Panasonic 42PET1U6 Datasheet

Panasonic 42PET1U6 Datasheet
Split System Submittal Data
System: 42PET1U6 Indoor: S-42PT1U6 Outdoor: U-42PE1U6
Single Split System - Ceiling-Suspended Heat Pumps
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit#:
Drawing#:
General Data
Power (V/P/Hz)
Circuit Ampacity (A)
Fuse Size, Max.(A)
230/208/1/60
15-40 Indoor-Outdoor
15-40 Indoor-Outdoor
Compressor
No. Used
R.L. Amps - L.R. (A)
DC Rotary Inverter
1
18.1 - 31.0
Outdoor Unit
Fan type
Dia & Length (in.) - No. used
Type Drive - No. Speeds
No. Poles (RPM)
No. Motors (W)
CFM (High)
F.L. Amps (A)
Propeller
18-7/64-2
DC Motor
8 - 830
2 - 90
3531
19.7
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in)
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifled
2 - 12.7
11.62
3/8"
Indoor Unit
Fan type
Dia & Length (in.) - No. used
No. Speeds
No. Poles (RPM, High)
No. Motors (W)
CFM (HI/Med/Lo)
Indoor Sound Rating (Hi) (dB-A)
F.L. Amps (A)
Centrifugal
5-29/32-4
3 & Auto
4 - 1099
1 - 100
1130/950/775
44
0.8
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in)
Drain Connection Size (in.)
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifled
3 - 14.9
3.51
9/32"
1-1/4"
Refrigerant
Lbs. - R410a
Control
Connection
Line Length, Max (ft.)
Line Difference, Max (ft.)
Line Size (in. O.D. Discharge)
Line Size (in. O.D. Suction)
R410A
7.94
Electric Expansion Valve
Flare
165
50 (outdoor lower),
100 (outdoor higher)
3/8"
5/8"
Dimensions (HxWxD)
Indoor Unit (Crated) (in.)
Indoor Unit (Uncrated) (in.)
Outdoor Unit (Crated) (in.)
Outdoor Unit (Uncrated) (in.)
12-15/32 x 66-1/16 x 31-1/16
9-7/16 x 62-1/32 x 26-3/8
52-3/8 x 39-31/32 x 6-3/32
48-7/16 x 37 x 13-3/8
Weight (lbs.)
(Indoor) Net
(Indoor) Shipping
(Outdoor) Net
(Outdoor) Shipping
84
97
220
240
(Indoor) Shipping Volume (cu.ft.)
(Outdoor) Shipping Volume (cu.ft.)
14.8
19.5
Performance Data @ ARI Standard Conditions (230/208V)
Option
Cooling
Total Capacity (BTU/H)
Sensible Capacity (BTU/H)
Latent Capacity (BTU/H)
SEER
Dehumidification (Pints/H)
Amps (A)
Power Inputs (W)
Outdoor Sound Rating (dB-A) High
Refrigerant Line Set
Fresh Air Intake
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removeable Locking
Remo-con Bracket
Heating
Total Capacity (BTU/H)
HSPF
Amps (A)
Max Amps (A)
Power Inputs (W)
Back-up Strip Heather (KW)
Outdoor Sound Rating (dB-A) High
39,000 (9,500 - 39,000)
23,560
15,440
15.6
12.6
21.1/23.3
4,140/4,140
53
44,500 (8,000 - 44,500)
10.2
18.6/20.6
18.6/20.6
3,630/3,630
N/A
53
Features
Controls
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver, Horizontal
Air Louver, Vertical
Power Failure Automatic
Changeover
Heating/Cooling Automatic
Changeover
Self-Diagnosis
Air Filter
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144
us.panasonic.com/aircon
Microprocessor
(Wired Remote Included)
(Wireless Remote Optional)
IC Thermostat
72 Hr. On/Off
N/A
Manual
Automatic
Built-In
Built-In
Built-In
Washable, Anti-Mold
Available
Knock-out
N/A
N/A
Optional Accessory
Available
Operating Range
Indoor Air Intake Temp
Outdoor Air Intake Temp
Cooling (Max)
Cooling (Min)
Heating (Max)
Heating (Min)
95F DB/71F WB
67 DB/57F WB
80F DB/67F WB
-DB/-WB
115F DB
0F DB
75F DB/65F WB
5F DB
2f
1-4 Dimensional data
Indoor unit : Ceiling Type
36, 42 Type
5-9/16
3-5/32
Hole for wall-through piping (View from front)
1-31/32
6-5/16
1-3/32
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain
(Knockout hole)
5-3/16connection2-25/32
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1920_TS_I
1-3/8
12-19/32
61-7/32
26-3/8
10
or more
8-7/16
(Service space)
9-7/8
(Service space)
(Service space)
9-7/8
3-1/2
(B) Outdoor
Unit: U-42PE1U6, U-42PS1U6
Outdoor
(B) OutdoorDimensions
Unit: U-42PE1U6,
U-42PS1U6
4-1/16
5-25/32
7-7/32
Dimension : inch
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1920_TS_I
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144
us.panasonic.com/aircon
4-1/16
5-25/32
1-4 Dimensional Data 1-4 Dimensional Data
3-1/2
9-7/16
8-7/16
Front
7-3/4
10
or more
5-1/2
62
9-7/16
62
Front
10
Air outlet or more
7-3/4
9-7/8
26-3/8
2 ft. or more
1-3/8
5-1/2
2 ft. or more
5-3/4
4-3/4
59-1/4 (Suspension bolt hole pitch)
Air intake
Air intake
(Suspension bolt hole pitch)
1-3/32
2-25/32
61-7/32
(Service space)
Dimension : inch
(B) Outdoor Unit: U-42PE1U6, U-42PS1U6
6-5/16
6-5/16
12-19/32
(Suspension bolt hole pitch)
1-4 Dimensional Data
Hole for wall-through piping (View from front)
5-3/16
6-5/16
5-9/16
3-5/32
6-11/16
5-3/4
4-3/4
59-1/4 (Suspension bolt hole pitch)
10
Air outlet or more
11-1/32
Holes in the rear side (View from front)
Holes in the rear side (View from front)
9-7/8
11-1/32
5-25/32
6-11/16
7-3/4
11-1/32
3-3/8
4-1/2
7-1/4
1-31/32
11-1/32
12-7/32
4-1/16
7-7/32
12-7/32
3-15/16
3-3/8
3-1/2
3-15/16
7-31/32
7-3/4
5-15/16
6-3/32
7-31/32
7-3/4
5-15/16
6-3/32
7-3/4
Indoor Dimensions
Indoor unit : Ceiling Type
36, 42 Type
4-1/2
7-1/4
Dimensional data
7-7/32
Dimension : inch
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (5/8") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake