Swegon GOLD Instructions
Swegon Gold is a powerful and versatile device designed to provide optimal indoor climate control. With its advanced features and intuitive interface, Swegon Gold offers a comprehensive solution for managing airflow, temperature, and other environmental factors. Whether you're looking to improve comfort, save energy, or enhance air quality, Swegon Gold has the capabilities to meet your needs.
Advertisement
Advertisement
FUNCTION MANUAL, INSTALLATION
GOLD
RX/PX/CX/SD
Generation F
Applicable to Program Version 1.22 and newer versions
GB.GOLDSKFFI.170308
Content
1. Image Management ................................................ 3
2. Main Setup .............................................................. 4
3. Filter Calibration ...................................................... 4
4. Functions ................................................................. 5
4.1 Airflow .......................................................................................... 5
4.1.1 Status ......................................................................................................5
4.1.2 Operation level .........................................................................................5
4.1.3 Regulation mode ......................................................................................6
4.1.4 Optimize ..................................................................................................7
4.1.5 Set point displacement .............................................................................7
4.1.6 Unit .........................................................................................................7
4.1.7 Air adjustment .........................................................................................7
4.1.8 Outdoor air compensation ........................................................................8
4.1.9 Booster diffusers ......................................................................................9
4.1.10 Automatic operation ..............................................................................9
4.2 Temperature................................................................................. 10
4.2.1 Status ....................................................................................................10
4.2.2 Settings..................................................................................................10
4.2.3 Regulation mode ....................................................................................13
4.2.4 Unit of temperature ...............................................................................14
4.2.5 Set point displacement ...........................................................................14
4.2.6 Neutral zone ..........................................................................................15
4.2.7 External temperature sensors ..................................................................15
4.2.8 Regulation sequence ..............................................................................16
4.2.9 Min. exhaust air .....................................................................................17
4.2.10 Morning Boost .....................................................................................18
4.2.11 Heating Boost ......................................................................................18
4.2.12 Cooling Boost ......................................................................................19
4.2.13 Intermittent night heat .........................................................................20
4.2.14 Summer night cool ...............................................................................21
4.2.15 Down regulation (airflow/pressure) .......................................................22
4.3 Time and schedule ....................................................................... 23
4.3.1 Time and date ........................................................................................23
4.3.2 Schedule settings ...................................................................................23
4.3.3 Day schedule ..........................................................................................24
4.3.4 Exceptions schedule ...............................................................................24
4.3.5 Calendar 1 and 2 ...................................................................................25
4.3.6 Prolonged operation...............................................................................25
4.4 Energy monitoring ....................................................................... 26
4.5 Filters ........................................................................................... 26
4.6 Software ...................................................................................... 26
4.7 Language ..................................................................................... 26
4.8 Alarm settings .............................................................................. 27
4.8.1 Fire alarms..............................................................................................27
4.8.2 External alarms .......................................................................................28
4.8.3 Temperature protection ..........................................................................28
4.8.4 Temperature alarm limits ........................................................................29
4.8.5 Service period ........................................................................................29
4.8.6 Alarm priority .........................................................................................29
4.9 Log .............................................................................................. 30
4.9.1 Continuous log ......................................................................................30
4.9.2 Log sender .............................................................................................30
4.10 Air handling unit ....................................................................... 31
4.10.1 Settings................................................................................................31
4.10.2 Fan status ............................................................................................32
4.10.3 Operation time .....................................................................................32
4.10.4 VOC/CO
2
sensor ...................................................................................32
4.10.5 Automatic functions .............................................................................32
4.11 Heat .......................................................................................... 33
4.11.1 Status .................................................................................................33
4.11.2 Pre-heat ...............................................................................................33
4.11.3 Extra regulation sequences 1 and 2.......................................................34
4.11.4 Reheat .................................................................................................35
4.11.5 Xzone ..................................................................................................35
4.11.6 Electric air heater ..................................................................................36
4.11.7 Season Heat .........................................................................................36
4.11.8 Automatic functions .............................................................................36
4.12 Cool .......................................................................................... 37
4.12.1 Status .................................................................................................37
4.12.2 Extra regulation sequences 1 and 2.......................................................37
4.12.3 Cool.....................................................................................................38
4.12.4 Xzone ..................................................................................................39
4.12.5 COOL DX .............................................................................................39
4.12.6 Delay time ............................................................................................40
4.12.7 Outdoor air limits .................................................................................40
4.12.8 Airflow, limits .......................................................................................40
4.13 Heat/Cool recovery ..................................................................... 41
4.13.1 Status ..................................................................................................41
4.13.2 Carry over control ................................................................................41
4.13.3 Efficiency measurement........................................................................41
4.13.4 Defrost .................................................................................................42
4.13.5 Type of heat exchanger (CX) .................................................................43
4.13.6 Glycol (CX) ...........................................................................................43
4.13.7 Calibration/Optimization (GOLD PX) .....................................................44
4.13.8 Automatic functions .............................................................................44
4.14 SMART Link ............................................................................... 45
4.15 Humidity .................................................................................... 46
4.15.1 Status ..................................................................................................46
4.15.2 Humidifying .........................................................................................46
4.15.3 Dehumidifying .....................................................................................47
4.15.4 Humidifier alarm ..................................................................................47
4.16 ReCO
2
........................................................................................ 48
4.17 All Year Comfort ........................................................................ 49
4.18 MIRU Control ............................................................................. 50
4.19 Inputs/Outputs ........................................................................... 51
4.20 Communication ......................................................................... 52
4.20.1 External Port B .....................................................................................52
4.20.2 Wireless LAN ........................................................................................52
4.20.3 E-mail ..................................................................................................53
4.20.4 EIA-485................................................................................................53
4.20.5 Modbus TCP ........................................................................................53
4.20.6 BACnet IP ............................................................................................53
4.20.7 EXOline TCP .........................................................................................54
4.20.8 Operation level communication ............................................................54
4.21 Base setting ............................................................................... 55
4.22. Users ........................................................................................ 55
4.23 Notes ......................................................................................... 56
4.24 Manual test ................................................................................ 56
4.25 IQnavigator
(hand-held terminal) .......................................................................... 57
4.25.1 Connect to IQlogic ...............................................................................57
4.25.2 Backlight brightness .............................................................................57
4.25.3 Acoustics .............................................................................................57
The document was originally written in Swedish.
2 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
1. Image Management
If the touch screen is at rest, press the hand-held terminal's On/
Off button.
Profile selection
Profile selection.
Press on installation. Kod=1111.
Guides
Main setup
Filter calibration
Main setup.
See Section2.
Filter calibration.
See Section3.
Dashboard
Timer, low speed
Stop
Alarm log
Log graph Flow chart
Dashboard.
See Section 2.2 in the
Operating Procedures
Manual of the IQnavigator hand-held micro terminal.
Functions
Air flow Temperature
Time and schedule
Energy monitoring
Filters Software
Language
Alarm prioritys
Log
Air handling unit
Heat Cool
Heat/Cool recovery
SMART Link Air humidity ReCO
2
All Year
Comfort
MIRU Control
Functions.
See Section 4
We reserve the right to alter specifications without notice.
www.swegon.com 3
GB.GOLDSKFFI.170308
2. Main Setup
Main setup can be selected when installing the AHU and is an aid for confi guring and starting up the AHU.
Time and date, air fl ow unit, airfl ow regulation mode, airfl ow operation level, temperature regulation, temperature settings and fan position settings can be entered here.
For more detailed information, see the relevant function below.
Main setup
See Section 4.3.1
See Sections 4.1.6 and 4.2.4
See Section 4.1.3
See Section 4.1.2
See Section 4.2.3.
See Section 4.2.2.
See Section 4.10.1
Main setup
1 Time and date
2 Air fl ow unit
3 Air fl ow regulation mode
4 Air fl ow operation level
5 Temperature regulation
6 Temperature settings
7 Fan position
8 Finish
Time
Date
Weekday
Wednesday
TIME AND DATE
Time zone
3. Filter Calibration
All the fi lters should be calibrated when the fans are started up for the fi rst time and when the duct system, air terminals and commissioning plates, if required, have been installed and commissioned.
After that every time fi lters are replaced. Calibration should then be activated for the fi lter or fi lters that are new. Relevant fi lters are the Supply air prefi lter, Extract air pre-fi lter, Supply air AHU fi lter, Extract air AHU fi lter, SA and EA AHU fi lter and Supply air end fi lter.
When fi lter calibration is activated, the air handling unit runs at the preset max. speed (depending on the functionality selected) for about 70 seconds.
After the fi lters have been calibrated, a pressure rise of up to 100
Pa is permissible (as the fi lters arrest impurities) after which an alarm indicating fouled fi lter is initiated. The alarm limit can be changed under Installation, Functions, Filters.
The fi lter function must be activated (see Section 4.5) in order to make it possible to enable fi lter calibration and alarm functions of the end fi lter and pre-fi lter in GOLD SD supply air and extract air handling units.
Filter calibration
Filter calibration
Supply air pre-fi lter
Extract air pre-fi lter
SA and EA pre-fi lter
Progress
CALIBRATION MODE
Supply air AHU fi lter
Extract air AHU fi lter
SA and EA AHU fi lter
Supply air end fi lter
Start
4 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4. Functions
4.1 Airfl ow
4.1.1 Status
All the relevant values can be read here. Used for performance checks.
Airfl ow
4.1.2 Operation level
The functions selected and the min. and max. airfl ows of each
AHU size (see the table below) determine which values can be set.
Depending on the function selected, fl ows can be set as follows
(l/s, m
3
/s, m
3
/h, cfm), pressure (Pa, psi, in.wc) or input signal strength (%).
Low speed
Should always be preset. The value for low speed cannot be higher than the value for high speed. Low speed can be set to 0, which means that the AHU is idle.
High Speed
Should always be preset. The value or pressure for high speed cannot be lower than the value for low speed.
Max. speed
Should always be preset. Used mainly for fi lter calibration. While fi lter calibration is in progress, the max. speed setting should be as high as the ventilation system permits without causing any breakdown. Also used for the pressure regulation, boosting,
Heating Boost and Cooling Boost functions. The value for max
Status
Operation level
speed cannot be lower than the value for high speed.
Min. /Max. speed
Used for the demand control function (the previous section also applies to max. speed). Preset the lowest and highest permissible fl ows for each fan. This means that the fans will not operate outside these limits, regardless the load.
Min./Max. fl ows
AIRFLOW MIN. FLOW FOR
AIRFLOW REG.,
ALL VARIANTS 2
SIZE
GOLD 004
GOLD 005
GOLD 007
GOLD 008
GOLD 011
GOLD 012
GOLD 014
GOLD 020
GOLD 025
GOLD 030
GOLD 035
GOLD 040
GOLD 050
GOLD 060
GOLD 070
GOLD 080
GOLD 100
GOLD 120 m
3
/s
0,08
0,08
0,08
0,20
0,20
0,20
0,20
0,30
0,30
0,50
0,50
0,75
0,6
1,00
1,00
1,50
1,50
2,50 m
3
/h
1
288
288
288
720
720
720
720
1080
1080
1800
1800
2700
2160
3600
3600
5400
5400
9000
MAX. FLOW, ONE-PIECE
AHU
ROTARY HEAT EXCH.
(RX) m
3
/h m
3
/s
1620
2340
2700
3600
0,45
0,65
0,75
1,00
3960
5040
5940
7560
9000
11520
1,10
1,40
1,65
2,10
2,50
3,20
14040 3,90
14040/18000
3
3,90/5,00
3
18000
23400
27000
34200
39600
50400
5,00
6,50
7,50
9,50
11,0
14,0
MAX. FLOW,
ONE-PIECE AHU
PLATE H. EXCH.
(PX) m
3
/h
1620
2340
2700
3600
3960
5040
5940
7560
9000
11520 m
3
/s
0,45
0,65
0,75
1,00
1,10
1,40
1,65
2,10
2,50
3,20
MAX. FLOW, ONE-PIECE
AHU
COIL H. EXCH. (CX)
MAX. FLOW, SA AND
EA AHU’S
(SD) m
3
/h m
3
/s m
3
/h m
3
/s
2160
2880
2880
4320
0,6
0,8
0,8
1,2
4320
6480
6480
10080
10080
14400
1,2
1,8
1,8
2,8
2,8
4,0
14040 3,90 14400 4,0
14040/18000
3
3,90/5,00
3
18000/21600
3
5,0/6,0
3
18000
23400
27000
34200
39600
50400
5,00
6,50
7,50
9,50
11,0
14,0
20160
28800
28800
43200
43200
64800
5,6
8,0
8,0
12,0
12,0
18,0
SMALLEST
STEP m
3
/h m
3
/s
25
25
25
25
25
25
100
100
25
25
25
25
100
100
100
100
100
100
0,01
0,01
0,01
0,01
0,01
0,01
0,01
0,01
0,01
0,01
0,05
0,05
0,05
0,05
0,05
0,05
0,05
0,05
1) When adjusting the fl ow, round off the value to the nearest settable step.
2) If pressure regulation is used, the airfl ow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
3) Cap. variant 1/cap.variant 2
We reserve the right to alter specifi cations without notice.
www.swegon.com 5
GB.GOLDSKFFI.170308
4.1.3 Regulation mode
The regulation moden can be selected individually for the supply air or the extract air respectively.
Airflow
Flow regulation involves operating the air handling unit to keep the preset airflow constant. The speed of the fans is automatically regulated to provide correct airflow even if the filters begin to become clogged, if air diffusers become blocked, etc.
A constant airflow is advantageous, since the airflow is always at the level preset from the beginning.
It should however be noted that everything that increases the pressure drop in the ventilation system, such as the blocking of air devices and dust accumulating in the filters, causes the fans to run at a higher speed. This causes higher power consumption and may also cause discomfort to the occupants such as excessive sound.
Duct pressure
The airflow automatically varies to provide constant pressure in the ducting. This type of regulation is therefore also called VAV
Regulation (Variable Air Volume).
Pressure regulation is used when e.g. damper operations increase the air volume in sections of the ventilation system.
The duct pressure is measured by an external in-duct pressure sensor which is connected to the control unit's BUS communication. The set point required (separate for low speed and high speed) is preset in Pa.
The function can be limited so that the fan speed will not exceed the preset max. values.
Demand
The airflow required is regulated in response to 0-10 V input signals from an external sensor, such as a carbon dioxide sensor, connected to control unit terminals 18-19. The required set point is set as a percentage of the input signal or in ppm.
The function can be limited so that the flow will not be higher or lower than the preset max. and min. values respectively.
Slave
The flow is constantly regulated to the same value as the other fan. If one fan is pressure-controlled or demand-controlled, the other one can be controlled as a slave to generate the same airflow.
The performance of the slave fan can be restricted if its maximum flow is set to a lower airflow rate.
It is not possible to control both fans as slaves. If you select one fan to operate as a slave, you lose the option to select the other fan as a slave.
Settings:
Value
Supply air
Extract air
Settings
Airflow
Duct pressure
Demand
Slave
Airflow
Duct pressure
Demand
Slave
Regulation mode
6 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.1.4 Optimize
The Optimize function optimises the air handling unit's airflow for the connected WISE system; see separate documentation for the WISE.
The function requires that the duct pressure setting is preset regulation type.
Settings:
Value
Optimize
Setting range
On/Off
Factory setting
Off
4.1.5 Set point displacement
The airflow is regulated between two flows in response to an
0-10 V DC input signal from an external signal, for example a potentiometer. The TBIQ-3-2 IQlogic + module accessory is required.
Set point displacement can be used e.g. in assembly halls, where a higher rate of air change is needed under full-load conditions.
The function is activated only when the AHU fans operate at high speed.
On a 0-10 V DC signal, the fans are gradually accelerated from the AHU’s high speed setting to its max. speed setting. On a max. input 10 V DC signal, the AHU fans operate at max. speed.
The function must be activated separately for the supply air fan and for the extract air fan.
Settings:
Value
Supply air
Extract air
Setting range
On/Off
On/Off
Factory setting
Off
Off
Optimize
Set point displacement
4.1.6 Unit
The required unit of airflow and unit of pressure can be set.
Settings:
Value
Unit of airflow
Unit of pressure
Setting range
l/s m
3
/s m
3
/h cfm
Pa psi in.wc
Factory settings
m
3
/s
Pa
Unit
4.1.7 Air adjustment
The speed of the fans can be locked for up to 72 hours. When the function is activated, the speed is locked at the current speed of operation. This is practical when making airflow adjustments in the duct system and air terminals. The desired period is preset, but can be interrupted earlier by selecting Stop or by changing the time setting to 0.
Air adjustment
We reserve the right to alter specifications without notice.
www.swegon.com 7
GB.GOLDSKFFI.170308
4.1.8 Outdoor air compensation
Outdoor air compensation of the airflow can be activated if you want to change the airflow for specific outdoor air temperatures.
An individually adjusted curve regulates the ratio between the airflow and the outdoor air temperature. The curve has four adjustable breakpoints..
If the function is selected solely for low speed or high speed operation, the curve will regulate only one of these. The airflow for the operating case that has not been selected will then be according to the preset set point for airflow/duct pressure.
In the flow regulation mode, the current set point for airflow is changed. When pressure regulation is selected, the current set point for pressure is changed. The function has no effect if the airflow is demand-controlled.
The airflow change is expressed in the preset airflow unit and pressure in Pa.
Settings:
Value Setting range
Factory setting
Outdoor air compensation mode Inactive/Low speed/High speed/Low
Inactive speed and
High speed
X1, breakpoint, outdoor air temp. -50 – +50 °C -20 °C
X2, breakpoint, outdoor air temp. -50 – +50 °C -10 °C
X3, breakpoint, outdoor air temp. -50 – +50 °C +10 °C
X4, breakpoint, outdoor air temp. -50 – +50 °C +20 °C
Supply air, flow
Y1, breakpoint, supply air
1)
25% of max.
Y2, breakpoint, supply air
1) airflow for air handling unit
25% of max.
Y3, breakpoint, supply air
1) airflow for air handling unit
25% of max.
Y4, breakpoint, supply air
1) airflow for air handling unit
25% of max. airflow for air handling unit
Extract air, flow
Y1, breakpoint, extract air
Y2, breakpoint, extract air
Y3, breakpoint, extract air
Y4, breakpoint, extract air
1)
1)
1)
1)
25% of max. airflow for air handling unit
25% of max. airflow for air handling unit
25% of max. airflow for air handling unit
25% of max. airflow for air handling unit
Supply air, pressure
Y1, breakpoint, supply air 20-750 Pa 100 Pa
Y2, breakpoint, supply air
Y3, breakpoint, supply air
Y4, breakpoint, supply air
Extract air, pressure
Y1, breakpoint, extract air
Y2, breakpoint, extract air
Y3, breakpoint, extract air
Y4, breakpoint, extract air
20-750 Pa
20-750 Pa
20-750 Pa
20-750 Pa
20-750 Pa
20-750 Pa
20-750 Pa
100 Pa
100 Pa
100 Pa
100 Pa
100 Pa
100 Pa
100 Pa
1)
See table for min./max. flows in Section 6.4.1.2
Outdoor air compensation
3,0
2,5
2,0
1,5
1,0
0,5
-30
1
2
3
4
-20 -10 0 +10 +20
X = Outdoor air temperature °C
Example:
Flow regulated air handling unit The same principle can be applied to a pressure regulated AHU, however this well cause a reduction in pressure in Pa.
If the outdoor air temperature is under -20 °C (X1), the flow set point will be a constant 2.0m
3
/s (Y1).
If the outdoor air temperature is between -20 °C (X1) and -10
°C (X2), the airflow will decrease from 2.0 m
3
/s (Y1) to 1.0 m
3
/s
(Y2) as shown in the curve.
If the outdoor air temperature is between -10 °C (X2) and 10 °C
(X3), the flow set point will be a constant 1.0 m
3
/s (Y2 and Y3).
If the outdoor air temperature is between 10 °C (X3) and 20 °C
(X4), the airflow will increase from 1.0 m
3
/s (Y3) to 2.5 m
3
/s (Y4) as shown in the curve.
If the outdoor air temperature is over 20 °C (X4), the flow set point will be a constant 2.5 m
3
/s.
8 www.swegon.com
We reserve the right to alter specifications without notice.
4.1.9 Booster diffusers
The function for Booster diffusers is used for controlling the air damper inside the air terminal and can be activated for heating or cooling. Heating or cooling is modulated depending on whether the supply air is warmer or colder than the room/extract air. An indicator is displayed if heating or cooling is active.
The IQlogic
+
module, TBIQ-3-2, accessory is required.
Value
Booster diffusers
Setting range
On/Off
Factory setting
Off
Booster diffusers
4.1.10 Automatic operation
Density-corrected airflow
The density of the air is different at different temperatures. This means that a specific volume of air changes at various air densities. The AHU automatically corrects this, so that correct air volume is always obtained.
The control equipment always displays the corrected airflow.
Pressure balance corrected extract airflow
The extract airflow is corrected by continuously measuring the pressure balance across the rotary heat exchanger. The extract airflow is guaranteed with consideration given to the air purging and leakage air flow.
GB.GOLDSKFFI.170308
We reserve the right to alter specifications without notice.
www.swegon.com 9
GB.GOLDSKFFI.170308
4.2 Temperature
N.B.! If the entry of new temperature settings involve large changes, you should fi rst stop the AHU before you enter the new settings.
Specifi c temperatures, such as set points, should be specifi ed in °C or °F, whereas displacements, deviations and differentials should be specifi ed in K (Kelvin).
If only GOLD SD supply air handling units are installed, they require an external room sensor for ERS, ORE and extract air regulation.
4.2.1 Status
All the relevant values can be read here. Used for performance checks.
4.2.2 Settings
ERS Regulation 1
ERS regulation refers to Extract air temperature-Related Supply air temperature regulation. This means that the temperature of the supply air is regulated in relation to the temperature of the extract air.
Under normal circumstances, the supply air temperature is regulated to be a few degrees lower than the extract air temperature. In this way, the heat exchanger will provide optimal performance, and this means excellent operating economy.
ERS control is suitable for use when there is surplus heat in the premises generated e.g. by machinery, lighting or people, and the premises have supply air diffusers suitable for discharging air below room temperature.
Temperature
Status
Settings
ERS Regulation 1
20
15
ERS 1 dif f.
ERS Regulation 1
The control unit regulates the ratio between the supply air and extract air temperature according to a factory-preset curve.
See the diagram to the right.
The step in the curve, breakpoint and differential can be changed.
Settings:
Value
Extract related supply air-1 step
Extract related supply air-1 diff
Extract related supply air-1 breakpoint
(refers to extract air temperature)
Setting range
1 - 4
1-7 K
12-26 °C
Factory setting
2
3 K
22 °C
The setting range for breakpoint and deviation are limited by the min. and max. settings.
Breakpoint
Step 1
Step 2
Step 3
Step 4
10
12 15 20
Extract air temperature °C
25
Factory setting means:
If the extract air temperature is below 22 °C (breakpoint), the supply air temperature set point will be automatically regulated to be 3 K (diff.) lower.
If the extract air temperature is above 22 °C, the supply air temperature set point will constantly be 19 °C (step 2).
10 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
ERS Regulation 2
Used if the factory preset performance curve in the ERS Control
1 function does not provide the results desired to meet special needs and conditions. Depending on which setting have been entered, the installation of an air heater for reheating may be required.
An individually adjusted curve regulates the ratio between the supply air and the extract air temperature. The curve has four adjustable breakpoints..
See the diagram to the right.
Settings:
Value Setting range
Factory setting
Extract air temperature
Extract related supply air-2 X1
Extract related supply air-2 X2
Extract related supply air-2 X3
Extract related supply air-2 X4
Supply air temperature set point
Extract related supply air-2 Y1
Extract related supply air-2 Y2
Extract related supply air-2 Y3
Extract related supply air-2 Y4
10-40 °C
10-40 °C
10-40 °C
10-40 °C
10-40 °C
10-40 °C
10-40 °C
10-40 °C
15 °C
20 °C
22 °C
22 °C
20 °C
18 °C
14 °C
12 °C
The set point displacement and Summer night cool functions can also affect the preset temperatures.
Supply air regulation
Supply air regulation involves maintaining a constant supply air temperature without consideration to the load in the premises.
This type of regulation can be used when the load and temperatures of the premises are predictable. In most cases this requires the installation of an air heater for reheating, possibly an air cooler as well.
Settings:
Value Setting range
Supply air (temp. set point) 0-40 °C
Factory setting
21 °C
ERS Regulation 2
22
20
15
10
9
12
1
15
2
20
3
4
X = Extract air temperature °C
25 27
Breakpoints according to factory setting involve the following:
If the extract air temperature is below 15°C (X1), the supply air temperature set point will constantly be 20 °C (Y1).
If the extract air temperature is between 15 °C (X1) and 20 °C
(X2), the supply air temperature set point is regulated from 20
°C (Y1) down to 18 °C (Y2) as shown in the curve.
If the extract air temperature is between 20 °C (X2) and 22 °C
(X3), the supply air temperature set point is regulated from 18
°C (Y2) down to 14 °C (Y3) as shown in the curve.
When the extract air temperature is 22 °C (X4), the supply air temperature set point is regulated from 14 °C (Y3) down to 12
°C (Y4).
If the extract air temperature is over 22 °C (X4), the supply air temperature set point will constantly be 12 °C (Y4).
Extract air regulation
Extract air control involves maintaining a constant temperature in the extract air duct (the premises), by regulating the supply air temperature.
This provides a uniform temperature in the premises regardless of the load and this type of regulation requires the installation of an air heater for reheating; possibly a cooling coil as well.
The extract air temperature is measured by the air handling unit's internal temperature sensor. If this internal temperature sensor does not give an adequate representative extract air temperature reading, an external room temperature sensor can be installed and wired to the control unit’s communications BUS (optional
COM1-3).
Settings:
Value
Extract air (temp. set point)
Supply air, min.
Supply air, max.
Setting range
0-40 °C
0-30 °C
8-50 °C
Factory setting
21 °C
16 °C
28 °C
We reserve the right to alter specifications without notice.
www.swegon.com 11
GB.GOLDSKFFI.170308
ORS regulation
ORS regulation refers to Outdoor air temperature-Related Supply air temperature regulation. This means that the temperature of the supply air is regulated in relation to the temperature of the outdoor air.
An individually adjusted curve regulates the ratio between the supply air and the outdoor air temperature. The curve has four adjustable breakpoints.
Settings (see also diagram to the right):
Value Setting range
Factory setting
Outdoor air temperature
Outdoor related supply air X1
Outdoor related supply air X2
Outdoor related supply air X3
Outdoor related supply air X4
Supply air temperature set point
Outdoor related supply air Y1
Outdoor related supply air Y2
Outdoor related supply air Y3
Outdoor related supply air Y4
-50 – +50 °C -20 °C
-50 – +50 °C -10 °C
-50 – +50 °C 10 °C
-50 – +50 °C 20 °C
10 – 40 °C
10 – 40 °C
10 – 40 °C
10 – 40 °C
21.5 °C
21.5 °C
21.5 °C
21,5 °C
ORE regulation
ORE regulation refers to Outdoor air temperature-Related Extract air temperature regulation. This means that the extract air temperature is regulated in relation to the outdoor air temperature.
An individually adjusted curve regulates the ratio between the extract air and the outdoor air temperature. The curve has four adjustable breakpoints.
Settings (see also diagram to the right):
Value Setting range
0 – 20 °C
16 – 50 °C
Factory setting
16 °C
28 °C
Supply air, min.
Supply air, max.
Outdoor air temperature
Outdoor related extract air X1
Outdoor related extract air X2
Outdoor related extract air X3
Outdoor related extract air X4
Extract air temperature set point
Outdoor related extract air Y1
Outdoor related extract air Y2
Outdoor related extract air Y3
Outdoor related extract air Y4
-50 – +50 °C -20 °C
-50 – +50 °C -10 °C
-50 – +50 °C 10 °C
-50 – +50 °C 20 °C
10 – 40 °C
10 – 40 °C
10 – 40 °C
10 – 40 °C
21.5 °C
21,5 °C
21,5 °C
21,5 °C
ORS regulation
25
20
1
2 3
4
15
-30 -20 -10 0 +10 +20
X = Outdoor air temperature °C
+30
Example:
If the outdoor air temperature is under -30 °C (X1), the supply air temperature set point will constantly be 18 °C (Y1).
If the outdoor air temperature is between -30 °C (X1) and -10
°C (X2), the supply air temperature set point is regulated from
18 °C (Y1) up to 20 °C (Y2) as shown in the curve.
If the outdoor temperature is between -10 °C (X2) and +10 °C
(X3) the supply air set point will constantly be 20 °C (Y3).
If the outdoor air temperature is between +10 °C (X3) and +30
°C (X4), the supply air temperature set point is regulated from
20 °C (Y3) down to 18 °C (Y4) as shown in the curve.
If the outdoor air temperature is over 30 °C (X4), the supply air temperature set point will constantly be 18 °C (Y4).
ORE regulation
25
20
15
1
2 3
4
-30 -20 -10 0 +10 +20
X = Outdoor air temperature °C
+30
Example:
If the outdoor air temperature is under -30 °C (X1), the extract air temperature set point will constantly be 18 °C (Y1).
If the outdoor air temperature is between -30 °C (X1) and -10
°C (X2), the extract air temperature set point is regulated from
18 °C (Y1) up to 20 °C (Y2) as shown in the curve.
If the outdoor temperature is between -10 °C (X2) and +10 °C
(X3) the extract air set point will constantly be 20 °C (Y3).
If the outdoor air temperature is between +10 °C (X3) and +30
°C (X4), the extract air temperature set point is regulated from
20 °C (Y3) down to 18 °C (Y4) as shown in the curve.
If the outdoor air temperature is over 30 °C (X4), the extract air temperature set point will constantly be 18 °C (Y4).
12 www.swegon.com
We reserve the right to alter specifications without notice.
4.2.3 Regulation mode
Select ERS 1, ERS 2, Supply air, Extract air, ORS or ORE temperature regulation.
Seasonal controlled temperature regulation makes it possible to have two different temperature regulation modes that alternate at preset outdoor temperatures.
Seasonal controlled temperature regulation operates with the air handling unit's internal temperature sensor, however for the best performance we recommend external outdoor temperature sensor TBLZ-1-24-3; see separate installation instructions.
Enable seasonal controlled temperature regulation and temperature regulation (ERS 1, ERS 2, Supply air, Extract air, ORS or ORE).
Set the temperature at which seasonal controlled temperature regulation shall be enabled and disabled respectively. By setting a span between the different temperatures, unwanted switching operations between the types of regulation can be avoided.
Settings:
Value
Temperature control
Setting range
ERS 1/ERS 2/Supply air/Extract air/ORS/
ORE
On/Off
Factory setting
Supply air
Off Seasonal controlled temperature regulation
Seasonal controlled temperature regulation
ERS 1/ERS 2/Supply air/Extract air/ORS/
ORE
-20 – +40 °C
Extract air
0 °C Seasonal controlled temperature regulation, enabled
Seasonal controlled temperature regulation, disabled
-20 – +40 °C 20 °C
Regulation mode
GB.GOLDSKFFI.170308
We reserve the right to alter specifications without notice.
www.swegon.com 13
GB.GOLDSKFFI.170308
4.2.4 Unit of temperature
The desired unit of temperature can be set.
Settings:
Value Setting range
Unit °C/ °F
Factory settings
°C
4.2.5 Set point displacement
Used for changing the supply air and extract air temperature set points by means of an external 0-10 VDC signal. For example, the temperature can be increased or decreased at certain times of the day by means of an external timer or potentiometer.
The accessory, IQlogic
+
module TBIQ-3-2, is required.
The set point can be influenced by ±5 °C.
If the AHU is operating in the supply air regulation or ORS regulation mode, the supply air temperature set point is displaced and the AHU is operating in the extract air regulation or ORE regulation mode, the extract air temperature set point is displaced.
When the AHU is operating in the ERS regulation 1 mode, the difference between extract air and supply air is influenced. The difference cannot be less than 0 °C. The difference will decrease as the input signal increases.
If the AHU is operating in the ERS regulation 2 mode, the supply air set point will be displaced.
When the function is activated, the set point is displaced as plotted in the diagram to the right.
Set point displacement will not affect any possible extra temperature zone (Xzone) which regulates according to its ordinary set point if set point displacement is in operation.
Settings:
Value
Set point displacement
Setting range
On/Off
Factory setting
Off
Unit of temperature
Set point displacement
-1
-2
-3
+2
+1
0
-4
-5
+5
+4
+3
0 5
Control signal V DC
10
Set point displacement involves the following:
Control signal 0 V DC: The set point is decreased by 5 °C.
Control signal 5 V DC: No change in set point.
Control signal 10 V DC: The set point increases by 5 °C.
14 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.2.6 Neutral zone
The neutral zone prevents the cooling and heating systems from counteracting each other.
The preset neutral zone is added to the set point for heating and the sum of these provides the set point for cooling.
When extract air regulation is active, the supply air set point is not affected. The neutral zone has no effect if the unit is operating in the ERS regulation mode.
Settings:
Value
Supply air, temperature control
Extract air, temperature control
Setting range
0.0 - 10 K
0.0 - 10 K
Factory setting
0.5 K
0.5 K
4.2.7 External temperature sensors
An extract air duct temperature sensor, TBLZ-1-76, can be connected to the air handling unit’s control circuit card. See separate instructions for installation.
Up to four external room temperature and/or outdoor temperature sensors can be wired to the air handling unit’s control circuit card. The TBLZ-1-24-2 room temperature sensor or TBLZ-1-24-3 outdoor temperature sensor accessories should be used. See separate installation instructions.
The sensor can be selected to control only intermittent night heat and/or summer night cooling (the AHU is then controlled during the daytime in response to signals from the internal sensor inside the AHU).
Locate the temperature sensors at suitable places to obtain representative readings.
The air handling unit is controlled in response to a computed mean value of the temperature sensors' readings, alternatively in response to signals from the temperature sensor that measures the lowest or highest value.
As an alternative, a temperature reading can be transmitted to the air handling via communication from e.g. a main system.
The same provision is available for room sensors for the Xzone function.
Settings:
Value Setting range
Factory setting
Extract air duct, temperature sensor
Room sensor 1
Room sensor 2
Room sensor 3
Room sensor 4
Room sensor function
Room temperature from communication
Room temperature, for intermittent night heat only
Room temperature, for summer night cooling only
Outdoor air sensor 1
Outdoor air sensor 2
Outdoor air sensor 3
On/Off
On/Off
On/Off
On/Off
On/Off
Medium/min./Max.
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
Off
Off
Off
Off
Off
Medium
Off
Off
Off
Off
Off
Off
Off Outdoor air sensor 4
Outdoor air sensor function Medium/min./Max.
Medium
Outdoor temperature from communication
On/Off Off
We reserve the right to alter specifications without notice.
Neutral zone
External temperature sensors
www.swegon.com 15
4.2.8 Regulation sequence
Heating mode
The mutual order for the heating mode regulation sequence can be selected as specified below.
Functions that have not been selected have no effect on the relevant regulation sequence.
Value
Heating mode
Setting range
1/2/3/4/5/6*
Factory setting
1
* 1 = HX - Extra regulation sequence - ReCO
2
- Reheating -
Down regulation of fan
2 = HX - Extra regulation sequence - Reheating - ReCO
2
-
Down regulation of fan
3 = HX - Reheating - ReCO
2
Down regulation of fan
- Extra regulation sequence -
Down regulation of fan
4 = HX - Reheating - Extra regulation sequence - ReCO
2
-
5 = HX - ReCO
2
- Reheating - Extra regulation sequence -
Down regulation of fan
6 = HX - ReCO
2
- Extra regulationsequence - Reheating -
Down regulation of fan
HX (heat exchanger):
The temperature efficiency of the air handling unit’s heat exchanger is modulated to provide max. heat recovery.
Extra regulation sequence:
Used in the heating mode for air heater (if required), air recirculation damper, etc.
ReCO
2
:
Recirculated air is variably mixed in up to the lowest permissible supply airflow. Assumes inclusion of the TCBR air recirculation section accessory.
Reheating:
Air heater for reheating provides heating capacity.
Down regulation of fan:
Down regulation can be selected for supply air only or supply air and extract air.
Regulation sequence
GB.GOLDSKFFI.170308
16 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
Cooling mode
The mutual order for the cooling mode regulation sequence can be selected as specified below.
Functions that have not been selected have no effect on the relevant regulation sequence.
Value
Cooling mode
Setting range
1/2/3/4/5/6*
Factory setting
1
* 1 = HX - Cooling Boost - Extra regulation sequence - ReCO
2
-
Cooling
2 = HX - Cooling Boost - Extra regulation sequence - Cooling -
ReCO
2
3 = HX -Cooling Boost - Cooling - ReCO
2
-
Extra regulation sequence
4 = HX - Cooling Boost - Cooling - Extra regulation sequence -
ReCO
2
5 = HX - ReCO
2
- Cooling Boost - Cooling -
Extra regulation sequence
6 = HX - ReCO
2
Cooling
- Cooling Boost - Extra regulation sequence -
HX (heat exchanger):
The temperature efficiency of the air handling unit’s heat exchanger is modulated to provide max. cool recovery.
Cooling Boost (Economy):
Involves increasing the supply air and extract air airflows to convey more cooling energy to the premises. The flow increase takes place between the current flow and the preset max. flow.
Extra regulation sequence:
Used in the cooling mode for air cooler (if required), etc.
ReCO
2
:
Recirculated air is variably mixed in up to the lowest permissible supply airflow. Assumes inclusion of the TCBR air recirculation section accessory.
Cooling:
Air cooler provides cooling capacity.
4.2.9 Min. exhaust air
The min. exhaust air function can be used whenever the exhaust air temperature is not permitted to be below a predetermined value.
The function controls the heat exchanger rotor speed (efficiency) in order to limit the exhaust air temperature to the required value. The function decelerates the heat exchanger rotor speed from the current level, until the exhaust air temperature reaches the preset minimum permissible setting.
Exhaust air regulation requires a separateTBLZ-1-58-aa temperature sensor (accessory) fitted in the AHU's exhaust air.
See separate installation instructions for the TBLZ-1-58-aa Internal temperature sensor.
Settings:
Value Setting range
Min. exhaust air On/Off
Min. exhaust air temperature -40 – + 20,0 °C
Factory setting
Off
5.0 °C
Min. exhaust air
We reserve the right to alter specifications without notice.
www.swegon.com 17
4.2.10 Morning Boost
The unit is utilised for heating the premises during a preset period prior to the switch-in time set on the timer.
The function is used if an air recirculation section is installed.
The AHU starts up prematurely and uses the same temperature regulation settings. The airflow / air pressure is adjustable.
When the function starts, the air recirculation damper opens and the supply air fan starts up. The extract air fan and the outdoor air damper remain closed.
Settings:
Value
Morning Boost
Start time (before the ordinary start time according to the timer)
Supply air, set point
Setting range
On/Off hour:min.
Factory setting
Off
00:00
1)
50% of max. supply air for
AHU alt. 100 Pa
1)
The setting range is the same as the AHU's min./max. setting for flow regulation and 10-750 Pa for pressure regulation
Morning Boost
4.2.11 Heating Boost
Heating boost (forced heating) means that the air handling unit, operating in the normal flow regulation mode, increases both the supply airflow and the extract airflow in order to carry more heat into the premises.
The fans are permitted to operate in the range between current flow modes or pressure (low speed, high speed) and the preset max speed. See Section 6.4.1.2.
The functions operates only when the AHU is operating in the extract air regulation and ORE regulation mode. If demand control or boost is selected in combination with heating boost, the flow is controlled by the function that transmits the highest output signal to the fans.
A regulated ramp function switches in and gradually increases the airflow when there is a heating load, and the supply air temperature is 3 K (preset at factory) lower than the preset max. supply air temperature.
Settings:
Value
Heating Boost
Start limit
Setting range
On/Off
2-10 K
Factory setting
Off
3 K
Heating Boost
GB.GOLDSKFFI.170308
18 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.2.12 Cooling Boost
Cooling Boost (forced cooling) means that the supply air and extract air airflows are increased to convey more cool air to the premises.
The fans are permitted to operate in the range between current flow modes or pressure (low speed, high speed) and the preset max speed. See Section 4.1.2.
The function can be selected in five variants as follows:
Comfort
The cooling outputs are activated if there is a cooling load.
A regulated ramp function switches in and gradually increases the airflow when there is a cooling load, and the supply air temperature is 3 K (preset at factory) higher than the preset max. supply air temperature.
Economy
Cooling Boost Economy initially uses a higher airflow to cool the premises, before a start signal is transmitted to chillers.
The function can also operate without the cooling function activated.
In the event of a cooling load, the airflows are slowly increased up to preset maximum flow. When the flows are up to max and if a cooing load is still present, the output contacts for cooling are activated.
The function requires that the outdoor air temperature is at least
2 K lower than the extract air temperature for it to be activated.
The normal cooling function is activated if the temperature difference is too small.
Sequence
The Cooling Boost Sequence is used if a chiller is sized for a higher cooling flow than normal flow.
If there is a cooling load, the flow is increased up to the preset max. flow and the cooling function is activated afterwards.
The Cooling Boost Sequence is blocked if no cooling function has been selected.
Comfort and economy
The comfort variant and the economy variant can be combined.
The function that has the highest signal (highest setpoint) applies.
Economy and sequence
The economy variant and the sequence variant can be combined. The function that has the highest signal (highest setpoint) applies.
Sequence and comfort
The sequence variant and the comfort variant can be combined.
The function that has the highest signal (highest setpoint) applies.
Comfort, economy and sequence
The comfort variant, economy variant and the squence variant can be combined. The function that has the highest signal
(highest setpoint) applies.
Cooling Boost
Settings:
Value
Cooling Boost
Start limit (Comfort)
Setting range
Inactive
Comfort
Economy
Sequence
Comfort and economy
Economy and sequence/
Sequence and comfort/
Comfort, economy and sequence
2-10 K
Factory setting
Inactive
3 K
We reserve the right to alter specifications without notice.
www.swegon.com 19
GB.GOLDSKFFI.170308
4.2.13 Intermittent night heat
The AHU is utilized for heating the premises when it is normally stopped by timer.
The function requires that an external room sensor is wired to the control unit’s communication BUS (optional COM 1-3) and that the AHU is fitted with an air heater for reheating the air. The function works best if the GOLD is equipped with an air recirculation section and shut-off dampers for the outdoor air and the exhaust air.
When the function is activated, the air handling unit detects when the room temperature drops below the preset start temperature. The unit starts with preset flows and the supply air temperature set point. At the same time, the damper in the air recirculation section opens, if one is installed.
If recirculation is in the Off position, the extract air fan is operating and the damper relay is open. The extract airflow setting can be decreased to the air handling unit‘s min. flow.
Intermittent night heat does not affect any possible extra temperature zone (Xzone) which regulates according to its ordinary set point if Intermittent night heat is in operation.
Conditions to be met for intermittent night-time heating to start:
• The AHU must be set to normal stop or extended normal stop.
• The room temperature must be lower than the preset start temperature.
Conditions to be met so that Intermittent night heat will stop:
• The air handling unit is running at normal low/high speed or external/manual stop has been activated.
• The room temperature exceeds the preset stop temperature.
• The alarm with preset stop priority trips.
(If needed, the air handling unit fans will continue to operate to cool the electric air heater although other conditions for stop have been met.)
Settings:
Value
Intermittent night heat
Air recirculation
Room temperature, start
Room temperature, stop
Supply air temperature, set point
Supply airflow, set point
Setting range
On/Off
On/Off
5 - 25 °C
5 - 25 °C
5 - 50 °C
1)
Factory setting
Off
On
16 °C
18 °C
28 °C
Extract air flow, set point
1)
50% of max. supply air for
AHU alt. 100 Pa
50% of max. supply air for
AHU alt. 100 Pa
Intermittent night heat
EXTRACT AIR
SUPPLY AIR
Intermittent night heat with air recirculation section:
Recirculation in the On position:
When conditions for start are met, outdoor air and exhaust air shut-off dampers remain closed. The damper in the air recirculation section opens. The extract air fan is idle.
The supply air fan operates according to the preset supply airflow and the air heater for reheating operates according to the preset supply air temperature set point, until the conditions for stop are met.
1) The setting range is the same as the AHU's min./max. setting for flow regulation and 10-750 Pa for pressure regulation
20 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.2.14 Summer night cool
The lower temperature at night is utilised to cool down the building structure. This reduces the cooling load during the first hours of the day. If a cooling unit is installed, it will not need to be operated, thus offering savings. If no cooling unit is installed, a certain cooling effect will still be achieved.
When the function is activated, the AHU fans operate at high speed, with a supply air set point of 10 °C (factory setting) from the preset time until the conditions necessary for stop are satisfied.
If the air handling unit is stopped for a period of time, test starts can be implemented in order to check whether all conditions, except heating demand, for summer night cooling have been met. If the conditions have been met, summer night cooling can be run. The start and stop dates of the period during which the air handling unit will be stopped can be preset.
The set point for flow or pressure on the supply air and extract air can be set. This then means that any outdoor compensation does not affect summer night cooling.
An extra temperature zone (Xzone), if required, obtains the same supply air set point if Summer night cool is in operation.
Conditions that must be met for Summer night cool to start at the preset time:
• The time is between the preset start time and stop time.
• The outdoor air temperature shall be higher than the preset value.
• The extract air temperature shall be higher than the preset value.
• The extract air is at least 2 °C warmer than the outdoor air.
• Heating has not been required between 12.00 and 23.59 hours.*
• The air handling unit shall be running at low speed or be in the normal stop operating mode.
• Intermittent night heat has not been active during the day.
Conditions that must be met for Summer night cool to stop:
• The time is not between the preset start time and stop time.
• The extract air temperature drops below the preset value.
• The outdoor temperature drops below the preset value.
• The extract air is less than 1 °C warmer than the outdoor air.
• The air handling unit is running at normal high speed or external/manual stop has been activated.
The function starts once per preset time period.
Summer night cool
Settings:
Value Setting range
Summer night cool On/Off
Start time 00:00-00:00
Stop time 00:00-00:00
Outdoor air, start
Extract air, start
Extract air, stop
-5 - +15 °C
17 - 27 °C
12 - 22 °C
Supply air, set point 0 - 20 °C
Start, period with stopped air
01-01 – 01-01 (month
– day) handling unit 1)
Stop, period with stopped air handling unit
1)
01-01 – 01-01
(month – day)
Supply air, set point Unit’s minimum flow maximum flow
2)
Supply air, set point 20 - 750 Pa
Extract air set point Unit’s minimum flow -
Extract air set point maximum flow
2)
20 - 750 Pa
Factory setting
Off
23:00
06:00
10 °C
22 °C
16 °C
10 °C
05-01
10-01
50% of maximum air flow for air handling unit
100 Pa
50% of maximum air flow for air handling unit
100 Pa
1) The condition for heating load can be deselected during the preset period.
2) See section 4.1.2.
We reserve the right to alter specifications without notice.
www.swegon.com 21
4.2.15 Down regulation (airflow/pressure)
Down regulation of the supply air flow is the last step in the regulation sequence for heating. The supply air fan or both the supply air and extract air fan can be selected. The extract air fan only cannot be selected.
See also Section 4.2.8.
Down regulation can take place to max. of 50% of the preset value, however not lower than the min. flow or 20 Pa.
Settings:
Value
Down regulation
Setting range
Inactive/Supply air/Supply air and extract air
Factory setting
Supply air
Down regulation
GB.GOLDSKFFI.170308
22 www.swegon.com
We reserve the right to alter specifications without notice.
4.3 Time and schedule
The built-in timer enables you to control the AHU's operating mode/time. Certain other oversteering functions such as external timer, communication, etc. affect the preset operating modes.
There are fi ve different operating modes:
Total stop = The AHU is completely stopped, no internal automatic functions or external control commands can start the AHU.
Normal Stop = The AHU has stopped, however all the internal and external automatic functions oversteer the stop.
Extended Normal Stop = The AHU has stopped, however all the internal and external automatic functions, with exception of
Summer night cool, oversteer the stop.
Low speed = The AHU is running at the preset low speed setting.
High speed = The AHU is running at the preset high speed setting.
4.3.1 Time and date
The current date and time can be set and adjusted if needed. The timer automatically takes leap years into consideration.
The relevant region and city can be selected, summer time/winter time changover will then be managed automatically.
Time source can be set to manual or via SNTP (requires connection to network) and BACnet. The time format and date format can be set.
4.3.2 Schedule settings
The relevant operating mode can be read under Schedule settings. Here you can also set a preselected operating mode, in which the air handling unit always operates during non-programmed time, under Day schedule and Exceptions schedule.
This setting (start and stop date not activated) is used most often and covers the majority of needs.
When the start and stop date is activated, this means that during the preset period (date) preset time applies during the day schedule and the exceptions schedule, and at all other times the
AHU runs in the preselected operating mode.
Settings:
Value
Preselected operating mode
Start date
Start date
Stop date
Stop date
Setting range
Total stop/Low speed/High speed/
Normal Stop/
Extended Normal
Stop
Active/Inactive
Year/Month/Day
Active/Inactive
Year/Month/Day
Factory settings
Low speed
Inactive
Inactive
Time and schedule
Time and date
Schedule settings
GB.GOLDSKFFI.170308
We reserve the right to alter specifi cations without notice.
www.swegon.com 23
GB.GOLDSKFFI.170308
4.3.3 Day schedule
Times and days can be set when the air handling unit is to run in the high speed mode, low speed mode or be switched off.
For each day (Monday - Sunday), six different events can be set to occur at a given point in time. Here, it is also possible to set six different events for two exceptions under
Ex1 and Ex2. The provisions for these exceptions can then be set under Exceptions schedule, Calendar 1 and Calendar 2.
Note that the preset event will not be carried over to the next 24-hour period. If no event is set from 00.00 hours of the next 24-hour period, the AHU will operate in the preselected operating mode preset under Schedule settings.
Settings:
Value Setting range
Day Mon/Tues/Wed/Thurs/Fri/Sat/Sun/Ex1/
Ex2
Time 00:00-23:59
Action Inactive/Total stop/Low speed/High speed/Normal Stop/ Extended Normal
Stop/Ignore
Factory settings
00:00
Inactive
Day schedule
4.3.4 Exceptions schedule
Possible exceptions (Ex1 and Ex2), previously preset in the day schedule can be set in the Exceptions schedule. Here you can determine on which date or weekday the relevant exception shall apply. If you select Calendar 1 or Calendar 2, which is the most often the case, these can be set according to particulars in the next section.
Settings:
Value Setting range
Factory settings
Exceptions schedule 1/2
Exceptions method Inactive/Date/Date range/Weekday/
Calendar 1/
Calendar 2
Calendar
1/2
Date
Start date
Start weekday Each day
Date range
Start date
Start weekday
Stop date
Year/Month/Day
Each day/
Monday/Tuesday/
Wednesday/
Thursday/Friday/
Saturday/Sunday
Year/Month/Day
Each day/
Monday/Tuesday/
Wednesday/
Thursday/Friday/
Saturday/Sunday
Year/Month/Day
Each day
Exceptions schedule
Stop weekday
Weekday
Start date
Start weekday
Calender 1
Calender 2
Each day/
Monday/Tuesday/
Wednesday/
Thursday/Friday/
Saturday/Sunday
Each day
Mon 1-12/Odd/
Even/Each
Day 1-7/8-14/15-
21/22-28/29-31/
Latest 7 days/Each day
Each day/
Monday/Tuesday/
Wednesday/
Thursday/Friday/ saturday/Sunday
See next chapter
See next chapter
Each day
24 www.swegon.com
We reserve the right to alter specifications without notice.
4.3.5 Calendar 1 and 2
The specific days when Exceptions schedule 1 or 2 shall apply can be set in Calendars 1 and 2. On condition that
Calendar 1 or 2 is selected, see previous section. In other cases, these settings will have no effect.
There is a total of ten possible settings under each calendar and various functions can be selected for each.
Settings (For Calendar 1 and Calendar 2 respectively):
Value Setting range
Function 1-10 Inactive/Date/Date range/
Weekday
Date
Start date Year/Month/Day
Start weekday Each day/Monday/Tuesday/
Wednesday/Thursday/Friday/
Saturday/Sunday
Date range
Start date
Stop date
Weekday
Start date
Year/Month/Day
Year/Month/Day
Month 1-12/Odd/Even/Each
Day 1-7/8-14/15-21/22-28/29-
31/Latest 7 days/Each day
Start weekday Each day/Monday/Tuesday/
Wednesday/Thursday/Friday/
Saturday/Sunday
Factory setting
Inactive
Each day
Each day
4.3.6 Prolonged operation
The control unit inputs for external low speed (terminals 14-15) and external high speed (terminals 16-17) respectively, can be supplemented with Prolonged operation. They can be used for overtime running activated by a pushbutton, for example.
The required time in hours and minutes can be set as follows.
Settings:
Value
Ext. low speedt
Ext. high speed
Setting range
0:00 - 23:59
0:00 - 23:59
(hrs.:min.)
Factory setting
00:00
00:00
(hrs.:min.)
Calendar 1
Calendar 2
Prolonged operation
GB.GOLDSKFFI.170308
We reserve the right to alter specifications without notice.
www.swegon.com 25
GB.GOLDSKFFI.170308
4.4 Energy monitoring
Readings of the power consumed by fans and other AHU components can be viewed here. SFP readings for the AHU fans and the effi ciency on heat transfer of the rotary heat exchanger can also be viewed. Accumulated energy consumption can be reset to zero.
4.5 Filters
Status
The current fi lter status and the current alarm limit can be viewed here. Used for performance checks.
Calibration
The fi lters should be calibrated when the fans are started up for the fi rst time and when the duct system, air terminals and commissioning plates, if required, have been installed and commissioned. After that every time fi lters are replaced. See also Section
3.
Pre-fi lter/AHU fi lter (GOLD SD)/End fi lter
Filter monitoring must be activated for the fi lter (in addition to the internal fi lter in the GOLD RX/PX/CX) to be monitored.
Settings:
Factory setting
Inactive
Value
Pre-fi lter
AHU fi lters
Setting range
Inactive/Supply air/Extract air/
Supply air and extract air
Inactive/Supply air/Extract air/
Supply air and extract air
On/Off End fi lter
Alarm limits
Alarm limit for installed fi lters can be changed.
Setting:
Value
Installed fi lters
Setting range
0-500 Pa
Inactive
Off
Factory setting
100 Pa
4.6 Software
The current program versions for the IQlogic control unit,
IQnavigator hand-held terminal and the component units on the communications bus can be viewed and updated from the SD circuit card.
4.7 Language
The language desired can be set here. The appropriate language is normally selected the fi rst time the AHU is started up. However, the language setting can be changed at any time.
Settings:
Value
Language
Setting range
Available languages are displayed
Factory setting
English
Energy monitoring
Filters
Software
Language
26 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.8 Alarm settings
4.8.1 Fire alarms
Internal fi re alarm
The air handling unit’s internal temperature sensors serve as fi re protection thermostats. An alarm is initiated if the supply air temperature sensor registers more than 70 °C or when the extract air temperature sensor registers more than 50 °C.
If an external Extract air/Room temperature sensor is connected and activated, this works parallel with the extract air temperature sensor of the AHU.
External fi ree alarm 1 and 2
External fi re alarm 1 (Terminals 6-7) and external fi re alarm 2
(Terminals 8-9) are used for external fi re-control equipment.
Alarm reset
The resetting of internal fi re alarms as well as the external fi re alarms 1 and 2 can be individually selected to manual or automatic.
After cool
The After cool function for electric air heaters can be individually activated, for internal fi re alarms as well as external fi re alarms 1 and 2.
Fan operation at fi re alarm
The fans of the air handling unit can be used for evacuating smoke, etc. It is possible to individually select the type of fan operation for each separate fi re alarm.
If the AHU is idle, the fans selected start up (10-100%), irrespective of whether stop (all types) is activated.
The AHU's damper relay is energized and the AHU's operation relay is de-energized. The damper that should be open in event of fi re, shall be connected to the damper relay (control unit terminals 28-30). The damper that should be closed in event of fi re, shall be connected to the operation relay (terminals 26-27 of the control unit, potential-free contact).
Priority
The mutual priority of the internal and the external fi re alarms can be set. If automatic is selected, this means that the fi rst input to be activated is given priority.
Alarm settings
Fire alarms
Settings:
Value
Internal fi re alarm
Internal fi re alarm reset
Internal fi re alarm after cool
External fi re alarm 1/2, resetting
External fi re alarm 1/2, after cool
Fan operation on an internal fi re alarm
Supply air fan on an internal fi re alarm
Extract air fan on an internal fi re alarm
Fan operation on external fi re alarm 1/2
Supply air fan on external fi re alarm 1/2
Extract air fan on external fi re alarm 1/2
Order of priority
Setting range
On/Off
Manual/Auto
Active/Inactive
Manual/Auto
Active/Inactive
Inactive/Supply air/
Extract air/Supply air and extract air
10-100%
10-100%
Inactive/Supply air/
Extract air/Supply air and extract air
10-100%
10-100%
Factory settings
Off
Manual
Inactive
Manual
Inactive
Inactive
100%
100%
Inactive
100%
100%
External fi re alarm 1/External fi re alarm 2/
Internal fi re alarm/
Automatic
External fi re alarm 1
We reserve the right to alter specifi cations without notice.
www.swegon.com 27
GB.GOLDSKFFI.170308
4.8.2 External alarms
External alarms can be used for external functions (control unit terminals 10-11 and 12-13).
Typical uses:
– Motor protection for the circulation pump in the heating or cooling circuit.
– Service alarm actuated by smoke detectors.
Set the following: Manual or automatic alarm reset, post-cooling for electric air heater and whether the alarm shall be activated on a closed or open circuit. The alarm can be time delayed.
Settings:
Value Setting range
Factory setting
External alarm 1 reset
External alarm 1 after cool
External alarm 1 input
Manual/Auto
Inactive/Active
Closed circuit/
Open circuit
0-600 sec.
Manual
Active
Closed circuit
10 sec.
External alarm 1 delay time
External alarm 2 reset
External alarm 2 after cool
External alarm 2 input
Manual/Auto
Inactive/Active
Closed circuit/
Manual
Active
Closed
External alarm 2 delay time
Open circuit
0-600 sec.
circuit
10 sec.
External alarms
4.8.3 Temperature protection
In the GOLD PX and CX units, the sensor in the inlet of the supply air fan can be used as temperature protection. Alarm priority and whether the AHU shall stop or not in event of an alarm can be set under Alarm priority, se Section 4.8.6.
For the GOLD RX unit, it is possible to use a separate sensor and its wiring is routed to the control unit. Select sensor input 4 for supply air = right and select sensor input 3 for supply air = left.
The alarm limit and alarm delay can be set for the sensor.
Settings:
Value
Temperature protection
Alarm delay
Alarm limit
Setting range
On/Off
1-900 sec.
3 – +20°C
Factory settings
Off
30 sec.
7°C
Temperature protection
28 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.8.4 Temperature alarm limits
Changes in the factory-preset alarm limits should only be made if you have special reasons for doing so and you should be aware of the consequences.
Pre-heating below set point
You can preset how much the temperature downstream of the pre-heater should be permitted to be below the temperature set point before an alarm is initiated.
Supply air below/above set point
You can preset how much the supply air temperature shall be permitted to be below or above the supply air temperature set point before an alarm is initiated. The alarm for supply air above the set point is normally blocked. Used in the cases in which cooling is installed.
Extract air below alarm limit
Alarm limit for extract air temperature can be set. When the extract air temperature is below the alarm limit, alarm 12:6 is generated.
Outdoor temperature, stop limit
On tripped heat exchanger alarms, alarm numbers: 15:1-15:4,
16;1-16:4, 17:1, 17:4-17:9 (See the Manual for alarms and information messages), the following applies: if the outdoor air temperature is above this stop limit, an alarm only will be initiated and if it is below the stop limit, the AHU will stop and an alarm will be initiated.
Settings:
Value Setting range
Pre-heat below set point
Supply air below set point
Supply air above set point
2 - 15 K
2 - 15 K
2 - 15 K
Extract air below alarm limit -8 - +20 °C
Outdoor temperature limit stop -40 – +50 °C
Factory setting
5.0 K
5.0 K
7.0 K
12,0 °C
5.0 °C
Temperature alarm limits
4.8.5 Service period
The air handling unit's service period can be set here. The remaining time to alarm can be read. An alarm will be initiated after the time interval has expired. If you reset the alarm in the alarm log, the alarm will trip again after 7 days. Following completed service, the alarm must always be reset in this menu and this will launch a new service interval.
Settings:
Value
Service period
Setting range
0 – 99 months
Factory setting
12 months
Service period
We reserve the right to alter specifications without notice.
www.swegon.com 29
4.8.6 Alarm priority
Changes in alarm priority should only be made if you have special reasons for doing so and you should be aware of the consequences. The priority of certain alarms cannot be changed.
Settings:
Value
Alarm number
Active
Priority
Air handling unit stop
Setting range
1:1 - 60:10
On/Off
Info*/A/B
On/Off
* Alarms are indicated as a flashing red LED on the hand-held terminal, no group alarm is forwarded.
Alarm priority
GB.GOLDSKFFI.170308
30 www.swegon.com
We reserve the right to alter specifications without notice.
4.9 Log
An SD card must be fi tted into the AHU's control card for the log function to work (2 GB SD cards are installed from the factory, 8
GB SD cards can be ordered as accessories).
4.9.1 Continuous log
The continuous log can be activated here. The login interval is one minute (1440 logins per 24-hour period). One login fi le is created for each 24-hour period.
Settings:
Value
Log fi le period
Setting range
On/Off
Factory settings
On
4.9.2 Log sender
The log function has a log sender function which can e-mail the log to an optional e-mail address and/or FTP address.
Settings:
Value
Log sender active
Live mode
Setting range
On/Off
E-mail/FTP/E-mail and FTP
Other settings can be entered in the AHU's web page.
Factory setting
Off
Log
Continuous log
Log sender
GB.GOLDSKFFI.170308
We reserve the right to alter specifi cations without notice.
www.swegon.com 31
GB.GOLDSKFFI.170308
4.10 Air handling unit
4.10.1 Settings
Set the type of air handling unit here. The type of air handling unit is normally preset for the unit supplied; except the GOLD SD extract air unit which must be set here.
N.B.! Do not change the air handling unit setting to a type that differs from the one supplied. If you do so, the air handling unit will not operate satisfactorily.
The air handling unit can be given a specifi c name (e.g. the unit's serial number). Naming in the hand-held terminal can only be done with digits, however on the web page the naming can also be done with alphabetical characters. The given name is then shown in all the images in the hand-held terminal and web page.
The type of AHU, size of the supply air and extract air fan respectively can be viewed.
GOLD RX/PX/CX
The AHU’s fan position 1 (left-hand fan seen from the inspection side, see illustrations) can be read and preset.
N.B.! This changes the function of the fans from supply air to extract air and vice versa. GOLD RX size 004-120/
GOLD RX Top can be changed at the site. The other variants must not be changed from the factory setting.
The fan position in the fl ow chart can be read and should be set according to the AHU's actual confi guration.
GOLD SD
The fan position, upper or lower level, can be read and should be set according to the AHU’s actual confi guration.
Settings:
Value
Type of air handling unit
GOLD RX/PX/CX
Name
Fan position 1
Flow chart, supply air fan position
GOLD SD
Name
Flowchart fan position
Setting range
GOLD RX/GOLD
PX/GOLD CX/
GOLD SD Supply air/GOLD
SD Extract air/
GOLD SD Supply air+CX/
GOLD SD Supply air+Extract air/
GOLD SD Supply air+Extract air+CX
Factory setting
Type of air handling unit supplied, except the GOLD
SD extract air handling unit
Optional
Extract air/
Supply air
Upper level/
Lower level
Optional
Upper level/
Lower level
Extract air
Lower level
Lower level
Air handling unit
Settings
GOLD RX 004-040
Fan arrangement 1
Fan pos. 1 set as extract air
(right-hand inspection side)
Fan arrangement 2
Fan pos. 1 set as extract air
(right-hand inspection side)
GOLD RX Top
Fan pos. 1 set as supply air
(left-hand inspection side)
Outdoor air Supply air
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as extract air
(right-hand inspection side)
Extract air Exhaust air
32 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.10.2 Fan status
The fan control speed setting can be viewed in percent of max. speed here.
4.10.3 Operation time
In operation times (in days) can if applicable be viewed for fan controls, heat exchanger/cooling recovery, preheating, extra heating regulation sequence, Xzone heating, AHU reheating,
ReCO
2
heating, extra cooling regulation sequence, Xzone cooling, AHU cooling, ReCO cooling water.
2
cooling, AYC heating water and AYC
4.10.4 VOC/CO
and the CO
2
sensor
unit. The VOC level can be read. The VOC sensor position in the flow chart can be selected if only monitoring has been selected.
2
You can select here the operating mode for the VOC sensor
Settings:
Value
VOC sensor mode
CO
2
unit 1)
Flow chart, VOC sensor position
Setting range
Inactive/Monitoring only/Monitoring and regulation
%/ppm
Supply air/
Extract air
Factory setting
Inactive
% 1)
Supply air
1) Factory set values: 0% = 500 ppm, 50% = 1000 ppm, 100% =
1500 ppm
Fan status
Operation time
VOC/CO
2
sensor
4.10.5 Automatic functions
Start up sequence
The air handling unit has a start up sequence with a factorypreset time delay between each step as follows:
1. The damper relay is energized and opens the shut-off damper
(if installed). The heat exchanger is controlled to max. heat recovery (not the GOLD SD without heat exchanger). The valve for reheating opens to 40% (if installed)
Time delay: 30 seconds.
2. The extract air fan starts in the current operating mode (not for ventilation systems with GOLD SD supply air handling unit only)
Time delay: 60 seconds.
3. The supply air fan starts (not for ventilation systems with
GOLD SD extract air handling unit only)
Time delay: 30 seconds.
4. The reheating function is ramped up or down depending on the heating load. Ramp time: 180 seconds. After that the heat exchanger is ramped up or down depending on the heating load. Ramp time: 180 seconds.
The entire start up sequence can be followed in the dashboard image.
The start up sequence prevents the extract air fan from starting up if the shut-off damper is closed. By first starting up the extract air fan and the heat exchanger, you can avoid chilling the premises with supply air on a start up under cold weather conditions.
Zero point calibration
The pressure sensor of the AHU is automatically calibrated. The calibration process takes about 70 seconds after the AHU has stopped (a notification is shown if the AHU has not stopped).
The zero point calibration text is displayed in the hand-held terminal. The fans cannot start while calibration is in progress.
We reserve the right to alter specifications without notice.
www.swegon.com 33
4.11 Heat
4.11.1 Status
All the relevant values can be read here. Used for performance checks.
4.11.2 Pre-heat
By preheating the outdoor air, it is possible to prevent moisture precipitation in the AHU's outdoor air fi lter, to reduce the risk of frosting in the heat exchanger and to eliminate the risk that pressure sensors and motor control systems are operating in too low ambient temperature.
Scope for setting Outdoor air temperature related preheat is available.
See also the Pre-heat function guide for more detailed information.
Settings:
Value Setting range
Pre-heat
Pre-heat set point
Outdoor air temperature related
On/Off
-40 – +40°C
On/Off
Difference, outdoor air temperature
0 – 25 K
Preheat, min. limit -40 – +40 °C
Periodic operation of pump On/Off
Periodic operation of valve On/Off
Periodic operation interval 0-168 hrs.
Periodic operation period
Alarm input, function
0-60 min.
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Factory setting
Off
5°C
Off
5 K
-10 °C
On
On
24 hrs.
3 min.
Inactive
Heat
Status
Pre-heat
GB.GOLDSKFFI.170308
34 www.swegon.com
We reserve the right to alter specifi cations without notice.
4.11.3 Extra regulation sequences 1 and 2
Used for extra regulation functions controlled by a 0-10 V (10-0
V) signal with ordinary temperature regulation sequence.
The function can be used for utilising existing heating or cooling sources, such as from a chiller. The function can also be used for an extra air heater or air cooler.
It can also be used for controlling dampers for recirculation, if required. In these cases, an inverted 10-0 V output is used.
Recirculation control is used for the TBBD mixing section (GOLD
SD only) The 10-0 V inverted output should be in the On position.
The maximum output signal can be limited from 100% down to
0 %.
The output signal of the extra regulation sequence is controlled from the TBIQ-3-2 IQlogic + lation instructions.
module accessory, see separate instal-
When the SMART Link DX function is selected, the extra regulation sequence is automatically activated. The extra regulation sequence cannot then be used for any other functionality. An
IQlogic+ module is not required (alarm for missing module is blocked).
The extra regulation sequence makes it possible to control two air heaters at the same time in the following combinations: water - electricity, water - water, electricity - electricity (Season heat, see also Section 4.11.7). The air heater for hot water is available without or without frost guard function.
When the output of the first air heater is not sufficient, the second is automatically brought into the sequence.
A start-up sequence, frost guard function, pump control, postcooling for electric air heater and other functionality are available.
For the start-up sequence, frost guard function, periodic operation and post-cooling, the same settings are used as for regular reheating.
Settings:
Value Setting range
Extra regulation sequence Inactive/Heat/Cool/
1/2
Inverted output 10-0V
Recirculation control
Max. output signal
Periodic operation interval 0-168 hrs.
Periodic operation period
Pump alarm
Heat and cool
On/Off
On/Off
0-100%
Periodic operation of pump On/Off
Periodic operation of valve On/Off
0-60 min.
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Factory setting
Inactive
Off
Off
100%
On
On
24 hrs.
3 min.
Inactive
Extra regulation sequence 1/2
GB.GOLDSKFFI.170308
We reserve the right to alter specifications without notice.
www.swegon.com 35
GB.GOLDSKFFI.170308
4.11.4 Reheat
The air heater is equipped with a quick-fit connector for connection to the AHU's control unit which automatically senses the type of air heater in use.
Air heater for hot water
When there is a reheating load, and the function Periodic operation of pump or of pump+valve is selected , the relay output is activated (control unit terminals 20-21) and this starts the circulation pump of the air heater.
If the outdoor temperature is low (colder than +12 °C), the pump output contact is continuously activated. During other times, the pump output contact is activated 3 min./day (factory setting) for periodic operation the circulation pump.
Settings:
Value Setting range
Air heater for hot water
Periodic operation of pump On/Off
Periodic operation of valve On/Off
Periodic operation interval 0-168 hrs.
Periodic operation period 0-60 min.
Factory setting
On
On
24 hrs.
3 min.
Electric air heater
When there is a reheating load, the relay output is activated
(control unit terminals 20-21).
The relay output can be used for indicating or blocking the external function.
Reheat
4.11.5 Xzone
The Xzone temperature control function is designed for controlling one extra temperature zone via the ventilation system.
Xzone can be used for all types of air handling units, and both reheating and cooling can be controlled in the extra zone.
See also the Xzone function guide for more detailed information.
Settings:
Value Setting range
Xzone
Air heater for hot water
On/Off
Periodic operation of pump On/Off
Periodic operation of valve On/Off
Periodic operation interval 0-168 hrs.
Periodic operation period
Alarm input, function
0-60 min.
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Factory setting
Off
On
On
24 hrs.
3 min.
Inactive
Xzone
36 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.11.6 Electric air heater
If the electric air heater has been in operation, the air heater is post-cooled for about 3 minutes (factory setting) when stop has been activated.
The text “After cool” appears in the hand-held terminal.
Settings:
Value
After cool
Setting range
1 - 25 min
Factory setting
3 min.
Electric air heater
4.11.7 Season Heat
The Season Heat function involves that the extra regulation sequence 1 functions is activated. See Section 4.11.3.
When both the standard function for reheating and the extra heating sequence are activated, it is possible to alternate between these via a digital input or communication.
Example: Hot water is only available in the winter. In the summer, any reheating load is backed up by an electric air heater. Changeover can be done manually or via external thermostat, external clock function or the like.
Settings:
Value
Season Heat
Extra reg. seq. enabled
(manual only)
Setting range
Inactive/Extra reg. seq. 1 closed contact/
Extra reg. seq. 1 open contact/Extra reg. seq. 1 Manual
On/Off
2)
1)
Factory setting
Inactive
Off
Season Heat
1) Extra regulation sequence 1 closed contact = When the contact is closed, only the standard reheating function is active. When the contact is opened a changeover to extra heating regulation sequence occurs.
Extra regulation sequence 1 open contact = When the contact is open, only the standard reheating function is active. When the contact is closed, a changeover to extra heating regulation sequence occurs.
Extra regulation sequence 1 Manual = Changeover is done in the hand-held terminal or on the AHU's web page.
2)
Extra regulation sequence in Off position involves that the standard function for reheating is active and in the On positin a changeover to extra regulation sequence occurs.
4.11.8 Automatic functions
Frost guard function, air heater for water
The frost guard function is always active if the connected air heater for hot water has been supplied by Swegon.
The function activates a heating device that keeps the temperature in the coil at 13 °C while the air handling unit is operating and 25 °C in the coil when the unit is stopped. An alarm is initiated and stops the AHU if the temperature sensor senses a temperature below 7 °C.
Capacity reduction of the electric air heater
Only in combination with Swegon's electric air heater.
A min. permissible air velocity of 2.0 m/s is required for preventing the electric heating elements from becoming overheated when they are generating full heating output.
If the air handling unit supply airflow drops below the value that corresponds to an air velocity of 2.0 m/s across the heat exchanger, the heating output of the air heater will be automatically reduced.
We reserve the right to alter specifications without notice.
www.swegon.com 37
4.12 Cool
4.12.1 Status
All the relevant values can be read here. Used for performance checks.
4.12.2 Extra regulation sequences 1 and 2
Used for extra regulation functions controlled by a 0-10 V (10-0
V) signal with ordinary temperature regulation sequence.
The function can be used for utilizing existing heating or cooling sources, such as from a chiller. The function can also be used for an extra air heater or air cooler.
It can also be used for controlling dampers for recirculation, if required. In these cases, an inverted 10-0 V output is used.
Recirculation control is used for the TBBD mixing section (GOLD
SD only) The 10-0 V inverted output should be in the On position.
The maximum output signal can be limited from 100% down to
0 %.
The output signal of the extra regulation sequence is controlled from the TBIQ-3-2 IQlogic
+
module accessory, see separate installation instructions.
When the SMART Link DX function is selected, the extra regulation sequence is automatically activated. The extra regulation sequence cannot then be used for any other functionality. An
IQlogic+ module is not required (alarm for missing module is blocked).
Settings:
Value Setting range
Extra regulation sequence
1/2
Output inverse 10-0V
Recirculation control
Inactive/Heat/Cool/
Heat and cool
On/Off
On/Off
Max. output signal 0-100%
Periodic operation of pump On/Off
Periodic operation of valve On/Off
Periodic operation interval 0-168 hrs.
Periodic operation period
Pump alarm
0-60 min.
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Factory setting
Inactive
Off
Off
100%
On
On
24 hrs.
3 min.
Inactive
Cool
Status
Extra regulation sequence 1/2
GB.GOLDSKFFI.170308
38 www.swegon.com
We reserve the right to alter specifi cations without notice.
4.12.3 Cool
The valve actuator of the air cooler for water is equipped with a quick-fit connector for connection to the AHU's control unit which automatically activates the cooling function.
1-step
Used if cooling in one step is connected. The cooling controller of the AHU regulates the cooling output according to the cooling load, 0-100 %. The cooling relay is energised when the cooling load exceeds 5 % and is de-energised when the cooling load is below 2 %.
2-step
Used when cooling in 2 steps is connected. The cooling controller of the AHU regulates the cooling output according to the cooling load, 0-100 %.
Cooling relay 1 is energised when the cooling load exceeds 5
% and is de-energised when the cooling load is less than 2 %.
Cooling relay 2 is energised when the cooling load exceeds 55 % and is de-energised when the cooling load is less than 50 %.
3-step, binary
Used when cooling with two inputs controlled with three binary steps is connected. The cooling controller of the AHU regulates the cooling output according to the cooling load, 0-100 %.
On an increasing cooling load:
Cooling relay 1 is energised when the cooling load is above 5
% and is de-energised when the cooling load is between 40-70
%. Cooling relay 2 is energised when the cooling load is above
40 %. Cooling relay 1 is energised again (together with cooling relay 2) when the cooling load is above 70%.
On a decreasing cooling load:
Cooling relay 1 is deenergised when cooling load is below 60 %, it is energised again when cooling load is below 30 % and is deenergised again when cooling load is below 2 %. Cooling relay 2 is de-energised when cooling load is below 30 %.
Settings:
Value Setting range
DX air cooler
Cooling Inactive/1 step/2 steps/3 steps, binary
Air cooler for water
Periodic operation of pump 1 On/Off
Periodic operation of pump 2 On/Off
Periodic operation of valve
Periodic operation interval
On/Off
0-168 hrs.
Periodic operation period 0-60 min.
Factory setting
Inactive
On
On
On
24 hrs.
3 min.
Cool
GB.GOLDSKFFI.170308
We reserve the right to alter specifications without notice.
www.swegon.com 39
GB.GOLDSKFFI.170308
4.12.4 Xzone
The Xzone temperature control function is designed for controlling one extra temperature zone via the ventilation system.
Xzone can be used for all types of air handling units, and both reheating and cooling can be controlled in the extra zone.
See also the Xzone function guide for more detailed information.
Settings:
Value Setting range
DX air cooler
Cooling Inactive/1 step/2 steps/3 steps, binary
Air cooler for water
Periodic operation of pump 1 On/Off
Periodic operation of pump 2 On/Off
Periodic operation of valve
Periodic operation interval
On/Off
0-168 hrs.
Periodic operation period
Alarm input 1, function
Alarm input 2, function
0-60 min.
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Inactive/Alarm on open contact/
Alarm on closed contact/Contactor function
Factory setting
Inactive
On
On
On
24 hrs.
3 min.
Inactive
Inactive
Xzone
4.12.5 COOL DX
COOL DX - Economy (without heat exchanger)
Used when the COOL DX chiller is connected. Both cooling relays of the air handling unit operate in parallel with the corresponding relay on the IQlogic
+
module in the COOL DX chiller.
COOL DX - Comfort
Used when the COOL DX chiller is connected. The heat exchanger in the AHU operates in sequence with the cooling unit to even out the supply air temperature.
COOL DX Top
Used when the COOL DX Top chiller is connected. Both cooling relays of the air handling unit operate in parallel with the corresponding relay on the IQlogic + module in the COOL DX chiller.
Settings:
Value
COOL DX
Setting range
Inactive/Economy/
Comfort/COOL DX Top
Factory setting
Inactive
COOL DX
40 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFFI.170308
4.12.6 Delay time
Restart time is computed from when the compressor starts until it is permitted to start again.
Step switch time is the time delay between two steps.
Stop/start time is computed from when the compressor stops until it is permitted to start again.
Settings:
Value
Restart time
Step switch time
Stop/start time
Setting range
0-20 min.
0-15 min.
0-15 min.
Factory setting
5 min.
5 min.
5 min.
4.12.7 Outdoor air limits
Provision is available for setting an outdoor temperature-related blocking function in 3 steps. If the outdoor temperature is below each step limit, the function of the cooling relays will be blocked.
The function is used for preventing the relevant compressors from being switched on and off too many times.
Settings:
Value
Step 1
Step 2
Step 3
Setting range
0 - 30°C
0 - 30°C
0 - 30°C
Factory setting
15°C
18°C
20°C
4.12.8 Airflow, limits
Cooling, 0-10 V:
The cooling function is blocked if the supply or extract airflows are lower than the preset limit.
If the airflow limit function is not of immediate interest, both flow limits are set to 0.
Cooling, On/Off:
The current airflow must exceed the preset airflow as a condition for the respective cooling step to be put into operation.
Settings:
Value Setting range
Factory settings
Cooling, 0-10 V
Supply air, 0-10 V
Extract air, 0-10 V
Cooling, On/Off
Supply air, On/Off, step 1
Extract air, On/Off, step 1
Supply air, On/Off, step 2
Extract air, On/Off, step 2
Supply air, On/Off, step 3
Extract air, On/Off, step 3
0 - Max. flow 25% of max. airflow for air handling unit
0 - Max. flow 25% of max. airflow for air handling unit
0 - Max. flow 25% of max. airflow for air handling unit
0 - Max. flow 25% of max. airflow for air handling unit
0 - Max. flow 50% of max. airflow for air handling unit
0 - Max. flow 50% of max. airflow for air handling unit
0 - Max. flow 75% of max. airflow for air handling unit
0 - Max. flow 75% of max. airflow for air handling unit
Delay time
Outdoor air limits
Air flow limits
We reserve the right to alter specifications without notice.
www.swegon.com 41
4.13 Heat/Cool recovery
4.13.1 Status
All the relevant values can be read here. Used for performance checks.
Heat/Cool recovery
Status
4.13.2 Carry over control
If the fans are generating low airfl ows, the rotary heat exchanger is decelerated to an appropriate speed to ensure a correct purging airfl ow through the heat exchanger.
Settings:
Value
Carry over control
Setting range
On/Off
Factory setting
Off
Carry over control
GB.GOLDSKFFI.170308
4.13.3 Effi ciency measurement
The effi ciency measurement of heat exchangers for RX/PX/CX can be enabled here.
The function requires two extra sensors, TBLZ-2-31-2 (extract air) and TBLZ-2-31-4 (exhaust air) which measure temperature and humidity. See the separate installation instructions.
Measured values are specifi ed under the humidity function.
Settings:
Value
Effi ciency measurement
Setting range
On/Off
Factory setting
Off
Effi ciency measurement
42 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.13.4 Defrost
In environments where the extract air can occasionally be humid, the defrosting function can be activated to protect the heat exchanger from frosting. The function continuously monitors the condition of the heat exchanger rotor to prevent it from becoming clogged due to condensate that has frozen inside the exchanger.
The function requires a separate pressure sensor (preset for heat exchanger defrosting) wired to the control unit inputs for external BUS communication and connected to the AHU pressure measurement tappings. See special installation instruction for the
TBLZ-1-23-aa pressure sensor.
The pressure drop across the rotor must then be calibrated to establish a reference pressure drop for monitoring purposes.
Calibration is put into effect by setting Calibration to the On position.
When the defrosting function is activated the pressure drop across the heat exchanger is continuously measured and the reading is compared with the calibration reading. If the pressure drop exceeds the preset limit value, a defrosting sequence is implemented in which the rotor speed is gradually ramped down
(ramp time max. 4 minutes) to the speed at which the pressure drop across the heat exchanger decreases to half of the preset limit value. The lowest permissible speed of the rotor is 0.5 rpm.
During the defrosting process, the warm extract air thaws any possible ice that has formed on surfaces. A delay time of 4 minutes gives the heat exchanger time to dry, before the rotor once again is ramped up (ramp time max. 4 minutes) to its ordinary speed.
The defrosting operates for a max permissible period of 30 minutes. If the pressure drop has not decreased within that max permissible period after six tries during a 24-hour period, an alarm will be initiated.
Note that the heat exchanger performs less efficiently while defrosting is in progress and that the supply air temperature will also drop downstream of the heat exchanger.
Settings:
Value
Defrost
Defrost limit value
Calibration
Setting range
On/Off
30 - 100 Pa
On/Off
Factory setting
Off
50 Pa
Off
Defrost
Extract air
Connection principle for the defrosting function with separate pressure sensor.
We reserve the right to alter specifications without notice.
www.swegon.com 43
GB.GOLDSKFFI.170308
4.13.5 Calibration/Optimization
(GOLD PX)
Defrosting, Standard
When the air handling unit is started up or if needed, a calibration should be carried out. When calibration is in progress, the air handling unit's limit values for alarms and defrosting are calculated.
Defrosting, RECOfrost
When the air handling unit is started up or if needed, a calibration should be carried out. When calibration is in progress, the air handling unit's limit values for alarms and defrosting are calculated.
When the air handling unit is started up or if needed, bypass optimization should be carried out. When bypass optimization is in progress, the damper positions of the bypass are optimized.
Calibration and bypass optimization can be activated to occur at the same time or individually. If they are activated individually, whichever one is activated first is of no importance.
Settings:
Value
Calibration
Bypass optimization
(RECOfrost only)
Setting range
On/Off
On/Off
Factory settings
Off
Off
Calibration/Optimization
4.13.6 Automatic functions
GOLD RX (rotary heat exchanger)
Purging function
Purging is an automatic function that prevents the rotary heat exchanger from standing still in the same position for a longer period when no heating is necessary.
Purging operation is activated when the AHU is operating but the heat exchanger rotor is not rotating. The heat exchanger rotor then rotates for 10 seconds every 10 minutes to purge its surfaces clean of impurities.
Calculation of the efficiency
The efficiency is calculated and displayed (0 – 100%).
Calculation of recovered energy
Recovered sensible energy is calculated and the values are displayed (instantaneous and accumulated).
Cooling recovery
Cooling recovery is an automatic function that helps the air handling unit on a cooling load and high outdoor air temperature to utilize the relative "cooling energy" that can be indoors. The heat exchanger rotates at max. speed and in this way recovers the relative cooling energy or chilliness in the extract air.
The conditions for this function to be activated are that there is a cooling demand and that the outdoor temperature is 1 °C higher than the extract air. The function stops when the cooling load ceases to exist or when the outdoor temperature is the same as that of the extract air.
Overtime heat exchanger operation
If the AHU stops, the heat exchanger automatically continues to recover heat for about 1 minute.
It takes a little time for the fans to stop rotating after a stop has been ordered and this prevents the supply air from chilling the premises.
GOLD CX/SD (coil heat exchanger)
Pump control, coil heat exchanger
The pump of the pipework package starts when heat recovery is needed. If heat recovery is not needed for more than 24 hours, the pump is exercised once a day.
Anti-frost protection
In cold weather, and if the extract air is humid, there is risk of frosting in the coil heat exchanger. The GOLD CX/SD is equipped with anti-frosting protection.
The temperature of the liquid circulated to the extract air coil and the humidity in the extract air are measured.
Taking the humidity into consideration, the control system calculates the lowest permissible temperature without risk of frosting inside the coil. The valve in the pipework package is then regulated to prevent the circulated liquid from dropping below this temperature.
GOLD PX (plate heat exchanger)
In cold weather, and when the extract air is humid, there is risk of frosting in the plate heat exchanger. The GOLD PX is therefore equipped with anti-frost protection.
Anti-frost protection, standard
The pressure drop across the heat exchanger and the outdoor air temperature are measured.
With consideration given to the pressure drop across the heat exchanger and the outdoor air temperature, the control system regulates dampers for bypass and heat exchanger (interlinked) in order to prevent the formation of frost.
RECOfrost anti-frost protection
The pressure drop across the heat exchanger, extract air temperature, moisture content in the extract air and outdoor air temperature are measured.
With consideration given to the pressure drop across the heat exchanger, the extract air temperature, the moisture content in the extract air and the outdoor air temperature, the control system individually regulates dampers for bypass and the heat exchanger for section-by-section defrosting without the formation of frost.
44 www.swegon.com
We reserve the right to alter specifications without notice.
4.14 SMART Link
The SMART Link function is intended for use for optimum control of the temperature and operation as well as the reading of alarms and the values for a Swegon chiller/heat pump.
For more information concerning waterborne heat pumps/chillers, see the Guide to the SMART Link/AQUA Link Functions.
For more information concerning DX heat pumps/chillers (Celest
+
LE), see the Guide to the SMART Link DX (GOLD RX only) Functions.
Settings:
Value Setting range
Factory setting
Type of unit Inactive/
Water, heat pump/
Water, chiller/
Water, reversible/
DX, heat pump/
DX, chiller/
DX, reversible
Inactive
Water
Heated water (set point)
Heated water, diff.
Chilled water (set point)
Chilled water, diff.
Outdoor air limit
(not applicable to the chiller)
Optimize
Optimizing cooling regulation speed
Optimizing heating regulation speed
Valve limit, lower
Valve limit, upper
Delay
AQUA Link
Pump alarm
10 - 80°C
1 - 10 K
0 - 20°C
1 - 10 K
1)
1)
-50 – +50°C
On/Off
40°C
3 K
12°C
2 K
-20°C
Off
0.01 - 6.00 K/min 0.3 K/min
0.01 - 6.00 K/min 0.3 K/min
5 - 90%
70 - 100%
30 - 3200
On/Off
Inactive/Alarm on closed contact/
Alarm on open contact/Contactor function
DX
Number of connected units
(Celest
+
)
Comfort mode, duration
1-4
Outdoor air limit
(not applicable to the chiller)
0-180 min
-50 – +50°C
Defrost delay 5 - 900 s
Dead band supply air temp.
0,0 - 5,0K
Stabilization time 60 - 600 s
75
95
60
Off
Inactive
1
30 min
-20°C
180 s
0,0K
240 s
1)
Min. and max. limited by preset values in the chiller/heat pump..
SMART Link
GB.GOLDSKFFI.170308
We reserve the right to alter specifi cations without notice.
www.swegon.com 45
GB.GOLDSKFFI.170308
4.15 Humidity
If the functions Dehumidifying regulation and Humidifying are activated at the same time, Dehumidifying regulation has priority and the possible settings for Humidifying are limited to being the same or lower than the setting for Dehumidifying regulation.
There is a delay of 5 minutes between Dehumidifying regulation having stopped and Humidifying starting up (ande vice versa).
4.15.1 Status
All the relevant values can be read here. Used for performance checks.
Humidity
Status
4.15.2 Humidifying
Evaporative humidifi cation (On/Off)
This function is suitable together with an evaporative humidifi er
(not Swegon).
The function requires the TBIQ-3-1 IQlogic
+
module accessory and one TBLZ-31-2 humidity sensor. See separate installation instructions. Install the humidity sensor in the extract air duct (or in the premises), see drawing.
The humidity in the extract air duct (the premises) is regulated between adjustable start and stop limits.
Steam humidifi cation (0 - 10V)
The function is appropriate for operation together with a steam humidifi er (not supplied by Swegon) and is a variable control system via 0-10 V control signal, as well as a contact function which interlocks the humidifi er if the air handling unit stops, if Summer night cool is used or if the humidity in the supply air exceeds the set point by more than 10%.
The function requires the TBIQ-3-1 IQlogic Plus module accessory and one TBLZ-31-1 humidity sensor accessories (for supply air regulation) or two TBLZ-31-1/2 humidity sensor accessories
(for extract air regulation), see separate installation instructions.
Install the humidity sensors in the extract air duct and the supply air duct respectively. See drawing!
The function keeps the humidity level constant in the extract air duct (the premises) by regulating the humidity in the supply air.
In order to prevent the humidity in the supply air from being too high, it is restricted to a maximum limit.
Alternatively the humidity in the supply air duct can be kept constant by selecting a regulating humidity sensor in the supply air.
The set point cannot be set higher than the max limit. If the dehumidifi cation function is activated, the max limit cannot be set higher than the set point for dehumidifi cation.
Settings:
Value
Humidifying
Setting range
Factory setting
Inactive/On/Off/
0-10V
Inactive
Supply air/Extract air Supply air Regulation sensor
Evaporative
Start
Stop
Steam
Set point
Max. supply air
10 - 95%RH
10 - 95%RH
10 - 95%RH
10 - 95%RH
40%RH
45%RH
30%RH
80%RH
Humidifying
Example, steam humidifi cation
46 www.swegon.com
TBLZ-1-31-2
Humidity sensor, extract air
TBLZ-1-31-1
Humidity sensor, supply air
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.15.3 Dehumidifying
The function is intended for dehumidifying the supply air in order to prevent condensation in the supply air duct or in connected air conditioning products.
The dehumidification regulation function controls the humidity in the supply air duct or the extract air duct by means of an air cooler and an air heater for reheating.
The function requires that an air cooler be mounted upstream of the air heater in the supply air duct. See the example to the right.
If control of the humidity in the supply air duct is required, install a TBLZ-1-31-1 humidity sensor in the supply air duct. If control of the humidity in the extract air duct is required, install a TBLZ-
1-31-2 humidity sensor in the extract air duct and a TBLZ-1-31-1 humidity sensor in the supply air duct. Connect the sensor to the
AHU. See separate installation instructions.
Cooling energy is emitted to condense the moisture in the supply airflow, which then is heated to the desired supply air temperature. This causes a reduction in the moisture content of the supply air.
The cooling unit used must be sized so that the temperature of the supply air will be below the dew point, otherwise no condensation will arise and no dehumidification will occur.
Settings:
Value
Dehumidification
Supply air - relative humidity
Extract air - relative humidity
Setting range
Inactive/Supply air/Extract air
10-90%RH
10-90%RH
Factory settings
Inactive
50%RH
50%RH
Dehumidifying
Example: Dehumidification regulation
TBLZ-1-31-2 Humidity sensor
Temperature sensor, supply air
TBLZ-1-31-1 Humidity sensor
4.15.4 Humidifier alarm
The alarm input can be selected to closed circuit, open circuit or contactor function.
Settings:
Value
Alarm input
Setting range
Inactive/Closed circuit/Open circuit/Contactor function
1)
Factory setting
Inactive
1)
Closed circuit involves closing the circuit in order to initiate an alarm. Open circuit involves opening the circuit in order to initiate an alarm. Contactor function involves the use of an auxiliary contact from a contactor, which controls the humidifier. The aux. contact is connected to the alarm input.
Humidifier alarm
We reserve the right to alter specifications without notice.
www.swegon.com 47
GB.GOLDSKFFI.170308
4.16 ReCO
The ReCO
2
2
function is designed for ensuring the correct air quality or air temperature, by means of recirculating extract air and minimizing the infl ow of outdoor air.
The function can be used in ventilation systems in which recirculated air intermixture is acceptable.
The function presupposes that the outdoor air damper and the damper in the air recirculation section are equipped with modulating damper actuators.
Lower outdoor air and exhaust air fl ows as well as lower extract air fan speed enable the unit to consume less power. A separate air quality sensor continuously measures the air quality of the ventilation system.
The pressure drop across the rotor must then be calibrated to establish a reference pressure drop for the function. Calibration is put into effect by setting Calibration to the On position.
For more information, see the ReCO
2
function guide.
Settings:
Factory setting
Value Setting range
Regulation mode
CO2/VOC, operating mode
Temperature mode
Inactive/
CO2/VOC /
CO2/VOC and air fl ow boost
Inactive/Heat sequence/Cool sequence/Heat and cool sequence
CO2/VOC
Set point
CO2, set point
VOC, set point
Min. outdoor air
0 - 100%
0 - 10000 ppm
0 - 10000 ppm
1)
Min. exhaust air
Calibration
Temperature
Min. outdoor air
1)
On/Off
1)
Inactive
Inactive
50%
1000 ppm
1500 ppm
25% of max. airfl ow for air handling unit
25% of max. airfl ow for air handling unit
Off
Min. exhaust air
Calibration
1)
On/Off
25% of max. airfl ow for air handling unit
25% of max. airfl ow for air handling unit
Off
1)
The setting range is the same as the AHU's min. - max. settings.
ReCO
2
Exhaust air
Outdoor air
Extract air
Supply air
Pressure sensor for outdoor air measurement
Outdoor airfl ow kept constant by pressure sensor
When the recirculation damper opens the extract air fan speed decreases and vice versa.
48 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.17 All Year Comfort
The All Year Comfort function controls, via control valves, the supply fl ow temperature to the comfort modules, cooling beams, perimeter wall units, etc. The water temperature is measured by two strap-on temperature sensors mounted on the water pipe of each circuit.
All Year Comfort has functions for outdoor compensation, room compensation, night compensation, dew point compensation as well as the monitoring and exercising of pumps and valves.
For more information, see the All Year Comfort function guide.
Settings:
Value
Function
Setting range
Inactive/Cooling water/Heating water/
Cooling water and heating water
Factory setting
Inactive
Chilled water
Chilled water
1)
Outdoor temp compensation
Outdoor temp X1
Outdoor temp X2
Outdoor temp X3
Outdoor temp X4
Chilled water temp Y1
Chilled water temp Y2
Chilled water temp Y3
Chilled water temp Y4
Outdoor temp for pump start
Outdoor temp for pump stop
Room temp compensation
Room temp. set point
Room temp. P-band
Room comp. night block
5 - 30°C
On/Off
-40 – +40°C
-40 – +40°C
-40 – +40°C
-40 – +40°C
5 – 30°C
5 – 30°C
5 – 30°C
5 – 30°C
14°C
12°C
-40 - +40°C 10°C
-40 - +40°C 7°C
14°C
Off
10°C
20°C
25°C
30°C
22°C
18°C
On/Off
0 - 40°C
1 - 10 K
On/Off
Off
21°C
5 K
Off
Night compensation
Night reduction
Time channel 1/2 start of night
Time channel 1/2 end of night
Time channel 1/2 period
On/Off
0 - 10 K
00:00 - 23:59
00:00 - 23:59
Inactive/
Monday/
Tuesday/
Wednesday/
Thursday/Friday/
Saturday/Sunday
Mon - Fri/Mon
- Sun/
Sat - Sun
Dew point compensation
Air fl ow compensation
On/Off
On/Off
Periodic operation pump On/Off
Periodic operation valve exercising On/Off
Periodic operation interval
Periodic operation period
Pump alarm
0-168 hrs.
0-60 min.
Inactive/Alarm on closed contact/Alarm on open contact/
Valve alarm
Contactor function
On/Off
Off
2 K
00:00
00:00
Inactive
Off
Off
On
Off
24 hrs.
3 min.
Inactive
Off
All Year
Comfort
Heated water
Heated water 1)
Outdoor temp compensation
Outdoor temp X1
Outdoor temp X2
Outdoor temp X3
Outdoor temp X4
Heated water temp Y1
Heated water temp Y2
Heated water temperatue Y3
Heated water temp Y4
Outdoor temp for pump start
Outdoor temp for pump stop
Room temp compensation
Room temp. set point
Room temp. P-band
Room comp. night block
Night compensation
Night reduction
Time channel 1/2 start of night
Time channel 1/2 end of night
Time channel 1/2 period
10 - 80°C
On/Off
-40 – +40°C
-40 – +40°C
-40 – +40°C
-40 – +40°C
10 – 80°C
10 – 80°C
10 – 80°C
10 – 80°C
20°C
15°C
-40 - +40°C 15°C
-40 - +40°C 18°C
30°C
Off
-20°C
0°C
5°C
15°C
40°C
30°C
On/Off
0 - 40°C
1 - 10 K
On/Off
On/Off
0 – -10 K
00:00 - 23:59
00:00 - 23:59
Inactive/
Monday/
Tuesday/
Wednesday/
Thursday/Friday/
Saturday/Sunday
Mon - Fri/Mon
- Sun/
Sat - Sun
Air fl ow compensation
Periodic operation pump
On/Off
On/Off
Periodic operation valve exercising On/Off
Periodic operation interval
Periodic operation period
Pump alarm
0-168 hrs.
0-60 min.
Inactive/Alarm on closed contact/Alarm on open contact/
Contactor func-
Valve alarm tion
On/Off
Off
21°C
5 K
Off
Off
-2 K
00:00
00:00
Inactive
Off
On
Off
24 hrs.
3 min.
Inactive
Off
1)
Omitted if the outdoor temperature compensation is selected.
We reserve the right to alter specifi cations without notice.
www.swegon.com 49
GB.GOLDSKFFI.170308
4.18 MIRU Control
Up to ten power roof ventilators with MIRU Control equipment can be connected to one GOLD air handling unit by means of bus communication.
If one or several power roof ventilator(s) is/are stopped via the control panel on the corresponding MIRU Control, the power roof ventilator(s) cannot be started via the GOLD unit hand-held terminal.
The settings in the hand-held micro terminal of the GOLD unit override the settings in the MIRU Control’s control panel.
It is possible in the hand-held micro terminal to select whether the power roof ventilator should be controlled in parallel with the GOLD unit, and whether it should follow the low-speed/ high-speed operating modes of the air handling unit.
The balanced ventilation function can be used if the power roof ventilators are used for variable fl ow. It is then possible to select which power roof ventilator(s) is/are to be included in the function.
In the case of balanced extract air, all the airfl ows of the activated power roof ventilators are added together. The extract airfl ow in the GOLD unit is decreased by the corresponding volume. In this way the supply airfl ow will be the same as the total extract airfl ow and balanced ventilation will be achieved inside the building.
In the case of balanced supply air, all the airfl ows of the activated power roof ventilators are added together. The supply airfl ow in the GOLD unit is increased by the corresponding volume. In this way the supply airfl ow will be the same as the total extract airfl ow and balanced ventilation will be achieved inside the building.
The function presupposes that pressure sensors for fl ow measurement and possible pressure regulation are connected to
MIRO Control.
All the time channels available in MIRU Control can be set separately for each connected power roof ventilator via the GOLD unit hand-held micro terminal. For a description of the function, see the separate Guide to the MIRU Control Functions.
Depending on the function selected in MIRU Control, it is possible to set the desired set point for pressure or fl ow, low speed and high speed, in the GOLD unit hand-held micro terminal.
For a description of the function, see the separate Guide to the
MIRU Control Functions.
MIRU Control
Settings:
Value Setting range
Fan numbers 1 – 10, function
Inactive/Parallel start/
Parallel low speed/high speed/Parallel start and low speed/high speed
Fan numbers 1 – 10, balance function
Inactive/Supply air/Extract air
Fans 1 – 10 low speed 0 – 750 Pa
Fans 1 – 10 low speed
1)
m3/s
Fans 1 – 10 high speed 0 – 750 Pa
Fans 1 – 10 high speed
1)
m3/s
Fans 1 – 10, channel
1 – 4 action
Inactive
Low speed, Mon., Low speed
Tue., low speed Wed., etc.
Low speed, Mon. – Fri.
Start time
Stop time
Low speed, Sat. – Sun.
Low speed, Mon. –
Sun.
High speed Mon., High speed Tue., High speed
Wed., etc.
High speed, Mon. – Fri.
High speed, Sat. – Sun.
High speed, Mon. –
Sun.
00:00-00:00
00:00-00:00
Factory setting
Inactive
Inactive
100
0
200
0
Inactive
00:00
00:00
50 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.19 Inputs/Outputs
Can for example be used if the air handling unit will be controlled/monitored via microprocessor substation or a PLC system.
External operation module 3/6 requires the TBIQ-3-2 IQlogic + module accessory; external communication module A/B/C requires the TBIQ-3-1 accessory. See separate installation instructions.
Settings:
Value Setting range
External operation module 3/6
Digital output 1/2 mode
Inactive/Air handling unit in operation/Air handling unit in auto operation/ Air handling unit in manual operation/Air handling unit in low speed operation/Air handling unit in high speed operation/A alarm/B alarm/Damper relay/Heat exchanger/Heat exchanger defrost/Reheat/
Reheating power reduction/
Heating Boost/Morning Boost/
Intermittent night heat/Airfl ow down regulation/Extra reg. sequence 1/2 heat/Extra reg. sequence 1/2 cool/Cooling/Cooling Boost/Summer night cool/ Supply air fan in operation/Extract air fan in operation/Internal fi re alarm tripped/External fi re alarm 1/
External fi re alarm 2/External fi re alarm 1 or 2/Any fi re
Digital input 1/2 alarm/External fi re alarm 1 with priority/External fi re alarm 2 with priority//Internal fi re alarm tripped with priority/
Preheating
Inactive/Alarm reset/Stop AYC heated water/Stop AYC chilled water
Analogue output 1 Indicates present supply airfl ow, from 0 to air handling unit’s max. speed (%)
Analogue output 2 Indicates present extract airfl ow, from 0 to air handling
Analogue input
1/2* unit’s max. speed (%)
Inactive/Set point displacement/Set point displacement, supply air/Set point displacement, extract air
External communication module A/B/C
External communication module
A/B/C
Temperature sensor no. 1
Temperature sensor no. 2
On/Off
On/Off
On/Off
Factory setting
Inactive
Inactive
Inactive
Off
Off
Off
* If analogue inputs 1 and 2 are both selected for setpoint displacement, only analogue input 1 will be used.
We reserve the right to alter specifi cations without notice.
Inputs/Outputs www.swegon.com 51
GB.GOLDSKFFI.170308
4.20 Communication
The potential for communication and monitoring is integrated as standard into the AHU. The AHU is ready to be connected via EIA-485. See Section 6.2 Wiring Terminal
Connections in the Operating & Maintenance Instructions.
Communication can also be established via Ethernet without software other than an ordinary web browser such as Internet Explorer.
Further information about interfaces, protocols and confi guration is available at www.swegon.se (com).
Communication
4.20.1 External Port B
For communication with network. Specify protocol and settings for Ethernet.
Settings:
Value
DHCP
IP address
(static or dynamic)
Net mask
Default GATEWAY
Primary DNS
Secondary DNS
MAC address
Setting range Factory setting
On/Off Off
10.200.1.1
255.255.255.0
0.0.0.0
0.0.0.0
0.0.0.0
Not adjustable
External Port B
4.20.2 Wireless LAN
The AHU's control unit is, as standard, equipped with Wi-Fi function and can be connected to e.g. a wireless hand-held terminal
(accessory), portable computer or smart phone.
The password can, via the hand-held terminal, be changed to an optional combination of digits. The password and the SSID can also be entered in alphabetical form on the AHU's web page.
To connect to a portable computer or smart phone, note the settings on SSID, password and IP address. Activate Wi-Fi in the portable computer or smart phone and search for the wireless network (with the same name as the SSID). Connect by entering the password.
Open your web browser and update the page. The web browser will then automatically connect to the control circuit card. To log on, write your user name (local or installation), and enter the password (local = 0000, installation = 1111, factory setting).
Settings:
Value Setting range
Wireless LAN
SSID
Password (WPA2-PSK)
1)
IP address
Net mask
MAC address
Channel (frequency band)
On/Off
Optional
Not adjustable
Not adjustable
Not adjustable
5 - 11
Factory setting
Off
GOLD
123456789
192.168.234.1
255.255.255.0
Not adjustable
5
1) Certain smart phones require at least six characters.
Wireless LAN
52 www.swegon.com
We reserve the right to alter specifi cations without notice.
GB.GOLDSKFFI.170308
4.20.3 E-mail
You can select whether the AHU shall handle outgoing e-mail here.
The settings can be entered on the AHU web page. See separate instructions.
There is a button for test transmission.
Settings:
Value
SMTP server
SMTP server
SMTP port number
SMTP username
SMTP password
Encryption
E-mail sender
E-mail reply path
Setting range
External/Internal
Optional address
Optional, to be entered on the web page
Optional, to be entered on the web page
On/Off
Optional, to be entered on the web page
Optional, to be entered on the web page
Factory setting
External
25
Off
4.20.4 EIA-485
Specify protocol and settings for EIA-485.
Settings:
Value
Protocol
Baud rate
Parity
Stopbits
Modbus ID/
Metasys ID/PLA
ELA
Shortest feedback delay
Setting range Factory setting
Inactive/Modbus/EXOline/ Modbus
Metasys N2 Open/LON
4800/9600/19200/38400 9600
None/Even/Odd
1/2
1 - 247
None
2
1
1-255
0 - 100 ms
1
0 ms
4.20.5 Modbus TCP
Specify settings for Modbus TCP.
Settings:
Value
Port number
Approved client IP address
Approved client netmask
Factory setting
502
0.0.0.0
0.0.0.0
EIA-485
Modbus TCP
4.20.6 BACnet IP
Enter the BACnet IP settings.
Settings:
Value
Network number Ext. B
Internal network number A
Device ID
Port number
Factory setting
0
0
0
47808
BACnet IP
We reserve the right to alter specifications without notice.
www.swegon.com 53
4.20.7 EXOline TCP
EXOline can be activated and enter the port number.
Settings:
Value Setting range
Port number
PLA
ELA
1 - 247
1-255
Factory setting
26486
1
1
EXOline TCP
GB.GOLDSKFFI.170308
4.20.8 Operation level communication
It is possible to change the operation level communication here.
Settings:
Value
Operation level communication
Setting range
Inactive/Total stop/Low speed/High speed/Normal stop/ Extended normal stop
Factory setting
Inactive
Operation level ommunication
54 www.swegon.com
We reserve the right to alter specifications without notice.
4.21 Base setting
Used for saving, loading and restoring the settings.
Date and time for the latest saved backup copy can be viewed.
The AHU's settings/communication settings are saved/loaded to/ from the control unit's internal memory or external SD circuit card that can be inserted into the control unit.
The AHU settings involve all settings except communication settings.
Communication settings involve all settings (except AHU settings).
Settings:
Value Alternative
Air handling settings
Export air handling settings Export to local backup/Export to
SD card
Import air handling settings Import from local backup/Import from SD card
Communication settings
Export communication settings
Import communication settings
Export to local backup/Export to
SD card
Import from local backup/Import from SD card
Base setting
GB.GOLDSKFFI.170308
4.22. Users
The requirements for password can be activated here under User level (local). The password is always 0000.
Settings:
Value Setting range
Requirements for user password On/Off
Factory setting
Off
Users
IQnavigator user
We reserve the right to alter specifi cations without notice.
www.swegon.com 55
4.23 Notes
Notes can be read here. Notes can only be written on the AHU's web page.
Notes
4.24 Manual test
NB! Manual test running can cause indoor comfort problems. There is also risk of overloading the system. The responsibility for discomfort and overload rests totally on the person who activates the function.
When you enter manual test, you must select a safe mode or live mode. Safe mode involves stopping the AHU and being able to run each installed function separately or together. In the safe mode the heat exchanger is oversteered in relation to the fan speed. Live mode involves permitting the AHU to continue to operate in the normal operating mode and installed functions can be infl uenced manually. In this live mode the heat exchanger is not oversteered in relation to the fan speed.
Manual test operation can take place for testing the inputs and outputs, fans and heat exchanger, etc.
Used for installation or troubleshooting to test that wired connections and functions operate correctly.
Certain alarms, functions and normal control modes will be blocked while manual testing is in progress.
On a return to the other image groups, the controller resumes normal operation and all settings for manual testing will be terminated.
Each image indicates which functions can be test run.
Manual test
GB.GOLDSKFFI.170308
56 www.swegon.com
We reserve the right to alter specifi cations without notice.
4.25 IQnavigator
(hand-held terminal)
4.25.1 Connect to IQlogic
The method of connection between the IQnavigator and IQlogic can be selected here.
Can be selected as direct (standard cable), DHCP or static IP (requires connection to network), and direct/wireless (requires the
IQnavigator hand-held terminal with WLAN TBLZ-1-71-2 accessory. See separate instructions).
Settings:
Value Setting range
Connect to IQlogic Direct/DHCP/Static IP/
Direct/Wireless
IQnavigator IP address Optional
IQnavigator Netmask Optional
Pre-selected
IQnavigator gateway
IQlogic IP address
Optional
Optional
Factory setting
Direct
4.25.2 Backlight brightness
The hand-held terminal can be set to four different backlight brightness settings.
Settings:
Value
Brightness mode
Setting range
Auto adjust/Low/
Medium/High
Factory setting
Auto adjust
IQnavigator
Connect to IQlogic
Brightness mode
4.25.3 Acoustics
Button sound effects on the hand-held terminal can be activated and the volume can be set in fi ve steps.
Settings:
Value Setting
range
Button sound effects On/Off
Volume 1-5
Factory settings
Off
3
Acoustics
GB.GOLDSKFFI.170308
We reserve the right to alter specifi cations without notice.
www.swegon.com 57
GB.GOLDSKFFI.170308
58 www.swegon.com
We reserve the right to alter specifications without notice.
![](http://s3.manualzz.com/store/data/034315583_1-ed2bfe547f3b0110737a41d8171d5822-210x147.png)
Advertisement
Key Features
- Precise airflow control for optimal comfort
- Advanced temperature regulation for efficient energy consumption
- Customizable schedules and calendar for effortless operation
- Extensive energy monitoring capabilities for informed decision-making
- Comprehensive filter management for improved air quality
- User-friendly interface with intuitive navigation
- Flexible configuration options for tailored solutions
- Advanced alarm and notification system for peace of mind
- Future-proof design with upgradeable software