Rosemount 3051S Wireless Series Scalable

Rosemount 3051S Wireless Series Scalable
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series Scalable
Pressure, Flow, and Level Solutions
www.rosemount.com
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Rosemount 3051S Wireless Series Scalable
Pressure, Flow, and Level Solutions
NOTICE
Read this manual before working with the product. For personal and system safety, and
for optimum product performance, make sure you thoroughly understand the contents
before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/ Middle East/ Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Rosemount® representative.
The products described in this document are NOT designed for nuclear-qualified
applications. Using non-nuclear qualified products in applications that require
nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Rosemount
Sales Representative.
Failure to follow these installation guidelines could result in death or serious injury:
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please
review the approvals section of this manual for any restrictions associated with a safe
installation.
• Before connecting a 375 Field Communicator in an explosive atmosphere, ensure the
instruments are installed in accordance with intrinsically safe or non-incendive field
wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Process leaks could result in death or serious injury.
• Install and tighten process connectors before applying pressure.
• Do not attempt to loosen or remove process connectors while the transmitter is in
service.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
www.rosemount.com
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
NOTICE
The Rosemount 3051S and all other wireless devices should be installed only after the
1420 Wireless Gateway has been installed and is functioning properly. Wireless devices
should also be powered up in order of proximity from the 1420 Wireless Gateway,
beginning with the closest. This will result in a simpler and faster network installation.
NOTICE
Shipping considerations for wireless products (Lithium Batteries):
The unit was shipped to you without the battery installed. Please remove the battery pack
from the unit prior to shipping.
Primary lithium batteries are regulated in transportation by the U. S. Department of
Transportation, and are also covered by IATA (International Air Transport Association),
ICAO (International Civil Aviation Organization), and ARD (European Ground
Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Please consult current regulations
and requirements before shipping.
The battery pack with the wireless unit contains two “C” size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each pack. Under normal conditions,
the battery materials are self-contained and are not reactive as long as the
batteries and the pack integrity are maintained. Care should be taken to
prevent thermal, electrical or mechanical damage. Contacts should be
protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Batteries should be stored in a clean and dry area. For maximum battery life,
storage temperature should not exceed 30° C.
Rosemount 3051S Wireless Series may be protected by one or more of the following U.S. Patent Nos.
4,370,890; 4,466,290; 4,612,812; 4,791,352; 4,798,089; 4,818,994; 4,833,922; 4,866,435; 4,926,340;
4,988,990; and 5,028,746. Mexico Patentado No. 154,961. May depend on model. Other foreign patents issued
and pending.
tp-2
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Table of Contents
SECTION 1
Introduction
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Shipping considerations for wireless products (Lithium Batteries): . . . . . .1-3
SECTION 2
Configuration
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Commissioning on the bench With HART . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Connection Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Fast Key Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Process Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Sensor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Set Process Variable Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Set Output (Transfer function) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Security (Write Protect) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Sensor Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Master Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Advanced Functions for HART Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Saving, Recalling, and Cloning Configuration Data . . . . . . . . . . . . . . . . .2-10
Device Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
Transmit Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
Remove Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
1-1
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
SECTION 3
Installation
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Mount the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-10
Consider Housing Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-11
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-11
Battery Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
Installing the LCD Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
Rosemount 304, 305 and 306 Integral Manifolds . . . . . . . . . . . . . . . . . . . . . .3-13
Rosemount 305 Integral Manifold Installation Procedure . . . . . . . . . . . .3-13
Rosemount 306 Integral Manifold Installation Procedure . . . . . . . . . . . .3-14
Rosemount 304 Conventional Manifold Installation Procedure . . . . . . . .3-15
Manifold Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-16
SECTION 4
Commissioning
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
Verify Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
SECTION 5
Operation and
Maintenance
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
Sensor Trim Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Zero Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Recall Factory Trim—Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
Compensating for Line Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
LCD Screen Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Startup Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Diagnostic Button Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Network Diagnostic Status Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
Device Diagnostic Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
SECTION 6
Troubleshooting
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
Disassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
Remove from Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
Remove Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
Remove Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-4
Remove the SuperModule from the Housing . . . . . . . . . . . . . . . . . . . . . . .6-4
Reassembly Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-5
Attach the SuperModule to the Wireless Housing . . . . . . . . . . . . . . . . . . .6-5
Install the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-5
Reassemble the Process Flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-5
1-2
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
APPENDIX A
Specifications and
Reference Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Ordering Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Rosemount 3051S Series Coplanar . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Rosemount 3051S Series In-Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-17
Rosemount 3051S Series Liquid Level . . . . . . . . . . . . . . . . . . . . . . . . . A-20
Seal Options (page A-21—A-22) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-21
Transmitter Options continued from page A-20 . . . . . . . . . . . . . . . . . . . A-22
APPENDIX B
Product
Certifications
Wireless Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ordinary Location Certification for FM . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B-1
B-1
B-1
B-1
B-1
B-2
B-2
1-3
Reference Manual
Rosemount 3051S Wireless Series
1-4
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 1
Rosemount 3051S Wireless Series
Introduction
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3
USING THIS MANUAL
www.rosemount.com
The sections in this manual provide information on installing, operating, and
maintaining the Rosemount 3051S Wireless pressure transmitter with HART®
protocol. The sections are organized as follows:
•
Section 2: Configuration provides instruction on commissioning and
operating 3051S Wireless transmitters. Information on software
functions, configuration parameters, and online variables is also
included.
•
Section 3: Installation contains mechanical and electrical installation
instructions.
•
Section 4: Commissioning contains techniques for properly
commissioning the device.
•
Section 5: Operation and Maintenance contains operation and
maintenance techniques.
•
Section 6: Troubleshooting provides troubleshooting techniques for
the most common operating problems.
•
Appendix A: Specifications and Reference Data supplies reference
and specification data, as well as ordering information.
•
Appendix B: Product Certifications contains approval information.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
MODELS COVERED
The following 3051S Wireless pressure transmitters are covered in this
manual.
Rosemount 3051S Wireless Coplanar™ Pressure Transmitter
Measurement Type
Performance
Class
Differential
Gage
Absolute
Classic
X
X
X
Rosemount 3051S Wireless In-Line Pressure Transmitter
Measurement Type
Performance
Class
Differential
Gage
Absolute
Classic
–
X
X
Rosemount 3051S Wireless Liquid Level Pressure Transmitter
1-2
Measurement Type
Performance
Class
Differential
Gage
Absolute
Classic
X
X
X
Reference Manual
00809-0100-4802, Rev BA
August 2007
SERVICE SUPPORT
Rosemount 3051S Wireless Series
To expedite the return process outside of the United States, contact the
nearest Rosemount representative.
Within the United States, call the Emerson Process Management Instrument
and Valves Response Center using the 1-800-654-RSMT (7768) toll-free
number. This center, available 24 hours a day, will assist you with any needed
information or materials.
The center will ask for product model and serial numbers, and will provide a
Return Material Authorization (RMA) number. The center will also ask for the
process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. If the product being returned was exposed to a
hazardous substance as defined by OSHA, a copy of the required Material Safety Data
Sheet (MSDS) for each hazardous substance identified must be included with the returned
goods.
NOTICE
Shipping considerations for wireless products (Lithium Batteries):
The unit was shipped to you without the battery installed. Please remove the battery pack from
the unit prior to shipping.
Primary lithium batteries (charged or discharged) are regulated in transportation by the U. S.
Department of Transportation, and are also covered by IATA (International Air Transport
Association), ICAO (International Civil Aviation Organization), and ARD (European Ground
Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Please consult current regulations and
requirements before shipping.
The battery pack with the wireless unit contains two “C” size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each pack. Under normal conditions,
the battery materials are self-contained and are not reactive as long as the
batteries and the pack integrity are maintained. Care should be taken to
prevent thermal, electrical or mechanical damage. Contacts should be
protected to prevent premature discharge.
Emerson Process Management Instrument and Valves Response Center
representatives will explain the additional information and procedures
necessary to return goods exposed to hazardous substances.
1-3
Reference Manual
Rosemount 3051S Wireless Series
1-4
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 2
Rosemount 3051S Wireless Series
Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Commissioning on the bench With HART . . . . . . . . . . . . page 2-2
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4
Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-5
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-6
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-7
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-9
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-10
Advanced Functions for HART Protocol . . . . . . . . . . . . . page 2-11
Device Network Configuration . . . . . . . . . . . . . . . . . . . . . page 2-12
OVERVIEW
This section contains information on commissioning and tasks that should be
performed on the bench prior to installation.
Field Communicator and AMS instructions are given to perform configuration
functions. For convenience, Field Communicator fast key sequences are
labeled “Fast Keys” for each software function below the appropriate
headings.
Example Software Function
Fast Keys
SAFETY MESSAGES
Warnings (
1, 2, 3, etc.
Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
)
Explosions can result in death or serious injury.
•
Before connecting a 375 Field Communicator in an explosive atmosphere, make
sure the instruments are installed in accordance with intrinsically safe or
nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
•
Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference this device
must accept any interference received, including interference that may cause
undesired operation.
This device must be installed to ensure a minimum antenna separation distance of
20cm from all persons.
www.rosemount.com
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
COMMISSIONING ON
THE BENCH WITH HART
Commissioning consists of testing the transmitter and verifying transmitter
configuration data. 3051S Wireless transmitters can be commissioned either
before or after installation. Commissioning the transmitter on the bench before
installation using a 375 Field Communicator or AMS ensures that all
transmitter components are in working order.
To commission on the bench requires a 375 Field Communicator or AMS.
Connect the Field Communicator leads to the terminals labeled “COMM” on
the terminal block. See Figure 2-1 on page 2-2.
When using a Field Communicator, any configuration changes made must be
sent to the transmitter by using the “Send” key (F2). AMS configuration
changes are implemented when the “Apply” button is clicked.
AMS Wireless and Direct Connections
AMS is capable of connecting to devices either directly, using a HART
modem, or wirelessly via the 1420. When configuring on the bench using a
HART modem, double click the device icon (or right click and select
Configure/Setup), then choose the Configure/Setup tab. Configure the device
settings using the Direct Connection menu. When configuring wirelessly via
the 1420, double click the device icon (or right click and select
Configure/Setup), then choose the Configure/Setup tab. Configure the device
settings using the Wireless Connection menu.
Connection Diagrams
Bench Hook-up
Connect the bench equipment as shown in Figures 2-1, and turn on the Field
Communicator by pressing the ON/OFF key or log into AMS. The Field
Communicator or AMS will search for a HART-compatible device and indicate
when the connection is made. If the Field Communicator or AMS fail to
connect, it indicates that no device was found. If this occurs, refer to
Section 6: Troubleshooting.
Field Hook-up
Figures 2-1 illustrates the wiring for a field hook-up with a Field Communicator
or AMS. The Field Communicator or AMS may be connected at “COMM” on
the transmitter terminal block.
Figure 2-1. 375 Connection
P/N 00753-9200-0010
P/N 00753-9200-0010
COMM
COMM
For HART communication, a 3051S WPT DD is required.
2-2
Reference Manual
00809-0100-4802, Rev BA
August 2007
REVIEW
CONFIGURATION DATA
Fast Keys
1, 5
Rosemount 3051S Wireless Series
NOTE
Information and procedures in this section that make use of Field
Communicator fast key sequences and AMS assume that the transmitter and
communication equipment are connected, powered, and operating correctly.
The following is a list of factory default configurations. These can be reviewed
by using the Field Communicator or AMS.
Field Communicator
Enter the fast key sequence to view the configuration data.
Manufacturer
Model
Measurement
Module Configuration
Module Range
Calibration Type
Model Number I
Model Number II
Model Number III
PV is
SV is
TV is
QV is
Unit
Lower Sensor Limit
Upper Sensor Limit
Lower Range Point (0%)
Upper Range Point (100%)
Min Span
Lower Trim Point
Upper Trim Point
Supported Trim
Sensor 1 Trim Units
Min Lower Trim
Max Lower Trim
Min Upper Trim
Max Upper Trim
Sensor 1 Min Trim Diff
Transfer Function
Damping
Sensor S/N
Unit
Lower Sensor Limit
Upper Sensor Limit
Unit
Lower Sensor Limit
Upper Sensor Limit
Supply Units
Lower Sensor Limit
Upper Sensor Limit
Isolator Material
Fill Fluid
Process Connector
Process Conn. Material
O Ring Material
Drain Vent Material
Number
Type
Diaphragm Material
Seal Fill Fluid
Tag
Date
Descriptor
Message
Write Protect
Power Mode
LCD Mode
Transmit Rate
Universal Rev
Field Device Rev
Software Rev
Hardware Rev
Radio Model Number
Radio Hardware Rev
Radio SW Major Rev
Radio SW Minor Rev
Radio SW Build
Physical Signaling
Transmitter S/N
Dev ID
Network ID
Node ID
Radio Type
Database Mode
Wireless Device Type
Poll Address
Num Req Preams
Dev Flags
Distributor
HI-HI Alert
HI Alert
LO Alert
LO-LO Alert
AMS
Right click on the device and select “Configure/Setup” from the menu. Select
the tabs to review the transmitter configuration data.
2-3
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
FIELD COMMUNICATOR
Menu Tree
1. PROCESS
VARIABLES
2. DIAG/SERVICE
1.
2.
3.
4.
5.
Pressure
Percent of Range
Sensor Temperature
Supply Voltage
Process Variable is
1. TEST DEVICE
1. Master Reset
2. Status
3. Status Log
1. Logged Sensor Status
2. Clear Status Log
1. Keypad Input
2. Apply Values
1. RERANGE
2. CALIBRATION
1. Tag
2. Unit
3. RANGE VALUES
3. BASIC SETUP
4.
5.
6.
7.
1.
2.
3.
4.
2. SENSOR TRIM
3. Recall Factory Trim
1. Keypad Input
2. Apply Values
1.
2.
3.
4.
5.
6.
7.
8.
DEVICE INFO
Transfer Function
Damping
LCD Display Config.
1. SENSORS
Date
Descriptor
Message
Write Protect
Model
Model Number I
Model Number II
Model Number III
1. PRESSURE SENSOR
4. DETAILED
SETUP
1. PROCESS
VARIABLES
2. RANGE VALUES
3. Unit
4. Transfer Function
5. Damping
6. Sensor Temperature
Unit
3. OUTPUT
CONDITION
1. Sensor Temperature
2. Sensor Temperature Unit
1. Keypad Input
2. Apply Values
1. DEVICE SETUP
2. PV
3. Lower Range
Point (0%)
4. Upper Range
Point (100%)
1.
2.
3.
4.
2. PROCESS
VARIABLES
1. Poll Address
2. Num Req Preams
5. Review
5. VARIABLE
REMAPPING
1. NETWORK
4. DEVICE
INFORMATION
2. FIELD
DEVICE INFO
3. SENSOR
INFO
4. DIAPHRAGM
SEALS INFO
1.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
4.
HI-HI Alert
HI Alert
LO Alert
LO-LO Alert
1.
2.
3.
4.
Process Variable is
Secondary Variable is
Tertiary Variable is
Quaternary Variable is
Radio Model No.
Radio Type
Wireless Device Type
Get Unique ID
Radio SW Major Rev
Radio SW Minor Rev
Radio SW Build
Radio Hardware Rev
1.
2.
3.
4.
5.
6.
Measurement Type
Module Config Type
Isolator Material
Fill fluid
Process Connector
Process Connection
Material
7. O-Ring Material
8. Drain Vent Material
9. Module Range
10. Sensor Serial
Number
1.
2.
3.
4.
2-4
Smart Power
Network ID
Set Join Key
Radio State
3. HART OUTPUT
4. ALERTS
# of Diaphragm Seals
Seal Type
Seal Fill Fluid
Remote Seal Isolator
Material
Pressure
Percent of Range
Sensor Temperature
Process Variable is
1. SENSOR TRIM
2. Recall Factory Trim
2. SENSOR
SERVICE
3. Unit
4. Damping
1. NETWORK
Online Menu
1.
2.
3.
4.
1. PROCESS
VARIABLES
2. DEVICE TEMP. SENSOR
2. SIGNAL
CONDITION
Lower Sensor Trim
Upper Sensor Trim
Calibration Type
Sensor Trim Points
1.
2.
3.
4.
5.
Zero trim
Lower Sensor Trim
Upper Sensor Trim
Calibration Type
Sensor Trim Points
1.
2.
3.
4.
5.
Pressure
Percent of Range
Sensor Temperature
Supply Voltage
Process Variable is
1.
2.
3.
4.
Power Mode
Transmit Rate
Database Mode
High Power Refresh
1.
2.
3.
4.
5.
Pressure
Percent of Range
Sensor Temperature
Supply Voltage
Process Variable is
1.
2.
3.
4.
5.
6.
7.
Configure Alert
Mode
Assigned Variable
Direction
Units
Set Point
Dead Band
1. Tag
2. Date
3. Descriptor
4. Message
5. Model
6. Model Number I
7. Model Number II
8. Model Number III
9. Write Protect
10. REVISION #’S
11. Final Assembly #
12. Device ID
13. Distributor
1. Universal
Rev.
2. Field
Device Rev.
3. Software
Rev.
4. Hardware
Rev.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Fast Key Sequence
Rosemount 3051S Wireless Series
The following menu indicates fast key sequences for common functions. A
check (⻫) indicates the basic configuration parameters. At minimum, these
parameters should be verified as part of the configuration and startup
procedure.
⻫
⻫
⻫
⻫
Function
HART Fast Key Sequence
Damping
Date
Descriptor
Device Info
Field Device Information
LCD Display Configuration
Lower Sensor Trim
Message
Network
Number of Requested Preambles
Poll Address
Range Values
Variable Re-mapping
Rerange- Keypad Input
Sensor Information
Sensor Temperature
Sensor Trim
Sensor Trim Points
Status
Tag
Transfer Function (Setting Output Type)
Transmitter Security (Write Protect)
Units (Process Variable)
Upper Sensor Trim
Zero Trim
1, 3, 6
1, 3, 4, 1
1, 3, 4, 2
1, 3, 4
1, 4, 4, 2
1, 3, 7
1, 2, 2, 2, 1
1, 3, 4, 3
1, 4, 3, 1
1, 4, 3, 3, 2
1, 4, 3, 3, 1
1, 3, 3
1, 4, 3, 5
1, 2, 2, 1, 1
1, 4, 4, 3
1, 1, 3
1, 2, 2, 2
1, 2, 2, 2, 4
1, 2, 1, 2
1, 3, 1
1, 3, 5
1, 3, 4, 4
1, 3, 2
1, 2, 2, 2, 2
1, 4, 1, 1, 2, 1, 1
CHECK OUTPUT
Before performing other transmitter on-line operations, review the digital
output parameters to ensure that the transmitter is operating properly and is
configured to the appropriate process variables.
Process Variables
The pressure output value in both engineering units and percent of range will
reflect the applied pressure even when the applied pressure is outside of the
configured range as long as the applied pressure is between the upper and
lower range limit of the transmitter. For example, if a Range 2 3051S_T (LRL
= 0 psi, URL = 150 psi) is ranged from 0 to 100 psi, an applied pressure of
150 psi will return a % of range output of 150% and an engineering output of
150 psi.
Fast Keys
1, 1
Field Communicator
The process variable menu displays the following process variables:
•
Pressure
•
Percent of Range
•
Sensor Temperature
•
Supply Voltage
2-5
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
AMS
Right click on the device and select “Process Variables...” from the menu.The
process variable screen displays the following process variables:
Sensor Temperature
Fast Keys
1, 1, 3
•
Pressure
•
Percent of range
•
Sensor temperature
•
Supply Voltage
•
Primary Variable (PV)
The 3051S Wireless contains a temperature sensor near the pressure sensor
in the SuperModule. This does not provide an accurate process temperature.
Field Communicator
Enter the fast key sequence “Sensor Temperature” to view the sensor
temperature reading.
AMS
Right click on the device and select “Process Variables...” from the menu.
“Snsr Temp” is the sensor temperature reading.
BASIC SETUP
Set Process Variable
Units
Fast Keys
1, 3, 2
The PV Unit command sets the process variable units to allow you to monitor
your process using the appropriate units of measure.
Field Communicator
Enter the fast key sequence “Set Process Variable Units.” Select from the
following engineering units:
•
•
•
•
•
•
inH2O
inHg
ftH2O
mmH2O
mmHg
psi
•
•
•
•
•
•
bar
mbar
g/cm2
kg/cm2
Pa
kPa
•
•
•
•
•
torr
atm
MPa
inH2O at 4 °C
mmH2O at 4 °C
AMS
Right click on the device and select “Configure/Setup” from the menu. In the
Basic Setup tab, use “Unit” drop down menu to select units.
Set Output
(Transfer function)
Fast Keys
1, 3, 5
The 3051S Wireless has two output settings: Linear and Square Root.
Activate the square root output option to make output proportional to flow. As
input approaches zero, the 3051S Wireless automatically switches to linear
output in order to ensure a more smooth, stable output near zero (see
Figure 2-2).
From 0 to 0.6 percent of the ranged pressure input, the slope of the curve is
unity (y = x). This allows accurate calibration near zero. Greater slopes would
cause large changes in output (for small changes at input). From 0.6 percent
to 0.8 percent, curve slope equals 42 (y = 42x) to achieve continuous
transition from linear to square root at the transition point.
2-6
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Field Communicator
Enter the fast key sequence “Set Output (Transfer function).”
AMS
Right click on the device and select “Configure/Setup” from the menu.
1. In the Basic Setup tab, use “Xfer fnctn” drop down menu to select output,
click Apply.
2. After carefully reading the warning provided, select yes.
Figure 2-2. Square Root Output
Transition Point
Full Scale
Flow (%)
Sq. Root
Curve
Sq. Root Curve
Transition Point
Transition Point
Linear Section
Slope=42
Slope=1
Security (Write Protect)
Fast Keys
1, 3, 4, 4
The 3051S Wireless has a software write protect security feature.
Field Communicator
Enter the fast key sequence “Transmitter Security” to view the Write Protect
setting.
AMS
Right click on the device and select “Configure/Setup” from the menu. In the
Basic Setup tab, review the Write Protect setting.
LCD DISPLAY
The LCD display indicates output and abbreviated diagnostic messages.
NOTE
Use Rosemount Wireless LCD Part Number: 00753-9004-0002.
The LCD display features a four-line display and a bar graph. The first line of
five characters displays the output description, the second line of seven digits
displays the actual value, the third line of six characters displays engineering
units and the fourth line displays “Error” when the transmitter is in alarm. The
LCD display can also display diagnostic messages. The bar graph represents
the network connectivity status.
2-7
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
See “LCD Screen Messages” on page 5-6 for more information on LCD
messages.
LCD Display Configuration
Fast Keys
1, 3, 7
AMS
Right click on the device and select “Configure/Setup” from the menu.
1. Under “Device” in the “Smart Power” tab, select the desired LCD option
to suit your application needs, click Apply.
2. After carefully reading the warning provided, select yes.
DETAILED SETUP
Alerts
Fast Keys
1, 4, 3, 4
Alerts allow the user to configure the transmitter to output a HART message
when the configured data point is exceeded. A process alert will be
transmitted continuously if the set points are exceeded and the alert mode is
ON. An alert will be displayed on a Field Communicator, AMS status screen or
in the error section of the LCD display. The alert will reset once the value
returns within range.
NOTE
HI alert value must be higher than the LO alert value. Both alert values must
be within the pressure or temperature sensor limits.
Units of Measurement
Example 1: Rising Alert
Alert “OFF”
Alert “ON”
Alert “OFF”
Alert Set Point
Deadband
Assigned Value
Time
Units of Measurement
Example 2: Falling Alert
2-8
Alert “OFF”
Alert “ON”
Alert “OFF”
Assigned Value
Alert Set Point
Deadband
Time
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Field Communicator
To configure the process alerts with a Field Communicator, perform the
following procedure:
1.
From the HOME screen, follow the fast key sequence “Alerts.” (1
Device Setup, 3 Configuration, 4 Device Output Configuration, 4
Alerts)
2.
Select 1 for HI-HI Alert.
Select 2 for HI Alert.
Select 3 for LO Alert.
Select 4 for LO-LO Alert.
3.
Select 1 to configure the alert.
AMS
Right click on the device and select “Configure/Setup” from the menu.
1. On the "Alerts" Page, press the "Configure Alert" button for each of the
process alerts desired (1 per tab). Follow the prompts from the alert
configuration wizard.
Sensor Temperature Unit
Fast Keys
1, 4, 1, 2, 2
The Sensor Temperature Unit command selects between Celsius and
Fahrenheit units for the sensor temperature. The sensor temperature output
is accessible via HART only.
Field Communicator
Enter the fast key sequence “Sensor Temperature Unit.”
AMS
Right click on the device and select “Configure/Setup” from the menu.
1. In the “Temperature” tab, use the drop down menu “Snsr temp unit” to
select F (Farenheit) or C (Celsius). Click Apply.
2. Click Next to acknowledge send warning.
3. Select Finish to acknowledge the method is complete.
4. After carefully reading the warning, select yes.
DIAGNOSTICS AND
SERVICE
Diagnostics and service functions listed below are primarily for use after field
installation. The Transmitter Test feature is designed to verify that the
transmitter is operating properly, and can be performed either on the bench or
in the field.
Master Reset
The master reset will reset device electronics.
Fast Keys
1, 2, 1
Field Communicator
Enter the fast key sequence “Master Reset.”
AMS
Right click on the device and select “Methods>Diagnostics and Test,” then
“Master Reset” from the menu.
2-9
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
ADVANCED FUNCTIONS
FOR HART PROTOCOL
Saving, Recalling, and
Cloning Configuration
Data
Fast Keys
left arrow, 1, 2
Use the cloning feature of the Field Communicator or the AMS “User
Configuration” feature to configure several 3051S Wireless transmitters
similarly. Cloning involves configuring a transmitter, saving the configuration
data, then sending a copy of the data to a separate transmitter. Several
possible procedures exist when saving, recalling, and cloning configuration
data. For complete instructions refer to the Field Communicator manual
(publication no. 00809-0100-4276) or AMS on-line guides. One common
method is as follows:
Field Communicator
1. Completely configure the first transmitter.
2. Save the configuration data:
a. Select F2 SAVE from the Field Communicator HOME/ONLINE
screen.
b. Ensure that the location to which the data will be saved is set to
MODULE. If it is not, select 1: Location to set the save location to
MODULE.
c. Select 2: Name, to name the configuration data. The default is the
transmitter tag number.
d. Ensure that the data type is set to STANDARD. If the data type is
NOT STANDARD, select 3: Data Type to set the data type to
STANDARD.
e. Select F2 SAVE.
3. Connect and power the receiving transmitter and Field Communicator.
4. Select the back arrow from the HOME/ONLINE screen. The Field
Communicator menu appears.
5. Select 1: Offline, 2: Saved Configuration, 1: Module Contents to reach
the MODULE CONTENTS menu.
6. Use the DOWN ARROW to scroll through the list of configurations in the
memory module, and use the RIGHT ARROW to select and retrieve the
required configuration.
7. Select 1: Edit.
8. Select 1: Mark All.
9. Select F2 SAVE.
10. Use the DOWN ARROW to scroll through the list of configurations in the
memory module, and use the RIGHT ARROW to select the configuration
again.
11. Select 3: Send to download the configuration to the transmitter.
12. Select OK after the control loop is set to manual.
13. After the configuration has been sent, select OK to acknowledge that the
loop can be returned to automatic control.
When finished, the Field Communicator informs you of the status. Repeat
Steps 3 through 13 to configure another transmitter.
2-10
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
NOTE
The transmitter receiving cloned data must have the same software version
(or later) as the original transmitter.
AMS creating a Reusable Copy
To create a reusable copy of a configuration perform the following procedure:
1. Completely configure the first transmitter.
2. Select View then User Configuration View from the menu bar (or click the
toolbar button).
3. In the User Configuration window, right click and select New from the
context menu.
4. In the New window, select a device from the list of templates shown, and
click OK.
5. The template is copied into the User Configurations window, with the tag
name highlighted; rename it as appropriate and press Enter.
NOTE
A device icon can also be copied by dragging and dropping a device template
or any other device icon from AMS Explorer or Device Connection View into
the User Configurations window.
The “Compare Configurations” window appears, showing the Current values
of the copied device on one side and mostly blank fields on the other (User
Configuration) side.
6. Transfer values from the current configuration to the user configuration
as appropriate or enter values by typing them into the available fields.
7. Click Apply to apply the values, or click OK to apply the values and close
the window.
AMS Applying a User Configuration
Any amount of user configurations can be created for the application. They
can also be saved, and applied to connected devices or to devices in the
Device List or Plant Database.
To apply a user configuration perform the following procedure:
1. Select the desired user configuration in the User Configurations window.
2. Drag the icon onto a like device in AMS Explorer or Device Connection
View. The Compare Configurations window opens, showing the
parameters of the target device on one side and the parameters of the
user configuration on the other.
3. Transfer parameters from the user configuration to the target device as
desired, Click OK to apply the configuration and close the window.
2-11
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
DEVICE NETWORK
CONFIGURATION
Network
Fast Keys
1, 4, 3, 1
In order to communicate with the 1420 Wireless Gateway, and ultimately the
Information System, the transmitter must be configured to communicate over
the wireless network. This step is the wireless equivalent of connecting wires
from a transmitter to the information system.
Using a Field Communicator or AMS, enter the Network ID and Join Key so
that they match the Network ID and Join Key of the gateway and other
devices in the network. If the Network ID and Join Key are not identical, the
transmitter will not communicate with the network. The Network ID and Join
Key may be obtained from the 1420 Wireless Gateway on the
Setup>Network>Settings page on the web server.
Transmit Rate
Fast Keys
1, 4, 3, 1, 1, 2
The Transmit Rate is the frequency at which a new measurement is taken and
transmitted over the wireless network. This by default is 5 minutes. This may
be changed at commissioning, or at any time via AMS or the 1420 Wireless
Gateway’s web server. The Transmit Rate should be between 15 seconds
and 60 minutes. For networks of up to 100 wireless devices, maximum
Transmit Rate is 60 seconds. For networks of 50 or fewer devices, the
maximum Transmit Rate is 15 seconds.
When device configuration is completed, remove the battery and replace the
battery cover. Tighten the cover to the proper tension for safety approvals.
Remove Battery
After the sensor and network have been configured, remove the battery pack
and replace the transmitter cover. The battery pack should be inserted only
when the device is ready to be commissioned.
Use caution when handling the battery pack. The battery pack may be
damaged if dropped from heights in excess of 20 ft.
2-12
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 3
Rosemount 3051S Wireless Series
Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-4
Installing the LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . page 3-12
Rosemount 304, 305 and 306 Integral Manifolds . . . . . . . page 3-13
OVERVIEW
The information in this section covers installation considerations. A Quick
Installation Guide (document number 00825-0100-4802) is shipped with
every transmitter to describe basic installation and startup procedures.
Dimensional drawings for each Rosemount 3051S Wireless variation and
mounting configuration are included in Appendix A: Specifications and
Reference Data.
Field Communicator and AMS instructions are given to perform configuration
functions. For convenience, Field Communicator fast key sequences are
labeled “Fast Keys” for each software function below the appropriate
headings.
SAFETY MESSAGES
Warnings (
Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operation. Information that
raises potential safety issues is indicated with a warning symbol (
). Refer
to the following safety messages before performing an operation preceded by
this symbol.
)
Failure to follow these installation guidelines could result in death or serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions can result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the approvals section of the 3051S Wireless reference manual for any restrictions
associated with a safe installation.
•
Before connecting a 375 Field Communicator in an explosive atmosphere, make
sure the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
•
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Electrical shock can result in death or serious injury.
•
www.rosemount.com
Avoid contact with the leads and terminals. High voltage may be present on leads
can cause electrical shock.
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Process leaks could result in death or serious injury.
•
Install and tighten process connectors before applying pressure.
•
Do not attempt to loosen or remove process connectors while the transmitter is
in service.
Replacement equipment or spare parts not approved by Rosemount Inc. for use as
spare parts could reduce the pressure retaining capabilities of the transmitter and
may render the instrument dangerous.
•
Use only bolts supplied or sold by Rosemount Inc. as spare parts.
Improper assembly of manifolds to traditional flange can damage SuperModule™.
•
For safe assembly of manifold to traditional flange, bolts must break back plane of
flange web (i.e., bolt hold) but must not contact module housing.
The battery pack with the wireless unit contains two “C” size primary lithium/thionyl chloride
batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in
each pack. Under normal conditions, the battery materials are self-contained and are not
reactive as long as the batteries and the pack integrity are maintained. Care should be
taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to
prevent premature discharge.
CONSIDERATIONS
General
Measurement performance depends upon proper installation of the
transmitter and impulse piping. Mount the transmitter close to the process and
use a minimum of piping to achieve best performance. Also, consider the
need for easy access, personnel safety, practical field calibration, and a
suitable transmitter environment. Install the transmitter to minimize vibration,
shock, and temperature fluctuation.
IMPORTANT
Install the enclosed pipe plug (found in the box) wrench tight into unused
conduit openings.
For material compatibility considerations, see document number
00816-0100-3045 on www.rosemount.com.
IMPORTANT
The Rosemount 3051S and all other wireless devices should be powered only
after the 1420 Wireless Gateway has been installed and is functioning
properly. Wireless devices should also be powered up in order of proximity to
the 1420 Wireless Gateway, beginning with the closest. This will result in a
simpler and faster network installation.
Mechanical
3-2
NOTE
For steam service or for applications with process temperatures greater than
the limits of the transmitter, do not blow down impulse piping through the
transmitter. Flush lines with the blocking valves closed and refill lines with
water before resuming measurement.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
NOTE
When the transmitter is mounted on its side, position the Coplanar flange to
ensure proper venting or draining. Mount the flange as shown in Figure 3-2 on
page 3-9, keeping drain/vent connections on the bottom for gas service and
on the top for liquid service.
Environmental
Access requirements and cover installation on page 3-4 can help optimize
transmitter performance. Mount the transmitter to minimize ambient
temperature changes, vibration, mechanical shock, and to avoid external
contact with corrosive materials. Appendix A: Specifications and Reference
Data lists temperature operating limits.
Figure 3-1. Installation Flowchart
START HERE
Bench
Calibration?
No
Field Install
Yes
Configure
(Section 2)
Set Units
Check Switches
(page 3-11)
Verify
Mount
Transmitter
(page 3-4)
Review
Transmitter
Configuration
(page 2-3)
Install Battery
(pages 3-12–3-11)
Check Process
Connection
(page 3-10)
Set Range
Points
Apply Pressure
Confirm
Transmitter
Configuration
(page 2-3)
Set Network
Parameters
Within
Specifications
?
No
Refer to
Section 4
Operation and
Maintenance
Yes
Trim Transmitter
for Mounting
Effects
(page 5-3)
Done
3-3
Reference Manual
Rosemount 3051S Wireless Series
INSTALLATION
PROCEDURES
00809-0100-4802, Rev BA
August 2007
For dimensional drawing information refer to Appendix A: Dimensional
Drawings on page A-10.
Process Flange Orientation
Mount the process flanges with sufficient clearance for process connections.
For safety reasons, place the drain/vent valves so the process fluid is directed
away from possible human contact when the vents are used. In addition,
consider the need for a testing or calibration input.
Housing Rotation
See “Consider Housing Rotation” on page 3-11.
Battery Side of Electronics Housing
Mount the transmitter so the battery side is accessible. Clearance of 2 3/8 in.
(60 mm) is required for cover removal. Use both conduit plugs on the conduit
openings.
Circuit Side of Electronics Housing
Provide 0.75 in. (19 mm) of clearance for units with out an LCD display. Three
inches of clearance is required for cover removal if a meter is installed.
Cover Installation
Always ensure a proper seal by installing the electronics housing cover(s) so
that metal contacts metal. Use Rosemount O-rings.
Mount the Transmitter
Mounting Brackets
Facilitate mounting transmitter to a 2-in. pipe, or to a panel. The B4 Bracket
(SST) option is standard for use with the Coplanar and In-Line flanges.
“Coplanar Flange Mounting Configurations” on page A-10 shows bracket
dimensions and mounting configurations for the B4 option.
Options B1–B3 and B7–B9 are sturdy, epoxy/polyester-painted brackets
designed for use with the traditional flange. The B1–B3 brackets have carbon
steel bolts, while the B7–B9 brackets have stainless steel bolts. The BA and
BC brackets and bolts are stainless steel. The B1/B7/BA and B3/B9/BC style
brackets support 2-inch pipe-mount installations, and the B2/B8 style brackets
support panel mounting.
NOTE
Most transmitters are calibrated in the horizontal position. Mounting the
transmitter in any other position will shift the zero point to the equivalent
amount of liquid head caused by the varied mounting position. To reset zero
point, refer to “Sensor Trim” on page 5-3.
Position the antenna such that it is vertical, typically straight up (antenna may
be pointed down as well.)
3-4
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Flange Bolts
The 3051S can be shipped with a Coplanar flange or a Traditional flange
installed with four 1.75-inch flange bolts. Mounting bolts and bolting
configurations for the Coplanar and Traditional flanges can be found on
page 2-6, 7. Stainless steel bolts supplied by Emerson Process Management
are coated with a lubricant to ease installation. Carbon steel bolts do not
require lubrication. No additional lubricant should be applied when installing
either type of bolt. Bolts supplied by Emerson Process Management are
identified by their head markings:
B7M
Carbon Steel (CS) Head Markings
316
B8M
660
CL A
KM
Monel® Head Marking
Stainless Steel (SST) Head Markings
F593_*
* The last digit in the F593_ head marking
may be any letter between A and M.
Bolt Installation
Only use bolts supplied with the Rosemount 3051S or sold by Emerson
Process Management as spare parts. When installing the transmitter to
one of the optional mounting brackets, torque the bolts to 125 in-lb.
(0,9 N-m). Use the following bolt installation procedure:
1. Finger-tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern.
3. Torque the bolts to the final torque value using the same
crossing pattern.
Torque values for the flange and manifold adapter bolts are as follows:
Table 3-1. Bolt Installation
Torque Values
Bolt Material
Initial Torque Value
Final Torque Value
CS-ASTM-A445 Standard
316 SST—Option L4
ASTM-A-193-B7M—Option L5
Monel®—Option L6
ASTM-A-453-660—Option L7
ASTM-A-193-B8M—Option L8
300 in.-lb (34 N-m)
150 in.-lb (17 N-m)
300 in.-lb (34 N-m)
300 in.-lb (34 N-m)
150 in.-lb (17 N-m)
150 in.-lb (17 N-m)
650 in.-lb (73 N-m)
300 in.-lb (34 N-m)
650 in.-lb (73 N-m)
650 in.-lb (73 N-m)
300 in.-lb (34 N-m)
300 in.-lb (34 N-m)
3-5
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
GAGE/ABSOLUTE TRANSMITTER
DIFFERENTIAL TRANSMITTER
Drain/Vent
Plug
Drain/Vent
Drain/Vent
1.75 (44) x 4
1.75 (44) x 4
1.50 (38) x 4
NOTE
Dimensions are in inches (millimeters).
3-6
1.50 (38) x 4
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Transmitter with
Flange Adapters
and Flange/ Adapter Bolts
Transmitter with
Flange Bolts
1.75 (44) x 4
2.88 (73) x 4
Description
Differential Pressure
Flange Bolts
Adapter Bolts
Flange/ Adapter Bolts
Gage/Absolute Pressure(2)
Flange Bolts
Adapter Bolts
Flange/ Adapter Bolts
Qty
Size in in. (mm)
4
4
4
1.75 (44)
1.50 (38)(1)
2.88 (73)
4
2
2
1.75 (44)
1.50 (38)(1)
2.88(73)
(1) DIN-compliant traditional flange requires 1.75 in. (44 mm) length adapter bolts.
(2) Rosemount 3051S In-line transmitters are direct mount and do not require bolts
for process connection.
3-7
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Impulse Piping
The piping between the process and the transmitter must accurately transfer
the pressure to obtain accurate measurements. There are five possible
sources of error: leaks, friction loss (particularly if purging is used), trapped
gas in a liquid line, liquid in a gas line, and density variations between the
legs.
The best location for the transmitter in relation to the process pipe depends on
the process itself. Use the following guidelines to determine transmitter
location and placement of impulse piping:
3-8
•
Keep impulse piping as short as possible.
•
For liquid service, slope the impulse piping at least 1 inch per foot
(8 cm per m) upward from the transmitter toward the
process connection.
•
For gas service, slope the impulse piping at least 1 inch per foot (8 cm
per m) downward from the transmitter toward the process connection.
•
Avoid high points in liquid lines and low points in gas lines.
•
Make sure both impulse legs are the same temperature.
•
Use impulse piping large enough to avoid friction effects and blockage.
•
Vent all gas from liquid piping legs.
•
When using a sealing fluid, fill both piping legs to the same level.
•
When purging, make the purge connection close to the process taps
and purge through equal lengths of the same size pipe. Avoid purging
through the transmitter.
•
Keep corrosive or hot (above 250 °F [121 °C]) process material out of
direct contact with the SuperModule and flanges.
•
Prevent sediment deposits in the impulse piping.
•
Keep the liquid head balanced on both legs of the impulse piping.
•
Avoid conditions that might allow process fluid to freeze within the
process flange.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Mounting Requirements
Refer to Figure 3-2 for examples of the following mounting configurations:
Liquid Flow Measurement
•
Place taps to the side of the line to prevent sediment deposits on the
process isolators.
•
Mount the transmitter beside or below the taps so gases vent into the
process line.
•
Mount drain/vent valve upward to allow gases to vent.
Gas Flow Measurement
•
Place taps in the top or side of the line.
•
Mount the transmitter beside or above the taps so to drain liquid into
the process line.
Steam Flow Measurement
•
Place taps to the side of the line.
•
Mount the transmitter below the taps to ensure that impulse piping will
remain filled with condensate.
•
Fill impulse lines with water to prevent steam from contacting the
transmitter directly and to ensure accurate measurement start-up.
NOTE
For steam or other elevated temperature services, it is important that
temperatures at the Coplanar process flanges must not exceed 250 °F
(121 °C) for transmitters with silicone fill, or 185 °F (85 °C) for inert fill. For
vacuum service, these temperature limits are reduced to 220 °F (104 °C) for
silicone fill and 160 °F (71 °C) for inert fill.
Figure 3-2. Installation
Examples
GAS OR LIQUID SERVICE
GAS SERVICE
STEAM SERVICE
3-9
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Process Connections
3051S Wireless transmitter flange process connection size is 1/4–18 NPT.
Flange adapters with 1/2–14 NPT connections are available as the D2 option.
Use your plant-approved lubricant or sealant when making the process
connections. The process connections on the transmitter flange are on
21/8-inch (54 mm) centers to allow direct mounting to a three-valve or
five-valve manifold. Rotate one or both of the flange adapters to attain
connection centers of 2 inches (51 mm), 21/8 inches (54 mm), or 21/4 inches
(57 mm).
Install and tighten all four flange bolts before applying pressure to avoid
leakage. When properly installed, the flange bolts will protrude through the top
of the SuperModule housing. Do not attempt to loosen or remove the flange
bolts while the transmitter is in service.
To install adapters to a Coplanar flange, perform the following procedure:
1. Remove the flange bolts.
2. Leaving the flange in place, move the adapters into position with the
O-ring installed.
3. Clamp the adapters and the Coplanar flange to the transmitter module
using the longer of the bolts supplied.
4. Tighten the bolts. Refer to “Flange Bolts” on page 3-5 for torque
specifications.
Failure to install proper flange adapter O-rings can cause process leaks, which can
result in death or serious injury.
The two flange adapters are distinguished by unique O-ring grooves. Only use the
O-ring that is designed for its specific flange adapter, as shown below.
ROSEMOUNT 3051S WIRELESS
3051/3001/3095/2024
Flange Adapter
O-ring
3051S
Wireless
3051C
2024
Teflon Based
Elastomer
ROSEMOUNT 1151
Flange Adapter
O-ring
Teflon
Elastomer
Refer to the Spare Parts list in Appendix A: Specifications and Reference Data for the
correct part numbers of the flange adapters and O-rings designed for 3051S Wireless
transmitters.
3-10
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Whenever you remove flanges or adapters, visually inspect the Teflon®
O-rings. Replace them if there are any signs of damage, such as nicks or
cuts. If you replace the O-rings, re-torque the flange bolts after installation to
compensate for cold flow. Refer to the process sensor body reassembly
procedure in Section 6: Troubleshooting on page 6-5.
Consider Housing
Rotation
The housing can be rotated to improve field access to wiring or to better view
the optional LCD display. Perform the following procedure:
Figure 3-3. Housings
Wireless PlantWeb Housing
Housing Rotation Set Screw
(3/32-inch allen)
1. Loosen the housing rotation set screw.
2. First rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing
counter clockwise to the desired location (up to 360° from thread limit).
3. Retighten the housing rotation set screw.
In addition to housing rotation, the optional LCD display can be rotated in
90-degree increments by squeezing the two tabs, pulling out, rotating and
snapping back into place.
NOTE
If LCD pins are inadvertently removed from the interface board, carefully
re-insert the pins before snapping the LCD display back into place.
Grounding
Transmitter Case
Always ground the transmitter case in accordance with national and local
electrical codes. The most effective transmitter case grounding method is a
direct connection to earth ground with minimal impedance. Methods for
grounding the transmitter case include:
•
External Ground Assembly: The External Ground Assembly can also
be ordered with the transmitter (Option Code D4), or as a spare part
(03151-9060-0001).
3-11
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Battery Installation
Figure 3-4. Battery Installation
Wireless Battery Installation
To make connections, perform the following procedure:
1. Remove the housing cover on the battery compartment side. The battery
supplies all power to the transmitter. Plug and seal both conduit
connections on the transmitter housing to avoid moisture accumulation in
the terminal side.
2. Connect the battery
3. Replace the battery cover and tighten to safety specification (metal to
metal)
INSTALLING THE
LCD DISPLAY
Transmitters ordered with the LCD display will be shipped with the display
installed.
NOTE
Only use Rosemount Wireless LCD Part Number: 00753-9004-0002
NOTE
An LCD from a wired device will not function in a wireless device.
In addition to housing rotation, the optional LCD display can be rotated in
90-degree increments by squeezing the two tabs, pulling out, rotating and
snapping back into place.
If LCD pins are inadvertently removed from the interface board, carefully
re-insert the pins before snapping the LCD display back into place.
Use the following procedure and Figure 3-5 to install the LCD display:
1. Remove the battery cover and battery.
2. Remove the transmitter cover opposite the field terminal side. Do not
remove the instrument covers in explosive environments when the circuit
is live.
3. Engage the four-pin connector into the LCD display and snap into place.
Note the following LCD temperature limits:
Operating:–40 to 175 °F (–20 to 80 °C)
Storage:–40 to 185 °F (–40 to 85 °C)
3-12
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Figure 3-5. Optional LCD
Display
LCD Display
Meter
Cover
ROSEMOUNT 304, 305
AND 306 INTEGRAL
MANIFOLDS
The Rosemount 305 is available in two designs: Traditional and Coplanar.
The traditional 305 Integral Manifold can be mounted to most primary
elements with mounting adapters in the market today. The Rosemount 306
Integral Manifold is used with In-line transmitters to provide block-and-bleed
valve capabilities of up to 10000 psi (690 bar). The Rosemount 304 comes in
two basic styles: traditional (flange x flange and flange x pipe) and wafer. The
304 traditional manifold comes in 2, 3, and 5-valve configurations. The 304
wafer manifold comes in 3 and 5 valve configurations.
Figure 3-6. Integral Manifold
Designs
CONVENTIONAL
Rosemount 305 Integral
Manifold Installation
Procedure
COPLANAR
TRADITIONAL
IN-LINE
To install a 305 Integral Manifold to a 3051S Wireless transmitter:
1. Inspect the Teflon SuperModule O-rings. If the O-rings are undamaged,
reusing them is recommended. If the O-rings are damaged (if they have
nicks or cuts, for example), replace them with new O-rings.
IMPORTANT
If replacing the O-rings, take care not to scratch or deface the O-ring grooves
or the surface of the isolating diaphragm while you remove the damaged
O-rings.
3-13
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
2. Install the Integral Manifold on the SuperModule. Use the four 2.25-in.
manifold bolts for alignment. Finger tighten the bolts, then tighten the
bolts incrementally in a cross pattern to final torque value. See “Flange
Bolts” on page 3-5 for complete bolt installation information and torque
values. When fully tightened, the bolts should extend through the top of
the module housing.
3. If the Teflon SuperModule O-rings have been replaced, the flange bolts
should be re-tightened after installation to compensate for cold flow of
the O-rings.
4. If applicable, install flange adapters on the process end of the manifold
using the 1.75-in. flange bolts supplied with the transmitter.
NOTE
Always perform a zero trim on the transmitter/manifold assembly after
installation to eliminate mounting effects. See Section 5: Operation and
Maintenance, “Zero Trim” on page 5-3.
Rosemount 306 Integral
Manifold Installation
Procedure
The 306 Manifold is for use only with a 3051S Wireless In-line transmitter.
Assemble the 306 Manifold to the 3051S Wireless In-line transmitter with a
thread sealant.
1. Place transmitter into holding fixture.
2. Apply appropriate thread paste or tape to threaded instrument end of the
manifold.
3. Count total threads on the manifold before starting assembly.
4. Start turning the manifold by hand into the process connection on the
transmitter.
NOTE
If using thread tape, be sure the thread tape does no strip when the manifold
assembly is started.
5. Wrench tighten manifold into process connection. (Note: Minimum toque
value is 425 in-lbs)
6. Count how many threads are still showing. (Note: Minimum engagement
is 3 revolutions)
7. Subtract the number of threads showing (after tightening) from the total
threads to calculate the revolutions engaged. Further tighten until a
minimum of 3 rotations is achieved.
8. For block and bleed manifold, verify the bleed screw is installed and
tightened. For two-valve manifold, verify the vent plug is installed and
tightened.
9. Leak-check assembly to maximum pressure range of transmitter.
3-14
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 304
Conventional Manifold
Installation Procedure
Rosemount 3051S Wireless Series
To install a 304 Conventional Manifold to a 3051S Wireless transmitter:
1. Align the Conventional Manifold with the transmitter flange. Use the four
manifold bolts for alignment.
2. Finger tighten the bolts, then tighten the bolts incrementally in a cross
pattern to final torque value. See “Flange Bolts” on page 2-6 for
complete bolt installation information and torque values. When fully
tightened, the bolts should extend through the top of the module housing.
3. If applicable, install flange adapters on the process end of the manifold
using the 1.75-in. flange bolts supplied with the transmitter.
Manifold Operation
Three-valve configuration shown.
In normal operation the two block valves between the
process and instrument ports will be open and the
equalizing valve(s) will be closed.
L
H
Drain/
Vent
Valve
Drain/
Vent
Valve
Equalize
(closed)
Isolate
(open)
Isolate
(open)
Process
To zero the 3051S, close the block valve to the low
pressure (downstream side) of the transmitter first.
L
H
Drain/
Vent
Valve
Drain/
Vent
Valve
Equalize
(closed)
Isolate
(open)
Isolate
(closed)
Process
Next, open the center (equalize) valve(s) to equalize
the pressure on both sides of the transmitter.
L
H
Drain/
Vent
Valve
Equalize
(open)
Isolate
(open)
Drain/
Vent
Valve
Isolate
(closed)
Process
3-15
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
The manifold valves are now in the proper configuration
for zeroing the transmitter. To return the transmitter to
service, close the equalizing valve(s) first.
L
H
Drain/
Vent
Valve
Drain/
Vent
Valve
Equalize
(closed)
Isolate
(open)
Isolate
(closed)
Process
Next, open the block valve on the low pressure side of
the transmitter.
L
H
Drain/
Vent
Valve
Equalize
(closed)
Isolate
(open)
Isolate
(open)
Process
3-16
Drain/
Vent
Valve
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 4
Rosemount 3051S Wireless Series
Commissioning
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2
Verify Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2
SAFETY MESSAGES
Warnings (
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
)
Failure to follow these installation guidelines could result in death or
serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
•
Before connecting a 375 Field Communicator in an explosive atmosphere, make
sure the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
•
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Process leaks could result in death or serious injury.
•
Install and tighten process connectors before applying pressure.
•
Do not attempt to loosen or remove process connectors while the transmitter is in
service.
Electrical shock could cause death or serious injury.
•
Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
NOTE
The Rosemount 3051S Wireless and all other wireless devices should be
installed only after the 1420 Wireless Gateway has been installed and is
functioning properly.
Wireless devices should also be powered up in order of proximity from the
1420 Wireless Gateway, beginning with the closest device to the 1420. This
will result in a simpler and faster network installation.
www.rosemount.com
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
NETWORK STATUS
If the Rosemount 3051S Wireless was configured with the Network ID and
Join Key and sufficient time for network polling has passed, the transmitter
should be connected to the network. To verify connectivity, open the 1420
Wireless Gateway’s integral web interface and navigate to the
Explorer>Status page.
This page will display the transmitter’s tag, PV, SV, TV, QV, Last Update,
Update Rate, Battery Voltage, and Status. A green status indicator means that
the device is working properly. A red indicator means that there is a problem
with either the device or its communication path. For more detail on a specific
device, click on the tag name.
VERIFY OPERATION
Operation can be verified in three locations, at the device via the Local
Display, using the 375 Field Communicator, or at the Gateway via the 1420
Wireless Gateway’s integrated web server.
Local Display
During normal operation, the LCD will display the PV value at the wireless
update rate up to as fast as 1 minute intervals. Refer to LCD Screen
Messages on page 5-6 for error codes and other LCD messages. Press the
Diagnostic button to display the TAG, Device ID, Network ID, Network
Status and Device Status screens. For Device Status screens, see LCD
Screen Messages on page 5-6.
Figure 4-1. Diagnostic Screen Sequence
Tag
Device ID
Network ID
Network Status
Device Variables
Abcde
id - XX
netwk
netwk
Suply
2parnt
volts
13 0 5
fgh
4-2
XXXXXX
ID
7. 2 1
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Figure 4-2. Network Join Status Screens
Searching for
Network
Joining Network
Connected with
1 Parent
Connected with
2 Parents
netwk
netwk
netwk
netwk
a -srch
joing
1parnt
2parnt
375 Field Communicator
To verify device operation using a HART Field Communicator, a 3051S DD is
required.
Table 4-1.
Function
Network
Key Sequence
Menu Items
1, 3, 3
Smart Power, Network ID, Set Join
Key, Radio State
1420 Wireless Gateway
To verify device operation using the 1420 Wireless Gateway’s integrated web
server, navigate to the Explorer>Status page. This page will show whether
the device has joined the network and if it is communicating properly.
If the Rosemount 3051S Wireless was configured with the Network ID and
Join Key and sufficient time for network polling has passed, the transmitter will
be connected to the network. To verify connectivity, open the 1420 Wireless
Gateway’s integral web interface and navigate to the Explorer>Status page.
This page will display the transmitter’s tag, PV, SV, TV, QV, Last Update,
Update Rate, Battery Voltage, and Status. A green status indicator means that
the device is working properly. A red indicator means that there is a problem
with either the device or its communication path. For more detail on a specific
device, click on the tag name.
4-3
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Troubleshooting
The most common cause of incorrect operation is incorrect configuration of
the Network ID and Join Key. The Network ID and Join Key in the device must
match that of the 1420 Wireless Gateway. The Network ID and Join Key may
be obtained from the 1420 Wireless Gateway on the
Setup>Network>Settings page on the web server.
4-4
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 5
Rosemount 3051S Wireless Series
Operation and Maintenance
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
LCD Screen Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-6
OVERVIEW
This section contains information on commissioning and operating 3051S
Wireless Pressure Transmitters. Tasks that should be performed on the bench
prior to installation are explained in this section.
Field Communicator and AMS instructions are given to perform configuration
functions. For convenience, Field Communicator fast key sequences are
labeled “Fast Keys” for each software function below the appropriate
headings.
CALIBRATION
Calibrating a 3051S Wireless transmitter may include the following
procedures:
•
Sensor Trim: Adjusts the position of the factory sensor characterization
curve to optimize performance over a specified pressure range, or to
adjust for mounting effects.
The 3051S SuperModule uses a microprocessor that contains information
about the sensor’s specific characteristics in response to pressure and
temperature inputs. A smart transmitter compensates for these sensor
variations. The process of generating the sensor performance profile is called
factory sensor characterization.
Sensor trimming requires an accurate pressure input and adds additional
compensation that adjusts the position of the factory sensor characterization
curve to optimize performance over a specific pressure range.
NOTE
Sensor trimming adjusts the position of the factory sensor characterization
curve. It is possible to degrade performance of the transmitter if the trim is
done improperly or with inaccurate equipment.
www.rosemount.com
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Table 5-1. Recommended
Calibration Tasks
Transmitter
3051S 2CD
3051S 2CG
3051S 2L
Bench Calibration Tasks
1. Set output configuration parameters:
a. Set the % range points.
b. Set the output units.
c. Set the output type.
3051S 2CA
3051S 2TA
3051S 2TG
2. Optional: Perform a sensor trim. (Accurate
pressure source required)
1. Set output configuration parameters:
a. Set the range points.
b. Set the output units.
c. Set the output type.
Field Calibration Tasks
1. Reconfigure parameters if necessary.
2. Zero trim the transmitter to
compensate for mounting effects or
static pressure effects.
1. Reconfigure parameters if necessary.
2. Perform low trim value section of the
sensor trim procedure to correct for
mounting position effects.
2. Optional: Perform a sensor trim if
equipment available (accurate absolute
pressure source required), otherwise
perform the low trim value section of the
sensor trim procedure.
NOTE:
A 375 Field Communicator or AMS is required for all sensor and output trim
procedures.
Rosemount 3051S2TG Range 5 transmitters use an absolute sensor that
requires an accurate absolute pressure source to perform the optional sensor
trim.
Sensor Trim Overview
Trim the sensor using either sensor or zero trim functions. Trim functions vary
in complexity and are application-dependent. Both trim functions alter the
transmitter’s interpretation of the input signal.
Zero trim is a single-point offset adjustment. It is useful for compensating for
mounting position effects and is most effective when performed with the
transmitter installed in its final mounting position. Since this correction
maintains the slope of the characterization curve, it should not be used in
place of a sensor trim over the full sensor range.
When performing a zero trim, ensure that the equalizing valve is open and all
wet legs are filled to the correct levels.
NOTE
Do not perform a zero trim on 3051S Wireless Absolute pressure transmitters.
Zero trim is zero based, and absolute pressure transmitters reference
absolute zero. To correct mounting position effects on a 3051S Wireless
Wireless Absolute Pressure Transmitter, perform a low trim within the sensor
trim function. The low trim function provides an offset correction similar to the
zero trim function, but it does not require zero-based input.
5-2
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Sensor trim is a two-point sensor calibration where two end-point pressures
are applied, and all output is linearized between them. Always adjust the low
trim value first to establish the correct offset. Adjustment of the high trim value
provides a slope correction to the characterization curve based on the low
trim value. The trim values allow you to optimize performance over your
specified measuring range at the calibration temperature.
Zero Trim
Fast Keys
1, 2, 3, 3, 1
NOTE
The transmitter must be within three percent of true zero (zero-based) in order
to calibrate with zero trim function.
Field Communicator
Calibrate the sensor with a 375 Field Communicator using the zero trim
function as follows:
1. Vent the transmitter and attach a 375 to the communication terminals.
2. From the HOME screen, follow the fast key sequence “Zero Trim.”
3. Follow the commands provided by the Field Communicator to complete
the zero trim adjustment.
AMS
Right click on the device and select “Methods>Calibrate>Sensor Calibration”
then “Zero trim” from the menu.
1. Click Next to acknowledge warning.
2. Click Next after applying appropriate pressure to sensor.
3. Select Finish to acknowledge the method is complete.
Sensor Trim
Fast Keys
1, 2, 3, 3
NOTE
Use a pressure input source that is at least three times more accurate than
the transmitter, and allow the input pressure to stabilize for ten seconds
before entering any values.
Field Communicator
To calibrate the sensor with a 375 Field Communicator using the sensor trim
function, perform the following procedure:
1. Assemble and power the entire calibration system including a
transmitter, 375, power supply, pressure input source, and readout
device.
2. From the HOME screen, enter the fast key sequence under “Sensor
Trim.”
3. Select 2: Lower sensor trim. The lower sensor trim value should be the
sensor trim point that is closest to zero.
5-3
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
NOTE
Select pressure input values so that lower and upper values are equal to or
outside the Lower and Upper Operating points. Do not attempt to obtain
reverse output by reversing the high and low points. This can be done by
going to Set Output (Transfer function) on page 2-6. The transmitter allows
approximately five percent deviation.
4. Follow the commands provided by the 375 to complete the adjustment of
the lower value.
5. Repeat the procedure for the upper value, replacing 2: Lower sensor trim
with 3: Upper sensor trim in Step 3.
AMS
Right click on the device and select “Methods>Calibrate>Sensor Calibration.”
1. Select “Lower Input Trim.” The lower sensor trim value should be the
sensor trim point that is closest to zero.
2. Click Next to acknowledge the warning.
3. Click Next after applying appropriate pressure to sensor.
4. Choose the appropriate pressure units from the drop-down list.
5. Enter the trim calibration value.
6. Select Finish to acknowledge the method is complete.
7. Right click on the device and select “Methods>Calibrate>Sensor
Calibration.”
8. Select “Upper sensor trim” and repeat steps 2-6.
Recall Factory Trim—
Sensor Trim
Fast Keys
1, 2, 3, 4, 1
The Recall Factory Trim—Sensor Trim command allows the restoration of the
as-shipped factory settings of the sensor trim. This command can be useful
for recovering from an inadvertent zero trim of an absolute pressure unit or
inaccurate pressure source.
Field Communicator
Enter the fast key sequence “Recall Factory Trim—Sensor Trim.”
AMS
Right click on the device and select “Methods>Calibrate>Sensor Calibration”
then “Revert to Factory Trim” from the menu.
1. Click Next to acknowledge the warning.
2. Select Finish to acknowledge the method is complete.
Compensating for
Line Pressure
5-4
The Rosemount 3051S Wireless Range 4 and 5 pressure transmitters require
a special calibration procedure when used in differential pressure
applications. The purpose of this procedure is to optimize transmitter
performance by reducing the effect of static line pressure in these
applications. The 3051S Wireless differential pressure transmitters (Ranges
0, 1, 2, and 3) do not require this procedure because optimization occurs in
the sensor.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Applying high static pressure to the 3051S Wireless Range 4 and Range 5
pressure transmitters causes a systematic shift in the output. This shift is
linear with static pressure; correct it by performing the “Sensor Trim”
procedure on page 5-3.
The following specifications show the static pressure effect for the 3051S
Wireless Range 4 and Range 5 transmitters used in differential pressure
applications:
Zero Effect:
± 0.1% of the upper range limit per 1000 psi (69 bar) for line pressures
from 0 to 2000 psi (0 to 138 bar)
For line pressures above 2000 psi (138 bar), the zero effect error is ± 0.2%
of the upper range limit plus an additional ± 0.2% of upper range limit error
for each 1000 psi (69 bar) of line pressure above 2000 psi (138 bar).
Example: Line pressure is 3000 psi (3 kpsi). Zero effect error calculation:
± {0.2 + 0.2 x [3 kpsi - 2 kpsi]} = ± 0.4% of the upper range limit
Span Effect:
Correctable to ±0.2% of reading per 1000 psi (69 bar) for line pressures
from 0 to 3626 psi (0 to 250 bar)
The systematic span shift caused by the application of static line pressure is
-1.00% of reading per 1000 psi (69 bar) for Range 4 transmitters, and -1.25%
of reading per 1000 psi (69 bar) for Range 5 transmitters.
Complete a 3051S Wireless sensor trim and enter the corrected values for
low trim (LT) and high trim (HT), refer to Sensor Trim on page 5-3.
Enter the corrected input values for low trim and high trim through the Field
Communicator keypad after you apply the nominal value of pressure as the
transmitter input.
NOTE
After sensor trimming 3051S Wireless Range 4 and 5 transmitters for high
differential pressure applications, verify that the Lower and Upper Operating
points are at nominal values using the 375 Field Communicator.
5-5
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
LCD SCREEN
MESSAGES
Startup Screen
Sequence
The following screens will display when the battery is first connected to the
Rosemount 3051S Wireless.
XXXXX
XXXXxxx
All Segments On: used to visually determine if
there are any bad segments on the LCD
xxxxxx
3051S
Device Identification: used to determine Device
Type.
WIrels
Abcde
fgh
PRESS
5 8. 0
PSI
5-6
Device Information - Tag: user entered tag which
is 8 characters long - will not display if all characters
are blank
PV Screen - process pressure
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
SNSR
2 5. 0 0
SV Screen - sensor temperature value
deg c
DEV
2 5. 2 5
TV Screen - feature board temperature value
deg c
Suply
7. 2 1
QV Screen - voltage reading at the power supply
terminals
volts
alert
Alert Screen - at least one alert is present - this
screen will not display if no alerts are present
presnt
Diagnostic Button
Screen Sequence
The following five screens will display when the device is operating properly
and the Diagnostic Button has been pressed.
Abcde
fgh
Device Information - Tag: user entered tag which
is 8 characters long - will not display if all characters
are blank
5-7
Reference Manual
Rosemount 3051S Wireless Series
id - XX
00809-0100-4802, Rev BA
August 2007
Device Identification: used to determine Device ID
XXXXXX
netwk
13 0 5
ID
netwk
Diagnostic Button Screen 3: assuming the device
has the correct join key, this ID tells the user what
network the device can connect with
Diagnostic Button Screen 4.11: the device has
joined a network and has been fully configured and
has multiple parents
2parnt
Suply
7. 2 1
Diagnostic Button Screen 5: voltage reading at
the power supply terminals
volts
Network Diagnostic
Status Screens
These screens display the network status of the device. Only one will be
shown during the startup sequence or diagnostic sequence.
netwk
unknwn
5-8
Diagnostic Button Screen 4.1: the device has yet
to retrieve the information from the 1420 and is still
in the process of being activated
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
netwk
Diagnostic Button Screen 4.2: the device has
received the ACTIVATE command from the 1420,
but is in the process of being configured to the
wireless network
active
netwk
Diagnostic Button Screen 4.3: the device has
sent JOIN request and is waiting for the ACTIVATE
command
joing
netwk
Diagnostic Button Screen 4.4: the device is in
active search
a -srch
netwk
Diagnostic Button Screen 4.5: the device is in
passive search
p -srch
netwk
Diagnostic Button Screen 4.6: the device
couldn’t find the network and is in deep sleep
mode to preserve battery power
sleep
5-9
Reference Manual
Rosemount 3051S Wireless Series
netwk
00809-0100-4802, Rev BA
August 2007
Diagnostic Button Screen 4.7: the device
synchronized to a network
sync
netwk
Diagnostic Button Screen 4.8: the device will
reset
reset
netwk
Diagnostic Button Screen 4.9: the device
couldn’t join because of dropped packets and will
reset
bckoff
netwk
Diagnostic Button Screen 4.10: the device has
joined a network and has been fully configured but
has only 1 parent device
1parnt
Device Diagnostic
Screens
The following screens will show the device diagnostics depending on the state
of the device.
DEV
fAilur
5-10
Device Information - Status: there is a critical error
which may prevent the device from operating
correctly. Check additional status screens for more
information.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
PRESS
5 8. 0
PV Screen - process pressure value
PSI
SNSR
2 5. 0 0
SV Screen - sensor temperature value
deg c
DEV
2 5. 2 5
TV Screen - feature board temperature value
deg c
Suply
7. 2 1
QV Screen - voltage reading at the power supply
terminals
volts
alert
Alert Screen - at least one alert is present - this
screen will not display if no alerts are present
presnt
5-11
Reference Manual
Rosemount 3051S Wireless Series
Abcde
fgh
id - 12
345678
suply
00809-0100-4802, Rev BA
August 2007
Diagnostic Button Screen 1 - Tag: user entered
tag which is 8 characters long - will not display if all
characters are blank
Diagnostic Button Screen 2: the device’s identifier
that is used to make up the HART long address - the
1420 Wireless Gateway may use this to help identify
devices if no unique user tag is available
Diagnostic Button Screen 7.1: the terminal
voltage has dropped below level of operating limit.
Replace the battery
(Part Number: 00753-9220-0001)
failur
suply
low
Diagnostic Button Screen 7.2: the terminal
voltage is below the recommended operating range
- if this is a battery operated device, the battery
should be replaced - for line powered devices, the
supply voltage should be increased
Diagnostic Button Screen 8: the device cannot
retrieve information from the radio in the device - the
device may still be operational and publishing HART
data
5-12
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
confg
failur
confg
warn
snsr
failur
snsr
warn
Diagnostic Button Screen 9.1: configuration of the
transmitter is invalid such that critical operation of
the device may be affected - check the extended
configuration status to identify which configuration
item(s) need to be corrected
Diagnostic Button Screen 9.2: configuration of the
transmitter is invalid such that non-critical operation
of the device may be affected - check the extended
configuration status to identify which configuration
item(s) need to be corrected
Diagnostic Button Screen 10.1: a sensor attached
to the transmitter has failed, and valid readings from
that sensor are no longer possible - check the
sensor and sensor wiring connections - check
additional status for more detailed information of the
failure source
Diagnostic Button Screen 10.2: a sensor attached
to the transmitter is degraded, readings from that
sensor may not be within accuracy specifications check the process, and sensor wiring connections check additional status for more detailed information
of the warning source
NOTE
Use the Rosemount Wireless LCD Part Number: 00753-9004-0002.
5-13
Reference Manual
Rosemount 3051S Wireless Series
5-14
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Section 6
Rosemount 3051S Wireless Series
Troubleshooting
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1
Disassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-3
Reassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-5
OVERVIEW
Table 6-1 provides summarized maintenance and troubleshooting
suggestions for the most common operating problems.
If you suspect malfunction despite the absence of any diagnostic messages
on the Field Communicator display, follow the procedures described here to
verify that transmitter hardware and process connections are in good working
order. Always deal with the most likely checkpoints first.
SAFETY MESSAGES
Warnings (
Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
)
Explosions can result in death or serious injury.
•
Before connecting a 375 Field Communicator in an explosive atmosphere, make
sure that the instruments are installed according to intrinsically safe or
nonincendive field wiring practices.
Improper installation or repair of the SuperModule with high pressure option (P0)
could result in death or serious injury.
•
For safe assembly, the high pressure SuperModule must be installed with ASTM
A193 Class 2 Grade B8M Bolts and either a 305 manifold or a DIN-compliant
traditional flange.
Static electricity can damage sensitive components.
•
Observe safe handling precautions for static-sensitive components.
Electrical shock can result in death or serious injury.
•
Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
Process leaks could result in death or serious injury.
www.rosemount.com
•
Install and tighten process connectors before applying pressure.
•
Do not attempt to loosen or remove process connectors while the transmitter is in
service.
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Table 6-1. Rosemount 3051S Wireless troubleshooting table
Symptom
Corrective Actions
Transmitter will not respond to changes in
applied pressure
Check test equipment
Check impulse piping or manifold for blockage
Verify applied pressure is within sensor limits
Digital Pressure Variable reading is low or high
Check test equipment (verify accuracy)
Check impulse piping for blockage or low fill in wet leg
Verify transmitter is calibrated properly
Verify pressure calculations for application
Digital Pressure Variable reading is erratic
Check application for faulty equipment in pressure line
Verify transmitter is not reacting directly to equipment turning on/off
LCD Meter is not functioning
Reseat the LCD according to Installing the LCD Display on page 3-12
Verify that the LCD Meter is a wireless LCD Meter. An LCD from a wired device will not
function in a wireless device. Rosemount part number: 00753-9004-0002
Verify that the LCD meter mode is not disabled.
6-2
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
DISASSEMBLY
PROCEDURES
Remove from Service
Be aware of the following:
•
Follow all plant safety rules and procedures.
•
Isolate and vent the process from the transmitter before removing the
transmitter from service.
•
Detach the process flange by removing the four flange bolts and two
alignment screws that secure it.
•
Do not scratch, puncture, or depress the isolating diaphragms.
•
Clean isolating diaphragms with a soft rag and a mild cleaning solution,
and rinse with clear water.
•
Whenever you remove the process flange or flange adapters, visually
inspect the Teflon o-rings. Replace the o-rings if they show any signs of
damage, such as nicks or cuts. If they are not damaged, reuse them.
The 3051S Wireless transmitter is attached to the process connection by four
bolts and two cap screws. Remove the bolts and separate the transmitter from
the process connection. Leave the process connection in place and ready for
re-installation.
The 3051S Wireless in-line transmitter is attached to the process by a single
hex nut process connection. Loosen the hex nut to separate the transmitter
from the process.
Remove Terminal Block
Wireless PlantWeb Housing
Remove the battery pack. Loosen the two small screws and pull the entire
terminal block out. This procedure will expose the SuperModule connector,
see Figure 6-1.
Wireless PlantWeb Terminals
P/N 00753-9200-0010
COMM
6-3
Reference Manual
Rosemount 3051S Wireless Series
Remove Feature
Assembly
00809-0100-4802, Rev BA
August 2007
The Wireless Feature Board is located in the electronics compartment. To
remove the assembly, perform the following procedure.
1. Remove the housing cover opposite the field terminal side.
2. Remove the LCD Display, if applicable. To do this, hold in the two clips
and pull outward.
3. Loosen the two small screws located on the assembly.
4. Replace the LCD Display. This will help in removing the assembly.
5. Pull out the assembly to expose and locate the SuperModule connector
and antenna connector.
6. Remove the LCD Display, if applicable. To do this, hold in the two clips
and pull outward.
7. Grasp antenna connector by the base and pull upwards to disconnect.
8. Grasp the SuperModule connector, squeeze the clips and pull upwards
(avoid pulling wires).
Figure 6-1. SuperModule
connector view
Remove the
SuperModule from the
Housing
6-4
Wireless PlantWeb Housing
IMPORTANT
To prevent damage to the SuperModule cable, disconnect it from the
PlantWeb assembly before you remove the SuperModule from the housing.
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
1. Loosen the housing rotation set screw with a 3/32-inch hex wrench, then
rotate back one full turn.
2. Unscrew the housing from the SuperModule.
Housing Rotation Set
Screw (3/32-inch allen)
REASSEMBLY
PROCEDURES
Attach the SuperModule
to the Wireless Housing
IMPORTANT
The V-Seal must be installed at the bottom of the housing.
1. Apply a light coat of low temperature silicon grease to the SuperModule
connector.
2. Insert the SuperModule connector into the top of the SuperModule.
3. Reconnect the antenna wiring.
4. Gently slide the assembly into the housing, making sure the pins from
the PlantWeb housing properly engage the receptacles on the assembly.
5. Tighten the captive mounting screws.
6. Attach the PlantWeb housing cover and tighten so that metal contacts
metal.
Install the Terminal Block
1. Gently slide the terminal block into the housing, making sure the pins
from the PlantWeb housing properly engage the receptacles on the
terminal block.
2. Tighten the captive screws on the terminal block.
3. Attach the Wireless PlantWeb housing cover and tighten so that metal
contacts metal.
Reassemble the Process
Flange
1. Inspect the Teflon SuperModule o-rings. If the o-rings are not damaged,
reuse them. Replace o-rings that show any signs of damage, such as
nicks, cuts, or general wear.
NOTE
If you are replacing the o-rings, be careful not to scratch the o-ring grooves or
the surface of the isolating diaphragm when removing the damaged o-rings.
2. Install the process flange on the SuperModule. To hold the process
flange in place, install the two alignment screws to finger tight (screws
are not pressure retaining). Do not overtighten; this will affect
module-to-flange alignment.
3. Install the appropriate flange bolts.
6-5
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
a. If the installation requires a 1/4–18 NPT mounting, use four 1.75-in.
flange bolts. Go to step f.
b. If the installation requires a 1/2–14 NPT mounting, use four 2.88-in.
process flange/adapter bolts. For gage pressure configurations, use
two 2.88-in. bolts and two 1.75-in. bolts. Go to step d.
c. If the installation uses a manifold (differential pressure applications
only), use appropriate bolts. Go to step e.
d. Hold the flange adapters and adapter o-rings in place while
finger-tightening the bolts. Go to step g.
e. Align the process flange with the manifold.
f. Finger tighten the bolts.
g. Tighten the bolts to the initial torque value using a crossed pattern.
See Table 6-2 for appropriate torque values.
h. Tighten the bolts to the final torque value using a crossed pattern.
See Table 6-2 for appropriate torque values. When fully tightened,
the bolts should extend through the top of the module housing.
i. If the installation uses a manifold, then install flange adapters on the
process end of the manifold using the 1.75-in. flange bolts supplied
with the transmitter.
Table 6-2. Bolt Installation
Torque Values
Bolt Material
Initial Torque Value
Final Torque Value
CS-ASTM-A445 Standard
300 in-lb. (34 N-m)
650 in-lb. (73 N-m)
316 SST—Option L4
150 in-lb. (17 N-m)
300 in-lb. (34 N-m)
ASTM-A-193-B7M—Option L5
300 in-lb. (34 N-m)
650 in-lb. (73 N-m)
Monel®—Option L6
300 in-lb. (34 N-m)
650 in-lb. (73 N-m)
ASTM-A-453-660—Option L7
150 in-lb. (17 N-m)
300 in-lb. (34 N-m)
ASTM-A-193-B8M—Option L8
150 in-lb. (17 N-m)
300 in-lb. (34 N-m)
4. If you replaced the Teflon SuperModule o-rings, re-torque the flange
bolts after installation to compensate for cold flow.
5. Install the drain/vent valve.
a. Apply sealing tape to the threads on the seat. Starting at the base of
the valve with the threaded end pointing toward the installer, apply
two clockwise turns of sealing tape.
b. Take care to place the opening on the valve so that process fluid will
drain toward the ground and away from human contact when the
valve is opened.
c. Tighten the drain/vent valve to 250 in-lb. (28.25 N-m).
NOTE
After replacing o-rings on Range 1 transmitters and re-installing the process
flange, expose the transmitter to a temperature of 185 °F (85 °C) for two
hours. Then re-tighten the flange bolts in a cross pattern, and again expose
the transmitter to a temperature of 185 °F (85 °C) for two hours before
calibration.
6-6
Reference Manual
00809-0100-4802, Rev BA
August 2007
Appendix A
Rosemount 3051S Wireless Series
Specifications and
Reference Data
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page A-1
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page A-4
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-7
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-10
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-12
SPECIFICATIONS
PERFORMANCE
SPECIFICATIONS
For zero-based spans, reference conditions, silicone oil fill, glass-filled TFE
o-rings, SST materials, Coplanar flange (3051S_C) or
1
/2 in.- 14 NPT (3051S_T) process connections, digital trim values set to equal
range points.
Conformance to specification (±3σ (Sigma))
Technology leadership, advanced manufacturing techniques and statistical
process control ensure specification conformance to ±3σ or better.
Digital Output
For wireless devices, use calibrated range in place of span.
www.rosemount.com
Reference Manual
Rosemount 3051S Wireless Series
Reference Accuracy
Classic(1)
Models
3051S_CD, CG
Ranges 2 - 4 ±0.055% of span.
For spans less than 10:1,
URL
± 0.015 + 0.005 ⎛ --------------⎞ % of span
⎝ span⎠
Range 5 ±0.065% of span.
For spans less than 10:1,
URL
± 0.015 + 0.005 ⎛ --------------⎞ % of span
⎝ span⎠
Range 1 ±0.10% of span.
For spans less than 15:1,
URL
± 0.025 + 0.005 ⎛ --------------⎞ % of span
⎝ span⎠
Range 0 ±0.10% of span.
For spans less than 2:1 = ±0.05% of URL
3051S_T
Ranges 1 - 4 ±0.055% of span.
For spans less than 10:1,
URL
± 0.0065 ⎛ --------------⎞ % of span
⎝ span⎠
Range 5 ±0.065% of span.
For spans less than 10:1,
URL
± 0.0065 ⎛ --------------⎞ % of span
⎝ span⎠
3051S_CA
Ranges 1 - 4 ±0.055% of span.
For spans less than 10:1,
URL
± 0.0065 ⎛ --------------⎞ % of span
⎝ span⎠
Range 0 ±0.075% of span.
For spans less than 5:1,
URL
± 0.025 + 0.01 ⎛ --------------⎞ % of span
⎝ span⎠
±0.065% of span.
For spans less than 10:1,
URL
± 0.015 + 0.005 ⎛ --------------⎞ % of span
⎝ span⎠
3051S_L
(1) Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability.
Total Performance
Classic(1)
Models
3051S_
CD Ranges 2-3 CG ±0.15% of span; for ±50°F (28°C) temperature changes; 0-100%
Ranges 2-5 T Ranges relative humidity, up to 740 psi
2-4 CA Ranges 2-4 (51 bar) line pressure (CD only), from 1:1 to 5:1 rangedown.
(1) Total performance is based on combined errors of reference accuracy, ambient temperature effect, and line
pressure effect.
Long Term Stability
Models
Classic
3051S_
CD Ranges 2 - 5
CG Ranges 2 - 5
T Ranges 1 - 5
and CA Ranges 1 - 4
A-2
±0.125% of URL for 5 years; for ±50°F (28°C) temperature
changes, up to 1000 psi (68,9 bar) line pressure (CD only)
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Ambient Temperature Effect
Models
Classic
3051S_CD, CG
Range 2 - 5
per 50 °F (28 °C)
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
Range 0
Range 1
± (0.25% URL + 0.05% span)
from 1:1 to 30:1
± (0.1% URL + 0.25% span)
from 1:1 to 50:1
3051S_T
Ranges 2 - 4
Range 5
Range 1
3051S_CA
Ranges 2 - 4
Range 0
Range 1
3051S_L
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
± (0.05% URL + 0.075% span)
from 1:1 to 5:1
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
± (0.1% URL + 0.25% span)
from 1:1 to 30:1
± (0.0125% URL + 0.0625% span)
from 1:1 to 5:1
± (0.025% URL + 0.125% span)
from >5:1 to 100:1
See Instrument Toolkit.
Line Pressure Effect
For line pressures above 2000 psi (137,9 bar) and ranges 4-5, see the 3051S Series reference manual (document number 00809-0100-4801).
Models
Classic
3051S_CD
Range 2 - 3
Zero Error(1)
± 0.05% URL per 1000 psi (69 bar)
Range 0
Range 1
Range 2 -3
Range 0
Range 1
± 0.125% URL per 100 psi (6,89 bar)
± 0.25% URL per 1000 psi (69 bar)
Span Error
± 0.1% of reading per 1000 psi (69 bar)
± 0.15% of reading per 100 psi (6,89 bar)
± 0.4% of reading per 1000 psi (69 bar)
Mounting Position Effects
Models
Classic
3051S_C
3051S_L
Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be calibrated out; no span effect
With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (25,4 mmH2O); with diaphragm in
horizontal plane, zero shift of up to 5 inH2O (127 mmH2O) plus extension length on extended units; all
zero shifts can be calibrated out; no span effect
Zero shifts to 2.5 inH2O (63,5 mmH20), which can be calibrated out; no span effect
3051S_T and 3051S_CA
A-3
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Vibration Effect
Less than ±0.1% of URL when tested per the requirements of IEC60770-1
field or pipeline with high vibration level (10-60 Hz 0.21mm displacement peak
amplitude / 60-2000 Hz 3g).
Electromagnetic Compatibility (EMC)
All Models:
Meets all relevant requirements of IEC/EN 61326.
FUNCTIONAL
SPECIFICATIONS
Range and Sensor Limits
Range and Sensor Limits 3051S_
Range
0
1
2
3
4
5
Lower (LRL)
Classic
Upper (URL)
3051S_CD
3051S_CG, LG
3051S_LD
0.1 inH2O
(0,25 mbar)
0.5 inH2O
(1,24 mbar)
2.5 inH2O
(6,23 mbar)
10.0 inH2O
(24,9 mbar)
3.0 psi
(206,8 mbar)
20.0 psi
(1,38 bar)
3.0 inH2O
(7,5 mbar)
25.0 inH2O
(62,3 mbar)
250.0 inH2O
(0,62 bar)
1000.0 inH2O
(2,49 bar)
300.0 psi
(20,7 bar)
2000.0 psi
(137,9 bar)
–3.0 inH2O
(–7,5 mbar)
–25.0 inH2O
(–62,3 mbar)
–250.0 inH2O
(–0,62 bar)
–1000.0 inH2O
(-2,49 bar)
–300.0 psi
(–20,7 bar)
– 2000.0 psi
(–137,9 bar)
NA
NA
–25.0 inH2O
(–62,3 mbar)
–250.0 inH2O
(–0,62 bar)
–393.0 inH2O
(–979 mbar)
–14.2 psig
(–979 mbar)
–14.2 psig
(–979 mbar)
–25.0 inH2O
(–62,3 mbar)
–250.0 inH2O
(–0,62 bar)
–1000.0 inH2O
(–2,49 bar)
–300.0 psi
(–20,7 bar)
– 2000.0 psi
(–137,9 bar)
3051S_T Range and Sensor Limits
Range
1
2
3
4
5
Minimum Span
Classic
Upper (URL)
Lower (LRL) (Abs.)
Lower(1) (LRL) (Gage)
0.3 psi (20,7 mbar)
1.5 psi (0,103 bar)
8 psi (0,55 bar)
40 psi (2,76 bar)
2000 psi (137,9 bar)
30 psi (2,07 bar)
150 psi (10,34 bar)
800 psi (55,16 bar)
4000 psi (275,8 bar)
10000 psi (689,5 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
–14.7 psig (–1,01 bar)
–14.7 psig (–1,01 bar)
–14.7 psig (–1,01 bar)
–14.7 psig (–1,01 bar)
–14.7 psig (–1,01 bar)
(1) Assumes atmospheric pressure of 14.7 psig.
3051S_CA, LA Range and Sensor Limits
Range
(1)
0
1
2
3
4
Minimum Span
Classic
Upper (URL)
Lower (LRL)
0.167 psia (11,5 mbar)
0.3 psia (20,7 mbar)
1.5 psia (0,103 bar)
8 psia (0,55 bar)
40 psia (2,76 bar)
5 psia (0,34 bar)
30 psia (2,07 bar)
150 psia (10,34 bar)
800 psia (55,16 bar)
4000 psia (275,8 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
0 psia (0 bar)
(1) Range 0 is not available for 3051S_LA.
A-4
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Wireless Self-Organizing Networks
Output
Wireless enabled HART.
Transmit Rate
User selectable, 15 sec. to 60 min.
Wireless Battery
Replaceable, Intrinsically Safe Lithium-thionyl chloride battery pack with Valox® PBT
enclosure. 5-year battery life at reference conditions.(1)
Overpressure Limits
Transmitters withstand the following limits without damage:
3051S_CD, CG
Range 0: 750 psi (51,7 bar)
Range 1: 2000 psig (137,9 bar)
Ranges 2–5: 3626 psig (250,0 bar)
4500 psig (310,3 bar) for option code P9
6092 psig (420 bar) for option code P0 (3051S2CD only)
3051S_CA
Range 0: 60 psia (4,13 bar)
Range 1: 750 psia (51,7 bar)
Range 2: 1500 psia (103,4 bar)
Range 3: 1600 psia (110,3 bar)
Range 4: 6000 psia (413,7 bar)
3051S_TG, TA
Range 1: 750 psi (51,7 bar)
Range 2: 1500 psi (103,4 bar)
Range 3: 1600 psi (110,3 bar)
Range 4: 6000 psi (413,7 bar)
Range 5: 15000 psi (1034,2 bar)
3051S_LD, LG, LA
Limit is flange rating or sensor rating, whichever is lower (see the table below).
Standard
Type
CS Rating
SST Rating
ANSI/ASME
Class 150
285 psig
275 psig
ANSI/ASME
Class 300
740 psig
720 psig
ANSI/ASME
Class 600
1480 psig
1440 psig
At 100 °F (38 °C), the rating decreases
with increasing temperature, per ANSI/ASME B16.5.
DIN
PN 10–40
40 bar
40 bar
DIN
PN 10/16
16 bar
16 bar
DIN
PN 25/40
40 bar
40 bar
At 248 °F (120 °C), the rating decreases
with increasing temperature, per DIN 2401.
Static Pressure Limit
3051S_CD Only
Operates within specifications between static line pressures of 0.5 psia and 3626 psig;
4500 psig (310,3 bar) for option code P9
6092 psig (420 bar) for option code P0 (3051S2CD only)
Range 0: 0.5 psia to 750 psig (0,03 to 51,71 bar)
Range 1: 0.5 psia to 2000 psig (0,03 to137,90 bar)
(1)
Reference conditions are 70 °F (21 °C), transmit rate of once per minute, and routing data
for three additional network devices.
A-5
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Burst Pressure Limits
Coplanar or traditional process flange
• 10000 psig (689,5 bar).
3051S_T:
• Ranges 1–4: 11000 psi (758,4 bar)
• Range 5: 26000 psig (1792,64 bar)
Temperature Limits
Ambient
–40 to 185 °F (–40 to 85 °C)
With LCD display(1): –40 to 175 °F (–40 to 80 °C)
With option code P0: –4 to 185 °F (–20 to 85 °C)
(1) LCD display may not be readable and LCD updates will be slower at temperatures below -4 °F
(-20 °C).
Storage
–50 to 230 °F (–40 to 85 °C)
With LCD display: –40 to 185 °F (–40 to 85 °C)
Process Temperature Limits
At atmospheric pressures and above.
3051S_C Coplanar
Silicone Fill Sensor(1)
with Coplanar Flange
with Traditional Flange
with Level Flange
with 305 Integral Manifold
Inert Fill Sensor(1)
–40 to 250 °F (–40 to 121 °C)(2)
–40 to 300 °F (–40 to 149 °C)(2)(3)
–40 to 300 °F (–40 to 149 °C)(2)
–40 to 300 °F (–40 to 149 °C)(2)(3)
0 to 185 °F (–18 to 85 °C)(4) (5)
3051S_T In-Line (Process Fill Fluid)
Silicone Fill Sensor(1)
Inert Fill Sensor(1)
–40 to 250 °F (–40 to 121 °C)(2)
–22 to 250 °F (–30 to 121 °C)(2)
3051S_L Low-Side Temperature Limits
Silicone Fill Sensor(1)
Inert Fill Sensor(1)
–40 to 250 °F (–40 to 121 °C)(2)
0 to 185 °F (–18 to 85 °C)(2)
3051S_L High-Side Temperature Limits
(Process Fill Fluid)
Syltherm® XLT
D. C.® Silicone 704(6)
D. C. Silicone 200
Inert (Halocarbon)
Glycerin and Water
Neobee M-20®
Propylene Glycol and Water
(1)
(2)
(3)
(4)
(5)
(6)
Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio.
220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia.
-20 °F (-29 °C) is the lower process temperature limit with option code P0.
160 °F (71 °C) limit in vacuum service.
Not available for 3051S_CA.
Upper limit of 600 °F (315 °C) is available with 1199 seal assemblies mounted away from the
transmitter with the use of capillaries and up to 500 °F (260 °C) with direct mount extension.
Humidity Limits
0–100% relative humidity
Volumetric Displacement
Less than 0.005 in3 (0,08 cm3)
A-6
–102 to 302 °F (–75 to 150 °C)
32 to 500 °F (0 to 260 °C)
–49 to 401 °F (–45 to 205 °C)
–49 to 320 °F (–45 to 160 °C)
5 to 203 °F (–15 to 95 °C)
5 to 437 °F (–15 to 225 °C)
5 to 203 °F (–15 to 95 °C)
Reference Manual
00809-0100-4802, Rev BA
August 2007
Electrical Connections
1
/2–14 NPT. HART interface connections fixed to terminal block.
Process Connections
3051S_C
/4–18 NPT on 21/8-in. centers
1
/2–14 NPT and RC 1/2 on 2-in.(50.8mm), 21/8-in. (54.0 mm), or 21/4-in. (57.2mm) centers
(process adapters)
1
3051S_T
/2–14 NPT female,
Non-Threaded instrument flange (available in SST for Range 1–4 transmitters only),
G1/2 A DIN 16288 Male (available in SST for Range 1–4 transmitters only), or
Autoclave type F-250-C (Pressure relieved 9/16–18 gland thread; 1/4 OD high pressure tube 60°
cone; available in SST for Range 5 transmitters only).
1
3051S_L
High pressure side: 2-in.(50.8mm), 3-in. (72 mm), or 4-in. (102mm), ASME B 16.5 (ANSI)
Class 150, 300 or 600 flange; 50, 80 or 100 mm, DIN 2501 PN 40 or 10/16 flange
Low pressure side: 1/4–18 NPT on flange, 1/2–14 NPT on process adapter
Process-Wetted Parts
Process Isolating Diaphragms
3051S_
Isolating Diaphragm Material CD, CG
T
CA
316L SST
Hastelloy C-276 ®
Monel 400
Tantalum
Gold-plated Monel 400
Gold-plated 316L SST
•
•
•
•
•
•
•
•
•
•
•
•
•
L
See Below
PHYSICAL
SPECIFICATIONS
Rosemount 3051S Wireless Series
Drain/Vent Valves
316 SST, Hastelloy C-276, or Monel 400 material
(Monel is not available with 3051S_L).
Process Flanges and Adapters
Plated carbon steel,
CF-8M (Cast version of 316 SST, material per ASTM-A743), CW-12MW (Cast version of
Hastelloy C-276, material per ASTM-A494),
M-30C (Cast version of Monel 400, material per ASTM-A494).
Wetted O-rings
Glass-filled TFE
(Graphite-filled TFE with Isolating Diaphragm code 6)
3051S_L Process Wetted Parts
Flanged Process Connection (Transmitter High Side)
Process Diaphragms, Including Process Gasket Surface
316L SST, Hastelloy C-276, or Tantalum
Extension
CF-3M (Cast version of 316L SST, material per ASTM-A743), or CW-12MW (Cast version of
Hastelloy C, material ASTM A494); fits schedule 40 and 80 pipe
Mounting Flange
Zinc-cobalt plated CS or 316 SST
A-7
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Reference Process Connection (Transmitter Low Side)
Isolating Diaphragms
316L SST or Hastelloy C-276
Reference Flange and Adapter
CF-3M (Cast version of 316L SST, material per ASTM-A743)
Non-Wetted Parts
Electronics Housing
Low-copper aluminum
Coplanar Sensor Module Housing
CF-3M (Cast version of 316L SST)
Bolts
Plated carbon steel per ASTM A449, Type 1
Austenitic 316 SST
ASTM A 453, Class A, Grade 660
ASTM A 193, Grade B7M
ASTM A 193, Class 2, Grade B8M
Monel
Sensor Module Fill Fluid
Silicone or inert halocarbon (Inert is not available with 3051S_CA). In-Line series uses
Fluorinert® FC-43.
Process Fill Fluid (Liquid Level Only)
3051S_L: Syltherm XLT, D.C. Silicone 704,
D.C. Silicone 200, inert, glycerin and water,
Neobee M-20, propylene glycol and water.
Paint
Polyurethane
Cover O-rings
Buna-N
Wireless Terminal Block and Battery Pack
PBT
Antenna
PBT/PC integrated omnidirectional antenna
A-8
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Shipping Weights for 3051S Wireless Pressure Transmitter
Table A-1. SuperModule Platform weights
SuperModule Platform
Weight in lb. (kg)
Coplanar(1)
In-Line
3.1 (1,4)
1.4 (0,6)
(1) Flange and bolts not included.
Table A-2. Transmitter weights without options
Complete Transmitter(1)
Add Weight In lb (kg)
3051S_C with wireless PlantWeb housing
3051S_T with wireless PlantWeb housing
7.7 (3,5)
4.1 (1,8)
(1) Fully functional transmitter with terminal block,
covers, and SST flange.
Table A-3. 3051S_L weights without options
Flush
lb. (kg)
12.5 (5,7)
17.5 (7,9)
23.5 (10,7)
17.5 (7,9)
22.5 (10,2)
32.5 (14,7)
15.3 (6,9)
25.2 (11,4)
13.8 (6,2)
19.5 (8,8)
17.8 (8,1)
23.2 (10,5)
Flange
2-in., 150
3-in., 150
4-in., 150
2-in., 300
3-in., 300
4-in., 300
2-in., 600
3-in., 600
DN 50 / PN 40
DN 80 / PN 40
DN 100 / PN 10/16
DN 100 / PN 40
2-in. Ext.
lb (kg)
—
19.5 (8,8)
26.5 (12,0)
—
24.5 (11,1)
35.5 (16,1)
—
27.2 (12,3)
—
21.5 (9,7)
19.8 (9,0)
25.2 (11,5)
4-in. Ext.
lb (kg)
—
20.5 (9,3)
28.5 (12,9)
—
25.5 (11,6)
37.5 (17,0)
—
28.2 (12,8)
—
22.5 (10,2)
20.8 (9,5)
26.2 (11,9)
6-in. Ext.
lb (kg)
—
21.5 (9,8)
30.5 (13,8)
—
26.5 (12,0)
39.5 (17,9)
—
29.2 (13,2)
—
23.5 (10,7)
21.8 (9,9)
27.2 (12,3)
Table A-4. Transmitter option weights
Option Code
M5
B4
B1, B2, B3
B7, B8, B9
BA, BC
F12, F22
F13, F23
E12, E22
F14, F24
F15, F25
G21
G22
G11
G12
G31
G41
Option
LCD display for aluminum PlantWeb housing(1),
LCD display for SST PlantWeb housing(1)
SST mounting bracket for Coplanar flange
Mounting Bracket for Traditional flange
Mounting Bracket for Traditional flange with SST bolts
SST Bracket for Traditional flange
SST Traditional flange(2)
Traditional flange (Hastelloy)
SST Coplanar flange(2)
Traditional flange (Monel)
Traditional Flange (SST with Hastelloy D/V)
Level flange—3 in., 150
Level flange—3 in., 300
Level flange—2 in., 150
Level flange—2 in., 300
DIN Level flange, SST, DN 50, PN 40
DIN Level flange, SST, DN 80, PN 40
Add lb (kg)
0.8 (0,4)
1.72 (0,8)
0.6 (0,3)
2.3 (1,0)
2.3 (1,0)
2.3 (1,0)
3.3 (1,5)
2.7 (1,2)
1.9 (0,9)
2.6 (1,2)
2.5 (1,1)
10.8 (4,9)
14.3 (6,5)
10.7 (4,9)
14.0 (6,4)
8.3 (3,8)
13.7 (6,2)
(1) Includes LCD display connector board and display cover
(2) Includes mounting bolts
Table A-5.
Item
Aluminum standard cover
Aluminum display cover
LCD display(1)
PlantWeb terminal block
Wireless battery
Weight In lb. (kg)
0.4 (0,2)
0.7 (0,3)
0.1 (0,1)
0.2 (0,1)
0.5 (0,2)
(1) Display only
A-9
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
DIMENSIONAL DRAWINGS
Dimensions are in inches (millimeters).
Process adapters (option D2) and Rosemount 305 integral manifolds must be ordered with the transmitter
.
Wireless PlantWeb Housing with In-Line and Coplanar SuperModule Platform
900 mHZ
Antenna
2.4 GHZ
Antenna
6.93
(176)
90°
10.91
(277)
3.457
(87.8)
6.72
(171)
6.07
(154)
4.20
(107)
7.70
(196) 8.53
(217) 9.63
(245)
Nameplate
Drain/
Vent
Coplanar Flange Process
Connection per IEC 81518
Flange Adapters
(Optional)
6.93
(176)
3.457
(87.8)
7.97
(202)
U-Bolt Bracket
1
/2-14 NPT Female or
G1/2 A DIN 16288 Male
Process Connection
A-10
Conduit
Entry
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Table A-6. 3051S_L Dimensional Specifications
Except where indicated, dimensions are in inches (millimeters).
Class
ASME B16.5 (ANSI) 150
ASME B16.5 (ANSI) 300
ASME B16.5 (ANSI) 600
DIN 2501 PN 10–40
DIN 2501 PN 25/40
DIN 2501 PN 10/16
Pipe
Size
2 (51)
3 (76)
4 (102)
2 (51)
3 (76)
4 (102)
2 (51)
3 (76)
DN 50
DN 80
DN 100
DN 100
Flange
Thickness A
Bolt Circle
Diameter B
Outside
Diameter C
No. of
Bolts
Bolt Hole
Diameter
Extension
Diameter(1) D
O.D. Gasket
Surface E
0.69 (18)
0.88 (22)
0.88 (22)
0.82 (21)
1.06 (27)
1.19 (30)
1.00 (25)
1.25 (32)
20 mm
24 mm
24 mm
20 mm
4.75 (121)
6.0 (152)
7.5 (191)
5.0 (127)
6.62 (168)
7.88 (200)
5.0 (127)
6.62 (168)
125 mm
160 mm
190 mm
180 mm
6.0 (152)
7.5 (191)
9.0 (229)
6.5 (165)
8.25 (210)
10.0 (254)
6.5 (165)
8.25 (210)
165 mm
200 mm
235 mm
220 mm
4
4
8
8
8
8
8
8
4
8
8
8
0.75 (19)
0.75 (19)
0.75 (19)
0.75 (19)
0.88 (22)
0.88 (22)
0.75 (19)
0.88 (22)
18 mm
18 mm
22 mm
18 mm
NA
2.58 (66)
3.5 (89)
NA
2.58 (66)
3.5 (89)
NA
2.58 (66)
NA
65 mm
89 mm
89 mm
3.6 (92)
5.0 (127)
6.2 (158)
3.6 (92)
5.0 (127)
6.2 (158)
3.6 (92)
5.0 (127)
4.0 (102)
5.4 (138)
6.2 (158)
6.2 (158)
Table A-7.
Class
ASME B16.5 (ANSI) 150
ASME B16.5 (ANSI) 300
ASME B16.5 (ANSI) 600
DIN 2501 PN 10–40
DIN 2501 PN 25/40
DIN 2501 PN 10/16
Lower Housing G
Pipe
Size
Process
Side F
1/4 NPT
1/2 NPT
H
2 (51)
3 (76)
4 (102)
2 (51)
3 (76)
4 (102)
2 (51)
3 (76)
DN 50
DN 80
DN 100
DN 100
2.12 (54)
3.6 (91)
3.6 (91)
2.12 (54)
3.6 (91)
3.6 (91)
2.12 (54)
3.6 (91)
2.4 (61)
3.6 (91)
3.6 (91)
3.6 (91)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
0.97 (25)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
1.31 (33)
6.66 (169)
6.66 (169)
6.66 (169)
6.66 (169)
6.66 (169)
6.66 (169)
8.66 (219)
8.66 (219)
6.66 (169)
6.66 (169)
6.66 (169)
6.66 (169)
(1)
Tolerances are 0.040 (1,02), –0.020 (0,51).
A-11
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
ORDERING INFORMATION
Rosemount 3051S Series Coplanar
Model
Transmitter Type
3051S
Code
Scalable pressure transmitter
Performance Class
1(1)
3(2)
2
Code
Ultra: 0.025% span accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty
Ultra for Flow: 0.04% reading accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty
Classic: 0.055% span accuracy, 100:1 rangedown, 5-year stability
Connection Type
C
Code
Coplanar
Measurement Type(3)
D
G
A
Code
Differential
Gage
Absolute
Pressure Range
0A(4)
1A
2A
3A
4A
5A
Code
Differential
-3 to 3 inH2O (-7,47 to 7,47 mbar)
-25 to 25 inH2O (-62,2 to 62,2 mbar)
-250 to 250 inH2O (-623 to 623 mbar)
-1000 to 1000 inH2O (-2,5 to 2,5 bar)
-300 to 300 psi (-20,7 to 20,7 bar)
-2000 to 2000 psi (-137,9 to 137,9 bar)
Isolating Diaphragm
2(5)
3(5)
4
5(6)
6
Gage
N/A
-25 to 25 inH2O (-62,2 to 62,2 mbar)
-250 to 250 inH2O (-623 to 623 mbar)
-393 to 1000 inH2O (-0,98 to 2,5 bar)
-14.2 to 300 psig (-0,98 to 21 bar)
-14.2 to 2000 psig (-0,98 to 137,9 bar)
7
Code
316L SST
Hastelloy C-276
Monel 400
Tantalum
Gold-plated Monel 400
Note: Includes graphite-filled TFE o-ring.
Gold-plated 316L SST
Process Connection(7)
000
A11
A12
B11(9)
B12(9)
C11
D11
EA2
EA3
EA5
E11
E12
E13(5)
E14
E15(5)
E16(5)
E21
E22
E23(5)
E24
E25(5)
E26(5)
F12
F13(5)
F14
Flange Material
None
Assemble to Rosemount 305 integral manifold
Assemble to 304 or AMF manifold and 316 SST traditional flange
Assemble to one Rosemount 1199 diaphragm seal
Assemble to two Rosemount 1199 diaphragm seals
Assemble to Rosemount 405 primary element
Assemble to Rosemount 1195 integral orifice and Rosemount 305 integral manifold
Assemble to Rosemount Annubar Primary Element with Coplanar flange 316 SST
Assemble to Rosemount Annubar Primary Element with Coplanar flange Hastelloy C-276
Assemble to Rosemount Annubar Primary Element with Coplanar flange 316 SST
1
Coplanar flange
/4–18 NPT
CS
1
Coplanar flange
/4–18 NPT
316 SST
1
Coplanar flange
/4–18 NPT
Hastelloy C-276
1
Coplanar flange
/4–18 NPT
Monel 400
1
Coplanar flange
/4–18 NPT
316 SST
1
Coplanar flange
/4–18 NPT
CS
Coplanar flange
RC 1/4
CS
Coplanar flange
RC 1/4
316 SST
Coplanar flange
RC 1/4
Hastelloy C-276
Coplanar flange
RC 1/4
Monel 400
Coplanar flange
RC 1/4
316 SST
Coplanar flange
RC 1/4
CS
1
Traditional flange
/4–18 NPT
316 SST
1
Traditional flange
/4–18 NPT
Hastelloy C-276
1
Traditional flange
/4–18 NPT
Monel 400
A-12
Size
Absolute
0 to 5 psia (0 to 0,34 bar)
0 to 30 psia (0 to 2,06 bar)
0 to 150 psia (0 to 10,34 bar)
0 to 800 psia (0 to 55,2 bar)
0 to 4000 psia (0 to 275,8 bar)
N/A
Material Type(8)
Drain Vent
316 SST
Hastelloy C-276
Hastelloy C-276
316 SST
316 SST
Hastelloy C-276
Monel 400
Hastelloy C-276
Hastelloy
316 SST
316 SST
Hastelloy C-276
Monel 400
Hastelloy C-276
Hastelloy C-276
316 SST
Hastelloy C-276
Monel 400
Bolting
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
F15(5)
F22
F23(5)
F24
F25(5)
F32
F52
F62
F72
G11
G12
G14(5)
G15(5)
G21
G22
G24(5)
G25(5)
G31
G41
Code
Traditional flange
Traditional flange
Traditional flange
Traditional flange
Traditional flange
Bottom vent traditional flange
DIN-compliant traditional flange
DIN-compliant traditional flange
DIN-compliant traditional flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Vertical mount level flange
Output(10)
1
A
B(11)
F(12)
X(13)
Code
4–20 mA with digital signal based on HART protocol
4–20 mA Safety Certified with digital signal based on HART protocol
FOUNDATION fieldbus protocol
Wireless (Requires wireless options and wireless housing 5A)
Housing Style
00
01(14)
1A
1B
1C
1J
1K
1L
5A
2A
2B
2C
2J
2E
2F
2G
2M
7J(15)
Code
None (SuperModule Platform only, no housing included)
Assemble to Rosemount 753R Web-Based Monitoring Indicator
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
Wireless PlantWeb housing
Junction Box housing
Junction Box housing
Junction Box housing
Junction Box housing
Junction Box Housing with output for remote display and interface
Junction Box Housing with output for remote display and interface
Junction Box Housing with output for remote display and interface
Junction Box Housing with output for remote display and interface
Quick Connect (A size Mini, 4-pin male termination)
Options
/4–18 NPT
RC 1/4
RC 1/4
RC 1/4
RC 1/4
1
/4–18 NPT
1
/4–18 NPT
1
/4–18 NPT
1
/4–18 NPT
2-in. ANSI class 150
2-in. ANSI class 300
2-in. ANSI class 150
2-in. ANSI class 300
3-in. ANSI class 150
3-in. ANSI class 300
3-in. ANSI class 150
3-in. ANSI class 300
DIN- DN 50 PN 40
DIN- DN 80 PN 40
Flange Material
316 SST
316 SST
Hastelloy C-276
Monel 400
316 SST
316 SST
316 SST
316 SST
316 SST
316 SST
316 SST
Hastelloy C-276
Hastelloy C-276
316 SST
316 SST
Hastelloy C-276
Hastelloy C-276
316 SST
316 SST
Drain Vent
Hastelloy C-276
316 SST
Hastelloy C-276
Monel 400
Hastelloy C-276
316 SST
316 SST
316 SST
316 SST
Bolting
Material(8)
Conduit Entry Size
Aluminum
Aluminum
Aluminum
316L SST
316L SST
316L SST
Aluminum
Aluminum
Aluminum
Aluminum
316L SST
Aluminum
Aluminum
Aluminum
316L SST
316L SST
1
7
/16-in. bolting
M10 bolting
M12 bolting
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
1
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
1
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
PlantWeb Control Functionality
FOUNDATION fieldbus Advanced Control Function Block Suite
A01(16)
PlantWeb Diagnostic Functionality
D01(16)
FOUNDATION fieldbus Diagnostics Suite
DA1(17)
HART Diagnostics Suite
PlantWeb Enhanced Measurement Functionality
H01(16)(18) Fully Compensated Mass Flow Block
A-13
Reference Manual
Rosemount 3051S Wireless Series
Code
00809-0100-4802, Rev BA
August 2007
Wireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WA
User Configurable Transmit Rate
Operating Frequency and Protocol
1
2.4 GHz DSSS, HART
2
900 MHz FHSS, HART
Antenna
WK
Integral, Omnidirectional Antenna
SmartPower™
1
Long-life Battery Pack
NOTE: Battery must be shipped separately, order Part No. 00753-9220-0001.
Code
Options
Mounting Brackets(19)
B4
Coplanar flange bracket, all SST, 2-in. pipe and panel
B1
Traditional flange bracket, CS, 2-in. pipe
B2
Traditional flange bracket, CS, panel
B3
Traditional flange flat bracket, CS, 2-in. pipe
B7
Traditional flange bracket, B1 with SST bolts
B8
Traditional flange bracket, B2 with SST bolts
B9
Traditional flange bracket, B3 with SST bolts
BA
Traditional flange bracket, B1, all SST
BC
Traditional flange bracket, B3, all SST
Special Configuration (Software)
C1(20)
Custom software configuration
Note: A Configuration Data Sheet must be completed.
C3
Gage pressure calibration on Rosemount 3051S_CA4 only
C4(20)(21)
NAMUR alarm and saturation levels, high alarm
C5(20)(21)
NAMUR alarm and saturation levels, low alarm
C6(1)(20)
Custom alarm and saturation signal levels, high alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
C7(1)(20)
Custom alarm and saturation signal levels, low alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
Low alarm (standard Rosemount alarm and saturation levels)
C8(20)(21)
Special Configuration (Hardware)
D1(20)(21)
Hardware adjustments (zero, span, alarm, security)
Note: Not available with housing style codes 00, 01, 2E, 2F, 2G, 2M, 5A, or 7J.
D2(19)
Process adapters 1/2-14 NPT
D4
External ground screw assembly
D5(19)
Delete transmitter drain/vent valves (install plugs)
Coplanar flange without drain/vent ports
D7(19)
D8(19)
Ceramic drain/vent valves
D9(19)
RC 1/2 process adapters
Product Certifications(22)
E1
ATEX Flameproof
I1
ATEX Intrinsically Safe
IA
ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
N1
ATEX Type n
K1
ATEX Flameproof, Intrinsically Safe, Type n, Dust (combination of E1, I1, N1, and ND)
ND
ATEX Dust
E4
JIS Flameproof
E5
FM Explosion-proof
I5
FM Intrinsically Safe, Non-Incendive
IE
FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K5
FM Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5 and I5)
E6
CSA Explosion-proof, Division 2
I6
CSA Intrinsically Safe
IF
CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K6
CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
D3(11)(23)
Measurement Canada Accuracy Approval
E7
SAA Flameproof, Dust Ignition-proof
I7
IECEx Intrinsically Safe
A-14
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
IG
N7
K7
KA
IECEx FISCO Intrinsically Safe
IECEx Type n
SAA Flameproof, Dust Ignition-proof, IECEx Intrinsically Safe, and Type n (combination of E7, I7, and N7)
ATEX and CSA Flameproof, Intrinsically Safe (combination of E1, I1, E6, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KB
FM and CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KC
FM and ATEX Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5, E1, I5, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KD
FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
DW(24)
NSF Drinking Water Approval
Alternate Materials of Construction
L1
Inert sensor fill fluid (differential and gage only)
Note: Silicone fill fluid is standard.
L2
Graphite-filled Teflon® (PTFE) o-ring
(19)
L4
Austenitic 316 SST bolts
L5(19)
ASTM A 193, Grade B7M bolts
L6(19)
Monel bolts
L7(19)
ASTM A 453, Class A, Grade 660 bolts
L8(19)
ASTM A 193, Class 2, Grade B8M bolts
Digital Display(25)
M5
PlantWeb LCD Display
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M7(1)(26)
Note: Use Belden 3084A cable or equivalent. Contact an Emerson Process Management representative for additional information.
M8(1)(26)
Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M9(1)(26)
Special Procedures
P1
Hydrostatic testing with certificate
P2(19)
Cleaning for special services
P3(19)
Cleaning for less than 1PPM chlorine/fluorine
P9
4500 psig (310 bar) static pressure limit (Rosemount 3051S_CD only)
P0(27)
6092 psig (420 bar) static pressure limit (Rosemount 3051S2CD only)
Special Certifications
Q4
Calibration certificate
QP
Calibration certificate and tamper evident seal
Q8(21)
Material traceability certification per EN 10204 3.1.B
QS(28)(21)
Certificate of FMEDA Data
Q16(21)
Surface finish certification for sanitary remote seals
Terminal Blocks
Transient terminal block
T1(29)
T2(30)
Terminal block with WAGO® spring clamp terminals
T3(30)
Transient terminal block with WAGO spring clamp terminals
Conduit Electrical Connector
GE(31)
M12, 4-pin, Male Connector (eurofast®)
GM(31)
A size Mini, 4-pin, Male Connector (minifast®)
Typical Model Number: 3051S1CD 2A 2 E12 A 1A DA1 B4 M5
(1) Not available with output codes B and X.
(2) Not available with output codes B and X or Housing code 01. This option is only available with range codes 2A and 3A, 316L SST isolating diaphragm and
silicone fill fluid.
(3) Performance Class code 3 is available with Measurement Type code D only.
(4) 3051S_CD0 is only available with traditional flange, 316 SST diaphragm material, silicone fill fluid, and Bolting option L4.
(5) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining
environments.
(6) Tantalum diaphragm material is only available for ranges 2A - 5A, differential and gage.
(7) Process connection option codes B12, C11, D11, EA2, EA3 and EA5 are only available on differential Measurement Type, code D.
(8) Material specified is cast as follows: CF-8M is the cast version of 316 SST, CF-3M is the cast version of 316L SST, CW-12MW is the cast version of Hastelloy
C-276, M-30C is the cast version of Monel 400. For housing, material is aluminum with polyurethane paint.
(9) Consult an Emerson Process Management representative for performance specifications.
(10) For spare SuperModule Platforms, select output code A.
(11) Requires PlantWeb housing and Hardware Adjustments option code D1. For the 3051S SIS Safety Transmitter, rangedown is limited to 10:1 on all models
with the exception of range 0. The 3051S2CD0 is limited to 2:1 rangedown, the 3051S2CA0 is limited to 5:1 rangedown.
A-15
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
(12) Requires PlantWeb housing.
(13) Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5) and CSA Intrinsically Safe (option code I6).
(14) Available with output code A only. Not available with approvals. See Rosemount 753R Product Data Sheet, 00813-0100-4379, to specify Web-Based
Monitoring Indicator. Does not integrate into plant host systems.
(15) Available with output code A only. Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5), ATEX Intrinsically Safe (option code I1), or
IECEx Intrinsically Safe (option code I7). Contact an Emerson Process Management representative for additional information.
(16) Requires PlantWeb housing and output code F.
(17) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard.
(18) Requires Rosemount Engineering Assistant to configure.
(19) Not available with process connection option code A11.
(20) Not available with output code F or Housing code 01.
(21) Not available with output code X.
(22) Valid when SuperModule Platform and housing have equivalent approvals.
(23) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information.
(24) Requires 316L SST wetted materials, glass-filled TFE O-ring (standard), and Process Connection code E12 or F12.
(25) Not available with Housing code 01 or 7J.
(26) Not available with output code F, Housing code 01, or option code DA1.
(27) Requires 316L SST or Hastelloy C-276 diaphragm material, assemble to Rosemount 305 integral manifold or DIN-compliant traditional flange process
connection, and bolting option L8. Limited to Pressure Range (Differential), ranges 2A – 5A.
(28) Not available with Housing code 01.
(29) Not available with Housing code 00, 01, 5A, or 7J.
(30) Available with output code A and PlantWeb housing only.
(31) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Non-Incendive approval (option
code I5) or FM FISCO Intrinsically Safe approval (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating
(NEMA 4X and IP66).
A-16
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Rosemount 3051S Series In-Line
Model
Transmitter Type
3051S
Code
Scalable pressure transmitter
Performance Class
1(1)
2
Code
Ultra: 0.025% span accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty
Classic: 0.055% span accuracy, 100:1 rangedown, 5-year stability
Device Type
T
Code
In-Line
Measurement Type
G
A
Code
Gage
Absolute
Pressure Range
TG
TA
1A
2A
3A
4A
5A
Code
-14.7 to 30 psi (-1,0 to 2,1 bar)
-14.7 to 150 psi (-1,0 to 10,3 bar)
-14.7 to 800 psi (-1,0 to 55 bar)
-14.7 to 4000 psi (-1,0 to 276 bar)
-14.7 to 10000 psi (-1,0 to 689 bar)
Isolating Diaphragm / Process Connection Material
0 to 30 psia (2,1 bar)
0 to 150 psia (10,3 bar)
0 to 800 psia (55 bar)
0 to 4000 psia (276 bar)
0 to 10000 psia (689 bar)
2(2)
3(2)
Code
316L SST
Hastelloy C-276
Process Connection Style
A11
B11(3)
E11
F11
G11
H11
Code
Assemble to Rosemount 306 integral manifold
Assemble to one Rosemount 1199 diaphragm seal
1
/2–14 NPT female
Non-threaded instrument-flange (I-flange) (Range 1-4 only)
G1/2 A DIN 16288 male (Range 1-4 only)
Coned and threaded, compatible with autoclave type F-250-C (Range 5A only)
Output(4)
A
B(5)
F(6)
X(7)
Code
4–20 mA with digital signal based on HART protocol
4–20 mA Safety Certified with digital signal based on HART protocol
FOUNDATION fieldbus protocol
Wireless (Requires wireless options and wireless housing 5A)
Housing Style
Materials(8)
00
01(9)
1A
1B
1C
1J
1K
1L
5A
2A
2B
2C
2J
2E
2F
2G
2M
7J(10)
None (SuperModule Platform only, no housing included)
Assemble to Rosemount 753R Web-Based Monitoring Indicator
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
PlantWeb housing
Wireless PlantWeb housing
Junction Box housing
Junction Box housing
Junction Box housing
Junction Box housing
Junction Box housing with output for remote interface
Junction Box housing with output for remote interface
Junction Box housing with output for remote interface
Junction Box housing with output for remote interface
Quick Connect (A size Mini, 4-pin male termination)
Aluminum
Aluminum
Aluminum
316L SST
316L SST
316L SST
Aluminum
Aluminum
Aluminum
Aluminum
316L SST
Aluminum
Aluminum
Aluminum
316L SST
316L SST
Conduit Entry Size
1
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
M20 x 1.5 (CM20)
G 1/2
1
/2–14 NPT
1
/2–14 NPT
M20 x 1.5 (CM20)
G 1/ 2
1
/2–14 NPT
1
/2–14 NPT
M20 x 1.5 (CM20)
G1/2
1
/2–14 NPT
A-17
Reference Manual
Rosemount 3051S Wireless Series
Code
00809-0100-4802, Rev BA
August 2007
Options
PlantWeb Control Functionality
A01(11)
FOUNDATION fieldbus Advanced Control Function Block Suite
PlantWeb Diagnostic Functionality
D01(11)
FOUNDATION fieldbus Diagnostics Suite
DA1(12)
HART Diagnostics Suite
PlantWeb Enhanced Measurement Functionality
H01(11)(13) Fully Compensated Mass Flow Block
Code
Wireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WA
User Configurable Transmit Rate
Operating Frequency and Protocol
1
2.4 GHz DSSS, HART
2
900 MHz FHSS, HART
Antenna
WK
Integral, Omnidirectional Antenna
SmartPower™
1
Long-life Battery Pack
NOTE: Battery must be shipped separately, order Part No. 00753-9220-0001.
Code
Options
Mounting Bracket
B4
Bracket, all SST, 2-in. pipe and panel
Special Configuration (Software)(14)
C1(14)
Custom software configuration
Note: A Configuration Data Sheet must be completed.
C4(14)(15)
NAMUR alarm and saturation values, high alarm
C5(14)(15)
NAMUR alarm and saturation values, low alarm
C6(1)(14)
Custom alarm and saturation signal levels, high alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
C7(1)(14)
Custom alarm and saturation signal levels, low alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
C8(14)(15)
Low alarm (Standard Rosemount alarm and saturation signal levels)
Special Configuration (Hardware)
D1(14)(15)
Hardware adjustments (zero, span, alarm, security)
Note: Not available with Housing Style codes 00, 01, 2E, 2F, 2G, 2M, 5A, or 7J.
D4
External ground screw assembly
Product Certifications(16)
E1
ATEX Flameproof
I1
ATEX Intrinsically Safe
IA
ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
N1
ATEX Type n
K1
ATEX Flameproof, Intrinsically Safe, Type n, Dust (combination of E1, I1, N1, and ND)
ND
ATEX Dust
E4
JIS Flameproof
E5
FM Explosion-proof
I5
FM Intrinsically Safe, Non-Incendive
IE
FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K5
FM Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5 and I5)
E6
CSA Explosion-proof, Division 2
I6
CSA Intrinsically Safe
IF
CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K6
CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
Measurement Canada Accuracy Approval
D3(5)(17)
E7
SAA Flameproof, Dust Ignition-proof
I7
IECEx Intrinsically Safe
IG
IECEx FISCO Intrinsically Safe
N7
IECEx Type n
K7
SAA Flameproof, Dust Ignition-proof, IECEx Intrinsically Safe, and Type n (combination of E7, I7, and N7)
KA
ATEX and CSA Flameproof, Intrinsically Safe (combination of E1, I1, E6, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
A-18
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
KB
FM and CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KC
FM and ATEX Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5, E1, I5, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KD
FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
DW(18)
NSF Drinking Water Approval
Alternate Materials of Construction
L1
Inert sensor fill fluid Note: Silicone fill fluid is standard.
Digital Display(19)
M5
PlantWeb LCD Display
M7(1)(20)
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Note: Use Belden 3084A cable or equivalent. Contact an Emerson Process Management representative for additional information.
M8(1)(19)
Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M9(1)(19)
Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Special Procedures
P1
Hydrostatic testing with certificate
P2(21)
Cleaning for special services
P3(21)
Cleaning for less than 1 PPM chlorine/fluorine
Special Certifications
Q4
Calibration certificate
QP
Calibration certificate and tamper evident seal
Q8(15)
Material traceability certification per EN 10204 3.1.B
Certificate of FMEDA Data
QS(15)(22)
Q16(15)
Surface finish certification for sanitary remote seals
Terminal Blocks
T1(23)
Transient terminal block
T2(24)
Terminal block with WAGO® spring clamp terminals
(24)
T3
Transient terminal block with WAGO spring clamp terminals
Conduit Electrical Connector
GE(25)
M12, 4-pin, Male Connector (eurofast®)
(25)
GM
A size Mini, 4-pin, Male Connector (minifast®)
Typical Model Number: 3051S1TG 2A 2 E11 A 1A DA1 B4 M5
(1) Not available with output codes B and X.
(2) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining
environments.
(3) Contact a Rosemount representative for performance specifications.
(4) For spare SuperModule Platforms, select output code A.
(5) Requires PlantWeb housing and Hardware Adjustments option code D1. For the 3051S SIS Safety Transmitter, rangedown is limited to 10:1.
(6) Requires PlantWeb housing.
(7) Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5) and CSA Intrinsically Safe (option code I6).
(8) Material specified is cast as follows: CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane paint.
(9) Available with output code A only. Not available with approvals. See Rosemount 753R Product Data Sheet, 00813-0100-4379, to specify Web-Based
Monitoring Indicator. Does not integrate into plant host systems.
(10) Available with output code A only. Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5), ATEX Intrinsically Safe (option code I1), or
IECEx Intrinsically Safe (option code I7). Contact an Emerson Process Management representative for additional information.
(11) Requires PlantWeb housing and output code F.
(12) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard.
(13) Requires Rosemount Engineering Assistant to configure.
(14) Not available with output code F or Housing code 01.
(15) Not available with output code X.
(16) Valid when SuperModule Platform and housing have equivalent approvals.
(17) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information.
(18) Requires 316L SST wetted materials and Process Connection code E11 or G11.
(19) Not available with Housing code 01 and 7J.
(20) Not available with output code F, Housing code 01, or option code DA1.
(21) Not available with process connection option code A11.
(22) Not available with Housing code 01.
(23) Not available with Housing code 00, 01, 5A, or 7J.
(24) Available with output code A and PlantWeb housing only.
(25) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Non-Incendive approval (option
code I5) or FM FISCO Intrinsically Safe approval (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating
(NEMA 4X and IP66).
A-19
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Series Liquid Level
Select either FF diaphragm seal type (see “Flush Flanged Seal” on page A-21) or for EF diaphragm seal type (see “Extended Flanged Seal” on page A-22)
and then finish this selection by choosing transmitter options.
Model
3051S
Code
1(1)
2
Code
L
Code
D
G
A
Code
Transmitter Type
Scalable pressure transmitter
Performance Class
Ultra: 0.065% span accuracy, 100:1 rangedown, limited 12-year warranty
Classic: 0.065% span accuracy, 100:1 rangedown
Connection Type
Level
Measurement Type
Differential
Gage
Absolute
Pressure Range
Differential (LD)
Gage (LG)
Absolute (LA)
1A
-25 to 25 inH2O (-62,2 to 62,2 mbar)
-25 to 25 inH2O (-62,2 to 62,2 mbar)
0 to 30 psia (2,1 bar)
2A
-250 to 250 inH2O (-623 to 623 mbar)
-250 to 250 inH2O (-623 to 623 mbar)
0 to 150 psia (10 bar)
3A
-1000 to 1000 inH2O (-2,5 to 2,5 bar)
-393 to 1000 inH2O (-0,98 to 2,5 bar)
0 to 800 psia (55 bar)
4A
-300 to 300 psi (-20,7 to 20,7 bar)
-14.2 to 300 psig (-0,98 to 21 bar)
0 to 4000 psia (276 bar)
5A
-2000 to 2000 psi (-137,9 to 137,9 bar)
-14.2 to 2000 psig (-0,98 to 137,9 bar)
N/A
Code
Output(2)
A
4-20 mA with digital signal based on HART protocol
B(3)
4-20 mA Safety Certified with digital signal based on HART protocol
F(4)
FOUNDATION fieldbus protocol
X(5)
Wireless (Requires wireless options and wireless housing 5A)
Code
Housing Style
Material(6)
Conduit Entry
00
None (SuperModule Platform only, no housing included)
01(7)
Assemble to Rosemount 753R Web-Based Monitoring Indicator
1
1A
PlantWeb housing
Aluminum
/2–14 NPT
1B
PlantWeb housing
Aluminum
M20 x 1.5 (CM20)
1C
PlantWeb housing
Aluminum
G1/2
1
1J
PlantWeb housing
316L SST
/2–14 NPT
1K
PlantWeb housing
316L SST
M20 x 1.5 (CM20)
1L
PlantWeb housing
316L SST
G1/2
1
5A
Wireless PlantWeb housing
Aluminum
/2–14 NPT
1
2A
Junction Box housing
Aluminum
/2–14 NPT
2B
Junction Box housing
Aluminum
M20 x 1.5 (CM20)
2C
Junction Box housing
Aluminum
G1/2
1
2J
Junction Box housing
316L SST
/2–14 NPT
1
2E
Junction Box with output for remote interface
Aluminum
/2–14 NPT
2F
Junction Box with output for remote interface
Aluminum
M20 x 1.5 (CM20)
2G
Junction Box with output for remote interface
Aluminum
G1/2
1
2M
Junction Box with output for remote interface
316L SST
/2–14 NPT
7J(8)
Quick Connect (A size Mini, 4-pin male termination) 316L SST
Code
Seal System Type
1
Direct-mount diaphragm seal system
Code
High Pressure Side Extension (between transmitter flange and seal)
0
Direct-mount (No extension)
Code
Low Pressure Side Connection (sensor module)
1
One capillary connection remote diaphragm seal (see Rosemount 1199 ordering table for seal information)
2
316L SST isolator / 316 SST transmitter flange
3
Hastelloy C-276 isolator / 316 SST transmitter flange
Code
Capillary Length
0
N/A
Code
Diaphragm Seal Fill Fluid
A
Syltherm XLT
C
D. C. Silicone 704
D
D. C. Silicone 200
H
Inert (Halocarbon)
G
Glycerine and Water
N
Neobee M-20
P
Propylene Glycol and Water
Next, select either Flush Flanged (FF) diaphragm seal (see page A-21) or Extended Flanged (EF) diaphragm seal (see page A-22).
A-20
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Seal Options (page A-21—A-22)
Flush Flanged Seal
Code(1) (2) Process Connection Style
(3) (4)
FF
Code(5)
Flush Flanged, Ra 125-250 gasket surface
Diaphragm Seal Size (High Side)
G
7
J
9
Code
2-in./DN 50
3-in.
DN 80
4-in./DN 100
Flange Rating (High Side)
1
2
4
G
E
Code
Class 150
Class 300
Class 600
PN 40
PN 10/16; available with 4 in. DN 100 only
Isolator Material (6)
Flange Material (High Side)(7)(8)
CA
DA
CB
DB
CC
DC
Code
316L SST
CS
316L SST
316 SST
Hastelloy
CS
Hastelloy
316 SST
Tantalum - seam welded(8)(9)
CS
Tantalum - seam welded(9)
316 SST
Lower Housing Material (High Side)(10)
0
A
B
Code
None
316 SST
Hastelloy
Flushing Connection Quantity and Size (Lower Housing, High Side)
0
1
3
7
9
Code
None
1 (1/4-in.)
2 (1/4-in.)
1 (1/2-in.)
2 (1/2-in.)
Seal Options: Gaskets
SJ
SK
SN
Code
Teflon® (PTFE) gasket for lower housing
Gylon gasket for lower housing
Grafoil™ gasket for lower housing
Other Options
ST(11)
Materials per NACE MR0175
Continue with transmitter options on page A-22
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Not available with output codes B and X.
For spare SuperModule Platforms, select output code A.
Requires PlantWeb housing and Hardware Adjustments option code D1. For the 3051S SIS Safety Transmitter, rangedown is limited to 10:1.
Requires PlantWeb housing.
Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5) and CSA Intrinsically Safe (option code I6).
Material specified is cast as follows: CF-3M is the cast version of 316L SST. For housing, material is aluminum with polyurethane paint.
Available with output code A only. Not available with approvals. See Rosemount 753R Product Data Sheet, 00813-0100-4379, to specify Web-Based
Monitoring Indicator. Does not integrate into plant host systems.
(8) Available with output code A only. Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5), ATEX Intrinsically Safe (option code I1), or
IECEx Intrinsically Safe (option code I7). Contact an Emerson Process Management representative for additional information.
(9) Not recommended for use with spiral wound metallic gaskets (see 1199 product data sheet, document 00813-0100-4016 for additional options).
(10) Standard gasket for lower housing consists of non-asbestos fiber.
(11) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining
environments.
A-21
Reference Manual
Rosemount 3051S Wireless Series
00809-0100-4802, Rev BA
August 2007
Extended Flanged Seal
Code
Process Connection Style
EF
Code
Extended flanged, Ra 125-250 gasket surface
Diaphragm Seal Size (High Side)
7
9
Code
3-in./DN 80, 2.58-in. diaphragm
4-in./DN 100, 3.5-in. diaphragm
Flange Rating (High Side)
1
2
4
G
E
Code
Class 150
Class 300
Class 600
PN 40
PN 10/16; available with 4 in. DN 100 only
Isolator Material and Extension Material
CA
DA
CB
DB
Code
316L SST
316L SST
Hastelloy
Hastelloy
Extension Length (High Side, 1st Position)
2
4
6
Code
2-in./50 mm
4-in./100 mm
6-in./150 mm
Extension Length (High Side, 2nd Position)
0
0-in./0 mm
Flange Material (High Side)
CS
316 SST
CS
316 SST
Continue with transmitter options below
Transmitter Options continued from page A-20
(— = Not Applicable
Code
• = Applicable)
Options
PlantWeb Control Functionality
A01(1)
FOUNDATION fieldbus Advanced Control Function Block Suite
PlantWeb Diagnostic Functionality
D01(1)
FOUNDATION fieldbus Diagnostics Suite
DA1(2)
HART Diagnostics Suite
PlantWeb Enhanced Measurement Functionality
H01(1)(3) Fully Compensated Mass Flow Block
Code
Wireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WA
User Configurable Transmit Rate
Operating Frequency and Protocol
1
2.4 GHz DSSS, HART
2
900 MHz FHSS, HART
Antenna
WK
Integral, Omnidirectional Antenna
SmartPower™
1
Code
Long-life battery pack
NOTE: Battery must be shipped separately, order Part No. 00753-9220-0001.
Options
Special Configuration (Software)
C1(4)
Custom software configuration
Note: A Configuration Data Sheet must be completed.
C3
Gage pressure calibration on Rosemount 3051S_LA only
C4(4)(5)
NAMUR alarm and saturation levels, high alarm
C5(4)(5)
NAMUR alarm and saturation levels, low alarm
C6(4)(6)
Custom alarm and saturation signal levels, high alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
A-22
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
C7(4)(6)
Custom alarm and saturation signal levels, low alarm
Note: Requires option code C1, custom software configuration. A Configuration Data Sheet must be completed.
C8(4)(5)
Low alarm (standard Rosemount alarm and saturation levels)
Special Configuration (hardware)
LD LG LA
D1(5)
Hardware adjustments (zero, span, alarm, security)
•
•
•
Note: Not available with fieldbus protocol or Housing Style codes 00, 01, 2E, 2F, 2G, 2M, 5A, or 7J.
D2
1/2-14 NPT process connections process adapters
•
— —
D4
External ground screw assembly
•
•
•
D5
Delete transmitter drain/vent valves (install plugs)
•
— —
D8
Ceramic drain/vent valves
•
— —
D9
RC 1/2 process connections (process adapters)
•
— —
Product Certifications(7)
E1
ATEX Flameproof
I1
ATEX Intrinsically Safe
IA
ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
N1
ATEX Type n
K1
ATEX Flameproof, Intrinsically Safe, Type n, Dust (combination of E1, I1, N1, and ND)
ND
ATEX Dust
E4
JIS Flameproof
E5
FM Explosion-proof
I5
FM Intrinsically Safe, Non-Incendive
IE
FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K5
FM Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5 and I5)
E6
CSA Explosion-proof, Division 2
I6
CSA Intrinsically Safe
IF
CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
K6
CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
D3(8)(9)
Measurement Canada Accuracy Approval
E7
SAA Flameproof, Dust Ignition-proof
I7
IECEx Intrinsically Safe
IG
IECEx FISCO Intrinsically Safe
N7
IECEx Type n
K7
SAA Flameproof, Dust Ignition-proof, IECEx Intrinsically Safe, and Type n (combination of E7, I7, and N7)
KA
ATEX and CSA Flameproof, Intrinsically Safe (combination of E1, I1, E6, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KB
FM and CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KC
FM and ATEX Explosion-proof, Intrinsically Safe, Non-Incendive (combination of E5, E1, I5, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
KD
FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Note: Only available on Housing Style codes 00, IA, IJ, 2A, 2J, 2E, or 2M.
Alternate Materials of Construction
L1
Inert sensor fill fluid (differential and gage only)
Note: Silicone fill fluid is standard.
L2
Graphite-filled TFE o-ring
L4
Austenitic 316 SST bolts
L5
ASTM A 193, Grade B7M bolts
L6
Monel bolts
L7
ASTM A 453, Class A, Grade 660 bolts
L8
ASTM A 193, Class 2, Grade B8M bolts
Digital Display(10)
M5
PlantWeb LCD Display
M7(6)(11)
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Note: Use Belden 3084A cable or equivalent. Contact an Emerson Process Management representative for additional information.
M8(6)(11)
Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
M9(6)(11)
Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Special Procedures
P1
Hydrostatic testing with certificate
P2
Cleaning for special services
P3
Cleaning for less than 1PPM chlorine/fluorine
Special Certifications
Q4
Calibration certificate
A-23
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
QP
Calibration certificate and tamper evident seal
Q8(5)
Material traceability certification per EN 10204 3.1.B
QS(5)(12) Certificate of FMEDA Data
Terminal blocks
T1(13)
Transient terminal block
T2(14)
Terminal block with WAGO® spring clamp terminals
T3(14)
Transient terminal block with WAGO spring clamp terminals
Conduit Electrical Connector
GE(15)
M12, 4-pin, Male Connector (eurofast®)
GM(15)
A size Mini, 4-pin, Male Connector (minifast®)
Typical Model Number for FF seal: 3051S2LD 2A A 1A 1 0
2 0
D
FF
7
1
DA
0
0
Typical Model Number for EF seal:
2 0
D
EF
7
1
DA
2
0
3051S2LD
2A
A
1A
1
0
(1) Requires PlantWeb housing and output code F.
(2) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard.
(3) Requires Rosemount Engineering Assistant to configure.
(4) Not available with output code F or Housing code 01.
(5) Not available with output code X.
(6) Not available with output codes B and X.
(7) Valid when SuperModule Platform and housing have equivalent approvals.
(8) Requires PlantWeb Housing and Hardware Adjustments option code D1.
(9) Limited availability depending on transmitter type and range. Contact a sales representative for additional information.
(10) Not available with Housing Code 01 or 7J.
(11) Not available with output code F, Housing code 01, or option code DA1.
(12) Not available with Housing Code 01.
(13) Not available with Housing code 00, 01, 5A, or 7J.
(14) Available with output code A and PlantWeb housing only.
(15) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Non-Incendive approval (option
code I5) or FM FISCO Intrinsically Safe approval (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating
(NEMA 4X and IP66).
A-24
Reference Manual
00809-0100-4802, Rev BA
August 2007
Appendix B
Rosemount 3051S Wireless Series
Product Certifications
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page B-1
Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . page B-1
FCC and IC Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-1
Ordinary Location Certification for FM . . . . . . . . . . . . . . . page B-1
European Directive Information . . . . . . . . . . . . . . . . . . . . page B-2
Hazardous Locations Certifications . . . . . . . . . . . . . . . . . page B-2
European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-3
IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-3
WIRELESS
CERTIFICATIONS
Approved Manufacturing
Locations
Rosemount Inc. — Chanhassen, Minnesota USA
Emerson Process Management GmbH & Co. — Wessling, Germany
Emerson Process Management Asia Pacific Private Limited — Singapore
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China
Telecommunication
Compliance
All wireless devices require certification to ensure that they adhere to
regulations regarding the use of the RF spectrum. Nearly every country requires
this type of product certification. Emerson is working with governmental
agencies around the world to supply fully compliant products and remove the
risk of violating country directives or laws governing wireless device usage. To
see which countries our devices have received certification for use in, see
www.rosemount.com/smartwireless.
FCC and IC Approvals
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference this
device must accept any interference received, including interference that may
cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance
of 20cm from all persons.
Ordinary Location
Certification for FM
www.rosemount.com
As standard, the transmitter has been examined and tested to determine that
the design meets basic electrical, mechanical, and fire protection requirements
by FM, a nationally recognized testing laboratory (NRTL) as accredited by the
Federal Occupational Safety and Health Administration (OSHA).
Reference Manual
Rosemount 3051S Wireless Series
European Directive
Information
00809-0100-4802, Rev BA
August 2007
The EC declaration of conformity for all applicable European directives for this
product can be found at www.rosemount.com. A hard copy may be obtained by
contacting an Emerson Process Management representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option)
Pressure Transmitters — QS Certificate of Assessment EC No. PED-H-100, Module H Conformity Assessment
All other Model 3051S Pressure Transmitters
— Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange Manifold — Sound Engineering Practice
Primary Elements, Flowmeter
— See appropriate Primary Element QIG
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All Models: EN 50081-1: 1992; EN 50082-2:1995;
EN 61326-1:1997 + A1, A2, and A3 – Industrial
Radio and Telecommunications Terminal Equipment Directive
(R&TTE)(1999/5/EC)
Emerson Process Management complies with the R&TTE Directive.
Hazardous Locations
Certifications
North American Certifications
Factory Mutual (FM) Approvals
I5
FM Intrinsic Safety, Non-Incendive, and Dust Ignition-proof.
Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G.
Zone Marking: Class I, Zone 0, AEx ia llC
Temperature Codes T4 (Tamb = -50 to 70° C)
Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II/III, Division 1, Groups E, F, and G.
Ambient temperature limits: -50 to 85° C
For use with Rosemount battery pack P/N 00753-9220-XXXX only.
Enclosure Type 4X / IP66
CSA - Canadian Standards Association
I6
B-2
CSA Intrinsic Safety
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Temp Code T3C
Enclosure Type 4X / IP66
For use with Rosemount battery pack P/N 00753-9220-XXXX only.
Reference Manual
00809-0100-4802, Rev BA
August 2007
European Certifications
Rosemount 3051S Wireless Series
I1
ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X
II 1G
Ex ia IIC T4 (Ta = -60 °C to 70 °C)
For use with Rosemount Battery P/N 00753-9220-XXXX only
IP66
1180
Country
Restriction
Bulgaria
France
Italy
Norway
General authorization required for outdoor use and public service
Outdoor use limited to 10mW e.i.r.p.
If used outside of own premises, general authorization is required.
May be restricted in the geographical area within a radius of 20 km from
the center of Ny-Alesund.
Use on a secondary basis. Individual license required.
Romania
Radio Power Label (See Figure 1) indicates
output power configuration of the radio.
Devices with this label are configured for
output power less than 10 mW e.i.r.p. At time
of purchase the customer must specify
ultimate country of installation and operation.
IECEx Certifications
I7
Figure 1.
Radio Power Label
IECEx Intrinsic Safety
Certificate No.: IECEx BAS 04.0017X
Ex ia IIC T4 (Ta = -60 °C to 70 °C)
For use with Rosemount Battery P/N 00753-9220-XXXX only
IP66
B-3
Reference Manual
Rosemount 3051S Wireless Series
B-4
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
NOTES
B-3
Reference Manual
Rosemount 3051S Wireless Series
NOTES
B-4
00809-0100-4802, Rev BA
August 2007
Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
SuperModule and Coplanar trademarks of Rosemount Inc.
PlantWeb is a mark of one of the Emerson Process Management companies.
HART is a registered trademark of the HART Communications Foundation.
Hastelloy C and Hastelloy C-276 are registered trademarks of Cabot Corp.
Monel is a registered trademark of International Nickel Co.
Syltherm and D.C. are registered trademarks of Dow Corning Co.
Neobee M-20 is a registered trademark of Stephan Chemical Co.
The 3-A symbol is a registered trademark of the 3-A Sanitary Standards Symbol Council.
FOUNDATION fieldbus is a registered trademark of the Fieldbus Foundation.
Teflon is a registered trademark of E.I. du Pont de Nemours & Co.
Grafoil is a trademark of Union Carbide Corp.
All other marks are the property of their respective owners.
Cover Photo: 3051\WIRELESS\3051S_WIRELESS
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (U.S.) 1 800 999 9307
T (International) (952) 906 8888
F (952) 949 7001
www.rosemount.com
Emerson Process Management
Heath Place
Bognor Regis
West Sussex PO22 9SH
England
Tel 44 (1243) 863 121
Fax 44 (1243) 867 554
¢00809-0100-4801V¤
© 2007 Rosemount Inc. All rights reserved.
Emerson Process Management Asia
Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947
[email protected]
Beijing Rosemount Far East
Instrument Co., Limited
No. 6 North Street,
Hepingli, Dong Cheng District
Beijing 100013, China
T (86) (10) 6428 2233
F (86) (10) 6422 8586
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement