Power Safety - Power Supply Systems UPS SRL

Power Safety - Power Supply Systems UPS SRL
Power Safety
Protect 3.
Industrial UPS
Protect 3.31 Single Phase output
10 kVA – 60 kVA
Protect 3.33 Three Phase output
10 kVA – 120 kVA
400 V AC input
384 V DC
Uninterruptible Power Supplies (UPS)
Designed for all Industrial applications
Engineering is our Business
• Oil & Gas, Petrochemicals
Offshore, Onshore, Pipelines
UPS solutions engineered by AEG Power Solutions have been
protecting Oil & Gas infrastructure, Power Stations and other
industrial installations for more than 60 years. Protect 3. is
just part of our Protector Product Range of true on-line UPS
suitable for all Industrial applications. See also our Protect 4.,
Protect 5. and Protect 8. ranges.
• Energy and Power
Generation, Transmission, Distribution
• Transportation
Rail, Airports, Shipping
• Water
Desalination, Treatment
Robust and Reliable
Protect 3. is extremely robust, both electrically and mechanically.
It is custom-designed for use in harsh industrial environments.
• Instrumentation & Process Control
Chemicals, Mining, Steel, Paper
Emergency Lightning
• All Industrial applications
PERFECT IN FORM AND FUNCTION
Power Safety
Protect 3.
Industrial UPS
Key features
• Full digital control
䡩 High reliability (no potentiometers)
䡩 High flexibility (software controlled parameters)
䡩 Fast dynamic response
• Ergonomic control unit with multilingual graphical display
(18 languages)
• High efficiency even at low output power
䡩 Reduced operating costs
䡩 Reduced air conditioning requirements
䡩 Reduced battery Ah requirements
• Oversized components
䡩 Higher reliability and MTBF
䡩 High overload capacity
• Output isolation transformer
• Standardized modules
• Low maintenance
• Short circuit resistant
• More EMC robust than UPS Standard IEC 62040-2
by a factor of 2 to 3
• Capable of communicating with computer and
control systems (SCADA, ESD, DCS, BMS)
䡩 Modbus/JBus
䡩 Profibus
䡩 Monitoring software
䡩 Ethernet, SNMP …
• System and alarm status via voltage-free contacts
• Complete system
Protect 3. is a true on-line double conversion UPS
classified as VFI SS 111 according to IEC 62040-3.
• This outstanding UPS range features
䡩 On-line operation ensuring permanent service
䡩 Microprocessor-driven control and command system to provide
reliable power supply
• 䡩 A battery management system that boosts life time and cuts
operating costs
• 䡩 A broad range of output power ratings, battery autonomies
and options to meet the needs of complex industrial
applications.
• The UPS offers a very high level of protection for users and
connected equipment
䡩 High intermittent overload capacity
䡩 High level short circuit strength
䡩 N-conductor with fulI loading capacity (3 phase systems)
䡩 Excellent dynamic response can easily handle high cyclic loads.
• Redundant controls
䡩 Separate microprocessors for Rectifier, Inverter,
Static Switch and Communication
• 䡩 Separate and redundant power supplies for control cards
• Redundant and individually monitored fans
• High protection degree (IP rating) possible
䡩 Ready for harsh environment
• Intelligent Battery management, test and status diagnostics
• Compatible with vented Lead Acid, Valve Regulated Lead Acid
(VRLA) and Nickel Cadmium batteries
• Designed to operate with Diesel Generators
• Strong mechanical design
• Frequency converter operation
• Remote monitoring and control capabilities
(programmable)
• EcoMode+ (Protect 3.33 as option)
Protect 3.: Specification
Single phase output
MODEL
Nominal rating
(at cos ϕ 0.8 lag) in kVA
P3.31-10
P3.31-20
P3.31-30
P3.31-40
P3.31-60
10
20
30
40
60
66
98
6 pulse
12 pulse
6 pulse
12 pulse
RECTIFIER UNIT
Input nominal voltage
Input operating range (min./max.)
Frequency
Input current in A at nominal load
Charging characteristic to IEC 478-10
Nominal DC voltage
Rectifier type
- Standard
- Optional
17
33
6 pulse
Mains filter
6 pulse
Mains filter
3 x 400 V (3 x 380 V, 3 x 415 V)
340 V– 460 V
50/60 Hz ±10 %
50
IU
384 V
6 pulse
Mains filter
INVERTER UNIT
DC input
Nominal AC voltage
Output voltage static response
Output voltage dynamic response
Recovery time
Frequency
Frequency tolerance without mains
Frequency synchronisation range
Power factor range
Unbalanced-load response
Output phase current in A
Voltage wave form
Voltage distortion
Crest factor
Overload response 1 min.
Overload response 10 min.
Short circuit response
43
384 V ± 20 %
230 V (220 V, 240 V)
<±1%
<±2%
1 ms
50/60 Hz
± 0,1 %
± 1 % (± 2 %, ± 3 %)
capacitive to inductive over entire cos ϕ-range
at 100% unbalanced load: voltage deviation <2%; angle deviation <2 degrees el.
87
130
174
sinusoidal
≤3%
max. 3
150 %
125 %
short circuit proof, short circuint current 2.7 x Inom
261
STATIC BYPASS SWITCH
AC voltage
Frequency
Nominal power in kVA
10
20
230 V (220 V, 240 V)
50/60 Hz
30
40
60
1810
1915
1200
860
550
1810
1915
1200
860
650
GENERAL DATA
Efficiency (AC to AC) - typical
Noise level depending on rating
EMC compatibility
Air cooling with redundant and monitored fans
Operating temperature range (min./max.)
(without de-rating)
Storage temperature range (min./max.)
Maximum altitude without de-rating
Protection degree to IEC 529/ EN 60529
(standard system)
Equipment colour
92 %
< 55–65 dB (A)
EN 62040-2
Yes
– 5° C/+ 40° C
– 30° C/+ 75° C
1000 m
IP 20
RAL 7035
WEIGHTS AND DIMENSIONS
Height standard UPS (mm)
Height with max. options (mm)
Width (mm)
Depth (mm)
Weight (kg)
1810
1915
600
860
275
1810
1915
600
860
325
1810
1915
750
860
375
Protect 3.: Specification
Three phase output
MODEL
Nominal rating
(at cos ϕ 0.8 lag) in kVA
P3.33-10
P3.33-20
P3.33-30
P3.33-40
P3.33-60
P3.33-80
P3.33-100
P3.33-120
10
20
30
40
60
80
100
120
130
163
195
6 pulse
12 pulse
6 pulse
12 pulse
6 pulse
12 pulse
RECTIFIER UNIT
Input nominal voltage
Input operating range (min./max.)
Frequency
Input current in A at nominal load
Charging characteristic to IEC 478-10
Nominal DC voltage
Rectifier type
- Standard
- Optional
17
33
50
6 pulse
Filter
6 pulse
Filter
6 pulse
Filter
3 x 400 V (3 x 380 V, 3 x 415 V)
340 V–460 V
50/60 Hz ±10 %
66
98
IU
384 V
6 pulse
Filter
6 pulse
Filter
INVERTER UNIT
DC input
Nominal AC voltage
Output voltage static response
Output voltage dynamic response
Recovery time
Frequency
Frequency tolerance without mains
Frequency synchronisation range
Power factor range
Unbalanced-load response
Output phase current in A
Voltage wave form
Voltage distortion
Crest factor
Overload response 1 min.
Overload response 10 min.
Short circuit response
14
384 V ± 20 %
3 x 400 V (3 x 380 V, 3 x 415 V)
<±1%
<±2%
1 ms
50/60 Hz
± 0,1 %
± 1 % (± 2 %, ± 3 %)
capacitive to inductive over entire cos ϕ-range
at 100% unbalanced load: voltage deviation <2%; angle deviation <2 degrees el.
29
43
58
87
116
145
sinusoidal
≤3%
max. 3
150 %
125 %
short circuit proof, short circuint current 2.7 x Inom
173
STATIC BYPASS SWITCH
AC voltage
Frequency
Nominal power in kVA
10
20
30
400 V (380 V, 415 V)
50/60 Hz
40
60
80
100
120
1710
1815
1200
735
800
1710
1815
1200
735
900
1710
1815
1200
735
900
GENERAL DATA
Efficiency (AC to AC) - typical
Noise level depending on rating
EMC compatibility
Air cooling with redundant and
monitored fans
Operating temperature range (min./max.)
(without de-rating)
Storage temperature range (min./max.)
Maximum altitude without de-rating
Protection degree to IEC 529/EN 60529
(standard system)
Equipment colour
94 %
< 55–65 dB (A)
EN 62040-2
Yes
– 5° C/+ 40° C
– 30° C/+ 75° C
1000 m
IP 20
RAL 7035
WEIGHTS AND DIMENSIONS
Height standard UPS (mm)
Height with max. options (mm)
Width (mm)
Depth (mm)
Weight (kg)
1710
1815
600
735
350
1710
1815
600
735
370
1710
1815
600
735
450
1710
1815
600
735
470
1710
1815
750
735
550
Power Safety
Protect 3.
Industrial UPS
Unique Design
• AC distribution panels
• Parallel operation for capacity and performance
Flexible Multi Master Technology and CAN bus communication enables up to 8 UPS to be connected in parallel
for increased power, redundancy or system upgrade.
• Parallel UPS can be operated with a central battery.
• Three microprocessor control system
These microprocessors simultaneously monitor and control
the rectifier, inverter and static switch units. This control
has been specially designed to provide a problem-free
power supply.
• Battery cubicles
• Explosion proof battery circuit breaker enclosures
•…
Compatible with all other AEG Power Solutions
solutions: Industrial DC systems, Telecom systems, ...
Project Management
• Quality plan
End to End Solutions
• Project planning
Exact solutions engineered for each application.
Possible UPS configurations
• Progress reviews
• Single systems
• Manufacturing reviews
• Parallel systems
• Factory acceptance tests
• Other input/output voltages
• Site acceptance tests
•…
•…
Additional system equipment
Customized documentation
• Bypass transformer
• Text translations to any language
• Voltage stabilizer
• Document numbering
• Maintenance Bypass Switch
•…
Services
AEG Power Solutions has considerable in-house
knowledge in battery technology and is able to offer
expert advice on the specifying, selection, operation
and testing of batteries. Our total system solutions
include a wide range of products using lead acid and
nickel-cadmium batteries in vented and gas recombination
technologies. Replacement batteries can be supplied
and installed by our Global Service Team.
With over 60 years of expertise in power systems and
solutions, AEG Power Solutions is renowned for its
unparalleled services and technical support in critical
application environments. As the world class system
provider, you can rely on a global network of
20 Services Centers supported by over 150 field
engineers and more than 100 certified service partners
around the world. From the power solution selection
to your process installation and commissioning, our
certified experts go beyond your expectations by
offering service excellence that will ensure the lowest
operational cost for your mission-critical equipment.
The reliability of your installed power solution is
supported by a Global Service Team renowned for its
short response time and trouble shooting efficiency.
Choosing one of the Pro Care Preventive
Maintenance Options gives you the ultimate peace
of mind reassuring complete cost control, security
and uninterrupted power supply in utmost critical
situations.
TM
You can also benefit from a full range of professional
services that will protect and ensure the durability of
your investment and will take over when you need it
the most:
• Pro Care Preventive Maintenance Options
• Turnkey solutions
• Installation & commissioning
• Maintenance services
• E-Service / remote monitoring
• 24/7 hotline
• Onsite training
• Hot swapping
• Onsite battery replacement
• Battery monitoring
• Facility and equipment management
• 24/7 global onsite contracts
• Power quality assessment
• Load bank & site capacity analysis
• Trouble shooting and repair.
TM
Protect 3. Highlights
• More than 60 years experience in UPS business
• True on-line double conversion UPS (VFI SS 111)
• UPS designed for industrial applications
• Short lead time
• High robustness for harsh working environments
• Redundant controls for high reliability
• Small footprint
• High efficiency even at low output power
• Compatible with every type of battery
• Full digital control
• Top class communication platform.
AEG is a registered trademark used under license from AB Electrolux
AEG Power Solutions GmbH
Emil-Siepmann-Str. 32
59581 Warstein-Belecke
Germany
Tel.: +49 2902 763 0
Fax: +49 2902 763 680
www.aegps.com
PERFECT IN FORM AND FUNCTION
P3.3X - AEG - 03/11/Version No. 2 - EN. Due to our policy of continuous development, data in this document is subject to change without notice and becomes contractual only after written confirmation.
Batteries
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF