Toshiba Mount-Anywhere Series Wafer

Field Intelligent Device – Mount-Anywhere Series - Wafer
Electromagnetic Flowmeter
LF414 /LF610
LF414 /LF612
1/2" to 8" (15 to 200 mm)
Introduction
The electromagnetic flowmeter uses Faraday’s Law of electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through which the fluid to be measured flows and in which low-level signals proportional to flow rates are obtained; and a converter, which supplies excitation current to the detector, and amplifies the signals from the detector and then processes and converts the signals into the 4–20mAdc current signal or communication signal. With the unique patented Mount- Anywhere magnetic field distribution technology, the meter is highly immune to upstream flow disturbances.
Combined with a multi-functional converter LF610
(combined type) or LF612 (separate type) equipped with its patented Noise-Sentry original noise- suppression circuit and advanced algorithms. The
LF410 has a very high tolerance to noise, giving the unit a very stable output even for slurry fluid measurement. IR (Infrared) switches enable parameter setting of the converter without removing the cover.
Flow direction can be set in either way, and its unique
128 x 128 dot matrix LCD display allows the LCD to be rotated electronically to 90, 180 and 270 degrees without opening the cover.
The AF900 hand-held terminal (HART*
1 communicator) can be used to communicate with the flowmeter from a remote place. PROFIBUS-PA*
2 interface is available as an option.
*1: HART protocol (Highway Addressable Remote
Transducer) is a communication protocol for industrial sensors recommended by the HCF (HART
Communication Foundation).
*2: PROFIBUS is the communication protocol for factory and process automation that the PROFIBUS
Organization recommends. Instead of analog control with a conventional analog signal (4-20mA), it is fieldbus which digitizes all signals. Flowmeters support
PROFIBUS-PA.
I/O
Converter
Converter
Signal cable
Terminal box
Power supply
Power supply
Detector
Detector
I/O
LF410/LF610
LF414/LF610F
LF410 LF612
LF414 LF612F
Figure2. LF410 Mount-Anywhere series
Flowmeters
Specifications
Overall Specifications
Certification number
Z01207
Fluid conductivity: 5µS/cm minimum
Fluid temperature:
14 to 356
°F (–10 to +180°C) : Ceramic type
Note : 248
°F (120°C) above is separate type
14 to 248
°F (–10 to +120°C) : Teflon PFA
Combined type
LF410/LF610
LF414/LF610F
Separate type
LF410/LF612
LF414/LF612F
Measurement range in terms of flow velocity:
0 –1.0
ft/s to 0 – 32.8
ft/s (0 – 0.3
m/s to 0 –10 m/s).
0 – 0.3
ft/s to 0 – 1.0
ft/s (0 – 0.1
m/s to 0 – 0.3
m/s) range is available optionally.
Accuracy:
±0.2 % of Rate
*
* This pulse output error result is established under standard operating conditions at Toshiba's flow calibration facility,
Fuchu Japan. (NIST Traceable).
* Individual meter measurement error may vary up to ±0.5% of
Rate at 1.64ft/s (0.5m/s) or more and ±0.3% of rate ±0.039 inch/s (1mm/s) at 1.64 ft/s (0.5 m/s) or less.
* Current output: plus ± 8µA (0.05% of span.)
* Refer to individual calibration data for each individual meter's measurement error.
Ambient temperature: -4 to 140 °F (-20 to + 60 °C)
Figure1. Configuration
Structure: IP 67 and NEMA 4X Watertight
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Power consumption:
17W(27VA) or less
19W(29VA) or less (with PROFIBUS)
Conformance to European Community Directives:
EMC directive 89/336/EEC
The low voltage 93/68/EEC
PED 97/23/EC (Note 1)
Note : See Table 1 for detail.
Approved hazardous location certifications:
Model: LF414/LF610F and LF414/LF612F cFMus explosion proof:
FM Class I, Division 2, Groups A,B,C, and D.
FM Class II, Division 2, Groups E, F and G.
FM Class III.
Detector and converter combination:
LF410/LF610: Combined type for standard specification.
LF410/LF612: Separate type for standard specification.
LF414/LF610F: Combined type with Ex approval of Class I, Division 2 (cFMus).
LF414/LF612F: Separate type with Ex approval of
Class I, Division 2 (cFMus).
Mount-Anywhere
Technology:
With TOSHIBA’s unique patented magnetic field distribution technology, the meter is highly immune to upstream flow disturbances.
A minimum of 1D (one diameter) length of upstream straight pipe from the flange is required to maintain the performance specification.
Note : The test results were obtained and demonstrated at
TOSHIBA's flow calibration facility, Fuchu Japan.
Model LF410 and LF414 Detectors
Mounting style: Wafer type
Fluid pressure:
-15 to 300psi, or -1.0 to 20 bar (-0.1 to 2.0MPa)
Note: The test pressure before shipping from the factory is equal to twice the nominal pressure rating of the customer specified flange connection during 15 minutes.
Connection flange standards:
ANSI 150, ANSI 300, BS10, BS16, DIN PN10,
DIN PN16, JIS10K, JIS16K, JIS20K
Principal materials:
Case —
1” to 4” (25 to 100mm): stainless steel
1/2”, 6”, and 8” (15, 150, 200mm): carbon steel
Linings —
1/2” to 4” (15 to 100mm):
Ceramic tube (std.) & Teflon PFA (opt.)
6” to 8” (150 and 200mm): Teflon PFA
Electrodes —
Type-Super smooth, polished with self cleaning finish, and non stick shape
316 stainless steel (std.)
Hastelloy C equivalent (std.) (in case of Teflon
PFA lining)
Note: Electrodes are electro-chemically polished after mechanically buffed.
Grounding rings — 316 stainless steel (std.)
Note: See Table 6 for optional materials and other related information.
Measuring tube material — 304 stainless steel (in case of Teflon PFA lining)
Coating —
1” to 4” (25 to 100mm):
No coating (stainless steel body).
1/2”, 6”, and 8” (15, 150, 200mm):
Corrosion resistant phthalic acid resin coating with pearl-gray colored.
Heat shock resistance: for a ceramic tube detector
Heating:
ΔT ≤ 302
°
F/0.5sec (150
°
C/0.5sec)
Cooling:
ΔT ≤ 212
°
F/0.5sec (100
°
C/0.5sec)
Note: The above means that the ceramic tube detector withstands the shock of sudden heating
(temperature difference 150
°C or less per
0.5seconds) and sudden cooling (temperature difference 100
°C or less per 0.5seconds).
Dimensions and weights: See Figures 3 to 8.
Cable connection port: for separate type detectors.
Cable glands —
LF410 (without cFMus approval):
Provided as standard, R(PT) 1/2 male screws.
LF414 (with cFMus approval):
Not provided, 3/4-14NPT male screws are required.
Applicable diameter —
0.433 to 0.512 inch (11 to 13mm)
Model LF610 and LF612 converters
Input signals
Analog signal — the voltage signal from detector, proportional to process flow rate (for LF612 separate type converter).
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
Digital input DI (opt.)
Signal type: 20 to 30Vdc voltage signal
Input resistance: 2.7k
Ω
Number of inputs: one point
DI function — One of the following functions can be assigned to the optional DI signal.
Range switching — Selects either the higher or lower range in the unidirectional or bidirectional
2-range setting.
Totalizer control — Starts and stops the built-in totalizer.
Fixed-value outputs —Outputs fixed-values for current and pulse outputs.
Zero adjustment — Executes zero adjustment
(on-stream at zero flow rate).
Output signals
Current output:
4–20mAdc (load resistance 0 to 750
Ω)
Note: The current output cannot be used with the
PROFIBUS-PA communication.
Digital outputs — One point (std.) and one more point is optionally available as follows.
Digital output DO1 (std.):
Output type: Transistor open collector
Number of outputs: One point
Output capacity: 30Vdc, 200mA maximum
Digital output DO2 (opt.):
Output type:
Solid-state relay output (non polarity)
Number of outputs: One point
Output capacity: 150Vdc, 150mA maximum or 150Vac (peak to peak), 100mA maximum
DO1 and DO2 functions — One of the following functions can be assigned to DO1 (std.) and/or
DO2 (opt.)
• Pulse output (available only for DO1, DO2)
Pulse rate: 3.6 to 36,000,000 pulses/hr (DO1)
3.6 to 360,000 pulses/hr (DO2)
(Over 3,600,000 pulses/hr, auto-setting)
Pulse width: 0.5 to 500ms (but less than half of the period for 100% flow rate)
Note: The same and simultaneous pulse is not available between DO1 and DO2.)
• Multi-range selection outputs (Note 1)
• High, High high, Low, and/or Low low alarm
outputs (Note 2)
• Empty pipe alarm output
• Digital Output Active Status (DO1 and DO2)
(Note 2)
• Preset count output
• Converter failure alarm output
TIC-LF414C
Note 1: Two outputs (DO1 and DO2) are needed for
4-range switching and forward/reverse 2-range switching.
Note 2: Normal Open (default set) or Normal Close is selected for alarm outputs when programming.
When power failure occurs, unit will be fault to
Normal Open.
Communications output:
• HART (std.) — Digital signal is superimposed on
4–20mAdc current signal as follows:
Conforms to HART protocol
Load resistance: 240 to 750
Ω
Load capacitance: 0.25µF maximum
Load inductance: 4mH maximum
• PROFIBUS (opt.)
Protocol: PROFIBUS-PA
Baud rate: 31.25kbps
Bus voltage: 9-30VDC
Consumption electric current of bus: less than 16mA
Manufacture Ident-No.: 093B
HEX
Standard Ident-No.: 9740
HEX
Slave address: 0-126 (Default address is 126)
Profile: Profile Ver.3.01 for Process Control
Devices
Function blocks: AI(Flow)×1 , Totalizer×1
LCD display:
Full dot-matrix 128×128 dot LCD display
(back–light provided)
The data on the LCD inside the converter can rotate to 90, 180, and 270 degrees by a software, without rotating the indicator itself. (Combined type only)
Parameter settings — Parameters can be set as follows:
• IR Switches: Three key switches are provided to set configuration parameters.
• Digital communication: The AF900 hand-held
terminal or PROFIBUS is needed to set parameters.
• Zero adjustment: Zero point adjustment can be started by pressing the switch in the converter.
• Damping: 0.5 to 60 seconds (selectable in one second increments)
“Field re-verification”
Mag-Prover
– Toshiba’s
Zero span calibration tool allows unit to be re-calibrated and verified using an internal software program (For more information contact
Toshiba International Corp.)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Conditions when power fails:
Parameter setting values are stored in non–volatile memory and the values will be restored when the power returns to normal condition. The outputs and display will remain as follows when power fails.
• Current output: 0mAdc
• Digital output: OFF
• LCD display: No display
• PROFIBUS: No communication
Power supply:
One of the following can be selected:
• 100 to 240Vac, 50/60Hz (std.)
(allowable voltage 80 to 264Vac)
• 24Vdc (allowable voltage 18 to 36Vdc)
• 110Vdc (allowable voltage 90 to 130Vdc)
Surge protection:
Arresters are installed in the power supply and a current signal output circuit to help protect the meter from lightning and improve personnel safety.
Case: Aluminum alloy (equal to IP67)
Coating: Acrylic resin-baked coating, pearl–gray colored
Cable connection port:
Cable glands —
LF610 and LF612 without cFMus Approval:
Provided as standard, OD of cableφ11~13mm
Material Nylon 66
G (PF) 1/2 male screws.
LF610F and LF612F with cFMus Approval:
Not provided, 1/2–14NPT male screws are required.
Applicable diameter —
0.433 to 0.512 inch (11 to 13mm)
Note: When PROFIBUS option is specified, cable gland size is
φ6~8mm for signal cable, φ11~13mm for power cable
Vibration resistance:
No resonance to the following levels of vibration:
• 10 to 150Hz with acceleration of 9.8m/s
2
• Vibration of 30Hz with 29.4 m/s
2
in 4h in each direction will not cause any defect to unit.
Note: Avoid using the flowmeter in an environment with constant vibration.
Dimensions and Weights:
See Figure 9 (for Separate type)
MTBF:
Converter: 220,000 hours (25 years) at 77 °F (25 °C) based on strict military specification
MIL-HDBK-217F
Detector: 350,000 hours (40 years) at 77 °F (25 °C) based on strict military specification
MIL-HDBK-217F
PED matrix in each flange connection.
The following sizes fall under the category for PED in each flange connection when the meter ships to
EU. All of them had complied with it from a notified body.
Table 1. PED matrix in each flange connection
Flange standard
DIN PN 16 and BS 16
DIN PN 10 and BS 10
ANSI 150 and JIS10K
Meter size
6 to 16 inch
(150 to 400mm)
10 to 16 inch
(250 to 400mm)
6 to 16 inch
(150 to 400mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
Installation
Dimensions
8.86(225)
5.16(131)
1.42(36)
Unit : inch( mm)
5.63(143)
TIC-LF414C
Unit : inch( mm)
8.86(225)
1.42(36)
5.63(143)
5.16(131)
2.52(64)
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
L1
Weight
(lb)
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
3.43(87) L1
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lb)
1 3.15 9.48 2.60 11
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
Note: 1 inch = 25.4mm
Note: 1 inch = 25.4mm
Figure 3. LF410/LF610 and LF414/LF610F flowmeters
Meter size 1/2"(15mm)
Figure 4. LF410/LF610 and LF414/LF610F flowmeters
Meter size 1"(25mm)
The dimension of L1 is changed when the material of grounding ring is chosen Pt-Ir or Ta.
Meter size L1
1 1/2”(40mm) 4.53 inch(115mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
8.86(225)
5.16(131)
1.42(36)
Unit : inch(mm)
5.63(143)
ANSI class 150 and class 300 dimensions
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lbs)
BS16, DIN PN16 and JIS 10K dimensions
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
L1
Note1: Eye bolts are provided at the top for flowmeters sized 8"(200mm).
Note2: 1 inch = 25.4mm
*When Teflon PFA lining is selected, L1 in the table above becomes as follows:
L1: 4.53 inch(115mm) for meter size 3"(80mm)
L1: 4.96 inch(126mm) for meter size 4"(100mm)
The dimension of L1 is changed when the material of grounding ring is chosen Pt-Ir or Ta
Meter size L1
1 1/2”(40mm) 4.53 inch(115mm)
Figure 5. LF410/LF610 and LF414/LF610F flowmeters
Meter sizes 1 1/2"(40mm) to 8"(200mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
3.46(88)
1.57(40)
Unit : inch(mm)
R (PT)1/2Male Screw (Two Places)
4.96(126)
1.38(35)
3.58(91)
TIC-LF414C
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lb)
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
The dimension of L1 is changed when the material of grounding ring is chosen Pt-Ir or Ta
Meter size L1
2.52(64)
L1
1 1/2”(40mm)
Note1: Cable glands are not provided for LF414 of FM and
CSA approved type.
Refer to the part of Cable connection port at detector.
Note2: 1 inch = 25.4mm
Figure 6. Separate type detectors LF410/LF414
Meter sizes 1/2" (15mm)
4.53 inch(15mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
3.46(88)
1.57(40)
Unit : inch(mm)
R(PT)½ Male Screw (Two places)
4.96(126)
1.38(35) 3.58(91)
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lb)
1 3.15 6.61 2.60 approx.
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
The dimension of L1 is changed when the material of grounding ring is chosen Pt-Ir or Ta
Meter size L1
3.43(87) L1
1 1/2”(40mm)
Note1: Cable glands are not provided for LF414 of FM and
CSA approved type.
Refer to the part Cable connection port at detector.
Note2: 1 inch = 25.4mm
Figure 7. Separate type detectors LF410/LF414
Meter sizes 1" (25mm)
4.53 inch(115mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
Unit : inch(mm)
3.46(88)
R(PT)½Male Screw (Two places)
4.96(126)
1.57(40)
1. 38(35) 3.58(91)
TIC-LF414C
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lbs)
2 4.33 8.15 4.02 11
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
L1
Note1: Cable glands are not provided for LF414 of FM and
CSA approved type.
Refer to the part of Cable connection port at detector.
Note2: Eye bolts are provided at the top for flowmeters sized 8"(200mm).
Note3: 1 inch = 25.4mm
* When Teflon PFA lining is selected, L1 in the table above becomes as follows:
L1: 4.53 inch(115mm) for meter size 3"(80mm)
L1: 4.96 inch(126mm) for meter size 4"(100mm)
The dimension of L1 is changed when the material of grounding ring is chosen Pt-Ir or Ta
Meter size L1
1 1/2”(40mm) 4.53 inch(115mm)
Figure 8. Separate type detectors LF410/LF414
Meter sizes 1 1/2"(40mm) to 8"(200mm)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
4 –
φ 0.43(φ 11)
0.98(25)
3.23(82)
0.51(13)
Unit : inch(mm)
Weight: Approx. 7 lb (3.5 kg)
矢視
A
取付金具
グ ラ ン ド
矢視
A
Note: Cable glands are not provided for LF612F cFMus approved type.
Refer to the part Cable connection port at detector.
( 単位:mm)
Note: 1 inch = 25.4 mm
Figure 9. Separate type converter LF612 and LF612F
External Connections
Combined type LF410/LF610 and LF414/LF610F flowmeters
I/O Cable (CVV-S)
Ground terminal
Intermediate voltage (IV) wire,
5.5mm
2
or more.
To be grounded with 100
Ω or less ground resistance.
Instrument Panel : Ordered separately
Current output
(4~20mAdc) or
PROFIBUS
Digital Output 1
Signal common for DI and DO
Digital Output 2
Digital Input
(20 to 30Vdc)
Grounded with
100
Ω or less ground resistance
Grounded with
100
Ω or less ground resistance
Power supply
Power Cable (CVV)
Power Switch*
1
(External double-pole power switch)
*1 Locate an external double-pole power switch on the power line near the flowmeter within easy reach of operation.
Use the appropriate switch rating as shown below:
Switch rating: 250Vac, 6A or more
In rush current: 15A or more
Figure 10. Combined type LF410/LF610 and LF414/LF610F flowmeters Wiring Diagram
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
・Separate type LF410/LF612 and LF414/LF612F flowmeters
Terminal board
Thick walled steel conduit
IV wire
5.5 mm
2
or more
Grounded with 100Ω or less ground resistance
Signal cable
(2-wire shielded hard-rubber sheathed cable)
Power switch
(External double-pole power switch )
[Instrument panel : ordered separately]
Grounded with 100Ω or less ground resistance
Power supply
Current output (4~20mAdc) or PROFIBUS
Digital output 1
Signal common for DI and DO
Connected detector
Excitation cable
(3-wire hard-rubber cable)
Digital output 2
Digital input
(20~30Vdc)
Power cable
(CVV)
Digital input cable
(CVV-S)
Grounded with 100Ω or less ground resistance
Figure 11. Separate type LF410/LF612 and LF414/LF612F flowmeters wiring Diagram
Table 2. LF610, LF610F, LF612 and LF612F Converters Signal Table
Symbol Description
L1 (+)
L2 (-)
GND
Power supply
Ground (for arrester)
Cable
Power cable (CVV)
DI
DO1
Digital Input (20~30Vdc)
Digital Output 1
DO2 Digital Output 2
COM Signal Common for DI, DO1, DO2
+
Current Output (4~20mAdc) or PROFIBUS
-
I/O cable (CVV-S)
Shielded cable for
PROFIBUS-PA
X
Excitation cable
E
A
Signal cable
G
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Wiring Precautions
(1) Explosion proof type flowmeters are not provided cable glands.
Refer to the part Cable connection port at detector and converter.
(2) Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100
Ω or less ground resistance). Make the wire as short as possible. Do not use a common ground shared with other equipment where earth current may flow. An independent earth ground is recommended.
(3) The allowable cable lengths between the detector and converter for the separate type flowmeter depend on the electrical conductivity of the object fluid. See Figure 12.
(4) DO1, DO2 (opt.), and DI (opt.) use the same common terminal (COM). This COM can not connect to other equipments which have their own ground terminal.
(Power supply for connecting to DI or DO, etc…)
Need to wire separately.
Wiring Precautions (PROFIBUS)
(1) For wiring path, avoid places near electrical equipment that may cause electromagnetic induction or electrostatic induction interference
(such as a motor, transformer and wireless transmitter).
(2) Use a PROFIBUS-PA cable for signal cable. In addition, make sure to use a shielded cable to improve noise resistance. Furthermore, installation of signal cable in metal conduit is recommended.
(3) General PROFIBUS-PA cables are designed for indoor use where cables are not exposed to humidity, rain, etc. When you install cables, make sure to check the operating conditions such as the operating temperature range of the cable by contacting its manufacturer.
(4) When you carry out cable end treatment of
PROFIBUS-PA cable, use a dedicated cable stripper etc. so that the core wire of the cable will not be nicked or damaged. In addition, for cables, be careful of allowable maximum bend diameter etc. (Basically, do not install cables in a way cables are twisted or bent.).
(5) Consider installing a PROFIBUS-PA arrester in the communication path of PROFBUS-PA so that the electromagnetic flowmeter will not be affected by lightning etc.
(6) The electromagnetic flowmeter is not equipped with terminating resistors. Use the terminating resistor unit for PROFIBUS-PA or junction box, if necessary.
(7) Only one PROFIBUS-PA cable goes through a cable gland of the Electromagnetic Flowmeter.
Please use the junction box at system configuration
.
300
200
100
50
30
10
5
3
3 5 10 20 30 50 100 200
Conductivity (
μS/cm)
Figure 12. Electrical Conductivity and
Cable Length
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Meter Size
To select the meter size:
See Table 3 to 4 and find meter sizes within the velocity of 0.3 to 32.8 ft/s (0.1
to 10m/s) for a specified full-scale (measuring range high limit) flow. Select one that has its full-scale velocity between 3.0 and 10 ft/s (1 and 3m/s).
Note: Make sure the full-scale flow rate used for the final planning stage stays within 32.8 ft/s
(10m/s) in terms of flow velocity.
Table 3. Flow rate and flow velocity (English unit)
Unit: gal/min
Size Flow rate
(inch) 0.328 ft/s 0.98 ft/s
3.0 ft/s 10 ft/s 32.8 ft/s
1/2 0.2801 0.8403 2.561 8.532
28.01
1
1 ½
2
3
4
6
8
0.7781
1.992
3.112
7.967
12.45
28.01
49.80
2.334 7.115 23.72
5.975 18.21 60.71
9.337 28.46 94.86
23.90 72.85 242.8
37.35 113.8 379.4
84.03 256.1 853.8
149.4 455.3 1,518
77.81
199.2
311.2
796.7
1,245
2,801
4,980
Table 4. Flow rate and flow velocity (SI unit)
Unit: m
3
/h
Size
Flow rate
(mm) 0.1 m/s 0.3 m/s 1.0 m/s 3.0 m/s 10 m/s
15 0.06362 0.1908 0.6361 1.908
25
40
0.1767
0.4523
0.5301
1.357
1.767
4.523
5.301
13.57
50
80
100
150
200
0.7067
1.809
2.827
6.361
11.31
2.120
5.428
8.482
19.08
33.93
7.067
18.09
28.27
63.61
113.1
21.20
54.28
84.82
190.8
229.3
6.361
17.67
45.23
70.67
180.9
282.7
636.1
1,131
Calibration Range
If the calibration range is not specified, the standard range as shown below will be used. If the range is specified, we will use the specified range for calibration.
Table 5. Standard Flow Range
Meter size inch(mm)
1/2 (15)
1 (25)
1 1/2 (40)
2 (50)
3 (80)
4 (100)
6 (150)
8 (200)
Standard flow range
Flow rate
(gal/min)
Flow rate
(m³/h)
Flow velocity
(m/s)
25
75
175
300
650
1,000
2,500
4,500
2
6
15
25
60
100
200
300
3.144
3.395
3.316
3.537
3.316
3.537
3.144
2.653
Note: The unit of "gal/min" is not exchanged
(converted) by "m
3
/h".
About establishment environment
Do not store or install the flowmeter :
• Where there is direct sunlight.
• Where excessive vibration or mechanical shock occurs.
• Where high temperature or high humidity conditions exist.
• Where corrosive atmospheres exist.
• Places that can be submerged under water.
• Where there is a sloped floor. To put the flowmeter temporarily on the floor, place it carefully with something, such as a block, to support it so that the flowmeter will not topple over.
In areas like the following, there may be the case that infrared switches do not function correctly. (If these are unavoidable, use an appropriate cover.)
(1) Where unit (operation panel) is exposed to direct sunlight, reflection of light onto window pane and diffused light reflection.
(2) Where smoke and steam may occur.
(3) Where exposed to direct snow, ice or mud.
Ordering Information
1. When ordering the LF410 series flowmeters, refer to Tables 6 and 7 (Type Specification Codes).
An entry must be made for each of the columns in each of these tables.
2. Fluid characteristics:
(1) Type of fluid to be measured and its characteristics
(2) Fluid temperature
(3) Fluid pressure
(4) Electrical conductivity of the fluid
3. Measuring range
4. I/O function setting
5. Ordering scope:
Flow calibration data: (required or not)
6. Other items
Specifications other than standard items
Consult a Toshiba representative before ordering when choosing materials of the wetted parts such as lining, electrodes, and grounding
rings.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Table 6. Specification Code (Wafer type detector LF410 Series)
Description
Detector category
Normal type Ex. type
L F 4 1 4 Hazardous location certification type (Note 1)
Meter size
D ½"(15mm)
E
F
G
H
1"(25mm)
1½"(40mm)
2"(50mm)
3"(80mm)
J
K
4"(100mm)
6"(150mm)
L 8"(200mm)
Mounting Style
P Detector/Converter combined type with PED (LF410/LF610) (Note 6)
Q Detector/Converter separate type with PED (LF410/LF612) (Note 6)
FM and CSA Class - I Division 2 type (Note 1)
C
D
E
F
J
K
L
Z
E
Z
C
C
D
F
H
Z
A
A
ANSI 150
ANSI 300
BS PN 10
BS PN 16
JIS 10K
JIS 16K
JIS 20K
Other
Ta (tantalum)
Other
Lining Material (Note 6)
Teflon PFA
316 stainless steel
316L stainless steel
Ta (tantalum)
Hastelloy C (Equivalent) other not provided
Coating no coating
C black epoxy
D black epoxy
Size code explanation: √ :Object : Standard : Option –: Not available
Note1
: Cable glands are not provided. Refer to the part of “Cable connection port” at detector and converter.
Note2
: Same shape of flange standard among ANSI 150, ANSI 300, BS10, BS16, DIN10, DIN16, JIS10K, JIS16K, and JIS20K.
Note3
: The type of material used is alumina ceramic, this is suitable for both acid and alkali liquids.
This ceramic lining and the electrodes are held with seals, there are two types, one for acids, and the other for alkalis.
Note4
: Separate type detector only. Specifying the code “C”, indicate the length of cables from 1 to 300m in 1 meter increments.
Note5
: Phthalic acid resin coating is standard for the flowmeter with meter size 1/2”(15mm), 6”(150mm), and 8”(200mm).
Note6
: Consult Toshiba before ordering when choose materials at the wetting parts.
Note7
: Check the Table 1 whether your chosen meter size meets this directive or not when the meter is shipped to EU. If yes, need to choose this code.
–
–
–
–
–
–
–
–
–
–
–
–
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
TIC-LF414C
Table 7. Specification Code for converters
Contents
A
F
A
B
Purpose
Standard cFMus class I, Division 2 approved
Shape
Integral type with case
Separate type with case
A
C
E
1
2
1
2
None
Panel, Accessory for wall mounting (BNP material: SUS304)
Accessory for pipe installation (BNP material: SUS304)
Digital output points 1 (DO1)
Digital output points 2 (DO1+DO2) +Digital input point 1 (DI)
Current output and Communication function
Current output + HART communication
PROFIBUS communication (Current output is not usable)
1
2
3
E
100Vac-240Vac, 50/60Hz
24Vdc
110Vdc
English
Code explanation: : Standard : Option –: Not available
LF610 type
–
–
–
–
LF612 type
–
–
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]