Dear Valued Customer, Over the years we have collected

Dear Valued Customer, Over the years we have collected
Dear Valued Customer,
Over the years we have collected information that has helped us apply our signal conditioning products to
solve real world signal interface and equipment operation challenges. We have attempted to organize this
information into useful technical and application sheets that can help our customers during the project
design phase or when they are “under the gun” during an installation and start-up.
Our Technical Application booklet consists of several sections.
Feature and Ordering Guide
General and Technical Information
Technical Applications
Temperature
Pressure
Flow
Speed
Weighing
Process
Frequently Asked Questions
Our service begins well before we ever sell a module. Unique features exist on many modules and allow the
user to solve more problems than are outlined in this booklet. This is why you will see a “Call for
Application Assistance” request in the corner of each technical sheet. When you call you get a qualified
technician who can help you utilize the modules’ unique features to solve an application problem.
Absolute Process Instrument’s products are of a rugged American design, backed by solid technical support
and a LIFETIME WARRANTY. Please don’t hesitate to call if we can be of service.
Sincerely,
API Sales and Application Engineering
Absolute Process Instruments, Inc.
1220 American Way
Libertyville, IL 60048
USA
Phone: 800-942-0315
Fax: 800-949-7502
www.api-usa.com
Model
Mo
Fea
de
Inp l Type
tur
ut
es
(Se
L
Ou oop e K
tpu
ey
Tr
Un t Loo acker )
i-A
®
p
Iso larm Track LED
BiC er
lat
No ed Li olor LED
ne
n-I
G
240 solat arized reen/R
e
d
V
e
O
120 AC 7 Outp utpu d LED
t
u
A
/2
t
m
Un 40 VA p Re
ive
C O sis
Un rsal 8 pera tive
ive
5tio Co
Un rsal 9 265 V n Po ntact
ive
AC
we
Ra
-3
tin
Lo rsal 1 0 VDC Ope r
g
op
r
0
a
O
t
3
i
P
p
n
0
o
e
g
Int
egr were VAC ratio Pow
Op
n
Fu al On d
era Pow er
nct
t
B
ing er
Ad ional oard
Po
jus
we
Tes Loo
t
r
a
t
p
Int
egr ble D Push Inpu
e
Co al Fil adba butto t Pow
mm ter
n
er
nd
Hi- on M ing fo Pote
Im
nt
r
od
UL pact P e Re HI-No iome
,C
ise ter
jec
la
No UL, C stic C tion Imm
100
SA
u
Ch
as
dB nity
Mu arge App e
Min
ltiro
Fa
.
Life Turn ctory vals
tim Zero Ca
li
eW
arr & Sp bratio
ant an
Po n
y
ten
tio
me
ter
Input
Type
DC Api 1000 G
A ■
DC Api 1005 G
A ■
DC Api 1020 G
A ■
DC Api 1025 G
A ■
DC Api 1040 G
A ■
DC Api 1040 G SPR
A ■
DC Api 1080 G
A ■
DC Api 1080 DIN
A ■
DC Api 1090 G
A ■
DC Api 1090 DIN
A ■
DC Api 1090 DD
A ■
DC Api 4010 G
T ■ ■
DC Api 4050 G
T ■ ■
DC Api 4300 G
T ■ ■
DC Api 4300 G HC
T ■ ■
DC Api 4300 G M01
T ■ ■
DC Api 4300 G M09
T ■ ■
DC Api 4300 G EXTSUP T ■ ■
DC Api 4310 G
T ■ ■
DC Api 4380 G
T ■ ■
DC Api 4380 G DF
T ■ ■
DC Api 4380 G HV3
T ■ ■
DC Api 4380 DIN
T ■ ■
DC Api 4380 DD
T ■ ■
DC Api 4385 G
T ■ ■
DC Api 7500 G
T ■ ■
DC Api 7500 G M02
T ■ ■
DC Api 7500 G SS
T ■ ■
DC Api DIN-HV-DC
T ■ ■
DC Api LPI-1
T
■
DC Api LPI-2
T
■
DC Api DPI-2
T
■
T/C Api 1200 G
A ■
T/C Api 1220 G
A ■
T/C Api 4000 G
T ■ ■
T/C Api 4100 G
T ■ ■
T/C Api 4130 G L
T ■ ■
RTD Api 1400 G
A ■
RTD Api 1420 G
A ■
RTD Api 4000 G
T ■ ■
RTD Api 4001 G
T ■ ■
RTD Api 4001 G L
T ■ ■
RTD Api 4001 G SA-B
T ■ ■
Key: A = Alarm
T = Transmitter
■ = Standard
✽ = Optional
F-1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Rev 04/02
■
■
■
■
■ ■
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
■ ■
■ ■ ■
■ ✽
■ ■ ✽
■ ■ ■
■ ■ ■
■ ■ ■
■
■ ■ ■
■
✽ ✽
■ ■ ■
■
■ ■ ■
■ ✽
■ ■ ■
■
✽ ✽
■ ■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
■ ■
■
■ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
✽ ✽
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■ ■
✽ ✽
■ ■
■ ■
✽ ✽
■ ✽
■
■
■
■
■
✽ ✽
■
■
■
✽ ✽
■
■
✽ ✽
■ ■
■
✽ ✽
■ ✽
■
■
■
■
■
✽ ✽
■
■
■
✽ ✽
■
■
■
✽ ✽
■
D = Driver
P = Power Supply
▲ = Approvals Pending
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
▲
■
▲
▲
■
■
■
■
■
■
■
■
■
■
■
▲
▲
■
■
■
■
■
▲
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Model
FREQ
FREQ
FREQ
FREQ
FREQ
FREQ
FREQ
AC
AC
AC
AC
AC
AC
POT
POT
POT
POT
POT
STR. G.
STR. G.
STR. G.
STR. G.
STR. G.
STR. G.
STR. G.
STR. G.
STR. G.
POWER
POWER
DRIVER
DRIVER
DRIVER
MATH
MATH
LOOP
LOOP
LOOP
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Api
Mo
Fea
de
Inp l Type
tur
ut
es
(Se
L
Ou oop e K
tpu
e
Tr
y
Un t Loo acker )
i-A
®
p
Iso larm Track LED
BiC er
lat
No ed Li olor LED
nea
n-I
G
240 solat rized reen/R
e
d
V
e
O
120 AC 7 Outp utpu d LED
t
/24 Am ut
Un 0 VA p Re
ive
C
sis
Un rsal 8 Opera tive
ive
5tio Co
Un rsal 9 265 V n Po ntact
ive
AC
we
Ra
-3
tin
Lo rsal 1 0 VDC Ope r
g
op
r
0
a
O
t
3
i
P
ow 0 VA pera ng P
Int
egr ere
C O tion ow
er
per
P
Fu al On d
nct
atin ower
B
gP
Ad ional oard
ow
jus
L
T
o
e
er
Int table st Pu op In
egr
p
s
D
h
u
Co al Fil eadba butto t Pow
mm ter
n
er
n
d
Hi- on M ing fo Pote
Imp
nt
r
od
UL act P e Re HI-No iome
,C
i
j
se ter
ec
la
No UL, C stic C tion Imm
100
SA
u
Ch
as
dB nity
Mu arge App e
Min
ltiro
Fa
.
Life Turn ctory vals
tim Zero Ca
li
eW
arr & Sp bratio
a
ant
y n Pot n
ent
iom
ete
r
Input
Type
1700 G
1720 G
7010 G
7500 G
7500 G M02
7500 G SS
7580 G
1600 G
1620 G
6010 G
6010 G 5A
6380 G
6380 G S
1800 G
1820 G
4003 G
4003 G I
4008 G
1500 G
1520 G
4051 G
4058 G
4059 G
4059 G D
SUM 000
SUM 025
SUM 125
9046-xx
9046-CH
3200 G
3200 G M01
3200 GM420
440X G
4440 G
LPI-1
LPI-2
DPI-2
Key: A = Alarm
■ = Standard
A
A
T
T
T
T
T
A
A
T
T
T
T
A
A
T
T
T
A
A
T
T
T
T
P
P
D
D
D
T
T
T
T
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■ ■
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■ ■
■
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■
■ ■
■
■ ■
■
■
■
■
■
■
■
■
■
■
■ ■
■
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T = Transmitter
✽ = Optional
■
■
■
■
■
■
■
■ ■
■ ■
■ ■
■
■
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
■
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
✽
■
■
■
■
■
✽
✽
✽
✽
✽
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■ ■
■
■
■
■
■
■ ■ ■
✽ ■ ■
■ ■
■ ■
■ ■
■ ■
■ ■
■ ■ ■
✽ ■ ■
■ ■
■ ■
■ ■
■ ■
■ ■ ■
✽ ■ ■
■
■ ■
■ ■
■ ■ ■
✽ ■ ■
■ ■
■ ■
■ ■
■ ■
■ ■
■ ■
■ ■
■
■
■ ■ ■
■ ■ ■
■ ■ ■
■
■ ■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
▲
▲
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
▲
▲
▲
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D = Driver
P = Power Supply
▲ = Approvals Pending
Rev 04/02
F-2
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Signal Conditioners
While there are many different types of signal conditioners, their basic function is to change or alter signals so
that different process devices can communicate with each other accurately. Signal conditioners are most commonly needed to link temperature, pressure, weighing, level and flow devices with indicators, recorders, and
computerized process monitoring and control systems. Signal conditioners can also perform some other tasks
for you as listed below.
SIGNAL CONVERSION
A signal conditioner can change an analog signal from one form to another allowing equipment with dissimilar
signals to communicate. For instance, if a piece of field equipment puts out a 4-20 mA signal and the control
system needs a ±10 V input signal, the signal from the field equipment must be converted. A signal conditioner that accepts a 4-20 mA input and produces a ±10 V output solves the problem.
SIGNAL BOOSTING
The signal conditioner increases load drive capability in the loop allowing installation of additional instruments.
This works because the input impedance of most isolators is much less the load drive capability of a loop.
Therefore adding an isolator to the loop boosts the loop's net load drive capability. This is especially useful when
it becomes necessary to add additional devices to an existing overloaded loop.
SIGNAL ALARMING
Warns of trouble if a process signal reaches a too high or too low level. A signal conditioner that accepts an analog signal (4-20 mA, 1-5 V, etc.) and produces a relay output is an inexpensive way of providing a redundant
safety device in the event of a system failure.
SIGNAL ISOLATION
Stops ground loops from affecting the accuracy of a process signal. Ground loops are a common complaint at
system startup and can be eliminated by installing isolated signal conditioners, or isolators, on the process loop
between a nonisolated device and a control system.
SPECIFYING
A signal conditioner requires much of the same information as specifying any other instrument. Always consider these elements:
❑ Power Source
❑ Input Signal
❑ Output Signal
❑ Desired Options
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
G-1
APIAN046
Rev 04/02
Did You Know...?
Api will do non-standard and special ranges
for all of our products.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Terms and Definitions
Accuracy: The closeness of an indication or reading of a measurement
device to the actual value of the quantity being measured. Accuracy calculations are based on the linearity, hysteresis, and repeatability characteristics of
the transducer/sensor and supporting electronics, the range of the transducer/sensor, as well as the resolution being displayed. It is usually expressed as
a ±% of full scale output of the transducer/sensor/system.
A/D (Analog to Digital): Conversion of a continuously varying signal (analog) to discrete binary numbered values (digital).
Alarm Condition: The input (process signal) has crossed the set (trip) point
and the relay has changed states into the alarm condition. The relay will
remain in this state until the input signal returns to the normal condition.
Background Noise: The total amount of noise from all sources of interference in a process loop, independent of the presence of a data/control signal.
Chatter: Describes a condition where the input signal hovers near the set
(trip) point, causing the relay to trip off, then back on in short bursts.
Generally solved by adding or expanding the deadband.
Clipping: A phenomena which occurs when an output signal is limited in
some way (usually in amplitude) by the full range of an amplifier/unit.
Common-Mode Rejection (CMR): The ability of a device to eliminate the
effect of AC or DC noise between the input signal and ground. Normally
expressed in dB at DC to 60 Hz.
D/A (Digital to Analog): Conversion of a discrete binary numbered values
(digital) to a continuously varying signal (analog).
Deadband: The range through which an input can be varied without initiating an observable response. Deadband is usually expressed in percent of
span.
Dual Alarm Trip: A unit that accepts one input signal, has two set (trip)
points, and one output relay per set point. Each set point is independent of the
other and can be set between 0-100% of the input range.
Electrical Interference: Electrical noise induced upon the signal wires that
obscures (interferes with) the wanted information signal.
Fail-Safe: Relay coil is energized when the input signal is in the normal operating condition. In the alarm condition, the relay coil de-energizes.
Considered a safety measure because, in the event of a loss of power to the
unit or other failure, the unit “fails” to an alarm condition.
Gain: The amount of amplification used in an electrical circuit.
High Alarm: The relay changes state when the input signal reaches or
exceeds the set (trip) point.
Hysteresis: The difference in output from a transducer/sensor when a measured value is first approached with increasing and then decreasing values.
Input Impedance: The total opposition, both resistive and reactive, that the
unit presents to the input signal loop.
Linearity: The closeness of a calibration curve to a specified straight line.
Linearity is expressed as the maximum absolute deviation of any calibration
point on a specified straight line during any one calibration cycle.
Loop Resistance: The total resistance in a circuit to current flow caused by
the resistance of all components.
Loop Impedance: The total opposition (resistive plus reactive) to current
flow in a circuit.
Low Alarm: The relay changes state when the input signal falls to or below
the set (trip) point
MOV (Metal Oxide Varistor): A voltage dependent resistor whose resistance predictably changes with voltage, often used as transient protectors.
Negative Temperature Coefficient: A decrease in resistance with an
increase in temperature.
Noise: An unwanted electrical signal on any signal wires.
Non-Fail-safe (Reverse Acting): Relay coil is de-energized when the input
signal is in the normal condition. In the alarm condition, the relay coil energizes. There is no alarm when there is a loss of power.
Normal (Non-Alarm) Condition: The process signal has not crossed the set
(trip) point.
Normally Closed: Describes a set of relay contacts that in the unpowered
state have continuity across them.
Normally Open: Describes a set of relay contacts which in the unpowered
state have no continuity across them.
Optical Isolation: Two circuits which are connected only through an LED
transmitter and photoelectric receiver with no electrical continuity between
them.
Positive Temperature Coefficient: An increase in resistance with an
increase in temperature.
Relay (Mechanical): An electromechanical device that completes or interrupts a circuit by physically moving electrical contacts.
Relay (Solid State): A solid state switching device which completes or interrupts a circuit electrically with no moving parts. Commonly called an SSR.
Repeatability: The ability of a transducer/sensor to reproduce output readings when the same measured value is applied to it consecutively.
Reset: The action of returning to the normal (non-alarm) condition.
Resistance: Opposition to current flow offered by a purely resistive component, measured in ohms.
Response Time: The time required by a sensor to reach 63.2% of its final
value in response to a step-change input. This is typically called “one time
constant”. Five time constants are required for the sensor to stabilize at 100%
of the step change value.
Root Mean Square (RMS): Square root of the mean of the square of the signal taken during one full cycle.
Sensitivity: The minimum change in input signal to which an instrument/sensor can respond.
Set Point: The point at which an alarm/controller is set to control a system.
Single Alarm Trip: A unit that accepts one input signal, has one set (trip)
point, and one output relay. The set point can be set between 0-100% of the
input range.
Span: The difference between the upper and lower limits of a range
expressed in the same units as the range.
Span Adjustment: The ability to adjust the gain of a sensor/unit so that the
output signal corresponds to the maximum input signal. The adjustment
range is normally expressed in counts or percentage.
Transducer: A device that converts energy from one form to another. This
term is generally applied to devices that take physical phenomenon (pressure,
temperature, humidity, flow, etc.) and convert it to an electrical signal.
Triac: A solid state switching device used to control alternating current.
Trip Point: Value at which the alarm relays change to the alarm condition.
True RMS: The true root-mean-square value of an AC or AC-plus-DC signal, for a perfect sine wave the RMS value is 1.11072 times the rectified average value. This value is often used to determine the power of a signal. For significantly non-sinusoidal signals a true RMS converter is required.
Volt: The unit of potential difference and electromotive force. One volt will
send a current of one ampere through a resistance of one ohm.
Voltage: The electrical potential difference that exists between two points
and is capable of producing a flow of current when a closed circuit is connected between the two points.
Zero Adjustment: The ability to adjust the output from a sensor/unit so that
the minimum output corresponds to the minimum input. The adjustment
range is normally expressed in counts or percentage.
Rev 04/02
APIAN044
G-2
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
What is Deadband?
DEFINITION
Deadband is the range through which an input can be varied without initiating an observable response.
Deadband is usually expressed in percent of span.
EXAMPLE
A 20% total deadband is applied to the setpoint of a monitored parameter. The relay will trip and reset to its
untripped state as indicated in the following graph.
20% TOTAL DEADBAND
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
G-3
APIAN050
Rev 04/02
Did You Know...?
That the functional test pushbutton on all Api
Alarm Trip modules will toggle the relays independent of the input signal.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
RFI and EMI
Electrical interference, or noise, is an unwanted electrical signal that can cause intolerable error in, or complete
disablement of an electronic control or measurement systems. Interference or electrical noise is broken down
into two somewhat overlapping categories: Radio Frequency Interference (RFI) and Electromagnetic
Interference (EMI). Some of the more commonly encountered sources of interference are:
❑ Mobile and stationary radio, television and hand-held transmitters (walkie-talkies)
❑ Cellular telephones
❑ Fluorescent lights
❑ Radar
❑ Weather related electrical discharges such as lightning
❑ Static discharges
❑ Induction heating systems
❑ High speed power switching elements such as SCRs and thyristors
❑ High AC current conductors
❑ Large solenoids or relays
❑ Transformers
❑ AC or DC motors
❑ Ultrasonic cleaning or welding equipment
❑ Welding equipment
❑ Engine ignition systems
The effects of Radio Frequency Interference (RFI) and Electromagnetic Interference (EMI) can cause unpredictable and non-repeatable degradation of instrument performance and accuracy, and even complete instrument
failure. This can result in reduced process efficiency and production, plant shutdowns, and sometimes dangerous safety hazards.
There are two basic approaches to protecting and electronic system from the harmful effects of radio frequency
and electromagnetic interference. The first is to keep the interference from entering the system or instrument
using special shielding, designs and terminal filters. The second is to design the system or instruments circuitry so that it is inherently immune to RFI/EMI.
Did You Know...?
That Api plug-in and DIN style signal conditioners and isolators use state-of-the-art optical isolation.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN047
G-4
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Relay Protection and EMI Suppression
When using Api alarm module relays to switch inductive loads, maximum relay life and transient EMI suppression is achieved by using external protection. All external protection devices should be placed directly
across the load and all leads lengths should be kept to a minimum length.
For AC inductive loads (see Figure 1), place a properly rated MOV across the load in parallel with a series RC
snubber. A good RC snubber consists of a 0.1 µF polypropylene capacitor of sufficient voltage and a 47 Ohm ½
Watt carbon film resistor.
Figure 1: AC inductive loads
For DC inductive loads (see Figure 2), place a diode across the load (1N4006 recommended) being sure to
observe proper polarity. Use of an RC snubber is an optional enhancement.
Figure 2: DC inductive loads
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
G-5
APIAN039
Rev 04/02
Did You Know...?
Api’s standard heavy-duty relay contacts are
rated 7A @ 240 VAC (resistive) and can
directly control most devices.
■
❏
❏
❏
❏
❏
❏
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Ohm’s Law
E=IxR
OHM'S LAW is the relationship between current, voltage and resistance. It states that current varies directly
with voltage and inversely with resistance.
E (Electromotive Force or Voltage) is the electrical potential that exists between two points and is capable of
producing a flow of current when a closed circuit is connected between the two points. The unit of measure for
voltage is the volt (V). One volt will send one ampere of current through a resistance of one ohm.
I (current) is the flow of electrons past a point in a specified period of time, usually one second. The unit of
measure for current is the ampere (A). One ampere of current is 6.24 x 1018 electrons passing a point in one second. Ampere is often shortened to amp.
R (resistance) is the opposition to current flow offered by a resistive component. The unit of measure for resistance is the ohm. One ohm is the resistance through which a current of one ampere will flow when a voltage of
one volt is applied.
E
R
ExI
E2
R
I2 x R
Pow
er
50°C
1.12
1.78
2.82
4.49
7.14
11.35
18.05
28.70
45.63
72.55
115.40
183.40
IxR
atts)
(W
P
Curre
nt
I
E R
(V
olts
P
E
mps)
(A
20°C
0.99
1.59
2.53
4.02
6.39
10.15
16.14
25.67
40.81
64.90
103.20
164.10
ge
0°C
0.92
1.46
2.33
3.70
5.88
9.36
14.87
23.65
37.61
59.80
95.10
151.20
a
Volt
AWG
10
12
14
16
18
20
22
24
26
28
30
32
Ohm’s and Watt’s Laws
P
R
e(
Oh
ms)
Typical Solid Copper Wire Resistance
Ohms per 1000ft
E2
P
n
) Resista
c
PxR
P
I
P
I2
E
I
Resistance may vary ±10% or more
depending on impurities, alloys, coatings,
state of annealing, etc. Always check wire
manufacturer’s specifications.
Did You Know...?
That Api has UL, CUL and CSA approval as well
as a LIFETIME WARRANTY on our plug-in and
DIN style signal conditioners.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN048
G-6
■
❏
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
What is a Ground Loop
In a process control loop, a ground loop circuit can develop when each device's ground is tied to a different earth potential thereby allowing current to flow between the grounds by way of the process loop (Figure 1). Ground loops cause problems by adding or subtracting current or voltage from the process loop. This addition and/or subtraction causes the receiving device to be unable to differentiate between the wanted and unwanted signals and thus can't accurately reflect
actual process signals.
The probability of multiple grounds and ground loops
being established is especially high when new programmable logic controllers (PLCs) or distributed control systems (DCSs) are installed. With so many conditions within a facility referenced to ground, the likelihood of establishing more than one ground point is great. Thus, if an
instrumentation system seems to be acting strangely or
erratically, and the problem seems to point toward ground
loops, the chore of eliminating all unintended ground
connections becomes overwhelming.
Figure 1. Ground loops may develop with nonisolated transmitters and receivers, resulting in inaccuracy and unreliability.
Keep in mind that eliminating ground loops just isn't feasible for some instruments, such as thermocouples and some analyzers, because they require a ground to obtain accurate rate measurements. Also, some instruments must be grounded to
ensure personnel safety. When ground loops can't be eliminated the solution lies in the use of signal isolators. These
devices break the galvanic path (DC continuity) between all grounds while allowing the analog signal to continue throughout the loop. An isolator also can eliminate the electrical noise of AC continuity (common mode voltage).
Signal isolators can use numerous techniques to achieve their function but the best signal isolators usually employ optical
isolators (Figure 2). Regardless of the isolation method used, an isolator must provide input, output, and power isolation.
If this three-way isolation is not provided, then an additional ground loop can develop between the isolator's power supply and the process input and/or output signal.
Figure 2. A signal isolator in the process loop blocks ground current to restore signal accuracy and reliability.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
G-7
APIAN038
Rev 04/02
Did You Know...?
A common design error is to “save money” by
selecting non-isolated transmitters. It costs
far more to correct the problem later.
When in doubt – isolate!
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
■
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Using the Built-In 4-20 mA Loop Power Supply
Many Api modules have a built in loop power supply which can be used to power the 4-20 mA input current
loop. The wiring diagrams below give examples of how a two-wire transmitter can be powered by the module’s
loop power supply and also provide input to the module.
When using the built-in loop power supply, there is no connection to the module’s signal minus (–) input terminal. An internal 50 ohm resistor across the input terminals allows you to do this without any problems.
8-Pin Modules
API 4010 G
API 4050 G
API 4300 G
API 4310 G
API 4380 G
API 4380 GHV
API 4385 G
API 4440 G
+18V Supply
from Terminal 4
Power
POWER (+)
4-20 mA
Loop-Powered
2-Wire Transmitter
SIGNAL (–)
(+) Input to
Terminal 5
+12V Supply from
Terminal 9
DIN Pack Modules
API 1080 DIN
API 1090 DIN
API 1090 DD
API 4380 DIN
API 4380 DD
Output
No Connection
to Signal (–)
Input Terminal 6
1
2
3
4
5
6
POWER (+)
4-20 mA
Loop-Powered
2-Wire Transmitter
SIGNAL (–)
(+) Input to
Terminal 8
7 8 9
No Connection
to Signal (–)
Input Terminal 7 10 11 12
Power
11-Pin Modules
API 1005 G
API 1025 G
API 1040 G
API 1080 G
API 1090 G
Output
3 2 1 11 10 9
POWER (+)
4-20 mA
Loop-Powered
2-Wire Transmitter
No Connection
to Signal (–)
Input Terminal 5
4 5 6 7 8
(+) Input to
Terminal 4
Api plug-in style modules are hot-swappable.
You can change them in the field while powered up in order to minimize downtime.
Power
+18V Supply
from Terminal 2
SIGNAL (–)
Did You Know...?
Outputs
Output
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN055
G-8
■
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Common Thermocouple Sensors
Type
J
K
N
T
E
R
S
Polarity &
Material
+ Iron
Wire ID
Properties
Very magnetic
Wire
Color
Practical
Temp Range
White
32 to 1336°F
Black (Ext. grade)
±4°F or 0.8% of rdg
0 to 724°C
Brown (T/C grade)
±2°F or 0.4% rdg
32 to 2282°F
Yellow (Ext. grade
±4°F or 0.8% of rdg
0 to 1250°C
Brown (T/C grade)
±2°F or 0.4% rdg
– Constantan
Red
+ Chromel
Yellow
– Alumel
Slightly magnetic Red
+ NICROSIL Greater stiffness
Orange
– NISIL
Red
+ Copper
Copper color
– Constantan
+ Chromel
Greater stiffness
32 to 2282°F
0 to 1250°C
Outer
Insulation
Limits of Error
Orange (Ext. grade) ±4°F or ±0.8% of rdg
Brown (T/C grade)
±2°F or ±0.4% of rdg
Blue
–299 to 700°F
Blue (Ext. grade)
±1.5°F or 0.8% of rdg, ±1% rdg <32°F
Red
–184 to 371°C
Brown (T/C grade)
±0.9°F or 0.4% rdg, ±0.8% rdg <32°F
32 to 1652°F
Purple (Ext. grade)
±3°F or 0.5% rdg
0 to 900°C
Brown (T/C grade)
±1.8°F or 0.4% rdg
32 to 2700°F
Green (Ext. grade)
±5°F or ±0.5% of rdg
0 to 1482°C
Green (T/C grade)
±2.5°F or ±0.25% of rdg
32 to 2700°F
Green (Ext. grade)
±5°F or ±0.5% of rdg
0 to 1482°C
Green (T/C grade)
±2.5°F or ±0.25% of rdg
Purple
– Constantan
Red
+ Pt 13%Rh Greater stiffness
Black
– Platinum
Red
+ Pt 10%Rh Greater stiffness
Black
– Platinum
Red
Extend thermocouples up to 2000 feet or 100 Ohms maximum resistance.
Extension wire must be the same type as the thermocouple.
Atmosphere for exposed junction
Type J
Reducing
Type K or N
Clean oxidizing
Type T
Mildly oxidizing and reducing or with moisture
Type E
Vacuum, inert mildly oxidizing or reducing
Type R or S
Resists oxidation and corrosion, but contaminated by hydrogen, carbon, and metal vapors
TEMPERATURE CONVERSION
°F = (°C x 9/5) + 32
°C = (°F – 32) x 5/9
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
T-1
APIAN145
Rev 04/02
Did You Know...?
That the API 4000 G can accept either thermocouples or RTDs.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring and Controlling Differential Temperature
PROBLEM
Monitor the temperature differential across a heat exchanger and provide an output signal for the process control computer and a local display.
SOLUTION
Install RTDs to measure the heat exchanger inlet and outlet temperatures and connect the RTDs to an API 4001
G SA-B Non-Isolated Differential RTD to DC Transmitter module.
The API 4001 G SA-B will directly measure the temperature differential and provide an output to drive the local
display and the process control computer.
Did You Know...?
Api will do non-standard and special ranges on
all of our products.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN115
T-2
❏
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Motor Overheating Alarm and Shutdown
PROBLEM
A motor in a critical process is subject to overload and burnout. An alarm is to be sounded when the motor reaches its rated temperature. The motor is to be shut down if it exceeds its rated temperature by 10 degrees.
SOLUTION
A 10 ohm copper RTD commonly imbedded in many motors is connected to an API 1420 G RTD Input Dual
Alarm Trip module which provides two independent setpoints and two independent isolated Form C (NO/NC)
relay contacts. One set of these contacts is wired to an alarm or annunciator panel to alert the proper personnel
of the overload condition. The other set of contacts is wired in series with the coil of the motor starter and shuts
down the motor when tripped.
Setpoint 1 is adjusted to the rated temperature, and Setpoint 2 is adjusted to the rated temperature plus 10
degrees. The standard heavy-duty relay contacts are rated 7A @ 240 VAC and can directly control most
devices.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
T-3
APIAN116
Rev 04/02
Did You Know...?
All Api dual alarm modules can be configured
for HI/HI, HI/LO or LO/LO operation.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Maintaining a Constant Differential Temperature
Across a Heat Exchanger
PROBLEM
A critical process requires precise control of the change in temperature of the process fluid across a heat
exchanger.
SOLUTION
Install RTDs at the process fluid heat exchanger inlet and outlet and connect the RTDs to an API 4001G SA-B
Non-Isolated Differential RTD to DC Transmitter module.
The API 4001 G SA-B computes the differential temperature and provides a proportional 4-20 mA output signal which is used by the API 3200 G Valve/Actuator Positioner/Controller module to drive the temperature control valve open or closed as necessary to maintain the required process fluid temperature differential.
Did You Know...?
Api never charges an expediting fee and will
accept American Express, MasterCard, and Visa
credit cards.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN117
T-4
❏
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Over-Temperature Alarm with
Retransmitted Temperature Signal
PROBLEM
An extruder temperature controller has a 4-20 mA output that is capable of driving only 250 ohms. The application requires enough drive for an over-temperature alarm trip (250 ohms), an analog temperature signal for a
chart recorder (250 ohms) and a programmable logic controller (250 ohms) for a total required drive of 750
ohms.
SOLUTION
Use the 4-20 mA output of the controller to drive an API 1040 G Non-Isolated DC to Single Alarm with DC
Transmitter module.
The API 1040 G provides a relay contact output for an over-temperature alarm in the event of SCR runaway
and retransmits the temperature signal to drive the inputs of the chart recorder and the PLC. The input impedance of the API 1040 G is 50 ohms and its output can drive up to 1000 ohms.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
T-5
APIAN133
Rev 04/02
Did You Know...?
The API 1040G is available with an additional
0-1 VDC setpoint retransmit output.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
■
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Why Take the Heat When You are Under Pressure?
Sometimes it is necessary to locate a pressure sensor where it is continuously exposed to temperatures near or
exceeding its upper temperature limits. When a pressure transmitter is used, the high temperatures gradually
degrade the electronics and considerably shorten the life of the sensor. The cost of production downtime and
repair or replacement of the sensor can run into thousands of dollars.
A solution would be to use a pressure transducer in the high temperature area and an Api Strain Gauge Signal
Conditioner mounted in a remote location such as the control room. The transducer will likely withstand the
high temperatures for longer periods of time and is less costly to replace should it become necessary. The API
4059 G module provides the power to the transducer and is fully field rangeable for the excitation supply, sensitivity and DC voltage or current output. The API 4059 G can be calibrated and fine tuned to the new transducer in minutes reducing the downtime to a minimum.
Did You Know...?
The API 4059 G can drive up to four load
cells for summing applications.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN036
P-1
■
❏
■
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Troubleshooting a Pressure Transducer, Load Cell,
Strain Gauge or Bridge
Using a meter with at least 10 megaohm input impedance, measure the voltage coming from the strain gauge at the locations
shown. Sensitivity is measured in mV/V.
Positive
Negative
Meter Reading
Meter Reading
Meter Lead
Meter Lead
No pressure/load
Full pressure/load
+ Exc
– Exc
Excitation Voltage
Excitation Voltage
+ Sig
– Exc
+ ½ Excitation Voltage
½ Excitation Voltage + (½ x Excitation Voltage x Sensitivity)
– Sig
– Exc
+ ½ Excitation Voltage
½ Excitation Voltage – (½ x Excitation Voltage x Sensitivity)
+ Sig
– Sig
Zero Volts
Excitation Voltage x Sensitivity
Typical Wiring Color Code For Load Cells. Always consult manufacturer; exceptions and/or custom wire colors exist!
Manufacturer
A&D
Allegany
Artech
Beowulf
BLH
Cardinal
Celtron
Digi Matex
Dillon
Electroscale
Entran
Evergreen
Flintec
Force Measurement
Futek
General Sensor
GSE
HBM
HBM (PLC/SBE)
Interface
Kubota
LeBow
Mettler Toledo
National Scale
NCI
Nikkei
Pennsylvania
Philips
Presage Promotion
Revere
Rice Lake
Sensortronic
Sensortronic (column)
Sensotec
Strainsert
T-Hydronics
Tedea Huntleigh
Thames Side
Toledo
Totalcomp
Transducers Inc.
Weigh-Tronix
+ Excitation
Red
Green
Red
Green
Green
Green
Red
Red
Green
Red
Red
Green
Green
Red
Red
Red
Red
Green
Red
Red
Red
Red
White
Green
Red
Red
Orange
Red
Blue
Green
Red
Red
Green
Red
Red
Red
Green
Red
Green
Red
Red
Green
– Excitation
White
Black
Black
Black
Black
Black
Black
White
White
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
Black
White
Black
Blue
Black
Black
Black
Blue
Blue
White
Black
Black
Black
Black
Black
Black
Black
Black
Blue
Black
Black
Black
Black
+ Signal
Green
White
Green
White
White
White
Green
Green
Black
Green
Yellow or Green
White
White
Green
Green
Green
White
White
Green
Green
Green
Green
Green
White
White
Green
Green
Green
Red
White
Green
Green
White
White
Green
Green
Red
Green
White
Green
Green
White
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
P-2
APIAN249
Rev 04/02
– Signal
Blue
Red
White
Red
Red
Red
White
Yellow
Red
White
White
Red
Red
White
White
White
Green
Red
White
White
Blue
White
Black
Red
Green
White
White
Gray
Black
Red
White
White
Red
Green
White
White
White
Yellow
Red
White
White
Red
Shield
Yellow
Blare
Blare
Bare
Yellow
Bare
Bare
Silver
Orange
Bare
+ Sense
– Sense
Bare
Yellow
Bare
Bare
Bare
Yellow
Yellow
Bare
Yellow
Bare
Orange
Yellow
Bare
Bare
Blare
Bare
Yellow
Orange
Blare
Blare
Blare
Bare
Bare
Bare
Blare
Bare
Yellow
Blare
Orange
Orange
Yellow
Red
Yellow
Blue
Blue
Brown
Did You Know...?
The API 4059 G Isolated Strain Gauge Input
to DC Transmitter module uses state-of-theart optical isolation and has NON-INTERACTIVE zero and span controls.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Pumping System High/Low Pressure Alarm
PROBLEM
A pump is required to maintain line pressure within set tolerances. Excess pressure may indicate a blockage or
restriction in the line, while low pressure may indicate pump failure or a major leak in the line. If the pressure
exceeds or drops below the normal pressure range, a remote alarm must be activated.
SOLUTION
A loop powered pressure transducer is installed at the discharge side of the pump. The pressure transducer is
connected to an API 1090 DIN DC Input, Field Selectable, Dual Setpoint Alarm module.
The API 1090 DIN provides the loop power for the 4-20 mA pressure transducer from its built-in loop excitation supply. Setpoint 1 is adjusted to the low pressure limit, and Setpoint 2 is adjusted to the high pressure limit.
The relay contacts are wired in parallel such that if the pressure is not between the setpoints (which in this application is the safe operating condition), a single remote alarm is activated. The standard heavy-duty relay contacts are rated 7A @ 240 VAC and can directly control most devices.
Did You Know...?
Selected Api transmitters have 20V output
compliance.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN205
P-3
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Pumping System High Pressure Shutdown
PROBLEM
High head pressure is causing pump failures. If the pressure exceeds a preset limit, the pump must be shut down.
A manual reset is necessary to restart pump.
SOLUTION
A loop powered pressure transducer is installed at the discharge side of the pump. The pressure transducer is
connected to an API 1080 DIN DC Input, Field Selectable Single Setpoint Alarm module.
The API 1080 DIN provides the loop power for the 4-20 mA pressure transducer from its built-in loop excitation supply. The setpoint is adjusted to the high pressure limit. The relay contacts are wired in series with the
motor starter such that if the pressure is not below the setpoint, the pump will be stopped. It is necessary to press
the START push button to restart the pump. The standard heavy-duty relay contacts are rated 7A @ 240 VAC
and can directly control most devices.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
P-4
APIAN206
Rev 04/02
Did You Know...?
The functional test pushbutton on all Api
alarm modules will toggle the relays independent of the input signal.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Calibration of a Pressure System
PROBLEM
The pressure of an extrusion process is to be monitored and charted. To ensure ongoing accuracy, the pressure
monitoring system must be capable of frequent calibration without having to use any external test equipment.
SOLUTION
An API 4051 G M01 Strain Gauge (Bridge) Input to DC Transmitter module provides the excitation voltage for
the pressure transducer and provides the 1-5 VDC output required by the chart recorder.
The API 4051 G M01 has an internal calibration resistor to unbalance a 350 ohm bridge to an 80% of span value
when the test switch is in the CAL position, allowing for convenient and accurate calibration.
Did You Know...?
That the API 4058 G4 and the API 4059 G
are field rangeable and can drive up to four
load cells.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN220
P-5
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Calibration of a Pressure Transducer
PROBLEM
The pressure of a critical process is to be monitored by a computer. To ensure accuracy and reliability, attention
has to be paid to the entire system calibration. How can the pressure system be calibrated using the internal calibration resistor of the pressure transducer?
SOLUTION
The API 4051 G M02 Strain Gauge (Bridge) Input to DC Transmitter module provides the stable excitation
voltage for the pressure transducer and produces the required 0-10 VDC output for the computer.
The API 4051 G M02 utilizes the pressure transducer's internal calibration resistor to unbalance the bridge to a
specified value when the test switch is in the CAL position, ensuring accurate system calibration.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
P-6
APIAN221
Rev 04/02
Did You Know...?
All Api plug-in and DIN style modules are covered by a LIFETIME WARRANTY.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Phase Separator Water Level Control
PROBLEM
A phase separator is equipped with 2 pressure sensors, one located above the water level and one below. During
operation the maximum pressure differential is 10%. It is necessary to maintain the water level so that there is
a 1% pressure differential between the sensors.
SOLUTION
Use an API 4408 G A-B Math Function module to obtain the pressure differential between the transmitters.
With a pressure differential of 0-10%, the output of the API 4408 G will be 4-5.6 mA. Expand the 4-5.6 mA
signal to 4-20 mA with an API 4300 G Isolated DC to DC Transmitter module for better resolution and control.
Use the output of the API 4300G to drive an API 1000 G DC Input Single Alarm Trip module to provide a relay
contact closure to operate a water removal pump. Adjust the setpoint of the API 1000 G to maintain the differential pressure at 1%. The second set of isolated relay output contacts can be wired to an annunciator panel or
other monitoring system as desired. The standard heavy-duty relay contacts are rated 7A @ 240VAC (resistive)
and can directly control most devices.
Did You Know...?
Api isolated transmitters have 2000 VRMS
input, output, and power isolation.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN222
P-7
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Monitoring Pressure with a PLC
PROBLEM
A pressure transmitter with an internally powered 4-20 mA output must be monitored by a programmable logic
controller (PLC) for use in control of a process, but the 4-20 mA input of the PLC is also powered from the
PLC’s built-in power supply. The standard API 4300 G Isolated DC to DC Transmitter generates a 4-20 mA
output at a 20 V compliance voltage. The output of the module would conflict with the power generated by the
PLC input channel.
SOLUTION
An API 4300 G EXTSUP Isolated DC to DC Transmitter module with External Supply modification will allow
the pressure signal to be transmitted to the PLC’s powered input.
The external supply modification uses the +24 VDC power supplied by the PLC and regulates the 4-20 mA output signal in proportion to the input signal it receives from the pressure transmitter. The 2000 VRMS isolation
of the module protects against unexpected ground loops and electrical noise.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
P-8
APIAN242
Rev 04/02
Did You Know...?
The external supply modification is available on
Api modules with other input types.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Pumping System High Pressure Alarm and Shutdown
PROBLEM
A pump is supplying liquid to a process which requires the line pressure to be maintained below some maximum value. If the pressure exceeds the preset limit, the pump must be shut down and a remote alarm activated.
SOLUTION
A pressure transducer is installed in the line on the discharge side of the pump. The pressure transducer is connected to an API 1500 G Strain Gauge (Bridge) Input Single Alarm Trip module which provides two isolated
Form C (NO/NC) relay contacts. One set of these contacts is wired in series with the coil of the pump motor
starter and shuts down the pump when tripped. The other set of contacts is wired to a remote alarm or annunciator panel to alert the proper personnel of the overpressure shutdown. The setpoint is field adjustable from 0100% of the input span.
The API 1500 G provides the stable excitation voltage for the pressure transducer from its built-in excitation
supply. The standard heavy-duty relay contacts are rated 7A @ 240 VAC and can directly control most devices.
Did You Know...?
All Api alarm modules have a bi-color
(red/green) LED to indicate alarm status.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN203
P-9
❏
❏
■
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Pumping System High/High Pressure
Alarm and Shutdown
PROBLEM
A pump is supplying liquid to a process which requires the line pressure to be maintained below some maximum value. If the pressure exceeds a preset warning limit, an alarm must be activated. If the pressure exceeds
a preset shutdown limit, the pump must be stopped.
SOLUTION
A pressure transducer is installed in the line on the discharge side of the pump. The pressure transducer is connected to an API 1520 G Strain Gauge (Bridge) Input Dual Alarm Trip module which provides two independent setpoints and two independent isolated Form C (NO/NC) relay contacts. One set of these contacts is wired
to an alarm or annunciator panel to alert the proper personnel of the overpressure condition. The other set of
contacts is wired in series with the coil of the pump motor starter and shuts down the pump when tripped.
The API 1520 G provides the stable excitation voltage for the pressure transducer from its built-in excitation
supply. Setpoint 2 is adjusted to the warning pressure limit, and Setpoint 1 is adjusted to the pressure shutdown
limit. The standard heavy-duty relay contacts are rated 7A @ 240 VAC and can directly control most devices.
Both setpoints are adjustable from 0-100% of the input span.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
P-10
APIAN204
Rev 04/02
Did You Know...?
Api will do non-standard and special ranges
on all of our products.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring and Controlling Liquid Flow
From a Single Flow Meter
PROBLEM
A process requires a controlled flow rate of a liquid with a local display of that flow rate and also a chart of the
flow rate for record keeping purposes.
SOLUTION
A single flow meter can be utilized for control and monitoring of flow rate if appropriate signal conditioning is
provided. In this example, the local display and the flow controller require a 4-20 mADC signal, while the
remote chart recorder requires a 0-5 VDC signal.
The flow meter is connected to a pair of API 4380 DIN Isolated, Field Ranging DC to DC Isolators. The first
API 4380 DIN provides loop power for the flow meter from its built-in loop excitation supply, and its 4-20
mADC output drives both the local display and the flow controller. The second API 4380 DIN converts the 420 mADC signal from the flow meter to a 0-5 VDC signal which is sent to the remotely located chart recorder.
Did You Know...?
The API 4380 DIN is available with a 9-30
VDC power supply. Specify API 4380 DD.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN302
F-1
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Controlling and Recording Water Flow
PROBLEM
A process requires a controlled water flow which must also be recorded.
SOLUTION
A linear flow meter and a control valve are installed in the water line. Power for the flow meter is provided by
the +18 VDC loop excitation supply available as standard on an API 7580 G Field Selectable Isolated
Frequency to DC Transmitter module. The API 7580 G converts the frequency output of the flow meter to a 420 mA signal which is used to control and monitor the flow to the process.
The API 7580 G features 30 selectable input ranges from 0-100 Hz to 0-30 KHz, and 16 selectable output
ranges. In addition, the optical isolation protects against unwanted ground loops and electrical noise.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-2
APIAN309
Rev 04/02
Did You Know...?
Many Api transmitters & alarms come standard with a +18 VDC input loop excitation
power supply.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring Product Moved by a Conveyor
PROBLEM
The amount of product in tons per hour moved by a conveyor is required for the conveyor controller, for a local
display, and for computer monitoring. The total loop impedance is 875 ohms.
SOLUTION
A sensor which produces an output proportional to the rate of movement of product is installed on the conveyor.
An API 4300 G Isolated DC to DC Transmitter module provides power for the sensor from its built-in +18 VDC
loop excitation supply. The 4-20 mADC output of the sensor is replicated by the API 4300 G and its 4-20
mADC output loop drives the conveyor controller, a loop powered display and the computer input. The output
of the API 4300 G is capable of driving up to 1000 ohms.
Did You Know...?
The API 4300 G can be provided with a
reverse acting output.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN312
F-3
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Air Flow Measurement
PROBLEM
Measure an air velocity value, convert it and display it as an air flow value.
SOLUTION
In accordance with Bernoulli's equation the velocity of a fluid stream is proportional to the square root of the
difference in pressure (DP) between the direct impact and stagnation pressures as measured with a pitot tube.
An API 4440 G Isolated DC to DC Transmitter with Square Root Extraction module performs the square root
function on the 4-20 mA signal obtained from the P/I device and produces an interpolated 4-20 mA output signal of velocity. The API 4440 G provides power for the P/I device from its standard built-in +18 VDC loop
excitation supply and its output loop is capable of driving up to a 1000 ohm load.
Since Flow = Velocity x Area, the cross sectional area of the pipe will determine the range of the scaling on
the loop powered display. This allows the velocity value to be displayed as a flow rate. The optical isolation of
the module protects against unwanted ground loops and electrical noise.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-4
APIAN323
Rev 04/02
Did You Know...?
Api plug-in and DIN style modules have a LIFETIME WARRANTY.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Fail Safe Valve Control
PROBLEM
For safety reasons an automated normally closed valve used in a coal mining operation must go to the full open
position if the control signal from the programmable logic controller (PLC) is lost.
SOLUTION
The valve is controlled by an API 3200 G Valve/Actuator Positioner/Controller module. The input to the API
3200 G comes through an API 1000 G DC Input Single Alarm Trip module, which selects either the PLC output or a constant 20 mA output from an API 4003 GIS DC Special Transmitter module.
If the signal from the PLC drops below 4 mA, the API 1000 G will trip to a low alarm state, and select the 20
mA signal for the API 3200 G, thus commanding the valve to open fully. When the signal from the PLC is 4
mA or greater, the API 1000 G selects the PLC output signal for the API 3200 G, thus controlling valve position as normal.
Did You Know...?
Api can do input to output reversals on our
transmitters.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN326
F-5
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Flow Control with Flow Meter Feedback
PROBLEM
Operate a valve to accurately control the flow of liquid chemical in a pipeline where the feedback signal is 420 mA from a flow meter.
SOLUTION
An API 3200 G M420 Valve/Actuator Positioner/Controller module compares the 4-20 mA flow command signal from the process control computer to the 4-20 mA flow feedback signal from the flow meter.
The API 3200 G M420 positions the valve as necessary to match the feedback signal to the command signal.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-6
APIAN327
Rev 04/02
Did You Know...?
Api also offers a Model API 3200 G with a
potentiometer feedback.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Auto-Ranging Flow Meter
PROBLEM
A flow in a process must be accurately measured throughout a wide range. The flow rate is used by a PLC to
control the process. Two flow meters are utilized, one very accurate at low flow and one very accurate at high
flow. A means for automatic selection of the appropriate flow meter is required.
SOLUTION
An API 7580 G Field Selectable Isolated Frequency to DC Transmitter module is used with each flow meter to
convert the frequency output to a 0-10 VDC signal proportional to flow. An API 1080 G DC Input, Wide
Ranging, Field Selectable Single Alarm Trip module monitors the flow rate and transfers the PLC analog input
to the flow meter appropriate for that range.
The second set of relay contacts of the API 1080 G provides a PLC binary input with a closure to indicate which
flow meter is selected.
Did You Know...?
Api isolated transmitters have 2000 volt
input, output and power isolation and are covered by a LIFETIME WARRANTY.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN328
F-7
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Flow Meter Auto-Select
PROBLEM
A flow in a process must be accurately measured throughout a wide range. The flow rate is used by a PLC to
control the process. Two flow meters are utilized, one calibrated for maximum accuracy at low flow and one for
maximum accuracy at high flow. A means for automatic selection of the appropriate flow meter is required.
SOLUTION
An API 7580 G Field Selectable Isolated Frequency to DC Transmitter module is used with each flow meter to
convert the frequency output to a 0-10 VDC signal proportional to flow. Each flow meter is powered by the builtin loop excitation supply from the corresponding API 7580 G.
An API 1080 G DC Input, Wide Ranging, Field Selectable Single Alarm Trip module monitors the flow rate
and transfers the the flow meter signal corresponding to the appropriate range to the PLC analog input.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-8
APIAN329
Rev 04/02
Did You Know...?
All Api plug-in and DIN style modules are covered by a LIFETIME WARRANTY.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring and Totalizing Flow
PROBLEM
Add a totalizer to a process flow monitoring system.
SOLUTION
An API 7500 G M02 Field Selectable Isolated DC to Frequency Transmitter module is inserted in the 4-20 mA
loop between the turbine flow meter and the chart recorder.
The API 7500 G M02 provides the 9 V p-p square wave required by the totalizer system.
Did You Know...?
That Api has field selectable units to convert
frequency to voltage (API 7580 G) and voltage to frequency (API 7500 G).
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN331
F-9
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Monitoring Bi-Directional Flow
PROBLEM
Dielectric fluid is continuously pumped through the jacket of an underground electric cable. There is a holding
tank and a pump at each end of the cable and the fluid is pumped from one tank to the other and back again. A
programmable logic controller with one analog input must monitor the flow at the downstream end of the cable
as a leak detection system to satisfy regulatory requirements.
SOLUTION
A flow meter with a 4-20 mA output is installed at each end of the cable. Flow Meter #1 measures the flow when
the fluid is being pumped from Dielectric Fluid Tank #1, and Flow Meter #2 measures the flow when the fluid
is being pumped from Dielectric Fluid Tank #2. An API 1000 G DC Input Single Alarm Trip module monitors
the flow at Flow Meter #2 to select which flow meter is connected to the input of the PLC.
When there is flow at Flow Meter #2, it is selected for the PLC. When there is no flow at Flow Meter #2, Flow
Meter #1 is selected for the PLC. Thus, regardless of the direction, the PLC can monitor for a low flow condition which may be caused by leakage.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-10
APIAN332
Rev 04/02
Did You Know...?
Api plug-in modules come standard with UL,
CUL and CSA approval.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
HVAC Variable Air Volume Control
PROBLEM
The constant volume heating, ventilating and air conditioning (HVAC) system for a wet chemistry laboratory is
being converted to variable air volume (VAV) to save energy. The amount of air exhausted by four fume hoods
in the lab will vary depending upon their sash positions. A room controller must monitor the room temperature,
the quantity of air exhausted and the quantity of air supplied, and operate supply air, auxiliary supply air, and
general exhaust air valves to maintain room temperature, room pressure and a minimum number of air changes
per hour for comfort and safety. The standard room controller has 8 analog inputs, 2 analog outputs and 1 frequency output, but 3 analog outputs are required.
SOLUTION
The room temperature sensor and valve position feedback potentiometers are monitored by the eight room controller analog inputs, and the supply air and the auxiliary supply air valves are controlled by the two 1-10 VDC
analog outputs.
An API 7580 G Isolated Frequency to DC Transmitter module converts the frequency output of the room controller to a 1-10 VDC signal to control the general exhaust air valve.
Did You Know...?
The API 7580 G has field rangeable frequency inputs and DC voltage or current outputs
for total flexibility.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN334
F-11
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Monitoring and Recording Mass Flow and
Mass Flow Ratio
PROBLEM
A natural gas turbine is equipped with water injection to satisfy environmental regulations. Mass flow meters
are installed on the fuel and water injection lines to the turbine, and are monitored by a local multi-point indicator which also calculates, displays and provides an analog output of the water to fuel mass flow ratio. The fuel
mass flow and the water to fuel mass flow ratio need to be plotted on a 2-pen chart recorder and also be monitored by a computer-based facility management system. The mass flow meters and the multi-point indicator are
independently self-powered.
SOLUTION
Use an API LPI-2 Loop Powered Isolator Twin-Pack module to prevent ground loops.
The API LPI-2 allows the Facility Management System computer to monitor both the inputs and the output of
the multi-point indicator without introducing errors due to ground loops.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-12
APIAN335
Rev 04/02
Did You Know...?
That a DIN style version of the LPI-2 is also
available. Specify model DPI-2.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Controlling Damper Position
PROBLEM
A programmable logic controller (PLC) is controlling a damper motor as part of a process. The damper is
equipped with a linear potentiometer for position feedback, and the PLC has a single-ended 4-20 mA input and
generates its own 24 VDC power for the loop.
SOLUTION
An API 4003 G I EXTSUP Isolated Potentiometer to DC Transmitter module with External Supply modification measures the resistance of the damper position feedback potentiometer and transmits it to the PLC’s powered input as a 4-20 mA signal.
The external supply modification uses the +24 VDC power supplied by the PLC and regulates the 4-20 mA signal. The 2000 VRMS isolation protects against unexpected ground loops and electrical noise.
Did You Know...?
The API 4003 G will accept potentiometer
inputs from 100 ohms to 1 megaohms.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN340
F-13
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Using a Hall Effect Flow Sensor
PROBLEM
An accurate flow measurement is required at low flow rates for a process controller. A local display is also
desired.
SOLUTION
Hall effect sensors are recommended when the output frequency from a flow meter over any part of the application flow range is 15 Hz or less. This frequency typically occurs at approximately the 10 to 1 turndown point
for flow meters.
An API 7010 G Isolated Frequency to DC Transmitter module provides the DC power for the Hall Effect sensor from its built-in loop excitation supply and converts the 0-15 Hz flow signal into a 4-20 mA signal to drive
the local display and the PLC. The 2000 VRMS isolation protects against unwanted ground loops and electrical
noise.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
F-14
APIAN343
Rev 04/02
Did You Know...?
For frequency inputs of 0-100 Hz or greater,
select the API 7580 G which is field rangeable up to 0-30 KHz.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
■
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring and Totalizing Flow Meter Output
PROBLEM
The frequency output signal of a flow meter must be monitored by a DCS as well as a remotely located counter/totalizer. The counter/totalizer accepts a TTL frequency input.
SOLUTION
An API 7580 G Isolated Frequency to DC Transmitter module is connected to the frequency output of the flow
meter. The API 7580 G has a built-in loop power supply to power the current loop.
The 7580 G converts the frequency to a 4-20 mA output which is sent to the DCS and an API 7500G M02
mounted near the remote counter/totalizer. The API 7500 G M02 converts the 4-20 mA signal to a TTL frequency signal for the counter/totalizer.
Did You Know...?
Most Api plug-in style modules are hot swappable?
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN344
F-15
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Automation of a Milling Machine Operation
PROBLEM
The optimum speed at which material is fed into a mill cutter is dependent on several factors. Included among
these factors is the amount of material to be removed, the density and hardness of the material and the sharpness of the cutter. Ideally, these remain constant and the feed rate can be set and maintained throughout the operation. In the real world, however, material size, shape, density and hardness can vary greatly, and cutters become
dull with use. These changes affect the load on the motor driving the mill cutter and a feedback signal of this
load can be used to adjust the feed rate to compensate.
SOLUTION
On a milling machine equipped with load feedback on the cutter, an effective automatic table feed control system can be implemented using an API 4003 G Potentiometer to DC Transmitter module for a speed reference
signal and an API 4408 G A-B Math Function with Isolated DC Output module to reduce the speed command
to the table motor controller as cutter load increases.
Here, the milling machine is equipped with a controller which accepts a 0-10 VDC input to vary the speed of
the moving table. It is also equipped with a 0-10 VDC output signal which is directly proportional to the load
on the cutter. The API 4003 G sets the maximum speed of the table with no load on the cutter. The API 4408
G subtracts the load feedback signal from the maximum table speed signal and sends the resulting signal to the
table motor speed controller. Thus the speed of the table is reduced as the load on the cutter increases, compensating for variations in material shape, density and hardness, as well as cutter sharpness.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
S-1
APIAN401
Rev 04/02
Did You Know...?
Poor quality sockets put your process at risk.
For your convenience, Api stocks quality 8-pin
and 11-pin sockets for use with our modules.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring Mixer Speed at a Remote Computer
PROBLEM
The speed of a mixing machine must be monitored by a computer located 1500 feet away, across an electrically noisy area. The tachometer on the mixer produces 24 pulses per revolution at 15 V peak-to-peak and the mixer
runs at speeds up to 50 RPM. The computer input accepts a frequency of 0-1000 Hz at 5 V peak-to-peak.
SOLUTION
Api signal conditioning is applied at the tachometer output and at the computer input to provide noise immunity and signal compatibility.
The tachometer output (24 pulse/rev x 50 rev/min x 1 min/60 sec = 20 pulse/sec) is converted to a 4-20 mADC
signal by the API 7010 G Isolated Frequency to DC Transmitter module. At the computer, the 4-20 mADC signal is converted by the API 7500 G Field Selectable Isolated DC to Frequency Transmitter module to a frequency of 0-1000 Hz.
Did You Know...?
Api isolated transmitters have 2000 volt
input, output and power isolation.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN407
S-2
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Monitoring the Speed of Scrubbers
PROBLEM
Material is fed to a pair of scrubbers rotating at 3600 RPM. If the speed of the scrubbers decreases due to overloading, the material is not adequately cleaned.
SOLUTION
As loading on a motor increases its speed will decrease and its electrical current draw will increase. The amount
of current drawn by the motor can be monitored and used as an indication of motor speed.
Current transformers are installed on the electrical lines supplying the motors. Each current transformer is connected to an API 6010 G 5A isolated AC to DC Transmitter, which consists of a socket with a built-in shunt,
and a plug-in module. This arrangement prevents damage to the current transformer if the plug-in module is
removed from the socket without powering down the scrubbers. The DC output from each API 6010 G 5A is
connected to a computer and can be used for monitoring scrubber speed or for controlling the feed rate of material to the scrubbers for most efficient operation. The 2000 VRMS optical isolation protects against unwanted
ground loops and electrical interference.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
S-3
APIAN410
Rev 04/02
Did You Know...?
Single (API 1600 G 5A) and dual (API 1620
G 5A) alarm modules are also available.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Motor Load Controller
PROBLEM
A DC motor driving a cutter may become overheated and damaged if stock is fed into the cutter too rapidly, but
production requirements dictate maximum machine output.
SOLUTION
A 4-20 mADC signal proportional to the cutter motor load is available to provide feedback for the feed motor
controller. An API 4300 G M01 Isolated DC to DC Transmitter module reverses the feedback signal so that
increasing load on the cutter will decrease the speed of the feed motor.
Conversely, decreasing load on the cutter increases the speed of the feed motor. The feed rate is controlled to
maintain the optimum load on the cutter at all times. In addition, the 2000 VRMS isolation protects against
unwanted ground loops and electrical noise commonly found in industrial environments.
Did You Know...?
All Api plug-in and DIN style modules are covered by a LIFETIME WARRANTY.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN419
S-4
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Manual Override of Computer Control
PROBLEM
The speed of a pump is controlled by a computer. A means to operate the pump at a fixed speed is necessary
when the computer fails or is shut down for maintenance.
SOLUTION
An API 4300 G MO Isolated DC to DC Transmitter module is installed between the computer and the pump's
speed controller.
When the switch is in the AUTO position, the speed control signal from the computer is replicated by the output of the API 4300 G MO and sent to the variable frequency drive for the pump. When the switch is in the
MANUAL position, the output of the API 4300 G MO holds a constant preset value regardless of the signal
from the computer. This manual output is field adjustable via a potentiometer on top of the module.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
S-5
APIAN425
Rev 04/02
Did You Know...?
Api isolated plug-in and DIN style modules use
state-of-the-art optical isolation.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring Motor Speed with a PLC
PROBLEM
A variable speed drive has an internally powered 4-20 mA output proportional to the speed of the motor it is
driving. The motor speed must be monitored by a programmable logic controller (PLC) for use in control of a
process, but the 4-20 mA input of the PLC is also powered from the PLC’s built-in power supply. The standard
API 4300 G Isolated DC to DC Transmitter generates a 4-20 mA output at a 20 V compliance voltage. The output of the module would conflict with the power generated by the PLC input channel.
SOLUTION
An API 4300 G EXTSUP Isolated DC to DC Transmitter module with External Supply modification will allow
the drive's powered output to be transmitted to the PLC’s powered input.
The external supply modification uses the +24 VDC power supplied by the PLC and regulates the 4-20 mA output signal in proportion to the input signal it receives from the variable speed drive. The 2000 VRMS isolation
of the module protects against unexpected ground loops and electrical noise.
Did You Know...?
Many PLC inputs are isolated only from the
backplane they plug into and not channel to
channel. Api’s isolators can eliminate this
problem.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN441
S-6
❏
❏
❏
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
When Does Six Make Sense Over Four?
Many strain gauges (bridges) are located a considerable distance from the Api Strain Gauge Signal Conditioner.
The long leads add an additional lead resistance which can result in a drop in the excitation supply voltage at
the bridge and unwanted errors in the measurement. Although the excitation supply on all Api Strain Gauge
Signal Conditioners is adjustable, it is suggested a six wire bridge be used to compensate for variations in the
lead resistance due to temperature changes. The additional two wires are called Sense Leads.
The API 4059 G Isolated Strain Gauge Signal Conditioner accepts a Sense Lead input. Internal circuitry in the
module monitors the voltage drop in the bridge leads and automatically compensates the excitation voltage at
the module so the actual excitation voltage at the bridge remains constant. Due to the design of the API 4059
G, it is only necessary to connect one of the sense leads for the feature to be effective.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
W-1
APIAN537
Rev 04/02
Did You Know...?
The API 4059 G is optically isolated, has noninteractive zero and span adjustments and is
field rangeable for input, output, excitation
and tare offset. Only a screwdriver is required
to make the changes.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Truck Scale System
PROBLEM
Total vehicle weight is to be displayed, printed out and sent to a computer for record keeping purposes.
SOLUTION
A weighing platform is equipped with strain gauges at each of its four corners, and the strain gauges are wired
to an Api summing box with an API 4059 G Field Selectable Isolated Strain Gauge (Bridge) to DC Transmitter
module.
The API 4059 G plugs into a socket on the API SUM 100 board and provides excitation voltage for all four of
the strain gauges from its built-in excitation power supply. The API SUM 100 summing box combines the four
strain gauge outputs and the API 4059 G converts the signal and drives the display, the printer and the computer.
Did You Know...?
The API 4059 G is standard with non-interacting zero and span adjust
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN513
W-2
❏
❏
❏
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Automation of a Dispensing Operation
PROBLEM
Automatically control the amount and rate of feed to a hopper dispensing dog food into a container.
SOLUTION
The hopper is equipped with three strain gauge load cells which are wired to an Api summing box with an API
4059 G Isolated Strain Gauge Input to DC Transmitter Module.
The API 4059 G plugs into a socket on the API SUM 100 board and provides excitation voltage for all three
of the strain gauges from its built-in excitation power supply. The API SUM 100 summing box combines the
three strain gauge outputs and the API 4059 G converts the signal and drives the display and the PLC.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
W-3
APIAN514
Rev 04/02
Did You Know...?
The API 4059 G comes standard with field
adjustable excitation supply, tare offset, input
sensitivity and DC voltage or current output.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitoring Critical Heater Operation
PROBLEM
There is a multi-heater mold where constant temperature is critical to the quality of a product. If a single heater
in the mold goes down, the operator must know as soon as possible and shut the mold down to prevent scrap.
SOLUTION
The API 1600 G AC Input Single Alarm Trip module will accept a mAAC input from a current transformer (CT)
and provide a contact closure when the detected current falls below a preset level. For example if the output from
the CT is 60 mAAC when all three heaters are on, you would adjust the setpoint for 55 mA. Should one of the
heaters fail the total current would fall approximately 20 mA causing an alarm indication and allowing the operator to shut down the system. By using a separate alarm for the upper and lower portions of the mold the troubleshooting time for the repair crew is reduced. Scrap is also reduced by detecting and correcting the problem
before a large amount of defective product is produced.
NOTE: During the normal ON/OFF cycle of the temperature controller the low current alarm will cycle with the
heater. When the alarm fails to reset as the heaters are turned back on or if an alarm indication occurs during the
"heat" cycle one or more of the heaters have failed.
Did You Know...?
The socket which we include with the API
6010 G 5A AC to DC Transmitter module has
the shunt resistor built-in, allowing the module
to be removed without damage to the current
transformer.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN911
O-1
❏
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Motor Current Monitor and Overcurrent Shutdown
PROBLEM
Monitor and record mixer motor current and provide overcurrent shutdown.
SOLUTION
Install a properly sized current transformer in the power line feeding the motor to provide a 0-5 Amp signal for
an API 6010 G 5A AC to DC Transmitter module. Use the 4-20 mADC output to drive an API 1000 G DC
Input Single Alarm Trip module and a chart recorder. Use one set of relay contacts of the API 1000 G in the
motor starter circuit to shut down the motor if the current exceeds the setpoint.
The other set of relay contacts may be wired to an annunciator or an alarm horn if so desired. The dual SPDT
contacts are isolated and are rated 7A @ 240VAC resistive, making them capable of driving most loads directly.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
O-2
APIAN918
Rev 04/02
Did You Know...?
Api plug-in modules come standard with UL,
CUL, and CSA approval.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Monitor and Display AC Motor Load
PROBLEM
The load on a motor is to be monitored by a computer and displayed locally as a percent of full load current.
The motor is rated 200 horsepower, and operates at 460 volts, 3-phase, with a full load current of 200 amps.
SOLUTION
Install a suitable current transformer (CT) with a 10:1 ratio on one of the legs of the input power to the motor,
and connect the CT output to an Api Shunt Socket with an API 6010 G 20A AC to DC Transmitter.
Use the 4-20 mA output of the API 6010 G 20A to drive a loop powered local display and the computer input.
Scale the loop powered display for an indication of 100% at 200 amps motor load. The 2000 VRMS optical isolation protects against unexpected ground loops and electrical interference commonly found in industrial applications.
Did You Know...?
All Api alarm modules come configured as
true failsafe unless otherwise specified.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN924
O-3
❏
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Monitoring Computer and Process Status
PROBLEM
A critical process is monitored by a computer which is powered independently. If power is lost to either the
process or the computer, or if the computer locks up, an alarm is to be activated.
SOLUTION
The computer is programmed to produce an output of 100 Hz at its analog output port. This output will not be
present when power to the computer is lost or when the program locks up for any reason.
The API 1700 G Frequency Input Single Alarm Trip module monitors the 100 Hz analog output of the computer and holds its normally closed alarm trip contacts open as long as the output signal is present. If power is
lost to the computer or if the program locks up, the contacts will return to their normally closed state and the
battery powered alarm will be activated. Since the API 1700 G is powered from the same source as the process,
the alarm will also be activated if power to the process is lost.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
O-4
APIAN908
Rev 04/02
Did You Know...?
Api will do non-standard and special ranges on
all of our modules.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Converting a Control Signal for a Process
PROBLEM
A programmable logic controller (PLC) is to be used to control an electroplating system which requires a 0-100
mA signal. The analog output of the PLC is 0-10 VDC and is not modifiable.
SOLUTION
An API 4010 G HC Non-isolated DC to DC Transmitter module is connected to the 0-10 VDC analog output
of the PLC.
The API 4010 G HC converts the PLC output to the 0-100 mA required by the electroplating system.
Did You Know...
Most Api plug-in style modules are hot swappable?
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
APIAN930
O-5
■
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Frequently Asked Questions – General
1.
Do you recommend placing a fuse at the power input (115 VAC) for protection?
It is not required, but if desired, a ½ Amp Fast Blow fuse can be used for each module.
2.
We are using many different types of your signal conditioners and wish to protect the inputs and outputs from short
circuits and over voltage. How can we achieve this?
Applying a short circuit to any of the signal input terminals will not affect the modules. Exposing the signal input to high voltage
will damage the unit but using a zener diode, due to its resistance value, will cause the input range to need recalibrating. Try a
Varistor or TransZorb®. Do NOT under any circumstances short circuit the signal output, the unit can be damaged.
3.
How much can you vary the voltage using the output adjustment potentiometer on the API 9046-24?
The output adjustment potentiometer is single turn and might provide about ±1.5 volts.
4.
Which direction do we turn the deadband potentiometer screw to give the minimum and the maximum deadband?
For the minimum amount (1%), turn the potentiometer screw CCW, counter-clockwise. For the maximum amount (100%), turn
the potentiometer screw CW, clockwise.
5.
We are running a 4-20 mA signal between a chart recorder and a DCS over a distance of 5000 feet (10,000 total loop). Can
we use your isolator signal conditioner for this?
Yes, however you must select the proper gauge wire to reduce the impedance of the system
total load = impedance of the instrument + impedance of the wire
For a 4-20 mA loop, our compliance voltage is 20 V which allows a total of 1000 ohm load. Also, to prevent problems from noise,
it is recommended that you use shielded, twisted pair wires.
6.
For modules with a 4-20 mA output signal, what are the minimum and maximum output load resistance?
For the units with a 20 V compliance, the output range is 10 to 1000 ohms.
For the units with a 12 V compliance, the output range is 10 to 600 ohms.
7.
What are the relay contacts rated for in your alarm output modules for a motor load?
For inductive loads, our relay contacts are rated for 3.5 Amps Inductive at 250 VAC or 30 VDC.
8.
We have a relay alarm output and would like to adjust the set point for 5 VDC input and the reset point for 4 VDC input.
How do we adjust the set point pot and the deadband pot to do this?
The deadband is the difference in the input signal between the points at which the relay energizes and de-energizes. The midpoint
between the set and reset points is 4.5 VDC. Turn the deadband pot fully counterclockwise for minimum deadband. With a 4.5
VDC input signal, turn the set point pot until the relay changes state. Then, increase the the input signal to 5 VDC. Turn the
deadband pot clockwise until the relay changes state.
9.
For the DC output models, what are the output impedances in the voltage and current mode?
The DC outputs are FET driven and are active outputs that change depending on the mode and range.
DC output with 12 V Compliance
DC output with 20 V Compliance
CURRENT Mode
less than 600 ohms
less than 1000 ohms
VOLTAGE Mode
greater than 1000 ohms
greater than 1000 ohms
10. For your DC Input modules in the current mode, the input impedance rating is 50 ohms. For troubleshooting purposes,
is that value the same with and without power applied to the module?
Yes.
TransZorb–Reg TM General Semiconductor
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Q-1
Rev 04/02
Did You Know...?
That the functional test pushbutton on all Api
Alarm Trip modules will toggle the relays independent of the input signal.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
■
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Frequently Asked Questions – DC Inputs
1.
Do you have a signal conditioner that will source up to an 800 mA output?
No. The highest outputs available are 100 mADC non-isolated (API 4010 G) and 50 mADC isolated (API 4300 G).
The API 4300 G EXTSUP will sink up to 200 mADC with an external power supply.
2.
We have a 4-20 mA input and require 4 set points at the output. Do you have a product for this?
Yes, you can connect 2 of our API 1020 G units in series in the 4-20 mA input loop since the input impedance for
current is 50 ohms and the drop is very low.
3.
I have an API 4385 G, with an input range of 12-20 mA and an output range of 4-20 mA. How do you set the
offset so that when the input is 12 mA, the output will be 4 mA?
Percent offset = Minimum Input Value / Input Span
For this example it is 12 / 8 = 1.5 x100 = 150%. The offset chart with the API 4385 G allows for up to 100%
making this is a special. Set switches B, D, E to 3, 4, F.
4.
Do you have a DC-DC transmitter that will accept an input of ±5 VDC and provide an output of ±40 mA,
ideally a ±20 mA minimum?
No, the maximum bipolar output we can provide is ±6 mA and possibly ±10 mA on the API 4300 G BP.
5.
Can you provide a transmitter that will accept a 4-20 mA input and split the output to give two outputs that
would be 4-20 mA for output 1 and 20-4 mA for output 2?
No. You can use two transmitters in series in the input loop to give the two outputs. Select the API 4380 G for the
4-20 mA output and an API 4385 G for the 20-4 mA output.
6.
Do you have a 4-20 mA DC transmitter that can operate a load of 1800 to 2000 ohms?
The API 4300 G with a 4-20 mA output can operate a maximum load of 1000 ohms maximum with its 20 Volt
compliance. To control a load of 1800-2000 ohms, you can use the API 4300 G EXTSUP. A 42 Volt power supply
is required for the 1800 ohm load, and a 48 Volt power supply is required for the 2000 ohm load. The power supply
voltage can not be less than these requirements or there will not be enough power to reach 20 mA. Also, the power
supply can not be more than these requirements or the API 4300 G EXTSUP will be damaged.
7.
We need a 0-10 VDC input with a 0-10 VDC output and be able to adjust the output down to any lower value
from the linearized output, for example, if the input is 8 V, then the output can be 8 V or less. Is this possible?
Yes. Use the API 4300 G set up for 0-10 VDC in and 0-10 VDC output with a 10K ohm potentiometer at the signal
input. One side of the pot would wire to the (+) signal, the other side of the pot. would wire to the (–) signal and
terminal 6, then wire the wiper from the pot to terminal 5 of the module.
Continued on next page...
Did You Know...?
Api will do non-standard and special ranges
for all of our products.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
Q-2
■
❏
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Frequently Asked Questions – DC Inputs
8. Do you have a signal conditioner that will accept a 0-5 VDC input and provide an output of 0-500 mVDC?
Yes, the API 4300 G with these ranges specified at the time of ordering.
9. What is the output impedance of the API 4380 G for the 4-20 mA mode?
The output drive circuit uses a MOSFET which is an active device with an impedance of at least 100 K ohms or
greater in the current mode.
10. Can we use the API 4300 G for an input signal of 500 VDC with the negative side of the signal floating and not
at true ground?
It depends. The socket is rated to 600 VDC maximum. So with true ground on the socket at the output side, no other
point on that socket can be above 600 VDC. Even though the API 4300 G is isolated and the input will accept the 500
VDC differential between terminals 5 and 6, the socket rating is between two points anywhere on the surface.
11. We would like to use the API 4380 G DF for the 100 microsecond response time but need an input range of 0
to 25 mV. Can you do this?
Yes, however the unit will be fixed for that input and the specified output. It will not be field selectable. The new part
number will be API 4300 G M80. The API 4300 G does not offer a response time as fast as the API 4380 product.
12. What is the fastest response time that is available in the API 4385 G DF?
This version offers a response time of 5 milliseconds.
13. What is the maximum current allowed for the 18 VDC unregulated loop power supply and what does the
waveform look like?
The maximum current is 25 mA and the waveform is a filtered full wave rectified +18 V with a maximum ripple of
1.5 V p-p.
14. We are using a DCS system that requires a 4-20 mA isolated input which also provides 24 VDC to power the
loop. Do you have an isolated signal conditioner that will sink the output loop?
Yes, the API 4300 G EXTSUP. This module controls the 4-20 mA output loop but derives the power from an
external source. The connection from the output of the API 4300 G EXTSUP to the input of the DCS requires no
additional components (resistors) other than the connecting wires.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Q-3
Rev 04/02
Did You Know...?
Many PLC inputs are isolated only from the
backplane they plug into and not channel to
channel. Api’s isolators can eliminate this
problem.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
■
❏
❏
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Frequently Asked Questions – Current Loops
1. Are the API LPI-1 and the API LPI-2 UL recognized or listed ?
No. These should not be required for UL listing since the operating current and voltage are below the
covered standards.
2. We have an API DPI-2. Can we have an input of 0-20 mA and an output of 0-20 mA?
No. The loop powered device requires a minimum of 4 mA to supply power to the module.
3. For the API DPI-2, what is the maximum voltage we can use with the 4-20 mA input loop?
60 VDC is the maximum voltage that can be used to power the input loop.
Frequently Asked Questions – RTDs
1. Do you have a temperature differential unit that will measure a difference of 10° C between the two
inputs?
Yes, the API 4001 G SA-B, but the two RTDs will require very precise matching (±0.1%) and it would be
helpful to know the operating temperature point so the factory can calibrate the unit precisely.
2. We are using an API 4001 G with an input of 0-100°C and output of 0-20 mA. If the input runs above 100°C
(say 150°C) what will the output do?
The output will go higher, maybe to 21 mA but then stop there. If the output must remain at about 20 mA
and go no higher, then a special clamp circuit can be ordered.
3. Will an API 4000 G work with an input temperature range of 1000 to 2000°F?
Yes, however to utilize the charts for selecting the switch positions in the field, we need to convert °F to °C. T h i s
would give 550°C to 1100°C which can be selected from the charts.
Did You Know...?
Api never charges an expediting fee and will
accept American Express, MasterCard, and
Visa credit cards.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
Q-4
❏
■
❏
❏
❏
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Frequently Asked Questions – Thermocouples
1. Will an API 4000 G work with an input temperature range of 1000 to 2000°F?
Yes, however to utilize the charts for selecting the switch positions in the field, we need to convert °F to °C. This would
give 550°C to 1100°C which can be selected from the charts.
2. We have four of your API 4130 GL modules set for a K type thermocouple with an input range of 0-2000°F
and an output range of 4-20 mA. For an input of 0°C, the outputs on all 4 units are calibrated to 4 mA. For an
input of 2000°F, the outputs of all 4 units are calibrated to 20 mA. When the input is at 1000°F, the outputs of
each of the 4 units is different (11.8, 11.9 etc.). Can better performance be achieved?
The linearity specification is ±0.5% of span which is ±10°F for a range of 2000°F. For an input of 1000°F, the
output can vary from 990°F to 1010°F.
Also, output span / input temp range gives (20 – 4 = 16), 16 mA / 2000°F = .008 mA per °F for the entire range. For
an input of 1000°F, the output can be in the range of 11.92 mA to 12.08 mA. You are getting 11.8, 11.9 etc. which are
probably the variations in the accuracy of the four thermocouples, the extension wire, the thermocouple simulator, the
multimeter and the wiring connections.
If you want Api to verify this with our NIST traceable simulators just call customer service at 800-942-0315 for an
RMA number. The API 4000 G is even more accurate which should be used for high precision applications.
3. Can the API 1200 G provide a setpoint of 7°C and a reset point of 6°C with an overall temperature span of 0-10°C?
No. The minimum span we can operate in is a temperature difference equivalent to 5 mV of output change from the
thermocouple. For example, a type J will produce 0.000 millivolts thermoelectric voltage at 0°C and 5.268 millivolts
at 100°C. Therefore, the minimum temperature span is about 100°C. For the set point at 7°C and reset point at 6°C,
the thermocouple itself has enough of a variance (usually 5%) to it that its output will not be exactly the same. So, we
can not guarantee the repeatability of the system to trip at 7°C each time.
4. What is cold junction compensation and why is it necessary?
Cold junction compensation is required for accurate temperature measurement when using a thermocouple. A
thermocouple junction, created whenever two dissimilar metals are connected together (such as Iron and CopperNickel), produces a potential difference that varies with temperature. Thermocouples generate a millivolt signal which
increases in proportion to the difference in temperature between the hot and the cold junctions. Thermocouple tables
are based on a standard 0°C cold junction temperature. Instruments designed to read thermocouples have a
temperature sensor at the instrument connection point designed to electronically correct the reading to the 0°C
standard. A millivolt meter can’t be used to accurately read a thermocouple directly since it has no 0°C compensation.
Additional connections with dissimilar metals create new thermocouple junctions also adding to the error if their
temperature varies.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Q-5
Rev 04/02
Did You Know...?
That the API 4000 G can accept either thermocouples or RTDs.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
❏
❏
■
❏
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Frequently Asked Questions – Frequency
1. Do you have a product that can provide an output signal of 5 KHz, 50% duty cycle, 20 mA max and 24 V p-p
max with no input?
Yes, the API 7500G M03.
2. We have an application which requires a signal conversion of ½ Hz to 6 Hz input to a DC output. Do you have
a signal conditioner to do this?
·
No. The minimum input frequency range that we offer is 0 to 15 Hz.
3. We have a PNP proximity sensor powered by the +18 VDC input loop supply of the Api 7580 G. It reads the
flywheel gear teeth and a sends a frequency signal to the API 7580 G and works fine throughout the range.
However, if the wheel is stopped with a tooth in-line with the sensor, the output will stay high (PNP output) and
the API 7580 G output will go high to the maximum of the range. How can we prevent this?
The +18 volt loop supply from the API 7580 G has a maximum ripple of 1.5 V p-p so the high output from the prox
sensor will have this ripple. The signal input to the 7580 G has a capacitor in series so any DC input charges, then
opens the circuit. However with the ripple, there will be a 50/60 Hertz signal present.
You must use a magnetic pick-up in place of the proximity sensor since the amplitude signal from the magnetic
pick-up will decrease as the flywheel slows down and when stopped, there will be no amplitude even with a tooth
in-line with the sensor head. The magnetic pick-up generates its own signal as the field changes. When the field stops
changing, the signal goes to zero.
4. Can you provide a module that will generate an output frequency (square wave) that we can vary between 55
and 75 Hz with No input signal?
Yes. Our API 7500 G M03 with a modification to utilize the test circuit that is adjustable with the test range
potentiometer. The test circuit is disabled internally and is always on. With the span pot set to the middle of the range,
adjust the test range pot to give an output of 65 Hz which is the center point for 55-75 and serves to orient the
window. Then, use the span pot to adjust the output frequency from 55 to 75 (the window is actually about 40 Hz).
The zero pot and the cutout pot are disabled and have no effect.
5. We have a 4-20 mA signal and want to convert it to a pulsed output of 0-270 pulses/minute so we can drive a
counter. Can you do this?
Yes. Convert the output to Hertz (cycles/second) so 270 / 60 = 4.5 Hz. Our API 7500 G SS has an output range of
0-5 Hz and the span pot can adjust down by 10 % to allow for 0-4.5 Hz. The counter, which will trip on either rising
or falling edges, can be set up to count at the edge of each cycle (square wave).
Did You Know...?
For frequency inputs of 0-100 Hz or greater,
select the API 7580 G which is field rangeable up to 0-30 KHz.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
Q-6
❏
❏
■
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Frequently Asked Questions – Strain Gauges
1. What is the performance over the entire range for the API 4058 G? How well does the output track the input
over the entire range?
·
The linearity specification for the API 4058 G is ±0.1% of span. The API 4059 G is the same.
2. What does the 70 msec response time mean on the API 4059 G? Are faster times available? If a signal with pulse
width of less than 70 msec is present at the input, will it show up at the output?
The output will track the input with about a 70msec delay. The API 4059 G can be factory set to 10 msec minimum.
If a pulse of less than the response time (70 msec or 10 msec) occurs at the input, the output will not reveal it, or there
might be a small blip.
3. Is the API 4058 G approved for Europe’s CE standards?
No, but if the entire system in the application needs to be CE approved, then our unit does not.
4. Our weighing scale uses a strain gauge with an excitation voltage of 10 V and a calibrated sensitivity of 2.2447
mV/V. The API 4058 G has been set up for an input of 0-20 mV by the OEM which supplied the equipment to
us. Are these switch settings correct?
If you are using all of the available range of the strain gauge, the maximum input signal to the module will be 22.447
mV which is beyond the switch settings. So, you need to verify the maximum load conditions and change the switch
settings to 0-25 mV if required.
5. When trying to adjust the span potentiometer on an API 4058 G the output signal, which drives a numerical
display, jumps by too large an amount when barely turning the potentiometer screw. What is wrong?
The resolutions of the zero and span potentiometers are related to the amount of turns of the pot screw and the amount
of adjustment capability (±15%). The factory can provide a finer resolution which means that the potentiometer screw
must be turned more to have the same amount of change in signal, however the total amount of adjustment
capability of the potentiometer will be reduced.
6. We have a load cell application with a very low output signal and we would like to drive the cell with a higher
excitation voltage (the load cell is rated 24 VDC max. and 10 VDC typical). Can your modules provide an
excitation voltage higher than 10 VDC?
No, however you can use an API 9046-24 power supply with 24 VDC output to excite the load cell. The output
signal would then be higher for the same load which could then drive an API 4310 G, narrow input span.
7. We have your API 4059 G and are trying to set up the unit to allow a ±30 mV input signal (3mV/V load cell
operating in the tension/compression mode) with a ±10 V output signal. The unit does not have a code to select
for the input of ±30 mV. Can we have this input option?
No, the API 4059 G will not accept ±30 mV and the span potentiometer does not have enough adjustment for this
special range. You can lower the excitation voltage to 7 VDC so that you would have a ±20 mV input (7V excitation
x 3 mV/V = 21 mV). If isolation is not necessary, select the API 4058 G which allows a ±30 mV to ±10 VDC
input/output combination.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Q-7
Rev 04/02
Did You Know...?
The API 4059 G is standard with non-interacting zero and span adjust.
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
❏
❏
■
❏
❏
■
❏
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Frequently Asked Questions – Strain Gauges
8. What would be the input range for our load cell that has a maximum capacity of 200 pounds, an excitation
voltage of 10 VDC, a rating of 2 mV/V, operating in the tension/compression mode, and measuring 75 pounds
full scale?
Full scale input to our module would be (75 / 200 ) x 10 V x 2 mV/V = 7.5 mV. For tension and compression, the
signal will be ±7.5 mV.
9. We have two load cells and wish to wire them to your API 4059 G. How do we accomplish this?
Connect both load cells in parallel. Each load cell would be wired the same, excitation voltage and return signals, to
the API 4059 G so there would be two sets of wires to terminals 4 & 5 and 7 & 8.
10. We have an API 4058 G and need to set it up with a load cell for tension and compression operation. The load
cell has a sensitivity of 2 mV/V and a maximum capacity of 50 pounds. Our largest load will be 40 pounds. We
also need the output to provide a 4-20 mA signal. What are the switch settings?
The maximum input signal to our module will be ±(40/50 x Excitation Voltage x 2 mV/V). This input value needs to
be close to one of the available input ranges for the API 4058 G. If we had an excitation voltage of 10 V, then the
input signal would be ±16 mV which would be 25% too low for the ±20 mV range since the zero & span
potentiometers only have ±15% adjustment. The excitation voltage should be lowered to provide an input signal that
is close to our next lower range of ±10 mV. If the excitation voltage is set to 6 V, then the signal from the load cell
will be ±(40/50 x 6 x 2) = 9.6 V. Then we can adjust the zero and span potentiometers to allow a 4 mA output for a
–9.6 V input and a 20 mA output for a +9.6 V input.
11. We use an API 4059 G with a load cell that comes with a calibration resistor to simulate 80% of full load. The
load cell will be used in both the tension and compression modes. How do we connect the calibration resistor
to your API 4059 G?
For both tension and compression modes, the signal will be bipolar (±). The tension mode (negative) places the
resistor between the (+) excitation signal, terminal 7, and the (–) signal input, terminal 5. This will simulate –80% of
full tension load. To calibrate the output, adjust the zero potentiometer to set the output to 10% of span.
The compression mode (positive) places the resistor between the (+) excitation signal, terminal 7, and the (+) signal
input, terminal 4. This will simulate +80% of full compression load. To calibrate the output, adjust the span
potentiometer to set the output to 90% of span.
Total span is ±100 % (bipolar) = 200% of full capacity, with 100% being the midpoint.
–80% = 20% / 200% = 10%
+80% = 180% / 200% = 90%
12. We have 4 load cells in our application each with a resistance of 350 ohms. Can we use your API 4051 G in this
application?
No. The API 4051 G excitation circuit can only source 30 mA maximum. Since your 4 load cells require about 114
mA total current, you must use either the API 4058 G or the API 4059 G.
Did You Know...?
The API 4059 G comes standard with field
adjustable excitation supply, tare offset, input
sensitivity and DC voltage or current output.
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Rev 04/02
Q-8
❏
❏
❏
■
❏
❏
■
General Info
Temperatur e
Pr essur e
Flow
Speed
Weighing
Pr ocess
Manufacturer of Quality Signal Conditioners Transmitters & Isolators
Application Notes
Frequently Asked Questions – Valve Actuator
1. We have an API 3200 G M01 with a 0-10 VDC feedback signal and a 0-10 VDC control input. How do
we calibrate this?
·
Set the deadband potentiometer fully CCW (counter-clockwise). Apply the minimum signal (0 VDC) to both
the feedback (terminals 6 & 7) and the control (terminals 4 & 5). Turn the zero potentiometer screw until
the relay changes state and has continuity from the common to the close position. The relay LED will be red
to indicate the close position.
Now apply the maximum signal (10 VDC) to both the feedback and the control inputs. Turn the span
potentiometer screw until the relay changes state and has continuity from the common to the open position.
The relay LED will be green signaling the open position.
Finally, apply 5 VDC to both the feedback and the control inputs. The relay contact should have no
continuity and the relay LED should be off. Using your multimeter to measure across terminals 4 and 7 (the
positive connections for both the feedback and the control) should be within the minimum deadband (about
1% of span) for no relay change of state. Change the feedback voltage to the desired deadband position.
Rotate the deadband potentiometer CW (clockwise) until the relay changes state.
2. We would like to compare two signals, each is 4-20 mA. If the DIFFERENCE between the two signals
at any point in the 4-20 mA range becomes greater than the deadband configured, an output relay
must change state to provide for an alarm. Do you have a product to accomplish this?
·
Yes. Order the API 3200 G M420. The deadband can be adjusted to allow for a 1 to 25% difference in the
two signals. If the difference is less than the deadband configured, then both relay contacts will not have
continuity with the common terminal. If the feedback 4-20 mA loop is higher than the control input, then
continuity will be from common (9) to open (11). If the feedback is less, than then continuity will be from
the common (9) to closed (10).
FREE APPLICATION ASSISTANCE
Call
Customer Service
800-942-0315
Q-9
APIAN
Rev 04/02
Did You Know...?
All Api plug-in and DIN-style modules are covered by a LIFETIME WARRANTY.