Variant Modular system for fault location, testing and

Variant Modular system for fault location, testing and
Variant
Cable test van
Variant
Modular system for fault location, testing
and diagnosis
■■ Expandable modular design
■■ High reliability thanks to redundant
system architecture
■■ easyGO® user interface
■■ ARM® multi-shot pre-location
■■ Powerful 0.1 Hz VLF test up to 18 uF
■■ Autonomous operation with Li-Ion
battery power
DESCRIPTION
With the new Variant series, Megger provides a fully
equipped measuring station for all VDE-compliant cable testing and fault location on PVC, PE, VPE and paper-insulated
cables in the voltage range up to 33 kV.
System components:
During the development of the Variant system, special attention was paid to reliability and availability:
■■Teleflex VX with ARM® multi-shot technology
■■A fail-safe, modular system
■■easyGO® and expert operating mode
■■Emergency operation in case of system control failure
The system also has the advantage of being simple to service.
Heavy extension reels come installed so they can be easily
extended. Electronic components are in place so that testing and calibration can be easily performed from the control
room.
■■System control with operating mode switch, phase switch
and safety system
■■Surge generator up to 3500 J
■■HV operating unit BPS
■■ARM® filter ARM 300
■■MFM 10 sheath fault location system
■■FLG 200 audio frequency generator
■■Ergonomic work station with desk and drawer cabinet
Variant
Cable test van
TECHNICAL DATA*
Variant cable fault location system
Standard – base module
Options
Operation
Manual switching system NSF, air insulated HV switch with integrated safety system,
5.7“ color TFT, connectors for external insulation tester (1000 V max.)
1-phased or 3-phased
Resistance-capacitance measurement
Integrated Iso module; measurement via HV lead
Measurement range
1 Ω … 2 GΩ; 0 … 19.9 μF
Test voltage
6 / 500 / 1000 V
3-phase activation via Teleflex connection cable
DC voltage test
Variant 80 kV
Output voltage/current
Variant 110 kV
0 … 110 kV, IN 7 mA, Imax 50 mA
0 … 80 kV, IN 11 mA, Imax 50 mA
Cable sheath testing
BPS 5000
Output voltage
Output current
0 … 10 kV
800 mA
MFM 10
Output voltage
0 … ±10 kV
Integrated pre-location method 0 … ±10 kV
Output current
750 mA
(optional with integrated audio frequency module
8.44 kHz)
VLF voltage testing according to DIN VDE 0276
VLF CR 54 test attachement
Voltage
0 … 54kVeff
Max. load
21 µF @ 18 kVeff @ 0.1 Hz
8 µF @ 36 kVeff @ 0.1 Hz
5 µF @ 54 kVeff @ 0.1 Hz
VLF Sin 54 test attachement
Voltage
0 … 54kV
Max. load
5 µF @ 36 kVeff @ 0.01 Hz
1 µF @ 36 kVeff @ 0.1 Hz
PD diagnosis in combination with VLF Sin 54
tan ð measurement in combination with
VLF Sin 54
Cable fault location – pre-location methods
Pulse reflectometry, ARM® Multishot, Decay method, ICE current pulse method, IFL intermittent fault localisation, ARM® Burning
Pulse reflectometry (Teleflex)
Operating mode
Symmetric/asymmetric reflection measurement,
differential and comparative measurement,
IFL (for intermittent faults)
Automatic functions
Determination of cable length and fault distance,
amplification, measurement range
Amplification
Default: - 37 ... + 37 dB, ProRange: max. 22 dB
Measurement range
20 m … 1280 km (@ v/2 = 80 m/μs)
Runtime factor v/2
10 ... 149.9 m/µs
Precision
0.1 % of measurement range
Sampling rate
400 MHz
Output impedance
10 ... 2000 Ω
Pulse width
20 ns … 10 µs
Pulse voltage
30 ... 160 V
2
Variant
Cable test van
Variant cable fault location system
Standard – base module
Options
HV prelocating methods
ARM® Multishot
Surge voltage
0 … 32 kV
(15 fault patterns per surge
pulse)
ICE current pulse method
1-phase
Surge voltage
0 … 32 kV
Surge module SZG 60 (only for 110 kV version)
Surge voltage 0 … 60 kV
ARM® Multishot
(only for 110 kV version with option SZG 60)
Surge voltage
0 … 60 kV
ICE current pulse method 3-phased
Surge voltage
0 … 32 kV
ICE current pulse method 3-phased
(only for 110kV version with option SZG 60)
Surge voltage
0 … 60 kV
Decay method
Surge voltage
0 ... 80 kV
Decay method
Voltage
0 … 110 kV
ARM® burning
Output voltage
Output current
0 … 15 kV
6 A
Fault conversion
BPS burning
voltage / current
6.0 A
1.5 A
0.8 A
0.5 A
110 A
28 A
0 … 1.2 kVDC
4 kVDC
8 kVDC
15 kVDC
0 ... 60 VAC
0 ... 240 VAC
Cable fault location – pinpointing methods
Acoustic pinpointing
Voltage levels
0 … 8, 0 … 16, 0 … 32 kV
Surge module C4 Surge module CD Surge module 60 kV SWG 2000
0 … 2 / 4 kV
0 … 8 / 16 / 32 kV
0 … 60 kV
8 / 16 / 32 kV
Surge energy
1750 J @ 8, 16 and 32 kV
1150 J
Surge sequence
individual surge,
6 – 20 surges/min
Step voltage method
low hazard potential due to
clocked DC voltage
3500 J
BPS 5000
Output voltage
Output current
1800 J
0 … 10kV
800 mA
MFM 10
0 … 10 kV
max. 750 mA
(optional with integrated audio frequency module
8.44 kHz)
Surge wave receiver
digiPHONE+
Step voltage receiver
ESG NT
Surge wave and step voltage receiver in one device
digiPHONE+ NT
Twisted field method, line tracing
Audio frequency generator (mobile or fully integrated)
10 W, 50 W oder 200 W
491, 982, 8440 Hz (also simultaneous)
SignalSelect®, automatic impedance change
Audio frequency receiver
Sheath fault pinpointing with AC audio frequency
direct or capacitive
3
2000 J
Variant cable fault location system
Standard – base module
Options
Safety and protection equipment
Earth monitoring
Operational earth and protective earth to station earth
Step voltage
Auxiliary earth to vehicle chassis
Discharge system
SafeDischarge technology
Monitoring
Key switch, rear door switch, emergency stop switch
(int./ext.) EN 50191
Supply voltage
Overvoltage protection, undervoltage protection,
residual current circuit breaker
Isolating transformer
2 kVA (for LV part of the system)
9 kVA (for whole system)
Connection of the measurement system
HV connection
1 x 3-phase cable
Multi:
50 m (motor drums)
3 x 1-phase cable
Economy: 50 m (manual drums)
Comfort: 50 m (motor drums)
Pro:
50 m (slip ring motor drums)
LV connection
Economy: 50 m mains/protective earth cable,
10 m auxiliary earth (manual drums)
Comfort: 50 m mains/protective earth cable (belt pull)
Pro: 50 m mains/protective earth cable (motor
drums)
Teleflex connection
External emergency
safety unit
3-phase coaxial cable 50 m (manual, belt pull or motor)
Economy: 15 m connection cable
50 m connection cable (manual, belt pull or motor)
System supply and operating conditions
Input voltage
230 V, 50 Hz
120 V, 60 Hz
Synchronous generator 7 kVA (with power take-off)
Travel power generator 5 / 8 kVA
(electronic regulation/ without power take-off)
Li-ion battery power including charging electronics 5 kVA
Input voltage
5 / 7 kVA (depending on options)
Electric heating 2000 W
Operating
temperature
HV unit: - 20˚ C ... + 55˚ C,
control unit: - 10˚ C ... + 55˚ C
Air conditioning on car roof
Storage temperature
- 25˚ C ... + 60˚ C
Weight
Standard Version
Starting from 650 kg
Depending on options up to 1250 kg
* We reserve the right to make technical changes .
SALES OFFICES
Megger GmbH
Obere Zeil 2
D-61440 Oberursel
Germany
T 0049 6171 92987-0
Einfo@megger.de
VARIANT_DS_EN_V02
Seba Dynatronic
Mess- und Ortungstechnik GmbH
Dr.-Herbert-Iann-Str. 6
96148 Baunach
Germany
T 0049 9544 68-0
Eteam.international@megger.de
www.megger.com
ISO 9001
The word ‘Megger’ is a registered trademark.
4