HIT-HY 10 PLUS
Adhesive Anchor
On the job. Every day.
Hilti. Outperform. Outlast.
Hilti Adhesive Anchor
An economical solution for
multiple base materials.
Applications
HIT-HY 10 PLUS Adhesive
Anchoring System
Hilti has you covered with the latest addition to the anchoring
portfolio: The new Hilti HIT-HY 10 PLUS Adhesive Anchor
System. This new adhesive can be used in a variety of base
materials including concrete, grouted CMU, hollow brick and
CMU*. HIT-HY 10 PLUS is an economical solution when an ICC
Evaluation Report is not required and the versatility makes it
great for many jobsite conditions. It is a high-value, everyday
adhesive that is easy to dispense with the same dispensers
as the rest of the Hilti adhesive portfolio (MD 2500 manual
dispenser and ED 3500-A battery dispenser).
• Slab extension through doweling
• Sign, fence or awning attachment to
masonry or concrete
• Scaffolding, pipe or fixture
attachment to masonry or concrete
• Small hole filling where anchors
have been removed
Outperform and Outlast
• Works in a variety of base materials
acting as a universal anchor
adhesive
• Cures in approximately 45 minutes
at 70°F providing quick installation
times to finish the job earlier
• Achieve various embedment depths
by combining mesh sleeves to
customize lengths in hollow base
materials
• Rebar and threaded rod tested in a
wide variety of depths and diameter
sizes to solve the application needs
on a jobsite
Technical Data
Product
Hybrid Urethane
Methacrylate
Base material
temperature
32° F to 104° F
(0° C to 40° C)
Diameter range
Order Information
Description
Package Contents
Qty of Foil
Packs
Item No.
HIT-HY 10 PLUS
(11.1 fl oz/330 ml)
Includes 1 foil pack with 1 mixer and 3/8"
filler tube per pack
1
00422710
HIT-HY 10 PLUS
(16.9 fl oz/330 ml)
Includes 20 foil packs with 1 mixer and 3/8"
filler tube per pack
20
00422711
HIT-HY 10 PLUS
3/8" to 3/4"
Package volume
• Volume of HIT-HY 10 PLUS 11.1 fl oz/330 ml foil
pack is 20.1 in3
• Volume of HIT-HY 10 PLUS 16.9 fl oz/500 ml foil
pack is 30.5 in3
Composite Mesh Sleeves for Hollow Masonry and Brick Material
Description
For use with:
Qty
Item No.
Mesh Sleeve HIT-SC 12x50
1/4" dia. rods
20
00375979
Mesh Sleeve HIT-SC 12x85
1/4" dia. rods
20
00375980
Mesh Sleeve HIT-SC 16x50
5/16", 3/8" dia. rods and 5/16" HIT-IC rods
20
00375981
Mesh Sleeve HIT-SC 16x85
5/16", 3/8" dia. rods and 5/16" HIT-IC rods
20
00375982
Mesh Sleeve HIT-SC 18x50
1/2" dia. rods
20
00360485
Mesh Sleeve HIT-SC 18x85
1/2" dia. rods
20
00360486
*For hollow brick and CMU, composite sleeves are required. See catalog for full ordering information.
2
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
HIT-HY 10 PLUS Adhesive Anchor System
1.1
Product Description
1.2
Material Specifications
1.3
Technical Data
1.1 Product
Description
Hilti HIT-HY 10 PLUS is a new hybrid
adhesive mortar combining resin,
hardener, cement and water. It’s
formulated for fast curing and easy
installation in a wide range of solid and
hollow concrete and masonry base
material with temperatures during
installation from 32°F (0°C) up to 104°F
(40°C). HIT-HY 10 PLUS is styrene free
and virtually odorless.
HIT-HY 10 PLUS Adhesive Anchor
System is easy to use in a wide variety
of applications. The system consists of
a side-by-side self opening adhesive
cartridge which fits all Hilti MD and
ED dispensers, a mixing nozzle which
comes with every cartridge, and either
a threaded rod or rebar (purchased
separately).
HIT-HY 10 PLUS is designed for
fastenings into solid base materials,
such as concrete, and is also suitable for
fastening into base materials containing
voids and holes such as hollow block
and clay brick with holes when used with
a screen tube.
Features
Benefits
For virtually all base materials
Good performance from one product for
many applications
Reusable
Open cartridges may be stored for up to
20 days by leaving the mixer attached
Easy to use
Low dispensing forces
Suitable for dry and saturated base
materials
Application versatility
Suitable for in-service temperatures up
to 122°F (long term) and 176°F (short
term)
Flexibility for use in demanding
environments
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
3
Hilti Adhesive Anchor
1.2 Material Specifications
Mechanical Properties
Material Specifications
fy
ksi (MPa)
min. fu
ksi (MPa)
Standard threaded rod, ASTM A 36, 9SMNPB36K and/or 9SMN36K conforming to DIN 1651.
36
(248)
58
(400)
HAS-E Rod material meets the requirements of ISO 898 Class 5.8
58
(400)
72.5
(500)
HAS-H Rod material meet the requirements of ASTM A 193 Grade B7
105
(724)
125
(862)
Stainless HAS rod material meets the requirements of ASTM F 593 (AISI 304) Condition CW 3/8"-5/8"
65
(448)
100
(689)
Stainless HAS rod material meets the requirements of ASTM F 593 (AISI 304) Condition CW 3/4"
45
(310)
85
(586)
HAS-E Standard Nut Material meets the requirements of SAE J995 Grade 5
HAS Stainless Steel Nut material meets the requirements of ASTM F 594
HAS-E Carbon Steel and Stainless Steel Washers meet dimensional requirements of ANSI B18.22.1 Type A Plain
HAS Stainless Steel Washers meet the requirements of AISI 304 or AISI 316 conforming to ASTM A 240
HAS-E Standard Washers meet the requirements of ASTM F 884, HV
All HAS-H and HAS-E rods, nuts & washers are zinc plated to ASTM B 633 SC 1
4
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
1.3 Technical Data
HIT-HY 10 PLUS Allowable Bond/Concrete Capacity and Steel Strength for
HAS / Threaded Rods in Normal Weight Concrete 1, 2, 3, 4
HIT-HY 10 PLUS Allowable
Bond/Concrete Capacity
Anchor
Diameter
Enbedment
Depth
in. (mm)
in. (mm)
Tensile
lb (kN)
Shear
lb (kN)
2-1/4
750
1325
(57)
(3.3)
(5.9)
3-3/8
1985
(86)
4-1/2
3/8
(9.5)
1/2
(12.7)
5/8
(15.9)
3/4
(19.1)
Allowable Bolt Strength4
HAS-E Standard
Carbon Steel
f′c ≥ 2500 psi (≥17 MPa)
HAS-SS AISI (304/316)
Stainless Steel
Tensile
lb (kN)
Shear
lb (kN)
Tensile
lb (kN)
Shear
lb (kN)
3135
2640
1360
3645
1880
(8.8)
(13.9)
(11.7)
(6.0)
(16.2)
(8.4)
2140
4820
(114)
(9.5)
(21.4)
3
1405
2730
(76)
(6.2)
(12.1)
4-1/2
3530
5570
4700
2420
6480
3340
(114)
(15.7)
(24.8)
(20.9)
(10.8)
(28.8)
(14.9)
6
4295
8575
(152)
(19.1)
(38.1)
3-3/4
1925
4065
(95)
(8.6)
(18.1)
5-5/8
4290
8580
7340
3780
10125
5215
(143)
(19.1)
(38.2)
(32.6)
(16.8)
(45.0)
(23.2)
7-1/2
5715
11430
(191)
(25.4)
(50.8)
4-1/2
2740
6065
(114)
(12.2)
(27.0)
7-1/2
5880
11760
10570
5445
12390
6385
(191)
(26.2)
(52.3)
(47.0)
(24.2)
(55.1)
(28.4)
9
7055
14110
(229)
(31.4)
(62.8)
1 Concrete/bond values above to be compared to the steel value. The lesser of the values is to be used for the design.
2 Allowable concrete tension and shear capacity based on the Strength Design method.
3 All values based on holes drilled with the specified carbide bit.
4 Steel strength as defined in AISC Manual of Steel Construction (ASD):
Tensile - 0.33 x Fu x Nomimal Area
Shear - 0.17 x Fu x Nominal Area
HIT-HY 10 PLUS Anchor Spacing and Edge Distance Guideliness for Normal Weight Concrete 1
Spacing
Edge Distance
Tension and Shear
Tension and Shear
smin = 3.0 hef
cmin = 2.0 hef
1 Minimum anchor spacing and edge distance necessary to have no reduction in anchor capacity, where hef is the effective embedment of the anchor.
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
5
Hilti Adhesive Anchor
1.3 Technical Data
HIT-HY 10 PLUS Allowable Bond/Concrete Capacity and Steel Strength for
Rebar in Normal Weight Concrete 1, 2, 3, 4
Anchor
Diameter
in. (mm)
#3
(9.5)
#4
(12.7)
#5
(15.9)
#6
(19.1)
Enbedment
Depth
in. (mm)
HIT-HY 10 PLUS Allowable
Bond/Concrete Capacity
Grade 60 Rebar
f′c ≥ 2500 psi (≥17 MPa)
Tensile
lb (kN)
Shear
lb (kN)
Yield Strength Tensile Strength
lb (kN)
lb (kN)
2-1/4
750
1325
(57)
(3.3)
(5.9)
6600
9900
4-1/2
2140
4820
(29.4)
(44.0)
(114)
(9.5)
(21.4)
3
1405
2730
(76)
(6.2)
(12.1)
12000
18000
6
4295
8575
(53.4)
(80.1)
(152)
(19.1)
(38.1)
3-3/4
1925
4065
(95)
(8.6)
(18.1)
18600
27900
7-1/2
5715
11430
(82.7)
(124.1)
(191)
(25.4)
(50.8)
4-1/2
2740
6065
(114)
(12.2)
(27.0)
26400
39600
9
7055
14110
(117.4)
(176.1)
(229)
(31.4)
(62.8)
1 Concrete/bond values above to be compared to the steel value. The lesser of the values is to be used for the design.
2 Allowable concrete tension and shear capacity based on the Strength Design method.
3 All values based on holes drilled with the specified carbide bit.
4 Rebar steel strength based on minimum steel strength and cross sectional area of rebar per ASTM.
HIT-HY 10 PLUS Allowable Bond/Concrete Capacity and Steel Strength for
Canadian Rebar in Normal Weight Concrete 1, 2, 3, 4
Rebar Size
10M
15M
20M
Enbedment
Depth
(mm)
HIT-HY 10 PLUS Allowable
Bond/Concrete Capacity
Strength Properties of
Metric Rebar
f′c ≥ 14.0 Mpa
fy ≥ 400 Mpa
Tensile
(kN)
Shear
(kN)
55
3.3
5.9
115
9.5
21.4
95
8.6
18.1
190
25.4
50.8
115
12.2
27.0
230
31.4
62.8
Yield Strength Tensile Strength
(kN)
(kN)
40
60
80
120
120
180
1 Concrete/bond values above to be compared to the steel value. The lesser of the values is to be used for the design.
2 Allowable concrete tension and shear capacity based on the Strength Design method.
3 All values based on holes drilled with the specified carbide bit.
4 Rebar steel strength based on minimum steel strength and cross sectional area of rebar per ASTM.
6
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
1.3 Technical Data
Allowable Tension Loads for Threaded Rods in the Vertical Face of
Grout-Filled Concrete Masonry Units (lb)1, 2, 7, 8, 9, 10, 11
Spacing4
Anchor
Diameter
(inches)
Embedment
(inches)3
3/8
1/2
Edge Distance5
Minimum,
smin
(inches)
Load
Reduction
Factor at
smin6
Critical,
ccr
(inches)
Minimum,
cmin
(inches)
Load
Reduction
Factor at
cmin6
13.5
4
0.50
12
4
0.75
18
4
0.50
20
4
0.75
2125
22.5
4
0.50
20
4
0.60
2850
27
4
0.50
20
4
0.60
Load @ ccr
and scr
Critical,
scr
(inches)
3-3/8
950
4-1/2
1500
5/8
5-5/8
3/4
6-3/4
Allowable Shear Loads for Threaded Rods in the Vertical Face of
Grout-Filled Concrete Masonry Units (lb) 1, 2, 7, 8, 9, 10, 11
Spacing4
Edge Distance5
Anchor
Diameter
(inches)
Embedment
(inches)3
Load @
ccr and scr
Critical,
scr
(inches)
Minimum,
smin
(inches)
Load
Reduction
Factor at
smin6
Critical,
ccr
(inches)
Minimum,
cmin
(inches)
3/8
3-3/8
675
13.5
4
0.50
12
4
1/2
4-1/2
1125
18
4
0.50
12
5/8
5-5/8
1950
22.5
4
0.50
20
3/4
6-3/4
3000
27
4
0.50
20
4
Load Reduction Factor at cmin6
Load
Perpendicular
to Edge
Load
Parallel
to Edge
0.88
1.00
4
0.50
1.00
4
0.33
0.75
0.25
0.60
1 A
ll values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units shall be light-, medium-, or normal-weight
conforming to ASTM C 90.
2 Anchors may be installed in any location in the face of the masonry wall (cell, bed joint, or web), except anchors must not be installed in or within one inch in any direction of a vertical (head)
joint.
3 Embedment depth is measured from the outside face of the concrete masonry unit.
4 The critical spacing, scr, is the anchor spacing where full load values in the Table may be used. The minimum spacing, smin, is the minimum anchor spacing for which values are available and
installation is recommended. Spacing is measured from the center of one anchor to the center of an adjacent anchor.
5 The critical edge distance, ccr, is the edge distance where full load values in the Table may be used. The minimum edge distance, cmin, is the minimum edge distance for which values are
available and installation is recommended. Edge distance is measured from the center of the anchor to the closest edge.
6 Load reduction factors are multiplicative, both spacing and edge distance load reduction factors must be considered.
Load values for anchors installed at less than scr and ccr must be multiplied by the appropriate load reduction factor for all edge distances (c) or anchor spacings (s).
7 Linear interpolation of load values between minimum spacing (smin) and critical spacing (scr) and between minimum edge distance (cmin) and critical edge distance (ccr) is permitted.
8 C
oncrete masonry wall thickness must be equal to or greater than 1.5 times the anchor embedment depth. EXCEPTION: the 5/8-inch- and the 3/4-inch-diameter anchors may be installed in
minimum nominally 8-inch-thick concrete masonry.
9 When using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. When using the alternative
basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 percent, or the alternative basic load combinations
may be reduced by a factor of 0.75.
10 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
Tapplied
Vapplied
11 For combined tension and shear loading: __________ + __________ ≤1
Tallowable Vallowable
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
7
Hilti Adhesive Anchor
1.3 Technical Data
Allowable Tension and Shear Loads for Threaded Rods in the Top of
Grout-Filled Concrete Masonry Units (lb)1, 2, 3, 5, 6, 7
Shear Load
Anchor
Diameter
(inches)
Embedment
(inches)
1/2
4-1/2
5/8
Edge
Distance4
(inches)
Minimum
Edge Distance
(inches)
1-3/4
4
8
1-3/4
5-5/8
4
Load Parallel
to Edge of
Masonry Wall
Load
Perpendicular
to Edge of
Masonry Wall
880
640
260
1190
1090
405
1100
950
305
1400
1370
490
Tension Load
1 A
ll values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units they shall be light-, medium-, or normal-weight
conforming to ASTM C 90.
2 When using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. When using the alternative
basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 percent, or the alternative basic load combinations
may be reduced by a factor of 0.75.
3 No more than one anchor shall be permitted to be installed in each CMU block.
4 The tabulated edge distance is measured from the anchor centerline to the edge of the CMU block.
5 Anchors are not permitted to be installed in a head joint, flange or web of the concrete masonry unit.
6 Linear interpolation of load values between the two tabulated edge distances is permitted.
7 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
Allowable Tension and Shear Loads for Threaded Rods in the
Vertical Face of Hollow Concrete Masonry Units (lb)1, 3, 4, 5, 6, 7
Anchor
Diameter
(inches)
Embedment
Tension Load
(inches)2
Shear Load
Minimum Edge
Distance, cmin
(inches)
1/4
2
115
170
4
5/16
2
185
250
4
3/8
2
260
395
4
1/2
2
260
615
4
1 All values are for anchors installed in light-, medium-, or normal-weight hollow concrete masonry units conforming to ASTM C 90.
2 Tabulated embedment depth is the length of the plastic HIT-SC screens.
3 Anchors shall be installed in the face of the hollow CMU masonry wall. A maximum of two anchors for each cell of the HCMU block is allowed.
4 Tabulated values are for one anchor installed in the center of the cell of the hollow CMU. When two anchors are installed in the same cell, they shall be spaced a minimum of 4 inches apart, and
their allowable load reduced by 30%.
5 The minimum edge distance, cmin, is the minimum edge distance for which values are available and installation is recommended. Edge distance is measured from the center of the anchor to the
closest edge.
6 Anchors are not recognized for resisting earthquake forces. For short-term loading due to wind forces, the allowable loads shall not be increased.
7 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
8
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
1.3 Technical Data
Allowable Tension and Shear Loads for Threaded Rods in the
Vertical Face of Hollow Clay Brick (lb)
Anchor Diameter
(inches)
Embedment
(inches)2
Tension Load
Shear Load
1/4
3-1/4
275
230
5/16
3-1/4
425
400
3/8
3-1/4
580
700
1/2
3-1/4
580
1030
Minimum Spacing,
smin (inches)
Minimum Edge
Distance, cmin
(inches)
8
12
1
2
3
4
5
All values are based on mortar shear strength of 40 psi or greater.
Tabulated embedment depth is the length of the plastic HIT-SC screens.
Anchors shall be installed in the face of the brick wall and in the center of the individual brick.
No more than one anchor shall be permitted to be installed in each brick.
The minimum edge distance, cmin, and the minimum spacing, smin, are the minimum distances for which values are available and installation is recommended. Edge distance is measured from
the center of the anchor to the closest edge. Spacing is measured from the center of one anchor to the center of an adjacent anchor
6 No adjustment for wind or earthquake loading is permitted with the tabulated loads.
7 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
Gel Time Table (Approximate)
Minimum Base-Material Temperature
Curing Time Table (Approximate)
°F
°C
Approximate Gel
Time
32
0
41
50
68
Minimum Base-Material Temperature
°F
°C
Approximate Curing
Time
10 minutes
32
0
4 hours
5
10 minutes
41
5
2 hours
10
8 minutes
50
10
1.5 hours
20
5 minutes
68
20
45 minutes
86
30
3 minutes
86
30
30 minutes
104
40
2 minutes
104
40
20 minutes
For SI: °C = 5/9 (°F - 32 °F)
For SI: °C = 5/9 (°F - 32 °F)
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
9
Hilti Adhesive Anchor
1.3 Technical Data
Figure 1 —
­ Influence of Base Material Temperature on Bond Strength of Hilti HIT-HY 10 PLUS1, 2
120
% of Allowable Load Values
110
100
90
80
70
60
50
0 2040 6080100120
140160
180200
Base Material Temperature, °F
1 S
hort term temperature loading only for temperatures greater than 122 °F. Short term elevated temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long
term temperatures are roughly constant over significant periods of time.
2 Published allowable tension and shear loads shall be reduced by the reduction percentage listed above.
10
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
1.3 Technical Data
Figure 2 — Locations for HIT-HY 10 PLUS Anchor System in Grout-Filled CMU
(Anchor Installation is Restricted to Non-Shaded Area)
Figure 3 — Edge Distances for Anchors Installed in the Vertical Face of Concrete Masonry Wall Contruction (Left); Edge
and End Distances for Threaded Rods Installed in the Top of Grout-Filled CMU Masonry Wall Construction
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
11
Hilti Adhesive Anchor
1.3 Technical Data
HIT-HY 10 PLUS Installation Specification Tables
Setting Details of Hilti HIT-HY 10 PLUS with Threaded Rod HAS
Inch Sizes
Rod Diameter
din.
3/8
1/2
5/8
3/4
Drill Bit Diameter
d0in.
7/16
9/16
3/4
7/8
Embedment Depth (concrete)
hefin.
2-1/4 to 4-1/2
3 to 6
3-3/4 to 7-1/2
4-1/2 to 9
Embedment Depth (grout-filled CMU)
hefin.
3-3/8
4-1/2
5-5/8
6-3/4
Installation Torque
Tinstft-lb
15
20
50
105
Diameter of Clearance Hole
dfin.
7/16
9/16
11/16
13/16
Minimum Base Material Thickness
hminin.
hef + 2 in.
hef + 2 in.
hef + 2 in.
hef + 2 in.
#3
#4
#5
#6
din.
3/8
1/2
5/8
3/4
Drill Bit Diameter1
d0in.
7/16
9/16
3/4
7/8
Embedment Range hef,min - hef,max
hefin.
2-1/4 to 4-1/2
3 to 6
3-3/4 to 7-1/2
4-1/2 to 9
Minimum Base Material Thickness
hminin.
hef + 2 in.
hef + 2 in.
hef + 2 in.
hef + 2 in.
10M
15M
20M
dmm
10
15
20
Drill Bit Diameter1
d0in.
9/16
3/4
1
Embedment Range hef,min - hef,max
hefmm
60 - 115
95 - 190
115 - 230
Minimum Base Material Thickness
hminmm
hef + 50
hef + 50
hef + 50
Setting Detail
Setting Details of Hilti HIT-HY 10 PLUS with Reinforcement Bars
US Inch Reinforcement Bar Sizes
Setting Parameter
Symbolunit
Rod Diameter
Setting Detail
1 Rebar diameter may vary. Use smallest drill bit that will accommodate rebar.
Canadian Reinforcement Bar Sizes
Setting Parameter
Symbolunit
Rod Diameter
Setting Detail
1 Rebar diameter may vary. Use smallest drill bit that will accommodate rebar.
12
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Hilti Adhesive Anchor
1.3 Technical Data
Setting Details of Hilti HIT-HY 10 PLUS with HAS
Characteristic
Hollow Concrete Masonry
Clay Brick with Holes
Symbol
Units
Anchor Rod Size
d
in.
1/4
5/16
3/8
1/2
5/16
3/8
1/2
Drill Bit Diameter
d0
in.
1/2
5/8
5/8
11/16
5/8
5/8
7/8
Minimum Hole Depth
h0
in.
Through face cell
3-3/4
Effective Embedment Depth
hef
in.
2
3-1/8
mm
12 x 50
16 x 50
16 x 50
18 x 50
16 x 85
16 x 85
18 x 85
Tinst
ft-lb
2.2
2.2
3.0
4.5
2.2
3.0
4.5
Small
24
16
16
9
8
8
5
Medium
38
25
25
15
13
13
8
-
ml
12
18
18
30
35
35
55
MD 2500
-
Approx.
number of
trigger pulls
2
3
3
5
6
6
9
ED 3500
-
Approx.
number of
trigger pulls
3
4
4
7
8
8
12
Required Screen
Installation Torque
Approximate Fastening
per Cartridge1
Approximate Filling Volume
2
HAS Rod
HAS Rod
1 Assumes no waste.
2 Screen must filled entirely prior to inserting threaded rod.
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
13
Material Safety Data Sheet
MSDS No.: Revision No.: Revision Date: Page: Product name:
HILTI HY10 Plus Adhesive
Description:
Methacrylate resin and hardener. Part A is in the large tube; Part B is in the small one.
Supplier:
Hilti, Inc. P.O. Box 21148, Tulsa, OK 74121
Emergency # (Chem-Trec.):
1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
334
001
08/05/10
1 of 2
INGREDIENTS AND EXPOSURE LIMITS
Ingredients:
CAS Number:
TLV:
PEL:
STEL:
Part A:
Quartz sand
14808-60-7
0.025 mg/m3 (R)
10
mg/m3(R)
_________
%SiO2 + 2
NE
27813-02-1
3290-92-4
7631-86-9
NE
NE
NE
NE
NE
NE
NE
NE
NE
14808-60-7
0.025 mg/m3 (R)
10
mg/m3(R)
_________
%SiO2 + 2
NE
00094-36-0
5 mg/m3
5 mg/m3
NE
Hydroxypropyl methacrylate
Trimethylolpropane trimethacrylate
Amorphous silica
Part B:
Quartz sand
Dibenzoyl peroxide
Abbreviations: (R) indicates “as respirable dust”. PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. STEL = Short Term Exposure Limit (15 minute time-weighted average). NE = None Established.
PHYSICAL DATA
Appearance:
Gray paste
Odor:
Ester-like odor
Vapor Density: (air = 1)
Not determined
Vapor Pressure (@68° F)
Not determined
Boiling Point:
464° F
VOC Content:
36 g/l
Evaporation Rate:
Not determined
Solubility in Water:
Insoluble
Specific Gravity:
1.7
pH:
6 (part B)
FIRE AND EXPLOSION HAZARD DATA
Flash Point:
>214° F
Ignition Temperature:
Extinguishing Media:
CO2, Dry Chemical, Foam, Water spray
Special Fire Fighting Procedures:
Use a self-contained breathing apparatus when fighting fires involving chemicals.
Unusual Fire and Explosion Hazards:
None known. Thermal decomposition products can be formed.
671° F
REACTIVITY DATA
Stability:
Dibenzoyl peroxide decomposes (non-violently) at 150° F. Ignition does not occur due to the water
content (> 5%).
Hazardous Polymerization:
Will not occur.
Incompatibility:
Strong acids and oxidizing agents. Do not store in direct sunlight.
Decomposition Products:
Thermal decomposition can yield C 0O and NOx.
Conditions to Avoid:
Avoid temperature extremes which could shorten the shelf-life of this product; i.e. below 41° F and
above 77° F. (See handling and storage requirements).
HEALTH HAZARD DATA
Known Hazards:
Eye and skin irritation. Possible sensitizer.
Signs and Symptoms of
Exposure:
Eyes: Can cause irritation. Skin: Prolonged and repeated contact can cause irritation. An
allergic skin reaction (sensitization e.g. rash, itching, reddening) can occur with some individuals.
Inhalation: Possible irritation. Ingestion: Not a likely route of exposure. 14
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
Material Safety Data Sheet
MSDS No.: Revision No.: Revision Date: Page: 334
001
08/05/10
2 of 2
Routes of Exposure:
Contact. Inhalation.
Carcinogenicity:
IARC classifies crystalline silica (quartz sand) as a Gp I carcinogen based upon evidence among
workers in industries where there has been long-term and chronic exposure (via inhalation) to silica
dust. This product does not pose a dust hazard; therefore, this classification is not relevant.
Medical Conditions
Aggravated by Exposure:
Eye, skin, and respiratory conditions.
EMERGENCY AND FIRST AID PROCEDURES
Eyes:
Flush with plenty of water. Contact a physician if symptoms occur.
Skin:
Wash with soap and water. Inhalation:
Move victim to fresh air. Contact a physician if symptoms persist.
Ingestion:
Do not induce vomiting unless directed by a physician. Contact a physician immediately.
Other:
Referral to a physician is recommended if there is any question about the seriousness of the injury/
exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
Ventilation:
General (natural or mechanically induced fresh air movements).
Eye Protection:
Safety glasses with side shields.
Skin Protection:
Impermeable gloves recommended.
Respiratory Protection:
None normally required. Where ventilation is inadequate to control vapors, use a NIOSH-approved
respirator with organic vapor cartridges. If dusts are generated during demolition or removal, wear
an appropriate dust mask or respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
Handling and Storing
Precautions:
Store in a cool, dry area preferably between 41º and 77º F. Do not store in direct sunlight. Avoid
prolonged or repeated contact. Use with adequate ventilation. Always wash thoroughly after
handling chemical products. For industrial use only. Keep out of reach of children.
Spill Procedures:
Take up with an absorbent material and place in a container for proper disposal.
REGULATORY INFORMATION
Hazard Communication:
This MSDS has been prepared in accordance with the federal OSHA Hazard Communication
Standard. 29 CFR 1910.1200.
HMIS Codes:
Health 1, Flammability 1, Reactivity 0, PPE B
DOT Shipping Name:
Not regulated
IATA / ICAO Shipping Name:
Not regulated
TSCA Inventory Status:
All chemical components listed on TSCA inventory.
SARA Title III, Section 313:
This product contains 5 - 10% Benzoyl peroxide (CAS #94-36-0) which is subject to reporting
under Section 313 of SARA Title III (40 CFR Part 372).
EPA Waste Code(s):
Not regulated by EPA as a hazardous waste
Waste Disposal Methods:
Consult with regulatory agencies or your corporate personnel for disposal methods that comply
with local, state, and federal safety, health and environmental regulations.
CONTACTS
Customer Service:
1 800 879 8000
Health / Safety:
1 800 879 6000
Emergency # (Chem-Trec):
1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
Technical Service: 1 800 879 8000
The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 10 PLUS Submittal Information 01/12
15
Hilti. Outperform. Outlast.
P.O. Box 21148, Tulsa, OK 74121 • Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti
(Canada) Corp. 1-800-363-4458 www.hilti.ca • Hilti is an equal opportunity employer • Hilti is a registered trademark of Hilti, Corp.
©Copyright 2012 by Hilti, Inc. (U.S.) H461 • 3487152 • 02/12 • DBS
The data contained in this literature was current as of the date of publication. Updates and changes may be made
based on later testing. If verification is needed that the data is still current, please contact the Hilti Technical
Support Specialists at 1-800-363-4458. All published load values contained in this literature represent the results
of testing by Hilti or test organizations. Local base materials were used. Because of variations in materials, on-site
testing is necessary to determine performance at any specific site. Laser beams represented by red lines in this
publication. Printed in the United States