ESIM264
Valid for ESIM264 v7.11.18 and up
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
• GSM alarm & management system ESIM264 (also referenced as alarm system, system or device) has radio transceiver operat ing in GSM 850/900/1800/1900 bands.
• DO NOT use the system where it can be interfere with other devices and cause any potential danger.
• DO NOT use the system with medical devices.
• DO NOT use the system in hazardous environment.
• DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
• DO NOT attempt to personally repair the system.
• System label is on the bottom side of the device.
GSM alarm system ESIM264 is a device mounted in limited access areas. Any system repairs must be done only by quali fied, safety aware personnel.
The system must be powered by main 16-24V 50 Hz ~1.5A max or 18-24V 1,5A max DC power supply which must be approved by LST EN 60950-1 standard and be easily accessible nearby the device. When connecting the power supply to the system, switching the pole terminals places does not have any affect.
Any additional devices linked to the system ESIM264 (computer, sensors, relays etc.) must be approved by LST EN 60950-1 standard.
Main power supply can be connected to AC mains only inside installation room with automatic 2-pole circuit breaker capable of disconnecting circuit in the event of short circuit or over-current condition. Open circuit breaker must have a gap between con nections of more than 3mm and the disconnection current 5A.
Phase
Null
PE
AC/DC
AC 230V
50 Hz/DC 24V
USB cable
ESIM364
Mains power and backup battery must be disconnected before any installation or tuning work starts. The system installa tion or maintenance must not be done during stormy conditions.
Backup battery must be connected via the connection which in the case of breaking would result in disconnection of one of battery pole terminals. Special care must be taken when connecting positive and negative battery terminals. Switching the pole terminals places is NOT allowed.
In order to avoid fire or explosion hazards the system must be used only with approved backup battery.
The device is fully turned off by disconnecting 2-pole switch off device of the main power supply and disconnecting backup battery connector.
Fuse F1 type – Slow Blown 3A. Replacement fuses have to be exactly the same as indicated by the manufacturer.
If you use I security class computer for setting the parameters it must be connected to earth.
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that the product must not be disposed of together with household waste. To prevent possible harm to human health and/or the environ ment, the product must be disposed on in an approved and environmentally safe recycling process. For further information on how to dispose of this product correctly, contact the system supplier, or the local authority responsible for waste disposal in your area.
The buyer must agree that the system will reduce the risk of fire, theft, burglary or other dangers but does not guarantee against such events.
“ELDES UAB” will not take any responsibility re garding personal or property or revenue loss while using the system. “ELDES UAB” liability ac cording to local laws does not exceed value of the purchased system. “ELDES UAB” is not affiliated with any of the cellular providers therefore is not responsible for the quality of cellular service.
The system carries a 24-month warranty by the manufacturer “ELDES UAB”. Warranty period starts from the day the system has been purchased by the end user. The warranty is valid only if the system has been used as intended, following all guidelines listed in the manual and within speci fied operating conditions. Receipt must be kept as a proof of purchase date.
The warranty is voided if the system has been exposed to mechanical impact, chemicals, high humidity, fluids, corrosive and hazardous environ ments or other force majeure factors.
If you require more detailed information on your system or in case of system failure occurrence, please, contact your alarm system installer.
This document describes basic configuration and usage of alarm system ESIM264. It is very impor tant to read the user manual before starting to use the system.
1. ESIM264 ................................................qty. 1
2. Microphone .........................................qty. 1
3. SMA antenna ......................................qty. 1
4. Backup battery connection wire qty. 1
5. user manual ........................................qty. 1
6. Resistor 5,6kΩ .....................................qty. 6
7. Resistor 3,3kΩ .....................................qty. 6
For full system configuration and control, please refer to ESIM264 installation manual lo cated at www.eldes.lt/en/download
1.1 Short Description of Main Definitions ...............................................4
1.2 EKB2 Keyboard Overview .......................................................................5
1.3 EKB3 Keyboard Overview .......................................................................7
1.4 Partitions ......................................................................................................7
2.1 Electrical & Mechanical Characteristics .............................................8
2.2 Main Unit, LED & Connector Functionality ......................................9
2.3 Wiring Diagrams .....................................................................................10
2.3.1 General Wiring .........................................................................10
2.3.2 Zone Connection Types ........................................................10
3.1 Setting Up Date & Time ........................................................................11
3.2. Arming, Disarming the System & Turning Off the Alarm .........12
3.2.1 Arm, Disarm & Turn off the Alarm by Phone Call .........12
3.2.2 Arm by SMS Message ............................................................13
3.2.3 Disarm & Turn off the Alarm by SMS Message .............13
3.2.4 Arm by EKB2/EKB3 Keyboard .............................................14
3.2.5 Disarm & Turn off the Alarm by EKB2/EKB3 Keyboard 14
3.2.6 Arm by iButton® Key ..............................................................15
3.2.7 Disarm & Turn off the Alarm by iButton® Key ...............15
3.2.8 Arm by EWK1 – Wireless Keyfob .......................................16
3.2.9 Disarm & Turn off the
Alarm by EWK1 – Wireless Keyfob ...................................16
3.3 Activating STAY Mode ..........................................................................17
3.3.1 Arm by EKB2 Keyboard in STAY Mode Manually .........17
3.4 Alarm Indications & Viewing Violated Zones / Tampers ...........19
3.5 Bypassing & Unbypassing Violated Zone ......................................20
3.6 Viewing System Information ..............................................................21
3.7 Managing Periodical System Information .....................................21
3.8 Viewing Zone & PGM Output Information ....................................22
3.9 Managing Temperature Information ..............................................23
3.10 Trouble Indications ................................................................................24
3.11 Controlling Electrical Appliances .....................................................25
3.12 Turning ON/OFF the Electrical
Appliances for a Determined Time Period ....................................26
Copyright © “ELDES uAB”, 2012. All rights reserved
It is not allowed to copy and distribute information in this document or pass to a third party without advanced written authorization by “ELDES UAB”. “ELDES UAB” reserves the right to update or modify this document and/or related products without a warning. Hereby,
“ELDES UAB” declares that this GSM alarm and management system ESIM264 is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The declaration of conformity may be consulted at www.eldes.lt
4
ESIM264 is an alarm system for private houses, cottages, village houses, garages, warehouses and other buildings, also capable of turning on/off the electrical appliances by SMS message and alarm system keyboard. This alarm system provides a simple thus effec tive way of use.
The system consists of:
• ESIM264 alarm system device;
• Up to 4 EKB2/EKB3 keyboards;
• Wired and/or wireless sensors: movement sensors, magnetic door sensors, smoke sensors etc.;
• Other devices: indoor/outdoor sirens, heating, lighting, gates etc.
For more details on ESIM264 system, please, consult with your alarm system installer.
The following table provides the explanation of main definitions which are met in this user manual.
Definition
System; alarm system
SMS
Keyboard
EKB2
EKB3
User phone number;
User 1... 5
System phone number user password iButton® key
Zone
PGM output
Partition
Description
ESIM264 device
Short Message Service text
Device with a set keys allowing to configure & control the system, view violated zones & system troubles
Model of LCD keyboard
Model of LED keyboard
Phone number of the user allowed to control the system
Phone number of the SIM card inserted in ESIM264 device
4-digit combination intended for system arming/disarming using a keyboard
Small metal tab containing a unique ID code intended for system arming/disarming
Alarm system input for wired and wireless sensor connection
Alarm system output for connection of electrical appliances (heating, lighting, gates etc.)
Section dividing one alarm system into two independent parts software-wise
EKB2 is an LCD keyboard intended for using with ESIM264 alarm system.
...
One menu level back / cancel
Menu navigation – up
Menu navigation – down
Confirm (enter) value
Value typing
Keyboard partition switch / minus symbol for entering negative temp. value
Additional menu / minus symbol for entering negative temp. value
GSM Signal
Strength
System Status
Message
System
Trouble
Indication
Custom
Keyboard
Partition
Title
Temperature
STAY
BYP
TBL
20,2
0
C ready
GARAGE
00:45
Digital Clock
Main Screen
View
Bypass Mode
Indication
Stay Mode
Indication
Fig. No. 1
Icon / Message Description
Delay
zone violated when system is disarmed.
Exit
Delay countdown initiated.
System is armed and menu is locked.
System is disarmed and menu is unlocked
+ CONFIGURATION
MODE
BURGLARY ALARM
Configuration mode activated.
Delay, Instant
or
Follow
zone violated when system is armed.
Icon / Message
24 ALARM
FIRE ALARM
TAMPER ALARM
READY
NOT READY
ARMED
STAY
BYP
TBL
Description
24H
zone violated.
Fire
zone violated.
Tamper violated
System is ready to be armed.
System is not ready to be armed – one or more zones / tampers violated.
System is armed (optional feature).
Stay
mode activated
One or more zones bypassed
One or more system troubles are present
MANUAL ELDES ESIM264 V2.1 5
EKB2 LCD screen is intended for displaying alarm system status messages and alerts. Message
is displayed on the screen that no zones are violated or no troubles are present and the system is prepared for arming. Message
(and
) shows up in case of zone violation or if system troubles are present. The alarm system cannot be armed until the troubles are removed or violated zone (-s) is restored, bypassed or set up to operate under
Force
mode. The following troubles allow system arming when present:
•
•
•
• backup battery problem; main power supply failure; date & time not set;
GSM connection problem.
The built-in mini buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for success fully carried out configuration, one long beep – for invalid configuration. In addition, the mini-buzzer continuously provides short beeps in case of alarm.
EKB2 can be used even in dark premises as the LCD screen and keys are illuminated continuously. In case of alarm the keyboard il lumination level is boosted and stays in this state until the system is disarmed. The illumination level lowers down in 3 minutes after the last key-touch while the system is disarmed.
6
EKB3 is a LED keyboard intended for using with ESIM264 alarm system.
ARMED
READY
SYSTEM
BYPS
112
Alarm system is armed /Configuration mode
System is prepared for arming
System troubles / valid command is being entered
Zone bypass mode
Violated zone
ARMED
READY
SYSTEM
1
6
5
4
3
2
A B
11
12
9
10
8
BYPS
7
1
4
7
*
2
5
8
0
3
6
9
#
STAY
BYPS
INST
CODE
Fig. No. 2
[BYPS]
[CODE]
[*]
[#]
[0] ... [9]
[STAY]
[INST]
Zone bypass mode
Additional options - system trouble list / violated high zone indication / violated tamper indication
Configuration mode (when typed as a 1st character) / cancel command (when typed as a 2nd character) / keyboard partition switch (if enabled)
Confirm (enter) command
Command typing
Manual
Stay
mode activation
(currently inactive)
The green LED
indicates that no zones are violated or no troubles are present and the system is prepared for arming. LED
lights up or flashes in case of zone violation or if system troubles are present. The alarm system cannot be armed until the troubles are removed or violated zone (-s) is restored, bypassed or set up to operate under
Force
mode. The following troubles allow system arming when present:
•
•
•
• backup battery problem; main power supply failure; date & time not set;
GSM connection problem.
The built-in mini buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for success fully carried out configuration command, one long beep – for invalid configuration command. In addition, the mini-buzzer continu ously provides short beeps in case of alarm.
EKB3 keys have a LED back-light, therefore it is possible to use this keyboard even in dark premises. In case of alarm the keyboard back-light turns on and lasts until the system is disarmed. The back-light lasts for 3 minutes after the last key-stroke while the system is disarmed.
Your alarm system may be divided into 2 partitions:
partition 0 & partition 1
. Each system partition operates independently from each other, therefore dividing the system into partitions allows to use 1 alarm system unit to secure 2 different areas, for example: office and warehouse, house and garage. By default configuration, the system is NOT divided into 2 partitions and all user phone numbers, user passwords, keyboards, iButton® keys, zones are assigned to
partition 0.
MANUAL ELDES ESIM264 V2.1 7
8
Electrical & Mechanical Characteristics
Main Power Supply
Current in Standby without External Sensors and Keyboard
Recommended Backup Battery Voltage, Capacity
Recommended Backup Battery Type
Maximum Battery Charge Current
GSM Modem Frequency
Cable Type for GSM Antenna Connection
Number of Zones on Board
Nominal Zone Resistance
Number of PGM Outputs on Board
PGM Output C1-C4 Circuit
16-24V 50 Hz ~1.5A max / 18-24V up to 80mA
12V; 1,3-7Ah
Lead-Acid
900mA
850/900/1800/1900MHz
Shielded
6 (ATZ mode: 12)
5,6kΩ (ATZ Mode: 5,6kΩ and 3,3kΩ)
4
1 R
OUT
1,5A max
Open Collector Output.
Output is pulled to COM when turned ON.
Voltage – 30V; Current – 100mA;
Connected to COM
500mA up to 30 meters unshielded
13,8V DC
1A
Maximum Commuting PGM Output Values
BELL: Siren Output when Activated
BELL: Maximum Siren Output Current
BELL: Maximum Cable Length for Siren Connection
BELL: Cable Type for Siren Connection
AUX: Auxiliary Equipment Power Supply Voltage
AUX/BELL: Maximum Accumulative Current of Auxiliary Equip ment and Siren
AUX: Maximum Cable Length for Auxiliary Equipment Connection
AUX: Cable Type for Auxiliary Equipment Connection
BUZ: Maximum Current of Mini Buzzer
BUZ: Power Supply Voltage of Mini Buzzer
BUZ: Cable Type for Mini Buzzer Connection
Dimensions
Operating Temperature Range
Supported Temperature Sensor Model
DATA: Maximum Cable Length for 1-Wire® Communication
DATA: Cable Type for 1-Wire® Communication
Supported iButton® Key Model
Maximum Supported Number of Keyboards
Y/G: Maximum Cable Length for RS485 Communication
Y/G: Cable Type for RS485 Communication
MIC: Maximum Cable Length for Microphone Connection
MIC: Cable Type for Microphone Connection
Wireless Transmitter-Receiver Frequency *
Wireless Communication Range*
Maximum Supported Number of Wireless Devices*
Event Log Size
Maximum Supported Number of Zones
Maximum Supported Number of PGM Outputs
Cable Type for Zone and PGM Output Connection
Communications
Supported Protocols
* only for system ESIM264 with module EWT1 up to 100 meters unshielded
150mA
5V DC unshielded
140x100x18mm
20...+55 0 C
Maxim®/Dallas® DS18S20, DS18B20 up to 30 meters unshielded
Maxim®/Dallas® DS1990A
4 x EKB2 / EKB3 up to 100 meters unshielded up to 2 meters unshielded
868 Mhz
Up to 30m in premises; up to 150m in open areas
16
500 events
44
44 unshielded
SMS, Voice calls. GPRS network, RS485, CSD
Ademco Contact ID®, 4+2, EGR100, Kronos
Main Unit Functionality
GSM MODEM GSM network 850/900/1800/1900MHz modem
SIM CARD
DEF uSB
FuSE F1
ANTENNA
MODuLES
EWT1
SIM card slot / holder
Pins for restoring default settings
Mini uSB port
3A fuse
GSM antenna SMA type connector
Slots for EA1, EA2 or EPGM8 module
Slots for EWT1 wireless module
USB
DEF
C4
C3
PRG
Z5 Z6
SIM
CARD
EWT1
Z1
Z2
Z3
Z4
Z5
LED Functionality
NETWORK GSM network signal strength
C2, C1 PGM output C1, C2 status – on/off
Z6
PWR
STATuS
Zone Z1 state – alarm/restore (ATZ mode: Z1 and Z7)
Zone Z2 state – alarm/restore (ATZ mode: Z2 and Z8)
Zone Z3 state – alarm/restore (ATZ mode: Z3 and Z9)
Zone Z4 state – alarm/restore (ATZ mode: Z4 and Z10)
Zone Z5 state – alarm/restore (ATZ mode: Z5 and Z11)
Zone Z6 state – alarm/restore (ATZ mode: Z6 and Z12)
Power supply status
Micro-controller status
Z1 CO Z2 Z3 CO
Fig. No.3
COM
BELL
BELL+
AuX
AuX+
AC/DC
AKu
AKu+
Connector Functionality
Z1 Z6
COM
DATA
Y
G
+5V
MIC
MIC+
BuZ
BuZ+
C1 C4
GSM
MODEM
ANTENNA
SMA
MODULES
AKU+
AKU-
BELL- BELL+
Security zones
Common terminal for all zones
1-Wire® interface for iButton® key & temperature sensor connection
Temperature sensor power supply contact (+5V)
Microphone negative terminal
Microphone positive terminal
Mini buzzer negative terminal
Mini buzzer positive terminal
PGM outputs
RS485 interface for communication (yellow wire)
RS485 interface for communication (green wire)
Common return terminal
Siren negative terminal
Siren positive terminal
Negative power supply terminal for auxiliary equipment
Positive power supply terminal for auxiliary equipment
Main power supply terminal
Backup battery negative terminal
Backup battery positive terminal
MANUAL ELDES ESIM264 V2.1 9
Z1 CO Z2 Z3 CO
BELL- BELL+
AKU+
AKU-
Backup Battery
12V 1.3-7Ah
Metal box
PE contact
Z1 Z2
Fig. No. 4
~16-24V
Fuse 500 mA
~230V 50Hz
Z5 Z6
BUZ
MIC iButton® key reader
Temperature sensor
Relay module
SIREN
500 mA max.
EPGM1
EKB3
Type 1 Type 2 Type 3 Type 4
EKB2
Type 5
Normally open contact with 5,6KΩ end of line resistor
Normally closed con tact with 5,6KΩ end of line resistor
Tamper and 5,6KΩ end of line resistor and 3,3KΩ end of line resistor with normally closed contact
ATZ Mode: 5,6KΩ end of line resistor and nor mally closed contact with 3,3KΩ end of line resistor and normally closed contact
ATZ Mode: Tamper,
5,6KΩ end of line resistor, 5,6KΩ end of line resistor with nor mally closed contact and 3,3KΩ end of line resistor with normally closed contact.
Fig. No. 5
10
System configuration described in this chapter is based on default system parameter values. Your alarm system installer may have changed those values. For more details, please, contact your alarm system installer.
This chapter provides a description of basic configuration and use of ESIM264 alarm system by the following methods:
•
•
•
•
•
SMS message;
Phone call;
EKB2 keyboard;
EKB3 keyboard; iButton® key.
SMS
EKB2
EKB3
In order to configure and control the system using SMS message, send the text command to the ESIM264 system phone number from one of the preset user phone numbers. In this user manual the underscore symbol ”_” represents one space character. Every underscore symbol must be re placed by a single space character. There must be no spaces or other un necesary characters at the beginning and at the end of the message.
– 4digit SMS password set by your alarm system installer.
The system configuration and control by EKB2 keyboard is performed by navigating throughout the menu section list dis played on LCD screen. To navigate in the menu path, touch ↓ , ↑ keys to select the desired menu section and touch
OK
key to open the selected section. To enter a required value, use
0... 9
keys and touch
OK
key for value confirmation or cancel/ go one menu section back by touching
← key. The value can be typed in directly by touching
0... 9
keys while highlighting the desired menu section. EKB2 menu type is “circle”, therefore when the last section in the menu list is selected, you will be brought back to the beginning of the list after touching the
↓
key. In this user manual, the menu path is provided under
“tree” view by starting at main screen view. In this user manual valid parameter values and range are indicated in brackets.
The system configuration and control by EKB3 keyboard is performed by entering a valid configuration command using the number keys
0... 9
and [#] key for confirmation. Some commands require [BYPS], [CODE] and [STAY] keys as well. The structure of standard configuration command is a combination of digits. In this user manual configuration commands, valid param eter values and range are indicated in brackets.
: When the alarm system is connected to a monitoring station the date and time are set automatically. The system retrie ves this data from the monitoring station by itself.
SMS
1. Send the following SMS message to the phone number of ESIM264 alarm system:
XXXX_YYYY.MM.DD_HR:MN
Value: YYYY– year; MM – month, range – [01... 12]; DD – day, range - [01... 31];
HR – hours, range – [00... 23], MN – minutes, range – [00... 59];
Example: 1111_2011.12.15_13:45
2. The system will reply with confirmation by SMS message to user phone number who sent the SMS message after the date & time is set successfully.
EKB2
Navigate through the following menu path using
OK
and arrow keys and enter the date and time values using the number keys:
OK
→
DATE/TIME SET
→
[YYYY-MM-DD_HR:MN]
Value: YYYY– year; MM – month, range – [01... 12]; DD – day, range - [01... 31];
HR – hours, range – [00... 23], MN – minutes, range – [00... 59];
Example: 2011-12-15 13:45
MANUAL ELDES ESIM264 V2.1 11
Before arming the system it is necessary to close all doors and windows in the secured area and move yourself away from the move ment detection field.
Don’t stand in
movement sensor detection zone Close all doors
Close all windows
Close all doors
Fig. No. 6
: User must leave the secured area before arming the system by phone call.
1. To arm the system, disarm the system or turn off the alarm, make a phone call to the system‘s phone number from any out of 5 preset user phone numbers. The phone call is free charge as the system rejects it and performs arming or disarming after-wards. When arming the system, it rejects the phone call after 2 rings, when disarming
- the system rejects the phone call immediately.
2. After the system is successfully armed or disarmed, it will reply with confirmation by SMS message to the user phone number who made a phone call.
CALL
SMS user
ESIM264
Fig. No. 7
3. When attempting to arm the system in case of violated zone / tamper presence, the system will reply with vio lated zone / tamper number. For more details, please refer to chapter
12
SMS
1. Leave the secured area.
2. To arm the system, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_ARM1 or XXXX_ARM2 or XXXX_ARM1,2
Value: 1 – partition 0; 2 – partition 1; 1,2 – both partitions
Example: 1111_ARM1
3. After the system is successfully armed, it will reply with confirmation by SMS message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 8
4. When attempting to arm the system in case of violated zone / tamper presence, the system will reply with vio lated zone / tamper number. For more details, please refer to chapter
SMS
1. The system will initiate the
Entry Delay
countdown (by default – 15 seconds) after the user has entered the secured area.
Entry Delay
countdown is intended for user to enter a valid user password before the alarm is caused.
2. To disarm the system or turn off the alarm, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_DISARM1
or
XXXX_DISARM2
or
XXXX_DISARM1,2
Value: 1 – partition 0; 2 – partition 1; 1,2 – both partitions
Example: 1111_DISARM1
3. After the system is successfully disarmed, it will reply with confirmation by SMS message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 9
MANUAL ELDES ESIM264 V2.1 13
EKB2
EKB3
1. To arm the system, enter any out of 10 available 4-digit user passwords using the number keys:
1
4
7 8
0
2
5
3
6
9
Fig. No. 10
[NNNN]
Value: NNNN – 4digit user password
EKB2 Example: 1111OK
EKB3 Example: 1111
2. The system will initiate the
Exit Delay
countdown (by default – 15 seconds) intended for user to leave the secu red area. The countdown is indicated by short beeps provided by keyboard built-in mini-buzzer (if any).
3. After the system is successfully armed, it will reply with confirmation by SMS message to
User 1
phone number
(by default).
SMS user
ESIM264
Fig. No. 11
EKB2
EKB3
1. The system will initiate the
Entry Delay
countdown (by default – 15 seconds) after the user has entered the secured area.
Entry Delay
countdown is intended for user to enter a valid user password before the alarm is caused.
2. To disarm the system or turn off the alarm, enter any out of 10 available 4-digit user passwords using the num ber keys:
1
4
7
2
5
8
0
3
6
9
Fig. No. 12
[NNNN]
Value: NNNN – 4digit user password
EKB2 Example: 1111OK
EKB3 Example: 1111
3. After the system is successfully disarmed, it will reply with confirmation by SMS message to
User 1
phone number (by default).
SMS user
ESIM264
Fig. No. 13
14
1. To arm the system, touch the iButton® key reader by any out of 5 iButton® keys:
Fig. No. 14
2. The system will initiate the
Exit Delay
countdown (by default – 15 seconds) intended for user to leave the secu red area. The countdown is indicated by short beeps provided by ESIM264 mini-buzzer (if any).
3. After the system is successfully armed, it will reply with confirmation by SMS message to
User 1
phone number
(by default).
SMS user
ESIM264
Fig. No. 15
1. The system will initiate the
Entry Delay
countdown (by default – 15 seconds) after the user has entered the secured area.
Entry Delay
countdown is intended for user to enter a valid user password before the alarm is caused.
2. To disarm the system or turn off the alarm, touch the iButton® key reader by any out of 5 iButton® keys:
Fig. No. 16
3. After the system is successfully disarmed, it will reply with confirmation by SMS message to
User 1
phone num ber (by default).
SMS user
ESIM264
Fig. No. 17
MANUAL ELDES ESIM264 V2.1 15
EWK1
1. To arm the system, press 1 out of 4 EWK1 buttons (by default – button) assigned to arm the alarm system.
Arm the system
Fig. No. 18
2. The system will initiate the
Exit Delay
countdown (by default – 15 seconds) intended for user to leave the secured area.
3. After the system is successfully armed, it will reply with confirmation by SMS message to
User 1
phone number (by default).
SMS user
ESIM264
Fig. No. 19
EWK1
1. The system will initiate the
Entry Delay
countdown (by default – 15 seconds) after the user has entered the secu red area.
Entry Delay
countdown is intended for user to enter a valid user password before the alarm is caused.
2. To disarm the system or turn off the alarm, press 1 out of 4 EWK1 buttons (by default – button) assigned to disarm the alarm system
Disarm the system
Fig. No. 20
3. After the system is successfully disarmed, it will reply with confirmation by SMS message to
User 1
phone number (by default).
SMS user
ESIM264
Fig. No. 21
16
EKB2
EKB3
EWK1
Stay
mode allows the user to remain in the secured area after arming the system. In
Stay
mode, the system does not cause the alarm when the zones, set up to operate under this mode, become violated. This mode is usually used when arming the system before night.
There are two ways to activate
Stay
mode:
- This mode is activated automatically in case the user does not leave the secured area (if
Delay
zone is not violated) during
Exit Delay
countdown when arming the system.
The system goes into
Stay
mode after the user opens an additional menu or presses [STAY] key and enters a valid user password by EKB2/EKB3 keyboard.
There is no
Exit Delay
countdown when activating S
tay
mode manually.
Stay
mode status is indicated in the main screen view of EKB2.
Stay
mode is NOT activated when arming the system by phone call or SMS message.
Delay Zone Becomes Instant in Stay Mode
feature may be enabled on your system. In that case the alarm will be caused instantly instead of
Entry Delay
countdown being initiated if a
Delay
zone becomes violated while the system is operating in
Stay
mode. For more details, please, contact your alarm system installer.
EKB2
1. Navigate through the following menu path using P2 and arrow keys and enter a valid user password using the number keys to arm the system in Stay mode manually:
P2
→
ENTER STAY
→
[NNNN]
→
OK
Value: [NNNN] 4digit user password
2. After the system is successfully armed, it will reply with confirmation by SMS message to User 1 phone number
(by default).
SMS user
ESIM264
For more details on how to disarm & turn off the alarm by EKB2 keyboard, please refer to chapter
MANUAL ELDES ESIM264 V2.1 17
EKB3
1. Arm the system in
Stay
mode manually by entering the following combination using [STAY] and number keys:
[STAYnnnn]
Value: nnnn 4digit user password
Example: STAY1111
2. After the system is successfully armed, it will reply with confirmation by SMS message to
User 1
phone number
(by default).
SMS user
ESIM264
For more details on how to disarm & turn off the alarm by EKB3 keyboard, please refer to chapter
18
By default configuration, the system makes a phone call to
User 1
in case of alarm. By answering the call, the user is able to listen on his/her mobile phone to what is happening in area surrounding ESIM264 unit. This feature is pro vided by a microphone (if any) connected to ESIM264.
The phone call is made to the next preset user (presumably to
User 2
) in a row in case the previous user was unreach able (was “out of radio coverage”, provided “busy” signal or did not answer the call). This routine is continued until one of the preset users is reachable, but will not go in a circle i. e. return to
User 1
if none of the users were reachable. In addition, the system will not make a phone call to the next preset user in a row if the previous user was reachable, but rejected the phone call. The phone calls will cease to be made to the user as soon as the system is disarmed.
CALL user
ESIM264
Fig. No. 22
Your alarm system installer may have configured the system to make the phone calls to the next available user even if the previous one has answered the call.
SMS
By, default configuration the system sends an SMS message containing violated zone or tamper number in case of alarm. The SMS message can also contain a star * character next to the violated tamper in case the tamper violation is caused due to wireless connection loss between ESIM264 and a wireless device (if any).
This SMS message is sent to
User 1
. The system sends the SMS message to the next preset user (presumably to User
2) in a row only if the previous user was unreachable (the system did not receive a successful SMS message delivery confirmation in 20 seconds from the recipient). This routine is continued until one of the preset users is reach able, but will not go in a circle i. e. return to
User 1
if none of the users were reachable. The SMS messages will cease to be sent to the user as soon as the system is disarmed.
SMS user
ESIM264
Fig. No. 23
See also chapter
Your alarm system installer may have configured the system to send the SMS message to the next available user even if the previous one has received it.
MANUAL ELDES ESIM264 V2.1 19
EKB2
The built-in EKB2 mini-buzzer and ESIM264 mini-buzzer (if any) provide short beeps continuously in case of alarm.
In addition, the LCD screen back-light level is boosted and the alarm message (depending on violated zone type or tamper violation) is displayed in the main screen view of EKB2 screen. The mini-buzzer can be silenced by disarm ing the system using any method. Navigate through the following menu path using
OK
and arrow keys to view the violated zone or tamper number:
VIEW VIOLATED ZONE:
VIEW VIOLATED TAMPER:
OK
→
VIOLATED ZONES
→
ZONE [1... 44]
OK
→
VIOLATED TAMPERS
→
TAMPER [1... 44]
EKB3
The built-in EKB3 mini-buzzer and ESIM264 mini-buzzer (if any) provide short beeps continuously in case of alarm. In addition, the violated zone number is indicated by illuminated zone LED or flashing
LED (if the violated zone number is above 12). The violated tamper number is indicated by illuminated
LED. The mini-buzzer can be silenced by disarming the system using any method.
For more details on EKB3 violated high zone & tamper number indication, please, refer to chapter
By default configuration, the siren (if any) provides continuous alarm sound for 1 minute in case of alarm. The fire alarm is indicated by pulsing siren alarm sound. Siren alarm sound can be silenced by disarming the system using any method.
Arming the system is disabled while there’s at least 1 violated zone. Bypassing the zone allows to temporally disable a particular violated zone and arm the alarm system after-wards.
EKB2
Navigate through the following path using OK and arrow keys to bypass a violated zone (-s):
Bypass a zone:
Bypass all zones:
OK
→
BYPASS
→
BYPASS LIST [1... 3]
→
ZONE [1... 44]
→
BYPASS
OK
→
BYPASS
→
BYP VIOLATED ZONES
Navigate through the following path using OK and arrow keys to unbypass a violated zone:
Unbypass a zone:
OK
→
BYPASS
→
BYPASS LIST [1... 3]
→
ZONE [1... 44]
→
uNBYPASS
: The alternative way to unbypass all zones at once is to arm and disarm the system.
EKB3
Bypass a violated zone by entering the following combination using [BYPS], number and [#] keys:
[BYPSxxyyyy#]
Value: xx – zone number, range – [01... 44]; yyyy – 4-digit user password
Example: BYPS051111#
: The alternative way to unbypass all zones at once is to arm and disarm the system.
: Bypassing a violated tamper is NOT allowed. Please, restore the tamper (for example: close sensor‘s enclosure) before arming the system
20
SMS
1. In order to find out the system‘s current information, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_INFO
Example: 1111_INFO
2. The system will reply to the user phone number who sent the SMS message with the following uptodate information:
• system date & time;
• system status (armed/disarmed);
• GSM signal strength level;
• main power supply status;
• temperature of the area surrounding ESIM264 temperature sensor (if any);
• state of zones (OK/alarm).
SMS
SMS user
ESIM264
Fig. No. 24
SMS
1. By default configuration, the SMS message mentioned in chapter
is sent periodically to
User 1
phone number at 11:00 daily.
SMS user
ESIM264 Fig. No. 25
2. In order to set a different SMS sending frequency (in days) and time, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_INFO:FF.TT
Value: FF – frequency in days, range – [0... 125]; TT – time, range – [0... 23]
Example: 1111_INFO:2.15 (every 2nd day at 15:00)
MANUAL ELDES ESIM264 V2.1 21
3. In order to disable periodic SMS message, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_INFO:0.0
Example: 1111_INFO:0.0
4. The system will reply with confirmation by SMS message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 26
SMS
1. In order to find out the current zone & PGM output information, send the following SMS message to the sys tem‘s phone number from any out of 5 preset user phone numbers:
XXXX_STATUS
Example: 1111_STATUS
2. The system will reply to the user phone number who sent the SMS message with the following uptodate information:
• system status (armed/disarmed);
• status of zones & PGM outputs (ON/OFF);
• zone alarm texts;
• PGM output names.
SMS
SMS user
ESIM264
Fig. No. 27
22
SMS
1. If the temperature sensor is installed in your system, it can send an SMS message containing temperature value in case the set lowest or highest temperature limit value is exceeded. This SMS message is sent to
User 1
only. By default configuration this SMS message is disabled.
SMS user
ESIM264
Fig. No. 28
2. In order enable or set a different lowest and highest temperature limit value, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_TEMP:MIN:MAX
Value: MIN lowest temperature limit boundary in o
MAX highest temperature limit boundary in o
Example: 1111_TEMP:-15:30
C, range - [-55... 125];
C, range [55... 125]
3. In order to disable temperature SMS message, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_TEMP:0:0
Example: 1111_TEMP:0.0
4. The system will reply with confirmation by SMS message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 29
MANUAL ELDES ESIM264 V2.1 23
EKB2
Message TBL displayed in the lower left side of the main screen view indicates presence of system troubles.
In order to find out more on the particular system problem, please, open menu section TROUBLES. The description on each system problem is indicated in the table below.
OK
→
TROuBLES
→
T [1... 6]
Trouble
TROuBLE 1
TROuBLE 2
TROuBLE 3
TROuBLE 4
TROuBLE 6
Name
VIOLATED TAMPER
REPLACE BATTERY
AC FAILuRE
TIME NOT SET
GSM ERROR
Description
One or more tampers are violated.
Backup battery problem.
Main power supply problem.
Date/time not set.
GSM connection problem.
EKB3
Yellow LED
indicates system troubles.
LED indications are mentioned in the table below.
SYSTEM LED Description
Illuminated continously
Flashing
One ore more zones or tampers are vio lated; other system troubles
One or more high zones are violated
1
2
3
4
5
6
In order to find out more on the particular system problem, please, enter command A. After this procedure the system will activate red zone LEDs for 15 seconds. The description on each LED indication is mentioned in the table below.
Zone LED Description
One or more tampers are violated.
Backup battery problem.
Main power supply problem.
Date/time not set.
One or more high zones (Z13 - Z44) are violated.
GSM connection problem.
In order to find out which particular high zone is violated, please, enter command B.
In order to find out which particular tamper is violated, please, enter command C.
[CODE#]
[CODE1]
[CODE2]
24
The number of violated high zone or tamper can be calculated using the table below according to the formula: number from zone
LED section B + number from zone LED section A.
LED #3 from section A is flashing and LED #8 from section B is illuminated continuously. According to the table below LED
#8 is equal to number 18, therefore 18 + 3 = 21.
: Violated high zone or tamper number is 21.
Zone LED section - A
(flashing)
Zone LED 1 = 1
Zone LED 2 = 2
Zone LED 3 = 3
Zone LED 4 = 4
Zone LED 5 = 5
Zone LED 6 = 6
Zone LED section - B
(illuminated continously)
Zone LED 7 = 12
Zone LED 8 = 18
Zone LED 9 = 24
Zone LED 10 = 30
Zone LED 11 = 36
Zone LED 12 = 42
SMS
Your system features 4 or more PGM outputs intended for connection and control of various electrical appliances. This provides a possibility to control garage gates, turn on and off your house heating, lighting, cooling system, reset smoke sensors to restored state etc. The PGM outputs must be configured by your installer before using them.
1. In order to turn ON a specified PGM output, send the following SMS message to the system’s phone number from any out of 5 preset user phone numbers:
XXXX_Cn:ON or XXXX_OutputName:ON
Value: Cn – PGM output number, range – [C1... C44]
Example: 1111_Pump:ON
2. In order to turn OFF a specified PGM output, send the following SMS message to the system‘s phone number from any out of 5 preset user phone numbers:
XXXX_Cn:OFF or XXXX_OutputName:OFF
Value: Cn – PGM output number, range – [C1... C44]
Example: 1111_C2:OFF
3. The system will reply with confirmation by SMS message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 30
MANUAL ELDES ESIM264 V2.1 25
1. In order to instantly turn ON a specified PGM output and keep it in this state for a determined time period, send the follo wing SMS message to the system’s phone number from any out of 5 preset user phone numbers:
XXXX_Cn:ON:hr.mn:sc or XXXX_OutputName:ON:hr.mn:sc
Value: Cn – PGM output number, range – [C1... C44]; hr – hours, range – [00... 23], mn – minutes, range – [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_Pump:ON:12:30:15
2. In order to instantly turn OFF a specified PGM output and keep it in this state for a determined time period, send the following
SMS message to the system’s phone number from any out of 10 preset user phone numbers:
XXXX_Cn:OFF:hr.mn:sc or XXXX_OutputName:OFF:hr.mn:sc
Value: Cn – PGM output number, range – [C1... C44]; hr – hours, range – [00... 23], mn – minutes, range – [00... 59]; sc – seconds, range – [00... 59].
Example: 1111_C3:OFF:13.25:56
3. The system will reply with confirmation by SMS text message to the user phone number who sent the SMS message.
SMS
SMS user
ESIM264
Fig. No. 31
The following system features become disabled automatically or may be disabled by your alarm system installer if the system is con nected to a monitoring station:
• Confirmation by SMS message when arming, disarming & turning off the alarm by phone call, SMS message, EKB2/EKB3 keyboard, iButton® key, EWK1 - wireless key-fob;
• Alarm indication by phone call;
• Alarm indication by SMS message;
• Violated zone/tamper name indication by SMS message;
• Temperature indication by SMS message;
• Periodical system information by SMS message;
• Main power loss/restore indication by SMS message.
For full system configuration and control, please refer to ESIM264 installation manual located at www.eldes.lt/en/download
Made in Lithuania. www.eldes.lt
iButton is a registered trademark of Maxim Integrated Products, Inc.
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project