INSTALLATION INSTRUCTIONS
Single Split System Air Conditioner
This air conditioner uses the refrigerant R410A.
NOTE
External diameter of service port R410A: 5/16"
Model No.
Indoor Units
Type
Indoor Unit Type
26
36
42
S-26PU1U6
(CZ-24KPU1U)**
S-36PU1U6
(CZ-36KPU1U)**
S-42PU1U6
(CZ-36KPU1U)**
U1
4-Way Cassette
K1
Wall Mounted
S-26PK1U6
T1
Ceiling
S-26PT1U6
S-36PT1U6
F1
Low Silhouette Duct
S-26PF1U6
S-36PF1U6
Remarks
with Wired Remote Controller: CZ-RTC2
with Wireless Remote Controller: CZ-RWSK1U
S-42PT1U6
with Wired Remote Controller: CZ-RTC2
with Wired Remote Controller: CZ-RTC2
** Panel (optional parts)
Remote Controllers
Timer Remote Controller (wired)
Wireless Remote Controller
CZ-RTC2
Timer Remote Controller comes with Instructions Manual.
CZ-RWSU1U
for U1 and T1 type Indoor units
CZ-RWSC1U
for F1 type Indoor units
CZ-RWSK1U
for K1 type Indoor units
Units should be installed by licensed contractor according to
local code requirements.
85464369532012
Panasonic_PAC-i_IndoorUnit_US-le1 1
CV6233186962
2011/11/02 15:17:08
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an
important part of your job to install or service the system so
it operates safely and efficiently.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
For safe installation and trouble-free operation, you must: thin aluminum fins on the air conditioner can cut your
fingers.
Carefully read this instruction booklet before beginning.
When Installing…
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
WARNING
in severe personal injury or death.
CAUTION
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location
for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air outlet at least
CAUTION
5 feet away from the unit.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including failure to follow the instructions in this document.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
SPECIAL PRECAUTIONS
WARNING
When Wiring
• Keep all tubing runs as short as possible.
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
WARNING
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• When performing piping work do not
mix air except for specifled refrigerant
(R410A) in refrigeration cycle. It
causes capacity down, and risk of
explosion and injury due to high
tension inside the refrigerant cycle.
• Refrigerant gas leakage may cause
fire.
• Do not add or replace refrigerant
other than specified type.
It may cause product damage,
burst and injury etc.
• To prevent possible hazards from insulation failure,
the unit must be grounded.
• Do not leak refrigerant while piping work for an installation
or re-installation, and while repairing refrigeration parts.
Handle liquid refrigerant carefully as it may cause frostbite.
2
Panasonic_PAC-i_IndoorUnit_US-le2 2
2011/11/02 15:17:09
When Servicing
CAUTION
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
WARNING
NOTICE
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
• Do not touch the air inlet or the
sharp aluminum fins of the
outdoor unit. You may get injured.
• Ventilate any enclosed areas when
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fire or heat, can produce
dangerously toxic gas.
• Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Others
CAUTION
• Do not touch the air inlet or the
sharp aluminum fins of the
outdoor unit. You may get injured.
• Do not sit or step on the unit,
you may fall down accidentally.
• Do not stick any object into the
FAN CASE.
You may be injured and the
unit may be damaged.
• This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
• This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
• FCC Caution: To assure continued compliance, follow the attached installation instructions.
Any changes or modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate this equipment.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set
limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws imposed to protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define
a Refrigerant Concentration Level (RCL) of 25 pounds
per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
3
Panasonic_PAC-i_IndoorUnit_US-le3 3
2011/11/02 15:17:09
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution
joints (optional).
When bending tubing ø5/8" or smaller, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with
caps or tape to prevent dirt, moisture, or other foreign substances
from entering. These substances can result in system malfunction.
CAUTION
Unit: inch
Material
Copper tube
O
Outer diameter
1/4
3/8
1/2
5/8
Wall thickness
t0.032
t0.032
t0.032
t0.04
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating
machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
New compatible
tool? with R410A?
Item
Manifold gauge
Remarks
Manifold gauge Yes
No
Types of refrigerant, refrigerating machine oil, and
pressure gauge are different.
Charge hose
Yes
No
To resist higher pressure, material must be changed.
Vacuum pump
Yes
Yes
Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
Leak detector
Yes
No
Leak detectors for CFC and HCFC that
react to chlorine do not function because
R410A contains no chlorine. Leak detector
for HFC134a can be used for R410A.
Flaring oil
Yes
No
For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
Vacuum pump
Outlet
Inlet
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
4
Panasonic_PAC-i_IndoorUnit_US-le4 4
2011/11/02 15:17:09
3-2. Use R410A exclusive cylinder only.
Configuration and characteristics of cylinders
When charging with a refrigerant cylinder, use an
electronic scale for charging refrigerant. In this
case, if the volume of refrigerant in the cylinder
becomes less than 20% of the fully-charged
amount, the composition of the refrigerant starts
to change. Thus, do not use the refrigerant if the
amount in the charging cylinder is less than 20%.
Valve
Also, charge the minimum necessary amount to
the charging cylinder before using it to charge the
air conditioning unit.
Liquid
Single valve
Charge liquid refrigerant with
cylinder in up-side-down position.
Fig. 1
Valve
Liquid
Single valve (with siphon tube)
Charge with cylinder in normal position.
Fig. 2
5
Panasonic_PAC-i_IndoorUnit_US-le5 5
2011/11/02 15:17:10
CONTENTS
Page
IMPORTANT! ............................................................... 2
Please Read Before Starting
Check of Density Limit
Precautions for Installation Using New Refrigerant
Page
4. ELECTRICAL WIRING............................................ 37
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire Diameter
for Power Supply System
4-3. Wiring System Diagram
4-4. How to Connect Wiring to the Terminal
1. GENERAL ................................................................. 7
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Outdoor Unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
5. HOW TO INSTALL THE WIRELESS REMOTE
CONTROLLER........................................................ 40
5-1. Wireless Remote Controller Installation
5-2. Room Temperature Sensor Setting
5-3. Address Switches
5-4. Setting the Model Code
<CZ-RWSU1U>
2. SELECTING THE INSTALLATION SITE ................ 12
2-1. Indoor Unit
■ 4-Way Cassette Type (U1 Type). . . . . . . . . . . . . . . . . .42
5-5. Indicator Section Installation
5-6. Operating Controller Installation
3. HOW TO INSTALL THE INDOOR UNIT .................. 13
■ 4-Way Cassette Type
(U1 Type) ................................................................. 13
3-1. Suspending the Indoor Unit
3-2. Preparation for Suspending
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. Before Installing the Ceiling Panel
3-7. Installing the Ceiling Panel
3-8. When Removing the Ceiling Panel for Servicing
3-9. Duct for Fresh Air
■ Ceiling Type (T1 Type). . . . . . . . . . . . . . . . . . . . . . . . . . 43
5-7. Indicator Section Installation
5-8. Operating Controller Installation
5-9. Electrical Wiring
5-10. Test Run Switch
5-11. Misoperation Alarm Indicators
<CZ-RWSC1U>
5-12. Separate Type Signal Receiving Unit Installation
5-13. Electrical Wiring
5-14. Test Run Switch
5-15. Misoperation Alarm Indicators
5-16. Basic Wiring Diagram
5-17. Wiring System Diagram for Group Control
5-18. Wiring System Diagram for Multiple Remote
Controllers
<CZ-RWSK1U>
5-19. Test Run Procedure
5-20. Check Items Before the Test Run
5-21. Preparing for the Test Run
5-22. Precautions
5-23. When Setting Indoor Unit Control PCB Switch
for Wall Mounted Indoor Unit
5-24. Diagnosis Table
■ Wall Mounted Type (K1 Type) .................................. 21
3-10. Removing the Wall Fixture from the Unit
3-11. Selecting and Making a Hole
3-12. Installing the Rear Panel on the Wall
3-13. Removing the Grille to Install the Indoor Unit
3-14. Preparing the Indoor Side Tubing
3-15. Wiring Instructions
3-16. Wiring Instructions for Inter-Unit Connections
3-17. Shaping the Tubing
3-18. Installing the Drain Hose
■ Ceiling Type (T1 Type) ............................................. 26
3-19. Suspending the Indoor Unit
3-20. Duct for Fresh Air
3-21. Installing the Drain Piping
■ Low Silhouette Ducted Type (F1 Type) .................... 30
3-22. Required Minimum Space for Installation and
Service
3-23. Suspending the Indoor Unit
3-24. Installing the Drain Piping
3-25. Checking the Drainage
3-26. Increasing the Fan Speed
3-27. When Installing the Indoor Unit
3-28. Required Minimum Space for Installation and
Service
6. APPENIDX .............................................................. 58
■ Name of Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
■ Care and Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
■ Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
■ Tips for Energy Saving. . . . . . . . . . . . . . . . . . . . . . . . . .63
■ SUPPLEMENT ON DRAIN PIPING ........................ 36
6
Panasonic_PAC-i_IndoorUnit_US-le6 6
2011/11/02 15:17:10
1. GENERAL
1-3. Type of Copper Tube and Insulation Material
This booklet briefly outlines where and how to install
the air conditioning system. Please read over the entire
set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the system
before beginning.
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the liquid
and gas tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
If you wish to purchase these materials separately
from a local source, you will need:
1-1. Tools Required for Installation (not supplied)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
1. Deoxidized annealed copper tube for refrigerant
tubing.
Flathead screwdriver
Phillips head screwdriver
Knife or wire stripper
Tape measure
Level gauge
Sabre saw or key hole saw
Hacksaw
Core bits
Hammer
Drill
Tube cutter
Tube flaring tool
Torque wrench
Adjustable wrench
Reamer (for deburring)
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing.
Wall thickness of the insulation should be not less
than 5/16".
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to
Section 4. “ELECTRICAL WIRING” for details.
CAUTION
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
1-2. Accessories Supplied with Outdoor Unit
1-4. Additional Materials Required for Installation
See Tables 1-1 to 1-6.
1. Refrigeration (armored) tape
Table
Type
2. Insulated staples or clamps for connecting wire
(See your local codes.)
1-1
4-Way Cassette
1-2
Wall Mounted
1-3
Ceiling
1-4
Low Silhouette Ducted
1-5
Wireless Remote Controller
5. Clamps or saddles to secure refrigerant tubing
1-6
Timer Wired Remote Controller
6. Scale for weighing
3. Putty
4. Refrigeration tubing lubricant
7
Panasonic_PAC-i_IndoorUnit_US-le7 7
2011/11/02 15:17:10
Table 1-1 4-Way Cassette
Part Name
Figure
Q’ty
Part Name
Figure
Q’ty
Full-scale installation diagram
1
Drain hose adaptor
1
Flare insulator
2
Sealing putty
1
Washer
8
Wired remote controller
(comes with 7-7/8 in. wire)
1
Wire joint
2
Wood screw
2
Insulating tape
(White)
1
Hose band
2
Packing
1
Drain insulator
1
Drain hose
1
Table 1-2 Wall Mounted
Part Name
Figure
Q’ty
Part Name
Figure
Q’ty
Full-scale diagram
1
Drain hose adaptor
1
Wall fixture
1
Wireless remote controller
1
12
Wireless remote controller
mounting cradle
1
Truss-head tapping screw
4 × 5/8 in.
2
Battery
2
Tapping screw
Truss-head
Phillips
4 × 5/8 in.
Rawl plug
12
Cover
1
Insulator
1
Table 1-3 Ceiling
Part Name
Figure
Q’ty
Part Name
Figure
Q’ty
Full-scale installation diagram
1
Insulating tape
2
Special washer
4
Vinyl clamp
8
1
Sealing putty
1
1
Drain hose
1
Wired remote controller
(comes with 7-7/8 in. wire)
1
Wood screw
2
Wire joint
2
Drain insulator
Flare insulator
T5
T3
1 Set
Drain hose adaptor
1
Drain hose clamp
6
8
Panasonic_PAC-i_IndoorUnit_US-le8 8
2011/11/02 15:17:10
Table1-4 Low Silhouette Ducted
Part Name
Figure
Q’ty
Part Name
Figure
Q’ty
Flare insulator
2
Drain hose adaptor
1
Insulating tape
1
Special washer
8
Jumper cable*
1
Vinyl clamp
8
Hose band
2
1
Packing
1
Wired remote controller
(comes with 7-7/8 in. wire)
Sealing putty
1
Wood screw
2
Drain insulator
1
Drain hose
1
Wire joint
2
Table 1-5
(Accessories for the Wireless Remote Controller)
<CZ-RWSU1U>
Part Name
Figure
Operation controller
‘Q’ty
Part Name
Figure
‘Q’ty
1
Spacers
2
1
Pan-head tapping screws
4 × 13/32 in.
4
Wireless remote controller
1
Truss-head tapping screws
4 × 5/8 in.
2
Wireless remote controller
mounting cradle
1
Vinyl clamps
L 5-29/32
3
Batteries
2
Wire joints
4
Indicator section
Run
Timer Heating preparations
<CZ-RWSK1U>
Part Name
Figure
‘Q’ty
Part Name
Figure
‘Q’ty
Wireless remote controller
1
Truss-head tapping screws
4 × 5/8 in.
2
Wireless remote controller
mounting cradle
1
Batteries
2
9
Panasonic_PAC-i_IndoorUnit_US-le9 9
2011/11/02 15:17:11
<CZ-RWSC1U>
Part Name
Figure
‘Q’ty
Part Name
Figure
‘Q’ty
Separate type signal receiving unit
(comes with 7-7/8 in. wire)
1
Small screws
M4 × 1-9/16 in.
2
Carrier for ceiling installation
1
Wood screws
2
Wireless remote controller
1
Spacers
4
Wireless remote controller
mounting cradle
1
Wire joints
4
Batteries
2
Clamp
1
Machine screws
M4 × 1 in.
2
Ceiling installation paper pattern
(3-3/4 × 2-1/32 in.)
1
Table 1-6
(Accessories for the Timer Wired Remote Controller)
Part Name
Figure
Part Name
‘Q’ty
Figure
‘Q’ty
Timer Wired Remote Controller
1
Wood screws
2
Connecting wiring
length 4 ft.
1
Spacers
2
Machine screws
M4 × 1 in.
2
Clamps
2
10
Panasonic_PAC-i_IndoorUnit_US-le10 10
2011/11/02 15:17:12
CAUTION
1. This unit requires no additional refrigerant charge up to 100 ft. tubing length.
In case of more than 100 ft., additional
refrigerant charge is required.
2. In case of multi type installation, indoor
units should be installed within the
same room. If multi type indoor units
are installed in different rooms, temperature control may develop problems
because thermostat operation must
follow the thermostat condition of 1
indoor unit only (the main unit).
WARNING
Always check the gas density
for the room in which the unit is
installed.
■ Check of limit density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally escapes, its density does not exceed the limit level
for that room.
CAUTION
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heavier than air.
11
Panasonic_PAC-i_IndoorUnit_US-le11 11
2011/11/02 15:17:12
2. SELECTING THE INSTALLATION SITE
Ceiling Type
2-1. Indoor Unit
Ceiling
AVOID:
areas where leakage of flammable gas may be
expected.
Wall
Min. 10 inch
places where large amounts of oil mist exist.
Min. 10 inch
Front view
direct sunlight.
NOTE
locations near inverter lamps which may affect the
performance of the unit.
The rear of the indoor unit can be installed flush
against the wall.
locations near heat sources which may affect the
performance of the unit.
Ceiling
Air
discharge
locations where external air may enter the room
directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
Air intake
Min. 2 ft.
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
Side view
Max 25 cm
installing the remote controller behind curtains or
furniture.
Low Silhouette Ducted Type
4-Way Cassette Type
locations where the receiver in the indoor unit is
exposed to the inverter lamp light. Faulty operation
of the unit occurs.
DO:
10 in.
3 ft.
10 in.
select an appropriate position from which every
corner of the room can be uniformly cooled.
3 ft.
3 ft.
3 ft.
3 ft.
10 in.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
Min.8 ft.
Shows Low Silhouette Ducted Type only
install the unit within the maximum elevation
difference above or below the outdoor unit and within
a total tubing length (L) from the outdoor unit as
detailed in the installation instructions packed with
the outdoor unit.
Wall Mounted Type
allow room for mounting the remote controller about
3 ft. off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
Min.
6 inch
Min.
6 inch
Min.
12 inch
NOTE
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft.
12
Panasonic_PAC-i_IndoorUnit_US-le12 12
2011/11/02 15:17:12
3. HOW TO INSTALL THE INDOOR UNIT
■ 4-Way Cassette Type
(U1 Type)
3-1. Suspending the Indoor Unit
Hole-in-anchor
Hole-in-plug
This unit uses a drain pump. Use a level gauge to
check that the unit is level.
Concrete
Insert
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs. 3-1
and 3-2), by attaching them to the ceiling support
structure, or by any other method that ensures that
the unit will be securely and safely suspended.
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in
the ceiling.
Table 3-1
A (Ceiling opening)
B
(Suspension bolt pitch)
Unit: inch (mm)
B
S-26PU1U6
(CZ-24KPU1U)
32-9/32
(820)
22-9/32
(566)
S-36PU1U6, S-42PU1U6
(CZ-36KPU1U)
43-11/16
(1,110)
33-11/16
(856)
Drain hose
side
32-9/32 (Ceiling opening)
A
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show the
relationship between the positions of the suspension fitting, the unit, and the panel.
29-13/16 (Suspension bolt pitch)
Length
Type
X
Grille center
Refrigerant
tubing side
Unit: inch
Fig. 3-2
Drain connection (other side)
(VP25)
Refrigerant tubing joint (gas tube side)
Refrigerant tubing joint
(liquid tube side)
C
D
1-3/16
E
A
B
Suspension lug
Unit: inch
Fig. 3-3
Table 3-2
Unit: inch (mm)
Length
A
B
C
D
E
S-26PU1U6
(CZ-24KPU1U)
6-3/16
(157)
7-5/32
(182)
10-9/32
(261)
12-1/8
(308)
4-7/8
(124)
S-36PU1U6, S-42PU1U6
(CZ-36KPU1U)
6-3/16
(157)
7-5/32
(182)
11-15/32
(291)
13-1/16
(338)
4-7/8
(124)
Type
13
Panasonic_PAC-i_IndoorUnit_US-le13 13
2011/11/02 15:17:13
(2) The length of each suspension bolt must be
appropriate for a distance between the bottom of
the bolt and the bottom of the ceiling of 5/8" or
more as shown in Fig. 3-4.
Full-scale installation diagram
(printed on a cardboard packing)
1-7/8"
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the
supplied full-scale installation diagram. (Fig. 3-4)
The size of the opening for the indoor unit can be
confirmed by attaching the full-scale installation
diagram beneath the unit. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
5/8" or more
3-3. Placing the Unit Inside the Ceiling
Full-scale installation
diagram
Fig. 3-4
Suspension bolt
Suspension lug
(3) Thread the 2 hexagonal nuts (field supply) and
washers onto the 4 suspension bolts as shown in
Fig. 3-5.
Use 2 sets of nuts and washers (upper and lower),
so that the unit will not fall off the suspension lugs.
Nuts and washers
(Use above and below)
Upper
Lower
Notch
Double nuts
1-7/8"
(4) Remove the protective cardboard used to protect
the fan parts during transport.
Fig. 3-5
(5) Adjust the distance between the unit and surface
of the ceiling. (1-7/8") (Fig. 3-4)
14
Panasonic_PAC-i_IndoorUnit_US-le14 14
2011/11/02 15:17:14
3-4. Installing the Drain Piping
Transparent part for
checking drainage
(1) Prepare standard hard PVC pipe for the drain and
use the supplied drain hose and hose band to prevent water leaks.
The PVC pipe must be purchased separately. The
transparent part allows you to check drainage.
(Fig. 3-6)
CAUTION
Packing
(supplied)
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-6)
Hose band
(supplied)
Drain hose
adapter
(supplied)
Drain hose
(supplied)
Adhere with
PVC adhesive.
Hard PVC pipe
(not supplied)
Fig. 3-6
Drain insulator (supplied)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
NOTE
Fig. 3-7
Ensure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
Air bleeder
CAUTION
● Do not install an air bleeder tube, as this may
cause water to spray from the drain tube outlet.
(Fig. 3-8)
Fig. 3-8
11" or less (as short as possible)
● If it is necessary to increase the height of the
drain pipe, the section directly after the connection port can be raised a maximum of 19-1/2".
Do not raise it any higher than 19-1/2", as this
could result in water leaks. (Fig. 3-9)
19-1/2" or less
● Do not install the pipe with an upward gradient
from the connection port. This will cause drain
water to flow backwards and leak when the unit is
stopped. (Fig. 3-10)
Fig. 3-9
Upward gradient prohibited
● Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should
not be allowed to hang unsupported from its
connection to the unit. Fasten the pipe to a wall,
frame, or other support as close to the unit as
possible. (Fig. 3-11)
Fig. 3-10
● Provide insulation for any drain pipe that is run
indoors.
Refer to “
Support
pieces
SUPPLEMENT ON DRAIN PIPING”.
Fig. 3-11
15
Panasonic_PAC-i_IndoorUnit_US-le15 15
2011/11/02 15:17:15
3-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch
and wipe up spilled water.
WARNING
Do not supply power to the
unit until the tubing and wiring to the outdoor unit are
completed.
(1) Take off the tube cover and through the opening,
slowly pour about 0.3 gal of water into the drain
pan to check drainage.
(2) Do Test Run to check the drainage after completing installation. When performing Test Run, refer to
the installation instructions attached to the outdoor
unit.
CAUTION
Be careful since the fan will
start turning when checking
the drainage.
5/16"(4 × 8 mm)
tapping screw
(3) After drain checking is finished, return the Operation Selector switch to the RUN position (ON position ) and remount the tube cover.
Tube cover
Siphon
WARNING
To mount the tube cover,
use 5/16" (4 × 8 mm) tapping screws. Do not use long
screws as they may puncture
the drain pan and cause water
leakage.
Fig. 3-12
16
Panasonic_PAC-i_IndoorUnit_US-le16 16
2011/11/02 15:17:16
■ Ceiling Panel
CAUTION
Latch
Screw
Never touch or attempt to
move the air direction louver
by hand or you may damage the unit. Instead, use the
remote controller if you want
to change the direction or air
flow.
Air-intake grille
3-6. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-13 and 3-14)
Ceiling panel
(a) Remove the 2 screws on the latch of the airintake grille. (Fig. 3-13)
Fig. 3-13
(b) Press on the 2 latches of the air-intake grille
with your thumbs in the direction of the arrow
to open the grille. (Fig. 3-13)
Air filter
45°
(c) With the air-intake grille open about 45°,
remove the safety cord (hook on the grille
side). (Fig. 3-14)
Safety cord
(d) Pull the air-intake grille towards you to remove
it from the ceiling panel.
(2) Pull down the two panel catches on the body of
the indoor unit body. (Fig. 3-15)
Unit body
Fig. 3-14
Ceiling panel
Panel catch
Panel catch
(arrange facing downwards)
(2 locations)
Electrical
component box
Electrical
component box
Clamp
Ceiling panel wiring
connector
Screws M5 with washer
(supplied)
Air filter
Air-intake grille
Fig. 3-15
17
Panasonic_PAC-i_IndoorUnit_US-le17 17
2011/11/02 15:17:16
3-7. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the
panel hook with the panel catch of the indoor unit.
NOTE
The ceiling panel must be mounted in the correct
direction. Note that the 2 catches of the panel differ in
size. Confirm that the catches are correctly matched
between the ceiling panel and the indoor unit body.
(2) Next, check to see that the ceiling panel is properly aligned with the seamline of the ceiling. If it is
not, remove the ceiling panel and slightly readjust
the indoor unit body to the proper suspension
point.
(3) When the ceiling panel has been properly aligned,
use the supplied 4 mounting screws (M5) with
washers to permanently fasten the ceiling panel.
(4) Install the wiring connector from the ceiling panel
to the connector in the electrical component box of
the indoor unit. After installing the connector, use
the clamp on the body of the indoor unit to secure
the wiring.
(5) Install the air filter and air-intake grille by performing the steps in section 3-6 in reverse.
NOTE
Hook again the safety cord in its original position before
closing the air-intake grille.
3-8. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove
the air-intake grille and air filter, disconnect the wiring
connector inside the electrical component box, and then
remove the 4 mounting screws.
18
Panasonic_PAC-i_IndoorUnit_US-le18 18
2011/11/02 15:17:17
3-9. Duct for Fresh Air
For fresh air intake
There is a duct connection part on side of the indoor
unit. (Fig. 3-16)
CZ-26BCU1U
CZ-42BCU1U
ho
/8
ø1
4-
Type
2-3/8
Air-intake plenum
le
Air-intake plenum (including Duct connection box and
flange) are attached to the indoor unit when used to
take fresh outdoor air.
CZ-24KPU1U
(S-26PU1U6)
CZ-36KPU1U
(S-36PU1U6, S-42PU1U6)
Q’ ty
4
8
1
1
-1
3/3
2
2-5/32
Detail of fresh air intake
(1) Accessories
Check that the following parts are in the box when
unpacking.
NAME
Screw (M5xL4-7/8”)
Screw (M4xL4-1/2”)
Duct connection box
Duct connection flange
ø4
Unit: inch
Fig. 3-16
REMARKS
Air-intake plenum (for fastening)
Duct connection flange/box (for fastening)
(for fresh air)
(for connecting fresh air duct)
(2) Installation
Installation steps (a) to (d) are the same for both the
CZ-26BCU1U and the CZ-42BCU1U. The drawing
illustrates installation of air-intake plenum to the
CZ-26BCU1U
Installation screws
(a) Installing the air-intake plenum
(M5 × L4-7/8", 4 pcs)
Set the air-intake plenum to the indoor unit taking care
not to set to the incorrect direction.
Socket
cover
Panel lead wire (3P, 2P)
Fasten the air-intake plenum with the supplied screws.
(M5 × L4-7/8", 4 pcs)
(b) Installing the duct connection box
Fasten the duct connection flange to the duct connection
box with the accessory screws. (M4 × L1/2", 4 pcs)
Clamper
Air-intake
plenum
Fit the duct connection box into the rectangular hole of
the air-intake plenum and fasten it to the side of the
air-intake plenum with the accessory screws.
(M4 × L1/2", 4 pcs)
3P socket (White)
2P socket (Green)
(switch box side)
3P socket (White)
2P socket (Green)
(ceiling panel side)
(c) Installing the indoor unit
Install the indoor unit to the ceiling.
(Install the indoor unit according to instructions enclosed
with the outdoor unit.)
CAUTION
Indoor
unit
When installing in a preexisting location, install the
indoor unit before installing
the duct connection box.
Fig. 3-17
19
Panasonic_PAC-i_IndoorUnit_US-le19 19
2011/11/02 15:17:17
(d) Installing the ceiling panel
Duct connection flange
Attach the ceiling panel to the air-intake plenum.
Drawing the panel downwards sets the panel in position
temporarily with the panel catch (at 2 locations).
Duct connection box
Installation screws
Remove the socket cover of the air-intake plenum and pass
the 8P sockets through it.
(Fix the panel lead wire to air-intake plenum side clamper.)
(M4xL1/2”, 4pcs.)
Connect the 3P socket (white) and 2P socket (green) to the
other side of the 3P socket (white) and 2P socket (green)
respectively.
Reattach the socket cover.
Panel catch
Please fix the socket cover located on the switch box
after closing the lid for the switch box.
CAUTION
Ceiling panel
Take adequate precautions
when installing onto the
ceiling.
The air-intake plenum is
especially prone to rupture
if struck on it's side.
Fig. 3-18
20
Panasonic_PAC-i_IndoorUnit_US-le20 20
2011/11/02 15:17:17
■ Wall Mounted Type (K1 Type)
3-10. Removing the Wall Fixture from the Unit
Remove the set screws and take off the rear panel.
(Fig. 3-19)
NOTE
Set screws for transportation only
Fig. 3-19
Tubing can be extended in 3 directions as shown in
Fig. 3-20. Select the direction that provides the shortest
run to the outside unit.
Right-rear
tubing
(recommended)
Left-rear tubling
3-11. Selecting and Making a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Make
sure the unit is horizontal using a level gauge or
tape measure to measure down from the ceiling.
Right tubing
Fig. 3-20
(2) Determine which side of the unit you should make
the hole. (Fig. 3-21)
In case of left-rear or right-rear tubing
(3) Before making a hole, check carefully that no studs
or pipes are directly run behind the spot to be cut.
CAUTION
Also avoid areas where electrical wiring or conduits are
located.
Center of
left-rear
tubing hole
The above precautions are also applicable if tubing
goes through the wall in any other location.
Center of
right-rear
tubing hole
Fig. 3-21
NOTE
(4) Using a sabre saw, key hole saw or hole-cutting
drill attachment, cut a hole in the wall. See Table
3-3 and Fig. 3-22.
Hole should be made at a slight downward slant to
the outdoor side.
Table 3-3
PVC pipe (locally purchased)
Hole Dia. (inch)
3-3/16"
Indoor
side
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4" shorter than the thickness of the
wall. (Fig. 3-23)
Outdoor
side
Cut at slight angle
Fig. 3-23
Fig. 3-22
OUTSIDE
INSIDE
(6) Place the plastic cover over the end of the pipe
(for indoor side only) and insert in the wall.
(Fig. 3-24)
Wall
Plastic cover
(Field supply)
PVC pipe
Slight
angle
Fig. 3-24
21
Panasonic_PAC-i_IndoorUnit_US-le21 21
2011/11/02 15:17:18
3-12. Installing the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to suspend
the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 10 screws provided. (Fig. 3-25)
If you are not able to line up the holes in the rear panel
with the beam locations marked on the wall, use toggle
bolts to go through the holes on the panel or drill 3/16"
dia. holes in the panel over the stud locations and then
mount the rear panel.
Fig. 3-25
Fig. 3-26
(2) Double-check with a ruler or level gauge that the panel is
level. This is important to install the unit properly.
(Fig. 3-26)
1-3/16" or more
(3) Make sure the panel is flush against the wall. Any space
between the wall and unit will cause noise and vibration.
3/16"
dia. hole
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 3-27)
Rawl plug
(Field supply)
Fig. 3-27
22
Panasonic_PAC-i_IndoorUnit_US-le22 22
2011/11/02 15:17:19
3-13. Removing the Grille to Install the Indoor Unit
Grille
Air-intake grille
Basically, these models can be installed and wired
without removing the grille. If access to any internal
part is needed, follow the steps given below:
How to remove the grille
(1) Set the 2 flaps in the horizontal position.
Fig. 3-28a
(2) Unscrew the 3 screws. (Fig. 3-28a)
Air-intake grille
(3) Remove the grille.
(a) Hold both corners of the air-intake grille, then
pull out and up to open. (Fig. 3-28b)
(b) Use a flathead screwdriver to push up the 3
tabs to remove the grille. (Fig. 3-28b)
(c) Pull the lower part of the grille toward you to
remove. (Fig. 3-28a)
Fig. 3-28b
How to replace the grille
(1) Close the flaps.
(2) Reinstall the grille into the lower part while aligning its tabs on the upper part. (Fig. 3-29a) Insert
the tabs in the slots and push the lower part of the
grille back into position.
Fig. 3-29a
(3) Press at each of the 5 tabs to completely close the
grille. Make sure that the grille and frame are firmly
fitted together. (Fig. 3-29b)
3-14. Preparing the Indoor Side Tubing
Fig. 3-29b
Arrangement of tubing by directions
Frame
(a) Right tubing
The corner of the right frame needs to be cut by a
hacksaw or the like. (Fig. 3-30)
Right tubing
outlet
(b) Right-rear or left-rear tubing
In this case, the corner of the frame needs not be
cut.
Fig. 3-30
To mount the indoor unit on the rear panel:
Mounting slot
Tab
(a) Hang the 3 mounting slots of the unit on the upper
tabs of the rear panel. (Fig. 3-31)
Fig. 3-31
23
Panasonic_PAC-i_IndoorUnit_US-le23 23
2011/11/02 15:17:20
3-15.
Wiring Instructions
General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and circuit breaker for
overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insulation failure, the unit must be grounded.
(4) All wiring must be connected tightly.
(5) Do not allow wiring to touch refrigerant tubing, compressor, or any moving parts of the fan.
Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will
accept no responsibility for any damage or misoperation that occurs as a result of such
unauthorized changes.
3-16. Wiring Instructions for Inter-Unit Connections
Rear
panel
(1) Insert the inter-unit wiring (according to local
electrical codes) into the through-the-wall PVC
pipe. Run the wiring toward the indoor side allowing
approx. 10 inches to extend from the wall face.
(Fig. 3-32)
Wall
Plastic
cover
Wiring
(2) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for
connection. (Figs. 3-33a and 3-33b)
10 in.
Fig. 3-32
Terminal
plate
(3) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Figs. 3-33a and
3-33b) while referring to the wiring diagram.
(4) Be sure to secure the wiring with the provided
clamp.
How to remove the cover plate
To access the terminal plate inside the indoor unit,
follow these steps.
Cover plate
(1) Using a Phillips head screwdriver, remove the
screw on the cover plate. (Figs. 3-33a and 3-33b)
Fig. 3-33a
Connection for Solenoid
Vale Kit (for 3WAY)
Clamping
strap
(2) Remove the cover plate.
Power wiring
(field supplied)
Earth screw
Conduit
(field supplied)
Remote control wiring
and Inter-unit control
wiring (field supplied)
Fig. 3-33b
24
Panasonic_PAC-i_IndoorUnit_US-le24 24
2011/11/02 15:17:21
Cover
3-17. Shaping the Tubing
Refrigerant
tubing
(1) Shape the refrigerant tubing so that it can easily go
into the hole. (Fig. 3-34)
(2) Push the wiring, refrigerant tubing and drain hose
through the hole in the wall. Adjust the indoor unit
so it is securely seated on the wall fixture.
Inter-unit
wiring
Drain hose
(3) Carefully bend the tubing (if necessary) to run along
the wall in the direction of the outdoor unit and then
insulate to the end of the fittings. The drain hose
should come straight down the wall to a point where
water runoff will not stain the wall.
Fig. 3-34
Insulating
tape
(4) Connect the refrigerant tubing to the outdoor
unit.(After performing a leak test on the connection,
insulate it with insulating tape. (Fig. 3-35))
Fig. 3-35
(5) Assemble the refrigerant tubing, drain hose and
inter-unit wiring as shown in Fig. 3-36.
Refrigerant tubing
Inter-unit wiring
3-18. Installing the Drain Hose
Drain hose
Fig. 3-36
(1) The drain hose should be slanted downward on the
outdoor side. (Fig. 3-37)
(2) Never form a trap in the course of the hose.
Slant
(3) If the drain hose will run in the room, insulate* the
hose so that chilled condensation will not damage
furniture or floors. (Fig. 3-38)
Indoor
unit
* Foamed polyethylene or its equivalent is
recommended.
WARNING
Drain
hose
Fig. 3-37
Do not supply power to the unit
or operate it until all tubing and
wiring to the outdoor unit are
completed.
Condensation
Insulation material
(field supply)
must be used.
Fig. 3-38
25
Panasonic_PAC-i_IndoorUnit_US-le25 25
2011/11/02 15:17:22
■ Ceiling Type (T1 Type)
Front face
3-19. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the
ceiling at the spot where you want to install the
indoor unit. Use a pencil to mark the drill holes.
(Fig. 3-39).
Rear
Full-scale diagram
Fig. 3-39
NOTE
Hole-in-anchor
Hole-in-plug
Since the diagram is made of paper, it may shrink or
stretch slightly because of high temperature or
humidity. For this reason, before drilling the holes
maintain the correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the full-scale
diagram.
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
(3) Depending on the ceiling type:
Fig. 3-40
(a) Insert suspension bolts as shown in Fig. 3-40.
Ceiling tiles
or
Ceiling support
(b) Use existing ceiling supports or construct a
suitable support as shown in Fig. 3-41.
It is important that you use
extreme care in supporting the
indoor unit from the ceiling.
Ensure that the ceiling is
sufficiently strong enough to
support the weight of the unit.
Before hanging the ceiling
unit, test the strength of each
attached suspension bolt.
A
A
Fig. 3-41
(4) Screw in the suspension bolts, allowing them to
protrude from the ceiling as shown in Fig. 3-41.
The distance of each exposed bolt must be of
equal length within 2 inches. (Fig. 3-42)
unit
Ceiling
surface
Within 2 in.
WARNING
Fixture
Fig. 3-42
26
Panasonic_PAC-i_IndoorUnit_US-le26 26
2011/11/02 15:17:23
(5) Before suspending the indoor unit, remove the 2
screws on the latch of the air-intake grilles, open
the grilles, and remove them by pushing the claws
of the hinges as shown in Fig. 3-43. Then remove
both side panels sliding them along the unit toward
the front after removing the two screws which fix
them. (Fig. 3-44)
Pull out the
air-Intake grille
pushing claws
of the hinges
Screw
Hinge
Latch
de
Sli
(6) Preparation for suspending the indoor unit. The
suspension method varies depending on whether
the unit is next to the ceiling or not.
(Figs. 3-45 and 3-46)
Air-intake grille
Fig. 3-43
Slide toward
front side
Side panel
Fig. 3-44
Suspension bolt
(field supply)
unit
Ceiling surface
Washer (supplied)
Fixture
Double nut
(field supply)
Fig. 3-45
Suspension bolt
(field supply)
Washer (field supply)
unit
Washer (supplied)
Double nut
(field supply)
Fig. 3-46
27
Panasonic_PAC-i_IndoorUnit_US-le27 27
2011/11/02 15:17:24
Approx.
1 inch
(7) Suspend the indoor unit as follows.
(a) Mount a washer and two hexagonal nuts on
each suspension bolt as shown in Fig. 3-47.
Ceiling
surface
(b) Lift the indoor unit with a lifting machine to the
ceiling surface, and place it on the washers
through the notches, to fix it in place.
(Fig. 3-48)
Washer
(supplied)
Nut
(field supply)
Suspension bolt
Fig. 3-47
(c) Tighten the two hexagonal nuts on each
suspension bolt to suspend the indoor unit as
shown in Fig. 3-49.
NOTE
A ceiling surface is not always level. Please confirm
that the indoor unit is evenly suspended. For the installation to be correct, leave a clearance of about 3/8"
between the ceiling panel and the ceiling surface and
fill the gap with an appropriate insulation or filler
material.
(8) If the tubing and wiring are to go towards the rear
of the unit, make holes in the wall. (Fig. 3-50)
Fig. 3-48
(9) Measure the thickness of the wall from the inside
to the outside and cut PVC pipe at a slight angle to
fit. Insert the PVC pipe in the wall. (Fig. 3-51)
Fig. 3-49
Indoor
side
Outdoor
side
Fig. 3-50
PVC pipe (field supply)
INSIDE
Wall
OUTSIDE
PVC pipe
Slight
angle
Cut at slight angle
Fig. 3-51
28
Panasonic_PAC-i_IndoorUnit_US-le28 28
2011/11/02 15:17:25
3-20. Duct for Fresh Air
Duct connection port
(Knock-out hole)
There is a duct connection port (knock-out hole) at the
right-rear on the panel top of the indoor unit for drawing
in fresh air. If it is necessary to draw in fresh air, remove
the cover by knocking it out and connect the duct to the
indoor unit through the connection port. (Fig. 3-52)
If connection at the right-rear on the panel top is not
appropriate, another duct connection port can be made
by cutting an opening on the left side of the rear panel of
the indoor unit as shown in Fig. 3-53.
Panel Top
Fig. 3-52
Right side
3-21. Installing the Drain Piping
Rear side
Prepare a standard PVC pipe for the drain and
connect it to the indoor unit drain pipe with the
supplied hose clamps to prevent water leaks.
A
4-11/32"
B
Connect the drain piping so that it slopes downward
from the unit to the outside. (Fig. 3-54)
3-15/16"
Never allow traps to occur in the course of the piping.
Insulate any piping inside the room to prevent
dripping.
Use the supplied drain pipe to connect the drain pipe
with the drain outlet of the indoor unit.
Cut this portion
S-26PT1U6
S-36PT1U6, S-42PT1U6
A
3-15/16"
7-3/32"
B
1-3/8"
1-31/32"
Fig. 3-53
After connecting the drain pipe securely, wrap the
supplied drain pipe insulator around the pipe, seal
the gap at the drain socket with the supplied black
insulation tape, then secure it with clamps.
(Fig. 3-55)
Min. 1/100
Good
After the drain piping, pour water into the drain pan to
check that the water drains smoothly.
CAUTION
Check local electrical codes
and regulations before
obtaining wire. Also, check any
specified instruction or
limitations.
Not good
Fig. 3-54
Drain pipe
clamp
(supplied)
Adhere with
PVC adhesive. Hard PVC pipe
(not supplied)
Indoor
unit
Side
Packing softened Drain hose
(supplied)
(supplied)
Drain hose
adapter
(supplied)
Fig. 3-55
29
Panasonic_PAC-i_IndoorUnit_US-le29 29
2011/11/02 15:17:26
3-22. Required Minimum Space for Installation and
Service
min.
9-27/32
Electrical
component box
Inspection
access
17-23/32
×
17-23/32
Indoor Unit
Refrigerant
tubing
min. 25-19/32
min.
15-3/4
This air conditioner is usually installed above the
ceiling so that the indoor unit and ducts are not
visible. Only the air intake and air outlet ports are
visible from below.
The minimum space for installation and service is
shown in Fig. 3-56 and Table 3-4.
It is recommended that space be provided (17-23/32"
× 17-23/32") for checking and servicing the
electrical system.
Fig. 3-57 and Table 3-5 show the detailed
dimensions of the indoor unit.
22-27/32
A (Suspension bolt pitch)
min.
9-27/32
■ Low Silhouette Ducted Type (F1 Type)
Air outlet duct flange
Unit: inch
Fig. 3-56
Table 3-4
Unit: inch (mm)
Type
A (Length)
26
36
42-17/32 (1,080)
61-13/32 (1,560)
3
4
Number of duct flanges
Table 3-5
Unit: inch (mm)
Dimension
A
Type
B
C
D
E
F
G
H
I
J
K
No. of
holes
L M
35-7/16
L-ø1/4
(Hole)
J
J
11
I
3/4
H (Duct suspension bolt pitch)
G (Ceiling opening dimension)
4-ø15/32
(Hole)
9
10
11
19-9/32
(9-21/32×2)
9-27/32 12 16
9-7/16 16 18
Refrigerant tubing joint (liquid tube)
Refrigerant tubing joint (gas tube)
Upper drain port (O.D. 1-1/4 in.)
Bottom drain port (O.D. 1-1/32 in.)
Suspension lug
Power supply outlet (2-ø1-3/16 hole)
Fresh air intake port (ø5-29/32 hole)
Flange for the flexible air outlet duct (ø7-7/8 hole)
Tube cover
Electrical component box
Flange for the air intake duct
(Option or field supply)
12-7/32
1-7/32
1-7/32 M-ø1/8
(Hole)
B
(Suspension bolt pitch)
22-27/32
31/32
31/32
8-9/32
31/32
6-7/8
10
Inspection access
(17-23/32
×
17-23/32)
(Field supply)
E
C
D
(Suspension bolt pitch)
E
E
1-9/16
(5-29/32)
F
2-15/16
2-9/16
9
7-15/32
7-9/32
3-17/32
K
A (O.D.)
4-17/32
I
3/4
(Ceiling opening dimension)
10-13/16
3-15/32
3-15/16
31/32
13/32
13/32
2-5/32
13/32
10-1/4
(O.D.)
7-7/8
2-5/32
13/32
58-9/32 61-13/32 13-3/16 12-7/32 57-15/32 58-27/32 5-1/8
(9-21/32×1)
31/32
54-11/32
(9-1/16×6)
31/32
13/32
56-25/32
42-17/32 11-13/32 2-23/32 38-19/32 39-31/32 5-1/8
24-13/16
S-36PF1U6
39-3/8
(7-3/32×5)
2-3/4 1-3/16
6-5/16
37-7/8
3-11/32
S-26PF1U6
9-21/32
2-3/4
1-3/8
5-1/8
11-7/32
Inspection access panel
Ceiling
Unit: inch
Fig. 3-57
30
Panasonic_PAC-i_IndoorUnit_US-le30 30
2011/11/02 15:17:27
3-23. Suspending the Indoor Unit
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Depending on the ceiling type:
• Insert suspension bolts as shown in Fig. 3-58
or
• Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-59.
Suspension bolt (M10 or 3/8")
(field supply)
WARNING
It is important that you use
extreme care in supporting the
indoor unit inside the ceiling.
Ensure that the ceiling is strong
enough to support the weight
of the unit. Before hanging the
unit, test the strength of each
attached suspension bolt.
Fig. 3-58
Ceiling tiles
Ceiling support
(1) When placing the unit inside the ceiling,
determine the pitch of the suspension bolts
referring to the dimensional data on the previous
page. (Fig. 3-57)
Tubing must be laid and connected inside the
ceiling when suspending the unit. If the ceiling is
already constructed, lay the tubing into position for
connection to the unit before placing the unit inside
the ceiling.
Fig. 3-59
Suspension bolt
Suspension lug
Nuts and washers
(2 sets)
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in Fig. 3-58.
(Cut the ceiling material, if necessary.)
Upper
Lower
(3) Thread the 2 hexagonal nuts and washers (field
supply) onto the 4 suspension bolts as shown in
Figs. 3-60 and 3-61. Use 2 sets of nuts and washers (upper and lower), so that the unit will not fall
off the suspension lugs.
Fig. 3-60
Suspension bolt
Hexagonal nut
Fig. 3-61
31
Panasonic_PAC-i_IndoorUnit_US-le31 31
2011/11/02 15:17:27
Fig. 3-62 shows an example of installation.
Bolt anchor
Air outlet duct
Suspension bolt
Air-intake duct
Air-outlet grille
Ceiling material
Indoor unit
Air-intake grille
Fig. 3-62
3-24. Installing the Drain Piping
(1) Prepare standard hard PVC pipe for the drain and
use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
When doing this, leave a gap between the drain
socket of the unit and the PVC pipe to allow the
drainage to be checked. The transparent drain
pipe allows you to check drainage. (Fig. 3-63)
Transparent part for
checking drainage
Packing
(supplied)
CAUTION
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-63)
Hose band
(supplied)
Drain hose
(supplied)
Drain hose
adapter
(supplied)
Adhere with
PVC adhesive.
Hard PVC pipe
(not supplied)
Fig. 3-63
Clamps (supplied)
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator
around the pipe, then secure it with the supplied
clamps. (Fig. 3-64)
Drain insulator (supplied)
NOTE
Fig. 3-64
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
32
Panasonic_PAC-i_IndoorUnit_US-le32 32
2011/11/02 15:17:28
Air bleeder
CAUTION
● Do not install an air bleeder tube as this may cause
water to spray from the drain pipe outlet. (Fig. 3-65)
Not good
● If it is necessary to increase the height of the drain
pipe, the section directly after the connection port
can be raised a maximum of 19-11/16".
Do not raise it any higher than 19-11/16", as this
could result in water leaks. (Fig. 3-66)
Fig. 3-65
11-13/16" or less
● Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water
to flow backward and leak when the unit is not
operating. (Fig. 3-67)
● Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should not
be allowed to hang unsupported from its connection
to the unit. Fasten the pipe to a wall, frame, or other
support as close to the unit as possible. (Fig. 3-68)
Refer to “
Good
19-11/16" or less
Fig. 3-66
Upward gradient
No good
SUPPLEMENT ON DRAIN PIPING”.
3-25. Checking the Drainage
Fig. 3-67
After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to
catch and wipe up spilled water.
Support pieces
Good
(1) Connect power to the power terminal board (L1, L2
terminal) inside the electrical component box.
Fig. 3-68
(2) Remove the tube cover and through the opening,
slowly pour about 0.3 gal. of water into the drain pan
to check drainage.
(3) Short the check pin (CN5 white) on the indoor control
board and operate the drain pump. Check the water
CAUTION
Be careful since the fan will start
when you short the pin on the
indoor control board.
(4) When the check of drainage is complete, open the
check pin (CN5 white) and remount the insulator and
drain cap onto the drain inspection port.
CAUTION
To mount the tube cover, use 5/16"
(4 × 8 mm) tapping screws.
Do not use long screws as they
may puncture the drain pan and
cause water leak-age.
33
Panasonic_PAC-i_IndoorUnit_US-le33 33
2011/11/02 15:17:29
3-26. Increasing the Fan Speed
Electrical component box
If external static pressure is too great (due to long
extension of ducts, for example), the air flow volume
may drop too low at each air outlet. This problem may
be solved by increasing the fan speed using the
following procedure:
Booster cable
Fan
motor
Booster cable
Fan motor socket
(At shipment)
(Booster cable installed)
Fig. 3-69
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets
between the disconnected fan motor sockets in
step 2 as shown in the Fig. 3-69.
(5) Place the cable neatly in the box and reinstall the
cover plate.
■ How to read the diagram
Indoor Fan Performance
26 Type
36 Type
200
0.2
50
(inAq)
t line
Limi
0.6
0.5
100
Lim
it li
ne
it lin
Lim
0.3
HT
150
External Static Pressure
0.4
e
100
0.5
0.4
0.3
HT
50
SUPPLEMENT ON DRAIN PIPING”.
0.1
M
500
0
900
700
0
500
Air Flow (CFM)
NOTE
0.1
L
L
0
300
0.2
H
H
M
Refer to “
0.8
(Pa)
(inAq)
l in e
Limit
(Pa)
150
External Static Pressure
The vertical axis is the external static pressure
(Pa) while the horizontal axis represents the air
flow (CFM).
The characteristic curves for “HT”, “H”, “M” and “L”
fan speed control are shown.
The nameplate values are shown based on the
“H” air flow. For the 26 type, the air flow is 636
CFM, while the external static pressure is 49 Pa
at “H” position. If external static pressure is too
great (due to long extension of duct, for example),
the air flow volume may drop too low at each air
outlet.
This problem may be solved by increasing the fan
speed as explained above.
0
1000
Air Flow (CFM)
HT : Using the booster cable
H : At shipment
Fig. 3-70
34
Panasonic_PAC-i_IndoorUnit_US-le34 34
2011/11/02 15:17:30
3-27. When Installing the Indoor Unit
Confirm that the indoor unit should be installed in a horizontal position.
Use the level gauge or vinyl tube and check every four corner of the
unit is in horizontal.
If the air outlet duct flange is positioned with downward gradient,
there is in danger of water splash or drainage.
Also, dust may sometimes be contaminated inside the drain pan caused
by the residual drain water.
Install the air outlet duct flange side in horizontal or upward and within the
range of 3/8" in the upward direction.
Never install it with a downward gradient against horizontal.
Level gauge
Air outlet duct flange
Make sure to confirm
that the unit is in horizontal
at the position of the
ceiling-mount hanger by
using a level gauge
or vinyl tubing.
(Prohibited)
(Prohibited)
Fig. 3-71
3-28. Required Minimum Space for Installation and Service
If the ceiling tiles cannot be removed, provide the opening holes on the
lower side of the indoor unit for removing the unit in order to maintain
and clean the drain pan and heat exchanger or provide a minimum of
1.0 ft. or more space.
Min. 1.0 ft. or more space
Fig. 3-72
35
Panasonic_PAC-i_IndoorUnit_US-le35 35
2011/11/02 15:17:30
■ SUPPLEMENT ON DRAIN PIPING
Checkpoint after installation
After installation of indoor and outdoor units, panels and electrical wiring, check the following items.
Checkpoint
1
Symptom
Make sure whether indoor and outdoor units are
correctly installed.
Remark
Fall, vibration, noise
2 Make sure whether gas leakage is tested.
3
Check
No cooling, no heating
Make sure whether insulation is completed.
(Refrigerant piping and drain piping)
Water leakage
4 Make sure whether drain water is running smoothly.
Water leakage
5
Make sure whether the power voltage matches the
nameplate.
Inoperative, burnout
6
Make sure whether there is miswiring or incorrect
connection.
Inoperative, burnout
7
Make sure whether the ground construction is
completed.
Ground leakage
8
Make sure whether the wire gauge is followed by the
recommended specifications.
Inoperative, burnout
9
Make sure whether the air intake and air outlet of the
indoor and outdoor units are sealed by obstacles.
No cooling, no heating
36
Panasonic_PAC-i_IndoorUnit_US-le36 36
2011/11/02 15:17:31
4. ELECTRICAL WIRING
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and
circuit breaker for overcurrent protection should be
provided in the exclusive line.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, must follow your
LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
(3) To prevent possible hazards from insulation
failure, the unit must be grounded.
The remote control wiring and the inter-unit
control wiring should be wired apart from the
inter-unit power wiring.
(4) Each wiring connection must be done in
accordance with the wiring system diagram.
Wrong wiring may cause the unit to disorder or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or malfunction that
occurs as a result of such unauthorized changes.
Use shielded wires for inter-unit control wiring
between units and ground the shield on one side
only.
(9) If the power supply cord of this appliance is
damaged, it must be replaced by a repair shop
appointed by the manufacturer, because specialpurpose tools are required.
(10) All wiring used must be Class 1.
4-2. Recommended Wire Length and Wire Diameter for Power Supply System
You must follow LOCAL ELECTRICAL CODES for wiring.
Outdoor Unit
Type
Time delay fuse or
circuit capacity
U-26PE1U6
30 A
U-36PE1U6
35 A
U-42PE1U6
40 A
Type
Time delay fuse or
circuit capacity
U-26PS1U6
25 A
U-36PS1U6
30 A
U-42PS1U6
35 A
37
Panasonic_PAC-i_IndoorUnit_US-le37 37
2011/11/02 15:17:31
Indoor Unit
Type
Time delay fuse or
circuit capacity
U1, K1, T1, F1
15 A
Control Wiring
(A) Inter-Unit Control Wiring
(B) Remote Control Wiring
(C) Control Wiring For Group Control
AWG #18
1
Use high voltage wire (300 V)*
AWG #18*2 (0.75 mm2)
AWG #18*2 - (0.75 mm2)
Max. 3,300 ft.
Max. 1,650 ft.
Max. 650 - ft. (Total)
AWG=American Wire Gauge
*1 With ring-type wire terminal
*2 Wire joint connection
4-3. Wiring System Diagrams
Basic wiring diagram for standard control
Outdoor
Outdoor unit
unit
INV
INV unit
unit
Inter-unit
power
Inter-unit
power
lineline
Indoor
Indoor 208 208
60 1-PH
Hz
/ 230/ 230
V, 60V,Hz,
unit
unit
L1
L1
L2
L2
**
1
L1
2
L2
Remote
Remote
controller
Controller
WHT
WHT 11
BLK
BLK 22
Wire joint
connection
G
11
22
Grounding
Grounding line
line
Grounding
Grounding line
line
G
G
A
A
U1
U1
U1
U1
U2
U2
U2
U2
B B
L1
L1 Power
Power supply
supply
L2
L2 208
208 // 230
230 V,
V, 60Hz
60Hz, 1-PH
11
22
** Disconnect
Disconnect switch
switch
Field
Field supply
supply
Outdoor
Outdoor unit
unit
INV
INV unit
unit
Inter-unit
power
Inter-unit
power
lineline
Indoor
Indoor 208 208
60 1-PH
Hz
/ 230/ 230
V, 60V,Hz,
unit
unit
L1
L1
L2
L2
**
C
1
L1
2
L2
C
Wire joint
connection
G
11
22
Grounding
Grounding line
line
L1
L1 Power
Power supply
supply
L2
L2 208
208 // 230
230 V,
V, 60Hz
60Hz, 1-PH
Grounding
Grounding line
line
G
G
A
A
U1
U1
U1
U1
U2
U2
U2
U2
NOTE
Disconnect switch may be needed by the National/Local code.
U1,CT1,
F1 Types
Type
(Outdoor Unit)
5P terminal
board board
8P terminal
ALWAYS COMPLY WITH NATIONAL AND LOCAL
CODE REQUIREMENTS.
L2U2 1U1 2U2G L1 L2
L1U1
NOTE
Power
Inter-unit
supply
control wiring
(1) Refer to Section 4-2. Recommended Wire Length
and Wire Diameter for Power Supply System for the
explanation of “A”, “B” and “C” in the above diagrams.
(2) Inter-Unit Control Wiring (A) and remote control
wiring (B), (C) have no polarity. But for other wiring,
respect polarity. Be sure to connect as shown in the
Wiring System Diagram.
(3) In case of separate supply connection to indoor unit,
over current protection must be provided between
power source and indoor unit.
Unit
Remote
Inter-unit
Power control
wiring
control
Remote
power
Linewiring
Line
control
Line
K1 Type
5P terminal board
L1 L2
U1 U2
Power
supply
Unit
control
Line
Remote
control
Line
MAXIMUM OVER CURRENT PROTECTION 15 A
(FUSE OR HACR TYPE CIRCUIT BREAKER)
38
Panasonic_PAC-i_OutdoorUnit_US-l22
22
Panasonic_PAC-i_IndoorUnit_US-le38 38
2011/07/08 15:17:31
9:46:23
2011/07/11
21:19:05
2011/11/02
7/08 9:46:23
Stranded wire
Strip 3/8"
WARNING
Loose wiring may cause the
terminal to overheat or result
in unit malfunction. A fire
hazard may also exist.
Therefore, ensure that all
wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow the instructions on “How to connect
wiring to the terminal” and fasten the wire securely with
the fixing screw of the terminal plate.
Ring
pressure
terminal
Fig. 4-1
Special
washer
4-4. How to Connect Wiring to the Terminal
Wire
Screw
Ring pressure
terminal
Terminal plate
Screw and
Special washer
Ring
pressure
terminal
For stranded wiring
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to expose the
stranded wiring about 3/8". (Fig. 4-1)
Wire
Fig. 4-2
(2) Using a Phillips head screwdriver, remove the terminal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal. (Fig. 4-1)
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a
screwdriver. (Fig. 4-2)
39
Panasonic_PAC-i_IndoorUnit_US-le39 39
2011/11/02 15:17:32
5. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER
IMPORTANT
When using this air conditioner with the wireless remote controller it may sometimes be impossible to change
the operation modes while other indoor unit is running.
When this happens, a double beep tone sounds, the (operation lamp) lights up, and the (Timer lamp) and
(Standby lamp) blink alternately.
Operation is the same even during (AUTO mode) automatic cooling or heating.
A beep tone sounds 5 times and no changes can be made when any of the ON/OFF, MODE, Temperature setting
buttons were pressed while set under central control by the system controller.
5-1. Wireless Remote Controller Installation
The remote controller can be operated from either a non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do not install the remote controller in the following places:
In direct sunlight.
Behind a curtain or other place where it is covered.
More than 26 ft. away from the air conditioner.
In the path of the air conditioner’s airstream.
Where it may become extremely hot or cold.
Where it may be subject to electrical or magnetic interference.
(1) If Wall-mounted Fixed Position
Install the remote controller at a convenient
location on a nearby wall. However, before
attaching the remote controller mounting cradle,
check that the remote controller can operate from
the desired wall position. (Fig. 5-1)
Fasten the remote control
mount with screws.
Fitting the remote
control in the mount.
2 Press
How to Install Batteries
1 Put in
See Fig. 5-2.
(1) Press and slide the lid on the back of the remote
controller in the direction of the arrow.
Remote control mount
Fig. 5-1
(2) Install two AAA alkaline batteries. Make sure the
batteries point in the direction marked in the
battery compartment.
(3) Press the reset hole, then replace the lid. If you
press it, the current time, ON time, and OFF time
are all reset to 0:00.
Reset hole
Cover
Fig. 5-2
40
Panasonic_PAC-i_IndoorUnit_US-le40 40
2011/11/02 15:17:32
5-2. Room Temperature Sensor Setting
The room temperature sensors are built into the indoor unit and the wireless remote controller. Either of these room
temperature sensors can operate.
The system is shipped from the factory set to the indoor unit sensor. To switch to the remote control sensor, press the
sensor switching button located inside the remote control cover and check that A/C SENSOR on the LCD display panel
goes out.
NOTE
If the sensor switch is set to the remote controller side,
but no room temperature data is sent to the main unit
for 10 minutes, the sensor is automatically switched to
the indoor unit side. As much as possible, install the
remote controller facing the unit.
Sensor button
Fig. 5-3
5-3. Address Switches
If you are installing more than 1 indoor unit (up to 6) in the same room, it is necessary for you to assign each unit its
own address so they each can be operated by their remote controller.
Up to 6 indoor units can be controlled separately through the address switches. The operating control has the reception
address switch and the remote controller has the transmission address switch. This function is utilized by matching the
transmission and reception address switches.
Remote control
address display
ADR
Address switch
positions
* Any address
switch position
available
ADR
ADR
ADR
123
123
123
456
456
456
5-4. Setting the Model Code
Flap display selector switch
Make the slide switch settings in the battery compartment box of the remote controller depending on the type of
indoor unit in which the wireless receiving unit is used.
Operation mode switch
In this Single Split System Air Conditioner set the switch to “A”.
* The switch is factory set to “S” / “A”.
* Always press the reset button after switching the setting.
S
K
N
A
H
C
2
Operation
mode switch
1
Flap display
selector switch
2
S
N
U1, T1 types
A
1
K
H
C
Heat pump with
Auto mode
S
K
N
K1 type
A
H
C
Heat pump without
Auto mode
S
K
N
F1 type
A
H
C
Cooling only
Fig. 5-4
41
Panasonic_PAC-i_IndoorUnit_US-le41 41
2011/11/02 15:17:33
<CZ-RWSU1U>
■ 4-Way Cassette Type (U1 Type)
Air intake grille
5-5. Indicator Section Installation
Mark section
(indicator section)
Remove the ceiling panel and indicator cover and
install the indicator section.
(1) Remove the ceiling panel.
(2) Remove the corner cover behind the mark section.
(3 screws)
(3) Remove the mark section inside the ceiling panel.
(2 screws)
(4) Install the indicator section in the location where the
mark section was attached. (2 screws)
(5) Form the wire to match the panel ribs as shown in
Fig. 5-6.
(6) Install the corner cover. (Restrain the wire with the
corner cover.)
Ceiling panel
Corner cover
3 screws
Fig. 5-5
5-6. Operating Controller Installation
CAUTION
Pass the wiring through under the shaft.
Do not twist the operating
controller wires together
with the power supply
wires. Doing so can result
in malfunction.
If electrical noise is induced
in the unit power supply,
take appropriate measures,
for example installing a
noise filter.
Wiring
Install the operating controller at the indoor unit intake
port section.
2 screws
Indicator section
(1) Fasten the operating controller to the indoor unit
intake port section (electrical component box
opposite side) with the 2 accessory screws
(4×L13/32").
Fig. 5-6
(2) Connect the operating controller 2 wires (WHT,
BLK) to the remote control wire (WHT) in the
electrical component box. (For details on
wiring, see the section “5-9. Electrical wiring” .)
Operating
controller
(3) Install the ceiling panel.
(4) Connect the indicator section and the operating
controller with the 6P connector (white).
Electrical
component box
Screws
Fig. 5-7
(5) Form the wires with vinyl clamps and fasten.
(6) Connect the ceiling panel wiring connector (2P,
3P) to the body connector in the electrical component
box.
(7) For details on test operation, see “Test Run.”
42
Panasonic_PAC-i_IndoorUnit_US-le42 42
2011/11/02 15:17:33
■ Ceiling Type (T1 Type)
5-7. Indicator Section Installation
Remove the side panel to install the indicator section.
(Fig. 5-8)
Indicator section
Indicator section
Cover B
(Not used when
the indicator section
is installed.)
(1) Remove the side panel.
Open the air intake grille, remove the screw at
one place and then remove the side panel by
sliding it toward the front (arrow direction).
(2) Remove cover A and cover B.
Insert a flathead screwdriver into the grooves
of cover A to remove cover A and cover B.
(When removing the cover, take care not to
scratch the panel.)
(3) Remove cover B from cover A.
(4) Install the indicator section at cover A.
(5) After passing through the lead wires, install cover
A and the indicator section at the panel hole.
(The protrusion part of cover A is fixed with the
panel hole.)
(6) Bundle the lead wires along with the wiring of the
louver motor.
(7) Install the side panel.
Panel
Side panel
Cover A
Grooves
Air intake grille
Cover A
Grooves
Fig. 5-8
5-8. Operating Controller Installation
CAUTION
Install the operating controller on the top face of the air
intake section (space between the fan motor and the
electrical component box). (Fig. 5-9)
Do not twist the operating
controller wires together
with the power supply
wires. Doing so can result
in malfunction.
(1) Fasten the operating controller to the ceiling
panel of the air intake section with the 2 supplied
screws (4×L13/32").
If electrical noise is
induced in the unit power
supply, take appropriate
measures, for example
installing a noise filter.
(2) Draw the lead wires into the electrical component
box and connect the operating controller 2 wires
(WHT, BLK) to the remote control wires in the
electrical component box.
(3) Connect the indicator section and the operating
controller using the 6P connector in the electrical
component box.
Operating controller
Electrical component box
Fig. 5-9
43
Panasonic_PAC-i_IndoorUnit_US-le43 43
2011/11/02 15:17:34
5-9. Electrical Wiring
Signal receiving unit
Indoor PCB
1
WL 2
Operating controller W2
CN2 (0.7 ft.)
CN1
BLU
W1 (4.3 ft.)
YEL
PNK
WHT
RED
BLK
GRY
BLK
W3 Indicator section
(4.3 ft.) CN1
BLU
YEL
PNK
RED
GRY
BLK
Relay connector
Fig. 5-10
Connection method
(1) Connect W1 to the indoor PCB WL connector.
(2) Connect W3 from the indicator section with W2 from the operating controller using the relay connector.
5-10. Test Run Switch
The test run switch is located in the operating control unit.
See the Installation Instractions attached to the outdoor unit.
5-10-1. How to use the test run setting (U1, T1 Types)
(1) Set DIP switch [DS] No. 1 on the wireless receiver
unit PCB from OFF to the ON position.
All OFF( ) for
initial settings.
(2) Press the ON/OFF operation button on the
wireless remote controller.
(3) Make a test run using the air conditioner in
COOL or HEAT mode.
1234
1.TEST RUN
2.PCB CHK.
3.RCU: MAIN
RCU: SUB
4.NORMAL
ALL •
(4) During the test run, each of the 3 indicator lamps
on the indoor unit flash.
DIP switch
No. 1
(5) During the test run, the air conditioner runs
continuously and the thermostat does not control
the system.
ADR
123
456
Address
switch
Flap
button
ON/OFF
operation
button
Fig. 5-11
(6) After the test run, be sure to reset DIP switch No. 1
back to the OFF position and check that no indicator
lamps are blinking.
(This receiver includes a 60-minute automatic OFF
timer function in order to prevent continuous test run.)
NOTE
In case of 4-way Cassette type, test run operation is not possible without the ceiling panel installation.
To protect the air conditioner from overloading, the outdoor unit will not start running for 3 minutes after
power is applied or the air conditioner is turned off and then back on.
When the air conditioner fails to start the test run, 1 or more of the 3 alarm indicator lamps on the indoor
unit will flash (See next section).
When the DIP switch is set to “TEST – ON,” temperature control from the wireless remote controller is disabled.
Do not use this setting at any time other than for the test run. Doing so will place an excessive load on the system.
To avoid placing an excessive load on the equipment, use this function only when conducting the test run.
44
Panasonic_PAC-i_IndoorUnit_US-le44 44
2011/11/02 15:17:34
5-11. Misoperation Alarm Indicators
Alarm indicator lamps on the indoor unit indicate the error
cause if the air conditioner fails to operate upon being
switched on. The possible alarm indications are given in
Table 5-1. Fig. 5-12 shows the location of the alarm lamps
on the indoor unit.
(See Table 5-1 and Fig. 5-12.)
Table 5-1
Alarm
(OPERATION
lamp)
(TIMER
lamp)
Cause of Trouble
(STANDBY
lamp)
S.C. errors* between the indoor unit’s controller (PCB) and the remote
controller.
Compressor protector is working.
S.C. errors between indoor and outdoor units.
Indoor or outdoor thermistor is malfunctioning.
Outdoor unit protector is working.
Indoor unit protector is working.
TEST RUN switch on the operation controller is in ON state.
*
S.C.: Serial communications
OPERATION
lamp
TIMER
lamp
STANDBY
lamp
Remote control
receiver
Fig. 5-12
NOTE
Stick the alarm message label accompanying the
wireless remote controller on the electrical component
box to indicate the cause of trouble for future reference.
45
Panasonic_PAC-i_IndoorUnit_US-le45 45
2011/11/02 15:17:35
<CZ-RWSC1U>
CAUTION
If the signal receiving unit is installed near a rapid-start or inverter type fluorescent
lamp (neither one uses glow lamps), it may be impossible to receive signals from the
wireless remote controller. To avoid signal interference from fluorescent lamps, install
the receiving unit at least 6.6 ft. away from the lamps and install at a location where
wireless remote controller signals can be received when the fluorescent lamps are on.
5-12. Separate Type Signal Receiving Unit Installation
CAUTION
Do not twist the operating
controller wires together
with the power supply
wires. Doing so can result
in malfunction.
M4 × L1"
Screws (2)
Signal receiving unit
Spacer
ALL•
RCU :
SU
PCB C B
H
TEST R K.
UN
If electrical noise is induced
in the unit power supply,
take appropriate measures,
for example installing a
noise filter.
RCU :
M
NORM AIN
AL
ADR
123
456
Notch
If local electrical codes allow, this signal receving
unit can be mounted using a conventional wall box
for flush mounting.
Switch box (no cover)
Cover plate
Fig. 5-13
Fasten the remote control
mount with screws.
(1) If Wall mounted Fixed Position
Install the remote controller at a convenient
location on a nearby wall. However, before
attaching the remote controller mounting cradle,
check that the remote controller can operate from
the desired wall position. (Fig. 5-14)
Fitting the remote
control in the mount.
2 Press
1 Put in
How to Install Batteries
See Fig. 5-15.
Remote control mount
Fig. 5-14
(1) Press and slide the lid on the back of the remote
controller in the direction of the arrow.
(2) Install two AAA alkaline batteries. Make sure the
batteries point in the direction marked in the
battery compartment.
(3) Press the reset hole, then replace the lid. If you
press it, the current time, ON time, and OFF time
are all reset to 0:00.
Reset hole
Cover
Fig. 5-15
46
Panasonic_PAC-i_IndoorUnit_US-le46 46
2011/11/02 15:17:35
When using the signal receiving unit on a wall with
the front exposed, choose a wall surface that the
signal receiving unit can be mounted on.
Run the remote con
cable through a notch
in the upper case.
(1) Insert a flathead screwdriver into the slot on the lower
side of the signal receiving unit and pry off the back
case.
(2) The wire routing at the signal receiving unit comes out
of the upper case (thin portion at upper center) so use
nippers or a similar tool to cut out a notch beforehand
large enough for the remote control cable (option) to
pass through as shown in Fig. 5-16.
(3) Remove the wire, which is connected prior to shipping,
from the connector.
Fig. 5-16
Clamp (Supplied)
About 3/32"-1/8"
Connector
Remote control cord
(Option)
Fig. 5-17
Remote control cord (Option)
Signal receiving unit
Clamp
(4) Connect the remote control cable (option) to the signal
receiving unit connector as shown in Fig. 5-17 after the
clamp (supplied) with the unit is installed.
ALL•
RCU :
SUB
PCB C
H
TEST R K.
UN
(5) After arranging the wiring on the printed circuit board
as shown in Fig. 5-18 so that it is contained within the
signal receiving unit, attach the back case. At this time,
arrange so that the head of the clamp faces the side.
RCU :
M
NORM AIN
AL
ADR
123
456
(6) Remove the cover plate and install the signal receiving
unit using the 2 wood screws.
Fig. 5-18
Wood screws (2)
(7) Fasten to the wall using the cord clip (supplied).
Fig. 5-19
(8) Reinstall the cover plate.
To use the signal receiving unit while mounted on the
ceiling, install by using the carrier for ceiling installation
supplied with the unit.
A
(1) Remove the cover plate by inserting a flathead
screwdriver into the notch in the lower section and
prying it off.
(2) Cut out a section (3-3/4"×2-1/32") on the ceiling using
the paper pattern (supplied) as a guide.
(3) Run the wire through the mounting carrier and insert
into the installation hole as shown in Fig. 5-20.
B
Fig. 5-20
(4) Fit securely into the ceiling material at sections (A)
and (B) as shown in Fig. 5-21.
(5) Connect the wire (2-wire core) from the signal
receiving unit with the wire from the indoor unit. (See
section on how to wire the receiving unit.) as shown in
Fig. 5-21.
Fig. 5-21
(6) Use the supplied spacers to adjust for a thickness
several inches more than the ceiling material and
lightly fasten the receiving unit in place with the small
screws (M4×1-9/16", 2 pcs.) supplied with the unit.
(7) Tighten the machine screws after fitting sections (A)
and (B) into the openings, in the gap between the
signal receiving unit and ceiling surface as in Fig. 5-22.
Do not apply strong force when tightening the screws.
Excessive force might warp or damage the cover.
When finished, the signal receiving unit should still be
able to move slightly when pressed as shown in Fig.
5-22.
Fig. 5-22
(8) Reinstall the cover plate.
47
Panasonic_PAC-i_IndoorUnit_US-le47 47
2011/11/02 15:17:35
5-13. Electrical Wiring
CAUTION
Be sure to do the wiring
correctly (incorrect
wiring will damage the
equipment).
Recommended wire diameter and allowable length
for signal receiving unit wiring and its branch wiring:
AWG #18, MAX 1,300 ft.
Terminal board
for indoor unit
remote control
wiring
1
2
WHT
1
BLK
2
Signal receiving
unit
Wire from signal receiving unit
Connection
Signal receiving unit wiring (field supply)
Wire joint (2 pcs.
white, supplied)
Signal receiving
unit wiring
Signal receiving
unit wiring
Wire joint CE-1
(supplied)
(1) Strip the insulation to approximately 9/16" from the ends
of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp connection
at the wire joint.
(3) If a special crimping tool is not used, or if the connection
is soldered, insulate the wires using insulation tape.
5-14. Test Run Switch
(1) Remove the cover plate of the signal receiving unit.
Set the “TEST RUN” switch of the dip switches to
the ON position.
(2) Press the ON/OFF operation button on the
wireless remote controller.
CAUTION
ALL•
RCU : SUB
PCB CHK.
TEST RUN
RCU : MAIN
NORMAL
123
ALL•
RCU : SUB
PCB CHK.
TEST RUN
To avoid placing an
excessive load on the
equipment, use this
function only when
conducting the test run.
(3) Make a test run using the air conditioner in
COOL or HEAT mode.
(4) During the test run, the “OPER.,” “TIMER,”
and “STDBY” LED all blink.
ADR
456
Fig. 5-23
To protect the air conditioner from overloading, the outdoor unit will not start running for approximately 3 minutes
after power is applied or the air conditioner is turned off and then back on.
When the DIP switch is set to “TEST – ON,” temperature control from the wireless remote controller is disabled.
Do not use this setting at any time other than for the test run. Doing so will place an excessive load on the system.
(5) After the test run, press the ON/OFF operation button on the wireless remote controller. Then, set the
TEST RUN switch back to the OFF position to cancel the test run mode.
(This receiver includes a 60-minute automatic OFF timer function in order to prevent continuous test run.)
48
Panasonic_PAC-i_IndoorUnit_US-le48 48
2011/11/02 15:17:36
5-15. Misoperation Alarm Indicators
A blinking lamp for other than the signal receiving unit
filter shows that a problem has occurred in the unit, so
make an inspection. (Refer to servicing information in
the service manual, etc.) Also, if wired remote controller
and dedicated service check lines (CV6380230938:
service use) are available, then detailed error
information can be obtained by connecting to the
service connector as shown in the drawing. For
information on how to connect to the signal receiving
unit, refer to the instruction manual that came with the
dedicated service check lines.
Service
connector
ALL•
RCU : SUB
PCB CHK.
TEST RUN
RCU : MAIN
NORMAL
Fig. 5-24
8. Transmitter
9. Remote control sensor
1. Operation Display
2. Start/Stop button
3. Fan speed button
10. Temperature setting buttons
4. Swing/Wind Direction button
11. Filter button
12. Mode Select button
13. Ventilation button
5. Timer setting button
14. Address button
15. Sensor button
16. Clock button
6. Reset button
7. Cover
Fig. 5-25
Table 5-2
Lamp
OPERATION
lamp
TIMER
lamp
STANDBY
lamp
Bright
Cause of Trouble
No power supply or mis-wiring of signal receiving unit.
S.C.* errors between the indoor unit’s controller (PCB) and
signal receiving unit.
S.C. errors between indoor and outdoor units.
Alternately Indoor unit protector is activated.
Alternately Outdoor unit protector is activated.
Compressor protector is activated.
Concurrent Mis-setting of indoor unit.
Concurrent Mis-setting of outdoor unit.
*
S.C.: Serial communications
49
Panasonic_PAC-i_IndoorUnit_US-le49 49
2011/11/02 15:17:37
5-16. Basic Wiring Diagram
In case of using shielded wires for inter-unit control
wiring, ground the shield on one side. (Fig. 5-26)
Otherwise misoperation because of electrical noise
may occur.
Be sure to do the wiring
correctly (incorrect wiring
will damage the equipment).
CAUTION
Remote
Controller
Shielded wire
1 2
Ground
Wire joint
1 2
Fig. 5-26
Indoor unit
No. 1
U1 U2
Inter-unit
control
wiring
U1 U2
Outdoor unit
: Ground (earth)
Wiring procedure
Carry out the wiring according to the above wiring
diagram.
Address setting is automatically executed
after turning on the system.
An indoor unit address is assigned to each
indoor unit.
Operation takes place successively at
intervals of 1 second, by using combinations
of the address setting of each unit.
50
Panasonic_PAC-i_IndoorUnit_US-le50 50
2011/11/02 15:17:37
5-17. Wiring System Diagram for Group Control
This diagram shows when several units (maximum of
8) are controlled by a signal receiving unit (main
unit). In this case, a signal receiving unit can be
connected at any indoor unit.
Wiring procedure
Wire according to the diagram at left:
Address setting is executed automatically when the
outdoor unit is turned on.
Each successive unit will respond at one-second
intervals following the order of the group address
when the remote controller is operated.
Group control using 2 signal receiving units
It does not matter which of the 2 signal receiving units
you set as the main controller.
Remote
Controller
(main)
1 2
When using multiple signal receiving units (up to 2
can be used), one is the main signal receiving
unit and the other is the sub-signal receiving unit.
(sub)
Connection wiring
for group control
To set up a sub-signal receiving unit, change its
remote control address connector (RCU. ADR)
located on its PCB from main to sub position
(main: when shipped from factory).
1 2
Wire joint
1 2
1 2
1 2
1 2
Indoor unit
No. 1
Indoor unit
No. 2
Indoor unit
No. 3
Indoor unit
No. 8
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
Outdoor unit
U1 U2
Outdoor unit
U1 U2
Outdoor unit
U1 U2
Outdoor unit
: Ground (earth)
51
Panasonic_PAC-i_IndoorUnit_US-le51 51
2011/11/02 15:17:37
5-18. Wiring System Diagram for Multiple Remote Controllers
When installing multiple remote controllers
This multiple system is used for operating the unit(s) at
different positions. (A maximum of 2 signal receiving
units can be installed.)
Setting method
To execute this control, make the setting according
to the following procedure.
(1) Of the two installed signal receiving units, make
one the main signal receiving unit (factory-shipped
state).
(2) On the other signal receiving unit, change the
address connector on the PCB from main to sub
position.
In this state, it functions as a sub-signal receiving
unit.
Basic wiring diagram
CAUTION
Carry out the wiring correctly
(incorrect wiring will damage
the equipment).
Signal receiving unit
(main)
(sub)
(Option)
1 2
1 2
To operate 1 indoor unit with 2 signal receiving units
set at different locations.
Remote control
cable terminal
board
Connection wiring
1 2
Indoor unit
Earth
52
Panasonic_PAC-i_IndoorUnit_US-le52 52
2011/11/02 15:17:38
<CZ-RWSK1U>
5-19. Test Run Procedure
Wall mounted Type
(K1 Type)
Check the “Check Items Before the Test Run.”
(Item 5-20)
Verify the combination (wiring) of indoor and
outdoor units.
Set the indoor unit controller to “TEST.”
Is operation
possible?
NO
(Item 5-21-3)
Check using the Diagnosis
function table. (Refer to 5-24)
Note: Check the indoor-side drainage.
YES
Return the indoor unit controller to
“NORM.” (Item 5-21-3)
5-20. Check Items Before the Test Run
(1) Turn ON the remote power switch at least 12 hours before the test run in order to charge the crankcase heater.
(2) Fully open the service valves on the gas-tube and liquid-tube sides.
(3) Set the sliding switches on the inside of the wireless remote controller cover to the correct settings for that model.
After changing the settings, press the RESET hole.
Verify that sliding switch 1 is in the “S” position.
Wireless remote controller transmitter
SKN
Set sliding switch 2 to the correct setting for these models.
AHC
AHC
A: Heat pump model
(H: Heat pump, no auto heating/cooling)
C: Cooling-only model
RESET hole
SENSOR button
Sliding switch
53
Panasonic_PAC-i_IndoorUnit_US-le53 53
2011/11/02 15:17:38
5-21. Preparing for the Test Run
5-21-1. Changing the room temperature sensor
Room temperature sensors are installed inside the indoor unit and the wireless remote controller.
Either room temperature sensor can be used.
When “Unit Sensor” is indicated on the wireless remote controller’s LCD, the indoor unit sensor is operating as the
room temperature sensor.
To change to the remote control sensor, open the remote control cover and press the SENSOR button once. The
“Unit Sensor” display disappears, and the remote control sensor becomes the room temperature sensor.
CAUTION
If the temperature data from the remote controller is not communicated to the indoor
unit for a period of 10 minutes when the remote control sensor is selected, the unit
automatically switches back to the indoor unit sensor.
Install the remote controller in a location where the signal can reliably be received by
the indoor unit.
5-21-2. Using the remote controller
Face the remote controller toward the receiver (indoor unit).
The maximum distance where the remote controller signal can be received is approximately 26 ft., however this
distance is only a guide. The actual distance may vary somewhat depending on battery capacity and other
conditions.
Make sure there are no obstructions which can block the signal between the remote controller and the receiver.
When the remote controller signal is received correctly, the indoor unit beeps.
(It beeps twice only when operation is started.)
Receiver
Wireless Remote Controller
Do not drop, throw, or wash the remote controller.
Do not place the remote controller in a location exposed to direct sunlight, or near a stove or similar appliance.
5-21-3. Test run
For S-26PK1U6
Using the controller
Controller
(1) Slide the main unit controller switch from “ON” to “TEST”.
ON
(The outdoor unit will not operate for approximately 3 minutes after
OFF
the power is turned ON, or after operation is stopped.)
TEST
(2) All indicator lamps on the display blink while test run is in progress.
Indicator
(3) Temperature control is not possible during the test run.
(4) If normal operation is not possible, the lamps on the display will indicate
the problem. Refer to “5-24. Diagnosis Table”.
(5) After the test run is completed, move the controller switch from “TEST” to “ON” and verify that the indicator lamps
stop blinking.
(A 60-minute automatic OFF timer function is included in order to prevent continuous test run.)
CAUTION
Do not use this setting at any time other than for the test run. Doing so will place an excessive load on
the system.
Test run is not possible if the power was turned ON when the controller switch was in the “TEST” position.
Leave the power ON and move the switch to “OFF,” then move the switch back to “TEST.”
54
Panasonic_PAC-i_IndoorUnit_US-le54 54
2011/11/02 15:17:38
5-22. Precautions
Request that the customer be present at the time the test run is performed. Explain the Operating Instructions to
the customer, and then have the customer actually operate the system.
Be sure to pass the manual and warranty certificate to the customer.
Verify that the AC 208 / 230 V wiring is not connected to the terminal plate which is used to connect the inter-unit
control wiring.
* If AC 208 / 230 V is accidentally applied to this terminal plate, the fuse (0.5A for both indoor and outdoor units) on
the inter-unit control PCB will be tripped in order to protect the PCB. Correct the wiring connections, then
disconnect the 2P connectors (indoor unit: blue, OC, CN40; outdoor unit: blue, OC) which are connected
to the PCB and connect the other 2P connectors (indoor unit: brown, EMG, CN44; outdoor unit: brown, EMG).
(See the figure below.)
If operation is still not possible with the brown connectors connected, cut the varistor (black) (for both the indoor
and outdoor units).
(Be sure to turn OFF the power before performing this work.)
Indoor unit control PCB
<For K1 Type>
Outdoor unit control PCB
Fuse
0.5A
2P connector (blue)
2P connector (brown)
Fuse
0.5A
SW103 TEST
OFF
Varistor (black) ON
VA002
CHK (2P plug)
Serial 1 connector (blue)
Varistor (black)
Serial 2 connector (brown)
55
Panasonic_PAC-i_IndoorUnit_US-le55 55
2011/11/02 15:17:39
5-23. When Setting Indoor Unit Control PCB Switch for Wall Mounted Indoor Unit
When using both the wired and wireless remote controller, refer to the procedure below.
If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.)
This setting is not necessary for the case of using wireless remote controller only.
The slide switch setting at the time of factory shipment for model K1 type is “B.”
S-26PK1U6
When using wired remote controller as “sub”, to set its
data to “sub” in remote controller setting mode.
When using wireless remote controller as “sub”, set the
switch on the indoor unit control PCS to A.
When using
wireless
A remote
controller
Nos. 1, 2 OFF, No. 3 ON.
as “sub”
When using
wireless
B remote
controller
as “main”
Nos. 1, 2, 3 all OFF
56
Panasonic_PAC-i_IndoorUnit_US-le56 56
2011/11/02 15:17:39
57
Panasonic_PAC-i_IndoorUnit_US-le57 57
2011/11/02 15:17:39
Operating lamp
Nothing is
displayed
P 0 9 displayed
L 0 7 displayed
L 0 2 displayed
L 1 3 displayed
P 0 5 displayed
E 2 0 displayed
E 1 6 displayed
E 1 5 displayed
E 0 6 displayed
E 0 4 displayed
E 1 4 displayed
E 0 9 displayed
Timer lamp and
Standby lamp are
blinking alternately.
Both the Operation
lamp and Standby
lamp are blinking
together.
Operation lamp and
Standby lamp are
blinking alternately.
Standby lamp
is blinking.
E 0 2 displayed is blinking.
E 0 1 displayed
Nothing is
displayed
Wired remote
Indoor unit
spcontroller dilay receiver lamp
5-24. Diagnosis Table
unit type mismatch
indoor unit ceiling panel connector is not
connected correctly.
٨ The
٨ Indoor-outdoor
circuit or open phase in the outdoor
unit power
٨ Insufficient gas
٨ Inter-unit
serial signal is being received at all from
the indoor units.
unit capacity is too high.
٨ Indoor
٨ No
unit capacity is too low.
٨ Indoor
inter-unit wiring is not
connected correctly.
٨ Indoor-outdoor
address setting has not been
completed.
٨ Inter-unit control wiring is cut or is not
connected correctly.
٨ Remote controller is not connected correctly
(remote controller receiving failure).
٨Remote controller is not connected correctly
(failure in transmission from remote controller
to indoor unit).
٨ Automatic
controller is not connected correctly.
unit power is not ON.
٨Remote
٨ Indoor
1:1 connection (single type)
panel connector at one of the
indoor units in the group is not
connected correctly.
as at left
٨ Ceiling
٨ Same
phase or open phase in the
3-phase power at one of the outdoor
units in the group
as at left
٨ Reversed
٨ Same
inter-unit wiring is cut or
is not connected correctly.
as at left
٨Indoor-outdoor
٨ Same
address setting has not been
completed.
٨ Inter-unit control wiring is cut or is not
connected correctly.
٨ Remote controller is not connected with
indoor unit correctly
٨ Remote controller is not connected with
indoor unit correctly
٨ Automatic
controller is not connected with
indoor unit correctly
٨ Indoor unit power is not ON.
٨ Remote
Group connection
as at left
unit ceiling panel connector is not
connected correctly.
٨ Indoor
٨ Control
wiring for group control is connected
to the indoor unit, however it is set for individual
operation.
٨ Same
phase or open phase in the
outdoor unit 3-phase power
as at left
as at left
as at left
٨ Reversed
٨ Same
٨ Same
٨ Same
wiring for group control is cut or
is not connected correctly.
as at left
as at left
٨ Control
٨ Same
٨ Same
as at left
Simultaneous-operation multi system
(flexible combination)
٨ Same
Cause
as at left
as at left
as at left
٨ Same
٨ Same
٨ Same
٨Same
٨ Same
٨ Same
as at left
as at left
as at left
as at left
as at left
as at left
2 remote controllers are
set as the main remote
controller.
٨ Same as at left
٨
٨ Same
٨ Same
٨ Same
Control by main-sub
remote controllers
6. APPENDIX
■ Name of Parts
4-Way Cassette type (U1 type)
Water drain
Ceiling panel
(optional)
Air outlet
(4 locations)
Air intake grille
(air intake)
Low Silhouette Ducted type (F1 type)
Flexible duct
(optional)
Water drain
Canvas duct
(optional)
Air outlet grille
(optional)
Ceiling type (T1 type)
Air intake grille
(air intake)
(optional)
Air outlet
Water drain
(Drain pipe can be
connected to
either the left or
right side.)
Air intake
grille (air
intake)
Wall Mounted type (K1 type)
Air intake
Air outlet
58
Panasonic_PAC-i_IndoorUnit_US-le58 58
2011/11/02 15:17:39
■ Care and Cleaning
WARNING
1. For safety, be sure to turn the air conditioner off and also to disconnect
the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the
internal components and cause an electric shock hazard.
Air intake and outlet side
(Indoor unit)
Clean the air intake and outlet side of the indoor unit with a vacuum cleaner
brush, or wipe them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid
detergent. When cleaning the air outlet side, be careful not to force the vanes
out of place.
CAUTION
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do
not wipe plastic parts using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be
cleaned every year. Consult your dealer or service center.
Air filter
The air filter collects dust and other particles from the air and should be cleaned at
regular intervals as indicated in the table below or when the filter indication ( ) on the
display of the remote controller (wired type) shows that the filter needs cleaning. If
the filter gets blocked, the efficiency of the air conditioner drops greatly.
Type
U1
F1*
T1
K1
Period
Six months
(Depending on filter
specifications)
Two weeks
Two weeks
*Low Silhouette Ducted type (F1) :
An air filter is not provided with this air conditioner at the time of shipment. To get
clean air and to extend the service life of the air conditioner, an air filter must be
installed in the air intake. For installation and cleaning the air filter, consult your
dealer or service center.
NOTE
How to clean the filter
The frequency with which the filter should be cleaned depends on the environment
in which the unit is used.
1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
59
Panasonic_PAC-i_IndoorUnit_US-le59 59
2011/11/02 15:17:40
■ Care and Cleaning (continued)
How to remove the filter
4-Way Cassette type (U1) :
1. Use a screwdriver to remove the bolt screw on each side for the two latches. (Be sure to
reattach the two bolt screws after cleaning.)
2. Press on the two latches of the air intake grille with your thumbs in the direction of the
arrow to open the grille.
3. Open the air intake grille downward.
CAUTION
• When cleaning the air filter, never remove the safety chain. If it is necessary to
remove it for servicing and maintenance inside, be sure to reinstall the safety chain
securely (hook on the grille side) after the work.
• When the filter has been removed, rotating parts (such as the fan), electrically
charged areas, etc. will be exposed in the unit’s opening. Bear in mind the dangers
that these parts and areas pose, and proceed with the work carefully.
4. Remove the air filter attached to the air intake grille.
U1 type
Latch
Air intake
grille
Safety chain
Bolt screws
Air filter
60
Panasonic_PAC-i_IndoorUnit_US-le60 60
2011/11/02 15:17:40
■ Care and Cleaning (continued)
How to remove the filter
(continued)
Ceiling type (T1) :
1. Take hold of the finger-hold on the air intake grille and press it to the rear, and the grille will
open downward.
2. Take hold of the finger-hold on the air filter, pull it toward you.
Air filter finger-hold
Air intake grill
Air intake grill
finger-hold
Hook
de
Sli
Screw
Air filter
Screw
Latch
Air filter finger-hold
* Take hold of the finger-hold on the air filter, pull it toward you.
Wall mounted type (K1):
1. Move the flap on the air outlet grille to its lowest position with the remote controller.
2. The filter is disengaged by pushing the tab up gently. Hold the air filter by the tab at the
bottom, and pull downward.
Air intake grille
Air filter
When replacing the filter, make sure that the FRONT mark is facing you. Push it up until you
hear it click back into position.
61
Panasonic_PAC-i_IndoorUnit_US-le61 61
2011/11/02 15:17:41
CAUTION
1. Certain metal edges and the condenser fins are sharp and may cause
injury if handled improperly; special care should be taken when you
clean these parts.
2. Periodically check the outdoor unit to see if the air outlet or air intake is
clogged with dirt or soot.
3. The internal coil and other components of the outdoor unit must also be
cleaned periodically. Consult your dealer or service center.
Care: After a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a
blockage, remove it.
Care: Before a prolonged idle period
• Operate the fan for half a day to dry out the inside.
• Disconnect the power supply and also turn off the circuit breaker.
• Clean the air filter and replace it in its original position.
• Outdoor unit internal components must be checked and cleaned periodically.
Contact your local dealer for this service.
62
Panasonic_PAC-i_IndoorUnit_US-le62 62
2011/11/02 15:17:41
■ Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work
properly, contact your dealer or a service center.
Trouble
Air conditioner does not run at all.
Compressor runs but soon stops.
Poor cooling (or heating)
performance.
Possible Cause
1. Power failure.
2. Leakage circuit breaker has
tripped.
3. Line voltage is too low.
4. Operation button is turned off.
5. The wireless remote controller or
heat pump is malfunctioning.
6. Batteries in wireless remote
controller have run down.
1. Obstruction in front of condenser
coil.
1. Dirty or clogged air filter.
2. Heat source or many people in
room.
3. Doors and/or windows are open.
4. Obstacle near air intake or air
discharge port.
5. Thermostat is set too high for
cooling (or too low for heating).
6. (Outdoor temperature is too low).
7. (Defrosting system does not
work.)
1. Trouble in wiring system
Lamps on the indoor
Remedy
1. Restore power.
2. Contact service center.
3. Consult your electrician or dealer.
4. Press the button again.
5. Consult your dealer.
6. Replace batteries.
1. Remove obstruction.
1. Clean air filter to improve the
airflow.
2. Eliminate heat source if possible.
3. Shut them to keep the heat (or
cold) out.
4. Remove it to ensure good airflow.
5. Set the temperature lower (or
higher).
6. (Consult your dealer.)
7. (Consult your dealer.)
1. Contact service center.
unit are flashing.
■ Tips for Energy Saving
Avoid
• Do not block the air intake and outlet of the unit. If either is obstructed, the
unit will not work well, and may be damaged.
• Do not let direct sunlight into the room. Use sunshades, blinds or curtains.
If the walls and ceiling of the room are warmed by the sun, it will take longer to
cool the room.
Do
• Always try to keep the air filter clean. (Refer to “Care and Cleaning”.) A clogged
filter will impair the performance of the unit.
• To prevent conditioned air from escaping, keep windows, doors and any other
openings closed.
NOTE
Should the power fail while the unit is running
If the power supply for this unit is temporarily cut off, the unit will automatically
resume operation once power is restored using the same settings before the
power was cut off.
63
Panasonic_PAC-i_IndoorUnit_US-le63 63
2011/11/02 15:17:41
DC0811-21111
Printed in Japan