Master HP

MHT 100

INPUT

Rated power

Voltage

Voltage tolerance

Frequency

Frequency tolerance

Power factor

Input current

Current distorsion

Soft start

BY PASS

Rated voltage

Voltage tolerance

Rated frequency

Frequency tolerance

Rated current

Number phases

Back-feed protection

Overload capacity Inx10ms

100000 VA

400 Vac three-phase Vac

+ 20% - 25%

50/60 Hz with autorange

45/65 Hz

0,99

141 A

<3%

0-100% in 10

400 Vac three-phase selectable 380 and 415

± 15% (selectable from ± 10% to ± 25% from front panel)

50/60 Hz (autorange)

± 2% (selectable from ± 1% to ± 5% from front panel)

141 A

3 yes

14

OUTPUT and INVERTER OUTPUT

Rated power

Active power

Number phases

Crest factor (Ipeak/Irms)

Waveform

Dynamic stability

Frequency

Voltage distortion with distorcing load

Voltage distortion with linear load

Frequency stability

Overload

100000 VA

90000 W

3 + N

3 : 1

Sinewave

± 5% in 5 ms same as the input (autorange)

<3%

<1%

± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present

110 % 125% 150% 200% of the rated current for 10' / 1' / 7

RECTIFIER OUTPUT

Ripple <1%

BATTERIES

Type

Maximum recharge current

ENVIRONMENTAL

Altitude max

Color

Remote controls

Safety compliance

EMC conformance

Protection rating

Line-Interactive/Smart Active efficiency

Noise

Maintenance-free sealed lead-acid

0.2xC10

1000 m

Dark grey RAL 7035

EPO and bypass

EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU

EN 62040-2 and Directive 2014/30/EU

3 up to 98,5%

63 dBA at 1 m

© RPS Spa - Member of the Riello Elettronica Group

Master HP

MHT 100

Remote signals

Operating temperature

Relative humidity

DATA

Weight

Dimensions (h w d) voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA)

0 ÷ 40 °C

95% no condensing

656 kg

1900x800x850 mm

© RPS Spa - Member of the Riello Elettronica Group