User manual UMG 96RM-PN 90-277 V

Add to my manuals
128 Pages

advertisement

User manual UMG 96RM-PN 90-277 V | Manualzz

Janitza electronics GmbH

Vor dem Polstück 6

D-35633 Lahnau

Support tel. +49 6441 9642-22

Fax +49 6441 9642-30

E-mail: [email protected]

Internet: http://www.janitza.com

Power Analyser

UMG 96 RM-PN

User manual and technical data

Power Analyser

UMG 96RM-PN

Table of contents

General information

Inspection on receipt

Available accessories

Product description

Proper use

UMG 96RM-PN features

Measuring process

Operating concept

10

11

11

GridVis network analysis software

Connection variants

11

12

Assembly 13

4

6

7

8

8

Installation 15

Supply voltage 15

Voltage measurement

Current measurement using I1 to I4

16

22

Analogue inputs 30

Residual current monitoring (RCM) via I5, I6 31

Thermistor input 33

RS485 interface

Ethernet / ProfiNet interface

34

37

Digital in-/outputs

LED status bar

39

44

Operation 45

Display mode

Programming mode

Parameters and measured values

45

45

47

2

Configuration 49

Connecting the supply voltage

Current and voltage transformer

49

49

Programming the current transformer for I1-I3 51

Programming the voltage transformer 52

Programming parameters

TCP/IP configuration

RS485 device address (addr. 000)

53

54

56

RS485 baud rate (addr. 001)

User password (addr. 050)

56

57

Parameters 58

Mean value

Averaging method

Min. and max. values

Mains frequency (addr. 034)

58

58

58

59

Power meters

Resetting energy meters (addr. 507)

60

60

Harmonics 61

Measured value rotation

Measured value screens

62

62

Direction of the rotating field

LCD contrast (addr. 035)

64

64

Backlight 64

Time logging

Operating hours counter

Total running time, comparator

66

66

66

Serial number (addr. 754)

Software release (addr. 750)

67

67

Commissioning 68

Connecting the supply voltage

Connecting the measured voltage

Applying the measuring-circuit voltage

Direction of the rotating field

Checking the phase assignment

Checking the power measurement

Applying the residual current

68

68

68

69

69

69

69

Failure monitoring (RCM) for I5, I6

Checking the measurement

Checking the single phase powers

Checking the sum powers

RS485 interface

Digital outputs

Digital output status indicators

Pulse output (Group 1)

Comparators and threshold value monitoring 82

Service and maintenance 88

Service 88

Device calibration

Calibration intervals

88

88

Firmware update

Error / warning messages

89

90

70

71

71

71

72

74

75

77

Technical data

Function parameters

Table 1 - Parameter list

Table 2 - Modbus address list

Number formats

Dimension diagrams

Measured value screen overview

Connection example 1

Connection example 2

Basic functions quick guide

TCP/IP addressing quick guide

UMG 96RM-PN

96

103

105

112

115

116

118

124

125

126

127

3

UMG 96RM-PN

General information

Comments on the manual

Copyright

This manual is subject to the statutory provisions of copyright law and may not be photocopied, reprinted, or reproduced - in whole or in part, by mechanical or electronic means - nor otherwise duplicated or republished, without the binding written permission of:

We welcome your comments. If anything in this manual seems unclear, please let us know by sending an e-mail to: [email protected]

Meaning of symbols

This manual uses the following pictograms:

4

Janitza electronics GmbH, Vor dem Polstück 1,

D 35633 Lahnau, Germany

Trademarks

c

Dangerous voltage!

Risk to life or serious injury. Before commencing work on the system and the device, they must first be de-energised.

All trademarks and the resulting rights are the property of their respective owners.

Disclaimer

Janitza electronics GmbH accepts no responsibility for errors or deficiencies within this manual, and makes no commitment to keep the contents of this functional description up to date.

m

Attention!

Please pay attention to the documentation.

This symbol is intended to warn you of potential dangers, which could occur during installation, commissioning and use.

C

Note!

UMG 96RM-PN

Instructions on use

Please read this operation manual as well as all other publications that must be consulted for working with this product (in particular, for the installation, operation or maintenance). can be caused by the operation or maintenance of the device.

Observe all safety instructions and warnings. Failure to comply with the instructions can result in personal injuries and/or damage to the product.

Additional legal and safety regulations required for the respective application are to be followed during the use of the device.

Any unauthorised changes or use of this device, which go beyond the mechanical, electrical or otherwise stated operating limitations, can result in bodily injury or/and damage to the product.

Any such unauthorised change constitutes "misuse" and/or "negligence" according to the warranty for the product and thus excludes the warranty for covering possible damage resulting from this.

c

If the device is not operated according to the operation manual, protection is no longer ensured and hazards can be presented by the device.

This device must only be operated and repaired by specialised personnel.

Specialised personnel are persons, that based on their respective training and experience, are qualified to recognise risks and prevent potential dangers that m

Single core conductor must be provided with core end sheath.

m

Only pluggable screw terminals with the same number of poles and the same type of construction are permitted to be connected together.

5

6

UMG 96RM-PN

Concerning this operation manual

Inspection on receipt

This operation manual is part of the product.

• Read the operation manual before using the device.

• Keep the operation manual instructions throughout the entire service life of the product and have them readily available for reference.

• Pass the operation manual on to each subsequent owner or user of the product.

The prerequisites of faultless, safe operation of this device are proper transport and proper storage, setup and installation, as well as careful operation and maintenance. If it can be assumed that risk-free operation is no longer possible, the device must be immediately put out of operation and secured against being put back into operation again.

Packing and unpacking must be carried out with customary care without the use of force and only using suitable tools. The devices should be visually checked for flawless mechanical condition.

It can be assumed that risk-free operation is no longer possible if the device, for example,

C

All screw-type terminals included in the scope of delivery are attached to the device.

• has visible damage,

• no longer works despite the mains power supply being intact,

• has been exposed to prolonged adverse conditions

(e.g. storage outside the permissible climate limits without being adapted to the room climate, condensation, etc.) or rough handling during transportation (e.g. falling from a height, even if there is no visible external damage, etc.).

• Please check the delivered items for completeness before you start installing the device.

UMG 96RM-PN

Available accessories

Number Part no.

1

1

2

1

52.22.251

10.01.855

10.01.849

10.01.871

1

1

1

1

1

1

1

1

1

10.01.875

10.01.865

10.01.857

10.01.859

08.01.505

52.00.008

29.01.065

15.06.015

15.06.025

Designation

Mounting clips

Screw-type terminal, pluggable, 2-pole (auxiliary power)

Screw-type terminal, pluggable, 4-pole (voltage measurement)

Screw-type terminal, pluggable, 6-pole (current measurement I1-I3)

Screw-type terminal, pluggable, 2-pole (current measurement I4)

Screw-type terminal, pluggable, 10-pole (digital/analogue inputs/outputs)

Screw-type terminal, pluggable, 2-pole (RS 485)

Screw-type terminal, pluggable, 3-pole (digital/pulse output)

Patch cable 2 m, twisted, grey (connection UMG 96RM-PC/switch)

RS485 termination resistor, 120 ohms

Silicone seal, 96 x 96

Interface converter RS485 <-> RS232

Interface converter RS485 <-> USB

7

UMG 96RM-PN

8

Product description

Proper use

The UMG 96RM-PN is intended for the measurement and calculation of electrical variables such as voltage, current, power, energy, harmonics, etc. in building installations, on distribution units, circuit breakers and busbar trunking systems.

The UMG 96RM-PN is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed.

A continuous monitoring of residual currents (residual current monitor, RCM) is performed via the current measurement inputs I5 and I6 via an external residual current transformer with a rated current of 30 mA.

Measurements in medium and high-voltage networks are always performed via current and voltage transformers.

Measured voltages and measured currents must derive from the same network.

The measurement results can be displayed and read out and further processed via the RS485 or ProfiNet interface.

The voltage measurement inputs are designed for measurements in low voltage networks where rated voltages of up to 300V phase to earth and surge voltages of overvoltage category III can occur.

The current measurement inputs I1-I4 of the UMG

96RM-PN are connected via external ../1A or ../5A current transformers.

m

Residual current monitoring monitors residual currents via external current transformers.

The device is

not an independent protective device!

Device parameters

• Supply voltage:

Option 230V: 90V - 277V (50/60Hz) or

DC 90V - 250V; 300V CATIII

Option 24V: 24 - 90V AC / DC; 150V CATIII

• Frequency range: 45 - 65 Hz

Device functions

• 3 voltage measurement channels, 300V

• 4 current measurements

(via current transformer ../5A or ../1A)

• 2 residual current measurements

(via residual current transformer ../30mA) or optionally 2 temperature measurements

• RS485 interface, ethernet and ProfiNet

• 2 digital outputs and additionally 3 digital inputs/ outputs

UMG 96RM-PN

9

UMG 96RM-PN

UMG 96RM-PN features

General information

• Front panel integration device with dimensions

96x96 mm

• Connection via pluggable screw terminals

• LC display with backlight

• Operation via 2 buttons

• 3 Voltage and 4 current measurement inputs

• Either 2 residual current or temperature measurement inputs

• 2 digital outputs and 3 digital inputs/outputs

• RS485 interface (Modbus RTU, slave, up to 115 kbps)

• 2 interfaces for ethernet / ProfiNet

• Working temperature range -10°C to +55°C

Measurement uncertainty

• Effective energy, measurement uncertainty class

0.5 for ../5A converter

• Effective energy, measurement uncertainty class 1 for ../1A converter

• Reactive energy, class 2

Measurement

• Measurement in IT, TN and TT networks

• Measurement in networks with rated voltages up to L-L 480V and L-N 277V

• Measurement range current 0 to 5A eff.

• True RMS (TRMS)

• Continuous sampling of the voltage and current measurement inputs

• Continuous monitoring of residual currents with failure monitoring

• Temperature measurement

• Frequency range of the fundamental oscillation 45

Hz to 65 Hz

• Measurement of the 1st to 40th harmonics, for ULN and I1-I3

• Uln, I, P (cons./del.), Q (ind./cap.)

• Capturing substantially more than 1000 measured values

• Fourier analysis 1st to 40th harmonics for U and

I1-I3

• 7 power meters for

Effective energy (cons.), Effective energy (delivery),

Effective energy (without backstop),

Reactive energy (in 4 quadrants: delivered, consumed,

in each case ind./cap.),

Reactive energy (without backstop), Apparent energy,

for each of L1, L2, L3 and sum

10

UMG 96RM-PN

Measuring process GridVis network analysis software

The UMG 96RM-PN measures continuously and calculates all effective values over a 10/12 period interval. The device measures the real effective value

(TRMS) of the voltages and currents connected to the measurement inputs.

The UMG 96RM-PN can be programmed and read out using the GridVis network analysis software (Download: www.janitza.com). For this, a PC must be connected to the UMG 96RM-PN via a serial interface (RS485) or by ethernet.

Operating concept GridVis features

You can program and call up the measured values via many routes using the UMG 96RM-PN.

• Programming the UMG 96RM-PN

• Graphical representation of measured values

• Directly on the device via 2 buttons.

• Using the GridVis programming software.

• Using the device homepage (no programming).

• Using the Modbus protocol.

You can modify and call up the data using the Modbus address list. The list can be called up via the device's home page and can be found on the enclosed CD.

• Using the PLC within a PROFINET environment.

This operation manual only describes how to operate the UMG 96RM-PN using the two buttons.

The GridVis programming software has its own "online help" system.

11

RS485

UMG 96RM-PN

Connection variants

Connection of a UMG 96RM-PN to a PC via an interface converter:

RS485

RS485

RS485

RS485

RS485

UMG 96RM-PN

UMG 96RM-PN

Ethernet

RS485

Direct connection of a UMG 96RM-PN to a PC/PLC via

Ethernet/ProfiNet.

RS485

PC

(GridVis)

SPS

PC

(GridVis)

SPS

RS485

PC

(GridVis)

SPS

Ethernet / ProfiNet

Ethernet

Connection of a UMG 96RM-PN via an UMG 604 as a gateway.

RS485

RS485

Ethernet / ProfiNet

Ethernet / ProfiNet

Connection of a UMG 96RM-PN to a PC/PLC via

Ethernet/ProfiNet.

Ethernet / ProfiNet

Ethernet / ProfiNet

Ethernet

RS485

UMG 604

RS485

RS485

UMG 96RM-PN

PC

(GridVis)

SPS

Ethernet / ProfiNet

UMG 96RM-PN

Ethernet / ProfiNet

Ethernet / ProfiNet

Ethernet / ProfiNet

RS485 UMG 96RM-PN

Ethernet / ProfiNet

Switch

Ethernet / ProfiNet

Ethernet / ProfiNet

Ethernet / ProfiNet

PC

(GridVis)

SPS

PC

(GridVis)

SPS

Ethernet / ProfiNet

PC

(GridVis)

SPS

Ethernet / ProfiNet

Ethernet / ProfiNet Ethernet / ProfiNet

PC

(GridVis)

SPS

Ethernet / ProfiNet

Ethernet / ProfiNet

Ethernet / ProfiNet

Ethernet / ProfiNet

UMG 96RM-PN

Assembly

Position of installation

The UMG 96RM-PN is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed.

Mounting position

To ensure adequate ventilation, the UMG 96RM-PN must be installed vertically. There should be separation above and below of at least 50mm with 20mm space to the sides.

Front panel section

Cut-out size:

92

+0.8

x 92

+0.8

mm.

Fig. Mounting position

UMG 96RM-PN

(View from rear)

m

Failure to meet the minimum clearances can destroy the UMG 96RM-PN at high ambient temperatures!

13

UMG 96RM-PN

Mounting

The UMG 96RM-PN is secured in the switchboard by the mounting clips on the side. Before insertion the device they must be removed, for example by using a screwdriver to lever them horizontally.

Mounting is then performed by sliding in and engaging the clips and subsequently screwing in the screws.

• Screw in the clamping screws until they are just touching the mounting plate.

• Tighten the clamping screws by two more turns each (tightening the screws too far can destroy the mounting clips).

Fig. Side view of the UMG 96RM-PN with mounting clip.

To release the clips, use a screwdriver to lever them horizontally.

Mounting plate

Clamping screw

Mounting clip Screwdriver

When clamping screws touch the mounting plate: max. two more turns to secure the device

14

UMG 96RM-PN

Installation

Supply voltage

The UMG 96RM-PN needs a supply voltage to operate.

The supply voltage is connected on the rear side of the device via terminal blocks.

Fuse

Before connecting the supply voltage, ensure that the voltage and frequency correspond to the details on the rating plate!

Circuit breaker m

• The supply voltage must be connected through a fuse according to the technical data.

• If installed in a building, a disconnector or circuit breaker must be provided for the supply voltage.

• The disconnector must be installed near the device and easily accessible to the user.

• The switch must be marked as the circuit breaker for this device.

• Voltages which are over the permitted voltage range can destroy the device.

Fig. Connection example of the supply voltage to a

UMG 96RM

L

N

15

UMG 96RM-PN

Voltage measurement

You can use the UMG 96RM-PN for voltage measurement in TN, TT, and IT systems.

Voltage measurement in the UMG 96RM-PN is designed for the overvoltage category 300V CAT III (measurement voltage surge 4kV).

In systems with no N, measured values requiring an N refer to a calculated N.

L1 L1

L2

L3

N

PE

277V/480V 50/60Hz

N

240V

50/60Hz

L1

L2

L3

480V 50/60Hz

V1 V2 V3 V

N

AC/DC

DC

Voltage measurement

UMG 96RM

Auxiliary supply

Impedance

V1 V2 V3 V

N

Earthing of the system

AC/DC

DC

Voltage measurement

UMG 96RM

Auxiliary supply

Fig. Schematic diagram - Measurement on three-phase

4-conductor systems.

16

Fig. Schematic diagram - Measurement on three-phase

3-conductor systems.

UMG 96RM-PN

Nominal network voltage

Lists of networks and their nominal network voltages in which the UMG 96RM-PN can be used.

Three-phase 4-conductor systems with earthed neutral conductor.

U

L-N /

U

L-L

66V / 115V

120V / 208V

127V / 220V

220V / 380V

230V / 400V

240V / 415V

260V / 440V

277V / 480V

Maximum system rated voltage

Fig. Table for network rated voltages i.a.w. EN60664-

1:2003 suitable for the voltage measurement inputs.

Unearthed three-phase 3-conductor systems.

U

L-L

66V

120V

127V

220V

230V

240V

260V

277V

347V

380V

400V

415V

440V

480V

Maximum system rated voltage

Fig. Table for network rated voltages i.a.w. EN60664-

1:2003 suitable for the voltage measurement inputs.

17

UMG 96RM-PN

Voltage measurement inputs

The UMG 96RM-PN has three voltage measurement inputs (V1, V2, V3).

Overvoltage

The voltage measurement inputs are suitable for measurements in networks where overvoltages of overvoltage category 300V CATIII (measurement voltage surge 4kV) can occur.

Frequency

The UMG 96RM-PN requires the mains frequency for the measurement and calculation of measured values.

The UMG 96RM-PN is suitable for measuring in the frequency range from 45 to 65 Hz.

Fuse

Circuit breaker

L1

L2

L3

N

Fig. Example connection for measuring voltage.

18

UMG 96RM-PN

When connecting the voltage to be measured, the following must be observed:

Isolation device

• A suitable circuit breaker must be fitted to disconnect and de-energise the UMG 96RM-PN.

• The circuit breaker must be placed in the vicinity of the UMG 96RM-PN, be marked for the user and easily accessible.

• The circuit breaker must be UL/IEC certified.

c

Attention!

Voltages that exceed the allow nominal network voltages must be connected via a voltage transformer.

c

Attention!

The UMG 96RM-PN is not suitable for measuring DC voltages.

Overcurrent protection device

• An overcurrent protection device must be used for line protection.

• For line protection, we recommend an overcurrent protection device as per the technical specifications.

• The overcurrent protection device must be suitable for the line cross section used.

• The overcurrent protection device must be UL/IEC certified.

• A circuit breaker can be used as an isolating and line protection device. The circuit breaker must be UL/IEC certified.

• Measured voltages and measured currents must derive from the same network.

c

Attention!

The voltage measurement inputs on the UMG 96RM-PN are dangerous if touched!

19

UMG 96RM-PN

Connection schematics, voltage measurement

• 3p 4w (addr. 509= 0), factory default setting

L1

L2

L3

N

V1 V2 V3 V

N

Fig. System with three phase conductors and a neutral conductor.

• 3p 4u (addr. 509 = 2)

L1

L2

L3

• 3p 4wu (addr. 509 = 1)

L1

L2

L3

N

V1 V2 V3 V

N

Fig. System with three phase conductors and a neutral conductor. Measurement made with a voltage transformer.

• 3p 2u (addr. 509 = 5)

L1

L2

L3

V1 V2 V3 V

N

Fig. System with three phase conductors without a neutral conductor. Measured values which require an N refer to a calculated N.

20

V1 V2 V3 V

N

Fig. System with three phase conductors without a neutral conductor. Measurement made with a voltage transformer. Measured values which require an N refer to a calculated N.

• 1p 2w1 (addr. 509 = 4)

L1

N

V1 V2 V3 V

N

Fig. Measured values derived from voltage measurement inputs V2 and V3 are taken to be zero and are not calculated.

• 1p 2w (addr. 509 = 6)

L1

L2

V1 V2 V3 V

N

Fig. TN-C system with single-phase threeconductor connection. Measured values derived from voltage measurement input V3 are taken to be zero and are not calculated.

UMG 96RM-PN

• 2p 4w (addr. 509 = 3)

L1

L2

L3

N

V1 V2 V3 V

N

Fig. System with equal loading of the phases.

The measured values for voltage measurement input V2 are calculated.

• 3p 1w (addr. 509 = 7)

L1

L2

L3

L1

L2

L3

L1

L2

L3

N

V1 V2 V3 V

N

Fig. 3 systems with equal loading of the phases.

21

UMG 96RM-PN

Current measurement using I1 to I4

The UMG 96RM-PN is intended for the connection of current transformers with secondary currents of ../1A and ../5A, via terminals I1-I4. The factory default for the current transformer ratio is 5/5A and must be adapted to the current transformer employed if necessary.

Direct measurement without a current transformer is not possible with the UMG 96RM-PN.

Only AC currents can be measured - DC currents cannot.

Current measurement input I4 only produces an apparent current measurement, due to there being no multiplier with a voltage. Power measurements are therefore not possible with input I4.

c

22

Attention!

The current measurement inputs are dangerous to touch.

Load

Fig. Current measurement (I1-I3) via current transformers (connection example)

m

The attached screw-type terminal must be fixed using the two screws on the device!

L1

L2

L3

N

UMG 96RM-PN

c

Earthing of current transformers!

If a connection is provided for the earthing of secondary windings, then it must be connected to the earth.

m

Attention!

The UMG 96RM-PN is not suitable for measuring DC voltages.

C

It is not necessary to configure a connection schematic for measurement input I4.

Fig. Current measurement (I4) via current transformers (connection example)

23

UMG 96RM-PN

Current direction

The current direction can be individually corrected via the existing serial interfaces or on the device for each phase.

If incorrectly connected, a subsequent re-connection of the current transformer is not required.

c

Attention!

Residual current monitoring is performed using the terminals I5 and I6 (cf. page

30). There is no directional sensitivity of the residual currents of the network or load sides (not directionally sensitive).

With residual current monitoring (RCM) there is no directional sensitivity of the residual currents on the network or load sides (not directionally sensitive).

c

Earthing of current transformers!

If a connection is provided for the earthing of secondary windings, then it must be connected to the earth.

c

Current transformer connections!

The secondary connection of the current transformer must be short circuited on this before the current feed to the UMG 96RM-

PN is disconnected!

If a test switch, which automatically shortcircuits the secondary wires of the current transformer, is available then it is sufficient to set this to the "Test" position insofar as the short-circuiting device has been checked beforehand.

24 c

Open-circuit current transformers!

High voltage spikes that are dangerous to touch can occur on current transformers that are driven with open-circuit secondary windings!

With "safe open-circuit current transformers" the winding insulation is rated such that the current transformer can be driven open. However, even these current transformers are dangerous to touch when they are driven open-circuit.

c

Attention!

The UMG96RM is only approved for measuring current with a current transformer.

UMG 96RM-PN

25

UMG 96RM-PN

Connection schematics, current measurement (I1-I3)

• 3p 4w (addr. 510= 0), factory default setting

L1

L2

L3

N

• 3p 2i (addr. 510 = 1)

L1

L2

L3

N

I1 I2 I3

Fig. Measurement in a three-phase network with unequal loading.

• 3p 2i0 (addr. 510 = 2)

L1

L2

L3

I1 I2 I3

Fig. System with equal loading of the phases.

The measured values for current measurement input I2 are measured.

• 3p 3w3 (addr. 510 = 3)

L1

L2

L3

I1 I2 I3

Fig. The measured values for current measurement input I2 are calculated.

26

I1 I2 I3

Fig. Measurement in a three-phase network with unequal loading.

• 3p 3w (addr. 510 = 4)

L1

L2

L3

N

I1 I2 I3

Fig. System with equal loading of the phases.

The measured values for current measurement inputs I2 and I3 are calculated.

• 1p 2i (addr. 510 = 6)

L1

L2

I1 I2 I3

Fig. Measured values derived from current measurement input I3 are taken to be zero and are not calculated.

UMG 96RM-PN

• 2p 4w (addr. 510 = 5)

L1

L2

L3

N

I1 I2 I3

Fig. System with equal loading of the phases.

The measured values for current measurement input I2 are calculated.

• 1p 2w (addr. 510 = 7)

L1

N

I1 I2 I3

Fig. Measured values derived from current measurement inputs I2 and I3 are taken to be zero and are not calculated.

27

UMG 96RM-PN

Connection schematics, current measurement (I1-I3)

• 3p 1w (addr. 510 = 8)

L1

L2

L3

L1

L2

L3

L1

L2

L3

Ammeter

If you wish to measure the current not only with the UMG

96RM but rather with an ammeter too, the ammeter must be connected to the UMG 96RM-PN in series.

UMG

S

1

A

I

S

2

I1 I2 I3

Fig. 3 systems with equal loading of the phases.

Einspeisung

Supply

(k)S

1

(K)P

1

Verbraucher

Consumer

S

2

(l)

P

2

(L)

Fig. Current measurement with an additional ammeter (example).

28

UMG 96RM-PN

Total current measurement

If the current measurement is done via two current transformers, the overall transformation ratio of the current transformers must be programmed into the UMG 96RM-PN.

Example: The current is measured via two current transformers. Both current transformers have a transformation ratio of 1000/5A. The summation measurement is performed using a total current transformer 5+5/5A.

UMG

I

S

1

S

2

The UMG 96RM-PN must then be setup as follows:

Primary current: 1000A + 1000A = 2000A

Secondary current: 5A

Einspeisung 1

Supply 1

Einspeisung 2

Supply 2

P

1

P

2

1S

1

1S

2

2S

1

2S

2

1P

1

(K)

(L)

1P

2

1S

1

(k)

(l)

1S

2

2S

1

(k)

(l)

2S

2

2P

1

(K)

(L)

2P

2

Verbraucher A

Consumer A

Verbraucher B

Consumer B

Fig. Current measurement via a total current transformer

(example).

29

UMG 96RM-PN

Analogue inputs

The UMG 96RM-PN has two analogue inputs, each of which can be used for a residual current measurement or a temperature measurement. A measurement is performed here via terminals 32-34 (Input 1) and 35-37

(Input 2).

c

Attention!

Operating equipment connected to the analogue inputs must feature reinforced or double insulation to the mains supply circuits!

The analogue inputs can be used either for residual current measuring or temperature measuring, per the following table:

Measurement

Temperature

Residual current

Terminal

32/34 (Input 1) and

35/37 (Input 2)

32/33/34 (Input 1) and

35/36/37 (Input 2)

Example - temperature sensor:

A temperature sensor in close proximity to non-isolated mains cables should measure within a 300V CAT III network.

Remedy:

The temperature sensor must be equipped with reinforced or double insulation for 300V CAT III. This equates to a test voltage for the temperature sensor of

3000V AC (duration 1 min.).

Example - residual current transformer:

A residual current transformer should measure on isolated mains cables within a 300V CAT III network.

Remedy:

The insulation of the mains cables and the insulation of the residual current transformer must fulfil the basic insulation requirements for 300V CAT III. This equates to a test voltage of 1500V AC (duration 1 min.) for the insulated mains cables and a test voltage of 1500 V

AC (duration 1 min.) for the residual current transformer.

30

UMG 96RM-PN

Residual current monitoring (RCM) via I5, I6

The UMG 96RM-PN is suitable for use as a residual current monitoring device (RCM) as well as for monitoring

AC, pulsing DC, and DC.

The UMG 96RM-PN can measure residual currents in accordance with IEC/TR 60755 (2008-01) of type A and type B.

The connection of suitable external residual current transformers with a rated current of 30 mA is performed via the residual current transformer inputs I5 (terminals

32-34) and I6 (terminals 35-37).

C

Residual current transformer ratio

The GridVis software included in the scope of the delivery can be used to individually program the residual current transformer inputs' transformer ratios.

PE N L1

Fig. Connection example of residual current monitoring via current transformers

L2 L3

31

UMG 96RM-PN

Connection example, residual current monitoring

L1

L2

L3

PEN

N

PE

Residual current transformer

Fig. Example

UMG96RM-PN with residual current monitoring via measuring inputs I5/I6.

L1 L2 L3 N I1 I2 I3 I4

UMG 96RM-PN

I5 I6

Residual current transformer

M

3~

C

It is not necessary to configure a connection schematic for measurement inputs I5 and I6!

32

UMG 96RM-PN

Thermistor input

The UMG 96RM-PN has two thermistor inputs. The temperature measurement is performed here via terminals 32/34 (Input 1) and 35/37 (Input 2).

Do not exceed the total resistance load (sensor + cable) of 4kOhm.

PT100

PT100 m

Use a shielded cable to connect the temperature sensor.

Fig. Example, temperature measurement with a PT100

33

UMG 96RM-PN

RS485 interface

On the UMG 96RM-PN, the RS485 interface is designed as a 2-pin plug contact, which communicates via the

Modbus RTU protocol (see also Programming parameters).

Termination resistors

The cable is terminated with resistors (120Ohm, 1/4W) at the beginning and at the end of a segment.

The UMG 96RM-PN does not contain any termination resistors.

Correct

RS485 bus

A

B

RS485 interface,

2 pin plug contact

Incorrect

120

34

RS485 bus

A

B

RS485 interface,

2-pin plug contact with termination resistor

(item no. 52.00.008)

Terminal strip in the cabinet.

Device with RS485 interface.

(without termination resistor)

Device with RS485 interface.

(with termination resistor on the device)

UMG 96RM-PN

Screening Cable type

Twisted screened cable should be used for connections via the RS485 interface.

The cable used must be suitable for an environmental temperature of at least 80°C.

• Earth the screens of all cables that lead to the cabinet and at the cabinet entry.

• Connect the screens over a generous area and in a manner that will conduct well, to a low-noise earth.

• Gather the cables mechanically above the earthing clamp in order to avoid damage due to cable movements.

• Use suitable cable glands to feed the cables into the cabinet, for example, armoured conduit couplings.

Recommended cable types:

Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)

Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)

Maximum cable length

1200m at a baud rate of 38.4k.

Cable

Strain relief

Screen braid of the cable

Earthing clamp

Noiseless ground

C

CAT cables are not suitable for bus wiring. Use the recommended cable types for this.

Fig. Screening procedure at cabinet entry.

35

UMG 96RM-PN

Bus structure

• All devices are connected in a bus structure (line) and each device has its own address within the bus (see also Parameter programming).

• Up to 32 subscribers can be connected together in a single segment.

• The cable is terminated with resistors (bus termination

120Ohm, 1/4W) at the beginning and at the end of a segment.

• With more than 32 subscribers, repeaters (amplifiers) must be used to connect the individual segments.

• Devices for which the bus connection is switched on must be under current.

• It is recommended that the master be placed at the end of a segment.

• If the master is replaced with a bus connection, the bus must be switched off.

• Replacing a slave with a bus connection that is either switched on or de-energised can destabilise the bus.

• Devices that are not connected to the bus can be replaced without destabilising the bus.

• The shield has to be installed continuously and needs to be broadly and well conducting connected to an external low voltage (or potential) ground at the end.

T

T

Master

Slave

Speisung notwendig / power supply necessary

T

Busabschluß eingeschaltet / bus terminator on

Slave Slave

T

Repeater

T

Slave Slave

Fig. Bus structure

36

UMG 96RM-PN

Ethernet / ProfiNet interface

The Ethernet network settings should be specified by the network administrator and set on the UMG 96RM-

PN accordingly.

If the network settings are not known, the UMG 96RM-

PN may not be integrated into the network through the patch cable.

The UMG 96RM-PN has two identical Ethernet interfaces.

This allows another Ethernet/ProfiNet terminal to be operated via the second interface, thus reducing outlay on cabling.

LEDs for the Ethernet interfaces

LED 1 LED 2

LED Colour Function

1 Green Lights up when there is a connection (a link)

2 Yellow Lights up intermittently when there is network activity

Ethernet connection

PC switch for PLC

Ethernet connection

Ethernet /

ProfiNet device

ProfiNet status LED bar

LED Status Function

RDY Off Device is not powered

RDY Flashing Device is being initialised

RDY

SF

BF

BF

BF

On

On

On

Device is ready for operation

Configuration error or system error

Flashing No ProfiNet connection,

Off

No connection in spite of physical connection

Connection to the PLC established / active

37

UMG 96RM-PN

m

Attention!

Connection of the UMG96RM-PN to the Ethernet may only be carried out after consulting the network administrator!

PROFIenergy / Entity Class 2

The UMG 96RM-PN is certified as

Entity Class 2 (measurement functionality) for use of the PROFIenergy

Profile V1.1.

C

Dynamic Configuration Protocol (DCP)

This function assigns unique addresses and names to the subscribers of a

ProfiNet system, and is prioritised by the UMG 96RM-PN.

• A PROFIenergy device provides a defined set of functions and information, helping to standardise and reduce configuration and installation effort.

Device master file

The device master file, abbreviated as GSD file, describes the ProfiNet characteristics of the UMG96RM-

PN. The GSD file is required, for example, by the configuration program of the PLC.

The device master file for the UMG96RM-PN has the file name "GSDML-V2.31-JanitzaelectronicsGmbH-

UMG96RM-PN-xxxxxxxx.xml" and is included on the data carrier as part of the scope of the delivery.

• PROFIenergy is a profile for energy management in production systems, which is based on ProfiNet.

• Energy consumers within the system can therefore be controlled and monitored with PROFlenergy using open and standardised commands.

• With automated comparison of functionality between the ProfiNet control centre and the UMG, additional configuration and installation is rendered unnecessary.

38

UMG 96RM-PN

Digital in-/outputs

The UMG 96RM-PN has 2 digital outputs and either

3 digital inputs or outputs, which are subdivided into two groups (see Figure, page 40). This is based on the rule that only the

whole of Group 2 (connection 28 to

31) can function either as an input or output; differing assignments within the same group are not possible!

Digital outputs, Group 2

• The status of the inputs and outputs in Group 2 is indicated by the associated LED (cf. chapter LED status bar).

Digital outputs, Group 1

• The status indicator appears on the display at K1 or

K2

• The status indicator on the display is not dependent on an inversion being activated (NC / NO)

Source e.g.

Comparator group

Inverter

Digital output 3

K1/K2 display status indicator

C

The digital outputs of group 2 are compatible.

not AC

Source e.g.

Comparator group

Inverter

Digital output 1

39

UMG 96RM-PN

Input/output byte coding

(Input/output data of the ProfiNet „digital IO“ module)

• If the digital inputs/outputs in group 2 are configured as inputs, bit-oriented coding of the statuses occurs

(bit 0 to 2). In this case, coding corresponds to the digital inputs with:

Bit 0 1 2 3 4 5 6 7

Input 3: 1 = signal is present

Input 2: 1 = signal is present

Input 1: 1 = signal is present

• The digital outputs can be controlled by setting the corresponding bits.

• If, for example, the digital inputs/outputs in group 2 are configured as outputs, bit-oriented coding occurs within bits 0 to 4:

Bit 0 1 2 3 4 5 6 7

Output 5: 1 = signal set

Output 4: 1 = signal set

Output 3: 1 = signal set

Output 2: 1 = signal set

Output 1: 1 = signal set

40

UMG 96RM-PN

Digital outputs

These outputs are galvanically separated from the analysis electronics using optocouplers. The digital outputs have a common supply.

• The digital outputs of group 1 can switch AC and DC loads. The digital outputs of group 2 can

not switch

AC loads.

• The digital outputs are not short-circuit proof.

• Connected cables that are longer than 30m must be shielded when laid.

• An external auxiliary voltage is required.

• The digital outputs of Group 1 can be used as pulse outputs.

• The digital outputs can be controlled via Modbus and

ProfiNet.

• The digital outputs

of Group 1 can output results of comparators.

Group 1

~

Fig. Connection of digital/pulse outputs

Group 2

~

41

UMG 96RM-PN

Example DC connection

m

Attention!

Digital outputs are not short-circuit proof!

UMG 96RM-PN

13

Digital Ouput 1

14

C

Functions for the digital outputs can be adjusted clearly in the GridVis software.

A connection between the UMG 96RM-PN and the PC via an interface is required to use the GridVis software.

Digital Ouput 2

15

28

Digital Ouput 3

29

C

When using the digital outputs of Group 1 as pulse outputs, the auxiliary voltage (DC) must have a max. residual ripple of 5%.

C

Digital Ouput 4

30

T h e d i g i t a l i n p u t s o r o u t p u t s o f

Group 2 cannot be configured as pulse inputs/outputs. It is possible to use them as switch inputs/outputs (ProfiNet/

Modbus, tariff switching).

Digital Ouput 5

31

Fig. Example for two relays connected to the digital outputs

42

External auxiliary voltage

+

24V DC

-

DC

DC

UMG 96RM-PN

Digital inputs

When Group 2 is assigned as inputs, the UMG96 RM-

PN has three digital inputs, each of which can have a signal generator connected to it. If there is a signal, the associated LED lights up green.

External auxiliary voltage

-

24V DC

+

An input signal is detected on a digital input if a voltage of at least 10V and maximum 28V is applied and a current of at least 1mA and a maximum of 6mA is flowing. Wiring longer than 30m must be screened.

Note the correct polarity of the supply voltage!

UMG 96RM-PN

Digital inputs 1-3

2k21

28

29

Digital

Input 1

S1

-

+

2k21

2k21

30

Digital

Input 2

S2

Group 2

2k21

2k21

31

Digital

Input 3

S3

2k21

2k21

Fig. Connection example of digital inputs.

Fig. Example for the connection of external switch contacts S1 and S2 to digital inputs 1 and 2.

43

UMG 96RM-PN

LED status bar

The LED status bar on the back of the device shows the different statuses of the inputs and outputs.

Digital inputs

The LED assigned to the input lights up

green if a signal of at least 1mA is fl owing on this interface.

Digital input/output 1/3

Digital input/output 2/4

Digital input/output 3/5

Digital outputs

The LED assigned to the output lights up red if the output is set as active - irrespective of whether there is an onwards connection to this interface.

Fig. LED status bar for the inputs or outputs

C

T h e d i g i t a l i n p u t s o r o u t p u t s o f

Group 2 cannot be confi gured as pulse inputs/outputs. It is possible to use them as switch inputs/outputs (Profi Net/

Modbus, tariff switching).

44

UMG 96RM-PN

Operation

Programming mode

The UMG 96RM-PN is operated with buttons 1 and 2, whereby the following distinctions are made:

• short press of button 1 or 2: next step (+1)

• long press of button 1 or 2: previous step (-1)

Measured values and programming data are presented on a liquid crystal display.

Programming mode displays and allows for the modification of the settings required for operation of the UMG 96RM-PN. Pressing and holding buttons 1 and 2 at the same time for approx. 1 second takes you

(after password prompt) to Programming mode. If no user password has been set up, you are taken directly to the first Programming menu. Programming mode is indicated on screen by the text "PRG".

A distinction is made between Display mode and

Programming mode. The requirement to enter a password makes it possible to prevent the programming data from being changed accidentally.

Button 2 then allows you to switch between the following

Programming menus:

Display mode

- Current transformer

- Voltage transformer

- Parameter list

- Device TCP/IP address

- Subnet mask

- Gateway address

In Display mode, using buttons 1 and 2, you can scroll through the programmed measured value screens. In the factory, all measured value screens listed in Profile

1 can be accessed. Up to three measured values are displayed on each measured value screen. The measured value rotation allows selected measured value screens to be displayed in turn after a configurable rotation time.

If you are in Programming mode and no button is pressed around 60 seconds or if buttons 1 and 2 are pressed simultaneously for around 1 second, the UMG

96RM-PN returns to Display mode.

45

UMG 96RM-PN

Delivery

Max. value, HT/Consumption

Min. value NT/Delivery

Mean value

Programming mode

Summation measurement

Phase conductor-

Phase conductor

Password

CT: Current transformer

VT: Voltage transformer

K1: Output 1

K2: Output 2

Button 2

Button 1

46

UMG 96RM-PN

Parameters and measured values Example of a parameter screen

All of the parameters required for operation of the UMG

96RM-PN, such as the current transformer data, and a selection of frequently required measured values are stored in the table.

The contents of most addresses can be accessed via the serial interface and with the buttons on the UMG

96RM-PN.

On the display of the UMG

96RM-PN the contents of address "000" is displayed as "001'. This parameter describes (according to the list) the device address of the UMG 96 RM-PN (in this case "001") within a bus.

On the device you can only enter the first 3 significant digits of a value. Values with more digits can be entered in GridVis.

The device only ever displays the first 3 significant digits of the value.

Selected measured values are summarised in measured value screen profiles, and can be displayed in Display mode with buttons 1 and 2.

Example of a measured value screen

In this example, the display of the UMG 96RM-PN shows each of the voltages L to N as 230V. Transistor outputs

K1 and K2 are active and a current can flow.

The current measured value screen profile, the current screen rotation profile and date and time can only be read and modified via the RS485 interface.

47

UMG 96RM-PN

Button functions

Display mode

Switch mode

At same time

Scroll

Short

Long

Measured values

A(+1)

Measured values

A(-1)

Measured values

B ...

Long Short

You can find an overview of the measured value screens in the chapter "Overview of measured value screens".

Password

Programming mode

Switch mode

Programming menu 1

(flashing)

Short

Long

(flashing)

At same time

Scroll

Programming menu +1

...

Programming menu -1

Programming

Confirm selection

Short: Number +1

Long: Number -1

Short: Value x 10

(move comma right)

Long: Value /10

(move comma left)

48

UMG 96RM-PN

Configuration

Connecting the supply voltage

The supply voltage must be connected for the configuration of the UMG 96RM-PN.

c

Attention!

If the supply voltage does not correspond to the voltage indicated on the rating plate, this may lead to malfunctions and severe damage to the device.

The supply voltage level for the UMG 96RM-PN is specified on the rating plate.

If no screen appears, check whether the supply voltage is within the rated voltage range.

C

The adjustable value 0 for the primary current transformer does not produce any meaningful work values, and must not be used.

Current and voltage transformer

A current transformer of 5/5A is set in factory. Only if voltage transformers are connected does the preprogrammed voltage transformer ratio need modifying. m

Devices based on automatic frequency detection require approx. 5 seconds to determine the mains frequency. During this time, the measured values do not comply with the promised measurement uncertainty.

When connecting voltage transformers, pay attention to the measured voltage specified on the rating plate of the UMG 96RM-PN!

C

Prior to commissioning potential production dependant contents of the energy counter and min/max values have to be deleted.

49

UMG 96RM-PN

C

Current and voltage transformer

The GridVis software can be used to individually program the transformation ratios for each current or voltage measurement input.

Only the transformation ratio for the respective group of current measurement inputs I1-I3 or voltage measurement inputs

V1-V3 can be set on the device.

The transformation ratio of current trans-

former input I4 and the residual current

transformer inputs I5, I6 must be set in the

GridVis software.

Current transformer input I4

Current transformer input I4 only produces an apparent current measurement, due to there being no multiplier with a voltage.

Power measurements with the input are therefore not possible. The transformation ratio can be set in the GridVis software.

Fig. Screen for configuration of the current and voltage transformer in the GridVis software.

C

If the device is operated within a PROFINET environment, parameters listed in the GSD file can also be configured via the PLC.

50

UMG 96RM-PN

Programming the current transformer for I1-I3

Switch to Programming mode:

• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously. If a user password has been set, then the password prompt appears with "000". The first digit of the user password flashes and can be modified with button 2. Pressing button 2 selects the next digit (it starts flashing). If the correct combination of number has been entered or if no user password was set, you are taken to Programming mode.

• The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

• The selection is confirmed with button 1.

• The first digit of the input range for the primary current flashes.

Enter the current transformer secondary current:

• Only 1A or 5A can be set as the secondary current.

• Use button 1 to select the secondary current.

• Modify the flashing digit with button 2.

Exit Programming mode:

• Exit Programming mode by pressing button 1 and 2 at the same time.

Enter the current transformer primary current:

• Modify the flashing digit with button 2.

• Use button 1 to select the next number you wish to modify. The selected digit to be modified flashes. If the entire number flashes, the decimal point can be moved with button 2.

51

UMG 96RM-PN

Programming the voltage transformer

• Switch to programming mode as described.

The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

• Button 2 is used to switch to the Voltage transformer settings.

• The selection is confirmed with button 1.

• The first digit of the input range for the primary voltage flashes. The same as assigning the current transformer ratio from the primary to the secondary current, the ratio can be set from the primary to the secondary voltage of the voltage transformer.

Current transformer, primary

Programming mode

Unit indicator

Current transformer, secondary

Current transformer symbol

Voltage transformer, primary

Programming mode

Unit indicator

Voltage transformer, secondary

Voltage transformer symbol

52

Programming parameters

Switch to Programming mode

• Switch to programming mode as described.

The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

• Button 2 is used to switch to the Voltage transformer settings. Repeatedly pressing button 2 displays the first parameter in the parameter list.

Modify a parameter

• Confirm the select with button 1.

• The last selected address is displayed with the associated value.

• The first digit of the address flashes and can be modified with button 2. Button 1 is used to select the digit, which is then in turn modified with button 2.

Modify a value

• Once the desired address has been set, a digit of the value can be selected with button 1 and modified with button 2.

Exit Programming mode

• Exit Programming mode by pressing button 1 and 2 at the same time.

UMG 96RM-PN

Fig. Password prompt

If a password was set, it can be entered with buttons 1 and 2.

Fig. Current transformer programming mode

Buttons 1 and 2 can be used to modify the primary and secondary current (cf. page 51).

Fig. Voltage transformer programming mode

Buttons 1 and 2 can be used to modify the primary and secondary voltage (cf. page 52).

Fig. Parameter screen programming mode

Buttons 1 and 2 can be used to modify the individual parameters (cf. page 47).

53

UMG 96RM-PN

TCP/IP configuration

Each device in an Ethernet has a unique TCP/IP address, which can be assigned manually for the UMG 96RM-PN.

The 4-byte-long device address (Byte 0 to 3) is appended within the TCP/IP configuration with the subnet mask and gateway details.

If the device is integrated into a ProfiNet environment, however, the address is generally assigned by the DCP function.

Set the device's TCP/IP address (addr)

• Switch to programming mode as described.

The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

• Pressing button 2 three times takes you to the TCP/IP settings for device addressing.

• Select the desired digit using button 1. Selection is indicated by the digit flashing.

• The selected digit can be adjusted with the 2 button.

• Use button 1 to select the next digit and set it with button 2 again.

• Once Byte 0 of the TCP/IP address is set, bytes 1 to 3 of the address can be set with button 1. Then the display jumps back to Byte 0 (

none of the digits are flashing).

54

Designation

Byte identifier of the address (e.g. Byte 0)

Address value, Byte 0

Fig. TCP/IP address, Byte 1

A TCP/IP address consists of 4 bytes with the following structure:

Byte 0 Byte 1 Byte 2 Byte 3

Example: xxx.xxx.xxx.xxx

192.168.003.177

Fig. TCP/IP address

Byte 2, value 003

Fig. TCP/IP address

Byte 3, value 177

UMG 96RM-PN

Set the subnet mask (SUb):

• In programming mode, button 2 takes you to the Subnet mask settings (SUb on screen).

• Use the button 1 to select the desired digit and set it with button 2. Repeat this step for every digit in Byte

0 to 3, the same as when setting the device's TCP/

IP address.

• Once the display returns to Byte 0 (

none of the digits flashing) you can set the gateway.

Set the gateway address (GAt):

• In programming mode, button 2 takes you to the Gateway address settings (GAt on screen).

• Use the 1 and 2 buttons to set the desired gateway address in Byte 0 to 3, in the same way as the above descriptions.

Fig. Subnet mask (SUb),

Byte 0, value 255

Fig. Gateway (GAt),

Byte 0, value 192

m

Attention!

Connection of the UMG96RM-PN to the Ethernet may only be carried out after consulting the network administrator!

C

Dynamic Configuration Protocol (DCP)

This function assigns unique addresses and names to the subscribers of a

ProfiNet system, and is prioritised by the UMG 96RM-PN.

C

Changes are only applied after exiting programming mode.

55

UMG 96RM-PN

RS485 device address (addr. 000) RS485 baud rate (addr. 001)

If multiple devices are connected together via the RS485 interface, then a Master device is only able to distinguish between these devices based on their device address.

Therefore each device on a network must have a different device address. Addresses can be set in the range from

1 to 247.

A common baud rate can be set for the RS485 interfaces.

A common baud rate must be selected in the network.

Address 003 can be used to set the number of stop bits

(0=1Bit, 1=2Bits). Data Bits (8) are preset to fixed values.

C

The setting range for the device address is between 0 and 255. The values 0 and 248 to 255 are reserved and must not be used.

Setting

0

3

4

1

2

Baud rate

9.6 kbps

19.2 kbps

38.4 kbps

57.6 kbps

115.2 kbps (factory setting)

56

User password (addr. 050)

To make it harder to accidentally modify the programming data, a user password can be set. You can only switch to the following Programming menus after entering the correct user password.

No user password is set in the factory. In this case, the Password menu is skipped and you are taken immediately to the Current transformer menu.

If a user password has been set, then the Password menu appears with "000" on the screen.

The first digit of the user password flashes and can be modified with button 2. Pressing button 1 selects the next digit (it starts flashing).

Only when the right combination of numbers is entered, takes you to the Programming menu for the current transformer.

Forgot password

If you no longer remember your password, you can only delete it using the GridVis PC software.

In order to do so, connect the UMG96RM-PN to the PC with a suitable interface. More information can be found in the GridVis assistant.

UMG 96RM-PN

57

UMG 96RM-PN

Parameters

Averaging method

Mean value

Averages for the current, voltage, and power measured values are calculated over an adjustable period.

The averages are identified by a bar over the top of the measured value.

The averaging time can be selected from a list of 9 fixed averaging times.

The used exponential averaging method achieves at least 95% of the measured value after the set averaging time.

Min. and max. values

Current averaging time (addr. 040)

Power averaging time (addr. 041)

Voltage averaging time (addr. 042)

Setting

0

3

4

1

2

5

6

7

8

Averaging time/Sec.

5

10

15

30

60

300

480 (factory setting)

600

900

All measured values are measured and calculated every

10/12 periods. Min. and max. values are determined for most measured values.

The min. value is the lowest measured value measured since the last time the values were cleared. The min. value is the lowest value measured since the last time the values were cleared. All min. and max. values are compared with the associated measured values, and overwritten if the value is under the min. value or over the max. value.

The min. and max. values are stored every 5 minutes to an EEPROM without the date and time. This means that, if there is failure of the supply voltage, only the min. and max. values for the last 5 minutes can be lost.

Clearing the min. and max. values (addr.506)

If "001" is written to address 506, all min. and max. values are cleared simultaneously.

58

UMG 96RM-PN

Mains frequency (addr. 034)

To automatically determine the mains frequency, a voltage L1-N of greater than 10Veff must be applied to voltage measurement input V1.

The sampling rate for the current and voltage inputs is then calculated from the mains frequency.

Setting range: 0, 45 - 65

0 = Frequency determined automatically

The mains frequency is determined from the measured voltage.

45 - 65 = Fixed frequency

The mains frequency is preset to a fixed value.

If the measured voltage is absent, it is not possible to determine the mains frequency, which makes it impossible to calculate the sampling rate. The acknowledgeable error message "500" appears.

Voltage, current, and all other values derived from these are calculated and still displayed based on the last frequency measurement or on possible line interfaces.

However, these determined measured values are no longer subject to the specified level of accuracy.

Once the frequency can be measured again, the error message disappears automatically approx. 5 seconds after the voltage returns.

The error is not displayed if a fixed frequency is set.

59

UMG 96RM-PN

Power meters Resetting energy meters (addr. 507)

The UMG 96RM-PN has power meters for effective energy, reactive energy, and apparent energy.

The effective, apparent, and reactive energy meters can only be reset as one.

To reset the energy meters, address 507 must be described with "001".

Reading off the effective energy

Total effective energy

The effective energy shown

in this example is:

12 345 678 kWh

The effective energy shown

in this example is:

134 178 kWh

60

C

Prior to commissioning potential production dependant contents of the energy counter and min/max values have to be deleted.

C

Resetting the power meters discards the data in the device.

To avoid possible data loss, you should read out and store these measured values with the GridVis software.

UMG 96RM-PN

Harmonics Total Harmonic Distortion (THD)

Harmonics are the integer multiples of a fundamental oscillation.

On the UMG 96RM-PN the fundamental oscillation of the voltage must be in the range from 45 to 65 Hz. At this fundamental oscillation the calculated harmonics relate to the voltages and currents.

Harmonics up to 40 times the fundamental oscillation are captured.

THD is the ratio of the effective value of the harmonics to the effective value of the fundamental oscillation.

Total harmonic distortion of the current (THDI):

The harmonics for the currents are given in amps, the harmonics for the voltages in volts.

Total harmonic distortion of the voltage (THDU):

Number of harmonic

Phase L3

Current harmonic

Value

Fig. Screen for the 15th harmonic of the current in phase L3 (example).

C

Harmonics are not displayed in the factory default setting.

Phase L3

Voltage

Value

Fig. Screen for the Total harmonic distortion (THD) of the voltage from phase L3 (example).

61

UMG 96RM-PN

Measured value rotation Rotation time (addr. 039)

All measured values are calculated every 10/12 periods, and are available once a second in the measured value screens. Two methods are available for bringing up the measured value screens:

Setting range: 0 to 60 seconds

If 0 seconds is set, then there is no rotation between the measured value screens selected for measured value rotation.

The rotation time applies to all screen rotation profiles.

• The automatically rotating display of selected measured value screens, referred to here as

"measured value rotation".

• Choosing a measured value screen from a selected screen profile, using buttons 1 and 2.

Screen rotation profile (addr. 038)

Setting range: 0 to 3

0 - Screen rotation profile 1, preassigned.

1 - Screen rotation profile 2, preassigned.

2 - Screen rotation profile 3, preassigned.

3 - Screen rotation profile, customer-specific.

Both methods are available simultaneously. Measured value rotation is active when at least one measured value screen is programmed with a rotation time greater than

0 seconds.

Pressing a button allows you to scroll through the measured value screens for the selected screen profile. If no button is pressed for around 60 seconds, the device switches to measured value rotation, and the measured values from the selected screen rotation profile programmed measured value screens are displayed in succession.

Measured value screens

After the power is restored, the UMG 96RM-PN displays the first measured value table from the current screen profile. So that the selection of measured values to be displayed remains clear, at the factory only one part of the available measured values is pre-programmed to be called up in the measured value screen. If you desire to display other measured values on the screen of the UMG

96RM-PN, select a different screen profile.

62

UMG 96RM-PN

Screen profile (addr. 037)

Setting range: 0 to 3

0 - Screen profile 1, fixed preassigned value.

1 - Screen profile 2, fixed preassigned value.

2 - Screen profile 3, fixed preassigned value.

3 - Screen profile, customer-specific.

C

The customer-specific profiles (screen rotation profile and screen profile) can only be programmed via the GridVis software.

C

Profile setting

The GridVis software provides a clear overview of the profiles (screen rotation profile and screen profile). In the software the Device configuration can be used to configure the profiles; customer-specific screen profiles can also be programmed.

A connection between the UMG 96RM-PN and the PC is required to use the GridVis software.

Fig. Profile setting screen in the GridVis software.

63

UMG 96RM-PN

Direction of the rotating field LCD contrast (addr. 035)

The direction of the rotating field of the voltages and the frequency of phase L1 are displayed in a screen.

The direction of the rotating field specifies the phase sequence in three-phase power grids. A “right-hand rotation field” usually exists.

In the UMG 96RM-PN, the phase sequence is tested and indicated on the voltage measurement inputs. A movement of the character string in a clockwise direction means there is a “right-hand rotation field” and an anticlockwise movement indicates a “left-hand rotation field”.

The direction of the rotating field is only determined when the measuring and supply voltage inputs are fully connected. If a phase is missing or if two identical phases are connected, the direction of the rotating field is not established and the character string is stationary on the screen.

The preferred direction for observing the LCD display is from below. The contrast of the LCD display can be adjusted by the user. The contrast can be set in the range from 0 to 9 in steps of 1.

0 = Characters very bright

9 = Characters very dark

Factory default setting: 5

Backlight

The backlight enables good legibility of the LCD display under poor visual conditions. The brightness can be controlled by the user in the range from 0 to 9 in steps of 1.

The UMG 96RM-PN has two different types of backlight:

- Operating lighting

- Standby lighting

Fig. Screen for the mains frequency (50.0) and the direction of

Fig. Direction of the rotating field not detectable.

UMG 96RM-PN

Operating lighting (addr. 036):

The operating lighting is activated by the push of a button or upon restart.

Standby lighting (addr. 747)

This type of backlight is activated after a customisable period of time (addr. 746). If there are no button presses during this period, the device switches to standby lighting.

If buttons 1 - 3 are pressed, the device switches to operating lighting and the defined period begins again from scratch.

C

DCP "Identify Station" signal of the PLC:

If the PLC sends control signals for device identification to the device, the backlight switches between maximum and minimum brightness (causing the display lighting to "flash"). To achieve this there is usually a "Flash" button in the PLC.

If the brightness values are the same for both types of lighting then no change is discernible between the backlight and standby lighting.

Addr. Description

036 Brightness for operating lighting

746 After how long to switch to standby lighting

747 Brightness for standby lighting

Setting range

0 to 9

60 to 9999 secs

0 to 9

Default

6

900 secs

0

0 = Minimum brightness, 9 = Maximum brightness

65

UMG 96RM-PN

Time logging

Operating hours counter

The UMG 96RM-PN logs the operating hours and the total running time of each comparator, whereby the time

• for the operating hours is measured with a resolution of 0.1 hrs and displayed in hours or

• the total running time of the comparators is displayed in seconds (when 999,999 secs is reached, the number is displayed in hours).

The operating hours counter measures the time in which the UMG 96RM-PN captures and displays measured values.

The time for the operating hours is measured with a resolution of 0.1 hrs and displayed in hours.

The operating hours counter cannot be reset.

Total running time, comparator

For a query using the measured value screens, the times are indicated with the numbers 1 to 6:

None = Operating hours counter

1 = Total running time, Comparator 1A

2 = Total running time, Comparator 2A

3 = Total running time, Comparator 1B

4 = Total running time, Comparator 2B

5 = Total running time, Comparator 1C

6 = Total running time, Comparator 2C

A maximum of 99,999.9 hrs (=11.4 years) can be shown on the measured value screen.

The total running time of a comparator is the sum of all times for which there was a threshold value violation in the comparator result.

The total running times of the comparators can only be reset via the GridVis software. The reset is performed for all total running times.

Fig. Measured value screen

Operating hours counter

The UMG 96RM-PN shows the number 140.8 hrs in the operating hours counter. This corresponds to 140 hours and 80 industry minutes. 100 industry minutes correspond to 60 minutes. In this example, the 80 industry minutes correspond to 48 minutes.

66

Serial number (addr. 754)

The serial number displayed by the UMG 96RM-PN has six digits and is a part of the serial number displayed on the rating plate.

The serial number cannot be modified.

Serial number indicator

Serial number as stated on the rating plate:

XX00-0000

Software release (addr. 750)

The software for the UMG 96RM-PN is continuously improved and expanded. The software version in the device is identified by a three-digit number, the software release. The software release cannot be modified by the user.

UMG 96RM-PN

67

UMG 96RM-PN

Applying the measuring-circuit voltage

Commissioning

Connecting the supply voltage

• The supply voltage level for the UMG 96RM-PN is specified on the rating plate.

• After applying the supply voltage, the UMG 96RM switches to the first measured value screen.

• If no display appears, check whether the power supply voltage is within the rated voltage range.

Connecting the measured voltage

• Measurement of voltages in networks with over

300VAC to earth must be connected via voltage transformers.

• After connecting the measured voltages, the measured values displayed by the UMG 96RM-PN for the L-N and L-L voltages must correspond to those at the voltage measurement input.

The UMG 96RM-PN is designed for the connection of ..

/1A and .. /5A current transformers.

Only AC currents can be measured via the current measurement inputs - DC currents cannot.

Short circuit all current transformer outputs except for one. Compare the currents displayed by the UMG 96RM with the applied current.

Bearing in mind the current transformer conversion ratio, the current displayed by the UMG 96RM-PN must correspond with the input current.

The UMG 96RM-PN must display approx. zero amperes in the short circuited current measurement inputs.

The current transformer ratio is factory-set to 5/5A and must be adapted to the current transformer used if necessary. m

Attention!

If the supply voltage does not correspond to the voltage indicated on the rating plate, this may lead to malfunctions and severe damage to the device.

m

Attention!

Voltages and currents that are outside the permissible measurement range can cause personal injury and lead to the destruction of the device.

m

Attention!

The UMG 96RM is not suitable for measuring DC voltages.

68

UMG 96RM-PN

Direction of the rotating field Applying the residual current

Check the direction of the rotating field voltage in the measured value display of the UMG 96RM.

A “right-hand” rotation field usually exists.

Connect residual current transformer only to the I5 and

I6 inputs with a rated current of 30mA! Both residual current inputs can measure AC currents, pulsing direct currents and DC currents.

Checking the phase assignment

The phase conductor assignment to the current transformer is correct if a current transformer is short-circuited on the secondary side and the current displayed by the UMG

96RM-PN drops to 0A in the associated phase.

Checking the power measurement

Bearing in mind the current transformer ratio, the residual current displayed by the UMG96RM-PN must correspond with the input current.

The current transformer ratio is factory-set to 1/1A and must be adapted to the residual current transformer used if necessary.

Short-circuit all current transformer outputs except for one and check the displayed power outputs.

The UMG 96RM-PN may only display one power output in the phase with a non-short-circuited current transformer input. If this is not the case, check the connection of the measured voltage and the measuring-circuit current.

If the effective power amount is correct but the sign of the power output is negative, this could have two possible causes:

• S1(k) and S2(l) are reversed at the current transformer.

• Effective energy is being supplied back into the network.

C

The UMG96RM-PN requires the mains frequency for residual current monitoring. For this purpose, the measured voltage should be applied or a fixed frequency should be set.

C

It is not necessary to configure a connection schematic for residual current inputs I5 and I6.

69

UMG 96RM-PN

Failure monitoring (RCM) for I5, I6

The UMG96RM-PN enables continuous monitoring of the connection to the residual current transformer on inputs I5 and I6.

m

The monitoring of the connection to the residual current transformer is only available in the AC mode!

Residual current transformers of Type A must be used for transformer monitoring!

Modbus addr. Value / Function

553 (I5)

554 (I6)

0 = Transformer monitoring, I5 and I6 deactivated

1 = Transformer monitoring, I5 and I6 activated

C

We recommend configuring the residual current measurement settings in GridVis.

If there is an interruption in the connection to the current transformer, this state is recorded in certain registers or indicated in the GridVis software:

Modbus addr. Value / Function

10014 (I5)

10015 (I6)

0 = Connection of the residual current transformer to I5 and I6 error-free

1 = Error in the current transformer connection to I5 and I6

70

UMG 96RM-PN

Checking the measurement Checking the sum powers

Once all voltage and current measurement inputs are properly connected, the signal phase and sum powers are also calculated and displayed properly.

Checking the single phase powers

If a current transformer is assigned to the wrong phase conductor, the associated power will also be measured and displayed incorrectly.

The assignment of phase conductor to current transformer on the UMG 96RM-PN is correct when there is no voltage between the phase conductor and the associated current transformer (primary).

To ensure that a phase conductor on the voltage measurement input is assigned to the right current transformer, you can short-circuit the current transformer in question on the secondary side. The apparent power displayed by the UMG 96RM-PN must be zero in this phase.

If all voltages, currents, and powers for the phase conductor in question are displayed properly, then the sum powers measured by the UMG 96RM must also be correct. For confirmation, the sum powers measured by the UMG 96RM should be compared with the effective and reactive power meter located in the supply.

If the apparent power is displayed correctly but the effective power has a "-" sign, the current transformer terminals are reversed or power is being supplied to the power company.

71

UMG 96RM-PN

RS485 interface

The MODBUS RTU protocol with CRC check on the RS485 interface can be used to access the data from the parameter and the measured value lists.

Address range:

Factory default setting:

1 to 247

1

C

C

The device address is factory set to 1 and the baud rate to 115.2 kbps.

Modbus functions (slave)

04 Read input registers

06 Preset single register

16 (10Hex) Preset multiple registers

23 (17Hex) Read/write 4X registers

The sequence of bytes is high before low byte (Motorola format).

Transmission parameters:

Data bits: 8

Parity: None

Stop bits (UMG 96RM): 2

External stop bits: 1 or 2

Number format: short 16 bit (-2

15 to 2

15

-1) float 32 bit (IEEE 754)

72

Broadcast (address 0) is not supported by the device.

The message length must not exceed

256 bytes.

UMG 96RM-PN

Example: Reading the L1-N voltage

The L1-N voltage is saved in the measured value list at address 19000. The L1-N voltage is available in the FLOAT format.

Address = 01 is approved as the UMG 96RM-PN device address.

The Query Message appears as follows:

The "Response" of the UMG96 RM-PN can appear as follows:

Name Hex Note

Device address 01

Function 03

Start addr. Hi

Start addr. Lo

Ind. Value Hi

Ind. Value Lo

Error check

4A

38

00

02

-

UMG 96RM, address = 1

"Read holding reg."

19000dez = 4A38hex

2dez = 0002hex

Name Hex Note

Device address 01

Function

Byte meter

03

06

Data

Data

Error check (CRC) -

00

E6

UMG 96RM, address = 1

00hex = 00dez

E6hex = 230dez

The L1-N voltage read by address 19000 is 230V.

73

UMG 96RM-PN

Digital outputs

The UMG 96RM-PN has two digital outputs in Group 1.

Another three digital outputs can be set in Group 2.

You can optionally assign different functions to the digital outputs.

The settings of the functions in the confi guration menu must be made using the GridVis software.

24V

DC

=

-

+

K1 K2

=

+

-

S1 S2 S3

=

-

+

K3 K4 K5

13 14 15

Group 1

28 29 30 31

Group 2

Digital inputs/outputs

74

Fig.: Digital outputs of Group 1 and digital inputs/outputs of Group 2

Fig.: GridVis software, confi guration menu

UMG 96RM-PN

Digital output status indicators

The status of the switch outputs of Group 1 is displayed on the display of the UMG 96RM-PN by circle symbols.

Statuses of the digital inputs of Group 2 - as described in the chapter "LED status bar" - are displayed by the rearwards-facing LEDs.

C

Since the display is only updated once a second, status changes in the outputs which are more rapid than this cannot be displayed.

Statuses of the digital outputs of Group 1

Group 1

Status of Digital output 1

Status of Digital output 2

A current of <1mA can flow.

Digital output 1: addr. 608 = 0

Digital output 2: addr. 609 = 0

A current of up to 50mA can flow.

Digital output 1: addr. 608 = 1

Digital output 2: addr. 609 = 1

75

UMG 96RM-PN

Functions of the digital outputs of Group 1

You can optionally assign the following functions to the two digital outputs of Group 1:

Digital output 1

Addr. 200 = 0

Addr. 200 = 1

Addr. 200 = 2

Addr. 200 = 5

Result of Comparator group 1

Pulse output

Value from external source Modbus

Value from external source Profi

Digital output 2

Addr. 202 = 0

Addr. 202 = 1

Addr. 202 = 2

Addr. 202 = 2

Result of Comparator group 2

Pulse output

Value from external source Modbus

Value from external source ProfiNet

76

Comparator group 1

Comparator A

Comparator B

Comparator C

Result

Addr. 616

0/1

Status of

Digital output 1

Addr. 608 =0

Selection of source

Pulse output

Addr. 100 = Measured value address

Addr. 106 = Minimum pulse length

Addr. 102 = Pulse value

External value

Addr. 602 = 0 (Off), >0 (On)

RS485

0/1

Addr. 200 =0

Addr. 200 =1

Addr. 200 =2

Addr. 200 =5

0/1

0/1

0/1

External value

Addr. 527 = 0 (Off), >0 (On)

Ethernet / ProfiNet

Inverter

Display

K1

UMG 96RM-PN

Addr. 201=0 (not inverted)

Addr. 201=1 (inverted)

K2

0/1

Digital output 1

Fig.: Overview block diagram for Digital output 1

External source External source

13

14

Modbus ProfiNet (PLC)

UMG 96RM-PN

Pulse output (Group 1)

The digital outputs of Group 1 can be used for the output of pulses for the computation of power consumption.

For this purpose, a pulse of defined length is applied on the output after reaching a certain, adjustable amount of power.

You need to make various adjustments in the configuration menu using the GridVis software to use a digital output as a pulse out.

• Digital output

• Selection of source

• Measured value selection

• Pulse length

• Pulse value

Fig.: GridVis software, configuration menu

C

The digital outputs of Group 2 cannot be configured as pulse outputs. Use as switch outputs is possible.

77

UMG 96RM-PN

UMG 96RM-PN

Pulse

Addr. 100 = 874 (address of Psum3)

Addr. 106 = 5 (50 ms)

Addr. 102 = 1000 (Wh/pulse)

0/1

Selection of source

Addr. 200 =1

Status of

Digital output 1

Addr. 608 =0

0/1

Display

K1 K2

Inverter

Addr. 201=0 (not inverted)

Addr. 201=1 (inverted)

0/1

Digital output 1

13

14

Fig.: Block diagram; example of Digital output 1 as a pulse output.

Measured value selection (addr. 100, 101): Source selection (addr. 200, 202):

Enter the address here for the power value which should be output as the effective pulse. See Table 2.

Enter here which source the measured value will supply that should be output on the digital output.

Selectable sources:

• Comparator group

• Pulse

• External source

78

UMG 96RM-PN

Pulse length (addr. 106):

The pulse length applies to both pulse outputs and is set using the GridVis software.

The values in the table are based on the minimum pulse length and the minimum pulse interval for the maximum number of pulses per hour.

The typical pulse length of S0 pulse is 30ms.

Pulse interval:

The pulse interval is at least as large as the selected pulse length.

The pulse interval depends on the measured power, for example, and can take hours or days.

Pulse length

10ms .. 10s

Pulse interval

>10ms

Pulse length Pulse interval

10 ms 10 ms

30 ms

50 ms

30 ms

50 ms

Max. pulse/h

180 000 pulses/h

60 000 pulses/h

36 000 pulses/h

100 ms

500 ms

100 ms

500 ms

18 000 pulses/h

3600 pulses/h

1 s

10 s

1 s

10 s

1800 pulses/h

180 pulses/h

Examples of the maximum possible number of pulses per hour.

C

Pulse interval

The pulse interval is proportional to the power output within the selected settings.

C

Measured value selection

When programming with GridVis you have a selection of work values which are derived from the power output values.

79

UMG 96RM-PN

Pulse value (addr. 102, 104)

The pulse value is used to indicate how much power (Wh or varh) should correspond to a pulse.

The pulse value is determined by the maximum connected load and the maximum number of pulses per hour.

If you check the pulse value with a positive sign, the pulses will only be emitted when the measured value has a positive sign.

If you check the pulse value with a negative sign, the pulses will only be produced when the measured value has a negative sign.

Pulse value = max. connected load max. number of pulses/h

[Pulse/Wh]

C

Since the effective energy meter operates with a backstop, pulses will only be generated when drawing electricity.

C

Since the reactive energy meter operates with a backstop, pulses will only be generated with inductive load applied.

80

Determine the pulse value

Set the pulse length

Set the pulse length in accordance with the requirements of the connected pulse receiver.

At a pulse length of 30 ms, for example, the UMG 96RM generates a maximum number of

60,000 pulses (see Table "maximum number of pulses" per hour.

Determining the maximum connected load

Example:

Current transformer

Voltage L-N

= 150/5 A

= Max. 300 V

Power per phase = 150 A x 300 V

= 45 kW

Power at 3 phases = 45kW x 3

Maximum connected load = 135 kW

Calculating the pulse value

Pulse value = max. connected load max. number of pulses/h

[Pulse/Wh]

Pulse value

Pulse value

Pulse value

= 135kW / 60,000 Imp/h

= 0.00225 kWh / pulse

= 2.25 Wh / pulses

UMG 96RM-PN

UMG 96RM-PN

Switch and pulse outputs

External supply voltage

230V AC

+

24V DC

-

13

+24V=

14

Data logger

1.5k

15

Fig.: Connection example for the circuit as pulse output.

C

When using the digital outputs as pulse outputs, the auxiliary voltage (DC) must have a max. residual ripple of 5%.

81

UMG 96RM-PN

Comparators and threshold value monitoring

Two comparator groups (1 - 2), each with 3 comparators

(A - C) are available to monitor threshold values.

The results of Comparators A to C can be combined with the AND/OR operators.

The combination result of Comparator group 1 can be assigned to Digital output 1 and the combination result of Comparator group 2 can be assigned to Digital output

2.

Additionally, the function "Flash display" can also be assigned to each comparator group, whereby the backlight of the screen alternates between maximum and minimum brightness when a comparator output is active.

C

The comparator or combination results

cannot be assigned to the digital outputs of

Group 2!

Fig.: GridVis software, configuration menu

Digital input values of group 2 and analogue input values ( residual current and temperature monitoring ) as well as current monitoring input I4 cannot be used by comparators.

C

We recommend configuring the comparator and threshold value monitoring settings in

GridVis.

82

Comparator group 1

Comparator A

Measured value (addr.110)

Threshold value (addr. 108)

Min. switch-on time (addr. 111)

Lead time (addr. 112)

Operator ">=", "<" (addr.113)

Comparator B

Measured value (addr.116)

Threshold value (addr. 114)

Min. switch-on time (addr. 117)

Lead time (addr. 118)

Operator ">=", "<" (addr.119)

Comparator C

Measured value (addr.122)

Threshold value (addr. 120)

Min. switch-on time (addr. 123)

Lead time (addr. 124)

Operator ">=", "<" (addr.125)

Comparator result (addr.610) Comparator result (addr.611) Comparator result (addr.612)

Total running time

(addr.5898)

Total running time

(addr.5900)

Total running time

(addr.5902)

Combine results of Comparators A, B and C

Combine the results of Comparators A, B and C with the AND/OR operators (addr. 107).

Combination result (addr.616)

Fig.: Comparator principle of Comparator group 1

UMG 96RM-PN

83

UMG 96RM-PN

Example: current monitoring on the N

If the current on the N is higher than 100 A for 60 seconds, then Digital output 1 should be active for at least 2 minutes.

The following programming must be undertaken:

The exceedance should be present at least for the lead time of 60 seconds.

Addr. 112 = 60 seconds

1. Comparator group 1

Select Comparator group 1 for threshold value monitoring.

The comparator group only has an effect on Digital output 1.

Since only one threshold value is being monitored, select

Comparator A and program it as follows:

The operator for the comparison between measured value and threshold value.

Addr. 113 = 0 (meaning >=)

2. Selection of source

Select Comparator group 1 as the source.

Addr. 200 = 0 (Comparator group 1)

The address of the measured value of Comparator A to be monitored:

Addr. 110 = 866 (address of the current on the N)

3. Inverter

The result from Comparator group 1 can also be inverted here. However, we will not do so here.

Addr. 201 = 0 (not inverted)

The measured values for Comparators B and C are 0.

Addr. 116 = 0 (the comparator is inactive)

Addr. 122 = 0 (the comparator is inactive)

The threshold value to be observed.

Addr. 108 = 100 (100 A)

4. Combine the comparators

Comparators B and C were not set and equal zero.

Using the OR operator on Comparators A, B and C, the result of Comparator A is output as the comparator result.

Addr. 107 = 0 (combine with the OR operator)

Digital output 1 should remain active for a min. switch-on time of 2 minutes if the threshold value is exceeded.

Addr. 111 = 120 seconds

Result

If the current on the N is higher than 100 A for over 60 seconds, then Digital output 1 is active for at least 2 minutes.

Digital output 1 becomes active. A current can flow.

84

UMG 96RM-PN

Comparator group 1

Comparator A

Comparator B

Comparator C

Result

Addr. 616

0/1

UMG 96RM-PN

Selection of source

Addr. 200 =0

Status of

Digital output 1

Addr. 608 =0

0/1

Display

K1 K2

Inverter

Addr. 201=0 (not inverted)

Addr. 201=1 (inverted)

0/1

Digital output 1

13

14

Block diagram: Use of Digital output 1 for threshold value monitoring.

C

We recommend configuring threshold value monitoring settings in GridVis.

C

On the UMG 96RM you can only enter

3-digit parameter addresses.

Using GridVis you can enter 4-digit parameter addresses.

85

UMG 96RM-PN

• Measured value (addr. 110,116,122,129,135,141)

The measured value contains the address of the measured value to be monitored.

Measured value = 0 the comparator is inactive.

• Threshold value (addr. 108,114,120,127,133,139)

The threshold value is where you write the value to be compared with the measured value.

• Comparator result (addr. 610,611,612,613,614,615)

The result of the comparison between the measured value and threshold value is in the comparator result.

In this context:

0 = There is no threshold value violation.

1 = There is a threshold value violation.

• Total running time

The sum of all times for which there was a threshold value violation in the comparator result.

• Min. switch-on time (addr. 111,117,123,130,136,142)

The logic operation result (e.g. Addr. 610) is retained for the duration of the min. switch-on time.

Setting range: 1 to 32,000 seconds

• Combine (addr. 107,126)

Combine the results of Comparators A, B, and C with the AND/OR operators.

• Lead time (addr. 112,118,124,131,137,143)

Only if there is a threshold value violation for at least the duration of the lead time is the comparator result modified.

The lead time can be assigned to times in the range from 1 to 32,000 seconds.

• Total combination result (addr. 616,617)

The combined comparator results of Comparators A,

B, and C are in the total combination result.

• Operator (addr. 113,119,125,132,138,144)

Two operators are available for comparing the measured value and the threshold value.

Operator = 0 means greater than or equal to (>=)

Operator = 1 means less than (<)

86

UMG 96RM-PN

Comparator running times

Comparator running times are time counters, which are added together at a set comparator output. i.e. if the condition of the comparator is fulfilled and the lead time has elapsed, the counter is increased by the corresponding amount of time - this does not take account of the min. switch-on time!

Threshold value

Threshold value violation (e.g. exceedance)

Comparator with set limit value violation

• The set limit value is compared to the measured value.

• If the limit value violation occurs for at least the duration of the lead time, the comparator result is changed.

• The result is retained for at least the duration of the min. switch-on time and for no longer than the duration of the limit value violation. If there is no longer a limit value violation and the min. switch-on time has elapsed, the result is reset.

Lead time

Min. switch-on time

Comparator result

Comparator running time

2 seconds

6 seconds

Measured value

87

UMG 96RM-PN

Service and maintenance

Service

The device underwent various safety checks before delivery and is marked with a seal. If a device is open, then the safety checks must be repeated. Warranty claims will only be accepted if the device is unopened.

Should questions arise, which are not described in this manual, please contact the manufacturer directly.

We will need the following information from you to answer any questions:

Repair and calibration

Repair work and calibration can be carried out by the manufacturer only.

Front film

- Device name (see rating plate),

- Serial number (see rating plate),

- Software release (see measured value display),

- Measured voltage and power supply voltage,

- Precise description of the error.

The front film can be cleaned with a soft cloth and standard household cleaning agent. Do not use acids and products containing acid for cleaning.

Disposal

Device calibration

The devices are calibrated by the manufacturer at the factory - it is not necessary to recalibrate the device providing that the environmental conditions are complied with.

The UMG 96RM can be reused or recycled as electronic scrap in accordance with the legal provisions.

The permanently installed lithium battery must be disposed of separately.

Calibration intervals

We recommend having the device recalibrated by the manufacturer or an accredited laboratory every

5 years approximately.

88

Firmware update

If the device is connected to a computer, then the device firmware can be updated via the GridVis software.

The new firmware is transferred by selecting a suitable update menu (Tools/Upgrade Devices menu) and the device.

Fig. GridVis firmware update assistant

UMG 96RM-PN

89

UMG 96RM-PN

Error / warning messages

Warnings

The UMG 96RM-PN can show four different error messages on the display:

• Warnings

• Serious errors

• Measurement range exceeded

Error messages for warnings and serious errors are depicted with the symbol "EEE" followed by an error number.

Warnings are less serious errors and must be acknowledged with button 1 or 2. The capture and display of measured values continues. This error is displayed again each time the power is switched on.

Fig. Warning message with number 500 (mains frequency)

The three-digit error number is composed of the error description and - if this can be established by the UMG

96RM - one or more causes for the error.

Fig. Error message

Symbol for an error message

Error number

Error

EEE

500

Error description

The mains frequency could not be established.

Possible causes:

The voltage on L1 is too low.

The mains frequency is not in the range from 45 to 65 Hz.

Remedy:

Check the mains frequency.

Select fixed frequency on the device.

90

UMG 96RM-PN

Serious errors

When a serious error occurs, the device must be sent in to the manufacturer for inspection.

Example error message 911:

Error

EEE

910

This error number is composed of serious error 910 and the internal error cause 0x01.

Error description

Error when reading the calibration.

Internal error causes:

In some cases, the UMG 96RM-PN can determine the cause for a serious internal error and report it using the following error codes.

In this example an error occurred when reading the calibration from the EEPROM. The device must be sent in to the manufacturer for inspection.

Error

0x01

0x02

0x04

0x08

Error description

EEPROM not responding

Address below range

Checksum error

Error in the internal I2C bus

91

UMG 96RM-PN

Measurement range exceeded

If the measurement range is exceeded, it is displayed as long as this persists and cannot be acknowledged.

The measurement range is exceeded if at least one of the voltage or current measurement inputs lies outside their specified measurement range.

The Up arrow is used to highlight in which phase the measurement range was exceeded.

The corresponding error message for current circuit I4 is as shown in the figure opposite.

The "V" and "A" symbols indicate whether the measurement range has been exceeded in the current or voltage circuit.

Examples

A = Current circuit

V = Voltage circuit

Indication of the phase (L1/L2/

L3) in which the measurement range was exceeded. An exceedance in current circuit

I4 is shown as in the figure opposite.

Threshold values for exceeding the measurement range:

I = 7 Aeff

U

L-N

= 300 V rms

92

A = Current circuit

Fig.: Indication of exceeding the measurement range in the current circuit of the 2nd phase (I2).

V = Voltage circuit

Fig.: Indication of exceeding the measurement range in voltage circuit L3

Fig.: Indication of exceeding the measurement range in current circuit I4

"Measurement range exceeded" parameter

Further description of the error is encoded in the parameter "measurement range exceeded" (addr.

600), stored in the following format:

F F F F F F F F

Phase 1: 1 1

Phase 2:

Phase 3:

Phase 4 (I4):

2

4

8

2

4

8

Example: Error in Phase 2 in the current circuit:

0x

F2FFFFFF

Example: Error in Phase 3 in the voltage circuit U

L-N

:

0x

FFF4FFFF

UMG 96RM-PN

93

UMG 96RM-PN

Procedure in the event of faults

Possible fault

No display

No current display

Cause

External fuse for the power supply voltage has tripped.

Measured voltage is not connected.

Measurement current is not connected.

Remedy

Replace fuse.

Connect the measured voltage.

Connect measuring-circuit current.

Current displayed is too high or too low.

Current measurement in the wrong phase.

Check connection and correct if necessary.

Current transformer factor is incorrectly programmed.

The current peak value at the measurement input was exceeded by harmonic components.

The current at the measurement input fell short of.

Measurement in the wrong phase.

Read out and program the CT ratio at the current transformer.

Install current transformer with a larger CT ratio.

Install current transformer with a smaller current transformer ratio.

Check connection and correct if necessary.

Voltage displayed is too high or too low.

Voltage displayed is too low.

Voltage transformer incorrectly programmed.

Measurement range exceeded.

Read out and program the voltage transformer ratio at the voltage transformer.

Use voltage transformers.

Phase shift ind/cap.

Effective power, consumption/supply reversed.

The peak voltage value at the measurement input has been exceeded by the harmonics.

A current circuit is assigned to the wrong voltage circuit.

At least one current transformer connection is mixed up/reversed.

A current circuit is assigned to the wrong voltage circuit.

Attention! Ensure the measurement inputs are not overloaded.

Check connection and correct if necessary.

Check connection and correct if necessary.

Check connection and correct if necessary.

94

UMG 96RM-PN

Possible fault

Effective power too high or too low.

Cause

The programmed CT ratio is incorrect.

An output is not responding.

"EEE" on the display

No connection with the device.

Device still does not work despite the above measures.

The current circuit is assigned to the wrong voltage circuit.

The programmed voltage transformer ratio is incorrect.

The output was incorrectly programmed.

The output was incorrectly connected.

See error messages.

RS485

- Device address is incorrect

- Different bus speeds (baud rate)

- Wrong protocol

- Termination missing

Ethernet / ProfiNet

- IP Device address is incorrect.

Device defective.

Remedy

Read out and program the CT ratio at the current transformer

Check connection and correct if necessary.

Read out and program the voltage transformer ratio at the voltage transformer.

Check the settings and correct if necessary.

Check connection and correct if necessary.

- Adjust the device address

- Adjust speed (baud rate)

- Select the correct protocol

- Terminate bus with termination resistor

- Adjust IP device address.

Send the device to the manufacturer for inspection and testing along with an accurate fault description.

95

UMG 96RM-PN

Technical data

General

Net weight (with attached connectors)

Package weight (incl. accessories)

Service life of backlight

Approx. 380g

Approx. 780g

40,000 hrs (backlighting is reduced by around 50% over this period)

Transport and storage

The following information applies to devices which are transported or stored in the original packaging.

Free fall 1m

Temperature

Relative humidity

K55 (-25°C to +70°C)

0 to 90% RH

Ambient conditions during operation

The UMG 96RM is intended for weather-protected, stationary use.

Protection class II in acc. with IEC 60536 (VDE 0106, Part 1).

Rated temperature range

Relative humidity

Operating altitude

Pollution degree

Mounting position

Ventilation

Protection against ingress of solid foreign bodies and water

- Front

- Rear

- Front with seal

K55 (-10°C to +55°C)

0 to 75% RH

0 to 2000m above sea level

2

Upright

Forced ventilation is not required.

IP40 in acc. with EN60529

IP20 in acc. with EN60529

IP54 in acc. with EN60529

96

UMG 96RM-PN

Power supply voltage

Option 230V

Option 24V

Nominal range

Power consumption

Nominal range

90V - 277V (50/60Hz) or DC 90V - 250V; 300V CATIII max. 8.5VA / 5W

24V - 90V AC / DC; 150V CATIII

Operating range

Internal fuse, not replaceable

Power consumption

+-10% of nominal range

Recommended overcurrent protection device for line protection

(certified under UL) max. 7VA / 5W

Typ T1A / 250V/277V according IEC 60127

Option 230V: 6 - 16A

Option 24V: 1 - 6A

(Char. B)

Recommendation for a maximum number of devices on a circuit breaker:

Option 230V : Circuit breaker B6A: max. 4 devices / Circuit breaker B16A: max. 11 devices

Option 24V : Circuit breaker B6A: max. 3 devices / Circuit breaker B16A: max. 9 devices

97

UMG 96RM-PN

Voltage measurement

Three-phase 4-conductor systems with rated voltages up to

Three-phase 3-conductor systems, unearthed, with rated voltages up to

Overvoltage category

Measurement surge voltage

Measurement range L-N

Measurement range L-L

Resolution

Crest factor

Impedance

Power consumption

Sampling rate

Frequency range of the fundamental oscillation

- Resolution

277V/480V (+-10%)

IT 480V (+-10%)

300V CAT III

4kV

0

1)

to 300Vrms

(max. overvoltage 520Vrms )

0 1) to 520Vrms (max. overvoltage 900Vrms)

0.01V

2.45 (related to the measurement range)

4MOhm/phase approx. 0.1VA

21.33 kHz (50Hz), 25.6 kHz (60Hz) for each measurement channel

45Hz to 65Hz

0.01Hz

1)

The UMG 96RM-PN can only detect measurements when a voltage L1-N greater than 20V eff (4-wire measurement) at voltage input V1 or a voltage L1-L2 greater than 34V eff (3-wire measurement) is applied.

98

Current measurement I1 - I4

Rated current

Measurement range

Crest factor

Resolution

Overvoltage category

Measurement surge voltage

Power consumption

Overload for 1 sec.

Sampling rate

Residual current monitoring I5 / I6

Rated current

Limiting current

Triggering current

Resolution

Crest factor

Burden

Overload for 1 sec.

Sustained overload

Overload for 20 ms

Residual current monitoring

UMG 96RM-PN

5A

0 to 6Arms

1,98

0.1mA (display 0.01A)

300V CAT II

2kV

Approx. 0.2 VA (Ri=5mOhm)

120A (sinusoidal)

21.33 kHz (50Hz), 25.6 kHz (60Hz) for each measurement channel

30mArms

40mArms

50

µA

1 µA

1.414 (related to 40mA)

4 Ohm

5A

1A

50A i.a.w. IEC/TR 60755 (2008-01), type A

Type B

99

UMG 96RM-PN

Thermistor input

2 optional inputs

Update time

Connectable sensors

Total burden (sensor + cable)

Sensor type

KTY83

KTY84

PT100

PT1000

Serial interface

RS485 to Modbus RTU/Slave

Stripping length

Ethernet / ProfiNet interface

Connection

Functions

Protocols

Temperature range

-55°C to +175°C

-40°C to +300°C

-99°C to +500°C

-99°C to +500°C

Conformance Class (CC)

ProfiNet version

ProfiNet profiles

100

1 second

PT100, PT1000, KTY83, KTY84

Max. 4 kOhm

Resistor range

500Ohm to 2.6kOhm

350Ohm to 2.6kOhm

60Ohm to 180Ohm

600Ohm to 1.8kOhm

Measurement uncertainty

± 1.5% rng

± 1.5% rng

± 1.5% rng

± 1.5% rng

9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps

7mm

RJ45

Embedded webserver (HTTP)

TCP/IP, Modbus/TCP (Port 502),

ICMP (Ping), NTP, Modbus RTU over Ethernet (Port 8000), FTP

ProfiNet (SNMP, DCP, MRP, LLDP, DCOM, RPC ...)

B — Switch class C (IRT)

2.2

PROFIenergy V1.1, Entity Class 2

Digital outputs

2 and 3 optional additional digital outputs, semiconductor relay, not short-circuit proof

Switching voltage Max. 33V AC, 60V DC

Switching current

Response time

Pulse output (energy pulses) max. 50mAeff AC/DC

10/12 periods + 10ms *

Max. 50Hz

* Response time, e.g. at 50 Hz: 200ms + 10ms = 210 ms

Digital inputs

3 optional additional digital outputs, semiconductor relay, not short-circuit proof

Maximum counter frequency 20Hz

Input signal present

Input signal not present

18V to 28V DC (typical 4mA)

0 to 5V DC, current less than 0.5mA

Terminal connection capacity (supply voltage)

Connectable conductors. Only one conductor can be connected per terminal!

Single core, multi-core, fine-stranded 0.2 - 2.5mm

2

, AWG 26 - 12

Terminal pins, core end sheath

Tightening torque

Stripping length

0.2 - 2.5mm

0.4 - 0.5Nm

7mm

2

UMG 96RM-PN

101

UMG 96RM-PN

Terminal connection capacity (voltage and current measurement)

Connectable conductors. Only one conductor can be connected per terminal!

Current

Single core, multi-core, fine-stranded

Terminal pins, core end sheath

Tightening torque

Stripping length

0.2 - 2.5mm

0.4 - 0.5Nm

7mm

2

0.2 - 2.5mm

2

, AWG 26-12

Voltage

0.08 - 4.0mm

2

, AWG 28-12

0.2 - 2.5mm

2

0.4 - 0.5Nm

7mm

Terminal connection capacity (residual current and temperature measurement inputs and digital inputs/outputs)

Rigid/flexible

Flexible with core end sheath without plastic sleeve

Flexible with core end sheath with plastic sleeve

Tightening torque

Stripping length

0.14 - 1.5mm

0.20 - 1.5mm

0.20 - 1.5mm

7mm

2

2

2

0.20 - 0.25Nm

, AWG 28-16

Cable length (digital inputs / outputs, temperature measurement input)

Up to 30m

Longer than 30m

Not screened

Screened

Terminal connection capacity (serial interface)

Single core, multi-core, fine-stranded

Terminal pins, core end sheath

Tightening torque

Stripping length

102

0.20 - 1.5mm

2

0.20 - 1.5mm

2

0.20 - 0.25Nm

7mm

UMG 96RM-PN

Function parameters

Function

Total effective power

Total reactive power

Total apparent power

Total effective energy

Total reactive energy

Total apparent energy

Frequency

Phase current I1 - I3

Measured neutral conductor current I4

Residual currents I5, I6

Computed neutral conductor current

Voltage

Voltage

Power factor

Short-term flicker, long-term flicker

Voltage dips (L-N)

Voltage rises (L-N)

Transient overvoltages

Voltage interruptions

Voltage unbalance (L-N)

1)

Voltage unbalance (L-N)

2)

Voltage harmonics

THD of the voltage

3)

THD of the voltage 4)

Pst, Plt

Udip

Uswl

Utr

Uint

Unba

Unb

Uh

THDu

THD-Ru

Symbol

P

QA, Qv

SA, Sv

Ea

ErA, ErV

EapA, EapV f

I

IN

I

Diff

INc

U L-N

U L-L

PFA, PFV

Precision class

0.5

5)

(IEC61557-12)

1 (IEC61557-12)

0.5

5)

(IEC61557-12)

0.5S

5) 6)

(IEC61557-12)

-

-

-

-

-

-

-

1 (IEC61557-12)

0.5

5)

(IEC61557-12)

0.05 (IEC61557-12)

0.2 (IEC61557-12)

1 (IEC61557-12)

1 (IEC61557-12)

1.0 (IEC61557-12)

0.2 (IEC61557-12)

0.2 (IEC61557-12)

0.5 (IEC61557-12)

Cl. 1 (IEC61000-4-7)

1.0 (IEC61557-12)

-

Measurement range

0 to 5.4 kW

0 to 5.4 kvar

0 to 5.4 kVA

0 to 5.4 kWh

0 to 5.4 kvarh

0 to 5.4 kVAh

45 to 65 Hz

0 to 6 Arms

0 to 6 Arms

0 to 40 mArms

0.03 to 25 A

10 to 300 Vrms

18 to 520 Vrms

0.00 to 1.00

-

-

-

-

-

-

-

Up to 2.5 kHz

Up to 2.5 kHz

-

Display range

0 W to 999 GW *

0 varh to 999 Gvar *

0 VA to 999 GVA *

0 Wh to 999 GWh *

0 varh to 999 Gvarh *

0 VAh to 999 GVAh *

45.00 Hz to 65.00 Hz

0 A to 999 kA

0 A to 999 kA

0 A to 999 kA

0.03 A to 999 kA

0 V to 999 kV

0 V to 999 kV

0.00 to 1.00

-

-

-

-

-

-

-

0 V to 999 kV

0% to 999%

-

103

UMG 96RM-PN

Function

Current harmonics

THD of the current

3)

THD of the current 4)

Mains signal voltage

1) In relation to the amplitude.

2) In relation to phase and amplitude.

3) In relation to fundamental oscillation.

4) In relation to effective value.

Symbol

Ih

THDi

THD-Ri

MSV

Precision class

Cl. 1 (IEC61000-4-7)

1.0 (IEC61557-12)

-

-

5) Precision class 0.5 with.../ 5A converter.

Precision class 1 with.../ 1A converter.

6) Precision class 0.5S per IEC62053-22

-

-

Measurement range

Up to 2.5 kHz

Up to 2.5 kHz

Display range

0 A to 999 kA

0% to 999%

-

-

* When the max. total working value range has been reached, the display returns to 0.

104

UMG 96RM-PN

Parameters and Modbus address list

The excerpt of the following parameter list contains settings necessary for proper operation of the UMG 96RM-PN, e.g. current transformers and device address. The values in the parameter list can be described and read.

Table 1 - Parameter list

C

A complete overview of the parameters and measured values as well as explanations on selected measured values can be found in the document "Modbus Address List", which can be found on the CD or online.

The excerpt of the measured value list stores the measured and calculated measured values, status data for the outputs, and logged values for viewing.

C

The addresses listed in this documentation within the range 0-800 can be set directly on the device. The addresses in the range of 1000 and above can only be edited via

Modbus!

Address Format RD/WR Unit Comment

0

1

10

12

14

3

16

18

20

SHORT

SHORT

SHORT

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

- kbps

-

A

A

V

V

A

A

Device address

Baud rate (0=9.6kbps, 1=19.2kbps,

2=38.4kbps, 3= 57.6kbps

Stoppbits

0 = 1 Bit, none parity

1 = 2 Bits, none parity

2 = 1 Bit, even parity

3 = 1 Bit, uneven parity

Current transformer I1, primary

Current transformer I1, sec.

Voltage transformer V1, prim.

Voltage transformer V1, sec.

Current transformer I2, primary

Current transformer I2, sec.

(*1) The values 0 and 248 to 255 are reserved and must not be used.

(*2) The adjustable value 0 does not produce any meaningful work values, and must not be used.

Setting range Default

0 - 255

(*1)

1

0 - 7

(5 - 7 for internal use

0..3 only)

4

0

0 - 1,000,000

(*2)

1 - 5

0 - 1,000,000

5

5

(*2)

400

100, 400

0 - 1,000,000

1 - 5

(*2)

400

5

5

105

UMG 96RM-PN

Address Format RD/WR Unit Comment

22

24

26

28

30

32

34

35

36

37

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

SHORT

SHORT

SHORT

SHORT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR -

-

-

V

V

A

A

V

V

Hz

Voltage transformer V2, prim.

Voltage transformer V2, sec.

Current transformer I3, primary

Current transformer I3, sec.

Voltage transformer V3, prim.

Voltage transformer V3, sec.

Frequency estimation

0=Auto, 45 - 65=Hz

Screen contrast

0 (low), 9 (high)

Backlight

0 (dark), 9 (bright)

Screen profile

0=Preassigned screen profile

1=Preassigned screen profile

2=Preassigned screen profile

38

39

40

41

42

45

SHORT

0..2=Preassigned

SHORT

SHORT

SHORT

SHORT

USHORT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

- s

-

-

- mA

3=Freely selectable screen profile

Screen rotation profile profiles selectable screen rotation profile

Rotation time

Averaging time, I

Averaging time, P

Averaging time, U

Current measurement response threshold I1 - I3 screen

rotation

3=Freely

50 SHORT RD/WR - Password

0 - 3

Setting range

0 - 1,000,000

100, 400

0 - 1,000,000

1 - 5

0 - 1,000,000

100, 400

0, 45 - 65

0 - 9

0 - 9

0 - 3

0 - 60

0 - 8*

0 - 8*

0 - 8*

0 - 200

0 - 999

5

6

0

Default

5

5

400

400

400

400

0

0

6

6

0

6

5

0 (no password)

UMG 96RM-PN

Address Format

111

112

113

114

116

117

118

119

120

122

100

101

102

104

106

107

108

110

SHORT

SHORT

FLOAT

FLOAT

SHORT

SHORT

FLOAT

SHORT

SHORT

SHORT

SHORT

FLOAT

SHORT

SHORT

SHORT

SHORT

FLOAT

SHORT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

Unit

-

-

Wh

Wh

-

10ms s

-

-

- s

-

- s

-

-

- s

Comment

Address of the measured value, digital outp. 1

Address of the measured value,

Digital outp. 2

Pulse value,

Digital output 1

Pulse value,

Digital output 2

Minimum pulse length (1=10ms)

Digital outp. 1/2

Result of Comparator group 1;

Combine A, B, C

Comparator 1A, Threshold value

Comparator 1A, address of the measured value

Comparator 1A, min. switch-on time

Comparator 1A, lead time

Comparator 1A, Operator

">="=0, "<"=1

Comparator 1B, Threshold value

Comparator 1B, address of the measured value

Comparator 1B, min. switch-on time

Comparator 1B, lead time

Comparator 1B, Operator

">="=0, "<"=1

Comparator 1C, Threshold value

Comparator 1C, address of the measured value

Setting range Default

0 - 32,000

0 - 32,000

874

882

-1,000,000 to +1,000,000 1000

-1,000,000 to +1,000,000 1000

1 - 1000

0,1

5 (=50ms)

0

-10

12

-1 to +10

12

-1 0

0 - 32,000 0

0 - 32,000

0 - 32,000

0,1

-10

12

-1 to +10

12

-1 0

0

0

0

0 - 32,000 0

0 - 32,000

0 - 32,000

0,1

-10

12

-1 to +10

12

-1 0

0

0

0

0 - 32,000 0

107

UMG 96RM-PN

Address Format RD/WR Unit Comment

123

124

125

126

SHORT

SHORT

SHORT

SHORT

RD/WR

RD/WR

RD/WR s s

-

Comparator 1C, min. switch-on time

Comparator 1C, lead time

Comparator 1C, Operator

RD/WR -

">="=0, "<"=1

Result of Comparator group 2;

Combine A, B, C

(1=and,

127

129

130

131

132

133

135

136

137

138

139

141

142

143

144

FLOAT

SHORT

SHORT

SHORT

SHORT

FLOAT

SHORT

SHORT

SHORT

SHORT

FLOAT

SHORT

SHORT

SHORT

SHORT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

-

- s s

-

-

- s s

-

-

- s s

-

0=or)

Comparator 2A, Threshold value

Comparator 2A, address of the measured value

Comparator 2A, min. switch-on time

Comparator 2A, lead time

Comparator 2A, Operator

">="=0, "<"=1

Comparator 2B, Threshold value

Comparator 2B, address of the measured value

Comparator 2B, min. switch-on time

Comparator 2B, lead time

Comparator 2B, Operator

">="=0, "<"=1

Comparator 2C, Threshold value

Comparator 2C, address of the measured value

Comparator 2C, min. switch-on time

Comparator 2C, lead time

Comparator 2C, Operator

">=" = 0, "<" = 1

108

Setting range

0 - 32,000

0 - 32,000

0,1

0,1

-10

12

-1 to +10

12

-1 0

0 - 32,000 0

0 - 32,000

0 - 32,000

0,1

-10

12

-1 to +10

12

-1 0

0

0

0

0 - 32,000 0

0 - 32,000

0 - 32,000

0,1

-10

12

-1 to +10

12

-1 0

0

0

0

0 - 32,000

0 - 32,000

0 - 32,000

0,1

0

0

0

0

Default

0

0

0

0

UMG 96RM-PN

Address

145

200

201

202

203

500

501

502

503

504

505

506

507

508

Format

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

Unit

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Comment

"Flash display"

Bit 1 = 1/0: active/inactive for

Comparator group output 1

Bit 2 = 1/0: active/inactive for

Comparator group output 2

Selection of source for

Digital output 1

Inverter Digital output 1

Selection of source for

Digital output 2

Inverter Digital output 2

Terminal assignment, I L1

Terminal assignment, I L2

Terminal assignment, I L3

Terminal assignment, U L1

Terminal assignment, U L2

Terminal assignment, U L3

Clear min and max values

Clear energy counter

Force write to EEPROM

Note: Energy values and min/max values are written to the EEPROM every 5 minutes.

Setting range

0-3

509

510

511

SHORT

SHORT

SHORT

RD/WR

RD/WR

-

-

Connection diagram, voltage

Connection diagram, current

RD/WR - Relevant voltage for THD and FFT

0 - 8

0 - 8

4)

0

In the display, the voltages can be displayed for THD and FFT as L-N or as L-L values. 0=LN, 1=LL

0

0

*1 0 =Comparator group, 1=Pulse output, 2=Value from an external source (Modbus), 3=Reserved, 4=Reserved, 5=ProfiNet

*2 0=Not inverted, 1=Inverted *3 0 = No measurement of the current or voltage path. *4 The setting 8 is equal setting 0.

Default

0

0 - 5

*1

0, 1

*2

1

0

0 - 5

*1

0, 1

*2

1

0

-3 to 0 to +3

3)

+1

-3 to 0 to +3

3)

+2

-3 to 0 to +3

3)

+3

0 - 3

3)

1

0 - 3

3)

2

0 - 3

3)

3

0 - 1

0 - 1

0 - 1

0

0

0

109

UMG 96RM-PN

Address Format RD/WR Unit Comment

521

524

525

524

530

532

534

536

538

540

542

543

544

546

548

549

550

551

552

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

FLOAT

SHORT

SHORT

FLOAT

FLOAT

SHORT

RD/WR -

0=Output,

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

RD/WR

-

-

-

A

A

A

A

A

A

-

-

-

-

-

-

-

-

-

Switch I/Os of Group 2

Inverter Digital output 3

Inverter Digital output 4

Inverter Digital output 5

Current transformer I4, primary

Current transformer I4, sec.

Current transformer I5, primary

Current transformer I5, sec.

Current transformer I6, primary

Current transformer I6, sec.

Input type I5

0=Residual current, 1=Temperature

Input type I6

0=Residual current, 1=Temperature

Temperature offset temp 1

Temperature offset temp 2

Temperature sensor temp 1

(0=PT100, 1=PT1000, 2=KTY83,

3=KTY84, 4=Resistance in ohms)

Temperature sensor temp 2

(0=PT100, 1=PT1000, 2=KTY83,

3=KTY84, 4=Resistance in ohms)

Tariff configuration, Input 1

If Input 1 is active, counters are set in Tariff 1*

Tariff configuration, Input 2

If Input 2 is active, counters are set in Tariff 2*

Tariff configuration, Input 3

If Input 3 is active, counters are set in Tariff 3*

110

Setting range

0,1

0, 1

0, 1

0, 1

*2

*2

*2

0 - 1,000,000

(*2)

1.0 - 5.0

1.0 - 5.0

0.0 - 1,000,000.0

1.0 - 5.0

5

5

0.0 - 1,000,000.0

0

0

0

0

(*2)

1

(*2)

1

1

1

0,1

0,1

-1000.0 to 1000.0

-1000.0 to 1000.0

0

0

0

0

0 - 4

0 - 4

0 - 127

0 - 127

0 - 127

Default

0

0

0

0

0

UMG 96RM-PN

Address

553

554

600

602

605

608

609

610

611

612

613

614

615

616

617

746

747

750

754

756

Format

SHORT

SHORT

UINT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SHORT

SERNR

SERNR

C

-

-

-

-

-

-

-

-

-

-

-

-

-

Unit

-

-

-

-

- s s

RD/WR

RD/WR

RD/WR

RD

RD

RD

RD

RD

RD/WR

RD/WR

RD/WR

RD

RD

RD

RD

RD

RD/WR

RD/WR

RD

RD

RD

Comment

Transformer monitoring I5

Transformer monitoring I6

Setting range Default

0 (inactive), 1 (active) 0

0 (inactive), 1 (active) 0

Measurement range exceeded

Modbus value for Output 1

Modbus value for Output 2

Status, Output 1

Status, Output 2

Comparator result 1, Output A

Comparator result 1, Output B

Comparator result 1, Output C

Comparator result 2, Output A

Comparator result 2, Output B

Comparator result 2, Output C

Combination result, Comparator group 1

Combination result, Comparator group 2

0 to 0xFFFFFFFF

0, 1

0, 1

After how long to switch to standby lighting

Brightness of standby lighting

Software release

Serial number

Production number

60 to 9999

0 - 9

900

0

The display only depicts the first 3 digits

(###) of a value. Values higher than 1000 are indicated by "k". Example: 003k = 3000

* The tariff counter is activated by a bit-by-bit coding:

Bit 0 = Effective energy, Bit 1 = Effective energy (consumed), Bit 2 = Effective energy (delivered)

Bit 3 = Reactive energy, Bit 4 = Reactive energy (inductive), Bit 5 = Reactive energy (capacitive)

Bit 6 = Apparent energy

111

UMG 96RM-PN

Table 2 - Modbus address list

(often needed measured values)

C

The addresses listed in this documentation within the range 0-800 can be set directly on the device.

The address range 800-999 is available for the programming of comparators on the device. The addresses in the range of 1000 and above can only be edited via

Modbus!

Modbus Address

Address on display

19000

19002

19004

19006

19008

19010

19012

19014

19016

19018

19020

19022

19024

19026

19028

19030

808

810

812

814

816

818

860

862

864

866

868

870

872

874

884

886

112

Format

float float float float float float float float float float float float float float float float

RD/WR

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

Unit

A

A

W

W

W

W

VA

VA

V

V

A

A

V

V

V

V

C

A complete overview of the parameters and measured values as well as explanations on selected measured values can be found in the document "Modbus Address List", which can be found on the CD or online.

Comment

Voltage L1-N

Voltage L2-N

Voltage L3-N

Voltage L1-L2

Voltage L2-L3

Voltage L3-L1

Current, L1

Current, L2

Current, L3

Vector sum; IN=I1+I2+I3

Effective power L1

Effective power L2

Effective power L3

Sum; Psum3=P1+P2+P3

Apparent power S L1

Apparent power S L2

Modbus Address

Address on display

19064

19066

19068

19070

19072

19074

19076

19078

19080

19082

19084

19086

19088

19090

19092

19032

19034

19036

19038

19040

19042

19044

19046

19048

19050

19052

19054

19056

19058

19060

19062

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

824

800

888

890

876

878

880

882

820

822

RD/WR

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

Format

float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float

Unit

VAh

VAh

VAh varh varh varh varh

Wh

Wh

Wh

Wh

Wh

Wh

Wh

VAh

-

Hz

-

Wh

Wh

Wh

Wh

Wh

VA

VA var var var var

-

-

Comment

Apparent power S L3

Sum; Ssum3=S1+S2+S3

Fund. reactive power (mains frequ.) Q L1

Fund. reactive power (mains frequ.) Q L2

Fund. reactive power (mains frequ.) Q L3

Sum; Qsum3=Q1+Q2+Q3

Fund.power factor, CosPhi; U L1-N IL1

Fund.power factor, CosPhi; U L2-N IL2

Fund.power factor, CosPhi; U L3-N IL3

Measured frequency

Rotation field; 1=right, 0=none, -1=left

Effective energy L1

Effective energy L2

Effective energy L3

Effective energy L1 - L3

Effective energy L1, consumed

Effective energy L2, consumed

Effective energy L3, consumed

Effective energy L1..L3, consumed, rate 1

Effective energy L1, delivered

Effective energy L2, delivered

Effective energy L3, delivered

Effective energy L1 - L3, delivered

Apparent energy L1

Apparent energy L2

Apparent energy L3

Apparent energy L1 - L3

Reactive energy L1

Reactive energy L2

Reactive energy L3

Reactive energy L1 - L3

UMG 96RM-PN

113

UMG 96RM-PN

Modbus Address

Address on display

19094

19096

19098

19100

19102

19104

19106

19108

19110

19112

19114

19116

19118

19120

-

-

-

-

-

-

-

-

836

838

840

908

910

912

Format

float float float float float float float float float float float float float float

RD/WR

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

RD

Unit

%

%

%

%

%

% varh varh varh varh varh varh varh varh

Comment

Reactive energy, inductive, L1

Reactive energy, inductive, L2

Reactive energy, inductive, L3

Reactive energy L1 - L3, ind.

Reactive energy, capacitive, L1

Reactive energy, capacitive, L2

Reactive energy, capacitive, L3

Reactive energy L1 - L3, cap.

Harmonic, THD, U L1-N

Harmonic, THD, U L2-N

Harmonic, THD, U L3-N

Harmonic, THD, I L1

Harmonic, THD, I L2

Harmonic, THD, I L3

114

Number formats

Type

short ushort int uint float

Size

16 bit

16 bit

32 bit

32 bit

32 bit

UMG 96RM-PN

Minimum

-2

15

0

-2 31

0

IEEE 754

Maximum

2

15

-1

2 16 -1

2 31 -1

2

32

-1

IEEE 754

C

Information on saving measured values and configuration data:

• The following measured values are saved at least every 5 minutes:

• Comparator timer

• S0 counter statuses

• Min. / Max. / Mean values

• Energy values

• Configuration data is saved immediately!

115

UMG 96RM-PN

Dimension diagrams

All dimensions in mm

Rear view View from below

91,5

116

Side view

72

(Depth without plug)

Cut-out size

92 +0,8

UMG 96RM-PN

6 57

78

117

UMG 96RM-PN

Measured value screen overview

A01

Measured values

L1-N voltage

L2-N voltage

L3-N voltage

A02

Measured values

L1-L2 voltage

L2-L3 voltage

L3-L1 voltage

A03

Measured values

L1 current

L2 current

L3 current

B01

Mean values

L1-N voltage

L2-N voltage

L3-N voltage

B02

Mean values

L1-L2 voltage

L2-L3 voltage

L3-L1 voltage

B03

Mean values

L1 current

L2 current

L3 current

C01

Max values

L1-N voltage

L2-N voltage

L3-N voltage

C02

Max values

L1-L2 voltage

L2-L3 voltage

L3-L1 voltage

C03

Max values

L1 current

L2 current

L3 current

A04

Measured value

Sum

Current on the N

B04

Mean value

Sum

Current on the N

C04

Max value

Total measured value

Current on the N

A05

Measured values

L1 effective power

L2 effective power

L3 effective power

A06

Measured value

Total effective power

A07

Measured values

L1 apparent power

L2 apparent power

L3 apparent power

118

B05

Mean value

L1 effective power

L2 effective power

L3 effective power

B06

Mean value

Total effective power

B07

Mean values

L1 apparent power

L2 apparent power

L3 apparent power

C05

Max values

L1 effective power

L2 effective power

L3 effective power

C06

Max value

Total effective power

C07

Max values

L1 apparent power

L2 apparent power

L3 apparent power

D01

Min values

L1-N voltage

L2-N voltage

L3-N voltage

D02

Min values

L1-L2 voltage

L2-L3 voltage

L3-L1 voltage

D03

Max values (mean v.)

L1 current

L2 current

L3 current

D04

Max values

Total mean value

Current on the N

D06

Max value

Total eff.pow. mean value

A08

Measured value

Sum

Apparent power

A09

Measured values

L1 reactive power

L2 reactive power

L3 reactive power

A10

Measured value

Total reactive p.

B08

Mean value

Sum

Apparent power

B09

Mean values

L1 reactive power

L2 reactive power

L3 reactive power

B10

Mean value

Total reactive p.

C08

Max value

Sum

Apparent power

C09

Max values (ind)

L1 reactive power

L2 reactive power

L3 reactive power

C10

Max value (ind)

Total reactive p.

A11

Measured value

Harmonic distortion (THD)

U L1

A12

Measured value

Harmonic distortion (THD)

I L1

A13

Max value

Harmonic distortion (THD)

U L1

A14

Max value

Harmonic distortion (THD)

I L1

B11

Measured value

Harmonic distortion (THD)

U L2

B12

Measured value

Harmonic distortion (THD)

I L2

B13

Max value

Harmonic distortion (THD)

U L2

B14

Max value

Harmonic distortion (THD)

I L2

C11

Measured value

Harmonic distortion (THD)

U L3

C12

Measured value

Harmonic distortion (THD)

I L3

C13

Max value

Harmonic distortion (THD)

U L3

C14

Max value

Harmonic distortion (THD)

I L3

UMG 96RM-PN

119

UMG 96RM-PN

A15

Measured value

L1 cos(phi)

L2 cos(phi)

L3 cos(phi)

A16

Measured value

Sum of cos(phi)

B16

Mean value

Sum of cos(phi)

A17

Measured value

Frequency L1

Rotary field indication

A18

Measured value

Total effective energy

(without backstop)

A19

Measured value (ind)

Reactive energy

B18

Measured value

Total effective energy

(consumption)

B19

Measured value

Total

Reactive energy cap.

B20

C18

Measured value

Total effective energy

(delivery)

C19

Measured value

Total

Reactive energy cap.

A20

Operating hours counter 1

Comparator 1A*

Total running time

A21

Measured value

1st harmonics

U L1

B21

Measured value

3rd harmonics

U L1

...

The highlighted menus are not displayed with the factory default setting.

120

...

D18

Measured value

Total

Apparent energy

D19

Measured value

Reactive energy L1 ind. (Tariff 1)

G20

Comparator 2C*

Total running time

H21

Measured value

15th harmonics

U L1

E18

Measured value

Effective energy L1

Consumption (Tariff 1)

E19

Measured value

Reactive energy L2 ind. (Tariff 1)

F18

Measured value

Effective energy L2

Consumption (Tariff 1)

F19

Measured value

Reactive energy L3 ind. (Tariff 1)

* Only the first 6 comparators are displayed.

G18

Measured value

Effective energy L3

Consumption (Tariff 1)

A22

Measured value

1st harmonics

U L2

A23

Measured value

1st harmonics

U L3

A24

Measured value

1st harmonics

I L1

A25

Measured value

1st harmonics

I L2

A26

Measured value

1st harmonics

I L3

A27

Max value

1st harmonics

U L1

A28

Max value

1st harmonics

U L2

B22

Measured value

3rd harmonics

U L2

B23

Measured value

3rd harmonics

U L3

B24

Measured value

3rd harmonics

I L1

B25

Measured value

3rd harmonics

I L2

B26

Measured value

3rd harmonics

I L3

B27

Max value

3rd harmonics

U L1

B28

Max value

3rd harmonics

U L2

...

...

...

...

...

...

...

H22

Measured value

15th harmonics

U L2

H23

Measured value

15th harmonics

U L3

H24

Measured value

15th harmonics

I L1

H25

Measured value

15th harmonics

I L2

H26

Measured value

15th harmonics

I L3

H27

Max value

15th harmonics

U L1

H28

Max value

15th harmonics

U L2

The highlighted menus are not displayed with the factory default setting.

UMG 96RM-PN

121

UMG 96RM-PN

A29

Max value

1st harmonics

U L3

A30

Max value

1st harmonics

I L1

A31

Max value

1st harmonics

I L2

A32

Max value

1st harmonics

I L3

A33

Measured value

L4 current

A34

Measured value

L5 current

A35

Measured value

L6 current

B29

Max value

3rd harmonics

U L3

B30

Max value

3rd harmonics

I L1

B31

Max value

3rd harmonics

I L2

B32

Max value

3rd harmonics

I L3

...

...

...

...

122

The highlighted menus are not displayed with the factory default setting.

H29

Max value

15th harmonics

U L3

H30

Max value

15th harmonics

I L1

H31

Max value

15th harmonics

I L2

H32

Max value

15th harmonics

I L3

Even and odd harmonics up to the 40th order can be accessed and displayed in the GridVis software.

UMG 96RM-PN

123

UMG 96RM-PN

Connection example 1

(with residual current monitoring I

PE

/ I

DIFF

)

=

+

-

S1 S2 S3

=

-

+

K3 K4 K5

0-30 mA

I

DIFF

0-30 mA

I

PE

24V

DC

=

-

+

K1 K2

13 14 15

Gruppe 1

28 29 30 31 32 33 34 35 36

Gruppe 2

I

5

I

6

37

Digital inputs / outputs Analog inputs

UMG 96RM-PN

16

B

RS485

17

A

Power supply voltage

N/- L/+

1 2

Voltage measurement

V

1

V

2

V

3

V

N

3 4 5 6

Current measurement

S2 S1 S2 S1 S2 S1 S2

I

4

S1

19 18

B

A

1) 2) 2) 2)

3) 3) 3) 3)

S2 S1

S2 S1

S2 S1

S2 S1

L1

L2

L3

N

230V/400V 50Hz

124

1)

UL/IEC-approved fuse

(6A, type C)

UL/IEC-approved fuse

(10A, type C)

3)

Short circuit jumpers (external)

UMG 96RM-PN

Connection example 2

(with temperature and residual current monitoring)

24V

DC

=

-

+

K1 K2

=

+

-

S1 S2 S3

=

-

+

K3 K4 K5

PT100

0-30 mA

I

DIFF

13 14 15

Gruppe 1

28 29 30 31 32 33 34 35 36

Gruppe 2

I

5

I

6

37

Digital inputs / outputs Analog inputs

UMG 96RM-PN

16

B

RS485

17

A

Power supply voltage

N/- L/+

1 2

Voltage measurement

V

1

V

2

V

3

V

N

3 4 5 6

Current measurement

S2 S1 S2 S1 S2 S1 S2

I

4

S1

19 18

B

A

1) 2) 2) 2)

3) 3) 3) 3)

S2 S1

S2 S1

S2 S1

S2 S1

L1

L2

L3

N

230V/400V 50Hz

1)

UL/IEC-approved fuse

(6A, type C)

UL/IEC-approved fuse

(10A, type C)

3)

Short circuit jumpers (external)

125

UMG 96RM-PN

Basic functions quick guide

Modify current transformer setting

Switch to Programming mode:

• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously for approx. 1 second.

The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

• The selection is confirmed with button 1.

• The first digit of the input range for the primary current flashes.

Modify primary current

• Modify the flashing digit with button 2.

• Use button 1 to select the next number you wish to modify. The selected digit to be modified flashes. If the entire number flashes, the decimal point can be moved with button 2.

Modify secondary current

• Only 1A or 5A can be set as the secondary current.

• Use button 1 to select the secondary current.

• Modify the flashing digit with button 2.

Exit Programming mode

• Switching to Display mode is done by pressing buttons

1 and 2 again simultaneously for approx. 1 second.

Retrieving measured values

Current transformer setting, primary current

Programming mode indicator

Current transformer setting, secondary current

Current transformer symbol

(only in Programming mode)

Switch to Display mode:

• If Programming mode is still active (PRG and CT symbols shown on the display), pressing buttons 1 and 2 simultaneously for approx. 1 second switches to Display mode.

• A measured value screen, e.g. for the voltage, appears

Button control

• Button 2 is used to switch between the measured value screens for current, voltage, power, etc.

• Button 1 is used to switch between the mean values, max values, etc. associated with a particular measured value.

126

TCP/IP addressing quick guide

Manual TCP/IP settings

Switch to Programming mode:

• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously for approx. 1 second.

The symbols for Programming mode "PRG", and for the current transformer "CT" appear.

Set the TCP/IP address (addr.)

• Use button 2 to switch to "Adr" on the display.

• Use button 1 to select the first digit of the address

(Byte 0) (digit flashes). Select the digit with button 2.

• Select the next digit with button 1 (digit flashes) and use button 2 to set the desired digit.

• Once Byte 0 of the address is set, bytes 1 to 3 can be set with button 1. Then the display jumps back to Byte

0 ( none of the digits are flashing).

Subnet mask (SUb)

• Use button 2 to switch to the subnet mask area and set it with buttons 1 and 2, in the same way as the address.

Set gateway address (GAt)

• Use buttons 2 and 1 to set the gateway in the same way as the address.

Exit Programming mode

• Exit the mode by pressing buttons 1 and 2 simultaneously, or wait for 60 seconds.

UMG 96RM-PN

Designation

Byte identifier of the address (e.g. Byte 0)

Address value, Byte 0

Fig. TCP/IP address, Byte 1

A TCP/IP address consists of 4 bytes with the following structure:

Byte 0 Byte 1 Byte 2 Byte 3 xxx.xxx.xxx.xxx

127

UMG 96RM-PN

128

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents