- No category
advertisement
User’s
Manual
YTA710
Temperature Transmitter
(Hardware)
IM 01C50G01-01EN
IM 01C50G01-01EN
1st Edition
YTA710
Temperature Transmitter (Hardware)
IM 01C50G01-01EN 1st Edition
CONTENTS
Insulation Resistance Test and Withstand Voltage Test ..............................2-2
2.6.1 Insulation resistance test procedure ..................................................2-2
2.6.2 Withstand voltage test procedure ......................................................2-3
Installation of Explosion Protected Type Transmitters ................................2-4
Hardware Error Burnout and Hardware Write Protect Switch .....................3-2
3.4.1 Local Parameter Setting (LPS) Overview ..........................................3-3
3.4.2 Parameters Configuration ..................................................................3-5
1
1st Edition: June 2016 (YK)
All Rights Reserved, Copyright © 2016, Yokogawa Electric Corporation
IM 01C50G01-01EN
5.3.1 Input signal Cable Selection ..............................................................5-2
5.3.2 Output Signal Cable Selection ...........................................................5-2
5.4.1 Input Terminal Connections ...............................................................5-2
5.4.2 Output Terminal Connection ..............................................................5-3
6.2.1 Selection of Equipment for Calibration ..............................................6-1
6.3.1 Replacement of Integral Indicator ......................................................6-3
6.3.2 Replacement of MAIN and TEMP Assembly .....................................6-3
6.4.1 Basic Troubleshooting Flow ...............................................................6-4
6.4.2 Example of Troubleshooting Flow .....................................................6-4
7. General Specifications
............................................................................ 7-1
2
IM 01C50G01-01EN
1. Preface
The YTA temperature transmitter is fully factorytested according to the specifications indicated on the order.
In order for the YTA temperature transmitter to be fully functional and to operate in an efficient manner, the manual must be carefully read to become familiar with the functions, operation, and handling of the YTA.
This manual gives instructions on handling, wiring, installation, maintenance, and general specifications.
To ensure correct use, please read this manual and following user’s manuals.
Document No.
Explanation
IM 01C50G01-01EN Hardware (This manual)
IM 01C50T01-02EN For HART protocol type
IM 01C50T02-02EN For F
OUNDATION
Fieldbus communication type
GS 01C50G01-01EN YTA710 Temperature
Transmitter
These manuals can be downloaded from the website of Yokogawa or purchased from the
Yokogawa representatives.
Website address: http://www.yokogawa.com/fld/
■ Notes on the User’s Manual
• This manual should be delivered to the end user.
• The information contained in this manual is subject to change without prior notice.
• The information contained in this manual, in whole or part, shall not be transcribed or copied without notice.
• In no case does this manual guarantee the merchant ability of the transmitter or its adaptability to a specific client need.
• Should any doubt or error be found in this manual, submit inquiries to your local dealer.
• No special specifications are contained in this manual.
• Changes to specifications, structure, and components used may not lead to the revision of this manual unless such changes affect the function and performance of the transmitter.
■ Notes on Safety and Modifications
• Before handling the YTA, it is absolutely imperative that users of this equipment read and observe the safety instructions mentioned in each section of the manual in order to ensure the protection and safety of operators, the YTA itself and the system containing the transmitter.
<1. Preface>
1-1
We are not liable for any accidents arising out of handling that does not adhere to the guidelines established in the safety instructions.
• No maintenance should be performed on explosionproof type temperature transmitters while the equipment is energized. If maintenance is required with the cover open, always first use a gas detector to check that no explosive gases are present.
• If the user attempts to repair or modify an explosionproof type transmitter and is unable to restore it to its original condition, damage to the explosionproof features result, leading to dangerous conditions. Contact your authorized
Yokogawa Electric Corporation representative for repairs or modifications of an explosionproof type transmitter.
■ For Safe Use of Product
Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
• In case of high process temperature, care should be taken not to burn yourself because the surface of the case reaches a high temperature.
• All installation shall comply with local installation requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about WIRING are not permitted for operators.
• Please confirm that voltages between the power supply and the instrument before connecting the power cables and that the cables are not powered before connecting.
(c) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact nearest
YOKOGAWA office.
• Care should be taken to prevent the build up of drift, dust or other material on the display glass and name plate. In case of its maintenance, soft and dry cloth is used.
IM 01C50G01-01EN
(d) Modification
Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
(e) Product Disposal
The instrument should be disposed of in accordance with local and national legislation/ regulations.
(f) Authorized Representative in EEA
In relation to the CE Marking, The authorized representative for this product in the EEA
(European Economic Area) is:
Yokogawa Europe B.V.
Euroweg 2, 3825 HD Amersfoort,The
Netherlands
Symbols used in this manual
The YTA temperature transmitter and this manual use the following safety related symbols and signals.
WARNING
Contains precautions to protect against the chance of explosion or electric shock which, if not observed, could lead to death or serious injury.
CAUTION
Contains precautions to protect against danger, which, if not observed, could lead to personal injury or damage to the instrument.
IMPORTANT
Contains precautions to be observed to protect against adverse conditions that may lead to damage to the instrument or a system failure.
NOTE
Contains precautions to be observed with regard to understanding operation and functions.
Some of the diagrams in this manual are partially omitted, described in writing, or simplified for ease of explanation. The screen drawings contained in the instruction manual may have a display position
<1. Preface>
1-2
or characters (upper/lower case) that differ slightly from the full-scale screen to an extent that does not hinder the understanding of functions or monitoring of operation.
■ Warranty
• The warranty period of the instrument is written on the estimate sheet that is included with your purchase. Any trouble arising during the warranty period shall be repaired free of charge.
• Inquiries with regard to problems with the instrument shall be accepted by the sales outlet or our local dealer representative.
• Should the instrument be found to be defective, inform us of the model name and the serial number of the instrument together with a detailed description of nonconformance and a progress report. Outline drawings or related data will also be helpful for repair.
• Whether or not the defective instrument is repaired free of charge depends on the result of our inspection.
Conditions not eligible for chargeexempt repair.
• Problems caused by improper or insufficient maintenance on the part of the customer.
• Trouble or damage caused by mishandling, misusage, or storage that exceeds the design or specification requirements.
• Problems caused by improper installation location or by maintenance conducted in a nonconforming location.
• Trouble or damage was caused by modification or repair that was handled by a party or parties other than our consigned agent.
• Trouble or damage was caused by inappropriate relocation following delivery.
• Trouble or damage was caused by fire, earthquake, wind or flood damage, lightning strikes or other acts of God that are not directly a result of problems with this instrument.
■ Trademarks
• HART is a trademark of the HART
Communication Foundation.
• Registered trademarks or trademarks appearing in this manual are not designated by a TM or ® symbol.
• Other company names and product names used in this manual are the registered trademarks or trademarks of their respective owners.
IM 01C50G01-01EN
SF
P
■ ATEX Documentation
This procedure is only applicable to the countries in European Union.
GB SK
CZ
DK
I
LT
E
LV
NL
EST
PL
F
SLO
H
BG
D
S
RO
M
GR
<1. Preface>
1-3
IM 01C50G01-01EN
<1. Preface>
■ Control of Pollution Caused by the Product
This is an explanation for the product based on “Control of Pollution caused by Electronic Information
Products” in the People’s Republic of China.
1-4
IM 01C50G01-01EN
<2. Notes on Handling>
2-1
2. Notes on Handling
The YTA temperature transmitter is fully factorytested upon shipment. When the YTA is delivered, check the appearance for damage, and also check that the transmitter mounting parts shown in Figure 2.1 are included with your shipment. If “No Mounting Bracket” is indicated, no transmitter mounting bracket is included.
Bracket fastening bolt
Vertical pipe
mounting bracket
Spring washer
Bracket fastening nut
Spring washer
U-bolt nut
U-bolt
Figure 2.1 Transmitter mounting parts
U-bolt nut
Horizontal pipe mounting bracket
Transmitter fastening bolt
F0201.ai
2.1 Nameplate
The model name and configuration are indicated on the nameplate. Verify that the configuration indicated in the “Model and Suffix Code” in Chapter
7 is in compliance with the specifications written on the order sheet.
2.3 Storage
When an extended storage period is expected, observe the following precautions:
1. If at all possible, store the transmitter in factoryshipped condition, that is, in the original shipping container.
2. Choose a storage location that satisfies the following requirements.
• A location that is not exposed to rain or water.
• A location subject to a minimum of vibration or impact.
• The following temperature and humidity range is recommended. Ordinary temperature and humidity (25°C, 65%) are preferable.
Temperature:
No Integral indicator –40 to 85°C
With Integral indicator –30 to 80°C
Humidity: 0 to 100% RH (at 40°C)
3. The performance of the transmitter may be impaired if stored in an area exposed to direct rain and water. To avoid damage to the transmitter, install it immediately after removal from shipping container. Follow wiring instructions in Chapter 5.
Figure 2.2 Name plate
F0202.ai
2.2 Transport
To prevent damage while in transit, leave the transmitter in the original shipping container until it reaches the installation site.
2.4 Choosing the Installation
Location
Although the temperature transmitter is designed to operate in a vigorous environment, to maintain stability and accuracy, the following is recommended:
(1) Ambient Temperature
It is preferable to not to expose the instrument to extreme temperatures or temperature fluctuations.
If the instrument is exposed to radiation heat a thermal protection system and appropriate ventilation is recommended.
(2) Environmental Requirements
Do not allow the instrument to be installed in a location that is exposed to corrosive atmospheric conditions. When using the instrument in a corrosive environment, ensure the location is well ventilated.
The unit and its wiring should be protected from exposure to rainwater.
IM 01C50G01-01EN
(3) Impact and Vibration
It is recommended that the instrument be installed in a location that is subject to a minimum amount of impact and vibration.
2.5 Use of a Transceiver
IMPORTANT
Although the temperature transmitter is designed to resist influence from high frequency noise; use of a transceiver in the vicinity of installation may cause problems. Installing the transmitter in an area free from high frequency noise (RFI) is recommended.
2.6 Insulation Resistance Test and Withstand Voltage Test
CAUTION
(1) Overvoltage of the test voltage that is so small that it does not cause an dielectric breakdown may in fact deteriorate insulation and lower the safety performance; to prevent this it is recommended that the amount of testing be kept to a minimum.
(2) The voltage for the insulation resistance test must be 500 V DC or lower, and the voltage for the withstand voltage test must be 500 V AC or lower. Failure to heed these guidelines may cause faulty operation.
(3) For with a lighting protector (option code:/A), please remove the lightning protector from terminal at the test. In case of testing with the lightning protector, the voltage for the insulation resistance test must be 100V DC or lower, and the voltage for the withstand voltage test must be 100V AC or lower.
Failure to heed these guidelines may cause faulty operation.
Follow the steps below to perform the test, the wiring of the transmission line must be removed before initiating testing.
<2. Notes on Handling>
2-2
2.6.1 Insulation resistance test procedure
Testing between the output terminal and input terminal
1. Lay transition wiring between the + terminal, the – terminal, and the check terminal of the terminal box.
2. Lay wiring across terminals 1, 2, 3, 4, and 5 of the terminal box.
3. Connect the insulation resistance meter (with the power turned OFF) between the transition wiring of Steps 1 and 2 above. The polarity of the input terminals must be positive and that of the output terminals must be negative.
4. Turn the power of the insulation resistance meter ON and measure the insulation resistance. The duration of the applied voltage must be the period during which 100MΩ or more is confirmed (or 20MΩ if the unit is equipped with a lightning protector).
5. Upon completion of the test, remove the insulation resistance meter, connect a 100KΩ resistor between the transition wiring, and allow the electricity to discharge. Do not touch the terminal with your bare hands while the electricity is discharging for more than 1 second.
Testing between the output terminal and grounding terminal
1. Lay transition wiring between the + terminal, the - terminal, and the check terminal of the terminal box, then connect an insulation resistance meter (with the power turned OFF) between the transition wiring and the grounding terminal. The polarity of the transition wiring must be positive and that of the grounding terminal must be negative.
2. Turn the power of the insulation resistance meter ON and measure the insulation resistance. The duration of the applied voltage must be the period during which 100MΩ or more is confirmed (or 20MΩ if the unit is equipped with a lightning protector).
3. Upon completion of the test, remove the insulation resistance meter, connect a 100KΩ resistor between the transition wiring and the grounding terminal, and allow the electricity to discharge. Do not touch the terminal with your bare hands while the electricity is discharging for more than 1 second.
IM 01C50G01-01EN
Testing between the input terminal and grounding terminal
1. Lay transition wiring between terminals 1, 2,
3, 4 and 5 of the terminal box, and connect the insulation resistor (with the power turned OFF) between the transition wiring and the grounding terminal. The polarity of the transition wiring must be positive and that of the grounding terminal must be negative.
2. Turn the power of the insulation resistance meter ON and measure the insulation resistance. The duration of the applied voltage must be the period during which 100MΩ or more is confirmed (or 20MΩ if the unit is equipped with a lightning protector).
3. Upon completion of the test, remove the insulation resistance meter, connect a 100KΩ resistor between the transition wiring and the grounding terminal, and allow the electricity to discharge. Do not touch the terminal with your bare hands while the electricity is discharging for more than 1 second.
2.6.2 Withstand voltage test procedure
Testing between the output terminal and the input terminal
1. Lay transition wiring between the + terminal, the – terminal, and the check terminal of the terminal box.
2. Lay transition wiring between terminals 1, 2, 3,
4 and 5 of the terminal box.
3. Connect the withstand voltage tester (with the power turned OFF) between the transition wiring shown in Steps 1 and 2 above.
4. After setting the current limit value of the withstand voltage tester to 10mA, turn the power ON, and carefully increase the impressed voltage from 0V to the specified value.
5. The voltage at the specified value must remain for a duration of one minute.
6. Upon completion of the test, carefully reduce the voltage so that no voltage surge occurs.
<2. Notes on Handling>
2-3
Testing between the output terminal and the grounding terminal
1. Lay the transition wiring between the + terminal, the - terminal and the check terminal of the terminal box, and connect the withstand voltage tester (with the power turned OFF) between the transition wiring and the grounding terminal.
Connect the grounding side of the withstand voltage tester to the grounding terminal.
2. After setting the current limit value of the withstand voltage tester to 10mA, turn the power ON, and gradually increase the impressed voltage from 0V to the specified value.
3. The voltage at the specified value must remain for a duration of one minute.
4. Upon completion of the test, carefully reduce the voltage so that no voltage surge occurs.
Testing between the input terminal and the grounding terminal
1. Lay the transition wiring across terminals 1, 2,
3, 4, and 5 of the terminal box and connect the withstand voltage tester (with the power turned
OFF) between the transition wiring and the grounding terminal. Connect the grounding side of the withstand voltage tester to the grounding terminal.
2. After setting the current limit value of the withstand voltage tester to 10mA, turn the power ON, and gradually increase the impressed voltage from 0V to the specified value.
3. The voltage at the specified value must remain for a duration of one minute.
4. Upon completion of the test, carefully reduce the voltage so that no voltage surge occurs.
IM 01C50G01-01EN
2.7 Installation of Explosion
Protected Type Transmitters
In this section, further requirements and differences and for explosionproof type instrument are described. For explosionproof type instrument, the description in this chapter is prior to other description in this users manual.
CAUTION
To preserve the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair activities. Please read the following sections very carefully.
2.7.1 ATEX Certification
(1) Technical Data
ATEX Flameproof Type and Dust Ignition
Proof Type
Caution for ATEX Flameproof Type and Dust
Ignition Proof Type
Note 1. Certificate information
• Model YTA710/KF2 temperature transmitter is applicable for use in hazardous locations.
• No. KEMA 07ATEX0130
• Applicable Standard:
EN 60079-0:2012+A11:2013,
EN 60079-1:2007, EN 60079-31:2009
• Type of Protection and Marking Code: II 2 G Ex d IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C, T90°C
Db
• Ambient Temperature for Gas Atmospheres:
–40 to 75°C (T6), –40 to 80°C (T5)
• Ambient Temperature for Dust Atmospheres:
–30 to 65°C (T70°C), –30 to 80°C (T90°C)
• Degree of protection of enclosure: IP66/IP67
Note 2. Installation
• Cable glands, adapters and/or blanking elements with a suitable IP rating shall be of Ex d IIC/Ex tb IIIC certified by ATEX and shall be installed so as to maintain the specific degree of protection (IP Code) of the equipment.
• All wiring shall comply with local installation requirement.
<2. Notes on Handling>
2-4
Note 3. Operation
• Keep strictly the “WARNING” on the label on the transmitter.
WARNING: AFTER DE-ENERGING, DELAY
10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT
TEMP.≥70°C, USE THE
HEATRESISTING CABLES AND
CABLE GLANDS OF HIGHER
THAN 90°C.
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
-SEE USER’S MANUAL
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
Note 4. Special Conditions for Safe Use
WARNING
• Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the generation of electrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• If the YTA is mounted in an area where the use of Category 2D equipment is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
• If the equipment is affected by external sources of heating or cooling from plant facilities, make sure that the parts in contact with the equipment or in the near vicinity of the equipment do not exceed the ambient temperature range of the equipment.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric
Corporation is prohibited and will void ATEX
Flameproof Certification.
IM 01C50G01-01EN
(2) Electrical Connection
The type of electrical connection is stamped near the electrical connection port according to the following marking.
Screw Size
ISO M20×1.5 female
ANSI 1/2 NPT female
Marking
M
N
<2. Notes on Handling>
(6) Name Plate
2-5
No. KEMA 07ATEX0130
Ex d IIC T6/T5 Gb
Ex tb IIIC T70°C, T90°C Db
TEMP. CLASS T6/T5
Tamb (Gas) -40 to +75°C(T6)
-40 to +80°C(T5)
(Dust) -30 to +65°C(T70°C)
-30 to +80°C(T90°C)
ENCLOSURE: IP66/IP67
WARNING
AFTER DE-ENERGIZING. DELAY
10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP.≥70°C,
USE THE HEAT-RESISTING
CABLES & CABLE GLANDS≥90°C.
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
-SEE USER’ S MANUAL
Location of the marking
F0203.ai
(3) Installation
WARNING
All wiring shall comply with local installation requirement and local electrical code.
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking when access to the instrument and peripheral devices in hazardous locations.
(5) Maintenance and Repair
WARNING
The instrument modification or parts replacement by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and will void the certification.
F0204.ai
MODEL: Specified model code.
SUFFIX: Specified suffix code.
STYLE: Style code.
SUPPLY: Supply voltage.
NO.: Serial number and year of production
*1
.
OUTPUT: Output signal.
FACTORY CAL: Specified calibration range.
TOKYO 180-8750 JAPAN:
The manufacturer name and the address
*2
.
*1: The third figure from the left shows the production year.
The relationship between the production year and the third figure is shown below.
The third figure S
The year of
Production
T
2016 2017
U
2018
V W X Y
2019 2020 2021 2022
For example, the production year of the product engraved in “NO.” column on the name plate as follows is 2016.
C2S616294
The year 2016
*2: “180-8750” is a postal code which represents the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identification number of Notified Body.
IM 01C50G01-01EN
2.7.2 IECEx Certification
(1) Technical Data
IECEx Flameproof Type and Dust Ignition
Proof Type
Caution for IECEx flameproof type and Dust Ignition
Proof Type
Note 1. Certification information
• Model YTA710/SF2 temperature transmitter is applicable for use in hazardous locations.
• No. IECEx KEM 07.0044
• Applicable Standard: IEC 60079-0:2011,
IEC 60079-1:2007, IEC 60079-31:2008
• Type of Protection and Marking Code:
Ex d IIC T6/T5 Gb, Ex tb IIIC T70°C, T90°C Db
• Ambient Temperature for Gas Atmospheres:
–40 to 75°C (T6), –40 to 80°C (T5)
• Ambient Temperature for Dust Atmospheres:
–30 to 65°C (T70°C), –30 to 80°C (T90°C)
• Enclosure: IP66/IP67
Note 2. Installation
• Cable glands, adapters and/or blanking elements with a suitable IP rating shall be of Ex d IIC/Ex tb IIIC certified by IECEx and shall be installed so as to maintain the specific degree of protection (IP Code) of the equipment.
• All wiring shall comply with local installation requirement.
Note 3. Operation
• Keep strictly the “WARNING” on the label on the transmitter.
WARNING: AFTER DE-ENERGING, DELAY
10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT
TEMP.≥70°C, USE THE
HEATRESISTING CABLES AND
CABLE GLANDS OF HIGHER
THAN 90°C.
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
-SEE USER’S MANUAL
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
<2. Notes on Handling>
Note 4. Special Conditions for Safe Use
2-6
WARNING
• Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the generation of electrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• If the YTA is mounted in an area where the use of EPL Db equipment is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
• If the equipment is affected by external sources of heating or cooling from plant facilities, make sure that the parts in contact with the equipment or in the near vicinity of the equipment do not exceed the ambient temperature range of the equipment.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Flameproof Certification.
(2) Electrical Connection
The type of electrical connection is stamped near the electrical connection port according to the following marking.
Screw Size
ISO M20×1.5 female
ANSI 1/2 NPT female
Marking
M
N
Location of the marking
F0203.ai
IM 01C50G01-01EN
2.7.3 FM Certification
(1) Technical Data
FM Explosionproof Type
Caution for FM Explosionproof type
Note 1. Certification information
• Model YTA710/FF1 temperature transmitter is applicable for use in hazardous locations:
• Applicable Standard: FM 3600, FM 3615,
FM 3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups
A, B, C, and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure rating: TYPE 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max. (4 to 20 mA type)
: 32 V dc max. (Fieldbus type)
• Output Signal: 4 to 20 mA
: 24 mA dc max. (Fieldbus type)
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical
Codes.
• “FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED”.
Note 3. Operation
• Keep strictly the “WARNING” on the nameplate attached on the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. “FACTORY
SEALED, CONDUIT SEAL
NOT REQUIRED”. AFTER DE-
ENERGIZING, DELAY 2 MINUTES
BEFORE OPENING. INSTALL
IN ACCORDANCE WITH THE
INSTRUCTION MANUAL IM
1C50G01-01EN.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric
Corporation is prohibited and will void Factory
Mutual Explosionproof Approval.
<2. Notes on Handling>
2-7
2.7.4 CSA Certification
(1) Technical Data
CSA Explosionproof Type
Caution for CSA Explosionproof type
Note 1. Certification information
• Model YTA710/CF1 temperature transmitter is applicable for use in hazardous locations:
• Certificate 1089576
• Applicable Standard:
C22.2 No.0, C22.2 No.0.4, C22.2 No.25,
C22.2 No.30, C22.2 No.94, C22.2 No.142,
C22.2 No.157, C22.2 No.213,
C22.2 No.61010-1, C22.2 No.61010-2-30
• Class I, Groups B, C and D;
• Class II, Groups E, F and G;
• Class III.
• Enclosure: TYPE 4X
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max. (4 to 20 mA type)
: 32 V dc max. (Fieldbus type)
• Output Signal: 4 to 20 mA
: 24 mA dc max. (Fieldbus type)
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the figure.
WARNING: A SEAL SHALL BE INSTALLED
WITHIN 50 cm OF THE
ENCLOSURE. UN SCELLEMENT
DOIT ÊTRE INSTALLÉ À MOINS
DE 50 cm DU BOÎTIER.
• When installed in Division 2, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED”.
Note 3. Operation
• Keep strictly the “WARNING” on the label attached on the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. AFTER DE-
ENERGIZING, DELAY 2 MINUTES
BEFORE OPENING. OUVRIR LE
CIRCUIT AVANT D’ENLEVER LE
COUVERCLE. APRÈS POWER-
OFF, ATTENDRE 2 MINUTES
AVANT D’OUVRIR.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
IM 01C50G01-01EN
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric
Corporation is prohibited and will void Canadian
Standards Explosionproof Certification.
50 cm Max.
Hazardous Locations Division 1
YTA710
50 cm Max.
Sensor
Sealing Fitting
Certified/Listed Temperature Sensor
Conduit
<2. Notes on Handling>
Sealing Fitting
Non-hazardous Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
2-8
Sensor
Hazardous Locations Division 2
YTA710
Conduit
Sealing Fitting
Certified/Listed Temperature Sensor
Note: Temperature sensor shall be certified in type of Hazardous Locations.
Non-hazardous Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
F0205.ai
2.8 EMC Conformity Standards
EN61326-1 Class A, Table 2
EN61326-2-3
EN61326-2-5 (for Fieldbus)
CAUTION
This instrument is a Class A product, and it is designed for use in the industrial environment.
Please use this instrument in the industrial environment only.
NOTE
YOKOGAWA recommends customer to apply the Metal Conduit Wiring or to use the twisted pair Shield Cable for signal wiring to conform the requirement of EMC Regulation, when customer installs the YTA710 Transmitter to the plant.
2.9 Safety Requirement
Standards
EN61010-1, C22.2 No.61010-1
• Altitude of installation site: Max. 2,000 m above sea level
• Installation category: I
(Anticipated transient overvoltage 330 V)
• Pollution degree: 2
• Indoor/Outdoor use
EN61010-2-030, C22.2 No.61010-2-030
• Measurement category: O(Other)
(Measurement Input voltage: 150mVdc max)
IM 01C50G01-01EN
<3. Part Names and Functions>
3. Part Names and Functions
3.1 Part Names
3-1
Name plate
O-ring
Burn out output direction setting switch upon hardware failure
SW1
1
2
O
N
BOUT
WP
TEMP assembly
MAIN assembly
Stud bolt
Indicator assembly
Amp. cover
O-ring
(HART)
Grounding terminal
Tag plate
Lock screw
(for ATEX and IECEx
flameproof type)
(FF)
Wiring connector
(input signal side)
Terminal cover
Wiring connector
(output signal side)
Grounding terminal
Integral indicator display
O
N
SIM
1
2
SW2
WP
SIMULATE_ENABLE switch
Write lock switch
Output signal terminal Input signal terminal
F0301.ai
Figure 3.1 Part Names
IM 01C50G01-01EN
3.2 Hardware Error Burnout and Hardware Write Protect
Switch
There are two slide switches on the MAIN assembly board. One sets the hardware error burnout direction, and the other sets a hardware write protection function which disables parameter changes through the use of a handheld terminal or some other communication method.
The temperature transmitter is equipped with a hardware error burnout function used to set the output direction upon hardware error, and a sensor burnout function that sets the direction of the output in the event of burnout of the temperature sensor.
When factory-shipped under normal conditions, the output of both hardware error burnout and sensor burnout are set to HIGH, but if suffix code
/C1 is specified, the hardware error burnout is set to LOW (-5%) output, and sensor burnout is set to
LOW (-2.5%) output, respectively. The setting of the direction of output from burnout can be changed.
To change the direction of output arising from burnout, set the swich on the MAIN assembly (see
Figure 3.1 and Table 3.1). To change the direction of output arising out of sensor burnout, a dedicated hand-held terminal is required to rewrite the parameters within the transmitter.
NOTE
1. Turn off the power supply before changing the switches
2. To change the switches, it is necessary to remove the integral indicator assembly.
Refer to “ 6.3.1 Replacement of Integral
Indicator” about the procedures.
Table 3.1 Burnout Direction and Hardware Write
Protect Swich
Burnout direction
(BOUT) and hardware write protect (WP) switch position
Hardware error burnout direction
Hardware error burnout output
Remark
Hardware write protect swich
1
2
SW1
O
N
HIGH
OFF
BOUT
WP
110% or more
(21.6 mA DC)
Set to HIGH upon shipment
Write enabled
1
2
SW1
O
N
LOW
BOUT
WP
-5% or less
(3.2 mA DC)
Set to LOW when suffix code /C1 is provided
ON
Write disabled
<3. Part Names and Functions>
3-2
3.3 Integral Indicator Display
Function
(1) Integral Indicator Display When Powering
On (HART)
All segments display
↓
Model name
↓
Communication Protocol
↓
Device revision
↓
Software revision
↓
Process variable display
F0302.ai
IM 01C50G01-01EN
(2) Process Variable Display
Process variable that can be displayed in YTA710 are shown in the Table 3.2. A cycle of up to four displays can be shown by assigning variables to the parameters. Indicates values of process variables with the indication limits –99999 to 99999.
Table 3.2 Process Variable Display
PV
SV
TV
QV
Process variable
Sensor1
Sensor1 – Terminal
Terminal
Sensor2
Sensor2 – Terminal
Sensor1 – Sensor2
Sensor2 – Sensor1
Sensor Average
Sensor Backup
DISP.1
F0303.ai
<3. Part Names and Functions>
3.4 Local Parameter Setting
3-3
WARNING
The local push button on the integral indicator must not be used in a hazardous area. When it is necessary to use the push button, operate it in a non- hazardous location.
IMPORTANT
• Do not turn off the power to the temperature transmitter immediately after performing parameter setting. Powering off within 30 seconds of performing this procedure will return the parameter to its previous setting.
• LCD update will be slower at low ambient temperature, and it is recommended to use
LPS function at temperatures above −10 degrees C.
3.4.1 Local Parameter Setting (LPS)
Overview
Parameter configuration by the 3 push button on the integral indicator offers easy and quick setup for parameters of Tag number, Unit, PV
Damping, Display out 1, and etc. There is no effect on measurement signal (analog output or communication signal) when Local Parameter
Setting is carried out.
Table 3.3 Action
Action Operation
Activate Push ▲ or ▼ button
Move
Edit
Push ▲ or ▼ button
Push SET button
Save
Cancel
Abort
After parameter setting → Push SET button → “SAVE?” → Push SET button →
“SAVED”
If “FAILED” appear, retry or check the specificasions.
After parameter setting → Push SET button → “SAVE?” → Push ▲ or ▼ button
→ “CANCL?” → Push SET button →
“CANCLD”
Hold down the SET button for over 2 seconds → “ABORT” and move to the process measurement display
Exit Push ▲ button (When the first parameter is selected) or
Push ▼ button (When the last parameter is selected)
Time out no operation for 10 minutes
IM 01C50G01-01EN
Table 3.4 Parameters List (HART)
Item
Tag number
Long tag number
PV unit
PV damping time constant
Sensor 1 type
Indicator Display Write Mode
TAG
LNG.TAG
PV.UNIT
PV.DAMP
S1.TYPE
RW
RW
RW
RW
RW
Sensor 1 wire
Sensor 2 type
Sensor 2 wire
PV lower range
PV upper range
Sensor burnout direction
Sensor burnout value
(mA)
Sensor burnout value
(%)
Display out 1
Write protect
Model
HART revision
Device revision
Software revision
S1.WIRE
S2.TYPE
S2.WIRE
PV LRV
PV URV
BUN.DIR
BUN mA
BUN %
DISP.1
WRT.PRT
MODEL
HART
DEV.REV
SW.REV
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
R
R
R
R
<3. Part Names and Functions>
3-4
Setting Type
Character
Character
Selection
Digit
Write Mode: RW=read/write, R=read only
Remarks
up to 8 characters up to 32 characters
K, °C, °F, °R, mV, ohm, mA, %,
NOUNIT
0.00 to 100.00 seconds
Selection
Selection
Selection
Selection
Digit
Digit
Selection
Digit mv, ohm, Pt100, JPt100, Pt200,
Pt500, Pt1000, Cu10, Ni120, TYPE.B,
TYPE.E, TYPE.J, TYPE.K, TYPE.N,
TYPE.R, TYPE.S, TYPE.T, TYPE.L,
TYPE.U, TYPE.W3, TYPE.C, USR.
TBL, NO.CNCT, SMATCH
2, 3, 4 same as sensor1 type same as sensor1 wire
HIGH, LOW, USER, OFF
3.6 to 21.6 mA
Digit
Selection
-2.5 to 110%
SENS.1, S.1-TER., TERM, SENS.2,
S.2 - TER., S.1 - S.2, S2 - S.1, AVG,
BACKUP, PV, SV, TV, QV, OUT %,
OUT.mA
ON, OFF Selection
─
─
─
─
Table 3.5
PD TAG
Item
Disp Out 1
Parameters List (FF)
Indicator Display Write Mode
PD.TAG
DISP.1
R
RW
Local Write Lock
Simulation
Model
Dev Rev
Software Rev
HW.LOCK
HW SIM
MODEL
DEV.REV.
SW.REV
RW
RW
R
R
R
Setting Type
─
Selection
Write Mode: RW=read/write, R=read only
Remarks
Character
Selection
─
─
─
SENS.1, S.1-TER., TERM, SENS.2,
S.2 - TER., S.1 - S.2, S2 - S.1, AVG,
BACKUP, AI1.OUT, AI2.OUT, AI3.OUT,
AI4.OUT
Up to 8 Character, OFF
ON, OFF
IM 01C50G01-01EN
3.4.2 Parameters Configuration
(1) Activating Local Parameter Setting
Push the ▲ or ▼ button on the integral indicator to activate the local parameter setting mode. The transmitter will exit automatically from the local parameter setting mode if no operation is carried out for 10 minutes.
(2) Parameter Setting Review (HART)
Process measurement display
Push ▼ button ↓
TAG
Push ▼ button
Push ▼ button
Push ▼ button
Push ▼ button
↓
LNG.TAG
↓
PV.UNIT
↓
PV.DAMP
↓
S1.TYPE
Push ▼ button
Push ▼ button
Push ▼ button
Push ▼ button
Push ▼ button
Push ▼ button
↓
S1.WIRE
↓
S2.TYPE
↓
S2.WIRE
↓
PV LRV
↓
PV URV
↓
BUN.DIR
Push ▼ button
Push ▼ button ↓
BUN %
Push ▼ button
↓
BUN mA
Push ▼ button
Push ▼ button
Push ▼ button
↓
DISP.1
↓
WRT.PRT
↓
MODEL
↓
HART
Push ▼ button
Push ▼ button
↓
DEV.REV.
↓
SW.REV
Push ▼ button ↓
Process measurement display
<3. Part Names and Functions>
3-5
(3) Tag Number (TAG) Configuration
Up to 8 alphanumeric characters for HART can be set.
TAG → Push SET button → Change the first character by pushing ▲/▼ button → Push SET button to go to the second character → Change the second character by pushing ▲/▼ button → Set all other characters in the same way → Hold down the SET button → “SAVE?” → Push SET button →
“SAVED”
Push ▲/▼ to return to the process measurement display.
See “(2) Parameter Setting Review (HART)”.
(4) PV Unit (PV.UNIT) Configuration
PV unit (unit of sensor mapping in PV) for the
Table3.4 can be changed as below
PV.UNIT → Push SET button → Select the temperature unit by pushing ▲/▼ button → Push
SET button → “SAVE?” → Push SET button →
“SAVED”
Push ▲/▼ to return to the process measurement display.
See “(2) Parameter Setting Review (HART)”.
(5) Damping Time Constant (PV.DAMP)
Configuration
The damping time constant for the amplifier assembly can be set from 0 to 100 seconds.
Damping time constant is rounded off to two decimal places.
PV.DAMP → Push SET button → Change the first digit by pushing ▲/▼ button → Push SET button to go to the second digit → Change the second figure by pushing ▲/▼ button → Set all other digits in the same way → Hold down the SET button →
“SAVE?” → Push SET button → “SAVED”
Push ▲/▼ to return to the process measurement display.
See “(2) Parameter Setting Review (HART)”.
Available numbers
Number of digits
1
Selection Remarks
0, 1, 2, 3, 4, 5, 6,
7, 8, 9, -9, -8, -7,
-6, -5, -4, -3, -2,
-1, -0
2 to 5 0, 1, 2, 3, 4, 5, 6,
7, 8, 9, Dot(.), r*
6 0, 1, 2, 3, 4, 5, 6,
7, 8, 9, Dot(.), r*
Determine plus and minus in the first digit. Return cannot be selected. In case of integer a minus cannot be selected.
A dot uses a one digit.
Two dots cannot use.
In case of integer a dot cannot be selected.
A dot cannot use in 6th digits.
*: Press the SET button at the time of r display, one digit will return.
IM 01C50G01-01EN
<3. Part Names and Functions>
3-6
(6) Other Parameters Configuration
Parameter
Long tag number
Sensor 1 type
Sensor 1 wire
Sensor 2 type
Sensor 2 wire
PV lower range
Indicator display
LNG.TAG
S1.TYPE
S1.WIRE
S2.TYPE
S2.WIRE
PV LRV
PV upper range
Sensor burnout direction
PV URV
BUN.DIR
Sensor burnout value (mA) BUN mA
Sensor burnout value (%) BUN %
Display
Write protect
DISP.1
WRT.PRT
Configuration
Please refer to “Tag Number Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “Damping Time Constant Configuration” for how to set.
Please refer to “Damping Time Constant Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “Damping Time Constant Configuration” for how to set.
Please refer to “Damping Time Constant Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
(7) Local Parameter Setting Lock
To disable parameter changes by the local parameter setting there are two different ways.
• Communication parameter write protect = On
• Hardware write protection switch on MAIN assembly = ON
Reviewing local parameter setting by push button on the integral indicator is available at any time even when the local parameter setting is locked.
(8) Parameter Setting Review (FF)
Process measurement display
Push ▼ button ↓
PD.TAG
Push ▼ button
Push ▼ button
Push ▼ button
Push ▼ button
↓
DISP.1
↓
HW.LOCK
↓
HW SIM
↓
MODEL
Push ▼ button
Push ▼ button
↓
DEV.REV.
↓
SW.REV
Push ▼ button ↓
Process measurement display
(9) FF Parameter Configuration
Parameter
Disp Out 1
Local Write Lock
Simulation
Indicator display
DISP.1
HW.LOCK
HW SIM
Configuration
Please refer to “PV Unit Configuration” for how to set.
Please refer to “Tag Number Configuration” for how to set.
Please refer to “PV Unit Configuration” for how to set.
IM 01C50G01-01EN
4. Installation
IMPORTANT
• When performing on-site pipe fitting work that involves welding, use care to prevent outflow of the welding current into the transmitter.
• Do not use the transmitter as a foothold for installation.
Horizontal Pipe Mounting
• When using a horizontal pipe mounting bracket
<4. Installation>
4-1
• For details of choosing the installation location, refer to the guidelines outlined in Section 2.4,
“Choosing the installation location”.
• The mounting bracket shown in Figure 4.1 is used for the transmitter and is installed on 50A
(2B) pipe.
It can be installed either on a horizontal pipe and a vertical pipe or on a wall.
• To install the mounting bracket on the transmitter, torque the transmitter lock screw to about 20 to 30N•m.
Vertical Pipe Mounting
U-bolt nut
Horizontal pipe mounting bracket
Spring washer
Transmitter fastening bolt
U-bolt
• When using a vertical pipe mounting bracket
Bracket fastening bolt
Vertical pipe
mounting bracket
Spring washer
U-bolt
Bracket fastening nut
Figure 4.1 Mounting the Transmitter
Spring washer
Transmitter fastening bolt
U-bolt nut
Wall Mounting
Note: Wall mounting bolts are user-supplied.
F0401.ai
IM 01C50G01-01EN
5. Wiring
5.1 Notes on Wiring
IMPORTANT
• Apply a waterproofing sealant to the threads of the connection port. (It is recommended that you use non-hardening sealant made of silicon resin for waterproofing.)
• Lay wiring as far away as possible from electrical noise sources such as large transformers, motors and power supplies.
• Remove the wiring connection dust-caps before wiring.
• To prevent electrical noise, the signal cable and the power cable must not be housed in the same conduit.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on ATEX and
IECEx flameproof type transmitters.
When the shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cove can be opened by hands. See Subsection 6.3
“Disassembly and Assembly” for details.
<5. Wiring>
5-1
5.2 Loop Construction
The YTA is a two-wire temperature transmitter that uses the output power supply wiring and signal wiring alternately.
The transmission loop requires DC power. Connect the transmitter with the distributor as shown in
Figure 5.1.
For the transmission loop, the load resistance of the distributor or other instrument to be installed in the loop and the lead wire must be within the range shown in Figure 5.2.
<Hazardous location>
Input signal
(thermocouple,
RTD, mV, etc.)
<Nonhazardous location>
Distributor
(power supply unit)
Receiver
+
–
Output signal
Figure 5.1 Loop Construction (for General-use
Type and Flameproof Type)
F0501.ai
600
External load resistance
R
(Ω)
250
Communication applicable range for HART
10.5 16.6
25.2
Power supply voltage E (V DC)
42
F0502.ai
Figure 5.2 Relation Between Power Supply
Voltage and External Load Resistance
Note: For intrinsic safe explosion-proof type units, the internal resistance of the safety barrier is also included in the load resistance.
IM 01C50G01-01EN
5.3 Cable Selection
5.3.1 Input signal Cable Selection
A dedicated cable is used for connection between the temperature sensor and the temperature transmitter.
When a thermocouple is used as the temperature sensor, a compensation wire must be used that it appropriate for the type of thermocouple (refer to compensating cables for JIS C 1610/IEC60584-3 thermocouples). When a RTD is used as the temperature sensor, 2-core/3-core/4-core cable must be used (refer to JIS C 1604/IEC60751). The terminal of the dedicated cable is a 4 mm screw.
5.3.2 Output Signal Cable Selection
• With regard to the type of wire to be used for wiring, use twisted wires or cables with performance equivalent of 600V vinyl insulated cable (JIS C3307).
• For wiring in areas susceptible to electrical noise, use shielded wires.
• For wiring in high or low temperature areas, use wires or cables suitable for such temperatures.
• For use in an atmosphere where harmful gases or liquids, oil, or solvents are present, use wires or cables made of materials resistant to those substances.
• It is recommended that a self-sealing terminal with insulation sleeve (4-mm screw) be used for lead wire ends.
<5. Wiring>
5.4 Cable and Terminal
Connections
5.4.1 Input Terminal Connections
NOTE
It is recommended that the terminals be connected in the order of STEP 1 and STEP 2.
5-2
CAUTION
When wiring, pay attention not to damage the cable and cores. All the cores of the cable must have the sufficient insulation around them.
STEP 1
(1)
a. Cable connection to RTD 3-wire
STEP 2
(2)
b. Power supply cable connection
Figure 5.3 Terminal Connection Procedure
F0503.ai
IM 01C50G01-01EN
The temperature sensor is to be connected as shown in Figures 5.5.
Figure 5.4 Terminal Diagram
3
4
1
2
5
(+)
(–)
Thermocouple and
DC voltage
Single input
3
4
1
2
5
(A)
(B)
RTD and resistance
(2-wire)
3
4
1
2
5
(A)
(B)
(B)
RTD and resistance
(3-wire)
3
4
1
2
5
(A)
(A)
(B)
(B)
RTD and resistance
(4-wire)
3
4
1
2
5
3
4
1
2
5
(–)
(+)
(+)
Thermocouple and
DC voltage
Dual input
3
4
1
2
5
(A1)
(B1)
(B1)
(B2)
(B2)
(A2)
RTD and resistance
(3-wire)
(+)
(–)
(B2)
(B2)
(A2)
3
4
1
2
5
Thermocouple +
RTD and resistance
(3-wire)
(A1)
(B1)
(B1)
(–)
(+)
3
4
1
2
5
(A1)
(B1)
(B2)
(A2)
RTD and resistance
(2-wire)
RTD and resistance
(3-wire)
+ Thermocouple
F0505.ai
Figure 5.5 Wiring Connection Diagram
F0504.ai
<5. Wiring>
5-3
5.4.2 Output Terminal Connection
(1) Connection of output signal/power supply cable
Connect the output signal cable (shared with the power supply cable) to the – terminal and the + terminal. For details, refer to Figure 5.1, “Loop construction”.
(2) Connection of wiring for field indicator
Connect the lead wire for the field indicator with the
– terminal and the C terminal.
Note: Use a field indicator with an internal resistance of 10Ω or less.
Field indicator
+
–
Power supply
Figure 5.6 Connection to Field Indicator
– +
F0506.ai
(3) Connection of check meter
Connect the check meter with the – terminal and the C terminal.
The current signal of output signal 4 to 20 mA DC is output from the – terminal and the C terminal.
Note: Use a check meter with internal resistance of 10Ω or less.
Check meter
Figure 5.7 Check Meter Connection
+
–
Power supply
F0507.ai
IM 01C50G01-01EN
5.5 Wiring Cautions
(1) General-use Type
Use metal conduit wiring or a waterproof gland
(metal wiring conduit JIS F 8801) for cable wiring.
• Apply nonhardening sealant to the threads of the wiring tap and a flexible fitting for secure waterproofing. Figure 5.8 shows an example of wiring on the output side. This example also applies to the wiring on the input side.
Flexible fitting
Wiring conduit
Apply a nonhardening sealant to the threads for waterproofing.
Tee
Drain plug
F0508.ai
Figure 5.8 Example of Wiring Using a Wiring
Conduit
5.6 Grounding
Grounding is always required for the proper operation of transmitters. Follow the domestic electrical requirements as regulated in each country. For a transmitter with a lightning protector, grounding should satisfy ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.
Grounding terminal
(Inside)
Grounding terminal
(Outside)
Figure 5.9 Grounding Terminal
F0509.ai
<5. Wiring>
5-4
IM 01C50G01-01EN
6. Maintenance
6.1 General
Each component of this instrument is configured in units to make maintenance easier.
This chapter contains disassembly and assembly procedures associated with calibration, adjustment and part replacement required for maintenance of the affected instrument.
IMPORTANT
1. Maintenance of this instrument should be performed in a service shop where the necessary tools are provided.
2. Handling the MAIN, TEMP, and Indicator assembly
Some of the parts contained in the MAIN,
TEMP, and Indicator assembly are susceptible to static electricity damage.
Before performing maintenance, use a ground wrist band or other antistatic mea sures, and avoid touching the electronic components and circuits with bare hands.
When removed from the instrument, keep the MAIN, TEMP, and Indicator assembly in an antistatic bag.
<6. Maintenance>
6-1
1. In accordance with the example wiring shown in
Figure 6.1, connect each equipment and initiate warm up. Lay wiring on the input side according to the sensor to be used.
Table 6.1
Name
Power supply
Load resistance
Voltmeter
Universal calibrator
Variable resistor
Calibration Equipment List
Recommended
SDBT, SDBS distributor
2792 type standard resistor
(250Ω ±0.005%)
Remark
4 to 20mA DC
(Output voltage:
26.5±1.5V, drop by internal 250Ω resistance included)
For 4 to 20mA DC
279301 type 6-dial variable resistor
(accuracy: ±0.01%
±2mΩ)
For 4 to 20mA DC signal
For calibration of
DC voltage and thermocouple
For calibration of
RTD input
a. Wiring of power supply and output
+ Output signal
– Load resistance
6.2 Calibration
This instrument is fully factory-tested and is guaranteed for the intended accuracy, eliminating the need for calibration. When calibration needs to be varified, the following equipment and calibration procedure is recommended.
6.2.1 Selection of Equipment for
Calibration
Table 6.1 lists the equipment required for calibration. The calibration equipment traceable to a verifying agency standard should be used.
6.2.2 Calibration Procedure
To conduct calibration required to evaluate the uncertainty while using the instrument, follow the steps below:
Voltmeter
b. Example of wiring for thermocouple or DC voltage input
(when 1 input type is used)
3
4
1
2
5
(+)
(–)
DC voltage generator
c. Example of wiring for RTD 4-core type
(when 1 input type is used)
3
4
1
2
5
(A)
(A)
(B)
(B)
Variable resistor
F0601.ai
Figure 6.1 Example of Wiring for Calibration
Equipment
IM 01C50G01-01EN
2. For DC voltage input
With a voltage generator, deliver input signals corresponding to 0, 25, 75, or 100% of the input span to the temperature transmitter. Measure the resulting input signal with the voltmeter
(digital multimeter) and check the output value relative to the input value.
3. For thermocouple input
Since this instrument is equipped with a reference junction compensating function, use a reference junction compensating function in universal calibrator in order to compensate for this function upon calibration. According to the reference millivolt table for thermocouple, obtain millivolt corresponding to 0, 25, 50, 75, or 100% of the span, and use that power as the input value, then deliver it from the universal calibrator to the temperature transmitter.
Measure the resulting output signal with the voltage meter (digital multimeter) and check the output value relative to the input value.
4. RTD
Using a RTD as input, calibration of the temperature transmitter is carried out via a
4-core wire connection.
As defined the reference resistor value table of the RTD, obtain resistance values corresponding to 0, 25, 50, 75 or 100% of the span, and use the obtained resistance as the input value, then deliver it to the temperature transmitter by means of a variable resistor.
Measure the resulting output signal with the voltmeter (digital multimeter) and check the output value relative to the input value.
5. In Steps 2 through 4, if the output signal deviates from the given range of accuracy when a given input signal is delivered, adjust the output using the handheld terminal. For details of how to adjust the output, refer to the additional reference, “HART Protocol” IM
01C50T01-02EN subsection 3.5.6 “Sensor
Trim” and the instruction manual for each terminal.
6.3 Disassembly and Assembly
This section details the procedure for part replacement or disassembly and assembly of each component depending on the maintenance process.
Before starting disassembly and assembly work, turn off the power, and use a tool suited to the associated work.
<6. Maintenance>
6-2
Table 6.2 lists the tools required for disassembly and assembly of the instrument.
Table 6.2 Tools for Disassembly and Assembly
Tool name
Phillips screwdriver
Standard screwdriver
Hexagonal wrench
Crescent wrench
Torque wrench
Box wrench
Box screwdriver
Forceps
Quantity
1
1
1
1
1
1
1
1
Remark
For M10 screw
CAUTION
Precautions for ATEX and IECEx Flameproof
Type Transmitters
• For a withstand flameproof type transmitter, as a rule, move the transmitter to a nonhazardous location, then proceed with maintenance and restore the instrument to the original condition.
• For a withstand ATEX and IECEx flameproof type transmitter, turn the lock bolt (hexagon socket bolt) clockwise with a wrench for hexagon head, unlock and remove the cover.
When installing the cover, it is the must to turn the lock bolt counterclockwise and lock the cover (locked to a torque of 0.7 Nm).
• For a withstand flameproof type transmitter, in no case should the user be allowed to modify the transmitter. Therefore, no user is allowed to add a integral indicator, or use the transmitter with the indicator removed.
Contact us for any modification.
Terminal cover
TEMP assembly
MAIN assembly
Indicator assembly
Amp. cover
Stud bolt
Lock screw
(for ATEX and IECEx
flameproof type)
Figure 6.2 Mounting and Removal of Integral
Indicator and MAIN and TEMP
Assembly
F0602.ai
IM 01C50G01-01EN
6.3.1 Replacement of Integral Indicator
Removal of integral indicator
1. Remove the cover.
2. Remove two mounting screws while using your hand to support the integral indicator.
3. Remove the indicator assembly from the
MAIN assembly. At this time, straighten and pull the indicator assembly forward so that the connector connecting the MAIN assembly and the indicator assembly is not damaged.
Mounting the Integral indicator
Integral Indicator can be installed in the following three directions.
<6. Maintenance>
6-3
6.3.2 Replacement of MAIN and TEMP
Assembly
IMPORTANT
Please replace the MAIN and TEMP assembly together.
Removal of MAIN AND TEMP assembly
1. Remove the cover.
2. If a integral indicator is mounted, refer to subsection 6.3.1 and remove the indicator.
3. Remove the two stud bolts.
4. Pull the MAIN assembly directly toward you.
5. Remove two stud bolts.
6. Pull the TEMP assembly directly toward you.
NOTE
Use care not to apply excessive force to the
MAIN and TEMP assembly during removal.
Mounting the MAIN and TEMP assembly
1. Align the mounting hole of the TEMP assembly with the stud bolt, and carefully insert the
TEMP assembly into the connector in a straight manner so that the connector is not damaged.
2. Tighten the two stud bolts.
3. Align the mounting hole of the MAIN assembly with the stud bolt, and carefully insert the
MAIN assembly into the connector in a straight manner so that the connector is not damaged.
4. Tighten the two stud bolts.
5. If the transmitter is equipped with an integral indicator, refer to subsection 6.3.1 to mount the indicator.
6. Mount the cover.
Figure 6.3 Installation Direction of Indicator
F0603.ai
1. Place the Indicator assembly in desired direction over the MAIN assembly.
2. Align the mounting hole of the Indicator assembly with the stud bolt hole, and carefully insert the indicator into the connector in a straight manner so that the connector is not damaged.
3. Tighten the two mounting screws that secure the indicator.
4. Mount the cover.
IM 01C50G01-01EN
6.4 Troubleshooting
When the measured value is found abnormal, follow the troubleshooting flowchart below. If the complex nature of the trouble means that the cause cannot be identified using the following flowchart, refer the matter to our service personnel.
6.4.1 Basic Troubleshooting Flow
When the process measurement is found to be abnormal, it is necessary to determine whether the input temperature is out of range, the sensor has failed or being damaged, or the unit has been improperly wired. If it is suspected that the measurement system is the source of the problem, use the flowchart to identify the affected area and determine how to proceed.
In these troubleshooting steps, the self diagnostic function provides helpful solutions to the problem, refer to the instructions in Section 6.5 for details.
: Part supported
by self-diagnosis
Measured value is found faulty
YES
Inspect the process
Error in process variable?
NO
Faulty area in measurement system
Error in measurement system
YES
Inspect receiver
Environmental condition
Receiver error
NO
Transmitter
Environmental condition: check, study, correction
Check the transmitter
Operating requirements
Operating requirements: check, study, correction
Figure 6.4 Basic Flow and Self-diagnosis
F0604.ai
<6. Maintenance>
6.4.2 Example of Troubleshooting Flow
6-4
The following phenomena indicate that this instrument may be out of operation.
[Example]
• No output signal is delivered.
• Process variable changes but the output
signal remains unchanged.
• The assessed value of the process variable
and the output are not coincident.
• If a integral indicator is attached, check the display of the error code.
• Connect a hand-held terminal and check self-diagnosis.
Was a faulty area found with selfdiagnosis?
NO
YES
Refer to the error message list and check for recovery measures.
Is the polarity of the power supply correct?
YES
NO
Check the polarity between the power supply and terminal box and correct it.
Are the power supply voltage and load resistance correct?
NO
YES
Is the sensor correctly connected?
Refer to Section 5.2 and set the specified voltage and load resistance.
NO
YES
Check the sensor connection and correct it.
Is there a disconnection in the loop?
Do the loop numbers correspond to the counterpart?
YES
NO
Check for disconnection or faulty wiring and take corrective measures.
Refer to our service personnel for details.
Figure 6.5 Example of Troubleshooting Flow
F0605.ai
IM 01C50G01-01EN
<6. Maintenance>
6-5
Table 6.3 Problems, Causes and Countermeasures
Observed
Problems
Output fluctuates greatly.
Transmitter outputs fixed current.
Possible Cause Countermeasure
Span is too narrow.
Check the range, and change the settings to make the span larger.
Input adjustment by user was not corrctly done.
Output adjustment by user was not correctly done.
The transmitter is in manual (test output) mode.
Clear the user adjustment
(Sensor trim) value or set it to off.
Clear the user adjustment
(output trim) value or set it to off.
Release manual mode. (Make the transmitter return to
Automatic Mode)
Output adjustment by user was not correctly
Clear the user adjustment
(output trim) value or set it to done.
off.
LRV is greater than URV. Set the correct value to URV and LRV.
Related
Parameter
Sim
(HART)
PV LRV
PV URV reset
Sensor1(2) Trim reset AO Trim exec Loop Test enable Dev Var reset AO Trim
─
Related Parameter
(FF)
Sensor1 Trim
Sensor2 Trim
─
SIM_ENABLE_MSG
─
Output is reversed.
(See note 1)
Parameters cannot be changed.
Sensor backup function doesn’t work correctly.
Output damping doesn’t work.
The transmitter is in write protect status.
Configuration of Sensor1 and Sensor2 is not correct.
Sensor backup mode is not enabled.
Damping time constant is set to “0 second.”
Release write protect.
• Check the type and wire settings for Sensor1 and
Sensor2.
• Check the connection of
Sensor1 and Sensor2.
Change PV mapping “Sensor
Backup.”
Set correct value.
PV LRV
PV URV
Write Protect
Sns1(2) Probe
Type
Sns1(2) Wire
PV is
AO Damping
─
WRITE_LOCK
SENSOR_TYPE_1(2)
SENSOR_
CONNECTION_1(2)
BACKUP_VALUE
PV_FTIME
Note 1: If the reversed output is desired and necessary setting was done by user, it is not considered as a problem.
6.5 Integral Indicator and Error Display
For temperature transmitters equipped with an integral indicator, errors in the temperature sensor or the transmitter cause an integral indicator to call up the applicable error code. Table 6.4 lists the error codes for
HART and the associated corrective actions. Table 6.6 lists the error codes for Foundation fieldbus.
Table 6.4 List of Error Codes (HART)
Alarm
Number
AL.00
Indicator
Message
CPU.ERR
MAIN CPU failed
AL.01
AL.02
AL.03
AL.04
AL.05
AL.06
AL.07
AL.08
AL.09
SENSOR
TMP.MEM
AD.CONV
CAL.ERR
CAL.ERR
TMP.ERR
COM.EEP
TMP.MEM
COM.ERR
Cause
Sensor non-volatile memory verifies alarm
Non-volatile memory of the TEMP ASSY verify alarm
Input circuit hardware failed
MAIN ASSY memory failed
TEMP ASSY memory failed
TEMP ASSY voltage failed
Communication non-volatile memory verifies alarm
Non-volatile memory of the TEMP ASSY verifies alarm
Internal communication failed
Output operation during error
According to the transmitter failure output (burnout)
Communacation disabled
According to the transmitter failure output (burnout)
Communication enabled
Continue to operate and output
According to the transmitter failure output (burnout)
Communication enabled
IM 01C50G01-01EN
<6. Maintenance>
6-6
AL.23
AL.24
AL.25
AL.26
AL.27
AL.30
AL.31
AL.40
AL.41
AL.42
AL.43
AL.44
AL.45
AL.50
AL.51
AL.52
AL.53
AL.54
AL.60
Alarm
Number
AL.10
AL.11
AL.12
AL.13
AL.14
AL.15
AL.20
AL.21
AL.22
AL.61
AL.62
Indicator
Message
S.1.FAIL
S.2.FAIL
S.1.SHRT
S.2.SHRT
S.1.CORR
S.2.CORR
S.1.SGNL
S.2.SGNL
TERMNL
S.1.FAIL
S.2.FAIL
DRIFT
S.1.CYCL
S.2.CYCL
PV LO
PV HI
S.1 LO
S.1 HI
S.2 LO
S.2 HI
AMBNT.L
AMBNT.H
LRV LO
LRV HI
URV LO
URV HI
SPAN.LO
PV.CFG
S.1 CFG
S.2 CFG
Cause Output operation during error
Sensor 1 failed or disconnected from terminal block Refar table 6.5
Sensor 2 failed or disconnected from terminal block Refar table 6.5
Sensor 1 short-circuited Refar table 6.5
Sensor 2 short-circuited
Sensor 1 corroded
Sensor 2 corroded
Refar table 6.5
Continue to operate and output
Continue to operate and output
Sensor 1 input is out of measurable range.
Sensor 2 input is out of measurable range.
Terminal block temperature is abnormal. Or terminal block temperature sensor failed
During sensor backup operation, Sensor1 fails, it has output Sensor2
During sensor backup operation, Sensor2 fails
Sensor drift
Temperature cycling times of Sensor1 exceeds the threshold
Temperature cycling times of Sensor2 exceeds the threshold
PV value is below the range limit setting
Continue to operate and output
Continue to operate and output
Refar table 6.5
Operating to the backup side.
When the backup side also fails, output is according to burnout setting.
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
PV value is above the range limit setting
Measured temperature of sensor 1 is too low
Measured temperature of sensor 1 is too high
Measured temperature of sensor 2 is too low
Measured temperature of sensor 2 is too high
Ambient temperature is below-40 degree C
Lower limit 3.68mA (-2%)
Upper limit 20.8mA (105%)
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
Ambient temperature is above 85 degree C
LRV setting is below the sensor operating temperature range
LRV setting is above the sensor operating temperature range
URV setting is below the sensor operating temperature range
URV setting is above the sensor operating temperature range
It is set below recommended minimum span
There is a setting error in the sensor that is mapped to the PV
There is a false set to sensor1
There is a false set to sensor2
Continue to operate and output
Continue to operate and output
Continue to operate and output
Continue to operate and output
Hold the output of the previous error
When it occurs at startup, hold at
4mA
Continue to operate and output
Continue to operate and output
Table 6.5 Output operation (HART)
Current output mapping
SENS.1
S.1-TER
TERM
SENS.2
S.2-TER
S.1-S.2
S.2-S.1
AVG
BACKUP
S.1.FAIL
Sensor Burnout
Sensor Burnout
*1
*1
*1
Sensor Burnout
Sensor Burnout
Sensor Burnout
*2
S.2.FAIL
*1
*1
*1
Sensor Burnout
Sensor Burnout
Sensor Burnout
Sensor Burnout
Sensor Burnout
*2
*1: Continue to operate and output.
*2: When both sensor1 and sensor2 occur error, output is burnout.
S.1.SHRT
Sensor Burnout
Sensor Burnout
*1
*1
*1
Sensor Burnout
Sensor Burnout
Sensor Burnout
*2
S.2.SHRT
*1
*1
*1
Sensor Burnout
Sensor Burnout
Sensor Burnout
Sensor Burnout
Sensor Burnout
*2
TERMNL
*1
Sensor Burnout
Sensor Burnout
*1
Sensor Burnout
*1
*1
*1
*1
IM 01C50G01-01EN
Table 6.6
AL.12
AL.13
AL.14
AL.15
AL.20
AL.21
AL.22
Alarm
Number
AL.00
AL.01
AL.02
AL.03
AL.04
AL.05
AL.06
AL.07
AL.08
AL.09
AL.10
AL.11
AL.61
AL.62
AL.100
AL.101
AL.101
AL.102
AL.102
AL.103
AL.103
AL.104
AL.104
AL.105
AL.23
AL.24
AL.25
AL.26
AL.27
AL.40
AL.41
AL.42
AL.43
AL.44
AL.45
AL.105
AL.106
AL.106
AL.110
AL.111
AL.112
AL.113
AL.114
AL.115
<6. Maintenance>
6-7
S.1 CFG
S.2 CFG
NOT.RDY
AI1 HH
AI1 LL
AI2 HH
AI2 LL
AI3 HH
AI3 LL
AI4 HH
AI4 LL
PID1.HH
S.1.FAIL
S.2.FAIL
DRIFT
S.1.CYCL
S.2.CYCL
S.1 LO
S.1 HI
S.2 LO
S.2 HI
AMBNT.L
AMBNT.H
PID1.LL
PID2.HH
PID2.LL
RS O/S
STB O/S
LTB O/S
MTB O/S
AI1 O/S
AI2 O/S
List of Error Codes (FF)
Indicator
Message
CPU.ERR
SENSOR
TMP.MEM
AD.CONV
CAL.ERR
CAL.ERR
TMP.ERR
COM.EEP
TMP.MEM
COM.ERR
S.1.FAIL
S.2.FAIL
S.1.SHRT
S.2.SHRT
S.1.CORR
S.2.CORR
S.1.SGNL
S.2.SGNL
TERMNL
Cause
MAIN CPU failed
Sensor non-volatile memory verifies alarm
Non-volatile memory of the TEMP ASSY verifies alarm
Input circuit hardware failed
MAIN ASSY memory failed
TEMP ASSY memory failed
TEMP ASSY voltage failed
Communication non-volatile memory verifies alarm
Non-volatile memory of the TEMP ASSY verifies alarm
Internal communication failed
Sensor 1 failed or disconnected from terminal block
Sensor 2 failed or disconnected from terminal block
Sensor 1 short-circuited
Sensor 2 short-circuited
Sensor 1 corroded
Sensor 2 corroded
Sensor 1 input is out of measurable range.
Sensor 2 input is out of measurable range.
Terminal block temperature is abnormal. Such as abnormal or disconnection of the terminal block temperature sensor
During sensor backup operation, Sensor1 fails, it has output Sensor2
During sensor backup operation, Sensor2 fails
Sensor drift
Temperature cycling times of Sensor1 exceeds the threshold
Temperature cycling times of Sensor2 exceeds the threshold
Measured temperature of sensor 1 is to low
Measured temperature of sensor 1 is to high
Measured temperature of sensor 2 is to low
Measured temperature of sensor 2 is to high
Ambient temperature is below-40 degree C
Ambient temperature is above 85 degree C
There is a false set to sensor1
There is a false set to sensor2
Any function block is not scheduled
HI HI alarm occurs in AI1 block
LO LO alarm occurs in AI1 block
HI HI alarm occurs in AI2 block
LO LO alarm occurs in AI2 block
HI HI alarm occurs in AI3 block
LO LO alarm occurs in AI3 block
HI HI alarm occurs in AI4 block
LO LO alarm occurs in AI4 block
HI HI alarm occurs in PID1block
LO LO alarm occurs in PID1 block
HI HI alarm occurs in PID2 block
LO LO alarm occurs in PID2 block
The actual mode of the RS block is O/S.
The actual mode of the STB block is O/S.
The actual mode of the LTB block is O/S.
The actual mode of the MTB block is O/S.
The actual mode of the AI1 block is O/S.
The actual mode of the AI2 block is O/S.
IM 01C50G01-01EN
SCHEDL
AR O/S
AR MAN
SCHEDL
AI1.SIM
AI2.SIM
AI3.SIM
AI4.SIM
AI1.MAN
AI2.MAN
AI3.MAN
AI4.MAN
PID.MAN
SCHEDL
PID.BYP
PID2.O/S
PID.MAN
SCHEDL
PID.BYP
SC O/S
SC MAN
SCHEDL
IS O/S
IS MAN
DI2.MAN
SCHEDL
DI2.SIM
DI3 O/S
DI3.MAN
SCHEDL
DI3.SIM
DI4 O/S
DI4.MAN
SCHEDL
DI4.SIM
PID1.O/S
Indicator
Message
AI3 O/S
AI4 O/S
SCHEDL
SCHEDL
SCHEDL
SCHEDL
STB.MAN
DI1 O/S
DI1.MAN
SCHEDL
DI1.SIM
DI2 O/S
AL.137
AL.138
AL.138
AL.138
AL.150
AL.151
AL.152
AL.153
AL.154
AL.155
AL.156
AL.157
AL.134
AL.134
AL.134
AL.135
AL.135
AL.135
AL.135
AL.136
AL.136
AL.136
AL.137
AL.137
AL.131
AL.131
AL.131
AL.132
AL.132
AL.132
AL.132
AL.133
AL.133
AL.133
AL.133
AL.134
Alarm
Number
AL.116
AL.117
AL.118
AL.119
AL.120
AL.121
AL.122
AL.130
AL.130
AL.130
AL.130
AL.131
The actual mode of the AI3 block is O/S.
The actual mode of the AI4 block is O/S.
Execution of AI1 is not scheduled.
Execution of AI2 is not scheduled.
Execution of AI2 is not scheduled.
Execution of AI1 is not scheduled.
The actual mode of the STB block is Man.
The actual mode of the DI1 block is O/S.
The actual mode of the DI1 block is Man.
Execution of DI1 is not scheduled.
Simulate of the DI1 block is active.
The actual mode of the DI2 block is O/S.
The actual mode of the DI2 block is Man.
Execution of DI2 is not scheduled.
Simulate of the DI2 block is active.
The actual mode of the DI3 block is O/S.
The actual mode of the DI3 block is Man.
Execution of DI3 is not scheduled.
Simulate of the DI3 block is active.
The actual mode of the DI4 block is O/S.
The actual mode of the DI4 block is Man.
Execution of DI4 is not scheduled.
Simulate of the DI4 block is active.
The actual mode of the PID1 block is O/S.
The actual mode of the PID1 block is Man.
Execution of PID1 is not scheduled.
The bypass action for PID1 is active.
The actual mode of the PID2 block is O/S.
The actual mode of the PID2 block is Man.
Execution of PID2 is not scheduled.
The bypass action for PID2 is active.
The actual mode of the SC block is O/S.
The actual mode of the SC block is Man.
Execution of SC is not scheduled.
The actual mode of the IS block is O/S.
The actual mode of the IS block is Man.
Execution of IS is not scheduled.
The actual mode of the AR block is O/S.
The actual mode of the AR block is Man.
Execution of AR is not scheduled.
Simulate of the AI1 block is active.
Simulate of the AI2 block is active.
Simulate of the AI3 block is active.
Simulate of the AI4 block is active.
The actual mode of the AI1 block is Man.
The actual mode of the AI2 block is Man.
The actual mode of the AI3 block is Man.
The actual mode of the AI4 block is Man.
Cause
<6. Maintenance>
6-8
IM 01C50G01-01EN
<7. General Specifications>
7. General Specifications
7.1 Standard Specifications
Performance Specifications
Accuracy
HART communication type:
A/D accuracy/span + D/A accuracy
(See Table 7.1.)
Fieldbus communication type:
A/D accuracy (See Table 7.1.)
Cold Junction Compensation Accuracy
± 0.5°C (± 0.9 °F) for T/C only
Include influence of the ambient temperature.
Ambient Temperature Effect (per 10°C change)
±0.1% or ±(Temperature coefficient/span), whichever is greater. (See Table 7.2.)
Stability
RTD: ±0.1% of reading or ±0.1°C per 2 years, whichever is greater at 23±2°C.
T/C: ±0.1% of reading or ±0.1°C per year, whichever is greater at 23±2°C.
5 Year Stability
RTD: ±0.25% of reading or ±0.25°C, whichever is greater at 23±2°C.
T/C: ±0.5% of reading or ±0.5°C, whichever is greater at 23±2°C.
Vibration Effect
The YTA710 are tested to the following specifications with no effect on performance per
IEC 60770-1
10 to 60 Hz 0.21 mm peak displacement
60 to 2000 Hz 3g
Power Supply Effect
±0.005% of calibrated span per volt
7-1
Functional Specifications
Input signals
Input number: single and dual input
Input type is selectable: Thermocouples, 2-, 3-, and 4-wire RTDs, ohms and DC millivolts.
See Table 7.1.
Input signal source resistance (for T/C, mV)
1 kΩ or lower
Input lead wire resistance (for RTD, ohm)
10 Ω per wire or lower
Span & Range Limits
See Table 7.1.
Output signals
Two wire 4 to 20 mA DC Type
Output range: 3.68 to 20.8 mA
HART® protocol is superimposed on the 4 to
20 mA signal.
Fieldbus communication Type
Output signal based on F
OUNDATION fieldbus
TM
communication protocol.
Isolation
Input/Output/GND isolated to 500V DC
Except lightning protector option.
Manual Test Output Function
The output value can be set manually.
Sensor Burnout (HART Type)
High (21.6 mA DC) or Low (3.6 mA DC), user selectable.
Output in Transmitter Failure (HART Type)
Down-scale: –5%, 3.2 mA DC or less , sensor burnout –2.5%, 3.6 mA (Optional code C1)
Down-scale: –5%, 3.2 mA DC or less (Optional code C2)
Up-scale: 110%, 21.6 mA DC or more
(Standard or Optional code C3)
IM 01C50G01-01EN
Update Time (HART Type)
Approximately 0.5 seconds for a single sensor
(0.8 second for dual sensors) at damping time 0
Turn-on Time (HART Type)
Approximately 6 seconds for a single sensor
(7 seconds for dual sensors)
Damping Time Constant
Selectable from 0 to 100 seconds
Self-Diagnostics
Self-diagnostic function based on the NAMUR
NE107 standard detects failures in the hardware, configuration and communications.
Sensor-Diagnostics
Sensor drift, temperature cycle detect, and corrosion of the sensor.
Fieldbus functions (Fieldbus Type)
Functional specifications for Fieldbus communication conform to the standard specifications (H1) of F
OUNDATION
Fieldbus.
Function Block (Fieldbus Type)
Resource block
The resource block contains physical transmitter information.
Transducer block
The transducer block contains the actual measurement data and information about sensor type and configuration and diagnostics.
LCD display block
The LCD display block is used to configure the local display, if an LCD display is being used.
Analog input (AI)
Four independent AI blocks can be selected.
Digital input (DI)
Four DI function blocks can be used as a limit switch for those temperature.
< 7. General Specifications >
7-2
Other Function block
As other Function blocks, Arithmetic (AR),
Signal Characterizer (SC), Input Selector
(IS), and two PID function blocks are available.
Function block
AI
DI
SC
IS
AR
PID
Execution time (ms)
30
30
30
30
30
45
Link master function
This function enables backup of network manager and local control only by field devices.
Alarm function
Fieldbus models securely support various alarm functions, such as High/Low alarm, notice of block error, etc. based on
F
OUNDATION
fieldbus specifications.
Software download function
This function permits to update YTA software via a F
OUNDATION
fieldbus.
EMC Conformity Standards
EN61326-1 Class A, Table2
EN61326-2-3
EN61326-2-5 (for fieldbus)
Safety Requirement Standards
EN61010-1, C22.2 No.61010-1
• Altitude of installation site:
Max. 2,000 m above sea level
• Installation category: I
(Anticipated transient overvoltage 330 V)
• Pollution degree: 2
• Indoor/Outdoor use
EN61010-2-030, C22.2 No.61010-2-030
• Measurement category: O (Other)
(Measurement Input voltage: 150mVdc max)
IM 01C50G01-01EN
Normal Operating Condition
(Optional features or approval codes may affect limits.)
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F)
–30 to 80°C (–22 to 176°F) (with indicator model)
Ambient Humidity Limits
0 to 100% RH at 40°C (104°F)
Supply Voltage Requirements
HART Type
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (option code /A)
Minimum voltage limited at 16.6 V DC for digital communications HART
With 24 V DC supply, up to a 550Ω load can be used. See graph below.
600
External load resistance
R
(Ω)
250
Digital
Communication range
HART
10.5 16.6
25.2
Power supply voltage E (V)
42
F0701.ai
Figure 7.1 Relationship Between Power Supply
Voltage and External Load Resistance
Fieldbus Type
9 to 32V DC for general use and flameproof type
Communication Requirements
Supply Voltage: 9 to 32 V DC
Current Draw:
Steady state: 15 mA (max)
Software download state: 24 mA (max)
Load Requirements (HART Type)
0 to 1290Ω for operation
250 to 600Ω for digital communication
<7. General Specifications>
7-3
Physical Specifications
Enclosure
Material & Coating
Low copper cast aluminum alloy with polyurethane, mint-green paint. (Munsell
5.6BG 3.3/2.9 or its equivalent), or ASTM
CF-8M Stainless Steel
Degrees of Protection
IP66/IP67, TYPE 4X
Name plate and tag
316 SST
Mounting
Optional mounting brackets can be used either for two-inch pipe or flat panel mounting.
Terminal Screws
M4 screws
Integral Indicator (with indicator model)
5-digit numerical display, 6-digit unit display and bar graph.
Local Parameter Setting (with indicator model)
Parameter configuration by the push button offers easy and quick setup for parameters.
Accessible parameters are different with each output cord.
Weight
Alminum housing:
1.3 kg (2.9 lb) without integral indicator and mounting
Integral indicator: 0.2 kg (0.4 lb)
Bracket for horizontal pipe: 0.3 kg
Bracket for vertical pipe: 1.0 kg
Stainless housing:
3.1 kg (6.8 lb) without integral indicator and mounting
Integral indicator: 0.3 kg (0.7 lb)
Connections
Refer to “Model and Suffix Codes.”
IM 01C50G01-01EN
< 7. General Specifications >
Table7.1
Sensor Type
T/C
RTD
B
E
J
K
N
R
S
T
C
W3
L
U
Sensor type, measurement range, and accuracy.
Pt100
Pt200
Pt500
Pt1000
JPt100
Standard
IEC60584
ASTM
E988
DIN43710
IEC60751
-200 to -50
-50 to 400
0 to 400
400 to 1400
1400 to 2000
2000 to 2300
0 to 400
400 to 1400
1400 to 2000
2000 to 2300
-200 to -50
-50 to 900
-200 to -50
-50 to 600
-200 to 850
-200 to 850
-200 to 850
-200 to 300
-200 to 500
Measurement Range
°C
100 to 300
300 to 1820
°F
212 to 572
572 to 3308
-200 to -50
-50 to 1000
-200 to -50
-50 to 1200
-328 to -58
-58 to 1832
-328 to -58
-58 to 2192
-200 to -50
-50 to 1372
-200 to -50
-50 to 1300
-50 to 0
0 to 600
600 to 1768
-50 to 0
0 to 600
600 to 1768
-328 to -58
-58 to 2502
-328 to -58
-58 to 2372
-58 to 32
32 to 1112
1112 to 3214
-58 to 32
32 to 1112
1112 to 3214
-328 to -58
-58 to 752
32 to 752
752 to 2552
2552 to 3632
3632 to 4172
32 to 752
752 to 2552
2552 to 3632
3632 to 4172
-328 to -58
-58 to 1652
-328 to -58
-58 to 1112
-328 to 1562
-328 to 1562
-328 to 1562
-328 to 572
-328 to 932
Cu10
Ni120 mV ohm
—
SAMA
RC21-4
—
—
—
-70 to 150 -94 to 302
-70 to 320 -94 to 608
-10 to 120 [mV]
0 to 2000 [Ω]
Minimum
Span
25°C
(45°F)
10°C
(18°F)
±1.0
±0.08
±1.8
±0.012 [mV]
±0.35 [Ω]
±0.144
3 mV
20 Ω
Note 1: Total Accuracy = (A/D Accuracy / Span + D/A Accuracy) or (± 0.1% of calibrated span), whichever is greater.
Accuracy of Fieldbus type: A/D Accuracy.
For T/C input, add Cold Junction Compensation Error (± 0.5°C) to the total accuracy.
Example: when selecting Pt100 with measurement range of 0 to 200 °C
0.1°C / 200°C×100% of span +0.02% of span = 0.07% of span
Since the value is smaller than ±0.1% of span, the total accuracy is ±0.1%.
Note 2: T/C C type is same as W5 (ASTM E988).
±0.35
±0.25
±0.1
±0.22
±0.14
±0.1
±0.8
±0.5
±0.6
±0.9
±0.3
±0.2
±0.25
±0.14
±0.7
±0.5
±0.7
±0.9
±0.1
±0.5
±0.25
±0.8
±0.35
±1.0
±0.6
±0.4
±1.0
±0.5
±0.4
A/D Accuracy
°C
±3.0
±0.75
°F
±5.4
±1.35
±0.35
±0.16
±0.25
±0.20
±0.63
±0.29
±0.45
±0.36
±0.9
±0.45
±1.44
±0.63
±1.8
±1.08
±0.72
±1.8
±0.9
±0.72
±0.45
±0.25
±1.26
±0.9
±1.26
±1.62
±1.44
±0.9
±1.08
±1.62
±0.54
±0.36
±0.63
±0.45
±0.18
±0.396
±0.25
±0.18
±0.18
D/A
Accuracy
7-4
±0.02% of span
IM 01C50G01-01EN
<7. General Specifications>
Table 7.2 Temperature coefficient
Sensor Type
Thermocouples E, J, K, N, T, L, U
Temperature Coefficient
0.08°C + 0.02% of abs.reading
Thermocouples R, S, W3, C
Thermocouple B
100°C ≤ Reading < 300°C 1°C + 0.02% of abs.reading
300°C ≤ Reading
0.25°C + 0.02% of abs.reading
0.5°C + 0.02% of abs.reading
RTD mV ohm
0.08°C + 0.02% of abs.reading
0.002 mV + 0.02% of abs.reading
0.1Ω + 0.02% of reading
Note 1: The “abs.reading” for thermocouples and RTD means the absolute value of the reading in °C.
Example of “abs.reading”
When the temperature value is 250 Kelvin, “abs.reading” is 23.15.
|250−273.15|= 23.15
Note 2: Ambient Temperature Effect per 10 °C change is ±0.1% or ±(temperature coefficient/span), whichever is greater.
Example of Ambient Temperature Effect
Conditions:
1) Input Sensor: Pt100
2) Calibration Range: −100 to 100°C
3) Reading value: −50°C
Ambient Temperature Effect per 10°C
Temperature Coefficient/Span=(0.08°C+0.02/100×|−50°C|)/{100°C−(−100°C)}= 0.00045 → 0.045%
Therefore, Ambient Temperature Effect is ±0.1%/10°C
7-5
IM 01C50G01-01EN
< 7. General Specifications>
7.2 Model and Suffix Codes
Model Codes
YTA710
· · · · · · · · · · · · · · · · Temperature Transmitter
Output
Signal
—
Sensor input
Housing code
2
· · · · · · · · · · · ·
A
· · · · · · · · · ·
C
· · · · · · · · · ·
Electrical Connection
0
· · · · · · · ·
Integral Indicator
Mounting Bracket
Option codes
-J
· · · · · · · · · · · · · ·
-F
· · · · · · · · · · · · · ·
A
4 to 20 mA DC with digital communication HART 7protocol
Digital communication (F
· · · · · · · · · · · · · Always A
1
· · · · · · · · · · · ·
2
· · · · · · · ·
4
· · · · · · · ·
D
· · · · · · ·
N
· · · · · · ·
B
· · · · ·
D
· · · · ·
J
· · · · ·
K
· · · · ·
N
· · · · ·
/
Single
Double
Aluminum
Stainless
Optional specification
Description
OUNDATION
Fieldbus protocol)
G 1/2 female
1/2 NPT female
M20 female
Digital indicator with Local Operating Switch
None
SUS304 stainless steel 2-inch horizontal pipe mounting bracket *1
SUS304 stainless steel 2-inch vertical pipe mounting bracket
SUS316 stainless steel 2-inch horizontal pipe mounting bracket *1
SUS316 stainless steel 2-inch vertical pipe mounting bracket
None
*1: For flat-panel mounting, please prepare bolts and nuts.
7.3 Optional Specifications
Plating *1
Item
Lightning protector
Output signal Low-side in Transmitter failure
NAMUR NE43
Compliant *2
*2
Description
Power supply voltage: 10.5 to 32 V DC
Allowable current: Max. 6000A (8×20μs), repeating 1000A (8×20μs), 100 times
Color change
Amplifier cover only
Munsell code: N1.5, black
Color change
Amplifier and terminal covers
Munsell code: 7.5BG4/1.5,Jade green
Metallic silver
Munsell code: 7.5R4/14,Red
Coating change High anti-corrosion coating
Output signal Low-side: –5%, 3.2 mA DC or less.
Sensor burnout is also set to ‘Low’: –2.5%, 3.6 mA DC.
Output signal limits:
3.8 mA to 20.5 mA
Failure alarm down-scale: output status at CPU failure and hardware error is –5%, 3.2 mA or less.
Sensor burnout is also set to Low: –2.5%, 3.6 mA DC.
Data Configuration *2
Wired tag plate
Sensor matching
*1: Not applicable for Stainless housing.
*2: Not applicable for Fieldbus type.
Failure alarm up-scale: output status at CPU failure and hardware error is 110%, 21.6 mA or more.
In this case Sensor burnout is High: 110%, 21.6 mA DC
Description into “Descriptor” parameter of HART protocol (max. 16 characters)
SUS316 stainless steel tag plate wired onto transmitter
RTD sensor matching function
7-6
Code
A
P1
P2
P7
PR
X2
C1
C2
C3
CA
N4
CM1
IM 01C50G01-01EN
<7. General Specifications>
[For Explosion Protected Type]
Item
ATEX
IECEx
FM
CSA
Description
[4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2007, EN 60079-31:2009
Certificate: KEMA 07ATEX0130
II 2 G Ex d IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C, T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female *1
[4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable standard: IEC 60079-0:2011, IEC 60079-1:2007-04, IEC 60079-31:2008
Certificate: IECEx KEM 07.0044
Ex d IIC T6/T5 Gb, Ex tb IIIC T70°C / T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C (–40 to 167°F) for T6,
–40 to 80°C (–40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C (–22 to 149°F) for T70°C,
–30 to 80°C (–22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female *1
[4-20mA & Fieldbus: Explosionproof approval]
Applicable standard: Class 3600, Class 3615, Class 3810, ANSI/NEMA250
Class I, Division 1, Groups A, B, C and D.;
Class II/III, Division 1, Groups E, F and G.
“FACTORY SEALD, CONDUIT SEAL NOT REQUIRED.”
Enclosure Ratings: TYPE 4X
Temperature Class: T6
Ambient Temperature: -–40 to 60°C (–40 to 140°F)
Electrical Connection: 1/2NPT female *2
[4-20mA & Fieldbus: Explosionproof approval]
Applicable standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.30, C22.2 No.94,
C22.2 No.142, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1
C22.2 No.61010-2-030
Class I, Groups B, C and D,
Class II, Groups E, F and G,
Class III.
For Class I, Division2 Groups ABCD Locations “FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED”
Enclosure TYPE 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C
Electrical Connection: 1/2 NPT female *2
*1: Applicable for Electrical Connection Code 2 and 4.
*2: Applicable for Electrical Connection Code 2.
7-7
Code
KF2
SF2
FF1
CF1
IM 01C50G01-01EN
7.4 Dimensions
2-inch horizontal pipe mounting
111(4.37)
Electrical Connection
(Output signal)
< 7. General Specifications >
7-8
Electrical Connection
(Input signal)
With Indicator
(Optional)
Unit: mm (Approx. inch)
65.4(2.57)
47.1
(1.85)
66.1(2.60)
18.5
(0.73)
Terminal Cover
Shrouding Bolt
(For Explosionproof type)
Ground Terminal
Tag Plate
Horizontal Pipe
Mounting Bracket
(Optional)
56(2.21)
2-inch vertical pipe mounting
111(4.37)
Electrical Connection
(Output signal)
2-inch pipe
ø60.5(ø2.38)
Electrical Connection
(Input signal)
With Indicator
(Optional)
Shrouding Bolt
(For Explosionproof type)
65.4(2.57)
47.1
(1.85)
66.1(2.60)
18.5
(0.73)
Terminal Cover
Ground Terminal
Tag Plate
Vertical Pipe
Mounting Bracket
(Optional)
2-inch pipe
ø60.5(ø2.38)
Terminals
Communication
Terminals
Connection hook
CHECK METER
Connection hook
*1
101(3.98)
64(2.52)
70(2.76)
98(3.86)
F0702.ai
M10×1.5 12-deep female for mounting bracket
Terminal Configuration
Power supply and output terminal
External indicator (ammeter) termial
*1
Ground terminal
*1 : When using an external indicator or a check meter, the internal resistance must be 10Ω or less.
The hook is not available for Fieldbus communication type.
F0703.ai
IM 01C50G01-01EN
Revision Information
Title : YTA710 Temperature Transmitter (Hardware)
Manual No. : IM 01C50G01-01EN
Edition
1st
Date
June 2016
Page
— New publication.
Revised Item i
IM 01C50G01-01EN
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Phone : 81-422-52-5555
Branch Sales Offices
Osaka, Nagoya, Hiroshima, Kurashiki, Fukuoka, Kitakyusyu
YOKOGAWA CORPORATION OF AMERICA
Head Office
12530 West Airport Blvd, Sugar Land, Texas 77478, USA
Phone : 1-281-340-3800 Fax : 1-281-340-3838
Georgia Office
2 Dart Road, Newnan, Georgia 30265, USA
Phone : 1-800-888-6400/ 1-770-253-7000 Fax : 1-770-254-0928
YOKOGAWA AMERICA DO SUL LTDA.
Praca Acapulco, 31 - Santo Amaro, Sáo Paulo/SP, BRAZIL, CEP-04675-190
Phone : 55-11-5681-2400 Fax : 55-11-5681-4434
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111
YOKOGAWA ELECTRIC CIS LTD.
Grokholskiy per 13 Building 2, 4th Floor 129090, Moscow, RUSSIA
Phone : 7-495-737-7868 Fax : 7-495-737-7869
YOKOGAWA CHINA CO., LTD.
3F Tower D Cartelo Crocodile Building, No.568 West Tianshan Road,
Shanghai 200335, CHINA
Phone : 86-21-62396262 Fax : 86-21-62387866
YOKOGAWA ELECTRIC KOREA CO., LTD.
(Yokogawa B/D, Yangpyeong-dong 4-Ga), 21, Seonyu-ro 45-gil, Yeongdeungpo-gu,
Seoul, 150-866, KOREA
Phone : 82-2-2628-6000 Fax : 82-2-2628-6400
YOKOGAWA ENGINEERING ASIA PTE. LTD.
5 Bedok South Road, Singapore 469270, SINGAPORE
Phone : 65-6241-9933 Fax : 65-6241-2606
YOKOGAWA INDIA LTD.
Plot No.96, Electronic City Complex, Hosur Road, Bangalore - 560 100, INDIA
Phone : 91-80-4158-6000 Fax : 91-80-2852-1442
YOKOGAWA AUSTRALIA PTY. LTD.
Tower A, 112-118 Talavera Road, Macquarie Park NSW 2113, AUSTRALIA
Phone : 61-2-8870-1100 Fax : 61-2-8870-1111
YOKOGAWA MIDDLE EAST & AFRICA B.S.C.(C)
P.O. Box 10070, Manama, Building 577, Road 2516, Busaiteen 225, Muharraq,
Kingdom of BAHRAIN
Phone : 973-17358100 Fax : 973-17336100
Apr. '15
Printed in Singapore
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Preface
- 8 Notes on Handling
- 8 Nameplate
- 8 Transport
- 8 Storage
- 8 Choosing the Installation Location
- 8 Use of a Transceiver
- 8 Insulation Resistance Test and Withstand Voltage Test
- 8 Installation of Explosion Protected Type Transmitters
- 8 EMC Conformity Standards
- 8 Safety Requirement Standards
- 9 Part Names and Functions
- 9 Part Names
- 9 Hardware Error Burnout and Hardware Write Protect Switch
- 9 Integral Indicator Display Function
- 9 Local Parameter Setting
- 25 Installation
- 26 Wiring
- 26 Notes on Wiring
- 26 Loop Construction
- 26 Cable Selection
- 26 Cable and Terminal Connections
- 26 Wiring Cautions
- 26 Grounding
- 27 Maintenance
- 27 General
- 27 Calibration
- 27 Disassembly and Assembly
- 27 Troubleshooting
- 27 Integral Indicator and Error Display
- 28 Dimensions