HYDRO-KING 2 CIRCUIT TIME SWITCH

IN TYPE 3R DUSTPROOF RAINPROOF ENCLOSURE, SUITABLE FOR POOL

LR3730

EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL.

FILTER CIRCUIT SINGLE POLE SINGLE THROW (SPST)

40 AMP. RESISTIVE, INDUCTIVE TUNGSTEN OR

1000V.A. PILOT DUTY -120-480 VOLT AC,

2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240V. AC

HEATER CONTROL CIRCUIT: 10 AMP 125 VOLTS A C MAX

CLOCK MOTOR: 110-125V. 60 HZ.

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO

ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.

WIRING

DIAGRAM

CLOCK

DIAL

TIME

POINTER

OFF

TRIPPER

MANUAL

LEVER

ON

TRIPPER

FIGURE 1

120V

SUPPLY

GND

NEUT

LINE

A 1 2

GND

CLOCK

MOTOR

TO

HEATER

TO

LOADS

WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid or strand

COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals.

Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).

REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP (°C)

75° INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

120V 240V

3 PHASE

240V 240V

PRESSURE PLATE

TERMINAL SCREW

14

12

10

8

15

20

30

40

60

60

60

75

1/2

1

2

2

2 1/2

3

5

N/A N/A

MAKE SURE WIRE

INSULATION CLEARS

PRESSURE PLATE

PROGRAMMING INSTRUCTIONS

• TO SET “ON” AND “OFF” TIMES: Hold trippers

against edge of CLOCK-DIAL, pointing to time (AM or

PM) when ON and OFF operations are desired,

tighten tripper screws firmly. For additional tripper pairs

on CLOCK-DIAL order 156T1978A.

• TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward.

Turn in either direction and align the exact time-of-day

on the CLOCK-DIAL (time now, when switch is put into

operation) to TIME POINTER. DO NOT MOVE POINTER.

OPERATING INSTRUCTIONS

• TO OPERATE SWITCH MANUALLY: Move MANUAL

LEVER below CLOCK-DIAL left or right as indicated by

arrows. This will not effect next operation.

CAUTION: You must turn heater off at least 15 minutes before

manually turning off filter system.

• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to

proper time-of-day. See programming instructions.

158TS12151

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698