tvw series - Littelfuse
Protection Relays
Voltage Monitoring Relays
TVW SERIES
Description
The TVW Series Provides protection for motors and other
sensitive loads. Continuously measures the voltage of each
of the three phases using a microcontroller circuit design
that senses under and overvoltage, voltage unbalance, phase
loss, and phase reversal. Protection is provided even when
regenerated voltages are present. Includes a trip delay to
prevent nuisance tripping and a restart delay to prevent short
cycling after a momentary power outage.
Wiring Diagram
L1 = Phase A
L2 = Phase B
L3 = Phase C
NO = Normally Open
NC = Normally Closed
C = Common, Transfer Contact
Relay contacts are isolated.
F = 2A Fast acting fuses are
recommended, but not required
Operation
Upon application of line voltage, the restart delay begins.
The output is de-energized during restart delay. Under normal
conditions, the output energizes after the restart delay.
Undervoltage, overvoltage, and voltage unbalance must be
sensed for the complete trip delay period before the output
de-energizes. The restart delay begins as soon as the output
de-energizes. If the restart delay is completed when a fault is
corrected, the output energizes immediately. The output will not
energize if a fault is sensed as the input voltage is applied. If the
voltage selector is set between two voltage marks (i.e. between
220 and 230V), the LED will flash red rapidly. The TVW provides
fault protection at the lower of the two line voltages (i.e. 220V).
Reset: Reset is automatic upon correction of a fault.
LED Operation
The LED flashes green during the restart delay, then glows
green when the output energizes. It flashes red during the trip
delay then glows red when the output de-energizes. It flashes
red/green if phase reversal is sensed. If the voltage selector
knob is between settings, it rapidly flashes red.
Features & Benefits
Ordering Information
TRIP DELAY
RESTART
DELAY
TVW5103S5S
208 to 240VAC
Fixed, 10%
Selectable
Fixed, 3s
Fixed, 5s
TVW575S1M
208 to 240VAC
Fixed, 7%
Selectable
Fixed, 5s
Fixed, 1m
TVW6510S0.4S
208, 220, 230,
240VAC
Fixed, 5%
Fixed, 10s
Fixed, 0.4s
TVW8510S0.4S
380, 400 &
415VAC
Fixed, 5%
Fixed, 10s
Fixed, 0.4s
TVW9510S0.4S
430, 440, 460,
480VAC
Fixed, 5%
Fixed, 10s
Fixed, 0.4s
MODEL
LINE VOLTAGE
VOLTAGE
UNBALANCE
FEATURES
BENEFITS
Proprietary
microcontroller based
circuitry
Constant monitoring to protect against phase loss,
phase reversal; over, under, and unbalanced voltage;
short cycling
Compact design
measures 2 in.
(50.8mm) square
Perfect for OEM applications where cost, size and
ease of installation are important
LED indication
Provides diagnostics of relay, fault and time
delay status
Encapsulated
Protects against shock, vibration and humidity
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/
www.littelfuse.com/tvw
Rev: 1-A-062716
Protection Relays
Voltage Monitoring Relays
TVW SERIES
Accessories
LPSM003ZXID (Indicating),
LPSM003Z (Non-indicating) Fuse Holders
Littelfuse POWR-SAFE Dead Front holders
provide optimum protection to personnel for
Class CC and Midget-Style fuses. 600 VAC/DC
0KLK002.T Midget Fuse (2 Amp)
10 x 38 fast acting, high-interrupting capacity,
current-limiting type fuse. 600 Vac/500 Vdc
P1015-13 (AWG 10/12), P1015-64 (AWG 14/16),
P1015-14 (AWG 18/22) Female Quick
Connect
These 0.25 in. (6.35 mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.
VRM6048 Voltage Reduction Module
Allows the voltage monitor to monitor a 3-phase
550 to 600VAC Line.
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/
www.littelfuse.com/tvw
Specifications
Line Voltage
Type
3-phase delta or wye with no connection
to neutral
Input Voltage/Tolerance
208 to 480VAC in 4 ranges/-30% - 20%
AC Line Frequency
50 - 100 Hz
Phase Sequence
ABC
Power Consumption
Approx. 2W for 240V units
Approx. 3W for 480V units
Overvoltage, Undervoltage,
& Voltage Unbalance
Overvoltage & Undervoltage Voltage detection with delay trip &
automatic reset
Undervoltage Trip Point
88 - 92% of the selected line voltage
Reset Voltage
≅ +3% of trip voltage
Overvoltage Trip Point
109 - 113% of the selected line voltage
Reset Voltage
≅ -3% of trip voltage
Trip Variation vs Temperature ≤ ±2%
Voltage Unbalance Factory fixed, from 4 - 10%
Reset On Balance
≅ -0.7% unbalance
Trip Delay Range
Fixed from 0.2 - 100s ±15% or ±0.1s,
whichever is greater
Restart Delay Range
Fixed from 0.4s - 999m ±15% or ±0.2s,
whichever is greater
Phase Reversal & Phase
Loss Response
≤ 200ms; automatic reset
Phase Loss
≥ 25% unbalance
Output
Type
Isolated, SPDT
Rating
208 to 240VAC (55°C) 10A resistive @ 125VAC, 5A @ 250VAC,
1/4 hp @ 125VAC
380 to 480VAC 10A resistive @ 240VAC, 1/4 hp @ 125VAC,
1/3 hp @ 250VAC, max. voltage 277VAC
Life
Mechanical - 1 x 10 6; Electrical - 1 x 105
Protection
Phase Reversal/Failure
ASME A17.1 Rule 210.6
Motors and Generators
NEMA MG1 14:30, 14:35
Surge
IEEE C62.41-1991 Level B
Dielectric Breakdown
208 to 240VAC
≥ 1500V RMS input to output terminals
380 to 480VAC
≥ 2500V RMS input to output terminals
Mechanical
Mounting
Surface mount with one #8 (M5 x 0.8) screw
DimensionsH 50.8 mm (2.0”); W 50.8 mm (2.0”);
D 31.75 mm (1.25”)
Termination
0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage
Temperature
-40° to 55°C / -40° to 85°C
Humidity
95% relative, non-condensing
Weight
≅ 2.8 oz (79 g)
Rev: 1-A-062716