advertisement
TECHNICAL DATA
& SERVICE MANUAL
SPLIT SYSTEM AIR CONDITIONER
Model No.
SPW-UMR74EXH56
SPW-UMR94EXH56
SPW-UMR124EXH56
SPW-UMR164EXH56
SPW-UMR184EXH56
SPW-UMR224EXH56
Product Code No.
854.0.2263
854.0.2264
854.0.2265
854.0.2301
854.0.2266
854.0.2267
0.8180.439.0 June 2005
SM940046
IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating standards.
For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions.
If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
WARNING When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
• Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or test ing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
2
Table of Contents
1. SPECIFICATIONS
1-1 Unit specifications
1-2 Major Component specifications
1-3 Other Component specifications
2. DIMENSIONAL DATA
3. ELECTRICAL DATA
3-1 Electric Wiring Diagram
3-2 Control PCB switches and functions
4. FUNCTION
4-1 Room Temperature Control
4-2 Automatic control for heating and cooling
5. REPLACING PCB
5-1 Replacing PCB
5-2 How to replace PCB
5-3 How to replace EEPROM with EEPROM included in PCB service pack
5-4 Table of setting
6. SERVICING AND MAINTENANCE FUNCTIONS
6-1 Indoor unit refrigerant noise countermeasures
6-2 Outdoor unit noise countermeasures: EEPROM 05
7. TROUBLE DIAGNOSIS
7-1 Contents of remote controller switch alarm display
7-2 Outdoor unit control panel led display
7-3 Trouble indications and inspection points
7-4 Remote controller servicing functions
7-5 Super W-Multi alarm codes
7-6 Inspection of parts
17
17
18
19
21
22
22
22
23
23
25
26
28
29
35
Page
13
13
14
15
15
16
7
10
4
4
11
3
1. SPECIFICATIONS
1-1 Unit Specifications
SPW-UMR74/94/124EXH56
Power source
Voltage rating
Performance
Capacity
Air circulation (High/Med./Low)
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
600/510/440 m³/h
Features
Controls/Temperature controls
Remote Controller (Option)
Fan speed
Air Filter
Sound pressure level (*)
Refrigerant tubing connections
Refrigerant tube diameter
Refrigerant
Refrigerant control
Dimensions & Weight
Dimensions high/med/low
Narrow tube
Wide tube wired wireless dB(A) mm(in.) mm(in.)
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
54/52/49
Flare type
6,35 (1/4)
12,7 (1/2)
R410A
Electronic expansion valve
Package dimensions
Weight
Height
Width
Depth
Height
Width
Depth
Volume
Net
Shipping mm mm mm mm mm mm m3 kg kg
266
571
852
365
745
1086
0,3
30,0
34
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(*) Power noise level measured at operating conditions (5mmH20 external static pressure)
4
SPW-UMR164/184EXH56
Power source
Voltage rating
Performance
Capacity
Air circulation (High/Med./Low)
Features
Controls/Temperature controls
Remote Controller (Option)
Fan speed
Air Filter
Sound pressure level (*)
Refrigerant tubing connections
Refrigerant tube diameter
Refrigerant
Refrigerant control
Dimensions & Weight
Dimensions
Package dimensions
Weight high/med/low
Narrow tube
Wide tube m³/h
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
875/600/400 wired wireless dB(A) mm(in.) mm(in.)
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
54/47/42
Flare type
6,35 (1/4)
12,7 (1/2)
R410A
Electronic expansion valve
Height
Width
Depth
Height
Width
Depth
Volume
Net
Shipping mm mm mm mm mm mm m3 kg kg
266
571
1058
365
745
1292
0,35
35
39
DATA SUBJECT TO CHANGE WITHOUT NOTICE
5
SPW-UMR224EXH56
Power source
Voltage rating
Performance
Capacity
Air circulation (High/Med./Low)
Features
Controls/Temperature controls
Remote Controller (Option)
Fan speed
Air Filter
Sound pressure level (*)
Refrigerant tubing connections
Refrigerant tube diameter
Refrigerant
Refrigerant control
Dimensions & Weight
Dimensions
Package dimensions
Weight high/med/low
Narrow tube
Wide tube m³/h
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
1000/700/600 wired wireless dB(A) mm(in.) mm(in.)
Microprocessor/ I.C. thermostat
RCS-SH80AG / RCS-KR1AG
RCS-BH80AG.WL
3 and Auto
Washable
57/49/46
Flare type
9,52 (3/8)
15,88 (5/8)
R410A
Electronic expansion valve
Height
Width
Depth
Height
Width
Depth
Volume
Net
Shipping mm mm mm mm mm mm m3 kg kg
266
571
1058
365
745
1292
0,35
35
39
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6
1-2 Major Component Specifications
SPW-XMR74/94/124EXH56
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps
Power input
Coil resistance (Ambient temp. 20 °C )
Safety devices
Run capacitor mm
Type
Operating temp. Open °C
µF
VAC
A
W
Ω
CR-CRP50A-B
Microprocessor
Centrifugal fan
2…. Ø 160 / L 240
3RGB-CO-45-30 5V/1….1
4 … 1060
0,45
110
BLU-BRN: 95
BRN-BLK: 37
BLK-GRY: 15
GRY-VLT: 15
WLT-RED: 30
RED-YEL: 101
Internal thermal protector - 7AM 037 A 5
150 ± 5K
1,8
450
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch face area
UKV-U030E
UKV-18D31
Aluminium plate fin / Copper tube
2 mm 1,6 m2 0,126
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7
SPW-XMR164/184EXH56
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps
Power input
Coil resistance (Ambient temp. 20 °C )
Safety devices
Run capacitor
CR-CRP50A-B
Microprocessor mm
Type
Operating temp. Open
Close
°C
°C
µF
VAC
A
W
Ω
Centrifugal fan
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1106
0,6
138
BLU-BRN: 68
BRN-BLK: 9
BLK-GRY: 36
GRY-VLT: 18
VLT-RED: 18
BRN-YEL: 105
Internal thermal protector - 7AM 037 A 5
150 ± 5K
2,0
450
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch face area
UKV-U030E
UKV-25D32
Aluminium plate fin / Copper tube
3 mm 1,6 m2 0,168
DATA SUBJECT TO CHANGE WITHOUT NOTICE
8
SPW-XMR224EXH56
Controller PCB
Part No.
Controls
Fan & Fan Motor
Type
Q'ty ……. Dia. and lenght
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Running Amps
Power input
Coil resistance (Ambient temp. 20 °C )
Safety devices
Run capacitor
CR-CRP50A-B
Microprocessor mm
Type
Operating temp. Open
Close
°C
°C
µF
VAC
A
W
Ω
Centrifugal fan
2…. Ø 160 / L 240
3FGB-CO-65-38 5V/1….1
4 … 1161
0,57
136
BLU-BRN: 68
BRN-BLK: 9
BLK-GRY: 36
GRY-VLT: 18
VLT-RED: 18
BRN-YEL: 105
Internal thermal protector - 7AM 037 A 5
150 ± 5K
3
450
Electronic expansion valve
Coil
Valve body
Heat Exch. Coil
Coil
Rows
Fin pitch face area
UKV-U030E
UKV-25D32
Aluminium plate fin / Copper tube
3 mm 1,6 m2 0,168
DATA SUBJECT TO CHANGE WITHOUT NOTICE
9
1-3 Other Component Specifications
Trasformer
Rating Primary
Secondary 1
Secondary 2
Secondary 3
Thermal cut-off temp.
Thermistor ( Coil sensor E1, E2)
Resistance
Thermistor ( Coil sensor E3)
Resistance
Thermistor ( Room sensor TA, TF/BL)
Resistance
Drain pump
Model
Rating Voltage
Input
Flow rate
Safety float switch
Model
Contact rating k Ω k Ω k Ω
ATR-IIJ225A
VAC 230V, 50Hz
AC 20V - 0.2A
AC 14V - 0.3A
AC 10,2V - 1.4A
136°C
PBC-41E-S26
0 °C 15,0 ± 5%
PBC-41E-S42-2
0 °C 15,0 ± 4,42%
DHKTEC-35-S85N
25 °C 5,0 ± 4%
PC 309564003
220/240V - 50Hz
14W
0,4 l/min
BI 1300 2725
230V AC/DC - 0,5A
10
2. DIMENSIONAL DATA
SPW-UMR74/94/124EXH56
11
SPW-UMR164/184/224EXH56
12
3. ELECTRICAL DATA
3-1 Electric Wiring Diagram
7P terminal board
1(L) 2(N) U1 power supply
U2 inter-unit control wiring
R1 R2 remote controller
13
3-2 Control PCB switches and functions
CR-TRP50A-B
EMG (CN044)
OC (CN040)
VARISTOR
(VA041)
T10:
(CN061)
EXCT:
(CN073)
DISP:
(CN072)
CHK:
(CN071)
JP1:
(JP001)
EXCT (CN073)
FAN DRIVE
(CN032)
FILTER
(CN070)
POWER LED
(D002)
JP1
(JP001)
GRL
(CN020)
DISP (CN072)
CHK (CN071)
T10 (CN061)
EEPROM
(IC010)
6 plug (yellow): used for remote control. (Refer to the remote control section)
1- start/stop input 2- COM
3- remote control prohibit/release input 4- start signal output
5- COM (+DC12v) 6- alarm signal output T10
2P plug (red): Can be used for demand control. When imput is present, forces the unit to operate with the termostat OFF.
2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not connected to an outdoor unit. (In this case, alarm "E04", which indicates trouble in the serial communication between the indoor and outdoor unit, does not occur.)
2P plug (white): Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, flap motor (F1 position), and electronic expansion valve full-open position to checked. However this function turns OFF if the indoor unit protection mechanism is activated. The unit can be operated even if the remote controller and outdoor unit are not connected. However even if the remote controller cannot is connected, it cannot be used to operate the unit. This function can be used for short-term tests.
Jumper wire: Allows selection of the T10 terminal
14
4. FUNCTIONS
4-1 Room temperature control
15
4-2 Automatic control for heating and cooling
16
5. REPLACING PCB
5-1 Replacing PCB
About EEPROM
(Erasable Programmable Read-Only Memory)
EEPROM is a component in which the various information necessary for functionning can be electronically written or erased. This component holds informations that is essential for the running of the unit, and must be handled with care.
D002 led lamp (red)
17
5-2 How to replace PCB
18
5-3 How to replace EEPROM with EEPROM included in PCB service pack
19
20
5-4 Table of settings
21
6. SERVICING AND MAINTENANCE FUNCTIONS
22
7. TROUBLE DIAGNOSIS
7-1 Contents of remote controller switch alarm display
23
24
7-2 Outdoor unit control panel LED display
25
7-3 Trouble indications and inspection points
26
27
7-4 Remote controller servicing functions
28
7-5 Super W-Multi alarm codes
29
30
31
32
33
34
7-6 Inspection of parts
35
36
37