TOP V PRO 6
TOP V PRO 6-10K UPS
Features:
• True double-conversion
• Microprocessor control optimizes reliability
• Input power factor correction
• Output power factor 0.9
• Wide input voltage (110 V – 300 V)
• Converter mode available
• ECO mode for energy saving
• Generator compatible
• Adjustable battery number
• Smart SNMP works well with either USB or RS-232 together
•Comprehensive display allows easy monitoring and access of UPS status
•Optional isolation transformer available. (Please check sales directly)
Specifications
MODEL
PHASE
CAPACITY*
INPUT
Nominal Voltage
Input Voltage Range
Frequency Range
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion
AC Mode to Battery Mode
Transfer Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery Type
Typical Recharge Time
Standard Model
Charging Current (max.)
Charging Voltage
Battery Type
Long-run Model*
Charging Current (max.)
Charging Voltage
INDICATORS
ALARM
Battery Mode
Low Battery
Overload
Fault
PHYSICAL
Long-run Model**
ENVIRONMENT
Humidity
Noise Level
MANAGEMENT
Smart RS-232/USB
Optional SNMP
Standart
Top V PRO 10K
Single phase with ground
6000 VA / 5400 W
10000 VA / 9000 W
208/220/230/240VAC
110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%)
46~54 Hz or 56~64 Hz
≧ 0.99 @ Nominal Voltage (100% load)
208/220/230/240VAC
± 1%
46~54 Hz or 56~64 Hz
50 Hz or 60Hz ± 0.1 Hz
3:1
≦ 3 % THD (Linear Load) ≦ 5 % THD (Non-linear Load)
Zero
Zero
Pure Sinewave
94%
90%
94%
91%
12 V / 9 Ah
9 hours recover to 90% capacity
1A/2A
218.4 VDC ±1%
273 VDC ±1%
Depending on the capacity of external batteries
1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)
273 VDC ±1% (Based on 20pcs batteries)
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault
indicators
LCD
Standard Model
Top V PRO 6K
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continously sounding
Dimension, D x W x H (mm)
Net Weight (kgs)
Dimension, D x W x H (mm)
Net Weight (kgs)
369 x 190 x 688
61
369 x 190 x 318
12
442 x 190 x 688
76
442 x 190 x 318
16
0-95% RH @ 0-50°C (non-condensing)
Less than 55dBA @ 1 Meter
0-95% RH @ 0-40°C (non-condensing)
Less than 58dBA @ 1 Meter
Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Power management from SNMP manager and web browser
CE, EN62040-1, EN62040-2, EN6100-2, EN6100-4
*1-3KVA: Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC
6-10KVA: Derate to 60% of capacity in Frequency converter mode and to 90% when the output voltage is adjusted to 208VAC
**Long-run model is only available in 200/208/220/230/240VAC systems (200VAC system only available for 1-3KVA).
*** Product specifications are subject to change without further notice