• Close the parasitic circuit
• Connect all devices to the potential equalizing cable as often as possible. Electrical conductors such as machine elements, metal tubes or supporting constructions should be integrated into the system.
• Protect the potential-equalization cable and connections against corrosion.
• Select the cross-section of the potential equalization cable according to the maximum equalization current.
If these different measures do not correct the problem, a galvanic separation according to ISO9549 may have to be installed. You may also want to consider the use of fiber-optic cables.
20 Document releases
Doc. Release
_10
Date
Dec. 6, 2006
Notes
See Hardware and firmware changes release 10
Hardware and firmware changes covered in document release-10:
Firmware Version Date PCB-No.
4.0 Dec. 5, 2005 66.0738.0502
4.1b Dec. 6, 2006 66.0738.0602
- Starting with PCB number 66.0738.0502 all models are equipped with a SMD power fuse
(250 VAC 1 A).
- Starting with PCB number 66.0738.0602:
The default factory setting for the probe supply voltage is 5 VDC. HygroClip EX probes require
15 VDC power supply. A third party analog probe may also require a supply voltage of more than
5 VDC (HygroFlex 2 and HygroFlex 3). Move jumper B20 to B19 to supply all probes with 15 VDC.
There is no connection between signal ground and terminal 3 of the power terminal block (TB1). If so desired, a connection can be established by closing solder pad B18, next to TB1. On previous versions of the PCB, the signal ground and terminal 3 of TB1 were always tied together.
- Firmware version 4.1a corrects an issue found when the ROTRONIC HW4 software (version
1.2.2 or higher) is used to adjust a HygroClip probe attached to the HygroFlex.
- Firmware version 4.1b allows ordering the HygroFlex 2 or HygroFlex 3 with both an Ethernet
(TCP/IP) and a RS-485 interface. When equipped with this option, the HygroFlex 3 does not have an external Test connector.
© 2006; Rotronic AG IN-E-HyFlex-V2_10.doc
IN-E-HyFlex-V4_10
Document code
Rotronic AG
Bassersdorf, Switzerland
Unit
HygroFlex transmitter version 4: instruction manual
Instruction Manual
Document Type
Page 61 of 61
Document title
- Most references to the ROTRONIC HW3 software have been removed from this manual. All
HygroFlex models can be configured with the ROTONIC HW4 software (version 1.2.2 or higher).
HW4 can read / record data from both the HygroFlex 2 and HygroFlex 3, and can be configured to monitor alarms triggered by these devices. The HygroFlex transmitter is still backward compatible with the ROTRONIC HW3 software