Esser IQ8 Control

Esser IQ8 Control
IQ8Control C Fire Alarm Panel
• State-of-the-art processor technology
• Maximum cable length for esserbus: 3,500 m
• Graphics supported, high performance
programming tool
• Innovative alarm signalling by means of
new IQ8Quad detector generation
• Supports IQ8Wireless Radio Technology and
IQ8Quad detectors with alarm devices
• A maximum of 31 control panels can
be networked via essernet (500 kB)
• Up to two esserbus loops, which can be
extended by spurs
• Micro modules compatible both for System
8000 and IQ8Control
• Modular space saving design
compact, flexible and future-proof
The IQ8Control C fire alarm panel
complies with the highest security
Both features ensure individual planning and guarantee a future-proof
solution in the domain of fire alarm technology. If required, the control panel
software can be replaced by an upgrade version via PC.
requirements for complex detection
purposes and reliable technology
standards. As an all-rounder within
the market segment for automatic
fire protection in small and mediumsize premises, the control panel is
provided with multiple features such
as compact dimensions, a broad
functional range and multiple expansion options as well as an excellent
cost/performance ratio.
Professional loop technology ensures economic efficiency even for
small applications
The IQ8Control C fire alarm panel is designed in compliance with high performance loop technology. The esserbus is a short and open circuit
resilient loop, offering highest operational reliability as well as cost saving
installation options on account of reduced wiring through combined loop
and spur topologies. All single-criterion and multi-criteria detectors
can be connected via the esserbus - this includes everything from Series
9000 standard fire detectors to Series 9200 intelligent fire detectors and
IQ8Quad detectors.
The IQ8Control C is completely compatible to the fire alarm system 8000
control panels. The modular design
allows flexible and user friendly integration of various modules, which
together from one unit. Each system
extension and the emergency power
supply can be adjusted to suit
advanced requirements by adding
one or more modules.
esserbus transponder
esserbus
IQ8Control C Fire Alarm Panel
Flexibility and reliability within the
Logged security
loop structure
The esserbus allows a combined
Each event is logged by the IQ8Control C fire alarm panel in second intervals. A maximum of 10,000 events can be verified at any time and subse-
loop and spur structure with a maximum length of 3.5 km. Up to 127
quently read out via an optional printer connection within the control panel
or via the tools 8000 programming software. The information can then be
bus devices can be divided in up to
stored on a data carrier if required.
127 detector zones, which guarantees a high degree of planning and
essernet
application flexibility. Each IQ8Quad
detector is supplied with isolators,
Within the essernet system up to 31 devices such as control panels, indicating and operating panels, gateways as well as user file depositories can
while other bus devices can be
be networked irrespective of hierarchical levels. Events and reports are
optionally provided with isolators.
Thus, each bus device remains
available for all devices when connected to the essernet.
operative in case of wire break or
short circuit. Only the corresponding
Easy installation and operation
The tools 8000 service and programming software package guarantees
part of the loop located between the
fast and simple commissioning. The settings are programmed directly at
affected bus devices with isolators is
replaced .
the control panel via a PC / laptop.
The esserbus transponders are bus
devices with freely programmable
Only essential information is displayed, which considerably facilitates
system operations. When connected to the essernet, decentralised operation is also possible.
inputs and outputs for controlling
and monitoring external devices or
for connecting special detectors.
Sensors integrated in single detectors
within the esserbus system are subject
Optionally, alarm and
status information can
be displayed via single
zone indicators at the
control panel, via decen-
to manual or time-related activation
/deactivation. The esserbus is suitable for transmitting alarm, fault and
maintenance signals. In addition,
each detector's position within the bus
system can be allocated when
viewing the corresponding text display.
tralised graphic layout
panels or plain text displays. It might as well
be printed out using
remote printers or the
printer integrated in the
control panel.
FAP 8008
external devices
IQ8Control M
OEC-c onverter
essernet
Loop length max. 1 km each
(with repeater max. 3 km)
Repeater
IQ8Control C
esserbus-PLus
Loop length max. 2 km
esserbus transponder
Management system
WINMAG
IQ8Control C
Innovative alarm signalling and
esserbus transponder
evacuation
Innovative integration for optical and
acoustic signalling devices, which
are consistently installed via the
Flash
Speech
esserbus transponder
powered loop network, is ensured by
esserbus-PLus
loop 1
bus supplied alarm signalling
devices and the IQ8Control C fire
loop 2
alarm panel. Thus, the IQ8Control C
fire alarm panel and the IQ8Quad fire
detectors provide an economic solution by means of minimised installation expenses.
All addressable alarm signalling
devices comply with EN 54-3. They
support alarm tones in compliance
with DIN 33404-3 and another 18
international alarm tones with a
Flash
Sound
Speech
The IQ8Quad detector with integrated alarm signalling devices and
its key features:
external power supply unit for the signalling devices is not required
· an
flasher,
sounder and speech alarm device can be individually controlled
·
device with the whole functional range
· each
· alarm signalling devices are automatically synchronised
standard sound pressures of up to
96 dB (A).
Trouble-free radio technology
integration
When connecting radio communication devices to the IQ8Control C fire
alarm control panel, all devices
remain individually addressable as
usual and the whole functional range
is maintained while each radio communication device is allocated only
one address. For planning purposes
and commissioning, the tools 8000
programming software package is
implemented. When using the software solution, the respective field
strength can be measured. Automatically generated frequency modifications secure trouble-free communic a t i o n b e t w e e n t h e r a d i o communication devices. In terms of
system expansion, the radio communication devices serve as an ideal
solution for maintaining unrestricted
functionality of all previous installations and further features can be
added to the functional range.
Wireless transponder
12V DC
esserbus-PLus
loop length max. 2 km
IQ8Control C
A variety of operating panel fronts: optimum solution for providers
and fire services
The wide range of operating panel fronts offers the an optimum solution for
all requirements set up by the providers and fire services. Therefore, it
perfectly bridges the
gap between man and
technology.
The operating panel
fronts are available in
various languages.
Each text is displayed
in the respective language on the standard
display or the 1/4-VGA
graphics display.
Arrangement of the devices:
320
Basis card,
power supply card
and
analog ring loop
module
450
185
Technical data
Mains voltage
230 V AC
Mains frequency
50 to 60 Hz
Rated voltage
12 V DC
Quiescent current
300 mA without operating panel
Rated current
0.7 A
Emergency power supply
2 x 12 Ah (max. 2 x 24 Ah, in 789300 extension housing)
Current drain for external users
max. 2.0 A
Ambient temperature
-5 °C to +45 °C
Storage temperature
-5 °C to +50 °C
Room climate
class 3K5 as per IEC 721-3-3: 1994
Class of protection
I in compliance with DIN EN 60950
Type of protection
IP 30
Housing
ABS, 10 % glass fibre reinforced., V-0
Colour
grey, similar to Pantone 538
Weight (without battery)
6.5 kg
Dimensions (W x H x D)
450 x 320 x 185 mm
VdS approval
G 299044
Order information
Part No.
Fire alarm panel IQ8Control C basic design, without operating front
808003
Package 1 of FACP IQ8Control C
808133
Package 3 of FACP IQ8Control C
808135
tools 8000 - initial equipment package / starters kit
789860
Analog loop module system 8000
784382
Analog loop module powered loop
804382
© 2007 Honeywell International Inc.
Battery
Peripheralmodule
Part No. 797965.G0 • 11/2007 • Technical information is subject to change without notice!
Battery
Dimensions (mm)
For further order data please refer to our "Fire Alarm Technology" product line catalogue.
Novar GmbH a Honeywell Company
Dieselstraße 2,
D-41469 Neuss
Phone: +49 (0) 21 37 / 17-0
Phone: +49 (0) 21 37 / 17-600
Fax:
+49 (0) 21 37 / 17-286
Honeywell Life Safety Austria GmbH
Fernkorngasse 10,
A-1100 Wien
Phone: +43 (0)1 / 6 00 60 30
Fax:
+43 (0)1 / 6 00 60 30-900
Administration
Customer Service Center
Internet:
www.esser-systems.com
E-mail:
[email protected]
Internet:
www.hls-austria.com
E-mail:
[email protected]
797966_G0_042009:797966_G0_1107.qxd
30.04.2009
11:42
Seite 2
IQ8Control M Fire Alarm Panel
• Latest processor technology
• Permissible wire length for esserbus up to 3,500 m
• Graphically supported powerful programming tool
• Innovative alarm signalling through the new alarm
generation IQ8Quad
• Supports IQ8Wireless RF technology
• Modular device structure
• Networking of up to 31 panels via essernet (500 kB)
• Up to 7 esserbus loops
• Up to 4 esserbus-PLus loops
Part No. 797966.G0 • 04/2009 • Technical information is subject to change without notice!
© 2009 Honeywell International Inc.
• EN-54 approval for up to 512 detectors
The fire alarm computer for
medium-sized to large premises:
flexible, multifunctional and
future-proof
The modular IQ8Control M fire alarm
computer uses proven technology and
fulfils the highest security requirements
for the comprehensive protection of
premises. Thus, it is just as suitable
for use in medium-sized premises with
complex security requirements as it
is for premises, which are spread over
a wide area and are networked.
The IQ8Control M is ideally suited to
medium-sized premises with complex
security requirements and for premises that cover a wide area and/or are
networked. The IQ8Control M is completely compatible with the fire alarm
system 8000 control panels. The
modular design allows flexible and
user-friendly integration of several individual modules, which together form
one unit. The system extension with
one or more additional modules can
be adapted to advanced requirements
very easily. This not only simplifies individual planning today, but also, as a
result of the FAP's extendibility options, ensures future-proof solutions.
If necessary, the control panel software can simply be replaced by an
upgrade version via a service PC.
Professional loop technology: multi-functional, extendible and
economic
The esserbus is a short and open circuit resilient loop, offering highest
operational reliability as well as cost saving installation options on
account of reduced wiring through combined loop and spur topologies.
All single-criterion and multi-criteria detectors can be connected via the
esserbus - this includes everything from Series 9000 standard fire detectors
to Series 9200 and IQ8Quad intelligent fire detectors.
IQ8Control M
esserbus transponder
esserbus
Detectors
series 9000
797966_G0_042009:797966_G0_1107.qxd
30.04.2009
11:42
Seite 3
IQ8Control M Fire Alarm Panel
Flexibility and reliability within the
loop structure
The esserbus allows a combined loop
and spur structure with a maximum
length of 3.5 km. Up to 127 bus devices can be divided in up to 127
detector zones, which guarantees
a high degree of planning and application flexibility. Each IQ8Quad
detector is supplied with isolators,
while other bus devices can be provided with them optionally.
Thus, each bus device remains operational in the case of a wire break or
short-circuits. Only the corresponding
part of the loop located between the
affected bus devices is automatically
isolated.
IQ8Control M allows implementation
of a maximum of 7 esserbus loops or
4 powered loops. The esserbus transponders are bus devices with freely
programmable inputs and outputs for
controlling and monitoring external
devices or for connecting special
detectors.
Sensors integrated in single detectors
within the esserbus system are subject to manual or time-related activation /deactivation. The esserbus is suitable for transmitting alarm, fault and
maintenance signals. In addition, the location of each detector within the
bus system can be allocated with an appropriate text display.
Logged security
Each event is logged to the second by the IQ8Control M fire alarm computer. A maximum of 10,000 events can be verified at any time and can be read
out via an optional printer connection within the control panel or via the tools
8000 programming software.
essernet
Within the essernet system up to 31 devices such as control panels, indicating and operating panels, gateways as well as electronic emergency
plans can be networked irrespective of hierarchical levels. Events and reports
are available for all devices when connected to the essernet.
Easy installation and operation
The tools 8000 service and programming software package guarantees
fast commissioning. The settings are programmed directly at the control
panel via a service PC. Only essential information is displayed, which considerably facilitates system operations. When connected to the essernet, decentralised operation is also possible. Optionally, alarm and status information
can be displayed via single
zone indicators at the control panel, via decentralised
graphic layout panels or plain
text displays. It can also be
printed out using remote printers or the printer integrated
in the control panel.
Example of a tools 8000 screen
FAP 8008
external
devices
OEC-converter
essernet
loop length max. 1 km each
(with repeater max. 3 km)
powered loop
loop length max. 2 km
esserbus-transponder
repeater
management system
WINMAG
IQ8Control M
System configuration example
797966_G0_042009:797966_G0_1107.qxd
30.04.2009
Innovative alarm signalling and
evacuation
The bus supplied alarm signalling
devices together with the IQ8Control
fire alarm computer ensure innovative
integration of optical and acoustic signalling devices, which are installed via
the powered loop network. Thus, the
IQ8Control M fire alarm computer and
the IQ8Quad fire detectors provide an
economic solution by means of minimised installation expenses.
11:42
Seite 4
esserbus transponder
IQ8Control M
Flash
esserbus transponder
Speech
esserbus-PLus
loop 1
loop 2
Flash
Sound
Speech
Bus supplied alarm signalling devices
All addressable alarm signalling
devices comply with EN 54-3. They
support alarm tones in compliance
with DIN 33404-3 and another 18 international alarm tones with a standard
sound level of up to 96 dB (A).
Trouble-free radio technology
integration
When connecting radio communication devices to the IQ8Control M fire
alarm computer, all devices remain
individually addressable as usual and
the whole functional range is maintained while each radio communication
device is allocated only one address.
For planning purposes and commissioning, the tools 8000 programming
software package is implemented.
This software can also be used to measure the respective field strength.
Automatically generated frequency
modifications secure trouble-free operation and communication between
the radio communication devices. In
terms of system expansion, the radio
communication devices serve as an
ideal solution for maintaining unrestricted functionality of all previous
installations whilst extending the
functional range.
esserbus-PLus 12V DC
loop length max. 2 km
IQ8Control M
Wireless
transponder
IQ8 wireless devices
The key features of the IQ8Quad detector with integrated alarm
signalling:
• an external power supply unit for the signalling devices is not required
• flasher, sounder and speech alarm device can be individually controlled
• each device - even with the whole functional range - only has one of the
127 addresses on the esserbus allocated to it
• alarm signalling devices are automatically synchronised
A variety of operating panel fronts:
optimum solution for providers and fire services
The wide range of operating panel fronts means that the right solution is
always available whatever the requirements of the providers and fire services, thus perfectly bridging the gap between man
and technology. The operating panel fronts of the
fire alarm panel are available in various languages.
The text is displayed in the
respective language on
the standard display and
on the 1/4-VGA graphics
display.
Examples of operating panel fronts
797966_G0_042009:797966_G0_1107.qxd
30.04.2009
11:42
Seite 1
450
185
Peripheralmodule
Basis card,
power supply card
and
analogue ring loop
module
Extension module
with 3
micromodule slots
640
Battery
Battery
Arrangement of the devices and Dimensions
-5 °C to +45 °C
-10 °C to +50 °C
I as per DIN EN 60950-1
Type of protection
Housing
Colour
Weight (w/o battery)
Dimensions (W x H x D)
Approval
IP 30
ABS, 10 % glass fibre reinforced, V-0
grey, similar to Pantone 538
11.5 kg
450 x 640 x 185 mm
VdS approval G 299044
Order Information
IQ8Control M basic version
Package 1, IQ8Control M with 4 mikromodule slots
Package 2, IQ8Control M with 4 micromodule slots and 64 single zone indicators
Package 3, IQ8Control M with 4 micromodule slots and built-in printer
Peripheral module with 1 additional micromodule slot
Extension module with 1 additional micromodule slot
Peripheral module
tools 8000 programming software
Part No.
808004
808214
808215
808216
772477
772478
772479
789860.10
For further order data please refer to our "Fire Alarm Technology" product line catalogue.
Novar GmbH a Honeywell Company
Dieselstr. 2,
41469 Neuss, Germany
Phone: +49 2137 17-0 (Administration)
+49 2137 17-600 (Customer Service Center)
Fax: +49 2137 17-286
Internet:
www.esser-systems.com
E-mail:
[email protected]
Honeywell Life Safety Austria GmbH
Lemböckgasse 49,
1230 Wien, Austria
Phone: +43 1 600 6030
Fax: +43 1 600 6030-900
Internet:
www.hls-austria.com
E-mail:
[email protected]
Part No. 797966.G0 • 04/2009 • Technical information is subject to change without notice!
Ambient temperature
Storage temperature
Class of protection
© 2009 Honeywell International Inc.
Technical data
Rated voltage
230 VAC
Nominal frequency
50 to 60 Hz
Rated current
0.7 A
Rated voltage
12 V DC
Quiescent current
300 mA w/o operating unit
Operating current for external load 2 A
Battery capacity
2 x 12 V / 24 Ah