Features
•Capable of switching 16 A of high in-rush lighting
load (LED, magnetic fluorescent ballast, electronic
fluorescent ballast, incandescent, magnetic lowvoltage, electronic low-voltage, neon / cold cathode
and motor loads)
•Provides 20 V- power for and responds to one
occupant sensor, one EcoSystem daylight sensor,
and one EcoSystem personal control input (infrared
receiver or wallstation)
•Communicates status and sensor levels over the
EcoSystem Bus
•Universal voltage input: 100 to 277 V~ 50/60 Hz
•Non-volatile (EEPROM) memory stores specific
system information for 10 years from power down to
power restored
•100% performance tested at factory
Note: Frequent switching of HID loads may affect the
lifetime of the lamps or ballasts. Please contact the
lamp or ballast manufacturers for more information
about compatibility with HID loads, especially when
used with occupancy sensors.
EcoSystem One-Line
EcoSystem Bus
EcoSystem
Ballast
To additional ballasts
and modules (up to
64 total)
1 2 3 4 5 6 7 8
Non-Dim Load
IR Receiver
EcoSystem
Switching
Power Module
EcoSystem
Bus Supply*
Lighting
Remote
EcoSystem
Ballast
EcoSystem
Ballast
Daylight
Sensor
Occupancy
Sensor
Wallstation
* Does not count as one of the ballasts or modules on the EcoSystem Bus. The bus supply can be an Energi Savr Node unit or can be
located in a Quantum hub.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
1
EcoSystem
C5-XPJ-16A
Switching Power Module
369409d 2 04.07.17
Specifications
Regulatory Approvals
•UL® 916 Listed and CSA 184 Certified
•Meets ANSI C62.41 Category A surge protection
standards up to and including 6000 V~
•Manufacturing facilities employ ESD reduction
practices that comply with the requirements of
ANSI/ESD S20.20
•Lutron Quality Systems registered to
ISO 9001.2000
•NOM
•Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC® 2014 300.22(C)(3)
•Meets the Canadian National Building Code plenum
requirements for a concealed space used as a
plenum within a floor or roof assembly
•For commercial use, Class A only
Power
Environment
•Ambient Temperature Operating Range: 32 ºF to
104 ºF (0 ºC to 40 ºC)
•Relative humidity: less than 90% non-condensing
•For indoor use only
Module Wiring (see Wiring pages for wiring diagrams)
•Terminal blocks accept wires of the following size:
EcoSystem Bus (E1, E2):
- 22 AWG to 12 AWG (0.5 mm2 to 2.5 mm2) solid wire
IEC PELV / NEC® Class 2 Sensors:
- 22 AWG to 12 AWG (0.5 mm2 to 2.5 mm2)
solid wire
•Wiring between module and load is 3 conductors:
Switched Hot
Neutral
Ground
•Wiring between module and sensors shall not
exceed manufacturer’s specifications.
•Operating Voltage: 100 to 277 V~ 50 / 60 Hz
•Output Rating: 16 A Softswitch maximum non-dim
load
•IEC PELV / NEC® Class 2 Sensor Power: 20 V50 mA maximum
Switchable Load Types
•LED
•Magnetic fluorescent ballast
•Electronic fluorescent ballast
•Incandescent and Halogen
•Magnetic low-voltage transformer
•Electronic low-voltage transformer
•Neon or Cold Cathode
•Motor Loads
-1/4 HP at 100 to 120 V~
-1/2 HP at 200 to 277 V~
Note: Do not use to switch receptacles.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
2
EcoSystem
C5-XPJ-16A
Switching Power Module
369409d 3 04.07.17
Dimensions
All dimensions shown as in (mm)
5.0
B
(130)
2.5
(64)
7.8
A
(200)
Electrical Contractors and Engineers
Mounting
•Mount the EcoSystem Switching Module onto a
4 in x 4 in (102 mm x 102 mm) standard (1900)
junction box (not included, but available;
Lutron P/N 241496)
•Mount on a vertical or horizontal surface; all power
wire connections will be made in the junction box; all
EcoSystem bus wiring (NEC® Class 1 or
IEC PELV / NEC® Class 2) and sensor wiring
(IEC PELV / NEC® Class 2 only) connections will be
made within the front cover of the unit
•Mount in a location where the PWR and STAT
indicators are visible
• All field-installed IEC PELV / NEC® Class 2 wiring
must be separated from line voltage wiring by at
least 0.25 in (6.4 mm)
• Some local electrical codes require
IEC PELV / NEC® Class 2 wiring to be separately
routed in a metal conduit
CEILING
WALL
C5-XPJ-16A
C5-XPJ-16A
Junction box
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
3
EcoSystem
C5-XPJ-16A
Switching Power Module
369409d 4 04.07.17
Wiring
EcoSystem Power Module Line Voltage Wiring
•Connect the input feed wires and the output load
wires to the module as indicated in the wiring
diagrams below
White
Black
Red
Green
EcoSystem Power Module
Green*
Green (ground)*
White*
White (neutral)*
Black*
Red (switched hot)*
Green*
Fixture Ground
White*
Distribution
Panel
Black*
Non-Dim Loads
Ground
Neutral
Line / Hot
Green*
Fixture Ground
White*
C5-XPJ-16A
Black*
Non-Dim Loads
* Colors indicate the module and Lutron ballast wire colors and / or Lutron ballast terminal colors
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
4
EcoSystem
C5-XPJ-16A
Switching Power Module
369409d 5 04.07.17
Wiring (continued)
EcoSystem Bus Wiring
•Wire the EcoSystem Bus to the E1 and E2 terminals
on the front of the module.
•When the EcoSystem Bus is wired as NEC® Class 1,
the bus wiring must enter the left side knockout and
maintain 0.25 in (6 mm) spacing from the
IEC PELV / NEC® Class 2 sensor wiring.
•When the EcoSystem Bus is wired IEC PELV / NEC®
Class 2, the bus wiring may enter either knockout on
the low voltage wiring area.
EcoSystem Bus Details
•E1 and E2 wires are not polarity sensitive
•Bus length is limited by the wire gauge used for E1
and E2 as follows:
Wire Gauge (solid wire) Bus Length (max)
12 AWG (4.0 mm2)
2200 ft (671 m)
14 AWG (2.5 mm2)
1400 ft (427 m)
16 AWG (1.5 mm2)
900 ft (274 m)
2
18 AWG (1.0 mm )
570 ft (174 m)
IEC PELV / NEC® Class
2 wiring knockout
EcoSystem Bus
wiring knockout
E1
E2
E1 - Purple
E2 - Purple/White
E1
E2
NOTE: See Specifications page for wiring specifications
To additional EcoSystem
modules, ballasts, and the
Lutron, Lutron, Quantum, Softswitch, and EcoSystem are trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries.
Energi Savr Node is a trademark of Lutron Electronics Co., Inc.
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
5
EcoSystem
C5-XPJ-16A
Switching Power Module
369409d 6 04.07.17
Wiring (continued)
Low Voltage Wiring IEC PELV / NEC® Class 2 Sensors
Wiring to IEC PELV / NEC® Class 2 Sensors
•Wire color designations of the IEC PELV / NEC® Class
2 Terminals:
Red = 20 VBlack = Common
White = IR (wallstation / IR receiver)
Blue = Occupancy Sensor
Yellow = Daylight Sensor Signal
•Wiring between module and sensors shall not exceed
manufacturer’s specifications.
IEC PELV / NEC®
Class 2 wiring
knockout
•Make sure that the supply breaker to the switching
power module is OFF when wiring.
Note: The module accepts only one IR Input. Use of
the IR output from the EcoSystem Daylight Sensor
precludes the use of an IR receiver or wallstation
with the module. When both a daylight sensor and
wallstation / IR receiver are wired to the same module,
the IR wire from the daylight sensor should not be
connected.
Black
Red
Blue
Occupant Sensor Wired to Module
Black
Black
Red
Red
White
White
Yellow
EcoSystem Daylight Sensor
Wired to Module
EcoSystem Daylight
Sensor and Wallstation
wired to the module
(IR wired only to keypad)
Yellow
NOTE: See Specifications page for wiring specifications
®
Job Name:
Job Number:
S P E C I F I C AT I O N S U B M I T TA L
Model Numbers:
Page
6
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement