advertisement
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
E-mail: [email protected]
Internet: http://www.janitza.com
Power Analyser
UMG 96 RM-PN
User manual and technical data
Power Analyser
UMG 96RM-PN
Table of contents
GridVis network analysis software
Current measurement using I1 to I4
Residual current monitoring (RCM) via I5, I6 31
Parameters and measured values
2
Current and voltage transformer
Programming the current transformer for I1-I3 51
Programming the voltage transformer 52
RS485 device address (addr. 000)
Resetting energy meters (addr. 507)
Direction of the rotating field
Total running time, comparator
Connecting the measured voltage
Applying the measuring-circuit voltage
Direction of the rotating field
Checking the power measurement
Failure monitoring (RCM) for I5, I6
Checking the single phase powers
Digital output status indicators
Comparators and threshold value monitoring 82
Measured value screen overview
UMG 96RM-PN
3
UMG 96RM-PN
General information
Comments on the manual
Copyright
This manual is subject to the statutory provisions of copyright law and may not be photocopied, reprinted, or reproduced - in whole or in part, by mechanical or electronic means - nor otherwise duplicated or republished, without the binding written permission of:
We welcome your comments. If anything in this manual seems unclear, please let us know by sending an e-mail to: [email protected]
Meaning of symbols
This manual uses the following pictograms:
4
Janitza electronics GmbH, Vor dem Polstück 1,
D 35633 Lahnau, Germany
Trademarks
c
Dangerous voltage!
Risk to life or serious injury. Before commencing work on the system and the device, they must first be de-energised.
All trademarks and the resulting rights are the property of their respective owners.
Disclaimer
Janitza electronics GmbH accepts no responsibility for errors or deficiencies within this manual, and makes no commitment to keep the contents of this functional description up to date.
m
Attention!
Please pay attention to the documentation.
This symbol is intended to warn you of potential dangers, which could occur during installation, commissioning and use.
C
Note!
UMG 96RM-PN
Instructions on use
Please read this operation manual as well as all other publications that must be consulted for working with this product (in particular, for the installation, operation or maintenance). can be caused by the operation or maintenance of the device.
Observe all safety instructions and warnings. Failure to comply with the instructions can result in personal injuries and/or damage to the product.
Additional legal and safety regulations required for the respective application are to be followed during the use of the device.
Any unauthorised changes or use of this device, which go beyond the mechanical, electrical or otherwise stated operating limitations, can result in bodily injury or/and damage to the product.
Any such unauthorised change constitutes "misuse" and/or "negligence" according to the warranty for the product and thus excludes the warranty for covering possible damage resulting from this.
c
If the device is not operated according to the operation manual, protection is no longer ensured and hazards can be presented by the device.
This device must only be operated and repaired by specialised personnel.
Specialised personnel are persons, that based on their respective training and experience, are qualified to recognise risks and prevent potential dangers that m
Single core conductor must be provided with core end sheath.
m
Only pluggable screw terminals with the same number of poles and the same type of construction are permitted to be connected together.
5
6
UMG 96RM-PN
Concerning this operation manual
Inspection on receipt
This operation manual is part of the product.
• Read the operation manual before using the device.
• Keep the operation manual instructions throughout the entire service life of the product and have them readily available for reference.
• Pass the operation manual on to each subsequent owner or user of the product.
The prerequisites of faultless, safe operation of this device are proper transport and proper storage, setup and installation, as well as careful operation and maintenance. If it can be assumed that risk-free operation is no longer possible, the device must be immediately put out of operation and secured against being put back into operation again.
Packing and unpacking must be carried out with customary care without the use of force and only using suitable tools. The devices should be visually checked for flawless mechanical condition.
It can be assumed that risk-free operation is no longer possible if the device, for example,
C
All screw-type terminals included in the scope of delivery are attached to the device.
• has visible damage,
• no longer works despite the mains power supply being intact,
• has been exposed to prolonged adverse conditions
(e.g. storage outside the permissible climate limits without being adapted to the room climate, condensation, etc.) or rough handling during transportation (e.g. falling from a height, even if there is no visible external damage, etc.).
• Please check the delivered items for completeness before you start installing the device.
UMG 96RM-PN
Available accessories
Number Part no.
1
1
2
1
52.22.251
10.01.855
10.01.849
10.01.871
1
1
1
1
1
1
1
1
1
10.01.875
10.01.865
10.01.857
10.01.859
08.01.505
52.00.008
29.01.065
15.06.015
15.06.025
Designation
Mounting clips
Screw-type terminal, pluggable, 2-pole (auxiliary power)
Screw-type terminal, pluggable, 4-pole (voltage measurement)
Screw-type terminal, pluggable, 6-pole (current measurement I1-I3)
Screw-type terminal, pluggable, 2-pole (current measurement I4)
Screw-type terminal, pluggable, 10-pole (digital/analogue inputs/outputs)
Screw-type terminal, pluggable, 2-pole (RS 485)
Screw-type terminal, pluggable, 3-pole (digital/pulse output)
Patch cable 2 m, twisted, grey (connection UMG 96RM-PC/switch)
RS485 termination resistor, 120 ohms
Silicone seal, 96 x 96
Interface converter RS485 <-> RS232
Interface converter RS485 <-> USB
7
UMG 96RM-PN
8
Product description
Proper use
The UMG 96RM-PN is intended for the measurement and calculation of electrical variables such as voltage, current, power, energy, harmonics, etc. in building installations, on distribution units, circuit breakers and busbar trunking systems.
The UMG 96RM-PN is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed.
A continuous monitoring of residual currents (residual current monitor, RCM) is performed via the current measurement inputs I5 and I6 via an external residual current transformer with a rated current of 30 mA.
Measurements in medium and high-voltage networks are always performed via current and voltage transformers.
Measured voltages and measured currents must derive from the same network.
The measurement results can be displayed and read out and further processed via the RS485 or ProfiNet interface.
The voltage measurement inputs are designed for measurements in low voltage networks where rated voltages of up to 300V phase to earth and surge voltages of overvoltage category III can occur.
The current measurement inputs I1-I4 of the UMG
96RM-PN are connected via external ../1A or ../5A current transformers.
m
Residual current monitoring monitors residual currents via external current transformers.
The device is
not an independent protective device!
Device parameters
• Supply voltage:
Option 230V: 90V - 277V (50/60Hz) or
DC 90V - 250V; 300V CATIII
Option 24V: 24 - 90V AC / DC; 150V CATIII
• Frequency range: 45 - 65 Hz
Device functions
• 3 voltage measurement channels, 300V
• 4 current measurements
(via current transformer ../5A or ../1A)
• 2 residual current measurements
(via residual current transformer ../30mA) or optionally 2 temperature measurements
• RS485 interface, ethernet and ProfiNet
• 2 digital outputs and additionally 3 digital inputs/ outputs
UMG 96RM-PN
9
UMG 96RM-PN
UMG 96RM-PN features
General information
• Front panel integration device with dimensions
96x96 mm
• Connection via pluggable screw terminals
• LC display with backlight
• Operation via 2 buttons
• 3 Voltage and 4 current measurement inputs
• Either 2 residual current or temperature measurement inputs
• 2 digital outputs and 3 digital inputs/outputs
• RS485 interface (Modbus RTU, slave, up to 115 kbps)
• 2 interfaces for ethernet / ProfiNet
• Working temperature range -10°C to +55°C
Measurement uncertainty
• Effective energy, measurement uncertainty class
0.5 for ../5A converter
• Effective energy, measurement uncertainty class 1 for ../1A converter
• Reactive energy, class 2
Measurement
• Measurement in IT, TN and TT networks
• Measurement in networks with rated voltages up to L-L 480V and L-N 277V
• Measurement range current 0 to 5A eff.
• True RMS (TRMS)
• Continuous sampling of the voltage and current measurement inputs
• Continuous monitoring of residual currents with failure monitoring
• Temperature measurement
• Frequency range of the fundamental oscillation 45
Hz to 65 Hz
• Measurement of the 1st to 40th harmonics, for ULN and I1-I3
• Uln, I, P (cons./del.), Q (ind./cap.)
• Capturing substantially more than 1000 measured values
• Fourier analysis 1st to 40th harmonics for U and
I1-I3
• 7 power meters for
Effective energy (cons.), Effective energy (delivery),
Effective energy (without backstop),
Reactive energy (in 4 quadrants: delivered, consumed,
in each case ind./cap.),
Reactive energy (without backstop), Apparent energy,
for each of L1, L2, L3 and sum
10
UMG 96RM-PN
Measuring process GridVis network analysis software
The UMG 96RM-PN measures continuously and calculates all effective values over a 10/12 period interval. The device measures the real effective value
(TRMS) of the voltages and currents connected to the measurement inputs.
The UMG 96RM-PN can be programmed and read out using the GridVis network analysis software (Download: www.janitza.com). For this, a PC must be connected to the UMG 96RM-PN via a serial interface (RS485) or by ethernet.
Operating concept GridVis features
You can program and call up the measured values via many routes using the UMG 96RM-PN.
• Programming the UMG 96RM-PN
• Graphical representation of measured values
• Directly on the device via 2 buttons.
• Using the GridVis programming software.
• Using the device homepage (no programming).
• Using the Modbus protocol.
You can modify and call up the data using the Modbus address list. The list can be called up via the device's home page and can be found on the enclosed CD.
• Using the PLC within a PROFINET environment.
This operation manual only describes how to operate the UMG 96RM-PN using the two buttons.
The GridVis programming software has its own "online help" system.
11
RS485
UMG 96RM-PN
Connection variants
Connection of a UMG 96RM-PN to a PC via an interface converter:
RS485
RS485
RS485
RS485
RS485
UMG 96RM-PN
UMG 96RM-PN
Ethernet
RS485
Direct connection of a UMG 96RM-PN to a PC/PLC via
Ethernet/ProfiNet.
RS485
PC
(GridVis)
SPS
PC
(GridVis)
SPS
RS485
PC
(GridVis)
SPS
Ethernet / ProfiNet
Ethernet
Connection of a UMG 96RM-PN via an UMG 604 as a gateway.
RS485
RS485
Ethernet / ProfiNet
Ethernet / ProfiNet
Connection of a UMG 96RM-PN to a PC/PLC via
Ethernet/ProfiNet.
Ethernet / ProfiNet
Ethernet / ProfiNet
Ethernet
RS485
UMG 604
RS485
RS485
UMG 96RM-PN
PC
(GridVis)
SPS
Ethernet / ProfiNet
UMG 96RM-PN
Ethernet / ProfiNet
Ethernet / ProfiNet
Ethernet / ProfiNet
RS485 UMG 96RM-PN
Ethernet / ProfiNet
Switch
Ethernet / ProfiNet
Ethernet / ProfiNet
Ethernet / ProfiNet
PC
(GridVis)
SPS
PC
(GridVis)
SPS
Ethernet / ProfiNet
PC
(GridVis)
SPS
Ethernet / ProfiNet
Ethernet / ProfiNet Ethernet / ProfiNet
PC
(GridVis)
SPS
Ethernet / ProfiNet
Ethernet / ProfiNet
Ethernet / ProfiNet
Ethernet / ProfiNet
UMG 96RM-PN
Assembly
Position of installation
The UMG 96RM-PN is suitable for integration into fixed and weatherproof switch panels. Conductive switch panels must be earthed.
Mounting position
To ensure adequate ventilation, the UMG 96RM-PN must be installed vertically. There should be separation above and below of at least 50mm with 20mm space to the sides.
Front panel section
Cut-out size:
92
+0.8
x 92
+0.8
mm.
Fig. Mounting position
UMG 96RM-PN
(View from rear)
m
Failure to meet the minimum clearances can destroy the UMG 96RM-PN at high ambient temperatures!
13
UMG 96RM-PN
Mounting
The UMG 96RM-PN is secured in the switchboard by the mounting clips on the side. Before insertion the device they must be removed, for example by using a screwdriver to lever them horizontally.
Mounting is then performed by sliding in and engaging the clips and subsequently screwing in the screws.
• Screw in the clamping screws until they are just touching the mounting plate.
• Tighten the clamping screws by two more turns each (tightening the screws too far can destroy the mounting clips).
Fig. Side view of the UMG 96RM-PN with mounting clip.
To release the clips, use a screwdriver to lever them horizontally.
Mounting plate
Clamping screw
Mounting clip Screwdriver
When clamping screws touch the mounting plate: max. two more turns to secure the device
14
UMG 96RM-PN
Installation
Supply voltage
The UMG 96RM-PN needs a supply voltage to operate.
The supply voltage is connected on the rear side of the device via terminal blocks.
Fuse
Before connecting the supply voltage, ensure that the voltage and frequency correspond to the details on the rating plate!
Circuit breaker m
• The supply voltage must be connected through a fuse according to the technical data.
• If installed in a building, a disconnector or circuit breaker must be provided for the supply voltage.
• The disconnector must be installed near the device and easily accessible to the user.
• The switch must be marked as the circuit breaker for this device.
• Voltages which are over the permitted voltage range can destroy the device.
Fig. Connection example of the supply voltage to a
UMG 96RM
L
N
15
UMG 96RM-PN
Voltage measurement
You can use the UMG 96RM-PN for voltage measurement in TN, TT, and IT systems.
Voltage measurement in the UMG 96RM-PN is designed for the overvoltage category 300V CAT III (measurement voltage surge 4kV).
In systems with no N, measured values requiring an N refer to a calculated N.
L1 L1
L2
L3
N
PE
277V/480V 50/60Hz
N
240V
50/60Hz
L1
L2
L3
480V 50/60Hz
V1 V2 V3 V
N
AC/DC
DC
Voltage measurement
UMG 96RM
Auxiliary supply
Impedance
V1 V2 V3 V
N
Earthing of the system
AC/DC
DC
Voltage measurement
UMG 96RM
Auxiliary supply
Fig. Schematic diagram - Measurement on three-phase
4-conductor systems.
16
Fig. Schematic diagram - Measurement on three-phase
3-conductor systems.
UMG 96RM-PN
Nominal network voltage
Lists of networks and their nominal network voltages in which the UMG 96RM-PN can be used.
Three-phase 4-conductor systems with earthed neutral conductor.
U
L-N /
U
L-L
66V / 115V
120V / 208V
127V / 220V
220V / 380V
230V / 400V
240V / 415V
260V / 440V
277V / 480V
Maximum system rated voltage
Fig. Table for network rated voltages i.a.w. EN60664-
1:2003 suitable for the voltage measurement inputs.
Unearthed three-phase 3-conductor systems.
U
L-L
66V
120V
127V
220V
230V
240V
260V
277V
347V
380V
400V
415V
440V
480V
Maximum system rated voltage
Fig. Table for network rated voltages i.a.w. EN60664-
1:2003 suitable for the voltage measurement inputs.
17
UMG 96RM-PN
Voltage measurement inputs
The UMG 96RM-PN has three voltage measurement inputs (V1, V2, V3).
Overvoltage
The voltage measurement inputs are suitable for measurements in networks where overvoltages of overvoltage category 300V CATIII (measurement voltage surge 4kV) can occur.
Frequency
The UMG 96RM-PN requires the mains frequency for the measurement and calculation of measured values.
The UMG 96RM-PN is suitable for measuring in the frequency range from 45 to 65 Hz.
Fuse
Circuit breaker
L1
L2
L3
N
Fig. Example connection for measuring voltage.
18
UMG 96RM-PN
When connecting the voltage to be measured, the following must be observed:
Isolation device
• A suitable circuit breaker must be fitted to disconnect and de-energise the UMG 96RM-PN.
• The circuit breaker must be placed in the vicinity of the UMG 96RM-PN, be marked for the user and easily accessible.
• The circuit breaker must be UL/IEC certified.
c
Attention!
Voltages that exceed the allow nominal network voltages must be connected via a voltage transformer.
c
Attention!
The UMG 96RM-PN is not suitable for measuring DC voltages.
Overcurrent protection device
• An overcurrent protection device must be used for line protection.
• For line protection, we recommend an overcurrent protection device as per the technical specifications.
• The overcurrent protection device must be suitable for the line cross section used.
• The overcurrent protection device must be UL/IEC certified.
• A circuit breaker can be used as an isolating and line protection device. The circuit breaker must be UL/IEC certified.
• Measured voltages and measured currents must derive from the same network.
c
Attention!
The voltage measurement inputs on the UMG 96RM-PN are dangerous if touched!
19
UMG 96RM-PN
Connection schematics, voltage measurement
• 3p 4w (addr. 509= 0), factory default setting
L1
L2
L3
N
V1 V2 V3 V
N
Fig. System with three phase conductors and a neutral conductor.
• 3p 4u (addr. 509 = 2)
L1
L2
L3
• 3p 4wu (addr. 509 = 1)
L1
L2
L3
N
V1 V2 V3 V
N
Fig. System with three phase conductors and a neutral conductor. Measurement made with a voltage transformer.
• 3p 2u (addr. 509 = 5)
L1
L2
L3
V1 V2 V3 V
N
Fig. System with three phase conductors without a neutral conductor. Measured values which require an N refer to a calculated N.
20
V1 V2 V3 V
N
Fig. System with three phase conductors without a neutral conductor. Measurement made with a voltage transformer. Measured values which require an N refer to a calculated N.
• 1p 2w1 (addr. 509 = 4)
L1
N
V1 V2 V3 V
N
Fig. Measured values derived from voltage measurement inputs V2 and V3 are taken to be zero and are not calculated.
• 1p 2w (addr. 509 = 6)
L1
L2
V1 V2 V3 V
N
Fig. TN-C system with single-phase threeconductor connection. Measured values derived from voltage measurement input V3 are taken to be zero and are not calculated.
UMG 96RM-PN
• 2p 4w (addr. 509 = 3)
L1
L2
L3
N
V1 V2 V3 V
N
Fig. System with equal loading of the phases.
The measured values for voltage measurement input V2 are calculated.
• 3p 1w (addr. 509 = 7)
L1
L2
L3
L1
L2
L3
L1
L2
L3
N
V1 V2 V3 V
N
Fig. 3 systems with equal loading of the phases.
21
UMG 96RM-PN
Current measurement using I1 to I4
The UMG 96RM-PN is intended for the connection of current transformers with secondary currents of ../1A and ../5A, via terminals I1-I4. The factory default for the current transformer ratio is 5/5A and must be adapted to the current transformer employed if necessary.
Direct measurement without a current transformer is not possible with the UMG 96RM-PN.
Only AC currents can be measured - DC currents cannot.
Current measurement input I4 only produces an apparent current measurement, due to there being no multiplier with a voltage. Power measurements are therefore not possible with input I4.
c
22
Attention!
The current measurement inputs are dangerous to touch.
Load
Fig. Current measurement (I1-I3) via current transformers (connection example)
m
The attached screw-type terminal must be fixed using the two screws on the device!
L1
L2
L3
N
UMG 96RM-PN
c
Earthing of current transformers!
If a connection is provided for the earthing of secondary windings, then it must be connected to the earth.
m
Attention!
The UMG 96RM-PN is not suitable for measuring DC voltages.
C
It is not necessary to configure a connection schematic for measurement input I4.
Fig. Current measurement (I4) via current transformers (connection example)
23
UMG 96RM-PN
Current direction
The current direction can be individually corrected via the existing serial interfaces or on the device for each phase.
If incorrectly connected, a subsequent re-connection of the current transformer is not required.
c
Attention!
Residual current monitoring is performed using the terminals I5 and I6 (cf. page
30). There is no directional sensitivity of the residual currents of the network or load sides (not directionally sensitive).
With residual current monitoring (RCM) there is no directional sensitivity of the residual currents on the network or load sides (not directionally sensitive).
c
Earthing of current transformers!
If a connection is provided for the earthing of secondary windings, then it must be connected to the earth.
c
Current transformer connections!
The secondary connection of the current transformer must be short circuited on this before the current feed to the UMG 96RM-
PN is disconnected!
If a test switch, which automatically shortcircuits the secondary wires of the current transformer, is available then it is sufficient to set this to the "Test" position insofar as the short-circuiting device has been checked beforehand.
24 c
Open-circuit current transformers!
High voltage spikes that are dangerous to touch can occur on current transformers that are driven with open-circuit secondary windings!
With "safe open-circuit current transformers" the winding insulation is rated such that the current transformer can be driven open. However, even these current transformers are dangerous to touch when they are driven open-circuit.
c
Attention!
The UMG96RM is only approved for measuring current with a current transformer.
UMG 96RM-PN
25
UMG 96RM-PN
Connection schematics, current measurement (I1-I3)
• 3p 4w (addr. 510= 0), factory default setting
L1
L2
L3
N
• 3p 2i (addr. 510 = 1)
L1
L2
L3
N
I1 I2 I3
Fig. Measurement in a three-phase network with unequal loading.
• 3p 2i0 (addr. 510 = 2)
L1
L2
L3
I1 I2 I3
Fig. System with equal loading of the phases.
The measured values for current measurement input I2 are measured.
• 3p 3w3 (addr. 510 = 3)
L1
L2
L3
I1 I2 I3
Fig. The measured values for current measurement input I2 are calculated.
26
I1 I2 I3
Fig. Measurement in a three-phase network with unequal loading.
• 3p 3w (addr. 510 = 4)
L1
L2
L3
N
I1 I2 I3
Fig. System with equal loading of the phases.
The measured values for current measurement inputs I2 and I3 are calculated.
• 1p 2i (addr. 510 = 6)
L1
L2
I1 I2 I3
Fig. Measured values derived from current measurement input I3 are taken to be zero and are not calculated.
UMG 96RM-PN
• 2p 4w (addr. 510 = 5)
L1
L2
L3
N
I1 I2 I3
Fig. System with equal loading of the phases.
The measured values for current measurement input I2 are calculated.
• 1p 2w (addr. 510 = 7)
L1
N
I1 I2 I3
Fig. Measured values derived from current measurement inputs I2 and I3 are taken to be zero and are not calculated.
27
UMG 96RM-PN
Connection schematics, current measurement (I1-I3)
• 3p 1w (addr. 510 = 8)
L1
L2
L3
L1
L2
L3
L1
L2
L3
Ammeter
If you wish to measure the current not only with the UMG
96RM but rather with an ammeter too, the ammeter must be connected to the UMG 96RM-PN in series.
UMG
S
1
A
I
S
2
I1 I2 I3
Fig. 3 systems with equal loading of the phases.
Einspeisung
Supply
(k)S
1
(K)P
1
Verbraucher
Consumer
S
2
(l)
P
2
(L)
Fig. Current measurement with an additional ammeter (example).
28
UMG 96RM-PN
Total current measurement
If the current measurement is done via two current transformers, the overall transformation ratio of the current transformers must be programmed into the UMG 96RM-PN.
Example: The current is measured via two current transformers. Both current transformers have a transformation ratio of 1000/5A. The summation measurement is performed using a total current transformer 5+5/5A.
UMG
I
S
1
S
2
The UMG 96RM-PN must then be setup as follows:
Primary current: 1000A + 1000A = 2000A
Secondary current: 5A
Einspeisung 1
Supply 1
Einspeisung 2
Supply 2
P
1
P
2
1S
1
1S
2
2S
1
2S
2
1P
1
(K)
(L)
1P
2
1S
1
(k)
(l)
1S
2
2S
1
(k)
(l)
2S
2
2P
1
(K)
(L)
2P
2
Verbraucher A
Consumer A
Verbraucher B
Consumer B
Fig. Current measurement via a total current transformer
(example).
29
UMG 96RM-PN
Analogue inputs
The UMG 96RM-PN has two analogue inputs, each of which can be used for a residual current measurement or a temperature measurement. A measurement is performed here via terminals 32-34 (Input 1) and 35-37
(Input 2).
c
Attention!
Operating equipment connected to the analogue inputs must feature reinforced or double insulation to the mains supply circuits!
The analogue inputs can be used either for residual current measuring or temperature measuring, per the following table:
Measurement
Temperature
Residual current
Terminal
32/34 (Input 1) and
35/37 (Input 2)
32/33/34 (Input 1) and
35/36/37 (Input 2)
Example - temperature sensor:
A temperature sensor in close proximity to non-isolated mains cables should measure within a 300V CAT III network.
Remedy:
The temperature sensor must be equipped with reinforced or double insulation for 300V CAT III. This equates to a test voltage for the temperature sensor of
3000V AC (duration 1 min.).
Example - residual current transformer:
A residual current transformer should measure on isolated mains cables within a 300V CAT III network.
Remedy:
The insulation of the mains cables and the insulation of the residual current transformer must fulfil the basic insulation requirements for 300V CAT III. This equates to a test voltage of 1500V AC (duration 1 min.) for the insulated mains cables and a test voltage of 1500 V
AC (duration 1 min.) for the residual current transformer.
30
UMG 96RM-PN
Residual current monitoring (RCM) via I5, I6
The UMG 96RM-PN is suitable for use as a residual current monitoring device (RCM) as well as for monitoring
AC, pulsing DC, and DC.
The UMG 96RM-PN can measure residual currents in accordance with IEC/TR 60755 (2008-01) of type A and type B.
The connection of suitable external residual current transformers with a rated current of 30 mA is performed via the residual current transformer inputs I5 (terminals
32-34) and I6 (terminals 35-37).
C
Residual current transformer ratio
The GridVis software included in the scope of the delivery can be used to individually program the residual current transformer inputs' transformer ratios.
PE N L1
Fig. Connection example of residual current monitoring via current transformers
L2 L3
31
UMG 96RM-PN
Connection example, residual current monitoring
L1
L2
L3
PEN
N
PE
Residual current transformer
Fig. Example
UMG96RM-PN with residual current monitoring via measuring inputs I5/I6.
L1 L2 L3 N I1 I2 I3 I4
UMG 96RM-PN
I5 I6
Residual current transformer
M
3~
C
It is not necessary to configure a connection schematic for measurement inputs I5 and I6!
32
UMG 96RM-PN
Thermistor input
The UMG 96RM-PN has two thermistor inputs. The temperature measurement is performed here via terminals 32/34 (Input 1) and 35/37 (Input 2).
Do not exceed the total resistance load (sensor + cable) of 4kOhm.
PT100
PT100 m
Use a shielded cable to connect the temperature sensor.
Fig. Example, temperature measurement with a PT100
33
UMG 96RM-PN
RS485 interface
On the UMG 96RM-PN, the RS485 interface is designed as a 2-pin plug contact, which communicates via the
Modbus RTU protocol (see also Programming parameters).
Termination resistors
The cable is terminated with resistors (120Ohm, 1/4W) at the beginning and at the end of a segment.
The UMG 96RM-PN does not contain any termination resistors.
Correct
RS485 bus
A
B
RS485 interface,
2 pin plug contact
Incorrect
120
Ω
34
RS485 bus
A
B
RS485 interface,
2-pin plug contact with termination resistor
(item no. 52.00.008)
Terminal strip in the cabinet.
Device with RS485 interface.
(without termination resistor)
Device with RS485 interface.
(with termination resistor on the device)
UMG 96RM-PN
Screening Cable type
Twisted screened cable should be used for connections via the RS485 interface.
The cable used must be suitable for an environmental temperature of at least 80°C.
• Earth the screens of all cables that lead to the cabinet and at the cabinet entry.
• Connect the screens over a generous area and in a manner that will conduct well, to a low-noise earth.
• Gather the cables mechanically above the earthing clamp in order to avoid damage due to cable movements.
• Use suitable cable glands to feed the cables into the cabinet, for example, armoured conduit couplings.
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)
Maximum cable length
1200m at a baud rate of 38.4k.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Noiseless ground
C
CAT cables are not suitable for bus wiring. Use the recommended cable types for this.
Fig. Screening procedure at cabinet entry.
35
UMG 96RM-PN
Bus structure
• All devices are connected in a bus structure (line) and each device has its own address within the bus (see also Parameter programming).
• Up to 32 subscribers can be connected together in a single segment.
• The cable is terminated with resistors (bus termination
120Ohm, 1/4W) at the beginning and at the end of a segment.
• With more than 32 subscribers, repeaters (amplifiers) must be used to connect the individual segments.
• Devices for which the bus connection is switched on must be under current.
• It is recommended that the master be placed at the end of a segment.
• If the master is replaced with a bus connection, the bus must be switched off.
• Replacing a slave with a bus connection that is either switched on or de-energised can destabilise the bus.
• Devices that are not connected to the bus can be replaced without destabilising the bus.
• The shield has to be installed continuously and needs to be broadly and well conducting connected to an external low voltage (or potential) ground at the end.
T
T
Master
Slave
Speisung notwendig / power supply necessary
T
Busabschluß eingeschaltet / bus terminator on
Slave Slave
T
Repeater
T
Slave Slave
Fig. Bus structure
36
UMG 96RM-PN
Ethernet / ProfiNet interface
The Ethernet network settings should be specified by the network administrator and set on the UMG 96RM-
PN accordingly.
If the network settings are not known, the UMG 96RM-
PN may not be integrated into the network through the patch cable.
The UMG 96RM-PN has two identical Ethernet interfaces.
This allows another Ethernet/ProfiNet terminal to be operated via the second interface, thus reducing outlay on cabling.
LEDs for the Ethernet interfaces
LED 1 LED 2
LED Colour Function
1 Green Lights up when there is a connection (a link)
2 Yellow Lights up intermittently when there is network activity
Ethernet connection
PC switch for PLC
Ethernet connection
Ethernet /
ProfiNet device
ProfiNet status LED bar
LED Status Function
RDY Off Device is not powered
RDY Flashing Device is being initialised
RDY
SF
BF
BF
BF
On
On
On
Device is ready for operation
Configuration error or system error
Flashing No ProfiNet connection,
Off
No connection in spite of physical connection
Connection to the PLC established / active
37
UMG 96RM-PN
m
Attention!
Connection of the UMG96RM-PN to the Ethernet may only be carried out after consulting the network administrator!
PROFIenergy / Entity Class 2
The UMG 96RM-PN is certified as
Entity Class 2 (measurement functionality) for use of the PROFIenergy
Profile V1.1.
C
Dynamic Configuration Protocol (DCP)
This function assigns unique addresses and names to the subscribers of a
ProfiNet system, and is prioritised by the UMG 96RM-PN.
• A PROFIenergy device provides a defined set of functions and information, helping to standardise and reduce configuration and installation effort.
Device master file
The device master file, abbreviated as GSD file, describes the ProfiNet characteristics of the UMG96RM-
PN. The GSD file is required, for example, by the configuration program of the PLC.
The device master file for the UMG96RM-PN has the file name "GSDML-V2.31-JanitzaelectronicsGmbH-
UMG96RM-PN-xxxxxxxx.xml" and is included on the data carrier as part of the scope of the delivery.
• PROFIenergy is a profile for energy management in production systems, which is based on ProfiNet.
• Energy consumers within the system can therefore be controlled and monitored with PROFlenergy using open and standardised commands.
• With automated comparison of functionality between the ProfiNet control centre and the UMG, additional configuration and installation is rendered unnecessary.
38
UMG 96RM-PN
Digital in-/outputs
The UMG 96RM-PN has 2 digital outputs and either
3 digital inputs or outputs, which are subdivided into two groups (see Figure, page 40). This is based on the rule that only the
whole of Group 2 (connection 28 to
31) can function either as an input or output; differing assignments within the same group are not possible!
Digital outputs, Group 2
• The status of the inputs and outputs in Group 2 is indicated by the associated LED (cf. chapter LED status bar).
Digital outputs, Group 1
• The status indicator appears on the display at K1 or
K2
• The status indicator on the display is not dependent on an inversion being activated (NC / NO)
Source e.g.
Comparator group
Inverter
Digital output 3
K1/K2 display status indicator
C
The digital outputs of group 2 are compatible.
not AC
Source e.g.
Comparator group
Inverter
Digital output 1
39
UMG 96RM-PN
Input/output byte coding
(Input/output data of the ProfiNet „digital IO“ module)
• If the digital inputs/outputs in group 2 are configured as inputs, bit-oriented coding of the statuses occurs
(bit 0 to 2). In this case, coding corresponds to the digital inputs with:
Bit 0 1 2 3 4 5 6 7
Input 3: 1 = signal is present
Input 2: 1 = signal is present
Input 1: 1 = signal is present
• The digital outputs can be controlled by setting the corresponding bits.
• If, for example, the digital inputs/outputs in group 2 are configured as outputs, bit-oriented coding occurs within bits 0 to 4:
Bit 0 1 2 3 4 5 6 7
Output 5: 1 = signal set
Output 4: 1 = signal set
Output 3: 1 = signal set
Output 2: 1 = signal set
Output 1: 1 = signal set
40
UMG 96RM-PN
Digital outputs
These outputs are galvanically separated from the analysis electronics using optocouplers. The digital outputs have a common supply.
• The digital outputs of group 1 can switch AC and DC loads. The digital outputs of group 2 can
not switch
AC loads.
• The digital outputs are not short-circuit proof.
• Connected cables that are longer than 30m must be shielded when laid.
• An external auxiliary voltage is required.
• The digital outputs of Group 1 can be used as pulse outputs.
• The digital outputs can be controlled via Modbus and
ProfiNet.
• The digital outputs
of Group 1 can output results of comparators.
Group 1
~
Fig. Connection of digital/pulse outputs
Group 2
~
41
UMG 96RM-PN
Example DC connection
m
Attention!
Digital outputs are not short-circuit proof!
UMG 96RM-PN
13
Digital Ouput 1
14
C
Functions for the digital outputs can be adjusted clearly in the GridVis software.
A connection between the UMG 96RM-PN and the PC via an interface is required to use the GridVis software.
Digital Ouput 2
15
28
Digital Ouput 3
29
C
When using the digital outputs of Group 1 as pulse outputs, the auxiliary voltage (DC) must have a max. residual ripple of 5%.
C
Digital Ouput 4
30
T h e d i g i t a l i n p u t s o r o u t p u t s o f
Group 2 cannot be configured as pulse inputs/outputs. It is possible to use them as switch inputs/outputs (ProfiNet/
Modbus, tariff switching).
Digital Ouput 5
31
Fig. Example for two relays connected to the digital outputs
42
External auxiliary voltage
+
24V DC
-
DC
DC
UMG 96RM-PN
Digital inputs
When Group 2 is assigned as inputs, the UMG96 RM-
PN has three digital inputs, each of which can have a signal generator connected to it. If there is a signal, the associated LED lights up green.
External auxiliary voltage
-
24V DC
+
An input signal is detected on a digital input if a voltage of at least 10V and maximum 28V is applied and a current of at least 1mA and a maximum of 6mA is flowing. Wiring longer than 30m must be screened.
Note the correct polarity of the supply voltage!
UMG 96RM-PN
Digital inputs 1-3
2k21
28
29
Digital
Input 1
S1
-
+
2k21
2k21
30
Digital
Input 2
S2
Group 2
2k21
2k21
31
Digital
Input 3
S3
2k21
2k21
Fig. Connection example of digital inputs.
Fig. Example for the connection of external switch contacts S1 and S2 to digital inputs 1 and 2.
43
UMG 96RM-PN
LED status bar
The LED status bar on the back of the device shows the different statuses of the inputs and outputs.
Digital inputs
The LED assigned to the input lights up
green if a signal of at least 1mA is fl owing on this interface.
Digital input/output 1/3
Digital input/output 2/4
Digital input/output 3/5
Digital outputs
The LED assigned to the output lights up red if the output is set as active - irrespective of whether there is an onwards connection to this interface.
Fig. LED status bar for the inputs or outputs
C
T h e d i g i t a l i n p u t s o r o u t p u t s o f
Group 2 cannot be confi gured as pulse inputs/outputs. It is possible to use them as switch inputs/outputs (Profi Net/
Modbus, tariff switching).
44
UMG 96RM-PN
Operation
Programming mode
The UMG 96RM-PN is operated with buttons 1 and 2, whereby the following distinctions are made:
• short press of button 1 or 2: next step (+1)
• long press of button 1 or 2: previous step (-1)
Measured values and programming data are presented on a liquid crystal display.
Programming mode displays and allows for the modification of the settings required for operation of the UMG 96RM-PN. Pressing and holding buttons 1 and 2 at the same time for approx. 1 second takes you
(after password prompt) to Programming mode. If no user password has been set up, you are taken directly to the first Programming menu. Programming mode is indicated on screen by the text "PRG".
A distinction is made between Display mode and
Programming mode. The requirement to enter a password makes it possible to prevent the programming data from being changed accidentally.
Button 2 then allows you to switch between the following
Programming menus:
Display mode
- Current transformer
- Voltage transformer
- Parameter list
- Device TCP/IP address
- Subnet mask
- Gateway address
In Display mode, using buttons 1 and 2, you can scroll through the programmed measured value screens. In the factory, all measured value screens listed in Profile
1 can be accessed. Up to three measured values are displayed on each measured value screen. The measured value rotation allows selected measured value screens to be displayed in turn after a configurable rotation time.
If you are in Programming mode and no button is pressed around 60 seconds or if buttons 1 and 2 are pressed simultaneously for around 1 second, the UMG
96RM-PN returns to Display mode.
45
UMG 96RM-PN
Delivery
Max. value, HT/Consumption
Min. value NT/Delivery
Mean value
Programming mode
Summation measurement
Phase conductor-
Phase conductor
Password
CT: Current transformer
VT: Voltage transformer
K1: Output 1
K2: Output 2
Button 2
Button 1
46
UMG 96RM-PN
Parameters and measured values Example of a parameter screen
All of the parameters required for operation of the UMG
96RM-PN, such as the current transformer data, and a selection of frequently required measured values are stored in the table.
The contents of most addresses can be accessed via the serial interface and with the buttons on the UMG
96RM-PN.
On the display of the UMG
96RM-PN the contents of address "000" is displayed as "001'. This parameter describes (according to the list) the device address of the UMG 96 RM-PN (in this case "001") within a bus.
On the device you can only enter the first 3 significant digits of a value. Values with more digits can be entered in GridVis.
The device only ever displays the first 3 significant digits of the value.
Selected measured values are summarised in measured value screen profiles, and can be displayed in Display mode with buttons 1 and 2.
Example of a measured value screen
In this example, the display of the UMG 96RM-PN shows each of the voltages L to N as 230V. Transistor outputs
K1 and K2 are active and a current can flow.
The current measured value screen profile, the current screen rotation profile and date and time can only be read and modified via the RS485 interface.
47
UMG 96RM-PN
Button functions
Display mode
Switch mode
At same time
Scroll
Short
Long
Measured values
A(+1)
Measured values
A(-1)
Measured values
B ...
Long Short
You can find an overview of the measured value screens in the chapter "Overview of measured value screens".
Password
Programming mode
Switch mode
Programming menu 1
(flashing)
Short
Long
(flashing)
At same time
Scroll
Programming menu +1
...
Programming menu -1
Programming
Confirm selection
Short: Number +1
Long: Number -1
Short: Value x 10
(move comma right)
Long: Value /10
(move comma left)
48
UMG 96RM-PN
Configuration
Connecting the supply voltage
The supply voltage must be connected for the configuration of the UMG 96RM-PN.
c
Attention!
If the supply voltage does not correspond to the voltage indicated on the rating plate, this may lead to malfunctions and severe damage to the device.
The supply voltage level for the UMG 96RM-PN is specified on the rating plate.
If no screen appears, check whether the supply voltage is within the rated voltage range.
C
The adjustable value 0 for the primary current transformer does not produce any meaningful work values, and must not be used.
Current and voltage transformer
A current transformer of 5/5A is set in factory. Only if voltage transformers are connected does the preprogrammed voltage transformer ratio need modifying. m
Devices based on automatic frequency detection require approx. 5 seconds to determine the mains frequency. During this time, the measured values do not comply with the promised measurement uncertainty.
When connecting voltage transformers, pay attention to the measured voltage specified on the rating plate of the UMG 96RM-PN!
C
Prior to commissioning potential production dependant contents of the energy counter and min/max values have to be deleted.
49
UMG 96RM-PN
C
Current and voltage transformer
The GridVis software can be used to individually program the transformation ratios for each current or voltage measurement input.
Only the transformation ratio for the respective group of current measurement inputs I1-I3 or voltage measurement inputs
V1-V3 can be set on the device.
The transformation ratio of current trans-
former input I4 and the residual current
transformer inputs I5, I6 must be set in the
GridVis software.
Current transformer input I4
Current transformer input I4 only produces an apparent current measurement, due to there being no multiplier with a voltage.
Power measurements with the input are therefore not possible. The transformation ratio can be set in the GridVis software.
Fig. Screen for configuration of the current and voltage transformer in the GridVis software.
C
If the device is operated within a PROFINET environment, parameters listed in the GSD file can also be configured via the PLC.
50
UMG 96RM-PN
Programming the current transformer for I1-I3
Switch to Programming mode:
• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously. If a user password has been set, then the password prompt appears with "000". The first digit of the user password flashes and can be modified with button 2. Pressing button 2 selects the next digit (it starts flashing). If the correct combination of number has been entered or if no user password was set, you are taken to Programming mode.
• The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
• The selection is confirmed with button 1.
• The first digit of the input range for the primary current flashes.
Enter the current transformer secondary current:
• Only 1A or 5A can be set as the secondary current.
• Use button 1 to select the secondary current.
• Modify the flashing digit with button 2.
Exit Programming mode:
• Exit Programming mode by pressing button 1 and 2 at the same time.
Enter the current transformer primary current:
• Modify the flashing digit with button 2.
• Use button 1 to select the next number you wish to modify. The selected digit to be modified flashes. If the entire number flashes, the decimal point can be moved with button 2.
51
UMG 96RM-PN
Programming the voltage transformer
• Switch to programming mode as described.
The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
• Button 2 is used to switch to the Voltage transformer settings.
• The selection is confirmed with button 1.
• The first digit of the input range for the primary voltage flashes. The same as assigning the current transformer ratio from the primary to the secondary current, the ratio can be set from the primary to the secondary voltage of the voltage transformer.
Current transformer, primary
Programming mode
Unit indicator
Current transformer, secondary
Current transformer symbol
Voltage transformer, primary
Programming mode
Unit indicator
Voltage transformer, secondary
Voltage transformer symbol
52
Programming parameters
Switch to Programming mode
• Switch to programming mode as described.
The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
• Button 2 is used to switch to the Voltage transformer settings. Repeatedly pressing button 2 displays the first parameter in the parameter list.
Modify a parameter
• Confirm the select with button 1.
• The last selected address is displayed with the associated value.
• The first digit of the address flashes and can be modified with button 2. Button 1 is used to select the digit, which is then in turn modified with button 2.
Modify a value
• Once the desired address has been set, a digit of the value can be selected with button 1 and modified with button 2.
Exit Programming mode
• Exit Programming mode by pressing button 1 and 2 at the same time.
UMG 96RM-PN
Fig. Password prompt
If a password was set, it can be entered with buttons 1 and 2.
Fig. Current transformer programming mode
Buttons 1 and 2 can be used to modify the primary and secondary current (cf. page 51).
Fig. Voltage transformer programming mode
Buttons 1 and 2 can be used to modify the primary and secondary voltage (cf. page 52).
Fig. Parameter screen programming mode
Buttons 1 and 2 can be used to modify the individual parameters (cf. page 47).
53
UMG 96RM-PN
TCP/IP configuration
Each device in an Ethernet has a unique TCP/IP address, which can be assigned manually for the UMG 96RM-PN.
The 4-byte-long device address (Byte 0 to 3) is appended within the TCP/IP configuration with the subnet mask and gateway details.
If the device is integrated into a ProfiNet environment, however, the address is generally assigned by the DCP function.
Set the device's TCP/IP address (addr)
• Switch to programming mode as described.
The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
• Pressing button 2 three times takes you to the TCP/IP settings for device addressing.
• Select the desired digit using button 1. Selection is indicated by the digit flashing.
• The selected digit can be adjusted with the 2 button.
• Use button 1 to select the next digit and set it with button 2 again.
• Once Byte 0 of the TCP/IP address is set, bytes 1 to 3 of the address can be set with button 1. Then the display jumps back to Byte 0 (
none of the digits are flashing).
54
Designation
Byte identifier of the address (e.g. Byte 0)
Address value, Byte 0
Fig. TCP/IP address, Byte 1
A TCP/IP address consists of 4 bytes with the following structure:
Byte 0 Byte 1 Byte 2 Byte 3
Example: xxx.xxx.xxx.xxx
192.168.003.177
Fig. TCP/IP address
Byte 2, value 003
Fig. TCP/IP address
Byte 3, value 177
UMG 96RM-PN
Set the subnet mask (SUb):
• In programming mode, button 2 takes you to the Subnet mask settings (SUb on screen).
• Use the button 1 to select the desired digit and set it with button 2. Repeat this step for every digit in Byte
0 to 3, the same as when setting the device's TCP/
IP address.
• Once the display returns to Byte 0 (
none of the digits flashing) you can set the gateway.
Set the gateway address (GAt):
• In programming mode, button 2 takes you to the Gateway address settings (GAt on screen).
• Use the 1 and 2 buttons to set the desired gateway address in Byte 0 to 3, in the same way as the above descriptions.
Fig. Subnet mask (SUb),
Byte 0, value 255
Fig. Gateway (GAt),
Byte 0, value 192
m
Attention!
Connection of the UMG96RM-PN to the Ethernet may only be carried out after consulting the network administrator!
C
Dynamic Configuration Protocol (DCP)
This function assigns unique addresses and names to the subscribers of a
ProfiNet system, and is prioritised by the UMG 96RM-PN.
C
Changes are only applied after exiting programming mode.
55
UMG 96RM-PN
RS485 device address (addr. 000) RS485 baud rate (addr. 001)
If multiple devices are connected together via the RS485 interface, then a Master device is only able to distinguish between these devices based on their device address.
Therefore each device on a network must have a different device address. Addresses can be set in the range from
1 to 247.
A common baud rate can be set for the RS485 interfaces.
A common baud rate must be selected in the network.
Address 003 can be used to set the number of stop bits
(0=1Bit, 1=2Bits). Data Bits (8) are preset to fixed values.
C
The setting range for the device address is between 0 and 255. The values 0 and 248 to 255 are reserved and must not be used.
Setting
0
3
4
1
2
Baud rate
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
115.2 kbps (factory setting)
56
User password (addr. 050)
To make it harder to accidentally modify the programming data, a user password can be set. You can only switch to the following Programming menus after entering the correct user password.
No user password is set in the factory. In this case, the Password menu is skipped and you are taken immediately to the Current transformer menu.
If a user password has been set, then the Password menu appears with "000" on the screen.
The first digit of the user password flashes and can be modified with button 2. Pressing button 1 selects the next digit (it starts flashing).
Only when the right combination of numbers is entered, takes you to the Programming menu for the current transformer.
Forgot password
If you no longer remember your password, you can only delete it using the GridVis PC software.
In order to do so, connect the UMG96RM-PN to the PC with a suitable interface. More information can be found in the GridVis assistant.
UMG 96RM-PN
57
UMG 96RM-PN
Parameters
Averaging method
Mean value
Averages for the current, voltage, and power measured values are calculated over an adjustable period.
The averages are identified by a bar over the top of the measured value.
The averaging time can be selected from a list of 9 fixed averaging times.
The used exponential averaging method achieves at least 95% of the measured value after the set averaging time.
Min. and max. values
Current averaging time (addr. 040)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Setting
0
3
4
1
2
5
6
7
8
Averaging time/Sec.
5
10
15
30
60
300
480 (factory setting)
600
900
All measured values are measured and calculated every
10/12 periods. Min. and max. values are determined for most measured values.
The min. value is the lowest measured value measured since the last time the values were cleared. The min. value is the lowest value measured since the last time the values were cleared. All min. and max. values are compared with the associated measured values, and overwritten if the value is under the min. value or over the max. value.
The min. and max. values are stored every 5 minutes to an EEPROM without the date and time. This means that, if there is failure of the supply voltage, only the min. and max. values for the last 5 minutes can be lost.
Clearing the min. and max. values (addr.506)
If "001" is written to address 506, all min. and max. values are cleared simultaneously.
58
UMG 96RM-PN
Mains frequency (addr. 034)
To automatically determine the mains frequency, a voltage L1-N of greater than 10Veff must be applied to voltage measurement input V1.
The sampling rate for the current and voltage inputs is then calculated from the mains frequency.
Setting range: 0, 45 - 65
0 = Frequency determined automatically
The mains frequency is determined from the measured voltage.
45 - 65 = Fixed frequency
The mains frequency is preset to a fixed value.
If the measured voltage is absent, it is not possible to determine the mains frequency, which makes it impossible to calculate the sampling rate. The acknowledgeable error message "500" appears.
Voltage, current, and all other values derived from these are calculated and still displayed based on the last frequency measurement or on possible line interfaces.
However, these determined measured values are no longer subject to the specified level of accuracy.
Once the frequency can be measured again, the error message disappears automatically approx. 5 seconds after the voltage returns.
The error is not displayed if a fixed frequency is set.
59
UMG 96RM-PN
Power meters Resetting energy meters (addr. 507)
The UMG 96RM-PN has power meters for effective energy, reactive energy, and apparent energy.
The effective, apparent, and reactive energy meters can only be reset as one.
To reset the energy meters, address 507 must be described with "001".
Reading off the effective energy
Total effective energy
The effective energy shown
in this example is:
12 345 678 kWh
The effective energy shown
in this example is:
134 178 kWh
60
C
Prior to commissioning potential production dependant contents of the energy counter and min/max values have to be deleted.
C
Resetting the power meters discards the data in the device.
To avoid possible data loss, you should read out and store these measured values with the GridVis software.
UMG 96RM-PN
Harmonics Total Harmonic Distortion (THD)
Harmonics are the integer multiples of a fundamental oscillation.
On the UMG 96RM-PN the fundamental oscillation of the voltage must be in the range from 45 to 65 Hz. At this fundamental oscillation the calculated harmonics relate to the voltages and currents.
Harmonics up to 40 times the fundamental oscillation are captured.
THD is the ratio of the effective value of the harmonics to the effective value of the fundamental oscillation.
Total harmonic distortion of the current (THDI):
The harmonics for the currents are given in amps, the harmonics for the voltages in volts.
Total harmonic distortion of the voltage (THDU):
Number of harmonic
Phase L3
Current harmonic
Value
Fig. Screen for the 15th harmonic of the current in phase L3 (example).
C
Harmonics are not displayed in the factory default setting.
Phase L3
Voltage
Value
Fig. Screen for the Total harmonic distortion (THD) of the voltage from phase L3 (example).
61
UMG 96RM-PN
Measured value rotation Rotation time (addr. 039)
All measured values are calculated every 10/12 periods, and are available once a second in the measured value screens. Two methods are available for bringing up the measured value screens:
Setting range: 0 to 60 seconds
If 0 seconds is set, then there is no rotation between the measured value screens selected for measured value rotation.
The rotation time applies to all screen rotation profiles.
• The automatically rotating display of selected measured value screens, referred to here as
"measured value rotation".
• Choosing a measured value screen from a selected screen profile, using buttons 1 and 2.
Screen rotation profile (addr. 038)
Setting range: 0 to 3
0 - Screen rotation profile 1, preassigned.
1 - Screen rotation profile 2, preassigned.
2 - Screen rotation profile 3, preassigned.
3 - Screen rotation profile, customer-specific.
Both methods are available simultaneously. Measured value rotation is active when at least one measured value screen is programmed with a rotation time greater than
0 seconds.
Pressing a button allows you to scroll through the measured value screens for the selected screen profile. If no button is pressed for around 60 seconds, the device switches to measured value rotation, and the measured values from the selected screen rotation profile programmed measured value screens are displayed in succession.
Measured value screens
After the power is restored, the UMG 96RM-PN displays the first measured value table from the current screen profile. So that the selection of measured values to be displayed remains clear, at the factory only one part of the available measured values is pre-programmed to be called up in the measured value screen. If you desire to display other measured values on the screen of the UMG
96RM-PN, select a different screen profile.
62
UMG 96RM-PN
Screen profile (addr. 037)
Setting range: 0 to 3
0 - Screen profile 1, fixed preassigned value.
1 - Screen profile 2, fixed preassigned value.
2 - Screen profile 3, fixed preassigned value.
3 - Screen profile, customer-specific.
C
The customer-specific profiles (screen rotation profile and screen profile) can only be programmed via the GridVis software.
C
Profile setting
The GridVis software provides a clear overview of the profiles (screen rotation profile and screen profile). In the software the Device configuration can be used to configure the profiles; customer-specific screen profiles can also be programmed.
A connection between the UMG 96RM-PN and the PC is required to use the GridVis software.
Fig. Profile setting screen in the GridVis software.
63
UMG 96RM-PN
Direction of the rotating field LCD contrast (addr. 035)
The direction of the rotating field of the voltages and the frequency of phase L1 are displayed in a screen.
The direction of the rotating field specifies the phase sequence in three-phase power grids. A “right-hand rotation field” usually exists.
In the UMG 96RM-PN, the phase sequence is tested and indicated on the voltage measurement inputs. A movement of the character string in a clockwise direction means there is a “right-hand rotation field” and an anticlockwise movement indicates a “left-hand rotation field”.
The direction of the rotating field is only determined when the measuring and supply voltage inputs are fully connected. If a phase is missing or if two identical phases are connected, the direction of the rotating field is not established and the character string is stationary on the screen.
The preferred direction for observing the LCD display is from below. The contrast of the LCD display can be adjusted by the user. The contrast can be set in the range from 0 to 9 in steps of 1.
0 = Characters very bright
9 = Characters very dark
Factory default setting: 5
Backlight
The backlight enables good legibility of the LCD display under poor visual conditions. The brightness can be controlled by the user in the range from 0 to 9 in steps of 1.
The UMG 96RM-PN has two different types of backlight:
- Operating lighting
- Standby lighting
Fig. Screen for the mains frequency (50.0) and the direction of
Fig. Direction of the rotating field not detectable.
UMG 96RM-PN
Operating lighting (addr. 036):
The operating lighting is activated by the push of a button or upon restart.
Standby lighting (addr. 747)
This type of backlight is activated after a customisable period of time (addr. 746). If there are no button presses during this period, the device switches to standby lighting.
If buttons 1 - 3 are pressed, the device switches to operating lighting and the defined period begins again from scratch.
C
DCP "Identify Station" signal of the PLC:
If the PLC sends control signals for device identification to the device, the backlight switches between maximum and minimum brightness (causing the display lighting to "flash"). To achieve this there is usually a "Flash" button in the PLC.
If the brightness values are the same for both types of lighting then no change is discernible between the backlight and standby lighting.
Addr. Description
036 Brightness for operating lighting
746 After how long to switch to standby lighting
747 Brightness for standby lighting
Setting range
0 to 9
60 to 9999 secs
0 to 9
Default
6
900 secs
0
0 = Minimum brightness, 9 = Maximum brightness
65
UMG 96RM-PN
Time logging
Operating hours counter
The UMG 96RM-PN logs the operating hours and the total running time of each comparator, whereby the time
• for the operating hours is measured with a resolution of 0.1 hrs and displayed in hours or
• the total running time of the comparators is displayed in seconds (when 999,999 secs is reached, the number is displayed in hours).
The operating hours counter measures the time in which the UMG 96RM-PN captures and displays measured values.
The time for the operating hours is measured with a resolution of 0.1 hrs and displayed in hours.
The operating hours counter cannot be reset.
Total running time, comparator
For a query using the measured value screens, the times are indicated with the numbers 1 to 6:
None = Operating hours counter
1 = Total running time, Comparator 1A
2 = Total running time, Comparator 2A
3 = Total running time, Comparator 1B
4 = Total running time, Comparator 2B
5 = Total running time, Comparator 1C
6 = Total running time, Comparator 2C
A maximum of 99,999.9 hrs (=11.4 years) can be shown on the measured value screen.
The total running time of a comparator is the sum of all times for which there was a threshold value violation in the comparator result.
The total running times of the comparators can only be reset via the GridVis software. The reset is performed for all total running times.
Fig. Measured value screen
Operating hours counter
The UMG 96RM-PN shows the number 140.8 hrs in the operating hours counter. This corresponds to 140 hours and 80 industry minutes. 100 industry minutes correspond to 60 minutes. In this example, the 80 industry minutes correspond to 48 minutes.
66
Serial number (addr. 754)
The serial number displayed by the UMG 96RM-PN has six digits and is a part of the serial number displayed on the rating plate.
The serial number cannot be modified.
Serial number indicator
Serial number as stated on the rating plate:
XX00-0000
Software release (addr. 750)
The software for the UMG 96RM-PN is continuously improved and expanded. The software version in the device is identified by a three-digit number, the software release. The software release cannot be modified by the user.
UMG 96RM-PN
67
UMG 96RM-PN
Applying the measuring-circuit voltage
Commissioning
Connecting the supply voltage
• The supply voltage level for the UMG 96RM-PN is specified on the rating plate.
• After applying the supply voltage, the UMG 96RM switches to the first measured value screen.
• If no display appears, check whether the power supply voltage is within the rated voltage range.
Connecting the measured voltage
• Measurement of voltages in networks with over
300VAC to earth must be connected via voltage transformers.
• After connecting the measured voltages, the measured values displayed by the UMG 96RM-PN for the L-N and L-L voltages must correspond to those at the voltage measurement input.
The UMG 96RM-PN is designed for the connection of ..
/1A and .. /5A current transformers.
Only AC currents can be measured via the current measurement inputs - DC currents cannot.
Short circuit all current transformer outputs except for one. Compare the currents displayed by the UMG 96RM with the applied current.
Bearing in mind the current transformer conversion ratio, the current displayed by the UMG 96RM-PN must correspond with the input current.
The UMG 96RM-PN must display approx. zero amperes in the short circuited current measurement inputs.
The current transformer ratio is factory-set to 5/5A and must be adapted to the current transformer used if necessary. m
Attention!
If the supply voltage does not correspond to the voltage indicated on the rating plate, this may lead to malfunctions and severe damage to the device.
m
Attention!
Voltages and currents that are outside the permissible measurement range can cause personal injury and lead to the destruction of the device.
m
Attention!
The UMG 96RM is not suitable for measuring DC voltages.
68
UMG 96RM-PN
Direction of the rotating field Applying the residual current
Check the direction of the rotating field voltage in the measured value display of the UMG 96RM.
A “right-hand” rotation field usually exists.
Connect residual current transformer only to the I5 and
I6 inputs with a rated current of 30mA! Both residual current inputs can measure AC currents, pulsing direct currents and DC currents.
Checking the phase assignment
The phase conductor assignment to the current transformer is correct if a current transformer is short-circuited on the secondary side and the current displayed by the UMG
96RM-PN drops to 0A in the associated phase.
Checking the power measurement
Bearing in mind the current transformer ratio, the residual current displayed by the UMG96RM-PN must correspond with the input current.
The current transformer ratio is factory-set to 1/1A and must be adapted to the residual current transformer used if necessary.
Short-circuit all current transformer outputs except for one and check the displayed power outputs.
The UMG 96RM-PN may only display one power output in the phase with a non-short-circuited current transformer input. If this is not the case, check the connection of the measured voltage and the measuring-circuit current.
If the effective power amount is correct but the sign of the power output is negative, this could have two possible causes:
• S1(k) and S2(l) are reversed at the current transformer.
• Effective energy is being supplied back into the network.
C
The UMG96RM-PN requires the mains frequency for residual current monitoring. For this purpose, the measured voltage should be applied or a fixed frequency should be set.
C
It is not necessary to configure a connection schematic for residual current inputs I5 and I6.
69
UMG 96RM-PN
Failure monitoring (RCM) for I5, I6
The UMG96RM-PN enables continuous monitoring of the connection to the residual current transformer on inputs I5 and I6.
m
The monitoring of the connection to the residual current transformer is only available in the AC mode!
Residual current transformers of Type A must be used for transformer monitoring!
Modbus addr. Value / Function
553 (I5)
554 (I6)
0 = Transformer monitoring, I5 and I6 deactivated
1 = Transformer monitoring, I5 and I6 activated
C
We recommend configuring the residual current measurement settings in GridVis.
If there is an interruption in the connection to the current transformer, this state is recorded in certain registers or indicated in the GridVis software:
Modbus addr. Value / Function
10014 (I5)
10015 (I6)
0 = Connection of the residual current transformer to I5 and I6 error-free
1 = Error in the current transformer connection to I5 and I6
70
UMG 96RM-PN
Checking the measurement Checking the sum powers
Once all voltage and current measurement inputs are properly connected, the signal phase and sum powers are also calculated and displayed properly.
Checking the single phase powers
If a current transformer is assigned to the wrong phase conductor, the associated power will also be measured and displayed incorrectly.
The assignment of phase conductor to current transformer on the UMG 96RM-PN is correct when there is no voltage between the phase conductor and the associated current transformer (primary).
To ensure that a phase conductor on the voltage measurement input is assigned to the right current transformer, you can short-circuit the current transformer in question on the secondary side. The apparent power displayed by the UMG 96RM-PN must be zero in this phase.
If all voltages, currents, and powers for the phase conductor in question are displayed properly, then the sum powers measured by the UMG 96RM must also be correct. For confirmation, the sum powers measured by the UMG 96RM should be compared with the effective and reactive power meter located in the supply.
If the apparent power is displayed correctly but the effective power has a "-" sign, the current transformer terminals are reversed or power is being supplied to the power company.
71
UMG 96RM-PN
RS485 interface
The MODBUS RTU protocol with CRC check on the RS485 interface can be used to access the data from the parameter and the measured value lists.
Address range:
Factory default setting:
1 to 247
1
C
C
The device address is factory set to 1 and the baud rate to 115.2 kbps.
Modbus functions (slave)
04 Read input registers
06 Preset single register
16 (10Hex) Preset multiple registers
23 (17Hex) Read/write 4X registers
The sequence of bytes is high before low byte (Motorola format).
Transmission parameters:
Data bits: 8
Parity: None
Stop bits (UMG 96RM): 2
External stop bits: 1 or 2
Number format: short 16 bit (-2
15 to 2
15
-1) float 32 bit (IEEE 754)
72
Broadcast (address 0) is not supported by the device.
The message length must not exceed
256 bytes.
UMG 96RM-PN
Example: Reading the L1-N voltage
The L1-N voltage is saved in the measured value list at address 19000. The L1-N voltage is available in the FLOAT format.
Address = 01 is approved as the UMG 96RM-PN device address.
The Query Message appears as follows:
The "Response" of the UMG96 RM-PN can appear as follows:
Name Hex Note
Device address 01
Function 03
Start addr. Hi
Start addr. Lo
Ind. Value Hi
Ind. Value Lo
Error check
4A
38
00
02
-
UMG 96RM, address = 1
"Read holding reg."
19000dez = 4A38hex
2dez = 0002hex
Name Hex Note
Device address 01
Function
Byte meter
03
06
Data
Data
Error check (CRC) -
00
E6
UMG 96RM, address = 1
00hex = 00dez
E6hex = 230dez
The L1-N voltage read by address 19000 is 230V.
73
UMG 96RM-PN
Digital outputs
The UMG 96RM-PN has two digital outputs in Group 1.
Another three digital outputs can be set in Group 2.
You can optionally assign different functions to the digital outputs.
The settings of the functions in the confi guration menu must be made using the GridVis software.
24V
DC
=
-
+
K1 K2
=
+
-
S1 S2 S3
=
-
+
K3 K4 K5
13 14 15
Group 1
28 29 30 31
Group 2
Digital inputs/outputs
74
Fig.: Digital outputs of Group 1 and digital inputs/outputs of Group 2
Fig.: GridVis software, confi guration menu
UMG 96RM-PN
Digital output status indicators
The status of the switch outputs of Group 1 is displayed on the display of the UMG 96RM-PN by circle symbols.
Statuses of the digital inputs of Group 2 - as described in the chapter "LED status bar" - are displayed by the rearwards-facing LEDs.
C
Since the display is only updated once a second, status changes in the outputs which are more rapid than this cannot be displayed.
Statuses of the digital outputs of Group 1
Group 1
Status of Digital output 1
Status of Digital output 2
A current of <1mA can flow.
Digital output 1: addr. 608 = 0
Digital output 2: addr. 609 = 0
A current of up to 50mA can flow.
Digital output 1: addr. 608 = 1
Digital output 2: addr. 609 = 1
75
UMG 96RM-PN
Functions of the digital outputs of Group 1
You can optionally assign the following functions to the two digital outputs of Group 1:
Digital output 1
Addr. 200 = 0
Addr. 200 = 1
Addr. 200 = 2
Addr. 200 = 5
Result of Comparator group 1
Pulse output
Value from external source Modbus
Value from external source Profi
Digital output 2
Addr. 202 = 0
Addr. 202 = 1
Addr. 202 = 2
Addr. 202 = 2
Result of Comparator group 2
Pulse output
Value from external source Modbus
Value from external source ProfiNet
76
Comparator group 1
Comparator A
Comparator B
Comparator C
Result
Addr. 616
0/1
Status of
Digital output 1
Addr. 608 =0
Selection of source
Pulse output
Addr. 100 = Measured value address
Addr. 106 = Minimum pulse length
Addr. 102 = Pulse value
External value
Addr. 602 = 0 (Off), >0 (On)
RS485
0/1
Addr. 200 =0
Addr. 200 =1
Addr. 200 =2
Addr. 200 =5
0/1
0/1
0/1
External value
Addr. 527 = 0 (Off), >0 (On)
Ethernet / ProfiNet
Inverter
Display
K1
UMG 96RM-PN
Addr. 201=0 (not inverted)
Addr. 201=1 (inverted)
K2
0/1
Digital output 1
Fig.: Overview block diagram for Digital output 1
External source External source
13
14
Modbus ProfiNet (PLC)
UMG 96RM-PN
Pulse output (Group 1)
The digital outputs of Group 1 can be used for the output of pulses for the computation of power consumption.
For this purpose, a pulse of defined length is applied on the output after reaching a certain, adjustable amount of power.
You need to make various adjustments in the configuration menu using the GridVis software to use a digital output as a pulse out.
• Digital output
• Selection of source
• Measured value selection
• Pulse length
• Pulse value
Fig.: GridVis software, configuration menu
C
The digital outputs of Group 2 cannot be configured as pulse outputs. Use as switch outputs is possible.
77
UMG 96RM-PN
UMG 96RM-PN
Pulse
Addr. 100 = 874 (address of Psum3)
Addr. 106 = 5 (50 ms)
Addr. 102 = 1000 (Wh/pulse)
0/1
Selection of source
Addr. 200 =1
Status of
Digital output 1
Addr. 608 =0
0/1
Display
K1 K2
Inverter
Addr. 201=0 (not inverted)
Addr. 201=1 (inverted)
0/1
Digital output 1
13
14
Fig.: Block diagram; example of Digital output 1 as a pulse output.
Measured value selection (addr. 100, 101): Source selection (addr. 200, 202):
Enter the address here for the power value which should be output as the effective pulse. See Table 2.
Enter here which source the measured value will supply that should be output on the digital output.
Selectable sources:
• Comparator group
• Pulse
• External source
78
UMG 96RM-PN
Pulse length (addr. 106):
The pulse length applies to both pulse outputs and is set using the GridVis software.
The values in the table are based on the minimum pulse length and the minimum pulse interval for the maximum number of pulses per hour.
The typical pulse length of S0 pulse is 30ms.
Pulse interval:
The pulse interval is at least as large as the selected pulse length.
The pulse interval depends on the measured power, for example, and can take hours or days.
Pulse length
10ms .. 10s
Pulse interval
>10ms
Pulse length Pulse interval
10 ms 10 ms
30 ms
50 ms
30 ms
50 ms
Max. pulse/h
180 000 pulses/h
60 000 pulses/h
36 000 pulses/h
100 ms
500 ms
100 ms
500 ms
18 000 pulses/h
3600 pulses/h
1 s
10 s
1 s
10 s
1800 pulses/h
180 pulses/h
Examples of the maximum possible number of pulses per hour.
C
Pulse interval
The pulse interval is proportional to the power output within the selected settings.
C
Measured value selection
When programming with GridVis you have a selection of work values which are derived from the power output values.
79
UMG 96RM-PN
Pulse value (addr. 102, 104)
The pulse value is used to indicate how much power (Wh or varh) should correspond to a pulse.
The pulse value is determined by the maximum connected load and the maximum number of pulses per hour.
If you check the pulse value with a positive sign, the pulses will only be emitted when the measured value has a positive sign.
If you check the pulse value with a negative sign, the pulses will only be produced when the measured value has a negative sign.
Pulse value = max. connected load max. number of pulses/h
[Pulse/Wh]
C
Since the effective energy meter operates with a backstop, pulses will only be generated when drawing electricity.
C
Since the reactive energy meter operates with a backstop, pulses will only be generated with inductive load applied.
80
Determine the pulse value
Set the pulse length
Set the pulse length in accordance with the requirements of the connected pulse receiver.
At a pulse length of 30 ms, for example, the UMG 96RM generates a maximum number of
60,000 pulses (see Table "maximum number of pulses" per hour.
Determining the maximum connected load
Example:
Current transformer
Voltage L-N
= 150/5 A
= Max. 300 V
Power per phase = 150 A x 300 V
= 45 kW
Power at 3 phases = 45kW x 3
Maximum connected load = 135 kW
Calculating the pulse value
Pulse value = max. connected load max. number of pulses/h
[Pulse/Wh]
Pulse value
Pulse value
Pulse value
= 135kW / 60,000 Imp/h
= 0.00225 kWh / pulse
= 2.25 Wh / pulses
UMG 96RM-PN
UMG 96RM-PN
Switch and pulse outputs
External supply voltage
230V AC
+
24V DC
-
13
+24V=
14
Data logger
1.5k
15
Fig.: Connection example for the circuit as pulse output.
C
When using the digital outputs as pulse outputs, the auxiliary voltage (DC) must have a max. residual ripple of 5%.
81
UMG 96RM-PN
Comparators and threshold value monitoring
Two comparator groups (1 - 2), each with 3 comparators
(A - C) are available to monitor threshold values.
The results of Comparators A to C can be combined with the AND/OR operators.
The combination result of Comparator group 1 can be assigned to Digital output 1 and the combination result of Comparator group 2 can be assigned to Digital output
2.
Additionally, the function "Flash display" can also be assigned to each comparator group, whereby the backlight of the screen alternates between maximum and minimum brightness when a comparator output is active.
C
The comparator or combination results
cannot be assigned to the digital outputs of
Group 2!
Fig.: GridVis software, configuration menu
Digital input values of group 2 and analogue input values ( residual current and temperature monitoring ) as well as current monitoring input I4 cannot be used by comparators.
C
We recommend configuring the comparator and threshold value monitoring settings in
GridVis.
82
Comparator group 1
Comparator A
Measured value (addr.110)
Threshold value (addr. 108)
Min. switch-on time (addr. 111)
Lead time (addr. 112)
Operator ">=", "<" (addr.113)
Comparator B
Measured value (addr.116)
Threshold value (addr. 114)
Min. switch-on time (addr. 117)
Lead time (addr. 118)
Operator ">=", "<" (addr.119)
Comparator C
Measured value (addr.122)
Threshold value (addr. 120)
Min. switch-on time (addr. 123)
Lead time (addr. 124)
Operator ">=", "<" (addr.125)
Comparator result (addr.610) Comparator result (addr.611) Comparator result (addr.612)
Total running time
(addr.5898)
Total running time
(addr.5900)
Total running time
(addr.5902)
Combine results of Comparators A, B and C
Combine the results of Comparators A, B and C with the AND/OR operators (addr. 107).
Combination result (addr.616)
Fig.: Comparator principle of Comparator group 1
UMG 96RM-PN
83
UMG 96RM-PN
Example: current monitoring on the N
If the current on the N is higher than 100 A for 60 seconds, then Digital output 1 should be active for at least 2 minutes.
The following programming must be undertaken:
The exceedance should be present at least for the lead time of 60 seconds.
Addr. 112 = 60 seconds
1. Comparator group 1
Select Comparator group 1 for threshold value monitoring.
The comparator group only has an effect on Digital output 1.
Since only one threshold value is being monitored, select
Comparator A and program it as follows:
The operator for the comparison between measured value and threshold value.
Addr. 113 = 0 (meaning >=)
2. Selection of source
Select Comparator group 1 as the source.
Addr. 200 = 0 (Comparator group 1)
The address of the measured value of Comparator A to be monitored:
Addr. 110 = 866 (address of the current on the N)
3. Inverter
The result from Comparator group 1 can also be inverted here. However, we will not do so here.
Addr. 201 = 0 (not inverted)
The measured values for Comparators B and C are 0.
Addr. 116 = 0 (the comparator is inactive)
Addr. 122 = 0 (the comparator is inactive)
The threshold value to be observed.
Addr. 108 = 100 (100 A)
4. Combine the comparators
Comparators B and C were not set and equal zero.
Using the OR operator on Comparators A, B and C, the result of Comparator A is output as the comparator result.
Addr. 107 = 0 (combine with the OR operator)
Digital output 1 should remain active for a min. switch-on time of 2 minutes if the threshold value is exceeded.
Addr. 111 = 120 seconds
Result
If the current on the N is higher than 100 A for over 60 seconds, then Digital output 1 is active for at least 2 minutes.
Digital output 1 becomes active. A current can flow.
84
UMG 96RM-PN
Comparator group 1
Comparator A
Comparator B
Comparator C
Result
Addr. 616
0/1
UMG 96RM-PN
Selection of source
Addr. 200 =0
Status of
Digital output 1
Addr. 608 =0
0/1
Display
K1 K2
Inverter
Addr. 201=0 (not inverted)
Addr. 201=1 (inverted)
0/1
Digital output 1
13
14
Block diagram: Use of Digital output 1 for threshold value monitoring.
C
We recommend configuring threshold value monitoring settings in GridVis.
C
On the UMG 96RM you can only enter
3-digit parameter addresses.
Using GridVis you can enter 4-digit parameter addresses.
85
UMG 96RM-PN
• Measured value (addr. 110,116,122,129,135,141)
The measured value contains the address of the measured value to be monitored.
Measured value = 0 the comparator is inactive.
• Threshold value (addr. 108,114,120,127,133,139)
The threshold value is where you write the value to be compared with the measured value.
• Comparator result (addr. 610,611,612,613,614,615)
The result of the comparison between the measured value and threshold value is in the comparator result.
In this context:
0 = There is no threshold value violation.
1 = There is a threshold value violation.
• Total running time
The sum of all times for which there was a threshold value violation in the comparator result.
• Min. switch-on time (addr. 111,117,123,130,136,142)
The logic operation result (e.g. Addr. 610) is retained for the duration of the min. switch-on time.
Setting range: 1 to 32,000 seconds
• Combine (addr. 107,126)
Combine the results of Comparators A, B, and C with the AND/OR operators.
• Lead time (addr. 112,118,124,131,137,143)
Only if there is a threshold value violation for at least the duration of the lead time is the comparator result modified.
The lead time can be assigned to times in the range from 1 to 32,000 seconds.
• Total combination result (addr. 616,617)
The combined comparator results of Comparators A,
B, and C are in the total combination result.
• Operator (addr. 113,119,125,132,138,144)
Two operators are available for comparing the measured value and the threshold value.
Operator = 0 means greater than or equal to (>=)
Operator = 1 means less than (<)
86
UMG 96RM-PN
Comparator running times
Comparator running times are time counters, which are added together at a set comparator output. i.e. if the condition of the comparator is fulfilled and the lead time has elapsed, the counter is increased by the corresponding amount of time - this does not take account of the min. switch-on time!
Threshold value
Threshold value violation (e.g. exceedance)
Comparator with set limit value violation
• The set limit value is compared to the measured value.
• If the limit value violation occurs for at least the duration of the lead time, the comparator result is changed.
• The result is retained for at least the duration of the min. switch-on time and for no longer than the duration of the limit value violation. If there is no longer a limit value violation and the min. switch-on time has elapsed, the result is reset.
Lead time
Min. switch-on time
Comparator result
Comparator running time
2 seconds
6 seconds
Measured value
87
UMG 96RM-PN
Service and maintenance
Service
The device underwent various safety checks before delivery and is marked with a seal. If a device is open, then the safety checks must be repeated. Warranty claims will only be accepted if the device is unopened.
Should questions arise, which are not described in this manual, please contact the manufacturer directly.
We will need the following information from you to answer any questions:
Repair and calibration
Repair work and calibration can be carried out by the manufacturer only.
Front film
- Device name (see rating plate),
- Serial number (see rating plate),
- Software release (see measured value display),
- Measured voltage and power supply voltage,
- Precise description of the error.
The front film can be cleaned with a soft cloth and standard household cleaning agent. Do not use acids and products containing acid for cleaning.
Disposal
Device calibration
The devices are calibrated by the manufacturer at the factory - it is not necessary to recalibrate the device providing that the environmental conditions are complied with.
The UMG 96RM can be reused or recycled as electronic scrap in accordance with the legal provisions.
The permanently installed lithium battery must be disposed of separately.
Calibration intervals
We recommend having the device recalibrated by the manufacturer or an accredited laboratory every
5 years approximately.
88
Firmware update
If the device is connected to a computer, then the device firmware can be updated via the GridVis software.
The new firmware is transferred by selecting a suitable update menu (Tools/Upgrade Devices menu) and the device.
Fig. GridVis firmware update assistant
UMG 96RM-PN
89
UMG 96RM-PN
Error / warning messages
Warnings
The UMG 96RM-PN can show four different error messages on the display:
• Warnings
• Serious errors
• Measurement range exceeded
Error messages for warnings and serious errors are depicted with the symbol "EEE" followed by an error number.
Warnings are less serious errors and must be acknowledged with button 1 or 2. The capture and display of measured values continues. This error is displayed again each time the power is switched on.
Fig. Warning message with number 500 (mains frequency)
The three-digit error number is composed of the error description and - if this can be established by the UMG
96RM - one or more causes for the error.
Fig. Error message
Symbol for an error message
Error number
Error
EEE
500
Error description
The mains frequency could not be established.
Possible causes:
The voltage on L1 is too low.
The mains frequency is not in the range from 45 to 65 Hz.
Remedy:
Check the mains frequency.
Select fixed frequency on the device.
90
UMG 96RM-PN
Serious errors
When a serious error occurs, the device must be sent in to the manufacturer for inspection.
Example error message 911:
Error
EEE
910
This error number is composed of serious error 910 and the internal error cause 0x01.
Error description
Error when reading the calibration.
Internal error causes:
In some cases, the UMG 96RM-PN can determine the cause for a serious internal error and report it using the following error codes.
In this example an error occurred when reading the calibration from the EEPROM. The device must be sent in to the manufacturer for inspection.
Error
0x01
0x02
0x04
0x08
Error description
EEPROM not responding
Address below range
Checksum error
Error in the internal I2C bus
91
UMG 96RM-PN
Measurement range exceeded
If the measurement range is exceeded, it is displayed as long as this persists and cannot be acknowledged.
The measurement range is exceeded if at least one of the voltage or current measurement inputs lies outside their specified measurement range.
The Up arrow is used to highlight in which phase the measurement range was exceeded.
The corresponding error message for current circuit I4 is as shown in the figure opposite.
The "V" and "A" symbols indicate whether the measurement range has been exceeded in the current or voltage circuit.
Examples
A = Current circuit
V = Voltage circuit
Indication of the phase (L1/L2/
L3) in which the measurement range was exceeded. An exceedance in current circuit
I4 is shown as in the figure opposite.
Threshold values for exceeding the measurement range:
I = 7 Aeff
U
L-N
= 300 V rms
92
A = Current circuit
Fig.: Indication of exceeding the measurement range in the current circuit of the 2nd phase (I2).
V = Voltage circuit
Fig.: Indication of exceeding the measurement range in voltage circuit L3
Fig.: Indication of exceeding the measurement range in current circuit I4
"Measurement range exceeded" parameter
Further description of the error is encoded in the parameter "measurement range exceeded" (addr.
600), stored in the following format:
F F F F F F F F
Phase 1: 1 1
Phase 2:
Phase 3:
Phase 4 (I4):
2
4
8
2
4
8
Example: Error in Phase 2 in the current circuit:
0x
F2FFFFFF
Example: Error in Phase 3 in the voltage circuit U
L-N
:
0x
FFF4FFFF
UMG 96RM-PN
93
UMG 96RM-PN
Procedure in the event of faults
Possible fault
No display
No current display
Cause
External fuse for the power supply voltage has tripped.
Measured voltage is not connected.
Measurement current is not connected.
Remedy
Replace fuse.
Connect the measured voltage.
Connect measuring-circuit current.
Current displayed is too high or too low.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed.
The current peak value at the measurement input was exceeded by harmonic components.
The current at the measurement input fell short of.
Measurement in the wrong phase.
Read out and program the CT ratio at the current transformer.
Install current transformer with a larger CT ratio.
Install current transformer with a smaller current transformer ratio.
Check connection and correct if necessary.
Voltage displayed is too high or too low.
Voltage displayed is too low.
Voltage transformer incorrectly programmed.
Measurement range exceeded.
Read out and program the voltage transformer ratio at the voltage transformer.
Use voltage transformers.
Phase shift ind/cap.
Effective power, consumption/supply reversed.
The peak voltage value at the measurement input has been exceeded by the harmonics.
A current circuit is assigned to the wrong voltage circuit.
At least one current transformer connection is mixed up/reversed.
A current circuit is assigned to the wrong voltage circuit.
Attention! Ensure the measurement inputs are not overloaded.
Check connection and correct if necessary.
Check connection and correct if necessary.
Check connection and correct if necessary.
94
UMG 96RM-PN
Possible fault
Effective power too high or too low.
Cause
The programmed CT ratio is incorrect.
An output is not responding.
"EEE" on the display
No connection with the device.
Device still does not work despite the above measures.
The current circuit is assigned to the wrong voltage circuit.
The programmed voltage transformer ratio is incorrect.
The output was incorrectly programmed.
The output was incorrectly connected.
See error messages.
RS485
- Device address is incorrect
- Different bus speeds (baud rate)
- Wrong protocol
- Termination missing
Ethernet / ProfiNet
- IP Device address is incorrect.
Device defective.
Remedy
Read out and program the CT ratio at the current transformer
Check connection and correct if necessary.
Read out and program the voltage transformer ratio at the voltage transformer.
Check the settings and correct if necessary.
Check connection and correct if necessary.
- Adjust the device address
- Adjust speed (baud rate)
- Select the correct protocol
- Terminate bus with termination resistor
- Adjust IP device address.
Send the device to the manufacturer for inspection and testing along with an accurate fault description.
95
UMG 96RM-PN
Technical data
General
Net weight (with attached connectors)
Package weight (incl. accessories)
Service life of backlight
Approx. 380g
Approx. 780g
40,000 hrs (backlighting is reduced by around 50% over this period)
Transport and storage
The following information applies to devices which are transported or stored in the original packaging.
Free fall 1m
Temperature
Relative humidity
K55 (-25°C to +70°C)
0 to 90% RH
Ambient conditions during operation
The UMG 96RM is intended for weather-protected, stationary use.
Protection class II in acc. with IEC 60536 (VDE 0106, Part 1).
Rated temperature range
Relative humidity
Operating altitude
Pollution degree
Mounting position
Ventilation
Protection against ingress of solid foreign bodies and water
- Front
- Rear
- Front with seal
K55 (-10°C to +55°C)
0 to 75% RH
0 to 2000m above sea level
2
Upright
Forced ventilation is not required.
IP40 in acc. with EN60529
IP20 in acc. with EN60529
IP54 in acc. with EN60529
96
UMG 96RM-PN
Power supply voltage
Option 230V
Option 24V
Nominal range
Power consumption
Nominal range
90V - 277V (50/60Hz) or DC 90V - 250V; 300V CATIII max. 8.5VA / 5W
24V - 90V AC / DC; 150V CATIII
Operating range
Internal fuse, not replaceable
Power consumption
+-10% of nominal range
Recommended overcurrent protection device for line protection
(certified under UL) max. 7VA / 5W
Typ T1A / 250V/277V according IEC 60127
Option 230V: 6 - 16A
Option 24V: 1 - 6A
(Char. B)
Recommendation for a maximum number of devices on a circuit breaker:
Option 230V : Circuit breaker B6A: max. 4 devices / Circuit breaker B16A: max. 11 devices
Option 24V : Circuit breaker B6A: max. 3 devices / Circuit breaker B16A: max. 9 devices
97
UMG 96RM-PN
Voltage measurement
Three-phase 4-conductor systems with rated voltages up to
Three-phase 3-conductor systems, unearthed, with rated voltages up to
Overvoltage category
Measurement surge voltage
Measurement range L-N
Measurement range L-L
Resolution
Crest factor
Impedance
Power consumption
Sampling rate
Frequency range of the fundamental oscillation
- Resolution
277V/480V (+-10%)
IT 480V (+-10%)
300V CAT III
4kV
0
1)
to 300Vrms
(max. overvoltage 520Vrms )
0 1) to 520Vrms (max. overvoltage 900Vrms)
0.01V
2.45 (related to the measurement range)
4MOhm/phase approx. 0.1VA
21.33 kHz (50Hz), 25.6 kHz (60Hz) for each measurement channel
45Hz to 65Hz
0.01Hz
1)
The UMG 96RM-PN can only detect measurements when a voltage L1-N greater than 20V eff (4-wire measurement) at voltage input V1 or a voltage L1-L2 greater than 34V eff (3-wire measurement) is applied.
98
Current measurement I1 - I4
Rated current
Measurement range
Crest factor
Resolution
Overvoltage category
Measurement surge voltage
Power consumption
Overload for 1 sec.
Sampling rate
Residual current monitoring I5 / I6
Rated current
Limiting current
Triggering current
Resolution
Crest factor
Burden
Overload for 1 sec.
Sustained overload
Overload for 20 ms
Residual current monitoring
UMG 96RM-PN
5A
0 to 6Arms
1,98
0.1mA (display 0.01A)
300V CAT II
2kV
Approx. 0.2 VA (Ri=5mOhm)
120A (sinusoidal)
21.33 kHz (50Hz), 25.6 kHz (60Hz) for each measurement channel
30mArms
40mArms
50
µA
1 µA
1.414 (related to 40mA)
4 Ohm
5A
1A
50A i.a.w. IEC/TR 60755 (2008-01), type A
Type B
99
UMG 96RM-PN
Thermistor input
2 optional inputs
Update time
Connectable sensors
Total burden (sensor + cable)
Sensor type
KTY83
KTY84
PT100
PT1000
Serial interface
RS485 to Modbus RTU/Slave
Stripping length
Ethernet / ProfiNet interface
Connection
Functions
Protocols
Temperature range
-55°C to +175°C
-40°C to +300°C
-99°C to +500°C
-99°C to +500°C
Conformance Class (CC)
ProfiNet version
ProfiNet profiles
100
1 second
PT100, PT1000, KTY83, KTY84
Max. 4 kOhm
Resistor range
500Ohm to 2.6kOhm
350Ohm to 2.6kOhm
60Ohm to 180Ohm
600Ohm to 1.8kOhm
Measurement uncertainty
± 1.5% rng
± 1.5% rng
± 1.5% rng
± 1.5% rng
9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps
7mm
RJ45
Embedded webserver (HTTP)
TCP/IP, Modbus/TCP (Port 502),
ICMP (Ping), NTP, Modbus RTU over Ethernet (Port 8000), FTP
ProfiNet (SNMP, DCP, MRP, LLDP, DCOM, RPC ...)
B — Switch class C (IRT)
2.2
PROFIenergy V1.1, Entity Class 2
Digital outputs
2 and 3 optional additional digital outputs, semiconductor relay, not short-circuit proof
Switching voltage Max. 33V AC, 60V DC
Switching current
Response time
Pulse output (energy pulses) max. 50mAeff AC/DC
10/12 periods + 10ms *
Max. 50Hz
* Response time, e.g. at 50 Hz: 200ms + 10ms = 210 ms
Digital inputs
3 optional additional digital outputs, semiconductor relay, not short-circuit proof
Maximum counter frequency 20Hz
Input signal present
Input signal not present
18V to 28V DC (typical 4mA)
0 to 5V DC, current less than 0.5mA
Terminal connection capacity (supply voltage)
Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.2 - 2.5mm
2
, AWG 26 - 12
Terminal pins, core end sheath
Tightening torque
Stripping length
0.2 - 2.5mm
0.4 - 0.5Nm
7mm
2
UMG 96RM-PN
101
UMG 96RM-PN
Terminal connection capacity (voltage and current measurement)
Connectable conductors. Only one conductor can be connected per terminal!
Current
Single core, multi-core, fine-stranded
Terminal pins, core end sheath
Tightening torque
Stripping length
0.2 - 2.5mm
0.4 - 0.5Nm
7mm
2
0.2 - 2.5mm
2
, AWG 26-12
Voltage
0.08 - 4.0mm
2
, AWG 28-12
0.2 - 2.5mm
2
0.4 - 0.5Nm
7mm
Terminal connection capacity (residual current and temperature measurement inputs and digital inputs/outputs)
Rigid/flexible
Flexible with core end sheath without plastic sleeve
Flexible with core end sheath with plastic sleeve
Tightening torque
Stripping length
0.14 - 1.5mm
0.20 - 1.5mm
0.20 - 1.5mm
7mm
2
2
2
0.20 - 0.25Nm
, AWG 28-16
Cable length (digital inputs / outputs, temperature measurement input)
Up to 30m
Longer than 30m
Not screened
Screened
Terminal connection capacity (serial interface)
Single core, multi-core, fine-stranded
Terminal pins, core end sheath
Tightening torque
Stripping length
102
0.20 - 1.5mm
2
0.20 - 1.5mm
2
0.20 - 0.25Nm
7mm
UMG 96RM-PN
Function parameters
Function
Total effective power
Total reactive power
Total apparent power
Total effective energy
Total reactive energy
Total apparent energy
Frequency
Phase current I1 - I3
Measured neutral conductor current I4
Residual currents I5, I6
Computed neutral conductor current
Voltage
Voltage
Power factor
Short-term flicker, long-term flicker
Voltage dips (L-N)
Voltage rises (L-N)
Transient overvoltages
Voltage interruptions
Voltage unbalance (L-N)
1)
Voltage unbalance (L-N)
2)
Voltage harmonics
THD of the voltage
3)
THD of the voltage 4)
Pst, Plt
Udip
Uswl
Utr
Uint
Unba
Unb
Uh
THDu
THD-Ru
Symbol
P
QA, Qv
SA, Sv
Ea
ErA, ErV
EapA, EapV f
I
IN
I
Diff
INc
U L-N
U L-L
PFA, PFV
Precision class
0.5
5)
(IEC61557-12)
1 (IEC61557-12)
0.5
5)
(IEC61557-12)
0.5S
5) 6)
(IEC61557-12)
-
-
-
-
-
-
-
1 (IEC61557-12)
0.5
5)
(IEC61557-12)
0.05 (IEC61557-12)
0.2 (IEC61557-12)
1 (IEC61557-12)
1 (IEC61557-12)
1.0 (IEC61557-12)
0.2 (IEC61557-12)
0.2 (IEC61557-12)
0.5 (IEC61557-12)
Cl. 1 (IEC61000-4-7)
1.0 (IEC61557-12)
-
Measurement range
0 to 5.4 kW
0 to 5.4 kvar
0 to 5.4 kVA
0 to 5.4 kWh
0 to 5.4 kvarh
0 to 5.4 kVAh
45 to 65 Hz
0 to 6 Arms
0 to 6 Arms
0 to 40 mArms
0.03 to 25 A
10 to 300 Vrms
18 to 520 Vrms
0.00 to 1.00
-
-
-
-
-
-
-
Up to 2.5 kHz
Up to 2.5 kHz
-
Display range
0 W to 999 GW *
0 varh to 999 Gvar *
0 VA to 999 GVA *
0 Wh to 999 GWh *
0 varh to 999 Gvarh *
0 VAh to 999 GVAh *
45.00 Hz to 65.00 Hz
0 A to 999 kA
0 A to 999 kA
0 A to 999 kA
0.03 A to 999 kA
0 V to 999 kV
0 V to 999 kV
0.00 to 1.00
-
-
-
-
-
-
-
0 V to 999 kV
0% to 999%
-
103
UMG 96RM-PN
Function
Current harmonics
THD of the current
3)
THD of the current 4)
Mains signal voltage
1) In relation to the amplitude.
2) In relation to phase and amplitude.
3) In relation to fundamental oscillation.
4) In relation to effective value.
Symbol
Ih
THDi
THD-Ri
MSV
Precision class
Cl. 1 (IEC61000-4-7)
1.0 (IEC61557-12)
-
-
5) Precision class 0.5 with.../ 5A converter.
Precision class 1 with.../ 1A converter.
6) Precision class 0.5S per IEC62053-22
-
-
Measurement range
Up to 2.5 kHz
Up to 2.5 kHz
Display range
0 A to 999 kA
0% to 999%
-
-
* When the max. total working value range has been reached, the display returns to 0.
104
UMG 96RM-PN
Parameters and Modbus address list
The excerpt of the following parameter list contains settings necessary for proper operation of the UMG 96RM-PN, e.g. current transformers and device address. The values in the parameter list can be described and read.
Table 1 - Parameter list
C
A complete overview of the parameters and measured values as well as explanations on selected measured values can be found in the document "Modbus Address List", which can be found on the CD or online.
The excerpt of the measured value list stores the measured and calculated measured values, status data for the outputs, and logged values for viewing.
C
The addresses listed in this documentation within the range 0-800 can be set directly on the device. The addresses in the range of 1000 and above can only be edited via
Modbus!
Address Format RD/WR Unit Comment
0
1
10
12
14
3
16
18
20
SHORT
SHORT
SHORT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
- kbps
-
A
A
V
V
A
A
Device address
Baud rate (0=9.6kbps, 1=19.2kbps,
2=38.4kbps, 3= 57.6kbps
Stoppbits
0 = 1 Bit, none parity
1 = 2 Bits, none parity
2 = 1 Bit, even parity
3 = 1 Bit, uneven parity
Current transformer I1, primary
Current transformer I1, sec.
Voltage transformer V1, prim.
Voltage transformer V1, sec.
Current transformer I2, primary
Current transformer I2, sec.
(*1) The values 0 and 248 to 255 are reserved and must not be used.
(*2) The adjustable value 0 does not produce any meaningful work values, and must not be used.
Setting range Default
0 - 255
(*1)
1
0 - 7
(5 - 7 for internal use
0..3 only)
4
0
0 - 1,000,000
(*2)
1 - 5
0 - 1,000,000
5
5
(*2)
400
100, 400
0 - 1,000,000
1 - 5
(*2)
400
5
5
105
UMG 96RM-PN
Address Format RD/WR Unit Comment
22
24
26
28
30
32
34
35
36
37
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
SHORT
SHORT
SHORT
SHORT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR -
-
-
V
V
A
A
V
V
Hz
Voltage transformer V2, prim.
Voltage transformer V2, sec.
Current transformer I3, primary
Current transformer I3, sec.
Voltage transformer V3, prim.
Voltage transformer V3, sec.
Frequency estimation
0=Auto, 45 - 65=Hz
Screen contrast
0 (low), 9 (high)
Backlight
0 (dark), 9 (bright)
Screen profile
0=Preassigned screen profile
1=Preassigned screen profile
2=Preassigned screen profile
38
39
40
41
42
45
SHORT
0..2=Preassigned
SHORT
SHORT
SHORT
SHORT
USHORT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
- s
-
-
- mA
3=Freely selectable screen profile
Screen rotation profile profiles selectable screen rotation profile
Rotation time
Averaging time, I
Averaging time, P
Averaging time, U
Current measurement response threshold I1 - I3 screen
rotation
3=Freely
50 SHORT RD/WR - Password
0 - 3
Setting range
0 - 1,000,000
100, 400
0 - 1,000,000
1 - 5
0 - 1,000,000
100, 400
0, 45 - 65
0 - 9
0 - 9
0 - 3
0 - 60
0 - 8*
0 - 8*
0 - 8*
0 - 200
0 - 999
5
6
0
Default
5
5
400
400
400
400
0
0
6
6
0
6
5
0 (no password)
UMG 96RM-PN
Address Format
111
112
113
114
116
117
118
119
120
122
100
101
102
104
106
107
108
110
SHORT
SHORT
FLOAT
FLOAT
SHORT
SHORT
FLOAT
SHORT
SHORT
SHORT
SHORT
FLOAT
SHORT
SHORT
SHORT
SHORT
FLOAT
SHORT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
Unit
-
-
Wh
Wh
-
10ms s
-
-
- s
-
- s
-
-
- s
Comment
Address of the measured value, digital outp. 1
Address of the measured value,
Digital outp. 2
Pulse value,
Digital output 1
Pulse value,
Digital output 2
Minimum pulse length (1=10ms)
Digital outp. 1/2
Result of Comparator group 1;
Combine A, B, C
Comparator 1A, Threshold value
Comparator 1A, address of the measured value
Comparator 1A, min. switch-on time
Comparator 1A, lead time
Comparator 1A, Operator
">="=0, "<"=1
Comparator 1B, Threshold value
Comparator 1B, address of the measured value
Comparator 1B, min. switch-on time
Comparator 1B, lead time
Comparator 1B, Operator
">="=0, "<"=1
Comparator 1C, Threshold value
Comparator 1C, address of the measured value
Setting range Default
0 - 32,000
0 - 32,000
874
882
-1,000,000 to +1,000,000 1000
-1,000,000 to +1,000,000 1000
1 - 1000
0,1
5 (=50ms)
0
-10
12
-1 to +10
12
-1 0
0 - 32,000 0
0 - 32,000
0 - 32,000
0,1
-10
12
-1 to +10
12
-1 0
0
0
0
0 - 32,000 0
0 - 32,000
0 - 32,000
0,1
-10
12
-1 to +10
12
-1 0
0
0
0
0 - 32,000 0
107
UMG 96RM-PN
Address Format RD/WR Unit Comment
123
124
125
126
SHORT
SHORT
SHORT
SHORT
RD/WR
RD/WR
RD/WR s s
-
Comparator 1C, min. switch-on time
Comparator 1C, lead time
Comparator 1C, Operator
RD/WR -
">="=0, "<"=1
Result of Comparator group 2;
Combine A, B, C
(1=and,
127
129
130
131
132
133
135
136
137
138
139
141
142
143
144
FLOAT
SHORT
SHORT
SHORT
SHORT
FLOAT
SHORT
SHORT
SHORT
SHORT
FLOAT
SHORT
SHORT
SHORT
SHORT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
-
- s s
-
-
- s s
-
-
- s s
-
0=or)
Comparator 2A, Threshold value
Comparator 2A, address of the measured value
Comparator 2A, min. switch-on time
Comparator 2A, lead time
Comparator 2A, Operator
">="=0, "<"=1
Comparator 2B, Threshold value
Comparator 2B, address of the measured value
Comparator 2B, min. switch-on time
Comparator 2B, lead time
Comparator 2B, Operator
">="=0, "<"=1
Comparator 2C, Threshold value
Comparator 2C, address of the measured value
Comparator 2C, min. switch-on time
Comparator 2C, lead time
Comparator 2C, Operator
">=" = 0, "<" = 1
108
Setting range
0 - 32,000
0 - 32,000
0,1
0,1
-10
12
-1 to +10
12
-1 0
0 - 32,000 0
0 - 32,000
0 - 32,000
0,1
-10
12
-1 to +10
12
-1 0
0
0
0
0 - 32,000 0
0 - 32,000
0 - 32,000
0,1
-10
12
-1 to +10
12
-1 0
0
0
0
0 - 32,000
0 - 32,000
0 - 32,000
0,1
0
0
0
0
Default
0
0
0
0
UMG 96RM-PN
Address
145
200
201
202
203
500
501
502
503
504
505
506
507
508
Format
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
Unit
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Comment
"Flash display"
Bit 1 = 1/0: active/inactive for
Comparator group output 1
Bit 2 = 1/0: active/inactive for
Comparator group output 2
Selection of source for
Digital output 1
Inverter Digital output 1
Selection of source for
Digital output 2
Inverter Digital output 2
Terminal assignment, I L1
Terminal assignment, I L2
Terminal assignment, I L3
Terminal assignment, U L1
Terminal assignment, U L2
Terminal assignment, U L3
Clear min and max values
Clear energy counter
Force write to EEPROM
Note: Energy values and min/max values are written to the EEPROM every 5 minutes.
Setting range
0-3
509
510
511
SHORT
SHORT
SHORT
RD/WR
RD/WR
-
-
Connection diagram, voltage
Connection diagram, current
RD/WR - Relevant voltage for THD and FFT
0 - 8
0 - 8
4)
0
In the display, the voltages can be displayed for THD and FFT as L-N or as L-L values. 0=LN, 1=LL
0
0
*1 0 =Comparator group, 1=Pulse output, 2=Value from an external source (Modbus), 3=Reserved, 4=Reserved, 5=ProfiNet
*2 0=Not inverted, 1=Inverted *3 0 = No measurement of the current or voltage path. *4 The setting 8 is equal setting 0.
Default
0
0 - 5
*1
0, 1
*2
1
0
0 - 5
*1
0, 1
*2
1
0
-3 to 0 to +3
3)
+1
-3 to 0 to +3
3)
+2
-3 to 0 to +3
3)
+3
0 - 3
3)
1
0 - 3
3)
2
0 - 3
3)
3
0 - 1
0 - 1
0 - 1
0
0
0
109
UMG 96RM-PN
Address Format RD/WR Unit Comment
521
524
525
524
530
532
534
536
538
540
542
543
544
546
548
549
550
551
552
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
SHORT
SHORT
FLOAT
FLOAT
SHORT
RD/WR -
0=Output,
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
RD/WR
-
-
-
A
A
A
A
A
A
-
-
-
-
-
-
-
-
-
Switch I/Os of Group 2
Inverter Digital output 3
Inverter Digital output 4
Inverter Digital output 5
Current transformer I4, primary
Current transformer I4, sec.
Current transformer I5, primary
Current transformer I5, sec.
Current transformer I6, primary
Current transformer I6, sec.
Input type I5
0=Residual current, 1=Temperature
Input type I6
0=Residual current, 1=Temperature
Temperature offset temp 1
Temperature offset temp 2
Temperature sensor temp 1
(0=PT100, 1=PT1000, 2=KTY83,
3=KTY84, 4=Resistance in ohms)
Temperature sensor temp 2
(0=PT100, 1=PT1000, 2=KTY83,
3=KTY84, 4=Resistance in ohms)
Tariff configuration, Input 1
If Input 1 is active, counters are set in Tariff 1*
Tariff configuration, Input 2
If Input 2 is active, counters are set in Tariff 2*
Tariff configuration, Input 3
If Input 3 is active, counters are set in Tariff 3*
110
Setting range
0,1
0, 1
0, 1
0, 1
*2
*2
*2
0 - 1,000,000
(*2)
1.0 - 5.0
1.0 - 5.0
0.0 - 1,000,000.0
1.0 - 5.0
5
5
0.0 - 1,000,000.0
0
0
0
0
(*2)
1
(*2)
1
1
1
0,1
0,1
-1000.0 to 1000.0
-1000.0 to 1000.0
0
0
0
0
0 - 4
0 - 4
0 - 127
0 - 127
0 - 127
Default
0
0
0
0
0
UMG 96RM-PN
Address
553
554
600
602
605
608
609
610
611
612
613
614
615
616
617
746
747
750
754
756
Format
SHORT
SHORT
UINT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
SERNR
SERNR
C
-
-
-
-
-
-
-
-
-
-
-
-
-
Unit
-
-
-
-
- s s
RD/WR
RD/WR
RD/WR
RD
RD
RD
RD
RD
RD/WR
RD/WR
RD/WR
RD
RD
RD
RD
RD
RD/WR
RD/WR
RD
RD
RD
Comment
Transformer monitoring I5
Transformer monitoring I6
Setting range Default
0 (inactive), 1 (active) 0
0 (inactive), 1 (active) 0
Measurement range exceeded
Modbus value for Output 1
Modbus value for Output 2
Status, Output 1
Status, Output 2
Comparator result 1, Output A
Comparator result 1, Output B
Comparator result 1, Output C
Comparator result 2, Output A
Comparator result 2, Output B
Comparator result 2, Output C
Combination result, Comparator group 1
Combination result, Comparator group 2
0 to 0xFFFFFFFF
0, 1
0, 1
After how long to switch to standby lighting
Brightness of standby lighting
Software release
Serial number
Production number
60 to 9999
0 - 9
900
0
The display only depicts the first 3 digits
(###) of a value. Values higher than 1000 are indicated by "k". Example: 003k = 3000
* The tariff counter is activated by a bit-by-bit coding:
Bit 0 = Effective energy, Bit 1 = Effective energy (consumed), Bit 2 = Effective energy (delivered)
Bit 3 = Reactive energy, Bit 4 = Reactive energy (inductive), Bit 5 = Reactive energy (capacitive)
Bit 6 = Apparent energy
111
UMG 96RM-PN
Table 2 - Modbus address list
(often needed measured values)
C
The addresses listed in this documentation within the range 0-800 can be set directly on the device.
The address range 800-999 is available for the programming of comparators on the device. The addresses in the range of 1000 and above can only be edited via
Modbus!
Modbus Address
Address on display
19000
19002
19004
19006
19008
19010
19012
19014
19016
19018
19020
19022
19024
19026
19028
19030
808
810
812
814
816
818
860
862
864
866
868
870
872
874
884
886
112
Format
float float float float float float float float float float float float float float float float
RD/WR
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
Unit
A
A
W
W
W
W
VA
VA
V
V
A
A
V
V
V
V
C
A complete overview of the parameters and measured values as well as explanations on selected measured values can be found in the document "Modbus Address List", which can be found on the CD or online.
Comment
Voltage L1-N
Voltage L2-N
Voltage L3-N
Voltage L1-L2
Voltage L2-L3
Voltage L3-L1
Current, L1
Current, L2
Current, L3
Vector sum; IN=I1+I2+I3
Effective power L1
Effective power L2
Effective power L3
Sum; Psum3=P1+P2+P3
Apparent power S L1
Apparent power S L2
Modbus Address
Address on display
19064
19066
19068
19070
19072
19074
19076
19078
19080
19082
19084
19086
19088
19090
19092
19032
19034
19036
19038
19040
19042
19044
19046
19048
19050
19052
19054
19056
19058
19060
19062
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
824
800
888
890
876
878
880
882
820
822
RD/WR
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
Format
float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float float
Unit
VAh
VAh
VAh varh varh varh varh
Wh
Wh
Wh
Wh
Wh
Wh
Wh
VAh
-
Hz
-
Wh
Wh
Wh
Wh
Wh
VA
VA var var var var
-
-
Comment
Apparent power S L3
Sum; Ssum3=S1+S2+S3
Fund. reactive power (mains frequ.) Q L1
Fund. reactive power (mains frequ.) Q L2
Fund. reactive power (mains frequ.) Q L3
Sum; Qsum3=Q1+Q2+Q3
Fund.power factor, CosPhi; U L1-N IL1
Fund.power factor, CosPhi; U L2-N IL2
Fund.power factor, CosPhi; U L3-N IL3
Measured frequency
Rotation field; 1=right, 0=none, -1=left
Effective energy L1
Effective energy L2
Effective energy L3
Effective energy L1 - L3
Effective energy L1, consumed
Effective energy L2, consumed
Effective energy L3, consumed
Effective energy L1..L3, consumed, rate 1
Effective energy L1, delivered
Effective energy L2, delivered
Effective energy L3, delivered
Effective energy L1 - L3, delivered
Apparent energy L1
Apparent energy L2
Apparent energy L3
Apparent energy L1 - L3
Reactive energy L1
Reactive energy L2
Reactive energy L3
Reactive energy L1 - L3
UMG 96RM-PN
113
UMG 96RM-PN
Modbus Address
Address on display
19094
19096
19098
19100
19102
19104
19106
19108
19110
19112
19114
19116
19118
19120
-
-
-
-
-
-
-
-
836
838
840
908
910
912
Format
float float float float float float float float float float float float float float
RD/WR
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
Unit
%
%
%
%
%
% varh varh varh varh varh varh varh varh
Comment
Reactive energy, inductive, L1
Reactive energy, inductive, L2
Reactive energy, inductive, L3
Reactive energy L1 - L3, ind.
Reactive energy, capacitive, L1
Reactive energy, capacitive, L2
Reactive energy, capacitive, L3
Reactive energy L1 - L3, cap.
Harmonic, THD, U L1-N
Harmonic, THD, U L2-N
Harmonic, THD, U L3-N
Harmonic, THD, I L1
Harmonic, THD, I L2
Harmonic, THD, I L3
114
Number formats
Type
short ushort int uint float
Size
16 bit
16 bit
32 bit
32 bit
32 bit
UMG 96RM-PN
Minimum
-2
15
0
-2 31
0
IEEE 754
Maximum
2
15
-1
2 16 -1
2 31 -1
2
32
-1
IEEE 754
C
Information on saving measured values and configuration data:
• The following measured values are saved at least every 5 minutes:
• Comparator timer
• S0 counter statuses
• Min. / Max. / Mean values
• Energy values
• Configuration data is saved immediately!
115
UMG 96RM-PN
Dimension diagrams
All dimensions in mm
Rear view View from below
□
91,5
116
Side view
72
(Depth without plug)
Cut-out size
92 +0,8
UMG 96RM-PN
6 57
78
117
UMG 96RM-PN
Measured value screen overview
A01
Measured values
L1-N voltage
L2-N voltage
L3-N voltage
A02
Measured values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
A03
Measured values
L1 current
L2 current
L3 current
B01
Mean values
L1-N voltage
L2-N voltage
L3-N voltage
B02
Mean values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
B03
Mean values
L1 current
L2 current
L3 current
C01
Max values
L1-N voltage
L2-N voltage
L3-N voltage
C02
Max values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
C03
Max values
L1 current
L2 current
L3 current
A04
Measured value
Sum
Current on the N
B04
Mean value
Sum
Current on the N
C04
Max value
Total measured value
Current on the N
A05
Measured values
L1 effective power
L2 effective power
L3 effective power
A06
Measured value
Total effective power
A07
Measured values
L1 apparent power
L2 apparent power
L3 apparent power
118
B05
Mean value
L1 effective power
L2 effective power
L3 effective power
B06
Mean value
Total effective power
B07
Mean values
L1 apparent power
L2 apparent power
L3 apparent power
C05
Max values
L1 effective power
L2 effective power
L3 effective power
C06
Max value
Total effective power
C07
Max values
L1 apparent power
L2 apparent power
L3 apparent power
D01
Min values
L1-N voltage
L2-N voltage
L3-N voltage
D02
Min values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
D03
Max values (mean v.)
L1 current
L2 current
L3 current
D04
Max values
Total mean value
Current on the N
D06
Max value
Total eff.pow. mean value
A08
Measured value
Sum
Apparent power
A09
Measured values
L1 reactive power
L2 reactive power
L3 reactive power
A10
Measured value
Total reactive p.
B08
Mean value
Sum
Apparent power
B09
Mean values
L1 reactive power
L2 reactive power
L3 reactive power
B10
Mean value
Total reactive p.
C08
Max value
Sum
Apparent power
C09
Max values (ind)
L1 reactive power
L2 reactive power
L3 reactive power
C10
Max value (ind)
Total reactive p.
A11
Measured value
Harmonic distortion (THD)
U L1
A12
Measured value
Harmonic distortion (THD)
I L1
A13
Max value
Harmonic distortion (THD)
U L1
A14
Max value
Harmonic distortion (THD)
I L1
B11
Measured value
Harmonic distortion (THD)
U L2
B12
Measured value
Harmonic distortion (THD)
I L2
B13
Max value
Harmonic distortion (THD)
U L2
B14
Max value
Harmonic distortion (THD)
I L2
C11
Measured value
Harmonic distortion (THD)
U L3
C12
Measured value
Harmonic distortion (THD)
I L3
C13
Max value
Harmonic distortion (THD)
U L3
C14
Max value
Harmonic distortion (THD)
I L3
UMG 96RM-PN
119
UMG 96RM-PN
A15
Measured value
L1 cos(phi)
L2 cos(phi)
L3 cos(phi)
A16
Measured value
Sum of cos(phi)
B16
Mean value
Sum of cos(phi)
A17
Measured value
Frequency L1
Rotary field indication
A18
Measured value
Total effective energy
(without backstop)
A19
Measured value (ind)
Reactive energy
B18
Measured value
Total effective energy
(consumption)
B19
Measured value
Total
Reactive energy cap.
B20
C18
Measured value
Total effective energy
(delivery)
C19
Measured value
Total
Reactive energy cap.
A20
Operating hours counter 1
Comparator 1A*
Total running time
A21
Measured value
1st harmonics
U L1
B21
Measured value
3rd harmonics
U L1
...
The highlighted menus are not displayed with the factory default setting.
120
...
D18
Measured value
Total
Apparent energy
D19
Measured value
Reactive energy L1 ind. (Tariff 1)
G20
Comparator 2C*
Total running time
H21
Measured value
15th harmonics
U L1
E18
Measured value
Effective energy L1
Consumption (Tariff 1)
E19
Measured value
Reactive energy L2 ind. (Tariff 1)
F18
Measured value
Effective energy L2
Consumption (Tariff 1)
F19
Measured value
Reactive energy L3 ind. (Tariff 1)
* Only the first 6 comparators are displayed.
G18
Measured value
Effective energy L3
Consumption (Tariff 1)
A22
Measured value
1st harmonics
U L2
A23
Measured value
1st harmonics
U L3
A24
Measured value
1st harmonics
I L1
A25
Measured value
1st harmonics
I L2
A26
Measured value
1st harmonics
I L3
A27
Max value
1st harmonics
U L1
A28
Max value
1st harmonics
U L2
B22
Measured value
3rd harmonics
U L2
B23
Measured value
3rd harmonics
U L3
B24
Measured value
3rd harmonics
I L1
B25
Measured value
3rd harmonics
I L2
B26
Measured value
3rd harmonics
I L3
B27
Max value
3rd harmonics
U L1
B28
Max value
3rd harmonics
U L2
...
...
...
...
...
...
...
H22
Measured value
15th harmonics
U L2
H23
Measured value
15th harmonics
U L3
H24
Measured value
15th harmonics
I L1
H25
Measured value
15th harmonics
I L2
H26
Measured value
15th harmonics
I L3
H27
Max value
15th harmonics
U L1
H28
Max value
15th harmonics
U L2
The highlighted menus are not displayed with the factory default setting.
UMG 96RM-PN
121
UMG 96RM-PN
A29
Max value
1st harmonics
U L3
A30
Max value
1st harmonics
I L1
A31
Max value
1st harmonics
I L2
A32
Max value
1st harmonics
I L3
A33
Measured value
L4 current
A34
Measured value
L5 current
A35
Measured value
L6 current
B29
Max value
3rd harmonics
U L3
B30
Max value
3rd harmonics
I L1
B31
Max value
3rd harmonics
I L2
B32
Max value
3rd harmonics
I L3
...
...
...
...
122
The highlighted menus are not displayed with the factory default setting.
H29
Max value
15th harmonics
U L3
H30
Max value
15th harmonics
I L1
H31
Max value
15th harmonics
I L2
H32
Max value
15th harmonics
I L3
Even and odd harmonics up to the 40th order can be accessed and displayed in the GridVis software.
UMG 96RM-PN
123
UMG 96RM-PN
Connection example 1
(with residual current monitoring I
PE
/ I
DIFF
)
=
+
-
S1 S2 S3
=
-
+
K3 K4 K5
0-30 mA
I
DIFF
0-30 mA
I
PE
24V
DC
=
-
+
K1 K2
13 14 15
Gruppe 1
28 29 30 31 32 33 34 35 36
Gruppe 2
I
5
I
6
37
Digital inputs / outputs Analog inputs
UMG 96RM-PN
16
B
RS485
17
A
Power supply voltage
N/- L/+
1 2
Voltage measurement
V
1
V
2
V
3
V
N
3 4 5 6
Current measurement
S2 S1 S2 S1 S2 S1 S2
I
4
S1
19 18
B
A
1) 2) 2) 2)
3) 3) 3) 3)
S2 S1
S2 S1
S2 S1
S2 S1
L1
L2
L3
N
230V/400V 50Hz
124
1)
UL/IEC-approved fuse
(6A, type C)
UL/IEC-approved fuse
(10A, type C)
3)
Short circuit jumpers (external)
UMG 96RM-PN
Connection example 2
(with temperature and residual current monitoring)
24V
DC
=
-
+
K1 K2
=
+
-
S1 S2 S3
=
-
+
K3 K4 K5
PT100
0-30 mA
I
DIFF
13 14 15
Gruppe 1
28 29 30 31 32 33 34 35 36
Gruppe 2
I
5
I
6
37
Digital inputs / outputs Analog inputs
UMG 96RM-PN
16
B
RS485
17
A
Power supply voltage
N/- L/+
1 2
Voltage measurement
V
1
V
2
V
3
V
N
3 4 5 6
Current measurement
S2 S1 S2 S1 S2 S1 S2
I
4
S1
19 18
B
A
1) 2) 2) 2)
3) 3) 3) 3)
S2 S1
S2 S1
S2 S1
S2 S1
L1
L2
L3
N
230V/400V 50Hz
1)
UL/IEC-approved fuse
(6A, type C)
UL/IEC-approved fuse
(10A, type C)
3)
Short circuit jumpers (external)
125
UMG 96RM-PN
Basic functions quick guide
Modify current transformer setting
Switch to Programming mode:
• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously for approx. 1 second.
The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
• The selection is confirmed with button 1.
• The first digit of the input range for the primary current flashes.
Modify primary current
• Modify the flashing digit with button 2.
• Use button 1 to select the next number you wish to modify. The selected digit to be modified flashes. If the entire number flashes, the decimal point can be moved with button 2.
Modify secondary current
• Only 1A or 5A can be set as the secondary current.
• Use button 1 to select the secondary current.
• Modify the flashing digit with button 2.
Exit Programming mode
• Switching to Display mode is done by pressing buttons
1 and 2 again simultaneously for approx. 1 second.
Retrieving measured values
Current transformer setting, primary current
Programming mode indicator
Current transformer setting, secondary current
Current transformer symbol
(only in Programming mode)
Switch to Display mode:
• If Programming mode is still active (PRG and CT symbols shown on the display), pressing buttons 1 and 2 simultaneously for approx. 1 second switches to Display mode.
• A measured value screen, e.g. for the voltage, appears
Button control
• Button 2 is used to switch between the measured value screens for current, voltage, power, etc.
• Button 1 is used to switch between the mean values, max values, etc. associated with a particular measured value.
126
TCP/IP addressing quick guide
Manual TCP/IP settings
Switch to Programming mode:
• Switching to Programming mode is done by pressing buttons 1 and 2 simultaneously for approx. 1 second.
The symbols for Programming mode "PRG", and for the current transformer "CT" appear.
Set the TCP/IP address (addr.)
• Use button 2 to switch to "Adr" on the display.
• Use button 1 to select the first digit of the address
(Byte 0) (digit flashes). Select the digit with button 2.
• Select the next digit with button 1 (digit flashes) and use button 2 to set the desired digit.
• Once Byte 0 of the address is set, bytes 1 to 3 can be set with button 1. Then the display jumps back to Byte
0 ( none of the digits are flashing).
Subnet mask (SUb)
• Use button 2 to switch to the subnet mask area and set it with buttons 1 and 2, in the same way as the address.
Set gateway address (GAt)
• Use buttons 2 and 1 to set the gateway in the same way as the address.
Exit Programming mode
• Exit the mode by pressing buttons 1 and 2 simultaneously, or wait for 60 seconds.
UMG 96RM-PN
Designation
Byte identifier of the address (e.g. Byte 0)
Address value, Byte 0
Fig. TCP/IP address, Byte 1
A TCP/IP address consists of 4 bytes with the following structure:
Byte 0 Byte 1 Byte 2 Byte 3 xxx.xxx.xxx.xxx
127
UMG 96RM-PN
128
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 General information
- 6 Inspection on receipt
- 7 Available accessories
- 8 Product description
- 8 Proper use
- 10 UMG 96RM-PN features
- 11 Measuring process
- 11 Operating concept
- 11 GridVis network analysis software
- 12 Connection variants
- 13 Assembly
- 15 Installation
- 15 Supply voltage
- 16 Voltage measurement
- 22 Current measurement using I1 to I4
- 30 Analogue inputs
- 31 Residual current monitoring (RCM) via I5, I6
- 33 Thermistor input
- 34 RS485 interface
- 37 Ethernet / ProfiNet interface
- 39 Digital in-/outputs
- 44 LED status bar
- 45 Operation
- 45 Display mode
- 45 Programming mode
- 47 Parameters and measured values
- 49 Configuration
- 49 Connecting the supply voltage
- 49 Current and voltage transformer
- 51 Programming the current transformer for I1-I3
- 52 Programming the voltage transformer
- 53 Programming parameters
- 54 TCP/IP configuration
- 56 RS485 device address (addr. 000)
- 56 RS485 baud rate (addr. 001)
- 57 User password (addr. 050)
- 58 Parameters
- 58 Mean value
- 58 Averaging method
- 58 Min. and max. values
- 59 Mains frequency (addr. 034)
- 60 Power meters
- 60 Resetting energy meters (addr. 507)
- 61 Harmonics
- 62 Measured value rotation
- 62 Measured value screens
- 64 Direction of the rotating field
- 64 LCD contrast (addr. 035)
- 64 Backlight
- 66 Time logging
- 66 Operating hours counter
- 66 Total running time, comparator
- 67 Serial number (addr. 754)
- 67 Software release (addr. 750)
- 68 Commissioning
- 68 Connecting the supply voltage
- 68 Connecting the measured voltage
- 68 Applying the measuring-circuit voltage
- 69 Direction of the rotating field
- 69 Checking the phase assignment
- 69 Checking the power measurement
- 69 Applying the residual current
- 70 Failure monitoring (RCM) for I5, I6
- 71 Checking the measurement
- 71 Checking the single phase powers
- 71 Checking the sum powers
- 72 RS485 interface
- 74 Digital outputs
- 75 Digital output status indicators
- 77 Pulse output (Group 1)
- 82 Comparators and threshold value monitoring
- 88 Service and maintenance
- 88 Service
- 88 Device calibration
- 88 Calibration intervals
- 89 Firmware update
- 90 Error / warning messages
- 96 Technical data
- 103 Function parameters
- 105 Table 1 - Parameter list
- 112 Table 2 - Modbus address list
- 115 Number formats
- 116 Dimension diagrams
- 118 Measured value screen overview
- 124 Connection example 1
- 125 Connection example 2
- 126 Basic functions quick guide
- 127 TCP/IP addressing quick guide