SD V2 050-10K [F] (E) [Converted].ai
Highest Tecnology
• True On-Line Double Convertion System
• 20 KHz Full Bridge PWM Inverter
• Constant Voltage & Current Limit
• Static Transfer Switch (make before break)
• Sealed Lead Acid Maintenance Free Battery
Uninterrupted and Stable Output
• Pure Sine Wave, Very Low Distortion
• High Efficiency
• Stable Voltage Output
• Synchronize to Line
Built-in 8 Bits Microprocessor Serial Interface
Port for Various Management & Monitoring Software
• Via PowView Software
• Via Hyper Terminal
• Other (Asynchronous Communication
LED & LCD Display with Key Pad
Utility & UPS Status
• Input Voltage
• UPS Output Voltage & Frequency
• UPS Output Percentage of Load Usage
• Battery Status, Voltage & Temperature
• Automatic Battery Life Time Checking
• UPS Operation Mode
• UPS Information
• UPS Alarm Events with Help Messages
Safe Shutdown System
• Automatic System and UPS Shutdown
• Automatic System Reboot After Power Returns
• Admin./User Broadcast of Power Event
Full Reliable Protection and Alarm System
• Input and Output Protection
• Overload and Short Circuit Protection
• Battery Circuit Breaker Protection
• Battery and Load Level Indicators
• Manual Bypass Switch type make before break
• Interface Port for Unattended Shutdown (RS-232)
Suitable for Office Use
• Compact Size and Quiet Operation
• With Casters for Mobility
Environment & Power Mornitoring
• Real-time Graphical Display of Power
• Environment Monitoring
• Power Quality Data Log
Remote UPS Management
• Remote Management via a Workstation
• Customizing-Configurable UPS Parameters
• Schduled System Shutdown & Reboot
• Remote management via modem
UPS Testing and Status
• Real-time Graphical Display of UPS Status
• Battery Remain Time
• Scheduled UPS Self-tests
• UPS Power Event Log
Safety Standard Design
• Low HF Feed-Back and Smooth Starting
• Surge Protection (IEC 1000-4-5, UL 1449)
• EMI/RFI Interface (VDE, EN 55022)
• Separated Battery Charger
• Isolated Battery Service
• Isolating Transformer
• Can Use with Generater
• Design and Manufactured Following IEC, EN
• Manufacture by ISO 9001 Certified Factory
UPS Management & Diagnostic
• UPS Self Test
• Scheduled UPS Shutdown & Restore
• UPS Alarm Event Checking
• Automatic save application when windows
shutdown by PowView
• Send e-mail when UPS alarm
• Send Short message (SMS) when UPS alarm (Option)
Requirements
• SYNDOME UPS SD-Series with Standard or
Intelligent Signal
• Microsoft. Windows Compatible
Microsoft. WindowsNT Compatible
FS-Z0704-021
Model
RatedPower
SD-100
SD-150
SD-200
SD-300
SD-500
SD-600
SD-800
1KVA/800W
1.5KVA/1.2KW
2KVA/1.6KW
3KVA/2.4KW
5KVA/4.0KW
6KVA/4.8KW
8KVA/6.4KW
Input
Voltage
Voltage tolerance
Frequency
220 Vac, single phase (L, N, G)
± 25 %
50 Hz ± 10 %
Output
Voltage
Voltage regulation
Response time
Frequency
Waveform
Total harmonic distortion
Overload capacity
Total efficiency (AC to AC)
Crest factor
Load Power Factor
Battery
Type
back-up time (full load)
Expansion
Charger
Recharge time
Battery completely discharged
220 Vac, single phase (L, N, G)
± 1% (Steady state), ± 4% (Dynamic state load step)
<5 ms
50 Hz ± 0.1% (free running), 50 Hz ± 1% (Syn rang)
Sine wave
<3 % at 100 % linear load, <5% at 100% non linear load
150 % for 30 seconds
>85 %
3 :1
0.8 (lag to lead)
Sealed lead acid maintenance free
10 minutes
As required
Constant voltage and current limit separated from input inverter
8 hours to 90 % after fully discharged
Auto cut - off inverter (line normal at auto-restart)
Transfer Time
Mains fail or recover
UPS to bypass or vice versa
Indicators
Utility and UPS Status
Load and battery capacity level
Communication Interface
DB-9connector (software required)
Tel Line
LAN Line
Zero (automatic)
Uninterrupted transfer at full load (automatic)
LED & LCD Display
LED
Sereal Interface port can be connected to work stations or servers which
provides the security of automatic, unattended shutdown for all major
operating systems.
yes
yes
Audible Alarm
Battery discharge
Fault
AccousticNoise
At one meter
Sounding every four seconds after main fails at alarm reset Sounding
once every seconds as battery approaches final discharge
Continuous
<45dB
Environment
Temperature
Humidity
0 °C to 45 °C
0-95% (non-condensing)
Dimension
Width (mm)
Height (mm)
Depth (mm)
Weight (kgs)
TechnicalRegulations
220
450
560
65
240
560
630
95
95
110
330
800
680
150
200
IEEE 587, EN50091, EN55022 CLASS A, EN50082-1
Option : Manual bypass switch at >3KVA
Specifications are subject to change without prior notice.
FS-B0904-024