PW-Series Modular Access Control System

Add to my manuals
4 Pages

advertisement

PW-Series Modular Access Control System | Manualzz

PW-Series

Modular Access

Control System

Intelligent Controllers

The PW-Series Modular Control System is an advanced access control hardware architecture capable of providing solutions for large enterprise applications. The Intelligent Controller (PW6K1IC,

PW3K1IC or PW6K1ICE) provides power and flexibility with its

32-bit architecture, TCP/IP support, flash memory, large local cardholder database, and large reader and I/O module support.

The Intelligent Controller is designed to operate off-line, making access control decisions independently from a PC or other controlling device. It can also be connected to a host computer for system configuration, alarm monitoring and direct control.

Connectivity to the host computer is accomplished via direct serial communication (RS232 or RS485), dial-up modem, or

TCP/IP network connection. The PW-6000 has Ethernet directly embedded and will support a second Ethernet connection.

The PW6K1IC Intelligent Controllers support any combination of up to 32 I/O or reader boards (16 for the PW3K1IC) to monitor alarm input points, relay output points and access control reader interfaces. By offering a modular design, the system can be tailored to meet a wide range of applications, while optimizing cost and mounting space.

The PW-6000 will support up to 300,000 cards and 50,000 transactions. The PW-6101 will support up to 240,000 cards and 50,000 transactions. The PW-3000 Intelligent Controller accommodates a card database of 7,800 cards and a standard transaction buffer of 5,000 transactions.

The PW-Series access modules have been designed to accommodate various mounting options. Units can be wall mounted in a high density configuration (PW5K2ENC1) when space is limited, a 19" rack configuration (PW5K2ENC2), or in a tile mount configuration (PW5K1ENC3). The PW-6000 controller utilizes a built-in Web server to configure the hardware attributes of the controller.

K E Y F E AT U R E S

• Up to 12 intervals per time zone where each interval is a start time, stop time and day map. The day map indicates the day of the week or holiday

• 255 possible holidays are defined by a starting date and duration

• Automatic calculation of leap year and

Daylight Saving Time

• 9-digit (32-bit) user ID standard /

15-digit maximum - PW-3000, 19-digit

(64-bit) user ID - PW-6000/PW-6101

• Support for FIPS long card numbers

• Activation and deactivation dates by card

• Up to 12 access levels per card or individual time zones per readers

• Up to 8-digit Personal Identification

Numbers (PIN) - PW-3000,

8-digit - PW6000/PW-6101

• Operating modes include locked, unlocked, facility code, card only, card and PIN, card or PIN, and PIN only

• Strike modes include fail-safe and fail-secure

• Up to eight card formats per reader

• Entire card bit-stream reported with invalid facility code or invalid card format

• Anti-passback support – free pass and exempt flags, last area accessed, last reader accessed and time/date of last access

• Configurable as standard, entry delay latching, entry delay non-latching and exit delay

• Configurable as standard (energize to activate) or fail-safe (de-energize to activate)

• Pulse control: single pulse (up to 24 hours) or repeating pulses (on/off in 0.1

second increments, up to 255 times)

• Any combination of 32 I/O or reader modules may be connected to the

PW6K1IC RS485 ports. 4,000 feet /

1,250 meters total bus length per port

(a max 16 I/O or reader board may connect to the PW3K1IC)

• UL294, UL1076 Listed

• AES FIPS 197 Encryption

• PW-6000 Web server for hardware configuration

PW-Series Modular Access Control System

Intelligent Controllers

S P E C I F I C AT I O N S

Database:

• Cardholders:

- 7,800 on PW-3000

- 300,000 on PW-6000

- 240,000 on PW-6101

• Transaction storage:

- 5,000 standard, 35,000 with memory expansion on PW-3000

- 50,000 on PW-6000/PW-6101

• Flash programming for firmware revision updates

• Access codes: virtually unlimited

• Holidays: virtually unlimited

• Time codes: 255

• Card reader formats: 8 per reader

• Credential facility codes: 8

• Elevator support: 128 floors

• Dedicated tamper alarm

• Dedicated power fail alarm

• Real time clock:

- Geographic time zone support

- Daylight Saving Time

- Leap year support

- 4 bit parallel accurate to 50 ppm

Database values may exceed current limitations of some security management systems.

Communication Modules:

• Primary communication support:

- RS232

- RS485

- Dial up modem

- Ethernet (TCP/IP)

• Communication speed: 38.4 KBps

• Redundant communication support, automatic dial back: (PW6K1IC)

- Dial back on alarm condition

- Dial back on transaction buffer capacity reached

- Dial back on primary power loss

• Download functionality:

- System functional during system download: Yes

- System functional during credential download: Yes

Access Modules:

PW-6000

• 2 RS485 ports supporting

32 total devices

PW-6101

• POE - Supporting 16 Single Reader

Modules via ethernet (PW6K1ICE or

PW6K1R1E)

PW-3000

• 2 RS485 ports supporting

16 total devices

• Access modules available:

- Single reader module (PW5K1R1)

- Dual reader module (PW6K1R2)

- 16 relay output module

(PW6K1OUT) (12 from the front edge)

- 16 alarm input module (PW6K1IN)

• Module connectivity via RS485 protocol (4000')

Operational Functionality:

• Duress detection

• Operational modes:

- Credential only

- PIN only

- Credential or PIN

- Credential and PIN

- Facility code only

• Maximum PIN size: 8 digit

• Door object support

• Threat level support: 100 levels

• Two person access rule

• Offline modes (selectable per reader):

- Facility code access

- Locked (no access)

- Unlocked (free access)

• Anti-passback support:

- While preventing access (hard)

- While allowing access (soft)

• Transaction prioritization: 999 levels

Reader Support:

• HID • Indala

• OmniProx • OmniClass

• DigiReaders • Wiegand

• Keypads

• Ingersoll Rand AD-400 Wireless

Lock Sets (PW-6000 panels only)

• Salto Sallis Wireless Readers

(PW-6000 panels only)

• Assa Abloy Wireless Readers

(PW-6000 Readers only)

Readers and Credentials:

• Prox:

- OmniProx

- HID Prox

- DigiReaders

- Indala Readers

• Smart:

- OmniClass

- iClass

- Mifare

- DESFire

• Keypad

• Magstripe

• Wiegand

C O M M O N S P E C I F I C AT I O N S

Enclosure Dimensions:

• Board: PW-3000/PW-6000

9.0" H x 5.5" W x 1.0" D

(228.6 mm H x 139.7 mm W x 25.4 mm D)

• PW-6101 IC and 0.96" H x 5.5" W x 2.75" D

Reader Module: (24mm H x 140mm W x 92mm D)

• PW5K2ENC1: 13.9" H x 17" W x 9" D

(353.0 mm H x 431.8 mm W x 228.6 mm D)

• PW5K2ENC2: 13.9" H x 18.9" W x 9" D

(353.0 mm H x 480.0 mm W x 228.6 mm D)

• PW5K1ENC3: 14" H x 16" W x 4.5" D

(355.6 mm H x 406.4 mm W x 114.3 mm D)

Environment:

• Temperature: 32 to 158° F (0 to 70° C) operational;

-67 to 185° F (-55 to 85° C) storage

• Humidity: 0 to 95% RHNC

Wire requirements:

• Power - twisted pair, 18 AWG

• RS485 - 24 AWG, 4,000' (1,200m) max, 2 twisted pairs with shield (120W, 23 pF, Belden 9842 or equiv.)

• RS232 - 24 AWG, 25' (7.6m) max

• Alarm input - twisted pair, 30 ohms max

Communication Features:

• RS485 port, 4000’ (1,250m) total bus length

• Standard speed is 38,400 bps

B E N E F I T S

• True 32-bit microprocessor provides fast transaction processing for the most demanding network applications

• Modular hardware architecture provides flexibility and expansion capabilities

• Flash memory allows new versions of firmware to be downloaded from the host computer to the controller(s) through the central network

• Large, local controller database allows access control decisions to be made by controller in real time without the need to communicate to the server

• Scalable architecture ensures optimal performance with a seamless upgrade path to accommodate future growth beyond its initial installation

• Seamless support for TCP/IP protocols to allow intelligent controllers to tap into a LAN or WAN connectivity

• Supports multiple reader and card formats for maximum flexibility and security options

• Multiple communication methods provide redundant paths for more robust system connectivity

• Supervised communication and

Lithium battery backup ensures system reliability

• System offline modes customizable per reader include facility code access, locked (no access), and unlocked (full access)

• Redundant communication port feature allowing secondary port communication if primary fails

P W - S E R I E S C O N F I G U R AT I O N

PW-Series Modular Access Control System

Intelligent Controllers

O R D E R I N G

Order # Description

PW-3000 and PW-6000 Intelligent Control System

PW6K1IC

PW3K1IC

PW6K1IN

PW6K1OUT

PW5K1R1

PW6K1R2

PW-6000 Intelligent Controller –

Capacity for 32 I/O or reader boards

PW-3000 Intelligent Controller –

Capacity for 16 I/O or reader boards

PW-Series 16 input module

PW-Series 16 relay output module

PW-Series single reader module

(only for use in PW5K1ENC4)

PW-Series dual reader module

PW5K1MX8 8-Port multiplexer

PW-6101 Intelligent Control System

PW6K1ICE

PW6K1R1E

Intelligent Controller

One door reader module

Pro-Watch ® is a registered trademark of Honeywell International Inc.

Microsoft ® , Microsoft ® BackOffice ® and Windows ® 2000 are registered trademarks of Microsoft Corporation

Order # Description

Enclosures and Accessories

PW5K2ENC1 PW-Series high density enclosure

(power supply and battery not included)

PW5K2ENC2

PW6K2E2PS

PW-Series high density enclosure for

19" rack installations (power supply and battery not included)

PW-Series 110/220 VAC, 4 amp power supply for PW5K2ENC1 and PW5K2ENC2 enclosures

PW5K1ENC3

PW5K1ENC4

PW5K1DCC

PW-Series remote enclosure with plug-in with

110V transformer/power supply

Single reader enclosure

(for use with PW5K1R1)

PW-Series daisy chain cable

For more information: www.honeywellintegrated.com

Automation and Control Solutions

Honeywell Security Products Americas

2700 Blankenbaker Pkwy, Suite 150

Louisville, KY 40299

1.800.323.4576 www.honeywell.com

L/PWSMACSD/D

September 2014

© 2014 Honeywell International Inc.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement