Series Six PLC Datasheets Manual, GEK-25367E

Series Six PLC Datasheets Manual, GEK-25367E
SERIES SIX
PROGRAMMABLE
GEK-83517C
CONTROLLERS
2 feet to 500 feet lengths
I/O CABLE
GENERAL DESCRIPTION
The cable is shielded and individual twisted-pair wires are
color-coded. (Refer to Figure 3, next page). The cable is
available in lengths ranging from 2 ft. (.6m) to 500 ft.
(152.5 meters).
The Input/Output (I/O) cable, consisting of 16, twistedpair wires and two connectors, provides electrical continuity for the parallel I/O Bus as it extends from rack to
rack within a Local, Central Processor Unit (CPU) or
Remote I/O station; it can also connect a Local station to
another Local station, or to a CPU station. Refer to Table
1 for I/O Cable features and benefits.
TABLE 1.
I
I
r-
Refer to Figure 1 (below) for I/O Cable specifications.
FEATURES AND BENEFITS
FEATURES
BENEFITS
I
Available in lengths from 2 feet to 500 feet.
I
Color-coded twisted-pairs.
I
- Cable Outside-Diameter:
0.465 + 0.020 (inches)
11.8 t 0.5 (mm)
Provides flexibility in Series Six setup.
Simplifies
- Jacket:
troubleshooting.
- Connectors:
- Conductor Size: No. 22 AWG (each wire)
FIGURE 1. SPECIFICATIONS
I
I
PVC material, 300V insulation
Temperature:
-2OQC to f80OC
- Internal Arrangement:
- Cable Length: 2 feet (0.6m) to 500 feet
(152.4m) in standard lengths
(determined by part number).
I
16 twisted pair with
overall shieId
37-Pin D-Type Connector.
One male, one female connector
per cable
GEK-83517
l/O Cable
FIGURE 2. I/O CABLE
INSTALLATION
Note that the cable has one connector with male terminals
and one with female terminals. AS a general rule, the
male connector on the cable connects to the upstream
module, and the female connector to the downstream
module. The specific modules which use this cable are:
the I/O Control module, the Auxiliary I/O module, the
I/O Receiver module, the I/O Transmitter module, and
the downstream port of the Remote I/O Receiver
module. All connectors should be secured using the furnished screws. Upstream is defined as toward CPU, downstream is away from CPU,
The shell of one of the connectors can be temporarily removed by loosening its screws, so that that end of the
cable can be more easily slid into, and through, a section
of conduit.
NOTE
The following constraints should be
observed when using this cable to interconnect various parts of the Series
Six I/O system:
1. The total cable length connecting
the racks within an I/O station (the
party-line bus) should be no more
t h a n 5 0 f e e t (15.2m). ( W i t h o u t
transmitters.)
2. The cable length between a Local
I/O station and the CPU station or
another Local station should be no
more than 500 feet (152.4m). (With
transmitters.)
3. The parallel I/O bus between any
Local I/O station and the CPU rack
should interface through no more than
four I/O Transmitter modules. (Up to
four transmitters between CPU and
furtherest I/O rack.)
Ref. PC-S&84-01
19
I/O Cable
GEK-83517
ORDERING
INFORMATION
Part Number
IC600WD002A
IC600WD005A
IC600WD010A
IC600WD025A
IC600WD050A
IC600WD 1OOA
IC600WD200A
IC600WD500A
2-foot Cable with Connectors
5-foot Cable with Connectors
10-foot Cable with Connectors
25-foot Cable with Connectors
50-foot Cable with Connectors
100-foot Cable with Connectors
200-foot Cable with Connectors
500-foot Cable with Connectors
0.6 Meters
1.5 Meters
3.0 Meters
7.5 Meters
15.0 Meters
30.0 Meters
60.0 Meters
150.0 Meters
CATALOG NUMBER REVISION SUFFIX
The equipment listed above having the catalog numbers shown and the same equipment
having a higher alpha suffix is designed for listing by UL for use as auxiliary control devices.
The equipment is a direct replacement for equipment having the same catalog number but a
lower alpha suffix.
This symbol on the nameplate means the product is listed by Underwriters Laboratories Inc. (UL Standard No. 508, Industrial Control Equipment, subsection Electronic
Power Conversion Equipment.)
For further information, contact your local GE Fanuc sales office.
GE Fanuc Automation North America, Inc., Charlottesville, Virginia
JANUARY, 1984
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement