Communication AC500
PROFIBUS DP S500-I/Os
Basic module
© ABB Group – Version 3.2 (2012-01)
 Technical Guides
PROFIBUS DP Communication
Contents

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 2

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 3

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Principle of Hardware Topology with Common Slaves
Up to 4 communication modules
with fieldbus connections in any
combination possible
AC500 PLC as a PROFIBUS DP Master
Standard PROFIBUS cable
CI541-DP
CI542-DP
Slaves with PROFIBUS DP interface
© ABB Group
March 11, 2013 | Slide 4
PROFIBUS DP Communication
Principle of Hardware Topology with Common Slaves
AC500 PLC as a PROFIBUS DP Master
Slaves with PROFIBUS DP interface
CI541-DP
CI542-DP
Adapter connector Dsub9
Active Termination ready
Standard PROFIBUS cable
© ABB Group
March 11, 2013 | Slide 5
PROFIBUS DP Communication
Principle of Hardware Topology with FieldBusPlug
Up to 4 communication modules
with fieldbus connections in any
combination possible
AC500 PLC as a fieldbus Master
Fieldbus cables
FieldBusPlugs
WISA®
Wireless I/Os
+ sensors
AC500
Slave PLC
S500
I/Os
Motor- Starter
Slaves with fieldbus neutral interface
© ABB Group
March 11, 2013 | Slide 6
Softstarter
Circuit Breaker
PROFIBUS DP Communication
CM572-DP as PROFIBUS DP Master Class1 (1)




Communication:

Profibus DP V0 / V1

Cyclic user data transfer between DP master of class 1 and
DP slaves

Acyclic data transfer initiated from DP master of class 1 to DP
slaves and from master class 2 to master class 1
Max nodes per network

32 subscribers

126 with repeaters
Data rate and cable:

Max RS485 network length (line topology), up to 1200 m at
9.6 kbit/s and up to 100 m at 12 Mbit/s

2 wires, 9 pole D-Sub connector
CM572-DP-XC

© ABB Group
March 11, 2013 | Slide 7
Version for usage in enhanced ambient conditions
PROFIBUS DP Communication
CM572-DP as a PROFIBUS DP Master Class1 (2)
Diagnostics:

Local on CPU display

With status LEDs (communication module)

By use of engineering tool in on-line mode

Extended diagnosis in application program by use of
dedicated function blocks

By use of standard PROFIBUS diagnosis tool (dedicated
software)
© ABB Group
March 11, 2013 | Slide 8
PROFIBUS DP Communication
AC500 CPU as a PROFIBUS DP Slave

Using AC500 CPUs as PROFIBUS slave


Communication:



© ABB Group
March 11, 2013 | Slide 9
With Profibus-FBP (PDP22)
Profibus DP V0
Cable:

FieldBusPlug PDP22

Transfer rate from 9.6 kbit/s up to 12 Mbit/s

Bus length up to 1200 m at 9.6 kbit/s and
up to 100 m at 12 Mbit/s.
Diagnostics:

Messages for local diagnosis on the CPU display

With engineering tool of master

Local diagnosis of the bus / slave with LEDs on the FBP
PROFIBUS DP Communication
CI541-DP, CI542-DP as PROFIBUS DP Slave Remote I/O



Using for PROFIBUS DP slave remote I/O

With built-in fieldbus interface (9-pole D-Sub connector)

Up to 10 S500 and S500-eCo can be connected to each
CI541-DP and CI542-DP

Fast counter functionality available onboard and on S500
Communication:

Profibus DP (DP-V0 and DP-V1)

Profibus DP bus configuration is managed by CM572-DP
master and Baud rate is detected automatically. Transfer rate
from 9.6 kbit/s up to 12 Mbit/s
Connection:


© ABB Group
March 11, 2013 | Slide 10
Plugged on the I/O terminal unit TU509-DP, TU510-DP or
TU510-DP-XC
Diagnostics:

Messages for local diagnosis on the CPU display

With engineering tool in on-line mode and /or by FBs

Local diagnosis of the bus / slave with LEDs indication
PROFIBUS DP Communication
CI541-DP as a PROFIBUS DP Slave Remote I/O


CI541-DP for PROFIBUS DP slave remote I/O

With built-in fieldbus interface (9-pole D-Sub connector)

Up to 10 S500 and S500-eCo can be connected to CI541-DP

2 rotary switches for settings of the Profibus DP identifier
4 analog inputs
(each input can be configured individually)


+/-10 V, 0..10 V, +/-20 mA, 4…20 mA (12-Bit resolution)

Temperature. Pt100, Pt1000, Ni1000 (2,3 wire-connection)
2 analog outputs
(each output can be configured individually)


8 digital inputs 24 V DC in one group

8 digital outputs (24 V DC, 0.5 mA) in one group


With separate UP3 power supply, to switch off externally.
CI541-DP-XC

© ABB Group
March 11, 2013 | Slide 11
+/-10 V, +/-20 mA, 4…20 mA (12-Bit resolution)
Version for usage in enhanced ambient conditions
PROFIBUS DP Communication
CI542-DP as a PROFIBUS DP Slave Remote I/O


CI542-DP for PROFIBUS DP slave remote I/O

With built-in fieldbus interface (9-pole D-Sub connector)

Up to 10 S500 & S500-eCo can be connected to CI542-DP

2 rotary switches for settings of the Profibus DP identifier
8 digital configurable inputs/outputs in one group

Each of the configurable I/O channels is defined as input or
output by user program

If used as outputs, a separate UP3 power supply can be
switch off externally

8 digital inputs 24 V DC in one group

8 digital outputs (24 V DC, 0.5 mA) in one group


CI542-DP-XC

© ABB Group
March 11, 2013 | Slide 12
With separate UP3 power supply, to switch off externally.
Version for usage in enhanced ambient conditions
PROFIBUS DP Communication
DC505-FBP as a PROFIBUS DP Slave Remote I/O

Using DC505-FBP for PROFIBUS slave remote I/O


Communication:



© ABB Group
March 11, 2013 | Slide 13
With Profibus-FBP (PDP22)
Profibus DP V0
Cable:

FieldBusPlug PDP22

Transfer rate from 9.6 kbit/s up to 12 Mbit/s

Bus length up to 1200 m at 9.6 kbit/s and up to 100 m
at 12 Mbit/s.
Diagnostics:

Messages for local diagnosis on the CPU display

With engineering tool of master

Local diagnosis of the bus /slave with LEDs on the FBP
PROFIBUS DP Communication
Summary: AC500 PROFIBUS DP Functionality
Profibus DP functionality
AC500 CPU ( Master)
AC500 CPU ( Slave)
S500 I/Os (Slave)
DC505-FBP
Multi master
CI541-DP / CI542-DP
yes, bus access via token
no
no
no
Profibus DP V0
yes
yes
yes
yes
Profibus DP V1
yes
no
yes
yes
LCD display of CPU and
LEDs on FBP
LEDs on interface
module and FBP
LEDs on interface
module
Protocols supported
Diagnosis
Error indication
LEDs on the
communication module
Online diagnosis
Using Engineering tool
Error code
yes
no
no
no
Associated function blocks
yes
no
no
yes
9-pole D-Sub
M12 FBP (standard)
M12 FBP (standard)
9-pole D-Sub
Physical layer
Connection
Baud rate
up to 12 Mbit/s
Distance
up to 1200 m at 90 kbit/s
Max. number of subscribers
© ABB Group
March 11, 2013 | Slide 14
Max. 126 (via amplifier), max. 32 (master/slave) per bus segment
PROFIBUS DP Communication
PROFIBUS Implementation Step by Step
1.
Make PROFIBUS settings in the slaves (hardware) like addresses and if necessary
communication parameters
2.
In case of non AC500 or non PDP-22 connected slaves copy the GSD file(s) to the hard disk of
your Engineering tool
3.
Create a software PROFIBUS configuration according to the hardware: define master and
select its right slot position in the terminal base. Define slave(s). Configure PROFIBUS
addresses and communication parameters for all devices. For I/O slave modules: configure
them, if necessary
4.
Create an I/O mapping: define symbol names for the slaves’ data as to be visible in the project
5.
Work within your project using variables generated by I/O mapping
6.
For diagnosis and additional features use the FBs from the PROFIBUS library
7.
Send the configuration (see item 2) to the CM572 acting as the PROFIBUS master
© ABB Group
March 11, 2013 | Slide 15
PROFIBUS DP Communication
PROFIBUS Implementation
The software project is created
PS501 version older
than V 2.x?
Yes
PROFIBUS configuration by
means of SYCON.net
Start
© ABB Group
March 11, 2013 | Slide 16
No
PROFIBUS configuration by
means of Control Builder Plus
Start
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 17

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Control Builder Plus: PROFIBUS Line Creation
1. Create a new project or
open your project in the
Control Builder Plus
2. Click the appropriate TA
slot according to the
hardware for the
CM572-DP acting as a
PROFIBUS master
3. Click right and select
“Plug device…”
© ABB Group
March 11, 2013 | Slide 18
PROFIBUS DP Communication
Master Selection
1.
Select “all vendors” from the vendor list
then Profibus / DP Master
2.
Select the CM572-DP from the list
3.
You can specify a name for the device
4.
Click the key “Plug Device”
Result: The PROFIBUS Line and the
master are added to the configuration tree
© ABB Group
March 11, 2013 | Slide 19
PROFIBUS DP Communication
Slave Selection
1. Click right on “CM572 Master”
2. Click on the item “Add Device…”
In the dialog all available PROFIBUS DP
slave devices are listed.
The AC500 devices and PDP22-FBP
are always present in the list (internal
implementation).
How to add a new device:
click here
3. Select the slave type from the list
4. Click the key “Add Device”
Result:
The slave is added to the configuration tree
© ABB Group
March 11, 2013 | Slide 20
PROFIBUS DP Communication
Modular Slave: Module Selection
Apply for all slave’s modules:
v
1.
Click right on “CI541-DP”
2.
Click on the item “Append device…”
3.
Select the module type from the list
according to the order of hardware
modules
4.
Click the key “Add Device”
v
The module is added to the configuration tree
© ABB Group
March 11, 2013 | Slide 21
PROFIBUS DP Communication
Configuration Steps
Result:
The PROFIBUS Line named
Adr1 containing the master
and one modular slave is
created
The next step:
Further configuration of the PROFIBUS line and PROFIBUS
components by double click on each tree element
For each PROFIBUS element in the tree:
© ABB Group
March 11, 2013 | Slide 22

Parameter can be modified

Information is displayed
PROFIBUS DP Communication
PROFIBUS Line Configuration
v
In the configuration tab you can modify the default settings as:
© ABB Group
March 11, 2013 | Slide 23

The behavior of the PLC (program execution) in case of CM572 error

Shortest scan time of the PROFIBUS (for experts only)
PROFIBUS DP Communication
CM572 Master Configuration
1. Double click on “CM572
Master”
2. Set at least the master
address and Baudrate
according to the project
3. To modify further
parameters click on “Edit
parameter values”
4. After manual modification
the parameter values can
be changed by the system:
(click on “Set optimal
values” or “Set default
values”
© ABB Group
March 11, 2013 | Slide 24
PROFIBUS DP Communication
Slave’s Module Configuration: Slave Configuration
1. Double click on
slave (here
“CI541_DP”)
2. Set at least the
slave address
according to the
project
3. Modify further
parameters if
necessary for
your project
© ABB Group
March 11, 2013 | Slide 25
PROFIBUS DP Communication
Slave’s Module Configuration: Device configuration
1. Double click on
slave (here
“CI541_IO”)
2. In the configuration
tab, due to modify
a parameter
double click on the
parameter field in
the column “Value”
3. Select parameter
from the list
© ABB Group
March 11, 2013 | Slide 26
PROFIBUS DP Communication
Slave’s Module Configuration: I/O Mapping
1. Click on tab “…
I/O Mapping”
2. Define symbol
names for the
variables
3. For this device
symbols can be
created byte or
bitwise. This
symbols will
occur in a
variable list of
your PS501
project.
© ABB Group
March 11, 2013 | Slide 27
PROFIBUS DP Communication
Slave’s Module Configuration: Device Configuration
In the configuration
tab you have to
modify the default
channel settings
according to
hardware analog
signal type
1. Due to modify a
parameter double
click on the
parameter field in
the column
“Value”
2. Select parameter
from the list
© ABB Group
March 11, 2013 | Slide 28
PROFIBUS DP Communication
Configuration Steps
Result:
PROFIBUS line and
PROFIBUS components
are configured
The next step:
Generation of Global variable lists in PS501 for configured
symbols which is done by creating the configuration for PS501
project
© ABB Group
March 11, 2013 | Slide 29
PROFIBUS DP Communication
Creating the Configuration for PS501 Project
© ABB Group
March 11, 2013 | Slide 30
1.
Create the
configuration data
by selecting Menu
“File/ Save Project”
2.
Double click on
CPU symbol
3.
Click on “Yes” key
to confirm creating
the configuration
PROFIBUS DP Communication
Add a Slave Device into the Device List (Repository) (1)
Each device communicating
via PROFIBUS DP
possesses a standardized
driver file (GSD file)
describing its parameters.
The GSD file is provided by
the device manufacturer.
For slaves not listed in the
Repository the dedicated
GSD file has to be copied
there.
© ABB Group
March 11, 2013 | Slide 31
PROFIBUS DP Communication
Add a Slave Device into the Device List (Repository) (2)
To add a not listed device proceed as follows:
1. Copy the GSD File into the hard disk of your
Engineering tool
2. Click on the branch CM572_DP
3. Select Menu “Tools/Device Repository…”
4. Select in the tree the branch DP Slave and
click on “Install…” key
5. Select the data type “*.gs?” and the adequate
path for the stored GSD file
6. Select the GSD file from the list and click
“Open” key
7. After you find the GSD file inserted to the DP
slave list click “Close” key
Back to slide Slave Selection
© ABB Group
March 11, 2013 | Slide 32
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 33

Configuration with Control Builder Plus

Programming and download with CodeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
CM572-DP Configuration
© ABB Group
March 11, 2013 | Slide 34

The PS501 project is opened.
In the tab “Ressources” the
variable lists grouped by
devices are visible.

Double click on a module
branch to open its variable
list.
PROFIBUS DP Communication
Programming and Download

For the data exchange no Function Blocks are needed. Use just the PROFIBUS variables
in your program.

For extended diagnosis, special DPV1 functions and slave parameterising use FBs from
the PROFIBUS_AC500_V10.lib which is automatically inserted to your project due to
defined PROFIBUS line.

The PROFIBUS configuration is downloaded to the communication module CM572-DP
automatically with the program download.
© ABB Group
March 11, 2013 | Slide 35
PROFIBUS DP Communication
Station Diagnosis

For the data exchange no Function Blocks are needed. Use just the PROFIBUS variables
in your program.
© ABB Group
March 11, 2013 | Slide 36
PROFIBUS DP Communication
Library PROFIBUS_AC500_V10.lib
Simulation mode is not available for these function blocks
Back to slide PROFIBUS Implementation
© ABB Group
March 11, 2013 | Slide 37
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 38

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Configuration with PS501
1. Select “Couplers“
2. Select “Append Subelement“
3. Select “CM572 …“
© ABB Group
March 11, 2013 | Slide 39
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 40

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
CM572-DPM (1)
SYCON.net allows to configure the network and create all data exchange.
Select SYCON.net inside “Resources”\”Tools”
It is necessary to name your project before
opening SYCON.net. If there is no project name
the following error message is displayed.
© ABB Group
March 11, 2013 | Slide 41
PROFIBUS DP Communication
CM572-DPM (2)
The fieldbus configuration software SYCON.net will be opened
and allows to configure the master and slave devices on network.
Drag and drop for external CM572-DPM:
The CM572 will be inserted automatically on network.
© ABB Group
March 11, 2013 | Slide 42
PROFIBUS DP Communication
CM572-DPM (3)
2. Select the board (slot-) number and “Accept”
Note: First module left to CPU is “1“
1. In order to access all protocol
parameters double click on icon
© ABB Group
March 11, 2013 | Slide 43
More information in CoDeSys Help
PROFIBUS DP Communication
CM572-DPM (4)
3. Choose “Baud Rate”
2. Master address
1. Select “Bus
Parameters”
© ABB Group
March 11, 2013 | Slide 44
4. Click “Apply” then
“Okay”
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 45

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (1)
The GSD files of all PROFIBUS slaves have to be copied into the folder:
C:\Program Files\Hilscher GmbH\SYCONnet\ABBPBGenericSlaveDTM\GSD
The GSD files of AC500 devices and PDP22 are copied during the PS501 installation.
© ABB Group
March 11, 2013 | Slide 46
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (2)
Open
SYCON.net
in the master
project
2. Select the device
1. Select “Network”/
“Device Catalog”
© ABB Group
March 11, 2013 | Slide 47
3. Reload
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (3)
Drag and drop for slave e.g. PDP22-FBP (DPV1 modular).
The icon will be inserted automatically into the network.
© ABB Group
March 11, 2013 | Slide 48
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (4)
1. In order to access
all slave parameters double click on
icon
© ABB Group
March 11, 2013 | Slide 49
2. Select “Modules” to define the
configuration of local extensions
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (5)
Configure the local
extensions beginning
with DC505-FBP
“Insert” or
“Append”
“Apply” and “OK”
© ABB Group
March 11, 2013 | Slide 50
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (6)
“Apply”
and “OK”
Select “Parameters” to configure the S500-I/O modules
© ABB Group
March 11, 2013 | Slide 51
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (7)
1. Click on the folder of a module
2. Click on “Name of variable” and
enter symbolic names
The names of the variables
will be used like global
variables inside PS501 project
More information in CoDeSys Help
© ABB Group
March 11, 2013 | Slide 52
PROFIBUS DP Communication
PDP22-FBP (DPV1 modular) (8)
Back in PS501:
“Resources”\
“Global Variables”\
“Slotx”\
“Slotx_Slavey”
© ABB Group
March 11, 2013 | Slide 53
The variables are available for
programming. They are displayed
with given symbol and automatically generated address.
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 54

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Download Configuration CM572 (1)
1. Right click on CM572 icon
2. Select “Configuration”
© ABB Group
March 11, 2013 | Slide 55
PROFIBUS DP Communication
Download Configuration CM572 (2)
3. Select “Driver” and then “Gateway Configuration”,
if not previously configured.
© ABB Group
March 11, 2013 | Slide 56
PROFIBUS DP Communication
Download Configuration CM572 (3)
6. Select the slot corresponding
to CM572 to configure
4. Select
5. Select “Scan” in order to search
“Device Assignment”
for the device available on your
configuration
© ABB Group
March 11, 2013 | Slide 57
PROFIBUS DP Communication
Download Configuration CM572 (4)
7. Right click
again on CM572
8. Select “Connect” in order
to open communication
© ABB Group
March 11, 2013 | Slide 58
PROFIBUS DP Communication
Download Configuration CM572 (5)
9. The CM572 is ready to
receive a new
configuration (green
color), right click again.
10. Select “Download” in
order to download
configuration.
Note: The program
execution has to be
stopped before
downloading
© ABB Group
March 11, 2013 | Slide 59
PROFIBUS DP Communication
Download Configuration CM572 (6)
11. When the download is
finished and a message
about successful download
is visible, right click again.
12. Select “Disconnect”
13. Select “Configuration”
© ABB Group
March 11, 2013 | Slide 60
PROFIBUS DP Communication
Download Configuration CM572 (7)
14. Remove the check
selecting device
15. Valid “OK”. The
download of the
configuration is
now terminated.
© ABB Group
March 11, 2013 | Slide 61
PROFIBUS DP Communication
Coming up

PROFIBUS: Hardware components, fieldbus topology

Configuration of AC500 with PS501 Control Builder Plus version 2.x

© ABB Group
March 11, 2013 | Slide 62

Configuration with Control Builder Plus

Programming and download with CoDeSys
Configuration of AC500 with PS501 version 1.x

Configuration with SYCON.net: PROFIBUS Master

Configuration with SYCON.net: PROFIBUS Slave

CM572 download configuration

CM572 diagnosis
PROFIBUS DP Communication
Diagnosis CM572
1. When the CM572 is
connected (green color),
right click.
2. Select “Diagnostic” in
order to open the
diagnostic interface.
© ABB Group
March 11, 2013 | Slide 63
PROFIBUS DP Communication
Bus Diagnosis
Select “Bus Diagnosis”
© ABB Group
March 11, 2013 | Slide 64
PROFIBUS DP Communication
Station Diagnosis
Select “Station Diagnosis”
Back to slide PROFIBUS Implementation
© ABB Group
March 11, 2013 | Slide 65
PROFIBUS DP Communication
Cross-References to Documentation (1)
1.
CoDeSys Help\Target System\AC500 / S500\
Hardware AC500\Communication modules\
CM572-DP Communication module PROFIBUS
2.
CoDeSys Help\Target System\AC500 / S500\
System technology\System technology of the AC 500
Communication modules\The PROFIBUS DP
communication module
3.
CoDeSys Help\Target System\AC500 / S500\
Function Block libraries AC500\PROFIBUS DP Library
4.
Hilscher GmbH\SYCONnet\ABBPBMasterDTM\*.chm or
Hilscher GmbH\SYCONnet\ ABBPBGenericSlaveDTM
\*.chm
© ABB Group
March 11, 2013 | Slide 66
PROFIBUS DP Communication
Cross-References to Documentation (2)
© ABB Group
March 11, 2013 | Slide 67
© ABB Group
March 11, 2013 | Slide 68