Panasonic 26PET1U6 Data Sheet
Add to my manuals3 Pages
Panasonic 26PET1U6 is a single split system ceiling-suspended heat pump designed for efficient cooling and heating in residential and commercial spaces. With a 230/208V power supply, it delivers up to 24,400 BTU/H cooling capacity and 30,800 BTU/H heating capacity. Featuring an inverter compressor, it offers precise temperature control and energy savings. The unit's compact design and low noise operation make it suitable for various indoor environments.
advertisement
Split System Submittal Data
System:
26PET1U6 Indoor: S-26PT1U6 Outdoor: U-26PE1U6
Single Split System - Ceiling-Suspended Heat Pumps
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit#:
Drawing#:
General Data
Power (V/P/Hz)
Circuit Ampacity (A)
Fuse Size, Max.(A)
Compressor
No. Used
R.L. Amps - L.R. (A)
Outdoor Unit
Fan type
Dia & Length (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles (RPM)
No. Motors (W)
CFM (High)
F.L. Amps (A)
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in)
230/208/1/60
15-30 Indoor-Outdoor
15-30 Indoor-Outdoor
DC Rotary Inverter
1
12.9 - 17.5
Propeller
18-7/64-1
DC Motor
8 - 800
1 - 90
1765
13.8
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifled
1 - 15.9
7.26
3/8"
Indoor Unit
Fan type
Dia & Length (in.) - No. Speeds
No. Speeds
No. Poles (RPM, High)
Centrifugal
5-1/8-4
3 & Auto
4 - 1179
No. Motors (W)
CFM (HI/Med/Lo)
1 - 31
550/490/460
Indoor Sound Rating (Hi) (dB-A) 39
F.L. Amps (A) 0.5
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in)
Drain Connection Size (in.)
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifled
3 - 14.9
1.81
9/32"
1-1/4"
Refrigerant
Lbs. - R410a
Control
Connection
Line Length, Max (ft.)
Line Difference, Max (ft.)
Line Size (in. O.D. Discharge)
Line Size (in. O.D. Suction)
R410A
4.19
Electric Expansion Valve
Flare
165
50 (outdoor lower),
100 (outdoor higher)
3/8"
5/8"
Dimensions (HxWxD)
Indoor Unit (Crated) (in.)
Indoor Unit (Uncrated) (in.)
Outdoor Unit (Crated) (in.)
Outdoor Unit (Uncrated) (in.)
Weight (lbs.)
(Indoor) Net
(Indoor) Shipping
(Outdoor) Net
(Outdoor) Shipping
(Indoor) Shipping Volume (cu.ft.) 8.9
(Outdoor) Shipping Volume (cu.ft.) 13
64
75
128
148
9-7/16 x 54-19/32 x 31-1/16
7-17/16 x 51-3/16 x 26-3/8
34-31/32 x 39-31/32 x 16-3/32
30-23/32 x 37 x 13 3/8
Performance Data @ ARI Standard Conditions (230V)
Cooling
Total Capacity (BTU/H)
Sensible Capacity (BTU/H)
Latent Capacity (BTU/H)
SEER
Dehumidification (Pints/H)
Amps (A)
Power Inputs (W)
Outdoor Sound Rating (dB-A)
24,400 (9,500 - 24,400)
14,330
10,070
14.5
7.7
15.6/17.3
2,880/2,880
49
Heating
Total Capacity (BTU/H)
HSPF
Amps (A)
Max Amps (A)
Power Inputs (W)
30,800 (8,000 - 30,800)
10.3
16.4/18.1
16.4/18.1
3,000/3,000
Back-up Strip Heather (KW) 0.00/0.00
Outdoor Sound Rating (dB-A) High 49
Features
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver, Horizontal
Air Louver, Vertical
Power Failure Automatic
Changeover
Heating/Cooling Automatic
Changeover
Self-Diagnosis
Air Filter
Microprocessor
LCD Wired Type, Temp. Sensor
Built in
IC Thermostat
72 Hr. On/Off
Built-In
Manual
Automatic
Built-In
Built-In
Built-In
Washable, Anti-Mold
Option
Refrigerant Line Set
Fresh Air Intake
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removeable Remo-con
Bracket
Available
Knock-out
N/A
N/A
Available
Available
Operating Range Indoor Air Intake Temp Outdoor Air Intake Temp
Cooling (Max)
Cooling (Min)
Heating (Max)
Heating (Min)
95F DB/71F WB
67 DB/57F WB
80F DB/67F WB
-DB/-WB
115F DB
0F DB
75F DB/65F WB
5F DB
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144 us.panasonic.com/aircon
1. Specifications
1-4 Dimensional data
Indoor unit : Ceiling Type
26 Type
6-3/32 3-15/16
12-7/32
11-1/32
2-17/32 5-9/32
3-3/8
11-1/32 4-9/16
Holes in the rear side (View from front)
5-3/4
3-9/32
5-9/16
Hole for wall-through piping (View from front)
5-3/16 2-25/32
1
48-7/16 (Suspension bolt hole pitch)
50-13/32
1-3/8
26-3/8
9-7/8 Air outlet
10 or more
(Service space)
Air intake
1-4 Dimensional data
Indoor unit : Ceiling Type
51-3/16
Front
10 or more
(Service space)
8-7/16
9-7/8
1. Specifications
Indoor unit : Ceiling Type
26 Type
6-3/32 3-15/16
12-7/32
11-1/32
3-3/8
11-1/32 4-9/16
Holes in the rear side (View from front)
5-3/16
3-1/2
6-3/32 3-15/16
12-7/32
11-1/32
5-25/32 2-17/32 5-9/32
7-7/32
3-3/8
11-1/32
5-3/4
3-9/32
5-9/16
2-17/32 5-9/32
5-3/4
3-9/32
2-25/32
5-9/16
Hole for wall-through piping (View from front)
Drain connection
Drain connection for left side
Hole for wall-through piping (View from front)
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
1-4 Dimensional Data
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
(B) Outdoor Unit: U-26PE1U6, U-26PS1U6
U-36PE1U6, U-36PS1U6
1-3/8
1919_THS_I
1
26-3/8
48-7/16 (Suspension bolt hole pitch)
50-13/32
1-3/8
SM830203-01_PAC-i_US-letter.indb41 41
9-7/8
26-3/8
Air intake
Air outlet
10 or more
(Service space)
51-3/16
Front
10 or more
(Service space)
8-7/16
9-7/8
2012/01/19 22:39:24
1
9-7/8
Air intake
Air outlet
10 or more
(Service space)
51-3/16
Front
10 or more
(Service space)
8-7/16
9-7/8
1-4 Dimensional Data
(B) Outdoor Unit: U-26PE1U6, U-26PS1U6
Outdoor Dimensions
3-1/2 4-1/16
5-25/32
7-7/32
Dimension : inch
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1919_THS_I
3-1/2
7-7/32
4-1/16
5-25/32
Dimension : inch
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1919_THS_I
1-41
SM830203-01_PAC-i_US-letter.indb41 41 2012/01/19 22:39:24
1-41
SM830203-01_PAC-i_US-letter.indb41 41 2012/01/19 22:39:24
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144 us.panasonic.com/aircon