F616499

Wired Remote Controller Installation Manual

SAFETY PRECAUTIONS

• Read the following “SAFETY PRECAUTIONS” carefully before installation.

Electrical work must be installed by a licensed electrician.

• The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.

Incorrect installation due to the non-observance of the instructions will cause harm or damage, and the seriousness is classified by the following indications.

WARNING

This indication shows the possibility of causing death or serious injury.

CAUTION

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:

Symbol with white background denotes item that is PROHIBITED from doing.

Symbol with dark background denotes item that must be carried out.

• Perform a functional test to confi rm that no abnormality occurs after the installation. Then, explain the operation, care and maintenance to user as stated in instructions. Please remind the customer to keep the operating instructions and installation instruction for future reference.

WARNING

Do not modify the length of the remote controller cable. Otherwise, it will cause fire or electrical shock.

Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause electrical shock.

Engage an authorized dealer or specialist for installation. If installation done by the user is defective, it will cause electrical shock or fire.

Install strictly according to these installation instructions. If installation is defective, it will cause electrical shock or fire.

Use specified accessories and parts for installation. Otherwise, it will cause the set to fall, fire or electrical shock.

For electrical work, follow the local national wiring standards and regulations, and these installation instructions. Otherwise, it will cause electrical shock or fire.

Wire routing must be properly arranged so that control board cover is affixed properly. If control board cover is not affixed perfectly, it will cause fire or electrical shock.

If passing the remote controller cable through a wall, be sure to install a water trap above the cable.

Otherwise, it will cause electrical shock.

CAUTION

Do not touch the sharp aluminium fin of air conditioner unit during wired remote controller installation, sharp parts may cause injury.

Install on a flat surface to avoid warping of remote controller, or else damage to the LCD case or operation problems may result.

Avoid installing the remote controller cable near refrigerant pipes or drain pipes, otherwise it will cause electrical shock or fire.

Install the remote controller cable at least 1 31/32"(5cm) away from electric wires of other appliances to avoid misoperation (electromagnetic noise).

Be sure to use only the accessory screws to avoid damage of remote controller PCB.

ATTACHED ACCESSORIES

No.

Name Qty Diagram Remark

1 Remote controller 1

2 Remote controller cable

3

4

Screw

(M4 machine pitched - 1 3/16"

(30mm))

Screw

(M4 self tapping - 9/16"(14mm)

1

3

3

5 Remote controller cable holder 1

6

7

8

Screw

(M4 machine screw & washer -

13/32"(10mm))

Screw

(M3 self tapping - 5/16"(8mm))

Screw

(M4 self tapping - 5/16"(8mm))

1

1

1

Length 32.5ft (9.9m)

Installing the remote controller to an outlet box

(embedded cable)

Installing the remote controller to the wall

(exposed cable)

Holder for remote controller cable at control board

Tighten remote controller cable with holder

Installing the remote controller cable to control board

Installing the green wire to terminal board

1. SELECTING THE INSTALLATION LOCATION

Remote controller 1

Upper case

Mounting plate

1 3/16"

( 30mm) or more

1 3/16"

( 30mm) or more

Remote controller mounting plate

4 23/32"

( 120mm) or more

1 3/16"

( 30mm) or more

Allow suffi cient space around the remote controller 1 as shown in the illustration above.

• Install in a place which is away from direct sunlight and high humidity.

• Install on a fl at surface to avoid warping of the remote controller. If installed to a wall with an uneven surface, damage to the LCD case or operation problems may result.

• Install in a place where the LCD can be easily seen for operation. (Standard height from the fl oor is 3.9ft to 4.9ft

(1.2 to 1.5 meters.))

• Avoid installing the remote controller cable near refrigerant pipes or drain pipes, otherwise it will cause electrical shock or fi re.

2. INSTALLING THE REMOTE CONTROLLER UNIT TO THE WALL

1.

3.

R e m o v e t h e r e m o t e c o n t r o l l e r 1 m o u n t i n g p l a t e .

(Insert a fl at-tipped screw driver or similar tool 3/32" to 1/8" (2 to

3 mm) into one of the gaps at the bottom of the case, and twist to open. Refer to the illustration at right.)

Be careful not to damage the mounting plate.

2. Do not remove the protective tape which is affi xed to the upper case circuit board when removing the remote controller mounting plate.

Secure the mounting plate to an outlet box or wall. Refer to (A) or (B) instructions below depending on your choice of cable installation.

4.

5.

Be sure to use only the screws provided.

Do not over tighten the screws, as it may result in damage to the mounting plate.

Screw driver

Gaps

Upper case

Mounting plate

Screw 3 or

Screw 4

A. IF REMOTE CONTROLLER CABLE IS EMBEDDED

3.

4.

5.

1.

2.

6.

Embed an outlet box into the wall. Outlet box may be purchased separately. Medium-sized square outlet box

(obtain locally) Part No. DS3744 (Panasonic Corporation) or equivalent.

Secure the remote controller mounting plate to the outlet box with the two accessory screws 3 .

Make sure that the mounting plate is fl at against the wall at this time, with no bending.

Pass the remote controller cable 2 into the box.

Route the remote controller cable 2 inside the mounting plate through rear feeding-out direction.

Insert fi rmly the connector of remote controller cable 2 to connector (CON1) in the upper case circuit board.

[Refer to the illustration at below.]

Secure the remote controller upper case to the mounting plate with the tabs provided.

Wall

Upper case

Upper tab CAUTION

When the wall is hollow, please be sure to use the sleeve for remote controller cable to prevent dangers caused by mice biting the cable.

Connector (CON1)

Mounting plate

Screw 3

Lower tab

Remote controller cable 2

Outlet box

Remote controller cable 2

Rear feeding-out position

Mounting plate

Tabs

Connector

(CON1)

Upper case

Upper case

Mounting plate

B. IF REMOTE CONTROLLER CABLE IS EXPOSED

1.

2.

Install the remote controller mounting plate to the wall with the two accessory screws 4.

Fasten the screws properly until screw head is lower than the rib and reach the base of remote controller mounting plate to ensure they do not damage the PCB inside the remote controller 1.

Rib

Wall

Remote controller cable 2

Wall

Upper case

Upper tab

Screws 4

Remote controller mounting plate

Connector (CON1)

Mounting plate

Screws 4

Lower tab

3.

4.

5.

6.

7.

The feeding-out direction for the remote controller cable can be either via top, left or right side.

Use nipper to cut a notch at the upper case. (Select the intended feeding-out position)

Route the remote controller cable 2 inside the mounting plate in accordance with the intended feeding-out direction. (Refer to the illustration at below)

Insert fi rmly the connector of remote controller cable 2 to connector (CON1) in the upper case circuit board.

(Refer to the illustration at below)

Secure the remote controller upper case to the mounting plate with the tabs provided.

Top feeding-out position

Remote controller cable 2

Notches

Remote controller 1

Connector

(CON1)

Left feeding-out position Upper case

Upper case

Right feeding-out

Mounting plate

Tabs

Mounting plate

3. CONNECTING THE REMOTE CONTROLLER CABLE TO INDOOR UNIT

CAUTION

Be sure to turn off the main power before installing and connecting the remote controller.

Otherwise, it will cause electrical shock.

1.

2.

3.

Open front grille.

(Please refer to HOW TO TAKE OUT FRONT GRILLE in the

Service manual.)

Open the control board cover and terminal board cover.

Connect remote controller cable 2 to remote controller 1 and guide the remote controller cable 2 into the unit through the wire insertion hole.

Front grille

4.

5.

6.

Guide the remote controller cable 2 into the remote controller cable holder 5 and tighten with screws 6. Fasten the remote controller cable holder with screw 7.

Firmly insert the connector of remote controller cable 2 into indoor PCB connector (CN-RMT) and tighten green wire from remote controller cable 2 with screw 8 to the grounding location provided.

Reinstall the terminal board cover. Be careful not to clamp the cable between terminal board cover and control board.

7. After completion, reinstall the removed parts by following the reverse procedure.

* Make sure the remote control cable wire is not touching the wire connected to terminal board, as shown

Control board cover

Green wire

(Remote controller)

Connector

(CN-RMT)

Terminal board cover

Terminal board cover

Screw 6

Remote controller cable holder 5

Remote controller cable 2

Screw 7

Note: Remote controller cable cannot be extended.

Screw 8

Remote controller cable 2

Remote controller 1

ENGLISH

F616499

1