PAX Digital Data Sheet/Manual PDF

PAX Digital Data Sheet/Manual PDF
MODEL PAX - 1/8 DIN DIGITAL INPUT PANEL METERS
z COUNT, DUAL COUNTER, RATE AND SLAVE DISPLAY
z 0.56" RED SUNLIGHT READABLE DISPLAY
z VARIABLE INTENSITY DISPLAY
z 10 POINT SCALING FOR NON-LINEAR PROCESSES (PAXI)
z FOUR SETPOINT ALARM OUTPUTS (W/Option Card)
z RETRANSMITTED ANALOG OUTPUT (W/Option Card) (PAXI)
z COMMUNICATION AND BUS CAPABILITIES (W/Option Card) (PAXI)
z BUS CAPABILITIES; DEVICENET, MODBUS, AND PROFIBUS-DP
z CRIMSON PROGRAMMING SOFTWARE (PAXI)
z ETHERNET(W/ External Gateway) (PAXI)
C
U
L
R
z NEMA 4X/IP65 SEALED FRONT BEZEL
US LISTED
IND. CONT. EQ.
51EB
GENERAL DESCRIPTION
The PAX Digital Input Panel Meters offer many features and performance
capabilities to suit a wide range of industrial applications. Available in three
different models, PAXC Counter/Dual Counter, PAXR Rate Meter and the PAXI
which offers both counting and rate in the same package. Refer to pages 4 - 5 for
the details on the specific models. The PAXC and PAXR offer only the Setpoint
Option, while the PAXI is the fully featured version offering all the capabilities
as outlined in this bulletin as well as a slave display feature. The optional plugin output cards allow the opportunity to configure the meter for present
applications, while providing easy upgrades for future needs.
The meters employ a bright 0.56" LED display. The meters are available with
a red sunlight readable or standard green LED display. The intensity of the
display can be adjusted from dark room applications up to sunlight readable,
making it ideal for viewing in bright light applications.
The meters accept digital inputs from a variety of sources including switch
contacts, outputs from CMOS or TTL circuits, magnetic pickups and all
standard RLC sensors. The meter can accept directional, uni-directional or
Quadrature signals simultaneously. The maximum input signal varies up to 34
KHz depending on the count mode and function configurations programmed.
Each input signal can be independently scaled to various process values.
The Rate Meters provide a MAX and MIN reading memory with
programmable capture time. The capture time is used to prevent detection of false
max or min readings which may occur during start-up or unusual process events.
The meters have four setpoint outputs, implemented on Plug-in option cards.
The Plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), or
either quad sinking or quad sourcing open collector logic outputs. The setpoint
alarms can be configured to suit a variety of control and alarm requirements.
Communication and Bus Capabilities are also available as option cards for
the PAXI only. These include RS232, RS485, Modbus, DeviceNet, and
Profibus-DP. Readout values and setpoint alarm values can be controlled
DIMENSIONS In inches (mm)
through the bus. Additionally, the meters have a feature that allows a remote
computer to directly control the outputs of the meter. With an RS232 or RS485
card installed, it is possible to configure the meter using Red Lion’s Crimson
software. The configuration data can be saved to a file for later recall.
A linear DC output signal is available as an optional Plug-in card for the PAXI
only. The card provides either 20 mA or 10 V signals. The output can be scaled
independent of the input range and can track any of the counter or rate displays.
Once the meters have been initially configured, the parameter list may be
locked out from further modification in its entirety or only the setpoint values
can be made accessible.
The meters have been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5" (127) W.
CAUTION: Risk of electric shock.
ORDERING INFORMATION
Meter Part Numbers
0
PAX
0
C - Counter/Dual Counter
R - Rate Meter
I - Counter/Dual Counter/
Rate Meter/Slave Display
0 - Red, Sunlight Readable Display
1 - Green Display
0 - 85 to 250 VAC
1 - 11 to 36 VDC, 24 VAC
Option Card and Accessories Part Numbers
TYPE
MODEL NO.
PAXCDS
Optional
Plug-In
Cards
PAXCDC
Accessories
Accessories
SFCRD*
ICM8
DESCRIPTION
PART NUMBERS
Dual Setpoint Relay Output Card
PAXCDS10
Quad Setpoint Relay Output Card
PAXCDS20
Quad Setpoint Sinking Open Collector Output Card
PAXCDS30
Quad Setpoint Sourcing Open Collector Output Card
PAXCDS40
RS485 Serial Communications Card with Terminal Block
PAXCDC10
Extended RS485 Serial Communications Card with Dual RJ11 Connector
PAXCDC1C
RS232 Serial Communications Card with Terminal Block
PAXCDC20
Extended RS232 Serial Communications Card with 9 Pin D Connector
PAXCDC2C
DeviceNet Communications Card
PAXCDC30
Modbus Communications Card
PAXCDC40
Extended Modbus Communications Card with Dual RJ11 Connector
PAXCDC4C
Profibus-DP Communications Card
PAXCDC50
Analog Output Card
PAXCDL10
Crimson 2 PC Configuration Software for Windows 98, ME, 2000 and XP
SFCRD200
Communication Gateway
ICM80000
*Crimson software is available for free download from http://www.redlion.net/
Shaded areas are only available for the PAXI
PANEL CUT-OUT
GENERAL METER SPECIFICATIONS
1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LED
2. POWER:
AC Versions:
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)
DC Versions:
DC Power: 11 to 36 VDC, 14 W
(derate operating temperature to 40° C if operating <15 VDC and three
plug-in option cards are installed)
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).
3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected
4. KEYPAD: 3 programmable function keys, 5 keys total
5. USER INPUTS: Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Commons: Not isolated
Logic State: Jumper selectable for sink/source logic
INPUT STATE
SINKING INPUTS
Ω pull-up to +12 V
5.1 KΩ
SOURCING INPUTS
Ω pull-down
5.1 KΩ
Active
VIN < 0.9 VDC
VIN > 3.6 VDC
Inactive
VIN > 3.6 VDC
VIN < 0.9 VDC
Response Time: 6 msec. typical; function dependent. Certain resets, stores
and inhibits respond within 25 µsec if an edge occurs with the associated
counter or within 6 msec if no count edge occurs with the associated
counter. These functions include
,
,
,
,
,
, and
. Once activated, all functions are latched for
50 msec min. to 100 msec max. After that period, another edge/level may
be recognized.
6. MEMORY: Nonvolatile E2PROM retains all programmable parameters and
display values.
7. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2
No. 1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/8843/UL
CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical
equipment for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air
Electromagnetic RF fields
EN 61000-4-3 Level 3; 10 V/m
80 MHz - 1 GHz
Fast transients (burst)
EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference
EN 61000-4-6 Level 3; 10 V/rms
150 KHz - 80 MHz
Simulation of cordless telephones ENV 50204 Level 3; 10 V/m
900 MHz ±5 MHz
200 Hz, 50% duty cycle
Emissions to EN 50081-2
RF interference
EN 55011
Enclosure class A
Power mains class A
Note:
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. relative humidity noncondensing
Altitude: Up to 2000 meters
9. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
10. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
11. WEIGHT: 10.1 oz. (286 g)
MODEL PAXC - 1/8 DIN COUNTER
z 6-DIGIT LED DISPLAY (Alternating 8 digits for counting)
z DUAL COUNT QUAD INPUTS
z UP TO 3 COUNT DISPLAYS
z SETPOINT ALARM OUTPUTS (W/Plug-in card)
PAXC SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES:
To determine the maximum frequency for the input(s), first answer the
questions with a yes (Y) or no (N). Next determine the Count Mode to be
used for the counter(s). If dual counters are used with different Count Modes,
then the lowest frequency applies to both counters.
FUNCTION QUESTIONS Single: Counter A or B Dual: Counter A & B
Are any setpoints used?
N
Is Counter C used?
N
COUNT MODE
(Values are in KHz)
(Values are in KHz)
Count x1
34
25
15
13
12
9
Count x2
17
13
9
7
9
7
5
4
Quadrature x1
22
19
12
10
7
6
4
3.5
Quadrature x2
Quadrature x4
17
8
13
6
9
4
7
3
7
6
4
3.5
N
Y
Y
N
18
Y
N
Y
N
N
Y
Y
N
Notes:
1. Counter Modes are explained in the Module 1 programming section.
2. Listed values are with frequency DIP switch set on HI frequency.
Y
Y
7.5
ANNUNCIATORS:
A - Counter A
B - Counter B
C - Counter C
- Upper significant digit display of counter
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
COUNTER DISPLAYS:
Maximum display: 8 digits: ± 99999999 (greater than 6 digits display
Alternates between high order and low order.)
INPUTS A and B:
DIP switch selectable to accept pulses from a variety of sources including
switch contacts, TTL outputs, magnetic pickups and all standard RLC
sensors.
LOGIC: Input trigger levels VIL = 1.5 V max.; VIH = 3.75 V min.
Current sinking: Internal 7.8 KΩ pull-up to +12 VDC, IMAX = 1.9 mA.
Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max. @ 28 VDC,
VMAX = 30 VDC.
Filter: Damping capacitor provided for switch contact bounce. Limits
input frequency to 50 Hz and input pulse widths to 10 msec. minimum.
DUAL COUNT MODES:
When any dual count mode is used, then User Inputs 1 and/or 2 will
accept the second signal of each signal pair. The user inputs do not have
the Logic/Mag, HI/LO Freq, and Sink/Source input setup switches. The
user inputs are inherently a logic input with no low frequency filtering.
Any mechanical contacts used for these inputs in a dual count mode
must be debounced externally. The user input may only be selected for
sink/source by the User Jumper placement.
MODEL PAXR - 1/8 DIN RATE METER
z 5-DIGIT LED DISPLAY
z RATE INDICATION
z MINIMUM/MAXIMUM RATE DISPLAYS
z SETPOINT ALARM OUTPUTS (W/Plug-in card)
PAXR SPECIFICATIONS
ANNUNCIATORS:
- Rate
- Maximum (High) Rate
- Minimum (Low) Rate
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
RATE DISPLAY:
Accuracy: ±0.01%
Minimum Frequency: 0.01 Hz
Maximum Frequency: 34 KHz
Maximum Display: 5 Digits: 99999
Adjustable Display (low) Update: 0.1 to 99.9 seconds
Over Range Display: “
”
INPUT A:
DIP switch selectable to accept pulses from a variety of sources including
TTL outputs, magnetic pickups and all standard RLC sensors.
LOGIC: Input trigger levels VIL = 1.5 V max.; VIH = 3.75 V min.
Current sinking: Internal 7.8 KΩ pull-up to +12 VDC, IMAX = 1.9 mA.
Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max. @ 28 VDC,
VMAX = 30 VDC.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9 KΩ @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
MODEL PAXI - 1/8 DIN COUNTER/RATE METER
z COUNT, RATE AND SLAVE DISPLAY
z 6-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
z VARIABLE INTENSITY DISPLAY
z 10 POINT SCALING (FOR NON-LINEAR PROCESSES)
z FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
z RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
z COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
z BUS CAPABILITIES; DEVICENET, MODBUS, AND PROFIBUS-DP
z CRIMSON PROGRAMMING SOFTWARE
PAXI SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES TABLE
To determine the maximum frequency for the input(s), first answer the
questions with a yes (Y) or no (N). Next determine the Count Mode to be used
for the counter(s). If dual counters are used with different Count Modes, then
the lowest frequency applies to both counters.
FUNCTION QUESTIONS Single: Counter A or B (with/without rate) or Rate only Dual: Counter A & B or Rate not assigned to active single counter
Are any setpoints used?
N
N
N
N
Y
Y
Y
Y
N
N
N
N
Y
Y
Y
Y
Is Prescaler Output used?
N
N
Y
Y
N
N
Y
Y
N
N
Y
Y
N
N
Y
Y
Is Counter C used?
N
Y
N
Y
N
Y
N
Y
N
Y
N
Y
N
Y
N
Y
COUNT MODE
(Values are in KHz)
(Values are in KHz)
Count x1
34
25
21
17
18
15
13
Count x2
17
13
16
12
9
7
Quadrature x1
22
19
20
17
12
10
Quadrature x2
17
13
16
12
9
7
8
(Values are in KHz)
(Values are in KHz)
11
13
12
13
11
9
8
7
9*
7*
9*
7*
5*
11
10
7*
6*
6*
5*
4*
6
7*
6*
6*
5*
4*
3.5 *
Quadrature x4
8
6
8
6
4
3
4
3
Rate Only
34
N/A
21
N/A
34
N/A
21
N/A
7.5
9
7
4*
5*
4*
3.5 *
3.5 *
3*
3.5 *
3*
Notes:
1.
2.
3.
4.
5.
Counter Modes are explained in the Module 1 programming section.
If using Rate with single counter with direction or quadrature, assign it to Input A for the listed frequency.
* Double the listed value for Rate frequency.
Listed values are with frequency DIP switch set on HI frequency.
Derate listed frequencies by 20% during serial communications. (Placing a 5 msec. delay between serial characters will eliminate the derating.)
ANNUNCIATORS:
A - Counter A
B - Counter B
C - Counter C
- Rate
- Maximum (High) Rate
- Minimum (Low) Rate
- Upper significant digit display of counter
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
RATE DISPLAY:
Accuracy: ±0.01%
Minimum Frequency: 0.01 Hz
Maximum Frequency: see Max Signal Frequencies Table.
Maximum Display: 5 Digits: 99999
Adjustable Display (low) Update: 0.1 to 99.9 seconds
Over Range Display: “
”
COUNTER DISPLAYS:
Maximum display: 8 digits: ± 99999999 (greater than 6 digits display
Alternates between high order and low order.)
INPUTS A and B:
DIP switch selectable to accept pulses from a variety of sources
including switch contacts, TTL outputs, magnetic pickups and all
standard RLC sensors.
LOGIC: Input trigger levels VIL = 1.5 V max.; VIH = 3.75 V min.
Current sinking: Internal 7.8 KΩ pull-up to +12 VDC, IMAX = 1.9 mA.
Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max. @ 28 VDC,
VMAX = 30 VDC.
Filter: Damping capacitor provided for switch contact bounce. Limits
input frequency to 50 Hz and input pulse widths to 10 msec. minimum.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9 KΩ @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
DUAL COUNT MODES:
When any dual count mode is used, then User Inputs 1 and/or 2 will
accept the second signal of each signal pair. The user inputs do not have
the Logic/Mag, HI/LO Freq, and Sink/Source input setup switches. The
user inputs are inherently a logic input with no low frequency filtering.
Any mechanical contacts used for these inputs in a dual count mode
must be debounced externally. The user input may only be selected for
sink/source by the User Jumper placement.
PRESCALER OUTPUT:
NPN Open Collector: ISNK = 100 mA max. @ VOL = 1 VDC max. VOH = 30
VDC max. With duty cycle of 25% min. and 50 % max.