Allen-Bradley ArmorPoint 24V dc Analog Output Modules, Series A Installation Instructions
Below you will find brief information for Analog Output Modules Series A 1738-OE2CM12, Analog Output Modules Series A 1738-OE2VM12. These modules are designed for use in industrial automation applications and offer a variety of features, including 2 single-ended, nonisolated outputs, a resolution of 13 bits for 1738-OE2CM12 and 14 bits for 1738-OE2VM12, an absolute accuracy of 0.1% full scale at 25 °C, a conversion rate of 16 μs for 1738-OE2CM12 and 20 μs for 1738-OE2VM12, and a variety of environmental specifications including operating temperature range of -20…60 °C and IP65/66/67 enclosure type rating.
Advertisement
Advertisement
Installation Instructions
ArmorPOINT™ 24V DC Analog
Output Modules
Catalog numbers 1738-OE2CM12, 1738-OE2VM12, Series A
Table of Contents
Topic
Prevent Electrostatic Discharge
Remove the Module from the Mounting Base
Page
2 ArmorPOINT™ 24V DC Analog Output Modules
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication.
Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1738-IN004B-EN-E - July 2011
4 ArmorPOINT™ 24V DC Analog Output Modules
About the Modules
The ArmorPOINT I/O family consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. Note that environmental requirements other than IP67 may require an additional appropriate housing. I/O connectors are sealed
M12 style. The mounting base ships with the module. The 1738-OE2CM12 module is shown here.
Connector M12-A
0
1738-OE2CM12/A
Analog Current Out
1
MOD
NET
Connector M12-B
LED indicators
0
1
45755
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 5
Mount the I/O Base
To mount the base on a wall or panel, use the screw holes provided in the base.
ATTENTION: The ArmorPOINT I/O module must be mounted on a grounded metal mounting plate or other conductive surface.
A mounting diagram for the ArmorPOINT base with adapter is shown here.
46.25 (1.8) 20.1 (0.8) 20.1 (0.8)
Millimeters
(Inches)
51.9 (2) 51.9 (2) 51.9 (2)
102
(4.02)
56
(2.2)
Adapter
45707
Install the mounting base as follows:
1. Lay out the required points as shown above in the drilling dimension diagram.
2. Drill the necessary holes for M4 (#8) machine or self-tapping screws.
3. Mount the base using M4 (#8) screws.
4. Ground the system using the ground lug connection. The ground lug connection is also a mounting hole.
Mounting base
Keyswitch – set to position 4 for 1738 analog output modules
Ground lug connection
Latching mechanism
45708
Publication 1738-IN004B-EN-E - July 2011
6 ArmorPOINT™ 24V DC Analog Output Modules
Install the Module
To install the analog output module, proceed as follows:
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 4 aligns with the notch in the base.
2. Position the module vertically above the mounting base. The module bridges two bases.
Module bridges two bases.
0
1738-OE2CM12/A
Analog Current Out
1
MOD
NET
0
1
45757
3. Push the module down until it engages the latching mechanism. You hear a clicking sound when the module is properly engaged. The locking mechanism locks the module to the base.
Remove the Module from the Mounting Base
To remove the module from the mounting base:
1. Insert a flat blade screwdriver into the slot of the orange latching mechanism.
2. Push the screwdriver toward the I/O module to disengage the latch. The module lifts up off the base.
3. Pull the module off the base.
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 7
Wire the Modules
The wiring instructions for the modules are shown here.
1738-OE2CM12, 1738-OE2VM12
(View into connector)
Pin 1 Output 0 (M12-A)
Output 1 (M12-B)
Pin 2 24V DC
Pin 3 Common
Pin 4 Common
Pin 5 No connect
43664
IMPORTANT
Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.
ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
Publication 1738-IN004B-EN-E - July 2011
8 ArmorPOINT™ 24V DC Analog Output Modules
Communicate with the Module
I/O messages are sent to (consumed) and received from (produced) the ArmorPOINT modules. These messages are mapped onto the processor’s memory. The ArmorPOINT analog output modules produce 2 Bytes of input data (scanner Rx – fault status). They consume 4 Bytes of output data (scanner Tx).
Default Data Map for Output Modules
Message size: 2 Bytes
Produces
(Scanner Rx)
Where:
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
High byte – channel 1 status
Not used HCA LCA CM CF
Low byte – channel 0 status
Not used HCA LCA CM CF
HCA = High Clamp Alarm; 0 = No error, 1 = Fault
LCA = Low Clamp Alarm; 0 = No error, 1 = Fault
CM = Calibration Mode; 0 = Normal, 1 = Calibration mode
CF = Channel Fault Status; 0 = No error, 1 = Fault
Message size: 4 Bytes
Consumes
(Scanner Tx)
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output channel 0 high byte
Output channel 1 high byte
Output channel 0 low byte
Output channel 1 low byte
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 9
Interpret Status Indicators
1738-OE2CM12
1738-OE2CM12/A
Analog Current Out
1
0
MOD
NET
Module status indicator
Network status indicator
0
1
I/O status indicators
45755
Indicator Status for Modules
Status Description
Module status Off
Green
No power applied to device.
Device operating normally.
Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration.
Recoverable fault.
Flashing red
Red Unrecoverable fault – may require device replacement.
Flashing red/green Device is in self-test.
Network status Off Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Flashing green
Green
Flashing red
Device is online but has no connections in the established state.
Device is online and has connections in the established state.
One or more I/O connections is in timed-out state.
Red Critical link failure – failed communication device. Device detected error that prevents it from communicating on the network.
Flashing red/green Communication faulted device – the device has detected a network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request – long protocol message.
Publication 1738-IN004B-EN-E - July 2011
10 ArmorPOINT™ 24V DC Analog Output Modules
Indicator Status for Modules
I/O status
Status
Off
Solid green
Flashing green
Flashing red
Solid red
Description
Module in CAL mode.
Device operating normally.
Channel being calibrated.
1738-OE2VM12 – Low or high clamp.
1738-OE2CM12 – Open wire or no power.
1738-OE2VM12 only – No power.
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 11
Specifications
ArmorPOINT 24V DC Analog Output Modules – 1738-OE2CM12,
1738-OE2VM12
Attribute
Outputs per module
Output voltage
Output current
Resolution
Absolute accuracy
(1)
Accuracy drift w/temp
Resistive load on mA output
Current load on output, max
Conversion type
Conversion rate
Value
2 single-ended, nonisolated
1738-OE2V
0V output until communication established
0…10V (user-configurable; 0V under, 5V over)
10V (user-configurable; -0.5V under, 5V over)
0 mA output until communication established
4…20 mA user configurable
0…20 mA user configurable
1738-OE2C
13 bits – over 0…21 mA
2.5
μ
A/cnt (average value – typical range: 2.3…2.7
μ
A/cnt)
1738-OE2V
14 bits (13 plus sign)
1.28
μ
V/cnt in unipolar or bipolar mode
0.1% full scale @ 25 °C
1738-OE2C – 30 ppm/°C
1738-OE2V – 5 ppm/°C
1738-OE2C – 0…750
Ω
1738-OE2V – 3 mA
Digital-to-analog converter
1738-OE2C – 16
μ s
1738-OE2V – 20
μ s
Signed integer Data format
(1)
Includes offset, gain, non-linearity and repeatability error terms
Publication 1738-IN004B-EN-E - July 2011
12 ArmorPOINT™ 24V DC Analog Output Modules
General Specifications
Attribute
Calibration
Mounting base screw torque
Indicators
Power dissipation, max @ 28.8V DC
Thermal dissipation, max @ 28.8V DC
Isolation voltage
POINTBus current
External DC power supply voltage, nom
External DC power voltage range
External DC power supply current
Dimensions, HxWxD
Weight
Wiring category
(1)
Keyswitch position
Step Response to 63% of FS
Value
Factory-calibrated
#8 screw
0.85 Nm (7.5 lb-in.) in aluminum
1.8 Nm (16 lb-in.) in steel
1 green/red – module status indicator, logic side
1 green/red – network status indicator, logic side
2 green/red – output status indicators, logic side
1738-OE2C
750
Ω
load on each output – 1.23 W
0
Ω
load on each output – 1.83 W
1738-OE2V
1.0 W
1738-OE2C
750
Ω
load on each output – 4.19 BTU/hr
0
Ω
load on each output – 6.24 BTU/hr
1738-OE2V
3.4 BTU/hr
50V rms
Tested @ 1250V AC rms for 60 s
75 mA @ 5V DC
24V DC
10…28.8V DC
1738-OE2C
70 mA @ 24V DC (including outputs @ 20 mA)
1738-OE2V
35 mA @ 24V DC (including outputs @ 3 mA)
31.75 x 66.80 x 107.95 mm
(1.25 x 2.63 x 4.25 in.)
0.289 kg (0.637 lb)
1 – on signal ports
4
24
μ s
(1)
Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1
, Industrial
Automation Wiring and Grounding Guidelines.
Publication 1738-IN004B-EN-E - July 2011
ArmorPOINT™ 24V DC Analog Output Modules 13
Environmental Specifications
Attribute
Temperature, operating
Temperature, nonoperating
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
ESD immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Emissions
Enclosure type rating
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5…95% noncondensing
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM @ 80 MHz…2000 MHz
10V/m with 200 Hz 50% pulse 100% AM @ 900 Mhz
10V/m with 200 Hz 50% pulse 100% AM @ 1890 Mhz
IEC 61000-4-4:
±3 kV @ 5 kHz on signal ports
IEC 61000-4-5:
±2 kV line-earth (CM) on shielded ports
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80% AM @ 150 kHz…80 MHz
CSPR 11:
Group 1, Class A
Meets IP65/66/67 (when marked)
Publication 1738-IN004B-EN-E - July 2011
14 ArmorPOINT™ 24V DC Analog Output Modules
Certifications
Certification (when product is marked)
(1)
CE
Value
C-Tick
European Union 89/336/EEC EMC Directive, compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
See the Product Certification link at http://www.ab.com
for Declaration of Conformity, Certificates, and other certification details.
Publication 1738-IN004B-EN-E - July 2011
Notes:
ArmorPOINT™ 24V DC Analog Output Modules 15
Publication 1738-IN004B-EN-E - July 2011
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Allen-Bradley, Rockwell Automation, ArmorPOINT, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1738-IN004B-EN-E - July 2011
Supersedes Publication 1738-IN004A-EN-E - June 2004
957824-30
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Advertisement
Key features
- 2 single-ended, nonisolated outputs
- 13 bits resolution for 1738-OE2CM12
- 14 bits resolution for 1738-OE2VM12
- 0.1% full scale accuracy at 25 °C
- 16 μs conversion rate for 1738-OE2CM12
- 20 μs conversion rate for 1738-OE2VM12
- Operating temperature range of -20…60 °C
- IP65/66/67 enclosure type rating