Panasonic 26PEF1U6 Datasheet

Panasonic 26PEF1U6 Datasheet
Split System Submittal Data
Concealed Duct Heat Pump
System: 26PEF1U6 Indoor/Outdoor: S-26PF1U6/U-26PE1U6
Approval:
Date:
Construction:
Unit #:
Drawing #:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Power
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
General Data (at 230V)
V/PH/Hz
230/208/1/60
(A)
15-30 Indoor-Outdoor
(A)
15-30 Indoor-Outdoor
(A)
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
(RPM)
No. Motors
(W)
(High)
CFM
(A)
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
DC Rotary Inverter
1
12.9-17.5
Propeller
18-7/64-1
Direct - Inverter
8-800
1-90
1765
13.8
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifled
1-15.9
(sq.ft.)
7.26
(in.)
3/8”
Refrigerant
R410A
Lbs. - R410a (outdoor unit)
4.19
Electric Expansion Valve
Control
Flare
Connection
165
Line Length, Max (ft.)
50 (Outdoor lower), 100 (Outdoor higher)
Lift Difference, Max (ft.)
Line Size
(in. O.D. Discharge)
3/8”
Line Size
(in. O.D. Suction)
5/8”
Dimensions
Indoor Unit
Outdoor Unit
Weight
Net
Shipping
Shipping Volume
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
(RPM, High)
No. Poles
(W)
No. Motors
(HI/Med/Lo)
CFM
Indoor Sound Rating (Hi) (dB-A)
(A)
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
Centrifugal
5-29/32-2
3 & Auto
4-920
1-70
670/530/460
34
0.9
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifled
3-14.9
(sq.ft.)
2.03
(in.)
9/32”
Max. head 2-33/64in. above drain connection (1-17/64)
(in.)
HxWxD
(Uncrated)
12-7/32 x 39-3/8 x 24-13/16
(Crated)
14-3/32 x 46-7/8 x 30-13/16
(Uncrated)
30-23/32 x 37 x 13-3/8
(Crated)
34-31/32 x 39-31/32 x 16-3/32
Indoor
(lbs.)
71
(lbs.)
82
(cu.ft.)
Indoor
11.8
Outdoor
128
148
Outdoor
13.0
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
(BTU/H)
24,000 (9,500-24,000)
Sensible Capacity
(BTU/H)
14,390
Latent Capacity
(BTU/H)
9,610
SEER
14
Dehumidification
(Pints/H)
7.7
(A)
13.6/15.0
Amps
(W)
2,600/2,600
Power Inputs
Outdoor Sound Rating
(dB-A)
49
Heating
Total Capacity
HSPF
(BTU/H) 28,600 (8,000-28,600)
9.7
Dimensions
Heating
Amps
Max. Amps
Power Inputs
Back-up Strip Heater
Outdoor Sounds Rating
(A)
(A)
(W)
(KW)
(dB-A)
Options
15.9/17.6 Refrigerant Line Set
15.9/17.6 Fresh Air Intake
3,340/3,340 Condensate Drain Pump
0.00/0.00 Wirelss Remote Controller
52 Non-Removeable Remo-con Bracket
Features
Microprocessor
Controls
Remote Controller
LCD Wired Type, Temp. Sensor Built In
IC Thermostat
Temperature Control
72HR, ON/OFF
Timer
Built-In
Night Setback
(Horizontal)
Manual
Air Louver
(Vertical)
AutomaticBuilt-In
Power Failure Automatic Restart
Heating/Cooling Automatic Changeover
Built-In
Self-Diagnosis
Built-In
Washable, Anti-Mold
Air Filter
3DQDVRQLF1RUWK$PHULFD
$LU&RQGLWLRQLQJ'LYLVLRQ
5REHUWV%OYG1:6XLWH
.HQQHVDZ*$
KWWSZZZSDQDVRQLFFRPDLUFRQ
Available
N/A
Standard
Available
Available
Operating Range
Indoor Air IntakeTemp. Outdoor Air IntakeTemp.
Cooling
Maximum
Minimum
95F DB/71F WB
67F DB/57F WB
115F DB
0F DB
Indoor Air IntakeTemp. Outdoor Air IntakeTemp.
Heating
Maximum
Minimum
80F DB/67F WB
-DB/-WB
75F DB/65F WB
5F DB