KATALOG 2003
Power & Energy Test Equipment
Main Features
Power / Energy / Harmonics Analysers
True real-time operation for capturing
anomalies, voltage interruptions and power
breaks.
2 Mb of memory allows data logging up to
several months.
Accurate Energy
Measurement
Active & Reactive
Import & Export
Inductive & Capacitive
Separate registers for Total,
Sub-total & Last Integration
Period
Voltage and Current
Harmonic Analysis
up to 63th component
AC powered and
Battery Powered
Battery Pack provides full
operation for up to 5 hours.
Meter Menu for display of all
measured parameters
Scope function allows viewing of
current and voltage waveforms.
Modem Remote Control by using GSM
or standard type of communication.
– Remote programming of instrument via PC.
– Downloading recorded data via PC from a
remote location.
– Receiving SMS alarms (task completed full
memory etc.)
Configuration menu for setting measuring
method, integration period, current scaling
factor, and selection of signals.
TECHNICAL SPECIFICATION
METER – Power measurement
AC VOLTAGES
Three-phase AC voltage input (3 differential inputs, L1 - N1, L2 - N2 , L3 - N3)
Optional on request:
10–550 Vrms L-N, 900 Vrms L-L
600 Vr ms L-N (over load 10 s)
10–750 Vrms L-N, 1000 Vrms L-L
800 Vr ms L-N (overload 10 s)
Resolution:
0.1 V
Accuracy:
± 0.5 % of reading ± 2 digits
Crest factor max.
1.4
Frequency range:
43–68 Hz fundamental
Input voltage range:
Three-phase AC input for connection to current transducers with voltage output
Input current (voltage range):
0.02–1 Vrms (from 0.02 x In to In) input
Resolution:
0.3 mV (0.3 A with 1000 A / 1 V)
± 0.5 % of reading ± 6 digits plus current transformer accuracy
Crest factor:
Maximum permissible overload:
Maximum input voltage:
2.5
150 % In (sinusoidal current)
1 V rms
PHASE ANGLE
Basic accuracy for P, Q, S,:
Resolution for P, Q, S,:
± 1 % of reading
0.01 of displayed value
The instrument computes harmonics on signals sampled with an A/D converter.
Recording interval:
160 ms (8 cycles)
rd
Spectrum calculation range:
DC – 63
th
Spectrum display range:
DC – 25
Displayed items for selected harmonic: Order, relative and absolute value
Range
Irange Urange
2 … 100 %
Limits of error
THD Total Harmonic
HD Harmonic
Distortion
Distortion
0.2 % x Ur/U (I r/I )
0.2 % x Ur/U (Ir/I)
Resolution
on LCD and PC
0.1 %
ENERGY
Consider phase angle data of used current transformer.
SCOPE
Display options
Waveform of pairs (L1: U1 and I1, L2: U2 and I2,
Ranging
Auto / manual
L3: U3 and I3), U1, 2, 3 , and I1, 2, 3
2
Quantities for complete three-phase system, i.e.:
Calculated:
active power (Pt), apparent power (St), reactive power
(Qt), power factor (Pft), neutral current (In);
SPECTRUM – Harmonics measurement
AC CURRENTS
Accuracy:
Quantities related to selected measuring connections per phase, i.e.:
Measured:
voltage (U), current (I), cosϕ between U and I
Calculated:
active power (P), apparent power (S), reactive power (Q),
power factor (Pf) with its characteristic (c, I, none)
Line – Line voltage;
Displayed quantities from integration of calculated power as:
– cumulative values (TOTAL);
– partly cumulative (resettable by user request) (SUBTOTAL);
– values related to last integration period (LAST IP).
Quantities. Active energy (EP), capacitive energy (EQC), inductive energy (EQI)
Basic accuracy:
± 1 % of reading
Resolution:
0.1 of displayed value
Power & Energy Test Equipment
Power / Energy / Harmonics Analysers
PC Software
Special SW Tools
Special tools enable a detailed, time domain based signal analysis. They represent a
powerful, modern troubleshooting tool for solving of all kinds of problems which are
appearing in power distribution systems. The user can choose between three modes,
differing in terms of sampling speed, trigger possibilities and recording time:
WAVEFORMS
Recording of voltages and currents with 128 samples/period.
Half period RMS values of recorded quantities are also
calculated and shown in this mode. Best suited for:
– monitoring of switching phenomena,
– locating of noise and disturbance sources,
– defining disturbance type,
– locating excessive harmonics sources.
Typical problems that can be solved by WAVEFORM analysis:
– capacitor banks switch over,
– transformer overheating,
– UPS problems,
– SMPS failures etc.
FAST LOGGING OF SIGNALS
Recording of half period RMS voltage and currents values.
Recommended when record length is critical and signal’s
details are not of importance. Best suited for:
– observing start up and inrush events,
– locating impedance problems,
– long term analysing of unstable mains.
Typical problems that can be solved with FAST LOGGING
analysis:
– too high inrush currents of large motors,
– undersized fuses and installation wiring,
– too weak voltage source etc.
TRANSIENTS
The recording mode with fastest sampling rate that the
instrument can provide. Up to 50 kHz transient detect ability in
this mode. Best suited for:
– monitoring atmospheric discharging,
– analysing switching problems,
– detailed analysis of high frequency noise and
notching.
Typical problems that can be solved with TRANSIENT analysis:
– frequency noise,
– voltage spikes caused by switching of capacitor
banks etc.
GENERAL SPECIFICATION
RECORDER
Periodics integration period: 1 s – 900 s
Selected signals:
max. 64
Statistics values:
each period divided in 200 parts (0.1 ms)
Voltage anomalies: based on half period, start, duration and extrems of voltage
EN 50160 ANALYSIS MODE
Voltage dips, swells, sags and breaks, resolution 10 ms, no gaps
Voltage unsimetry, Voltage RMS values, Frequency
th
Harmonics:
up to 43 component
Flickers Plt Pst:
no gap
FLICKER MEASUREMENT
The instrument computes flickers according to IEC 61000-4-15
WAVEFORMS
Sampling rate:
128 scans / period
Trigger:
level, manual, timer
Buffer: min. 10 periods of pre / post size, up to 7812 periods can be recorded
Channels:
3 x U, 3 X I, U lines, Min / Max rms values: Avg
Pf, cosϕ, Crest factor, THD U, I Frequency
Harmonics / direction:
magnitudes / positive / negative
FAST LOGGING
Sampling rate: 128 scans / period, min, max, Avg recorded each halfperiod
Trigger:
level, manual, timer
Buffer:
pre / post size, up to 166 minutes of recording
Channels:
3 x U, 3 X I, Single or multichannel mode
TRANSIENTS
Capturing:
>20 µs transient detect ability
Trigger:
Level, slope, manual
Buffer: min. 10 periods of pre / post size, up to 1000 periods can be recorded
Channels:
3 x U, 3 X I, Single or multichannel mode
Display: Graphic Liquid Crystal Display with LED backlight, 160 x 116 dots resolution
NON – VOLATILE MEMORY
2048 Kbytes SRAM, battery backed.
DIGITAL HARDWARE SPECIFICATION
A/D conversion,
14 bit with 128 samples per channel per period (43–68 Hz).
OUTPUTS
Communication type:
Baud rate:
RS 232 serial interface, fully opto isolated
2400–57600 baud.
Connector:
9 pin D-type.
Communication cable:
Standard type
POWER SUPPLY
Operating range:
Optional:
230 V A.C. + 10 % – 20 %, 45–65 Hz, 8 VA
115 V A.C. + 10 % – 20 %, 45–65 Hz, 8 VA
DC power supply:
Internal 4 x 1.2 V NiCd or NiMh rechargeable IEC LR14
batteries provide full operation for up to 5 hours.
Charger:
Internal built-in battery charger, charging time approx. 10 hours.
GENERAL
Working temperature range:
– 20 °C … + 60 °C
Max. humidity:
85 % RH (0 ÷ 40 °C)
Pollution degree:
2
Protection classification:
II - double insulation
Overvoltage category:
Voltage inputs: CAT III 600 V; optional CAT IV 600 V
AC power supply CAT III 300 V
Protection degree:
IP 44 (IP 54 on request)
Dimensions:
265 x 110 x 185 mm
Weight (without accessories):
2 kg
3
Power & Energy Test Equipment
PowerLink (Windows 95/98/2000/NT)
Power / Energy / Harmonics Analysers
Recorder mode
Simple set-up
– Selection of signals and type of
analysis (periodics, anomalies,
statistics, EN 50160.
– Selection of recording time and
averaging cycles integration
period.
Recording can be set also from
instrument directly.
Analysis
PERIODICS AND STATISTICS ANALYSIS
Direct mode
On-line monitoring of three-phase
currents and voltages
• 6-CHANNEL OSCILLOSCOPE
Over 300 quantities (64 at the same time) can be recorded and stored in this mode. All important
quantities and events can be selected:
– average, minimum and maximum voltage and
current RMS values,
– harmonics and THD of voltage and current
– particular and total power (classified sign and
character)
– voltage events and anomalies (interruptions,
dips, sags), type and duration
– flicker Pst and Plt values
– other EN50160 parameters: signaling,
interharmonics, unbalances.
• HARMONICS UP TO 63th
• EN 50160 AUTO-MODE with statistics and results based on the standard
• HARMONICS REPORT
• STATISTICS REPORT in EN 50160
graphic and tabelaric form
• FLICKER DIAGRAMS
ENERGY counter, P, S, Q, PF
• and
other calculations
POW
REP ER QUA
ORT
LITY
Reporting
Acco
rding
to EN
5016
0
Test Reports
– Saving of results, graphs and reports for further analysis
– Exporting of data and graphs in xls files for making custom reports.
– Print-out of results and graphs.
Harmonics Report