Series Series
MULTIPLE SPLIT TYPE AIR CONDITIONERS
Series
CM05EU4-E
High COP (energy consumption efficiency)
Achieved Top class in the Industry
Comparison of COP (energy consumption efficiency) <10 HP system>
COP 4.0
3.5
50%
Energy
saving
Comparing to the current energy
saving type,
14.5%
Energy
saving
COP upgraded by about 15%!
3.0
2.5
2.0
0
3.39
3.88
2.58
Comparing to our equivalent product
10 years before,
COP upgraded by about 50%!
(10HP equivalent model)
Our equivalent
product 10 years
before
CITY MULTI
Inverter driven outdoor fan motor
newly employed!
R410A highly efficient inverter
compressor employed!
• Improvement of
heat exchanger performance
• Newly designed refrigerant circuit
(low pressure loss)
Resulting in Total Energy
Conservation
Heating operation range covers an outdoor
temperature of down to -20˚C (wet bulb temperature)
Operating range in
cooling is from an
outdoor temperature
of -5˚C, while that in
heating has
expanded to an
outdoor temperature
of -20˚C!
The operation range
can now cover even
cold regions.
✻ -12˚C~15˚C for
PUMY series.
Operable even in
very cold regions
Under heating
-20˚C
✻
Outdoor temperature
(wet bulb temperature)
15.5˚C
✻
Under cooling
Outdoor temperature
(dry bulb temperature)
-5˚C
-20
-10
0
10
20
30
43˚C
40
High static pressure of 60Pa
achieved, the industry top class*
Flexibility in air conditioning design has been enlarged with a high static
pressure of 60Pa.
(except PUMY series)
Facilitated connection
of supply hood
*Optional parts
Outdoor unit packing
without using wooden materials
The use of wooden frame for the transport of the outdoor unit has been discontinued. The structure is so designed that the unit can be
transported with a forklift not using wooden frames or pallets. This contributes in reducing waste and preserving the global environment.
Eliminating wood consumption
thanks to the wooden packing
discontinued.
Transportable by a forklift
without using pallets.
Night Mode Quiet
operation can reduce
sound level of 8dB!
(10HP)
Front and rear double
suction structure
CITYMULTI
Series Night mode quiet
operation can reduce sound level by
sensing ambient temperature condition.
Air passage and machine
compartment separated
57dB
dB
above
˚C
30
(10HP)
49dB
dB
below
˚C
30
*Needs to set night mode setting at the site.
*Night mode could be turn off automatically due to ambient
temperature and required capacity load condition.
The front and rear double suction structure
provides the smooth airflow to reduce the
pressure loss, which results in low noise.
The machine compartment is sealed up to
attain the low noise level in all directions.
(except PUMY series)
“All
Directions”
Series provide
for air conditioning comfort with
MITSUBISHI ELECTRIC's
leading edge technologies.
Less cold draught,
More comfort
Only with
MITSUBISHI
ELECTRIC
CITYMULTI
Series can change the target evaporating
temperature during cooling mode.
Unit with higher off coil temperature can offer more comfort due
less chance of cold draughts.
Conventional Model
CITYMULTI
Cooling Operation
Set Temperature
of 14˚C (except PUMY series)
By selecting a dip switch on the
unit, a cooling operation set
temperature of 14˚C is possible on
the floor standing and ceiling
concealed models. Suitable for
lower set temperature applications
like Gymnasiums etc,,,.
Series
Only with
MITSUBISHI
ELECTRIC
High-capacity
reluctance DC motor
drive compressor
Motor efficiency greatly improved +
Reduced suction refrigerant heating loss
Anti-Corrosion
Blue Fin as a
Standard!
CITYMULTI
Series will
have an Anti-Corrosion heat
exchanger (Blue Fin) as a
standard.
Industry Top class
Low Noise Design
New Fan Design
City Multi Y/R2 VRF systems led the introduction of larger single fan rotors
some ten years ago and achieved substantially lower noise levels over
multiple designs. Continuing development in the areas of blade shape and
weight has achieved higher performance and lower noise level.
Conventional model fan
New model fan
Mitsubishi Electric
City Multi
Series
– towards a new era of
highly advanced air conditioning –
As a market leading company,
Mitsubishi Electric offers the
"State of the Art" City Multi
VRF
system, adopting
advanced refrigeration & control
technology, thereby achieving
high performance and ultimate
design flexibility.
1
Series Product Lineup
Outdoor Unit
New
Air Cooled System
4HP 5HP 6HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP
Heat Pump
Heat Recovery
28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 50HP
Heat Pump
Water Cooled System
8HP
10HP
16HP
20HP
Heat Pump
Heat Recovery
PLFY-P VCM-E/VAM-E
........p.27, 28 / 41, 42
Indoor Unit
PEFY-P VMH-E
........p.35 / 51, 52
PLFY-P VLMD-E
........p.29 / 43, 44
PCFY-P VGM-E
........p.36 / 53
PMFY-P VBM-E
........p.30 / 45
PKFY-P VAM-E/VGM-E
/VFM-E
........p.37 / 54, 55
PEFY-P VMR-E-L/R
New ........p.31 / 46
New PEFY-P VMS-E
........p.32 / 47
New
PFFY-P VKM-E
........p.38 / 56
PFFY-P VLEM-E/VLRM-E
........p.39 / 57, 58
PEFY-P VML-E
........p.33 / 48
PEFY-P VMM-E
........p.34 / 49, 50
PEFY-P VMH-E-F
........p.40 / 59, 60
Lossnay/OA Processing Units
Air Conditioning MANAGEMENT SYSTEM
2
FEATURES
Effective space utilization thanks to a
small installation space.
The installation space of the outdoor unit has
greatly been reduced. The reduction counts for
about 33%* maximum comparing to our
conventional CITY MULTI Series.*24·26HP outdoor units
Effective utilization of vacant spaces
The compact design
and isolated installation
of each unit allow
utilization of vacant
spaces effectively.
conventional CITY MULTI
24
450
450
840
840
450
26
HP
33%
450
Easy installation
even in a
narrow space
reduction
1990
2990
3.46m2
5.20m2
*Image of 28~32HP system
Outdoor unit installation space (including service space)
4~6HP
8~14HP
16HP
1unit
18~26HP
1unit
28~32HP
1unit
34~50HP NEW
2units
2units
Installation Space
Air Cooled
1unit
1990
450
150
840
330
630
1740
840
450
1740
10
950
1690
840
1390
(1540)
150
450
10
0.61m2
450
990
0.99m2
450
990
1290
1990
1.72m2
2.24m2
3.46m2
WY Series (Heat Pump)
10HP
16HP
8HP
Installation Space
Water Cooled
(upside piping)
1740
450
10
990
20HP
10
1990
100
(250)
450
840
840
450
450
2690
3.74(4.14)m2
8HP
6.94m2
WR2 Series (Heat Recovery)
10HP
16HP
20HP
550
550
550
550
450
450
450
450
1,980
1.98m2
1,980
990
0.99m2
1.98m2
Easy carrying-in by single package design
Reduced carrying-in process thanks to the single package configuration
For lifting up to building rooftop with a crane
For field
combining type
As the lifting up and
down operation is
repeated frequently, the
installation work longer.
3
One
shot
The CITY MULTI
(4~26HP) can be
delivered in one go,
thus allowing far
speedier installation.
R2 WR2
The World's First and Only "2-Pipe" Heat Recovery System
The Innovative BC Controller Which Makes a 2-pipe System Possible
BC Controller Operation
Operation primarily for cooling
Check valve
Cooling
High
Low pressure gas
pressure
Low pressure pipe
gas
Heat
exchanger Compressor
Fan
Low pressure 2-phase
Cooling
Cooling
High
pressure gas
Gas/liquid
separator
Heating
Total heat recovery operation
Operation primarily for cooling
Outdoor unit
4-way valve
Total heat recovery operation
BC controller
Switching valve Indoor unit
Heating
Low pressure gas
Low pressure gas
Cooling
High
pressure gas
Cooling
High
pressure gas
Low pressure gas Low pressure 2-phase
High pressure liquid
LEV
High pressure 2-phase
High pressure pipe
Heating
Low pressure gas
High pressure gas
Low pressure gas
Low pressure 2-phase
High pressure liquid
High pressure 2-phase
High pressure liquid
R2 WR2
R2 WR2
Achieving smallest number
of pipework connection
thanks to 2-pipe system
Heat Recovery System can
create maximum of 15HP
capacity from 10HP unit!
Comparison of piping connection
The waste heat recovery system in the refrigerant system increases the energysaving effect as the cooling and heating simultaneous operation is carried out.
City Multi R2/WR2
=2 connections
=3 connections
Total number of connections
20
Outdoor unit
BC Controller
Outdoor unit
input
10HP Cooling 5HP: Waste heat utilized
A Heating 10HP, Cooling 5HP, Total 15HP
Indoor unit output
B Heating 7.5HP, Cooling 7.5HP, Total 15HP
Cooling 10HP
C
(
Cooling capacity of each indoor
unit is approx. 10/15 of the rating.
)
Operation pattern of
New City Multi R2 System
7.5HP
Optimum operation pattern
10HP
In the same mode, the
compressor capacity is the
maximum output
(in this case 10HP).
15HP
(
Heating indoor unit
Indoor unit
The total number of connections for City Multi R2 is only
68 when the 16 indoor units are installed.
10HP
Total 15HP indoor
unit is connected with
10HP outdoor unit.
)
A Primarily heating operation
B Total heat recovery operation
7.5HP
5HP
3-pipe type
C
Total number of connections
5HP 7.5HP
58
15HP
10HP
Cooling indoor unit
Outdoor unit
R2 WR2
The more frequently cooling and heating simultaneous
operation is carried out, the higher the energy-saving effect is.
COP in heat recovery operation
Branch unit
Number of branches 2-pipe type
4
20
10
44
16
68
3-pipe type
58
154
–
Energy consumption efficiency (COP)
8
Indoor unit
Cooling and heating balance operation
7
Cooling and heating
simultaneous and primarily
cooling operation
6
Cooling and heating
simultaneous and primarily
heating operation
5
4
3
Cooling and heating non-simultaneous model
2
1
0
20
40
60
80
Heating
100 ratio
4
FEATURES
Downsizing of refrigerant
piping connections
Gas
Gas piping
piping :: downed
downed by
by 2 sizes
sizes
Liquid
Liquid piping
piping :: downed
downed by
by 1 size
size
By making the connection diameter of refrigerant piping
smaller, the piping space can be minimized, and the ease of field
installation. Workability upgraded and the piping materials reduced.
Comparison of piping size (for 10HP system)
Conventional type
List of major piping sizes
System capacity
4~6HP system
8HP system
10/12HP system
14HP system
16HP system
18~26HP system
28~32HP system
34~50HP system
CITY MULTI
type
Gas
piping
Liquid
piping
Gas
piping
Liquid
piping
φ28.58
φ12.7
φ22.2
φ9.52
(10HP
(10HP system)
system)
Liquid piping
φ9.52
Gas piping
φ15.88
φ19.05
φ22.2
φ12.7
φ15.88
φ19.05
φ28.58
φ34.93
φ41.28
Significant reduction of field piping connections
Eliminating the
oil equalizing pipe
(8~32HP)
The single package design eliminates the oil equalizing pipe and
the piping between outdoor units, thus upgrading the reliability,
reducing complexity and reducing the installation cost.
4~14HP
16HP
18~26HP
28~32HP
34~50HP
NEW
Oil equalizing
pipe not
required
Liquid piping
Piping between
units not
required
Gas
piping
Liquid
piping
Gas piping
Liquid
piping
Gas piping
Oil equalizing
pipe not
required
Oil equalizing
piping
Liquid
piping
Connection spot : 6
Connection spot : 2
Gas
piping
Connection spot : 12
*The actual product may differ from the photo.
Upgrading reliability by minimizing the number
of parts and providing back up function
18~26HP
28~32HP
In case of one
compressor fails,
Facilitating
maintenance work by
minimizing the number
of parts, and
upgrading reliability by
simplifying
construction designed
5
Compressor
In case of one
compressor fails,
34~50HP
NEW
Alternate
operation
Compressor
Compressor
Compressor
backup operation
Compressor
Compressor
backup operation
Backup In case of
operation malfunction
mulfunction
Realizing refrigerant piping total length of
400m* top class in industry *CITY
*CITY MULTI
MULTI R2
R2 Series
Series
S Series (4~6HP)
Refrigerant Piping Restrictions
Total length........................................................
Furthest length..................................................
Furthest length after first branch.......................
Top-bottom differentials between units
Between indoor unit and outdoor unit
(outdoor unit is upper)......................................
Between indoor unit and outdoor unit
(outdoor unit is lower)........................................
Between indoor units.........................................
120m or less
80m or less
30m or less
30m or less
20m or less
12m or less
Y Series (8~32HP)
Refrigerant Piping Restrictions
Total length........................................................
Furthest length..................................................
Furthest length [equivalent length]...................
Furthest length after first branch.......................
Top-bottom differentials between units
Between indoor unit and outdoor unit
(outdoor unit is upper)......................................
Between indoor unit and outdoor unit
(outdoor unit is lower)........................................
Between indoor units.........................................
300m or less
150m or less
175m or less
40m or less
Y Series
Outdoor unit
50m or less
40m or less*
15m or less
Top-bottom differential 50m
Furthest piping length
175m (equivalent length)
(actual length 150m)
* 4m or less in cooling at outdoor temperature 0˚C or lower.
Indoor unit
between indoor units
top-bottom differential
15m
Y Series (34~50HP)
Refrigerant Piping Restrictions
Total length........................................................
Furthest length..................................................
Furthest length [equivalent length]...................
Furthest length after first branch.......................
Between Main and Sub outdoor unit.................
Top-bottom differentials between units
Between indoor unit and outdoor unit
(outdoor unit is upper)......................................
Between indoor unit and outdoor unit
(outdoor unit is lower)........................................
Between indoor units.........................................
Between Main and Sub outdoor unit.................
300m or less
150m or less
175m or less
40m or less
4m or less
50m or less
Outdoor unit
40m or less*
15m or less
0.1m or less
* 4m or less in cooling at outdoor temperature 0˚C or lower.
Top-bottom differential 50m
Indoor unit
Furthest piping length
175m (equivalent length)
(actual length 150m)
between indoor units
top-bottom differential
15m
6
FEATURES
Realizing refrigerant piping total length of
400m* top class in industry *CITY
*CITY MULTI
MULTI R2
R2 Series
Series
R2 Series (P200, P250, P300, P350 type)
Refrigerant Piping Restrictions
Total length............................................................
Furthest length......................................................
Furthest length [equivalent length]........................
Difference between outdoor unit and
BC controller unit...................................................
Difference between BC controller
main-unit and furthest indoor unit.......................
Top-bottom differentials between units
Between indoor unit and outdoor unit (outdoor unit is upper)....
Between indoor unit and outdoor unit (outdoor unit is lower).....
Between indoor unit and BC controller...................
Between indoor units.............................................
R2 Series
300m or less (400m) *2
150m or less
P200, P250, P300, P350 types
175m or less
110m or less
40m or less*3
Between indoor unit and
BC controller topbottom differential 15m
50m or less
40m or less
15m or less (10m) *1
15m or less (10m) *1
*1. Value in ( ) is applied to the P200/P250 type indoor unit.
*2. Please refer to 'refrigerant piping limits' (see the figure) in case of the total length is greater than 300m.
*3. Please refer to 'Limits between BC controller - indoor unit' (see the figure) in case of the piping length between
BC controller and furthest indoor unit is greater than 40m (except P250 indoor unit).
*4. Do not use joint or header for P200/P250 type indoor unit.
*5. Do not connect P200/P250 type indoor unit with the indoor unit of any other capacity at a same branch port.
Outdoor unit
Difference of
height 50m
Furthest piping length
175m (equivalent length)
(actual length 150m)
Between indoor units
top-bottom
differential 15m
Between indoor unit and
BC controller
top-bottom differential 15m
R2 Series (P200 ~ P650 type)
R2 Series
Refrigerant Piping Restrictions
Total length............................................................
Furthest length......................................................
Furthest length [equivalent length]........................
Difference between outdoor unit and
BC controller main-unit..........................................
Difference between BC controller
main-unit and furthest indoor unit..........................
Top-bottom differentials between units
Between indoor unit and outdoor unit [outdoor unit is upper]....
Between indoor unit and outdoor unit [outdoor unit is lower].....
Between indoor unit and BC controller...................
Between indoor units.............................................
Between BC controller main-unit and sub-unit..............
Between indoor unit (BC controller main-unit)
and indoor unit (BC controller sub-unit).......................
300m or less (400m) *1
150m or less
175m or less
110m or less
Top-bottom
differential 50m
40m or less *2
Between indoor unit and
BC controller topbottom differential 15m
50m or less
40m or less
15m or less
15m or less (10m)*3
15m or less
15m or less (10m)*3
* If indoor units (over 16 branches) are connected, two BC controller units are required and there must be three pipes
between BC controllers.
*1. Please refer to 'refrigerant piping limits' (see the figure) in case of the total length is greater than 300m.
*2. Please refer to 'Limits between BC controller - indoor unit' (see the figure) in case of the piping length between
BC controller and furthest indoor unit is greater than 40m (except P250 indoor unit).
*3. Value in ( ) is applied to the P200/P250 type indoor unit.
*4. Do not use joint or header for P200/P250 type indoor unit.
Outdoor unit
P200 ~ P650 types
Furthest piping length
175 m (equivalent length)
(actual length 150 m)
Between indoor units
top-bottom
differential 15m
Between indoor unit and
BC controller
top-bottom differential 15m
In case of a BC controller unit
(16 branches or less)
• Refrigerant Piping Limits
Main pipe and
branch pipe: 2-pipe
Piping total lenght (m)
400
350
Top-bottom
differential
50m or less
300
40
50
60
70
80
90
100
110
Distance between outdoor unit and BC Controller (m)
• Limits between BC contoller - indoor unit
Distance between BC controller (Main) furthest indoor unit (m)
Distribution sub-control
250
200
30
Between indoor
units
topbottom
differential
15m or less
70
110 m or less between outdoor
unit and BC controller (2-pipe)
Three pipes between
BC controllers
Distribution
control
main-unit
Between distribution
controls top-bottom
differential 15m or less
60
50
40
Maximum length between indoor unit and
BC controller 40 m or less (2-pipe)
30
20
10
0
0
5
10
15
Height differential between BC controller (Main) - furthest indoor unit (m)
7
Outdoor unit
In case of two BC controller units
(Over 16 branches)
Series Product Lineup
Wide variation of outdoor unit to adapt with various applications.
Series Type
S Series
A Heat Pump
4HP
5HP
6HP
PUMY-P100YHM
PUMY-P125YHM
PUMY-P140YHM
PUMY-P100VHM
PUMY-P125VHM
PUMY-P140VHM
8HP
10HP
12HP
14HP
16HP
Heat Pump PUHY-P200YGM-A PUHY-P250YGM-A PUHY-P300YGM-A PUHY-P350YGM-A PUHY-P400YGM-A
Y Series A
–
Cooling Only PUY-P200YGM-A PUY-P250YGM-A PUY-P300YGM-A PUY-P350YGM-A
R2 Series A Heat Recovery PURY-P200YGM-A PURY-P250YGM-A PURY-P300YGM-A PURY-P350YGM-A PURY-P400YGM-A
Series Type
24HP
26HP
18HP
20HP
22HP
A Heat Pump PUHY-P450YGM-A PUHY-P500YGM-A PUHY-P550YGM-A PUHY-P600YGM-A PUHY-P650YGM-A
R2 Series A Heat Recovery PURY-P450YGM-A PURY-P500YGM-A PURY-P550YGM-A PURY-P600YGM-A PURY-P650YGM-A
28HP
30HP
32HP
A Heat Pump PUHY-P700YSGM-A PUHY-P750YSGM-A PUHY-P800YSGM-A
Series Type
Series Type
Y Series
Y Series
34HP
36HP
38HP
40HP
42HP
44HP
46HP
48HP
50HP
A Heat Pump PUHY-P850YSGM-A PUHY-P900YSGM-A PUHY-P950YSGM-A PUHY-P1000YSGM-A PUHY-P1050YSGM-A PUHY-P1100YSGM-A PUHY-P1150YSGM-A PUHY-P1200YSGM-A PUHY-P1250YSGM-A
Series Type
Y Series
Series Type
8HP
10HP
16HP
20HP
WY Series W Heat Pump PQHY-P200YGM-A PQHY-P250YGM-A PQHY-P400YSGM-A PQHY-P500YSGM-A
WR2 Series W Heat Recovery PQRY-P200YGM-A PQRY-P250YGM-A PQRY-P400YSGM-A PQRY-P500YSGM-A
Type: A =Air Cooled.
W =Water Cooled.
8
OUTDOOR UNIT
Specifications & External Dimensions
New
S SERIES
R410A
Specifications
Model name
Power source
Cooling capacity
(Nominal)
PUMY-P100YHM
PUMY-P125YHM
PUMY-P140YHM
3-phase, 380-400-415V, 50Hz
11.2
14.0
15.5
*1
kW
9,600
13,300
12,000
*1 kcal / h
38,200
52,900
47,800
*1 Btu / h
14,000
12,500
*2 kcal / h
5.32
3.30
4.27
Power input
kW
8.51-8.09-7.80
5.28-5.02-4.84
6.83-6.49-6.26
Current input
A
2.91
3.39
3.28
COP
15 ~ 24˚C (59~75˚F)
Temp. range of Indoor
W.B.
- 5 ~ 46˚C (23~115˚F)
cooling
Outdoor
D.B.
10 to 46˚C D.B.(50 to 115˚FD.B.) : in case of connecting PKFY-P20/P25 type indoor unit.
18.0
12.5
16.0
Heating capacity
*3
kW
15,500
10,800
13,800
(Nominal )
*3 kcal / h
61,400
42,700
54,600
*3 Btu / h
5.32
3.63
4.29
Power input
kW
8.51-8.09-7.80
5.81-5.52-5.32
6.87-6.52-6.29
Current input
A
3.38
3.44
3.73
COP
15~27˚C (59~81˚F)
Temp. range of Indoor temp.
D.B.
-12~15˚C (10~59˚F)
Heating
Outdoor temp.
W.B.
50 ~ 130% of outdoor unit capacity
Indoor unit
Total capacity
P20 ~ P140 / 1 ~ 8
P20 ~ P125 / 1 ~ 6
P20 ~ P140 / 1 ~ 8
connectable
Model / Quantity
51/53
49/51
50/52
Noise level (measured in anechoic room) dB <A>
φ9.52 (φ3/8" ) Flare
Liquid
mm(in.)
Diameter of
φ15.88 (φ5/38" ) Flare
mm(in.)
refrigerant pipe Gas
Galvanized steel sheet
External finish
<MUNSELL 3Y 7.8/1.1>
1,350 ✕ 950 ✕ 330
mm
External dimension H ✕ W ✕ D
140
kg
Net weight
Salt-resistant cross fin & copper tube
Heat exchanger
Type
Inverter scroll hermetic compressor
Compressor
Maker
Mitsubishi Electric Corporation
Starting method
Inverter
2.9
1.9
2.4
Motor output
kW
Case heater
kW
Lubricant ✕ original charge
MEL56 x 2.3 L
m3 / min
FAN
Air flow rate
100
External static press.
0 Pa
Type ✕ Quantity
Propeller fan ✕ 2
Control, Driving mechanism
DC-control, Direct-driven by motor
kW
Motor output
0.06 x 2
HIC circuit (HIC: Heat Inter-Changer)
Protection
High pressure protection
High pressure sensor, High pressure switch 4.15 MPa
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Compressor
Discharge thermo protection, Over-current protection
Fan motor
Over-heat protection, Voltage protection
Defrosting method
Auto-defrost mode (Reversed refrigerant circle)
Refrigerant
Type x original charge
R410A ✕ 8.5kg ( 19 lb)
Control
LEV circuit
Standard
Document
Installation Manual
attachment
Accessory
Grounded lead wire ✕ 2
Optional parts
Joint: CMY-Y62G-F ; Header:CMY-Y64/68G-F
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
Remark
*3 Nominal heating conditions
*2 Nominal cooling conditions
*1 Nominal cooling conditions
Unit converter
Note:
20˚CDB (68˚FDB)
Indoor: 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB)
kcal= kW ✕ 860
7˚CDB/6˚CWB
35˚CDB (95˚FDB)
Outdoor 35˚CDB (95˚FDB)
Btu/h= kW ✕ 3,412
7.5m (24-9/16ft)
5m (16-3/8ft)
Pipe length: 7.5m (24-9/16ft)
cfm= m3/min ✕ 35.31
0m (0ft)
0m (0ft)
Level difference: 0m (0ft)
lb= kg/0.4536
* Nominal condition *1, *3 are subject to JIS B8615-1
* The specification data is subject to rounding variation.
* Due to continuing improvement, above specifications may be subject to change without notice.
9
OUTDOOR UNIT
Specifications & External Dimensions
New
S SERIES
R410A
Specifications
Model name
Power source
Cooling capacity
(Nominal)
PUMY-P100VHM
PUMY-P125VHM
PUMY-P140VHM
1-phase, 220-230-240V, 50Hz 220V,60Hz
11.2
15.5
14.0
*1
kW
9,600
13,300
12,000
*1 kcal / h
38,200
52,900
47,800
*1 Btu / h
10,000
14,000
12,500
*2 kcal / h
3.34
5.35
4.32
Power input
kW
15.4/14.8/14.1 15.4
24.7/23.6/22.7
24.7
20.0/19.1/18.3 20.0
Current input
A
3.35
2.90
3.24
COP
15 ~ 24˚C (59~75˚F)
Temp. range of Indoor
W.B.
- 5 ~ 46˚C (23~115˚F)
cooling
Outdoor
D.B.
10 to 46˚C D.B.(50 to 115˚FD.B.) : in case of connecting PKFY-P20/P25 type indoor unit.
12.5
18.0
16.0
Heating capacity
*3
kW
10,800
15,500
13,800
(Nominal )
*3 kcal / h
42,700
61,400
54,600
*3 Btu / h
3.66
5.58
4.33
Power input
kW
16.9/16.2/15.5 16.9
25.8/24.7/23.6
25.8
20.0/19.1/18.3 20.0
Current input
A
3.42
3.23
3.69
COP
15~27˚C (59~81˚F)
Temp. range of Indoor temp.
D.B.
-12~15˚C (10~59˚F)
Heating
Outdoor temp.
W.B.
50 ~ 130% of outdoor unit capacity
Indoor unit
Total capacity
P20 ~ P125 / 1 ~ 6
P20 ~ P140 / 1 ~ 8
connectable
Model / Quantity
51/53
49/51
50/52
Noise level (measured in anechoic room) dB <A>
φ9.52 (φ3/8" ) Liquid
Liquid
mm(in.)
Diameter of
φ15.88 (φ5/38" ) Gas
mm(in.)
refrigerant pipe Gas
Galvanized steel sheet
External finish
<MUNSELL 3Y 7.8/1.1>
1,350 ✕ 950 ✕ 330
mm
External dimension H ✕ W ✕ D
127
kg
Net weight
Salt-resistant cross fin & copper tube
Heat exchanger
Type
Inverter scroll hermetic compressor
Compressor
Maker
Mitsubishi Electric Corporation
Starting method
Inverter
3.3
2.2
Motor output
kW
2.9
Case heater
kW
Lubricant ✕ original charge
MEL56 x 2.3 L
m3 / min
FAN
Air flow rate
100
External static press.
0 Pa
Type ✕ Quantity
Propeller fan ✕ 2
Control, Driving mechanism
DC-control, Direct-driven by motor
kW
Motor output
0.06 x 2
HIC circuit (HIC: Heat Inter-Changer)
Protection
High pressure protection
High pressure sensor, High pressure switch 4.15 MPa
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Compressor
Discharge thermo protection, Over-current protection
Fan motor
Over-heat protection, Voltage protection
Defrosting method
Auto-defrost mode (Reversed refrigerant circle)
Refrigerant
Type x original charge
R410A ✕ 8.5kg ( 19 lb)
Control
LEV circuit
Standard
Document
Installation Manual
attachment
Accessory
Grounded lead wire ✕ 2
Optional parts
Joint: CMY-Y62G-F ; Header:CMY-Y64/68G-F
Only one indoor unit of Fresh Air type is connected with one outdoor unit.
Remark
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
*1 Nominal cooling conditions
*2 Nominal cooling conditions
*3 Nominal heating conditions
Unit converter
Note:
Indoor: 27˚CDB/19˚CWB
27˚CDB/19.5˚CWB
20˚CDB
kcal= kW ✕ 860
Outdoor 35˚CDB
35˚CDB
7˚CDB/6˚CWB
Btu/h= kW ✕ 3,412
Pipe length: 10m
5m
10m
cfm= m3/min ✕ 35.31
Level difference: 0m (0ft)
0m (0ft)
0m (0ft)
lb= kg/0.4536
* Nominal condition *1, *3 are subject to JIS B8615-1
* The specification data is subject to rounding variation.
* Due to continuing improvement, above specifications may be subject to change without notice.
10
OUTDOOR UNIT
New
Specifications & External Dimensions
S SERIES
R410A
External Dimensions
PUMY-P100,125,140YHM / PUMY-P100,125,140VHM
Unit : mm
Rear Air Intake
Service space
2-12 X 36 Oval holes
(Foundation Bolt M10)
500
Air Discharge
70
56
(
950
Rear Air Intake
322
Handle for moving
42
417
370
330
FOUNDATION
Over
56
10
10m
m
37
Ov
er
Side Air Intake
28
Over
m
175
Installation Feet
53
0m
15
600
30
er
175
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
<Foundation bolt height>
m
0m
Less than
Ov
15
30
er
Ov
500
mm
Over
10
150
Over
FREE
er
2-U Shaped notched holes
(Foundation Bolt M10)
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
Dimensions of space needed
for service access are
shown in the below diagram.
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
Ov
3 FOUNDATION BOLTS
19
2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Ground for the power supply
Side Air Intake
Terminal connection
Left····· For the power supply
Center·····For the transmission line
Right····· For concentration control
)
Ground for the transmission line
Ground for concentration control
Handle for moving
Handle for moving
635
Handle for moving
1350
Service panel
Example of Notes
Handle for moving
✻1507
1
371
Air intake
✻ 1423
920
1 • • • Refrigerant GAS pipe connction ø15.88 (5/8")Flare
2 • • • Refrigerant LIQUID pipe connection ø 9.52 (3/8")Flare
✻1 • • • Indication of STOP VALVE connection location.
23
2
Front piping cover
Piping Knock-Out Hole Details
11
55
92
23
19
71
Rear piping cover
Bottom piping hole
(Knock-Out)
219
40
Power supply wiring hole
(2-ø27Knock-Out)
Rear trunking hole
(Knock-Out)
73 63
63
ø92
73
23 27 92
73 63
27
65
23
92
45
40
55
75
ø 92
Front piping hole
(Knock-Out)
Right trunking hole
(Knock-Out)
81
45
55
Front trunking hole 40
(Knock-Out)
Power supply wiring hole
(2-ø27Knock-Out)
Right piping hole
(Knock-Out)
30
ø92
27
Power supply wiring hole
(2-ø27Knock-Out)
71
92
65
Rear piping hole
(Knock-Out)
220
145
145
145
Drain hole
5-ø33
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
Specifications
Model name
kW (*1)
kcal/h (*2)
BTU/h (*1)
Capacity
kW
A
6.14
10.3/9.8/9.4
3.65
Compressor
Power source
Power input
Current
COP
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
PUHY-P200YGM-A
PUY-P200YGM-A
Cooling
Heating
22.4
25.0
20,000
–
76,400
85,300
Fan
Airflow rate
PUHY-P250YGM-A
PUY-P250YGM-A
Cooling
Heating
28.0
31.5
25,000
–
95,500
107,500
5.98
10.0/9.5/9.2
4.18
4.7
m3/min
L/s
cfm
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Gas side
Refrigerant piping diameter
mm(in.) Liquid side
Refrigerant type
Noise level (dB) (A-characteristic value) (*3)
External finish
kg(lbs)
Net weight
Total capacity
Indoor unit
Model/Quantity
Height (H)
External dimension
mm(in.) Width (W)
Depth (D)
W.B.
Indoor
Temp. range of
D.B.
Outdoor
cooling
D.B
Indoor
Temp. range of
W.B.
Outdoor
heating
φ19.05(φ3/4") Brazed
φ9.52(φ3/8") Flare
56
218(481)
Models P20~P250/1~13
PUHY-P300YGM-A
PUHY-P350YGM-A
PUHY-P400YGM-A
PUY-P300YGM-A
PUY-P350YGM-A
Cooling
Heating
Cooling
Heating
Cooling
Heating
33.5
37.5
40.0
45.0
45.0
50.0
30,000
–
35,000
–
40,000
–
114,300
128,000
136,500
153,500
153,500
170,600
3N ~ 380/400/415V 50/60Hz
7.72
7.62
9.57
9.1
11.39
11.02
13.42
12.43
13.0/12.3/11.9 12.8/12.2/11.7 16.1/15.3/14.7 15.3/14.5/14.0 19.2/18.2/17.6 18.6/17.6/17.0 22.6/21.5/20.7 20.9/19.9/19.2
3.63
4.13
3.50
4.12
3.51
4.08
3.35
4.02
Salt Ptotected Fin
Inverter scroll hermetic compressor
Inverter
6.7
9.7
8.0
9.6
Propeller fan ✕ 1
240
200
4,000
3,333
8,476
7,063
0.64
0.38
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
φ22.2(φ7/8") Brazed
φ28.58(φ1-1/8") Brazed
φ12.7(φ1/2") Flare
φ12.7(φ1/2") Flare
φ9.52(φ3/8") Flare (φ12.7(φ1/2") for over 90m) φ9.52(φ3/8") Flare (φ12.7(φ1/2") for over 40m)
R410A
60
61
57
59
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
233(514)
275(607)
233(514)
233(514)
50~130% of outdoor unit capacity
Models P20~P250/1~20
Models P20~P250/1~22
Models P20~P250/1~16
Models P20~P250/1~19
1840(72-1/2")
990(39")
1290(50-13/16")
840(33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
PUHY-P450YGM-A
Heating
Cooling
50.0
56.0
45,000
–
170,600
191,100
PUHY-P550YGM-A
PUHY-P600YGM-A
PUHY-P650YGM-A
Cooling
Heating
Cooling
Heating
Cooling
Heating
63.0
67.0
67.4
75.0
73.0
81.5
55,000
–
60,000
–
65,000
–
215,000
228,600
230,000
255,900
249,100
278,100
Power source
3N ~ 380/400/415V 50/60Hz
kW
Power input
13.61
13.86
15.59
15.89
17.08
16.37
17.59
17.73
19.65
19.82
A
Current
22.9/21.8/21.0 23.3/22.2/21.4 26.3/25.0/24.0 26.8/25.4/24.5 28.8/27.3/26.4 27.6/26.2/25.3 29.6/28.2/27.1 29.9/28.4/27.4 33.1/31.5/30.3 33.4/31.7/30.6
3.67
COP
4.04
3.59
3.96
3.69
4.09
3.83
4.23
3.72
4.11
Salt Protected Fin
Heat exchanger type
Inverter scroll hermetic compressor + Scroll hermetic
Type
Inverter + Direct
Starting method
6.8 + 5.3
8.2 + 5.3
9.3 + 5.3
10.1 + 5.3
10.9 + 5.3
Motor output (kW)
Type ✕ Quantity
Propeller fan ✕ 2
m3/min
400
L/s
6,667
Airflow rate
cfm
14,126
0.38 ✕ 2
Motor output (kW)
High pressure switch 4.15MPa (601 psi)
High pressure protection
Over-current protection for AC bus, Over-heat protection
Inverter circuit
Over-heat protection/Thermal switch
Compressor/fan
Gas side
φ28.58(φ1-1/8") Brazed
Refrigerant piping diameter
φ15.88(φ5/8") Flare
mm(in.) Liquid side
R410A
Refrigerant type
60/61 (50Hz/60Hz)
61/62 (50Hz/60Hz)
62/62.5 (50Hz/60Hz)
Noise level (dB) (A-characteristic value) (*3)
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
External finish
kg(lbs)
455(1004)
455(1004)
455(1004)
455(1004)
455(1004)
Net weight
Total capacity
50~130% of outdoor unit capacity
Indoor unit
Model/Quantity
Models P20~P250/1~24
Models P20~P250/1~24
Models P20~P250/1~24
Models P20~P250/1~32
Models P20~P250/1~32
Height (H)
1840(72-1/2")
1990(78-3/8")
External dimension
mm(in.) Width (W)
Depth (D)
840(33-1/8")
Indoor
W.B.
15~24˚C (59~75˚F)
Temp. range of
Outdoor
D.B.
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
cooling
Indoor
D.B
15~27˚C (59~81˚F)
Temp. range of
Outdoor
W.B.
-20~15.5˚C (-4~60˚F)
Note: 1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
*1 (JIS Standard: JIS B8615-1) Cooling 27˚C(81˚F)DB/19˚C(66.2˚F)WB Outdoor: 35˚C(95˚F)DB
*2 Cooling Indoor: 27˚C(81˚F)DB/19.5˚C(67.1˚F)WB Outdoor: 35˚C(95˚F)DB *3 It is measured in anechoic room.
Heating Indoor: 20˚C(68˚F)DB
Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
Pipe length: 5m(16-3/8Ft)
Height difference: 0m
Pipe length: 7.5m(24-9/16Ft)
Height difference: 0m
Model name
Capacity
kW (*1)
kcal/h (*2)
BTU/h (*1)
PUHY-P500YGM-A
Cooling
Heating
56.0
63.0
50,000
–
191,100
215,000
Compressor
Fan
Protection
External Dimensions
16
840
65 160
768
16
70
166
20
553
Y
80
57
A
Conn. pipe(Gas)
200: ø19.05 <Brazed>
250: ø22.2 <Brazed>
300: ø22.2 <Brazed>
350: ø28.58 <Brazed>
2X2-14X20 0val hole
ø62 Knockout hole
<Hole for power supply>
(Mounting hole)
Changeable to ø27,ø33 by using
attached conduit mounting plate <Accessory>
80
Knockout hole
<Bottom piping hole>
900(mounting pitch)
45
Air outlet
Cross section X – X
45
990
Top view
265
Conn. pipe(Liquid)
200: ø9.52 <Flare>
250: ø9.52 <Flare>
300: ø9.52 <Flare>
350: ø12.7 <Flare>
Unit : mm
877
ø27 Knockout hole
<Bottom hole for
control wiring>
Y
845(mounting pitch)
PUHY-P200,250,300,350YGM-A
PUY-P200,250,300,350YGM-A
494
A
132
136
136
146
ø53
1840
Air
inlet
135
80
40
1575
Knockout hole
ø27 Knockout hole
<Left side hole for
control wiring>
Service panel
Refrig. service
valve (Liquid)
<Flare>
67 160
X
37
117
117
Left side view
37
100
83
Knockout hole
<Left piping hole> Refrig. service
67 207
valve(Gas)
<Flange>
Knockout hole
<Front piping
hole>
Front view
11 78
235
150
44
X
280
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
Air
inlet
5
Cross section Y – Y
134 100
12
<Accessories>
• Refrigerant (Gas) conn. pipe......1 pc.
(P200type:Packaged in the accessory kit)
(P250,P300,P350type:Already installed on the unit)
• Packing for conn. pipe................1 pc.
(P200type:Not attached)
(P250,P300,P350type:Attached near the ball valve)
• Conduit mouting plate
ø33, ø27..............................1 pc.Each
• Tapping screw M4......................2 pcs.
10 90
Model
200
250
300
350
207
67
12
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
External Dimensions
PUHY-P400YGM-A
Unit : mm
840
Y
503
65 160
1068
Cross section X –
Conn. pipe(Gas)
ø28.58<Brazed>
80 ø62 Knockout hole
<Hole for power supply>
to ø46,ø53 by using
X Changeable
attached conduit mounting plate <Accessory>
Conn. pipe(Liquid)
ø12.7<Flare>
16
20
70
166
80
57
145
Knockout hole
<Bottom piping hole>
877
ø27 Knockout hole
<Bottom hole for
control wiring>
Y
845(mounting pitch)
16
644
2X2-14X20 Oval hole
(Mounting hole)
45
1200(mounting pitch)
45
1290
Top view
ø53
265
Air outlet
Air
inlet
Knockout hole
<Accessories>
• Refrigerant (Gas) conn. pipe......1 pc.
(Already installed on the unit)
• Packing for conn. pipe................1 pc.
(Attached near the ball valve)
• Conduit mouting plate
ø53, ø46.............................1 pc.Each
• Tapping screw M4.....................2 pcs.
135
Service panel
Refrig. service
valve (Liquid)
<Flare>
X
40
67 160
X
235
150
100
Knockout hole
37
115
115
37 <Left piping hole>
Left side view
Refrig. service
valve(Gas)
<Flange>
83
68
355
Knockout hole
<Front piping
hole>
11 78
10
89
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
134 100
44
80
ø27 Knockout hole
<Left side hole for
control wiring>
1575
Cross section Y – Y
1840
Air
inlet
5
280
12
355
68
Front view
PUHY-P450,500,550,600,650YGM-A
16
1000
Y
Y
768
Conn. pipe(Liquid)
ø15.88<Flare>
80
ø62 Knockout hole
3X2-14X20 Oval hole
<Hole for power supply>
Changeable to ø46,ø53 by using
(Mounting hole)
attached conduit mounting plate <Accessory>
16
20
70
162
80
65 160
Conn. pipe(Gas)
ø28.58<Brazed>
553
ø27 Knockout hole
<Bottom hole for
control wiring>
57
145
840
Y
Knockout hole
<Bottom piping hole>
845(mounting pitch)
Y
877
494
45
950(mounting pitch)
950(mounting pitch)
45
1990
Cross section X – X
Top view
ø53
265
Air outlet
Air
inlet
13
40
Service panel
Refrig. service
valve (Liquid)
<Flare>
X
67 160
X
115
115
Left side view
37 <Left piping hole>
100
Refrig. service
valve(Gas)
<Flange>
83
68
205
Knockout hole
<Front piping hole>
Front view
11 78
Knockout hole
37
235
89
134 100
44
80
10
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
135
ø27 Knockout hole
<Left side hole for
control wiring>
1575
Knockout hole
<Accessories>
• Refrigerant (Gas) conn. pipe....1 pc.
(Already installed on the unit)
• Packing for conn. pipe......1 pc.
(Attached near the ball valve)
• Conduit mouting plate
ø53, ø46......1 pc.Each
• Tapping screw M4...2 pcs.
150
Cross section Y – Y
1840
Air
inlet
5
280
12
205
68
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
Specifications
PUHY-P700YSGM-A
Model name
Capacity
kW (*1)
kcal/h (*2)
BTU/h (*1)
Compressor
Power source
Power input
kW
Current
A
COP
Composing unit model name
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
Fan
Airflow rate
m3/min
L/s
cfm
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Heating
88.0
–
300,300
21.7
36.6/34.8/33.5
21.83
Total capacity
Model/Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
Indoor W.B.
Temp. range of cooling
Outdoor D.B.
Indoor D.B
Temp. range of heating
Outdoor W.B.
36.8/35.0/33.7
4.03
3.61
PUHY-P700YGM-A (Compressor unit)
Current
COP
kW (*1)
kcal/h (*2)
BTU/h (*1)
0.64
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
–
–
Propeller fan ✕ 1
240
4,000
8,476
0.64
–
–
Thermal switch
R410A
–
PUHN-P01YGM-A (Heat exchanger unit)
–
–
–
Propeller fan ✕ 1
240
4,000
8,476
0.64
–
–
Thermal switch
0.64
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
φ34.93(φ1-3/8") Brazed
φ28.58(φ1-1/8") Flange / φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed + Flare
φ12.7(φ1/2") Flare / φ12.7(φ1/2") Brazed
–
R410A
62
63
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
155(342)
430(948)
50~130% of outdoor unit capacity
430(948)
Models P20~P250/1~34
155(342)
Models P20~P250/1~34
1840(72-1/2")
1690(66-9/16")
990(39")
1690(66-9/16")
840(33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
990(39")
Cooling
90.0
80,000
Heating
100.0
–
341,200
307,100
3N ~ 380/400/415V 50/60Hz
kW
A
Compressor
Fan
m3/min
L/s
cfm
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Gas side (main)(mm(in.))
Gas side (between Comp unit and HEX unit)(mm(in.)
Liquid side (main)(mm(in.))
Liquid side (between Comp unit and HEX unit)(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg(lbs)
Refrigerant
piping diameter
Total capacity
Model/Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
Indoor W.B.
Temp. range of cooling
Outdoor D.B.
Indoor D.B
Temp. range of heating
Outdoor W.B.
26.75
45.1/42.9/41.3
3.36
26.9
45.4/43.1/41.5
PUHY-P800YGM-A (Compressor unit)
PUHN-P01YGM-A (Heat exchanger unit)
3.72
Salt Protected Fin
Inverter scroll hermetic compressor ✕ 2
Inverter
10.1 + 10.1
Propeller fan ✕ 1
–
–
–
Propeller fan ✕ 1
240
240
4,000
8,476
0.64
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
φ34.93(φ1-3/8") Brazed
φ28.58(φ1-1/8") Flange / φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed + Flare
φ12.7(φ1/2") Flare / φ12.7(φ1/2") Brazed
4,000
8,476
0.64
–
–
Thermal switch
–
R410A
64
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
155(342)
430(948)
50~130% of outdoor unit capacity
Models P20~P250/1~34
1840(72-1/2")
Indoor unit
Note:
25.37
42.8/40.6/39.2
3.72
PUHY-P800YSGM-A
Composing unit model name
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
Airflow rate
24.9
42.0/39.9/38.4
3.37
Inverter scroll hermetic compressor ✕ 2
Inverter
9.4 + 9.4
Propeller fan ✕ 1
240
4,000
8,476
–
Model name
Power source
Power input
75,000
286,600
Heating
94.5
–
322,400
PUHN-P01YGM-A (Heat exchanger unit) PUHY-P750YGM-A (Compressor unit)
Salt Protected Fin
Inverter scroll hermetic compressor ✕ 2
Inverter
8.6 + 8.6
Propeller fan ✕ 1
240
4,000
8,476
Indoor unit
Capacity
Cooling
84.0
3N ~ 380/400/415V 50/60Hz
Refrigerant
piping diameter
Compressor/fan
Gas side (main)(mm(in.))
Gas side (between Comp unit and HEX unit)(mm(in.)
Liquid side (main)(mm(in.))
Liquid side (between Comp unit and HEX unit)(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg(lbs)
PUHY-P750YSGM-A
Cooling
78.4
70,000
267,500
990(39")
840(33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
1690(66-9/16")
1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
*1 (JIS Standard: JIS B8615-1) Cooling 27˚C(81˚F)DB/19˚C(66.2˚F)WB Outdoor: 35˚C(95˚F)DB
*2 Cooling Indoor: 27˚C(81˚F)DB/19.5˚C(67.1˚F)WB Outdoor: 35˚C(95˚F)DB
Heating Indoor: 20˚C(68˚F)DB
Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
Pipe length: 5m(16-3/8Ft)
Height difference: 0m
Pipe length: 7.5m(24-9/16Ft)
Height difference: 0m
*3 It is measured in anechoic room.
14
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
Refrig.service valve
(Liquid pipe to HEX unit)
ø12.7<Flare>
124
Refrig.service valve
(Gas pipe to indoor unit)
ø27 Knockout hole
<Bottom hole for
control wiring>
159
161
107
840
ø75 Knockout hole
<Hole for power supply>
Changeable to ø62 by using
attached conduit mounting plate
<Accessory>
Refrig.service valve
(Gas pipe to HEX unit)
ø28.58<Braze>
877
Unit : mm
Refrig.service valve
(Liquid pipe to indoor unit)
845(mounting pitch)
Knockout hole
<Bottom piping hole>
3 X 2 – 14 X 20 Oval hole
45
800(mounting pitch)
800(mounting pitch)
16
PUHY-P700,750,800YGM-A
16
External Dimensions
45
1690
(Mounting hole)
Cross section X – X
Top view
Service panel
1840
Air
inlet
Knockout hole
Air
inlet
1575
<Accessories>
• Refrigerant conn. pipe with flange (to indoor unit:Gas)....1 pc.
(Already installed on the unit)
• Refrigerant conn. pipe with flange (to HEX unit:Gas).......1 pc.
(Already installed on the unit)
• Packing for conn. pipe with flange (to indoor unit:Gas)....1 pc.
(Attached near ball valve)
• Packing for conn. pipe with flange (to HEX unit:Gas)......1 pc.
(Attached near ball valve)
• Conduit mouting plate
ø62...........................1 pc.
• Tapping screw µ4.....2 pcs.
265
Air outlet
Service panel
ø27 Knockout hole
175
11
78
3
12
241
117 83
Knockout hole
<Front piping hole>
37
254
88
Conn. pipe(Gas)
ø34.93<Braze>
840
845(mounting pitch)
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary space around the
unit and foundation work.
120
60
ø27hole+rubber bush
<Hole for power supply>
(Bottom of controlbox)
2x2-14x20 Oval hole
(Mounting hole)
Cross section x-x
16
82
ø27hole+rubber bush
<Hole for control wiring>
(Bottom of controlbox)
Conn. pipe(Liquid)
ø19.05<Braze+Flare>
Front view
16
Left side view
PUHN-P01YGM-A
877
175
280
134 100
10 89
37
X
X
Knockout hole
<Left side piping
hole for HEX unit>
900(mounting pitch)
45
45
990
Air outlet
Air outlet
265
Top view
1575
Air
inlet
Air
inlet
117
37
67
80
207
134 115
157
207 67
Knockout hole
<Front side piping hole>
Left side view
80
50
40
250
45
11 78
165
10 90
Refrig. service valve
(Liquid pipe to compressor unit)
ø12.7<Braze>
37 117
Air
inlet
Right side view
Front view
877
2690
840
990
Air outlet
HEX unit
10
1690
Compressor unit
265
PUHY-P700,750,800YSGM-A
70
Air
inlet
Knockout hole
<Right side piping hole>
x
x
Refrig. service valve
(Gas pipe to compressor unit)
ø28.58<Braze>
Air
inlet
1840
Air
inlet
Air
inlet
1575
1840
Air
inlet
Gas pipe used to connect
compressor unit and HEX unit
Left side view
15
Liquid pipe used to connect
compressor unit and HEX unit
Conn.pipe(Gas)
ø34.93<Braze>
Front view
Conn.pipe(Liquid)
ø19.05<Braze+Flare>
11
135
<Left side hole for
80 40 control wiring>
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary space around the
unit and foundation work.
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
Specifications
PUHY-P850YSGM-A
Model name
Capacity (*1)
kW
Btu/h(*1)
kcal/h(*2)
Power input
kW
Current input
A
COP
Power source
Heating
96.0
327,500
108.0
368,500
85,000
25.28
–
27.47
42.6/40.5/39.0
3.80
46.3/44.0/42.4
3.93
PUHY-P450YMM-A
PUHY-P400YSM-A
9.4 + 5.3 / 8.5 + 5.3
Propeller fan ✕ 2
8.5 + 5.3 / 8.5 + 5.3
PUHY-P900YSGM-A
Heating
Cooling
113.0
344,600
90,000
385,500
–
29.10
108.0
368,500
26.71
45.0/42.8/41.2
49.1/46.6/44.9
3.78
3.88
Motor output (kW)
Type ✕ Quantity
Fan
m3/min
L/s
cfm
Airflow rate
Protection
Motor output (kW)
High pressure protection
Inverter scroll hermetic comp. + Scroll hermetic comp.
Inverter + Direct
8.5 + 5.3 / 8.5 + 5.3
10.3 + 5.3 / 9.6 + 5.3
Propeller fan ✕ 2
400
400
6,667
14,126
0.38 ✕ 2
30.42
51.3/48.7/47.0
49.3/46.8/45.1
3.69
3.93
PUHY-P550YMM-A
PUHY-P400YSM-A
11.2 + 5.3 / 10.9 + 5.3
Propeller fan ✕ 2
8.5 + 5.3 / 8.5 + 5.3
6,667
400
6,667
14,126
0.38 ✕ 2
14,126
0.38 ✕ 2
6,667
400
6,667
14,126
0.38 ✕ 2
14,126
0.38 ✕ 2
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
φ41.28(φ1-5/8") Brazed
φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed
φ15.88(φ5/8") Flare
φ9.52(φ3/8") Flare
R410A
63/64
63/64
63/64
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
460 (1015)
458 (1010)
460 (1015)
458 (1010)
458 (1010)
PUHY-P1000YSGM-A
Model name
Capacity (*1)
kW
Btu/h(*1)
kcal/h(*2)
Power input
kW
Current input
A
COP
Power source
Composing unit model name
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
Compressor
Fan
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Gas side (main)(mm(in.))
Gas side (between unit and distributor)(mm(in.))
Liquid side (main)(mm(in.))
Liquid side (between unit and distributor)(mm(in.))
Oil balance pipe(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg (lbs.)
Refrigerant
piping diameter
Total capacity
Model / Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
W.B.
Indoor
Temp. range of cooling
Outdoor D.B.
D.B.
Indoor
Temp. range of heating
Outdoor W.B.
PUHY-P1050YSGM-A
Cooling
113.0
385,500
100,000
Heating
127.0
433,300
–
31.11
52.5/49.8/48.0
32.68
55.1/52.4/50.5
3.63
3.89
Cooling
Heating
132.0
450,300
–
34.24
57.8/54.9/52.9
3.86
118.0
402,600
105,000
33.48
56.5/53.6/51.7
3.52
3-phase 4-wire 380/400/415V 50/60Hz
PUHY-P400YSM-A
PUHY-P650YMM-A
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp. + Scroll hermetic comp.
Inverter + Direct
PUHY-P600YMM-A
m3/min
L/s
cfm
460 (1015)
50~130% of outdoor unit capacity
P20~P250 / 1~42
1840 (72-1/2")
1990 (78-3/8")
840 (33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
Total capacity
Model / Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
W.B.
Indoor
Temp. range of cooling
Outdoor D.B.
D.B.
Indoor
Temp. range of heating
Outdoor W.B.
Note:
Propeller fan ✕ 2
400
Propeller fan ✕ 2
Refrigerant
piping diameter
Gas side (main)(mm(in.))
Gas side (between unit and distributor)(mm(in.))
Liquid side (main)(mm(in.))
Liquid side (between unit and distributor)(mm(in.))
Oil balance pipe(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg (lbs.)
Indoor unit
407,700
–
High pressure switch 4.15MPa (601 psi)
High pressure switch 4.15MPa (601 psi)
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection Over-voltage and over-current protection for AC bus, Over-heat protection Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
Over-heat protection/Thermal switch
Over-heat protection/Thermal switch
Inverter circuit
Compressor/fan
Airflow rate
Heating
119.5
95,000
29.23
PUHY-P500YMM-A
PUHY-P400YSM-A
Salt-resistant cross fin & copper tube
Type
Starting method
Indoor unit
PUHY-P950YSGM-A
Cooling
101.0
3-phase 4-wire 380/400/415V 50/60Hz
Composing unit model name
Heat exchanger type
Compressor
Cooling
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
8.5 + 5.3 / 8.5 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
PUHY-P400YSM-A
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
8.5 + 5.3 / 8.5 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
High pressure switch 4.15MPa (601 psi)
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
Over-heat protection/Thermal switch
φ41.28(φ1-5/8") Brazed
φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed
φ15.88(φ5/8") Flare
φ9.52(φ3/8") Flare
R410A
63/64
458 (1010)
63.5/64.5
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
460 (1015)
458 (1010)
460 (1015)
50~130% of outdoor unit capacity
P20~P250 / 1~42
1840 (72-1/2")
1990 (78-3/8")
840 (33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
*1 (JIS Standard: JIS B8615-1) Cooling 27˚C(81˚F)DB/19˚C(66.2˚F)WB Outdoor: 35˚C(95˚F)DB
*2 Cooling Indoor: 27˚C(81˚F)DB/19.5˚C(67.1˚F)WB Outdoor: 35˚C(95˚F)DB
Heating Indoor: 20˚C(68˚F)DB
Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
Pipe length: 5m(16-3/8Ft)
Height difference: 0m
Pipe length: 7.5m(24-9/16Ft)
Height difference: 0m
*3 It is measured in anechoic room.
16
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
Specifications
PUHY-P1100YSGM-A
Model name
Capacity (*1)
kW
Btu/h(*1)
kcal/h(*2)
Power input
kW
Current input
A
COP
Heating
140.0
423,000
110,000
477,600
–
36.39
61.4/58.3/56.2
36.93
62.3/59.2/57.0
39.96
67.4/64.0/61.7
3.41
3.79
3.25
Power source
Composing unit model name
Heat exchanger type
PUHY-P450YMM-A
Compressor
Fan
m3/min
L/s
cfm
Airflow rate
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
9.4 + 5.3 / 8.5 + 5.3
Propeller fan ✕ 2
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
400
6,667
6,667
14,126
–
38.46
64.9/61.6/59.4
3.77
PUHY-P650YSM-A
10.3 + 5.3 / 9.6 + 5.3
Propeller fan ✕ 2
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
400
6,667
6,667
14,126
14,126
0.38 ✕ 2
0.38 ✕ 2
High pressure switch 4.15MPa (601 psi)
14,126
0.38 ✕ 2
0.38 ✕ 2
High pressure switch 4.15MPa (601 psi)
Refrigerant
piping diameter
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
Over-heat protection/Thermal switch
φ41.28(φ1-5/8") Brazed
φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed
φ15.88(φ5/8") Flare
φ9.52(φ3/8") Flare
R410A
64/65
64/65
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
460 (1015)
458 (1010)
458 (1010)
1840 (72-1/2")
1990 (78-3/8")
840 (33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
PUHY-P1200YSGM-A
Model name
Capacity (*1)
kW
Btu/h(*1)
kcal/h(*2)
kW
A
PUHY-P1250YSGM-A
Cooling
136.0
464,000
120,000
44.40
Heating
150.0
511,700
–
39.73
74.9/71.2/68.6
3.06
67.0/63.7/61.4
3.78
Cooling
140.0
Heating
156.5
533,900
–
42.63
71.9/68.3/65.8
3.67
477,600
125,000
47.56
80.2/76.2/73.5
2.94
3-phase 4-wire 380/400/415V 50/60Hz
PUHY-P650YSM-A
PUHY-P600YMM-A
PUHY-P550YMM-A
PUHY-P650YSM-A
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp. + Scroll hermetic comp.
Inverter + Direct
Compressor
Power input
Current input
COP
Power source
Composing unit model name
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
460 (1015)
50~130% of outdoor unit capacity
P20~P250 / 1~42
Total capacity
Model / Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
W.B.
Indoor
Temp. range of cooling
Outdoor D.B.
D.B.
Indoor
Temp. range of heating
Outdoor W.B.
Indoor unit
Fan
m3/min
L/s
cfm
Protection
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Gas side (main)(mm(in.))
Gas side (between unit and distributor)(mm(in.))
Liquid side (main)(mm(in.))
Liquid side (between unit and distributor)(mm(in.))
Oil balance pipe(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg (lbs.)
Refrigerant
piping diameter
Total capacity
Model / Quantity
Height (H)
External dimension
Width (W)
(mm(in.))
Depth (D)
W.B.
Indoor
Temp. range of cooling
Outdoor D.B.
D.B.
Indoor
Temp. range of heating
Outdoor W.B.
17
145.0
494,700
115,000
Inverter + Direct
Gas side (main)(mm(in.))
Gas side (between unit and distributor)(mm(in.))
Liquid side (main)(mm(in.))
Liquid side (between unit and distributor)(mm(in.))
Oil balance pipe(mm(in.))
Refrigerant type
Noise level (dB)
Set
(A-characteristic value) (*3)
External finish
Net weight
kg (lbs.)
Note:
Heating
130.0
443,500
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp. + Scroll hermetic comp.
Motor output (kW)
Type ✕ Quantity
Indoor unit
Cooling
3-phase 4-wire 380/400/415V 50/60Hz
PUHY-P650YSM-A
PUHY-P500YMM-A
Type
Starting method
Airflow rate
PUHY-P1150YSGM-A
Cooling
124.0
11.2 + 5.3 / 10.9 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
11.6 + 5.3 / 11.6 + 5.3
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
High pressure switch 4.15MPa (601 psi)
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
Over-heat protection/Thermal switch
φ41.28(φ1-5/8") Brazed
φ28.58(φ1-1/8") Brazed
φ19.05(φ3/4") Brazed
φ15.88(φ5/8") Flare
φ9.52(φ3/8") Flare
R410A
64/65
458 (1010)
65/65.5
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
460 (1015)
458 (1010)
460 (1015)
50~130% of outdoor unit capacity
P20~P250 / 1~42
1840 (72-1/2")
1990 (78-3/8")
840 (33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
*1 (JIS Standard: JIS B8615-1) Cooling 27˚C(81˚F)DB/19˚C(66.2˚F)WB Outdoor: 35˚C(95˚F)DB
*2 Cooling Indoor: 27˚C(81˚F)DB/19.5˚C(67.1˚F)WB Outdoor: 35˚C(95˚F)DB
Heating Indoor: 20˚C(68˚F)DB
Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
Pipe length: 5m(16-3/8Ft)
Height difference: 0m
Pipe length: 7.5m(24-9/16Ft)
Height difference: 0m
*3 It is measured in anechoic room.
OUTDOOR UNIT
Specifications & External Dimensions
Y SERIES
R410A
External Dimensions
1000
16
494
Y
Y
Y
ø27 Knockout hole
<Bottom hole for control wiring>
70
65 160
16
80
76
57
45
ø62 Knockout hole
Conn. pipe
<To sub unit:Gas>
ø28.58<Brazed>
950(mounting pitch)
950(mounting pitch)
45
1990
80 <Hole for power supply>
768
Changeable to ø46,ø53 by using attached
conduit mounting plate <Accessory>
3✕2–14✕20 Oval hole
(Mounting hole)
Cross section X–X
Top view
ø53
265
Air outlet
5
Air
inlet
Service panel
10
37
115
115
37
Left side view
280
X
X
67 160
235
217
194
163
89
134 100
Knockout hole
<Front piping
hole>
Refrig.service valve
<Gas>
Knockout hole
<Left piping hole>
Refrig.service valve
<Liquid>
100
68
Conn. pipe<Liquid>
ø15.88<Flare>
205
285
48
Service valve
<Oil balance>
ø9.52<Flare>
11 78
135
80 40
ø27 Knockout hole
<Left side hole for
control wiring>
1575
Knockout hole
205
68
Front view
1000
16
494
Refrig.service valve
<Gas>
Y
Y
840
Y
Refrig.service valve
<Liquid>
Y
ø27 Knockout hole
<Bottom hole for control wiring>
16
70
57
92
76
80
20
Knockout hole
<Bottom piping hole>
845(mounting pitch)
PUHY-P450,650YSM-A
1840
Air
inlet
<Accessories>
• Refrigerant(Gas) conn.pipe....1pc.
(Already installed on the unit)
• Packing for conn.pipe....1pc.
(Attached near the ball valve)
• Conduit mounting plate
ø53, ø46...1pc.Each
• Tapping screw M4....2pcs.
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
Note3.This unit is used in combination with
a sub unit.(Refer to Drawing No.W656886
Outline Drawing of Outdoor Unit set)
553
12
Cross section Y–Y
877
145
20
Knockout hole
<Bottom piping hole>
877
Refrig.service valve
<Gas>
840
Y
845(mounting pitch)
Refrig.service valve
<Liquid>
553
PUHY-P450,500,550,
600,650YMM-A
65 160
45
ø62 Knockout hole
768
950(mounting pitch)
950(mounting pitch)
45
1990
80 <Hole for power supply>
Changeable to ø46,ø53 by using attached
conduit mounting plate <Accessory>
3✕2–14✕20 Oval hole
(Mounting hole)
Cross section X–X
Top view
5
877
840
PUHY-P850,900,950,
1000,1050,1100,1150,
1200,1250YSGM-A
Air
inlet
Knockout hole
Air
inlet
ø27 Knockout hole
<Left side hole for
Conn.pipe <Gas>
ø41.28<Brazed>
1575
Service panel
X
X
Conn.pipe
<To main unit:Gas>
ø28.58<Brazed>
67
160
115
115
37
100
Knockout hole
<Left piping hole>
62
68
Knockout hole
<Front piping hole>
Left side view
1990
205
285
48
Service valve<Oil balance>
ø9.52<Flare>
Conn.pipe<Liquid>
ø15.88<Flare>
68
Front view
10
1990
Main unit
Air outlet
205
11 78
37
245
235
217
163
89
134 100
45
135
control wiring>
80 40
10
<Accessories>
• Gas distributor....1pc.
(Already installed on the unit)
• Liquid distributor....1pc.
• Packing for conn. pipe....1pc.
(Attached near the gas distributor)
• Conduit mounting plate
ø53, ø46....1pc.Each
• Tapping screw M4....2pcs.
• Conn. pipe(Gas)....2pcs.
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
Note3.This unit is used in combination with
a main unit.(Refer to Drawing No.W656886
Outline Drawing of Outdoor Unit set)
1840
Cross section Y–Y
280
12
265
ø53
Air outlet
Sub unit
Air
inlet
Air
inlet
Distributor(Gas)
f
PUHY-P850YSGM-A PUHY-P900YSGM-A PUHY-P950YSGM-A PUHY-P1000YSGM-A PUHY-P1050YSGM-A PUHY-P1100YSGM-A PUHY-P1150YSGM-A PUHY-P1200YSGM-A PUHY-P1250YSGM-A
PUHY-P450YMM-A PUHY-P500YMM-A PUHY-P550YMM-A PUHY-P600YMM-A PUHY-P650YMM-A PUHY-P450YMM-A PUHY-P500YMM-A PUHY-P550YMM-A PUHY-P600YMM-A
PUHY-P650YSM-A
PUHY-P400YSM-A
Main unit
Sub unit
Indoor units~
Distributor
Distributor~
Main unit
Distributor~
Sub unit
Oil balance pipe
Liquid
Gas
Liquid
Gas
Liquid
Gas
a
ø19.05
b
c
ø41.28
ø15.88
ø28.58
ø15.88
ø28.58
ø9.52
d
e
f
g
g
e
d
c
Left side view
b
Front view
Distributor(Liquid)
a
Indoor units
Note1.Pipe size is as show in the table on the left.
18
OUTDOOR UNIT
Specifications & External Dimensions
R2 SERIES
R410A
Specifications
Model name
Capacity
kW (*1)
kcal/h (*2)
BTU/h (*1)
Fan
Airflow rate
PURY-P250YGM-A
Heating
Cooling
31.5
28.0
–
25,000
107,500
95,500
PURY-P300YGM-A
PURY-P350YGM-A
PURY-P400YGM-A
Heating
Cooling
Heating
Cooling
Heating
Cooling
50.0
45.0
45.0
40.0
37.5
33.5
–
40,000
–
35,000
–
30,000
170,600
153,500
153,500
136,500
128,000
114,300
3N ~ 380/400/415V 50/60Hz
12.43
13.42
11.02
11.39
9.1
9.57
7.62
7.72
20.9/19.9/19.2
22.6/21.5/20.7
18.6/17.6/17.0
19.2/18.2/17.6
15.3/14.5/14.0
16.1/15.3/14.7
12.8/12.2/11.7
13.0/12.3/11.9
4.02
3.35
4.08
3.51
4.12
3.50
4.13
3.63
Salt Protected Fin
Inverter scroll hermetic compressor
Inverter
6.7
8.0
9.6
9.7
Propeller fan ✕ 1
240
200
4,000
3,333
8,476
7,063
0.64
0.38
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
φ28.58(φ1-1/8") brazed
φ22.2(φ7/8") brazed
φ19.05(φ3/4") brazed
φ22.2(φ7/8") brazed
R410A
57
59
60
61
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
251(554)
251(554)
251(554)
291(642)
50~150% of outdoor unit capacity
Models P20~P250/1~16
Models P20~P250/1~16
Models P20~P250/1~20
Models P20~P250/1~24
1840(72-1/2")
1290(50-13/16")
990(39")
840(33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
5.98
10.0/9.5/9.2
4.18
6.14
10.3/9.8/9.4
3.65
kW
A
Compressor
Power source
Power input
Current
COP
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
PURY-P200YGM-A
Heating
Cooling
25.0
22.4
–
20,000
85,300
76,400
4.7
m3/min
L/s
cfm
Protection device
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Refrigerant piping diameter
Gas side
(mm(in.)) Liquid side
Refrigerant type
Noise level (dB) (A-characteristic value) (*3)
External finish
Net weight
kg (lbs)
Total capacity
Indoor unit
Model/Quantity
Height (H)
External dimension
(mm(in.)) Width (W)
Depth (D)
Temp. range of
W.B.
Indoor
cooling
D.B.
Outdoor
Temp. range of
D.B
Indoor
heating
W.B.
Outdoor
kW (*1)
kcal/h (*2)
BTU/h (*1)
kW
A
Compressor
Power source
Power input
Current
COP
Heat exchanger type
Type
Starting method
Motor output (kW)
Type ✕ Quantity
Fan
Airflow rate
56
236(521)
Models P20~P250/1~15
PURY-P450YGM-A
Cooling
Heating
50.0
56.0
45,000
–
170,600
191,100
Model name
Capacity
φ19.05(φ3/4") brazed
φ15.88(φ5/8") brazed
m3/min
L/s
cfm
Protection device
Motor output (kW)
High pressure protection
Inverter circuit
Compressor/fan
Refrigerant piping diameter
Gas side
(mm(in.)) Liquid side
Refrigerant type
Noise level (dB) (A-characteristic value) (*3)
External finish
kg (lbs)
Net weight
Total capacity
Indoor unit
Model/Quantity
Height (H)
External dimension
(mm(in.)) Width (W)
Depth (D)
Temp. range of
W.B.
Indoor
cooling
D.B.
Outdoor
Temp. range of
D.B
Indoor
heating
W.B.
Outdoor
PURY-P550YGM-A
PURY-P600YGM-A
Cooling
Heating
Cooling
Heating
63.0
67.0
67.4
75.0
55,000
–
60,000
–
215,000
228,600
230,000
255,900
3N ~ 380/400/415V 50/60Hz
13.61
13.86
15.59
15.89
17.08
16.37
17.59
17.73
22.9/21.8/21.0
23.3/22.2/21.4
26.3/25.0/24.0
26.8/25.4/24.5
28.8/27.3/26.4
27.6/26.2/25.3
29.6/28.2/27.1
29.9/28.4/27.4
3.67
4.04
3.59
3.96
3.69
4.09
3.83
4.23
Salt Protected Fin
Inverter scroll hermetic compressor
Inverter
8.2 + 5.3
9.3 + 5.3
10.1 + 5.3
6.8 + 5.3
Propeller fan ✕ 1
Propeller fan ✕ 2
400
6,667
14,126
0.38 ✕ 2
High pressure switch 4.15MPa (601 psi)
Over-voltage and over-current protection for AC bus, Over-heat protection
Over-heat protection/Thermal switch
φ28.58(φ1-1/8") brazed
φ22.2(φ7/8") brazed
φ28.58(φ1-1/8") brazed
R410A
61/62 (50Hz/60Hz)
60/61 (50Hz/60Hz)
Pre-coated galvanized sheets + powder coating (for-BS type) <MUNSEL 5Y 8/1 or similar>
481(1061)
481(1061)
481(1061)
481(1061)
50~150% of outdoor unit capacity
Models P20~P250/1~24
Models P20~P250/1~24
Models P20~P250/1~24
Models P20~P250/1~32
1840(72-1/2")
1990(78-3/8")
840(33-1/8")
15~24˚C (59~75˚F)
-5~43˚C (23~109˚F) 0~43˚C (32~109˚F)(When the Outdoor is at a position lower than the Indoors)
15~27˚C (59~81˚F)
-20~15.5˚C (-4~60˚F)
Note: 1. Cooling/heating capacity indicates the maximum value at operation
*1 (JIS Standard: JIS B8615-1) Cooling 27˚C(81˚F)DB/19˚C(66.2˚F)WB
Heating Indoor: 20˚C(68˚F)DB
Pipe length: 7.5m(24-9/16Ft)
PURY-P500YGM-A
Cooling
Heating
56.0
63.0
50,000
–
191,100
215,000
under the following condition.
Outdoor: 35˚C(95˚F)DB
*2 Cooling Indoor: 27˚C(81˚F)DB/19.5˚C(67.1˚F)WB Outdoor: 35˚C(95˚F)DB
Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
Pipe length: 5m(16-3/8Ft)
Height difference: 0m
Height difference: 0m
PURY-P650YGM-A
Cooling
Heating
73.0
81.5
65,000
–
249,100
278,100
19.65
33.1/31.5/30.3
3.72
19.82
33.4/31.7/30.6
4.11
10.9 + 5.3
62/62.5 (50Hz/60Hz)
481(1061)
Models P20~P250/1~32
*3 It is measured in anechoic room.
External Dimensions
494
840
553
20
65 160
2X2-14X20 0val hole
80 ø62 Knockout hole <Hole for the power supply>
768
Knockout hole
<Bottom piping hole>
16
70
45
Changeable to ø27,ø33 by using
attached conduit mounting plate <Accessory>
Cross section X–X
900(bolt hole)
45
990
Plane view
Air outlet
265
Conn. pipe
(high pressure)
200:ø15.88<brazed>
250:ø19.05<brazed>
300:ø19.05<brazed>
350:ø19.05<brazed>
B
80
57
A
Y
Unit : mm
877
ø27 Knockout hole
<Bottom hole for the
control wiring>
Y
Conn. pipe
(low pressure)
200:ø19.05<brazed>
250:ø22.2 <brazed>
300:ø22.2 <brazed>
350:ø28.58<brazed>
845(bolt hole)
16
PURY-P200,250,300,350YGM-A
B
115
120
120
120
135
80
40
1840
1575
Knockout hole
ø27 Knockout hole
<Left side hole for
the control wiring>
Service panel
Refrig. service
valve (high pressure) 67 160
<Flare>
X
37
117
117 37
Left side view
Knockout hole
<Left piping hole>
Refrig. service
83
valve(low pressure) 100
<Flange>
67 207
Knockout hole
<Front piping
hole>
Front view
11 78
235
15
X
184
19
[Accessories]
• Refrigerant (high pressure) conn. pipe..............1pc.
• Refrigerant (low pressure) conn. pipe................1pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. low pressure pipe..................1pc.
(Attached near the ball valve)
• Conduit mouting plate
ø33, ø27............................Each 1pc.
• Tapping screw M4.....................1pcs.
Air
inlet
Air
inlet
280
5
134 100
12
Cross section Y–Y
10 90
A
145
135
135
145
ø53
Model
200
250
300
350
207
67
OUTDOOR UNIT
Specifications & External Dimensions
R2 SERIES
R410A
External Dimensions
PURY-P400YGM-A
Unit : mm
503
65 160
1068
Conn. pipe
(low pressure)
ø28.58<brazed>
80
Cross section X–X
Conn. pipe
(high pressure)
ø22.2 <brazed>
16
20
81
70
80
57
145
840
Y
Knockout hole
<Bottom piping hole>
877
ø27 Knockout hole
<Bottom hole for the
control wiring>
Y
845(bolt hole)
16
644
2X2-14X20 Oval hole
ø62 Knockout hole
<Hole for the power supply>
Changeable to ø46,ø53 by using
attached conduit mounting plate <Accessory>
45
1200(bolt hole)
45
1290
Plane view
ø53
265
Air outlet
Air
inlet
[Accessories]
• Refrigerant (high pressure) conn. pipe........... 1pc.
(The connecting pipe has been fixed with the unit)
• Refrigerant (low pressure) conn. pipe............. 1pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. high pressure pipe.............. 1pc.
(Attached near the ball valve)
• Packing for conn. low pressure pipe............... 1pc.
(Attached near the ball valve)
• Conduit mouting plate
ø53, ø46................... Each 1pc.
• Tapping screw M4............ 2pcs.
Knockout hole
135
Service panel
Refrig. service
valve (high pressure)
67 160
<Flange>
X
40
X
115
115
37
Knockout hole
<Left piping hole>
Left side view
Knockout hole
<Front piping
hole>
11 78
235
Refrig. service
83
valve(low pressure) 100
<Flange>
355
68
10
37
184
89
280
15
80
ø27 Knockout hole
<Left side hole for
the control wiring>
1575
Cross section Y–Y
1840
Air
inlet
5
134 100
12
355
68
Front view
PURY-P450,500,550,600,650YGM-A
1000
16
494
Y
65 160
Conn. pipe
(high pressure)
450:ø22.2 <brazed>
500:ø22.2 <brazed>
550:ø28.58<brazed>
600:ø28.58<brazed>
650:ø28.58<brazed>
80
ø62 Knockout hole
<Hole for the power supply>
Changeable to ø46,ø53 by using
attached conduit mounting plate <Accessory>
3X2-14X20 Oval hole
45
950(bolt hole)
950(bolt hole)
45
1990
Cross section X–X
Plane view
Air outlet
265
768
ø53
Conn. pipe
(low pressure)
ø28.58<brazed>
16
70
145
80
57
145
20
877
ø27 Knockout hole
<Bottom hole for the
control wiring>
840
Y
Knockout hole
<Bottom piping hole>
845(bolt hole)
Y
553
Y
37
115
115
Left side view
37
Service panel
X
Refrig. service
90
valve(low pressure) 100
<Flange>
68 205
Knockout hole
<Left piping hole>
11 78
150 44
235
Refrig. service
valve (high pressure)
67 160
<Flange>
X
Knockout hole
<Front piping hole>
280
135
80 40
1575
Knockout hole
ø27 Knockout hole
<Left side hole for
the control wiring>
134 100
[Accessories]
• Refrigerant (high pressure) conn. pipe.......... 1 pc.
(The connecting pipe has been fixed with the unit)
• Refrigerant (low pressure) conn. pipe............ 1 pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. high pressure pipe............. 1 pc.
(Attached near the ball valve)
• Packing for conn. low pressure pipe.............. 1 pc.
(Attached near the ball valve)
• Conduit mouting plate
ø53, ø46..................... Each 1 pc.
• Tapping screw M4.............. 2 pcs.
Air
inlet
89
Cross section Y–Y
1840
Air
inlet
5
10
12
290
260
260
290
205
68
Front view
20
HEAT SOURCE UNIT
Specifications & External Dimensions
WY SERIES
R410A
Specifications
PQHY-P200YGM-A
Heating
Cooling
25.0
22.4
85,300
76,400
Model name
kW
BTU/h
Capacity
Power source
Power input
Current
COP
Type
Compressor
Motor output
Heat
Type
exchanger Water volume in the coil
PQHY-P250YGM-A
PQHY-P400YSGM-A
Heating
Heating
Cooling
Cooling
31.5
50.0
28.0
45.0
107,500
170,600
95,500
153,500
3N~380/400/415V 50/60Hz
4.69
7.9/7.5/7.2
5.33
4.79
8.0/7.6/7.4
4.68
PQHY-P500YSGM-A
Heating
Cooling
63.0
56.0
215,000
191,100
5.80
11.01
13.60
11.35
15.06
9.7/9.3/8.9
18.5/17.6/17.0
22.9/21.8/21.0
19.1/18.2/17.5
25.4/24.2/23.3
5.43
4.54
4.63
3.96
3.72
Inverter scroll hermetic compressor
5.0
6.0
9.7
11.6
kW
Double coil
Double coil
Double coil
Double coil
9.5
10.5
17.5
19.5
R
3
4.56
5.76
9.12
11.52
m /h
Circulating Volume
161
203
322
407
cfh
water
16.5
19.5
16.5
19.5
kPa
Pressure drop
R410A
R410A
R410A
R410A
Refrigerant
External finish
Galvanized sheets
Height(H)
1,800(70-7/8")
Width(W) mm(in.)
990(39")
1,980(78")
External dimension
Depth(D)
550(21-11/16")
High pressure switch 4.15 MPa (601psi)
High pressure protection
Protection
Over-heat protection
Compressor
devices
Inverter
Over-voltage and over-current protection for AC bus, Over-heat protection
ø9.52 flare / ø19.05 Flange
ø9.52 flare /ø22.2 Flange
ø12.7 flare / ø28.58 Flange
ø15.88 flare / ø28.58 Flange
Refrigerant piping diameter
Gas/Liquid
50%~130% of heat sourse unit capacity
Indoor
Total capacity
unit
Model P20~250/1~13
Model P20~250/1~22
Model / Quantity
Model P20~250/1~24
Model P20~250/1~16
46
50
Noise level
dB<A>
53
47
272(600)
208+244(459+538)
Net weight
kg(lbs.)
208+248(459+547)
275(607)
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27CDB
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB
Operating temperature range
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
Water :10˚C~45˚C
kW
A
5.95
10.0/9.5/9.1
4.71
Note: 1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor:27˚C(80.6˚F)DB/19˚CWB
Water temperature: 30˚C(80˚F)
Heating Indoor:20˚C(68˚F)DB
Water temperature:20˚C(68˚F)
9
Pipe length:7.5m(24- /16Ft)
Height difference:0m
2.The ambient temperature of heat source unit has to be kept below 40˚C(104˚F)(dry bulb).
The ambient relative humidity of heat source unit has to be kept below 80%.
3.This unit can not be installed in the outdoor.(No protection against the weather.)
4.It is measured in anechoic room.
5.When the total capacity of indoor units exceeds 130% of heat source units capacity,
the operating temperature range of circulating water is 15˚C(59˚F)~45˚C(113˚F)
External Dimensions
ø38 Knockout hole
<Hole for the power supply>
123
206
318
Piping space
(left side pipe)
568
ø27 Knockout hole
<Hole for the control wiring>
Water outlet
(PT1 1/2 screw)
600
Piping space
(upside pipe)
400
400
Front view
ø38 Knockout hole
<Hole for the power supply>
ø27 Knockout hole
<Hole for the control wiring>
Piping space
(left side pipe)
Plane view
50
Plane view
Service space
(front side)
16
95
415
255
140
126
94
2X2-14X20 Oval hole
(mounting hole)
602
256
154
ø40 <piping hole>
Note 1 Water inlet
(PT1 1/2 screw)
Note 1 Water outlet
(PT1 1/2 screw)
ø70<piping hole>
69
415
255
126
495
45
550
990
900(mounting pitch)
45
570(mounting pitch)
PQHY-P200,P250YGM-A
Fig. A
Conn. pipe<liquid>
200:ø9.52<flare>
250:ø9.52<flare>
Conn. pipe<gas>
200:ø19.05<brazed>
250:ø22.2<brazed>
ø62 Knockout hole
<piping hole>
1772
(1800)
1590
108 wiring>
A
78
B
1397
1497
1579
1598
1626
Refrig. service valve<liquid>
Water inlet
(PT1 1/2 screw)
ø27 Knockout hole
<Hole for the control
Refrig. service valve<gas>
ø38 Knockout hole
<piping hole>
939
879
924
Knockout hole
ø38 Knockout hole
<Hole for the power
supply>
Note 2
Drain(PT1 screw)
127
182
Drain
(PT1 screw)
495
Left side view
[Accessories]
• Refrigerant <gas> conn. pipe........... 1pc.
• Packing for conn. pipe.................... 1pc.
(Attached near the ball valve)
• Bushing......................................... 2pcs.
21
B
A
Model
P200 1346 1289
P250 1346 1299
Front view
Right side view
Rear view
Note 1. At the time of product shipment, the front side piping specification serves as the local drainage connection. When connecting on the rear side, please remove the rear side plug
sealing corks, and attach to a front side. Ensure there is no leak after the attachment has been fitted.
2. Take notice of service space as Fig. A (In case of single setting, 600mm or more of back space as front space makes easier access when servicing the unit from the rear side.)
3. In case the temperature around the heat source unit has possibility to drop under 0°C, be careful for the following point to prevent the pipe burst by the water pipe freeze-up.
• Circulate the water all the time even if the heat source unit is not in operation.
• Drain the water from inside of the heat source unit when the heat source unit will not operate for a long term.
HEAT SOURCE UNIT
Specifications & External Dimensions
WY SERIES
R410A
External Dimensions
Piping space
(left side pipe)
1990
10
990
990
900(mounting pitch)
900(mounting pitch)
Water inlet
(PT2 screw)
2X2-14X20 Oval hole
(mounting hole)
Piping space
(upside pipe)
400
550
400
16
ø70<piping hole>
154
69
126
272
418
Water outlet
(PT2 screw)
602
2X2-14X20 Oval hole
(mounting hole)
Plane view
Service space
(front side)
45
570(mounting pitch)
45
600
PQHY-P400,P500YSGM-A
143
233
318
ø56
<piping hole>
568
719
Plane view
Front view
ø38 Knockout hole
<Hole for the power supply>
Piping space
(left side pipe)
ø27 Knockout hole
<Hole for the control wiring>
Fig. A
418
272
Heat exchanger unit
Water outlet
(PT2 screw)
Compressor unit
ø27 Knockout hole
<Hole for the control
wiring>
1590
78
Left side view
[Accessories]
• Refrigerant <gas> conn.pipe.............................................. 1pc.
(The connecting pipe is fixed with the unit)
• Refrigerant <liquid> conn.pipe........................................... 1pc.
(Packaged in the accessory kit)
• Refrigerant conn.pipe between HEX unit and Compressor unit
ø9.52................................................................................ 2pcs.
(Packaged in the accessory kit)
ø19.05.............................................................................. 2pcs.
(Packaged in the accessory kit)
ø25.4................................................................................ 2pcs.
(Packaged in the accessory kit : HEX unit)
(The connecting pipe is fixed with the unit : Compressor unit)
• Packing for conn.pipe....................................................... 4pcs.
(Attached near the ball valve)
• Bushing............................................................................. 6pcs.
• Extension code for water heat source............................... 1set
Drain
(PT1 screw)
Front view
Locally piping
ø9.52 <braze+flare>
ø19.05 <braze+flare>
ø25.4 <flange,brazed>
ø38 Knockout hole
<Hole for the power
supply>
939
182
Drain
(PT1 screw)
Refrig. service
valve<gas>
127
126
624
585
Knockout hole
<piping hole>
660
950
Knockout hole
879
Refrig. service valve
<liquid>
Water inlet
(PT2 screw)
108
1772
Conn. pipe<liquid>
P400:ø12.7<braze+flare>
P500:ø15.88<braze+flare>
(1800)
131
76
1599
Conn. pipe<gas>
P400:ø28.58<brazed>
P500:ø28.58<brazed>
Conn.pipe between HEX unit
and Compressor unit
(Extension code for water heat source)
Control signal wire
<connector,locally connected>
Right side view
Note 1. At the time of product shipment, the front side piping specification serves as the local drainage connection. When connecting on the rear side, please remove the rear side plug sealing corks, and attach to a front side. Ensure
there is no leak after the attachment has been fitted.
2. Take notice of service space as Fig. A (In case of single setting, 600mm or more of back space as front space makes easier access when servicing the unit from the rear side.)
3. In case the temperature around the heat source unit has possibility to drop under 0°C, be careful for the following point to prevent the pipe burst by the water pipe freeze-up.
• Circulate the water all the time even if the heat source unit is not in operation.
• Drain the water from inside of the heat source unit when the heat source unit will not operate for a long term.
4. Use the extension code for water heat source (option) to take space (more than 2m) between HEX unit Compressor unit.
22
HEAT SOURCE UNIT
Specifications & External Dimensions
WR2 SERIES
R410A
Specifications
Model name
kW
BTU/h
Capacity
Power source
Power input
Current
COP
Type
Compressor
Motor output
Type
Heat
exchanger Water volume in the coil
PQRY-P250YGM-A
PQRY-P400YSGM-A
Heating
Heating
Cooling
Cooling
31.5
50.0
28.0
45.0
107,500
170,600
95,500
153,500
3N~380/400/415V 50/60Hz
PQRY-P200YGM-A
Heating
Cooling
25.0
22.4
85,300
76,400
5.8
11.01
13.6
11.35
15.06
9.7/9.3/8.9
18.5/17.6/17.0
22.9/21.8/21.0
19.1/18.2/17.5
25.4/24.2/23.3
5.43
4.54
4.63
3.96
3.72
Inverter scroll hermetic compressor
6.0
9.7
11.6
5.0
Double coil
Double coil
Double coil
Double coil
10.5
17.5
19.5
9.5
5.76
9.12
11.52
4.56
203
322
407
161
19.5
16.5
19.5
16.5
R410A
R410A
R410A
R410A
Galvanized sheets
1,800(70-7/8")
990(39")
1,980(78")
550(21-11/16")
High pressure switch 4.15 MPa (601psi)
Over-heat protection
Over-voltage and over-current protection for AC bus, Over-heat protection
ø15.88 flare / ø19.05 Flange
ø19.05 flare /ø22.2 Flange
ø22.2 flare / ø28.58 Flange
ø22.2 flare / ø28.58 Flange
50%~150% of heat sourse unit capacity
kW
A
4.69
7.9/7.5/7.2
5.33
4.79
8.0/7.6/7.4
4.68
kW
R
m3/h
Circulating Volume
cfh
water
kPa
Pressure drop
Refrigerant
External finish
Height(H)
Width(W) mm(in.)
External dimension
Depth(D)
High pressure protection
Protection
Compressor
devices
Inverter
Refrigerant piping diameter
gas / Liquid
Total capacity
indoor
Model / Quantity
unit
dB<A>
Noise level
kg(lbs)
Net weight
Operating temperature range
PQRY-P500YSGM-A
Heating
Cooling
63.0
56.0
215,000
191,100
5.95
10.0/9.5/9.1
4.71
Model P20~250/1~15
46
263(580)
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27CDB
Water :10˚C~45˚C
Water :10˚C~45˚C
Model P20~250/1~19
47
266(587)
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB
Water :10˚C~45˚C
Water :10˚C~45˚C
Note: 1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor:27˚C(80.6˚F)DB/19˚CWB
Water temperature: 30˚C(80˚F)
Heating Indoor:20˚C(68˚F)DB
Water temperature:20˚C(68˚F)
Pipe length:7.5m(24-9/16Ft) Height difference:0m
2.The ambient temperature of heat source unit has to be kept below 40˚C(104˚F)(dry bulb).
The ambient relative humidity of heat source unit has to be kept below 80%.
Model P20~250/1~24
50
208+232(459+512)
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB
Water :10˚C~45˚C
Water :10˚C~45˚C
Model P20~250/1~24
53
208+236(459+521)
Indoor:15˚CWB~24˚CWB Indoor:15˚CDB~27˚CDB
Water :10˚C~45˚C
Water :10˚C~45˚C
3.This unit can not be installed in the outdoor.(No protection against the weather.)
4.It is measured in anechoic room.
5.When the total capacity of indoor units exceeds 130% of heat source units capacity,
the operating temperature range of circulating water is 15˚C(59˚F)~45˚C(113˚F)
External Dimensions
ø38 Knockout hole
<Hole for the power supply>
154
123
206
318
Water outlet
(PT1 1/2 screw)
600
Front view
Piping space
(left side pipe)
Fig. A
Plane view
ø27 Knockout hole
<Hole for the control wiring>
Piping space
(upside pipe)
400
ø38 Knockout hole
<Hole for the power supply>
ø27 Knockout hole
<Hole for the control wiring>
568
50
Plane view
Service space
(front side)
16
95
415
255
140
126
94
256
69
415
255
126
ø40 <piping hole>
Note 1 Water outlet
(PT1 1/2 screw)
ø70<piping hole>
550
Note 1 Water inlet
(PT1 1/2 screw)
495
Piping space
(left side pipe)
2X2-14X20 Oval hole
(mounting hole)
400
45
602
990
900(mounting pitch)
45
570(mounting pitch)
PQRY-P200,P250YGM-A
Conn. pipe<high pressure>
200:ø15.88<braze+flare>
250:ø19.05<braze+flare>
Conn. pipe<low pressure>
200:ø19.05<brazed>
250:ø22.2 <brazed>
ø62 Knockout hole
<piping hole>
1772
(1800)
1590
108 wiring>
A
78
B
1579
1598
1626
1397
1497
Refrig. service valve
<high pressure>
Water inlet
(PT1 1/2 screw)
ø27 Knockout hole
<Hole for the control
Refrig. service valve
<low pressure>
ø38 Knockout hole
<piping hole>
939
879
924
Knockout hole
ø38 Knockout hole
<Hole for the power
supply>
Note 2
Drain(PT1 screw)
127
182
Drain
(PT1 screw)
495
Left side view
[Accessories]
• Refrigerant <low pressure> conn. pipe.......... 1pc.
(The connecting pipe is fixed with the unit)
• Refrigerant <high pressure> conn. pipe......... 1pc.
(Packaged in the accsessory kit)
• Packing for conn. pipe.................................... 1pc.
(Attached near the ball valve)
• Bushing......................................................... 2pcs.
23
B
A
Model
P200 1347 1289
P250 1342 1299
Front view
Right side view
Rear view
Note 1. At the time of product shipment, the front side piping specification serves as the local drainage connection. When connecting on the rear side, please remove the rear side plug
sealing corks, and attach to a front side. Ensure there is no leak after the attachment has been fitted.
2. Take notice of service space as Fig. A (In case of single setting, 600mm or more of back space as front space makes easier access when servicing the unit from the rear side.)
3. In case the temperature around the heat source unit has possibility to drop under 0°C, be careful for the following point to prevent the pipe burst by the water pipe freeze-up.
• Circulate the water all the time even if the heat source unit is not in operation.
• Drain the water from inside of the heat source unit when the heat source unit will not operate for a long term.
HEAT SOURCE UNIT
Specifications & External Dimensions
WR2 SERIES
R410A
External Dimensions
1990
10
990
Piping space
(left side pipe)
990
900(mounting pitch)
900(mounting pitch)
Water inlet
(PT2 screw)
550
16
154
69
126
272
418
Water outlet
(PT2 screw)
400
2X2-14X20 Oval hole
(mounting hole)
Plane view
Service space
(front side)
Piping space
400
(upside pipe)
602
2X2-14X20 Oval hole
(mounting hole)
45
570(mounting pitch)
45
600
PQRY-P400,P500YSGM-A
ø70<piping hole>
143
233
318
ø56
<piping hole>
568
719
Plane view
Front view
ø38 Knockout hole
<Hole for the power supply>
Piping space
(left side pipe)
ø27 Knockout hole
<Hole for the control wiring>
Fig. A
418
272
Heat exchanger unit
ø27 Knockout hole
<Hole for the control
wiring>
Compressor unit
108
1772
Refrig.
service valve
<high pressure>
(1800)
1599
131
76
1590
Conn. pipe<low pressure>
ø28.58<brazed>
Conn. pipe
<high pressure>
ø22.2<brazed>
Water outlet
(PT2 screw)
78
Water inlet
(PT2 screw)
Left side view
[Accessories]
• Refrigerant conn.pipe....................................................... 2pcs.
(The connecting pipe is fixed with the unit)
• Refrigerant conn.pipe between HEX unit and Compressor unit
ø9.52................................................................................ 2pcs.
(Packaged in the accessory kit)
ø19.05.............................................................................. 2pcs.
(Packaged in the accessory kit)
ø25.4................................................................................ 2pcs.
(Packaged in the accessory kit : HEX unit)
(The connecting pipe is fixed with the unit : Compressor unit)
• Packing for conn.pipe....................................................... 4pcs.
(Attached near the ball valve)
• Bushing............................................................................ 2pcs.
• Extension code for water heat source............................... 1set
Drain
(PT1 screw)
939
Right side view
Front view
Locally piping
ø9.52 <braze+flare>
ø19.05 <braze+flare>
ø25.4 <flange,brazed>
ø38 Knockout hole
<Hole for the power
supply>
182
Drain
(PT1 screw)
879
Refrig.
service
valve
<low pressure>
127
585
Knockout hole
<piping hole>
648
126
660
950
Knockout hole
Conn.pipe between HEX unit
and Compressor unit
(Extension code for water heat source)
Control signal wire
<connector,locally connected>
Note 1. At the time of product shipment, the front side piping specification serves as the local drainage connection. When connecting on the rear side, please remove the rear side plug sealing corks, and attach to a front side. Ensure
there is no leak after the attachment has been fitted.
2. Take notice of service space as Fig. A (In case of single setting, 600mm or more of back space as front space makes easier access when servicing the unit from the rear side.)
3. In case the temperature around the heat source unit has possibility to drop under 0°C, be careful for the following point to prevent the pipe burst by the water pipe freeze-up.
• Circulate the water all the time even if the heat source unit is not in operation.
• Drain the water from inside of the heat source unit when the heat source unit will not operate for a long term.
4. Use the extension code for water heat source (option) to take space (more than 2m) between HEX unit and Compressor unit.
24
BC CONTROLLER
Specifications & External Dimensions
CMB-P-V-GB
BC Controller for
R2/WR2 SERIES
CMB-P-V-G
CMB-P-V-GA
R410A
CMB-P-V-GB
Specifications
Model name
Number of branch
Power source
CMB-P104V-G CMB-P105V-G CMB-P106V-G CMB-P108V-G CMB-P1010V-G
5
4
6
8
10
~220/230/240V 50Hz/60Hz
0.067/0.076/0.085 0.082/0.093/0.104 0.097/0.110/0.123 0.127/0.144/0.161 0.156/0.177/0.198
0.030/0.034/0.038 0.038/0.043/0.048 0.045/0.051/0.057 0.060/0.068/0.076 0.075/0.085/0.095
0.054/0.061/0.067 0.066/0.074/0.082 0.078/0.088/0.097 0.102/0.115/0.127 0.126/0.141/0.156
0.024/0.027/0.030 0.030/0.034/0.038 0.036/0.041/0.045 0.048/0.054/0.060 0.060/0.068/0.075
0.31/0.34/0.36 0.38/0.41/0.44 0.45/0.48/0.52 0.58/0.63/0.68 0.71/0.77/0.83
0.14/0.15/0.16 0.18/0.19/0.20 0.21/0.23/0.24 0.28/0.30/0.32 0.35/0.37/0.40
0.25/0.27/0.28 0.30/0.33/0.35 0.36/0.39/0.41 0.47/0.50/0.53 0.58/0.62/0.65
0.11/0.12/0.13 0.14/0.15/0.16 0.17/0.18/0.19 0.22/0.24/0.25 0.28/0.30/0.32
Galvanizing
Cooling
heating
Cooling
60Hz
heating
Cooling
50Hz
heating
Cooling
60Hz
heating
50Hz
Power input
kW
Current
A
External finish
Indoor unit capacity
connectable to 1 branch *
Conncctable Outdoor unit
Height
Width
Depth
CMB-P1013V-G CMB-P1016V-G CMB-P108V-GA CMB-P1010V-GA CMB-P1013V-GA CMB-P1016V-GA CMB-P104V-GB
13
16
8
10
13
16
4
~220/230/240V 50Hz/60Hz
0.201/0.288/0.255 0.246/0.279/0.312 0.127/0.144/0.161 0.156/0.177/0.198 0.201/0.228/0.255 0.246/0.279/0.312 0.060/0.068/0.076
0.097/0.110/0.123 0.119/0.135/0.151 0.060/0.068/0.076 0.075/0.085/0.095 0.097/0.110/0.123 0.119/0.135/0.151 0.030/0.034/0.038
0.162/0.182/0.201 0.198/0.222/0.246 0.102/0.115/0.127 0.126/0.141/0.156 0.162/0.182/0.201 0.198/0.222/0.246 0.048/0.054/0.060
0.078/0.088/0.097 0.096/0.108/0.119 0.048/0.054/0.060 0.060/0.068/0.075 0.078/0.088/0.097 0.096/0.108/0.119 0.024/0.027/0.030
0.92/1.00/1.07 1.12/1.22/1.30 0.58/0.63/0.68 0.71/0.77/0.83 0.92/1.00/1.07 1.12/1.22/1.30 0.28/0.30/0.32
0.45/0.48/0.52 0.55/0.59/0.63 0.28/0.30/0.32 0.35/0.37/0.40 0.45/0.48/0.52 0.55/0.59/0.63 0.14/0.15/0.16
0.74/0.80/0.84 0.90/0.97/1.03 0.47/0.50/0.53 0.58/0.62/0.65 0.74/0.80/0.84 0.90/0.97/1.03 0.22/0.24/0.25
0.36/0.39/0.41 0.44/0.47/0.50 0.22/0.24/0.25 0.28/0.30/0.32 0.36/0.39/0.41 0.44/0.47/0.50 0.11/0.12/0.13
Galvanizing
CMB-P108V-GB
8
0.119/0.135/0.151
0.060/0.068/0.076
0.096/0.108/0.119
0.048/0.054/0.060
0.55/0.59/0.63
0.28/0.30/0.32
0.44/0.47/0.50
0.22/0.24/0.25
Model P140 or smaller
Model P140 or smaller
PURY-P200~650YGM-A *2
CMB-P108V~P1016V-GA
289
mm
284
1098
1110
mm
648
520
mm
432
For P200 type: ø15.88 Brazed
For P250, P300, P350 type: ø19.05 Brazed
High pressure
For P200 type: ø15.88 Brazed
For P400 to P500 type: ø22.22 Brazed
pipe
For P250, P300, P350 type: ø19.05 Brazed
To outdoor
For P550 to P650 type: ø28.58 Brazed
unit
For P200 type: ø19.05 Brazed
For P200 type: ø19.05 Brazed
Low pressure
For P250, P300 type: ø22.2 Brazed
For P250, P300 type: ø22.2 Brazed
pipe
For P350 to P650 type: ø28.58 Brazed
For P350 type: ø28.58 Brazed
ø9.52 Flare
ø9.52 Flare
Liquid pipe
Refrigerant
(ø6.35 with attached reducer used, ø12.7 with optional joint pipe used)
To indoor
(ø6.35 with attached reducer used, ø12.7 with optional joint pipe used)
piping
ø15.88 Flare
unit
ø15.88 Flare
Gas pipe
diameter
(ø12.7 with attached reducer used, ø19.05 with optional joint pipe used)
(ø12.7 with attached reducer used, ø19.05 with optional joint pipe used)
For total capacity below P200 type: ø19.05 Brazed
Low press gas
For total capacity below P201 to P300 type: ø22.2 Brazed
pipe
For total capacity below P301 to P350 type: ø28.58 Brazed
To another
High press gas
For total capacity below P200 type: ø15.88 Brazed
BC controller
pipe
For total capacity below P201 to P350 type: ø19.05 Brazed
For total capacity below P300 type: ø9.52 Brazed
Liquid pipe
For total capacity below P301 to P350 type: ø12.7 Brazed
VP-25
Drain pipe
VP-25
Net weight
24
27
29
34
39
47
54
44
49
57
64
22
32
•Drain connection pipe (with flexible hose and insulation)
•Drain connection pipe (with flexible hose and insulation)
Accessories
•Reducer
•Reducer
*1 Use optional joint pipe combining 2-branch when the total unit capacity exceeds P140.
*2 Additional pipework is needed to connect with P300 type or lower outdoor unit.
Use the reducer (standard accessory) when the indoor unit Model P50 or smaller is connected.
PURY-P200, 250, 300, 350YGM-A
284
648
432
External Dimensions
4
5
6
7
8
9
10
11
12
13
14
15
16
23
Service space
(200)
648
702 (Lifting bolt pitch)
70 76
128
1
2
3
4
5
6
7
8
255
284
Connection pipe of
indoor unit (Liquid)
ø9.52 (Flare)
60XA=B
60
ø15.88 (Flare)
Connection pipe of
indoor unit (Gas)
ø15.88 (Flare)
200
ø31
Connnection pipe of
outdoor unit (High pressure)
For P200 type: ø15.88 Brazed
For P250, P300 type: ø19.05 Brazed
For P350 type: ø22.22 Brazed
For P400 to P650 type: ø28.58 Brazed
14
Detail of X section
210
388 (Lifting bolt pitch)
Connection pipe of
SUB BC CONTROLLER (Liquid)
Total capacity of indoor unit
For 300 or less: ø9.52<Brazed>
For 301 or over: ø12.7<Brazed> (with accessory)
Connection pipe of
SUB BC CONTROLLER (Low pressure)
Total capacity of indoor unit
For 200 or less: ø19.05<Brazed> (with accessory)
From 201 to 300: ø22.2<Brazed>
For 301 or over: ø28.58<Brazed> (with accessory)
66
74
1110
23
1164 (Lifting bolt pitch)
90
76
Access door
450
74
Service
space
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
260
128
27
60
1
70
Connection pipe of
indoor unit (Gas)
200
<Accessories>
• Refrigerant <Low pressure> conn. pipe...............1pc
• Refrigerant <High pressure> conn. pipe..............1pc
• Reducer (Large, Small).....Quantity for all connection
• Drain hose (VP-25 connection)............................1pc
• Hose band............................................................1pc
• Tie band...............................................................1pc
Note 1. Suspesion bolt (ø10), washer (M10) and nut (M10) prepare
in the field.
2. Take notice of service space as follows:
(Please give attention not to occupy service space by letting
ducts and pipes through)
In the following, Access door in service space is a door for
service. There fore, another door is necessary to unload products.
3. Please take space to connect SUB BC CONTROLLER.
200 200
Connection pipe of indoor unit (Liquid)
ø9.52 (Flare)
70
60XA=B
700
Connection pipe of outdoor unit
(Low pressure)
For P200 type: ø19.05 Brazed
For P250, P300 type: ø22.2 Brazed
For P350 type: ø28.58 Brazed
For P400 to P650 type: ø28.58 Brazed
289
128
250
64
64 103
268
333
130
Connection pipe of
SUB BC CONTROLLER (High pressure)
Total capacity of indoor unit
For 200 or less: ø15.88<Brazed> (with accessory)
For 201 or over: ø19.05<Brazed>
103
Control box
X
450
Y
Detail of Y section
268
Drain piping
VP-25 connection
70
CMB-P108,1010,1013,1016V-GA
30
12
Drain hose (Accessory)
ø15.88 (Flare)
200
CMB-P108V-GA
CMB-P1010V-GA
CMB-P1013V-GA
CMB-P1016V-GA
A
7
9
12
15
B
420
540
720
900
(700)
250
Access door
450
70
X
Band (accessory)
25
B
180
420
200
298 (Lifting bolt pitch)
64 103
130
Connection pipe of
indoor unit (Gas)
200
A
3
7
Control box
27
3
64
Total capacity of indoor unit.
For 200 or less: ø19.05<Brazed>
(with accessory)
From 201 to 300: ø22.2<Brazed>
For 301 or over: ø28.58<Brazed>
(with accessory)
58
27
60
2
45
181
Connection pipe of
indoor unit (Liquid)
ø9.52 (Flare)
60XC=D
255
128
Connnection pipe of
MASTER BC CONTROLLER
(Low pressure)
(200)
B (Lifting bolt pitch)
1
Y
250
Service
space
A
23
Connection pipe of outdoor unit (Low pressure)
200: ø219.05<Brazed> (with accessory)
250, 300: ø22.2<Brazed>
70 76
350: ø28.58<Brazed> (with accessory)
284
Access door
450
CMB-P104V-GB
CMB-P108V-GB
Connnection pipe of
MASTER BC CONTROLLER (Liquid)
Total capacity of indoor unit.
For 300 or less: ø9.52<Brazed>
For 301 or over: ø12.7<Brazed> (with accessory)
Connnection pipe of
MASTER BC CONTROLLER (High pressure)
Total capacity of indoor unit.
For 200 or less: ø15.88<Brazed>
(with accessory)
For 201 or over: ø19.05<Brazed>
Drain piping
VP-25 connection
200
298 (Lifting bolt pitch)
362
248
64 103
64
181
14
Detail of Y section
Detail of X section
248
Control box
X
130
1098 1152
Drain hose (Accessory)
58
Detail of Y section
702
Band (accessory)
D
180
240
300
420
540
720
900
169
Detail of X section
Y
648
C
3
4
5
7
9
12
15
(700)
14
70
Connnection pipe of outdoor unit
(High pressure)
200: ø15.88<Brazed> (with accessory)
250, 300, 350: ø19.05<Brazed>
ø31
30
12
Drain piping
VP-25 connection
B
30
12
CMB-P104V-G
CMB-P105V-G
CMB-P106V-G
CMB-P108V-G
CMB-P1010V-G
CMB-P1013V-G
CMB-P1016V-G
Note 1. Suspesion bolt (ø10), washer (M10)
and nut (M10) prepare in the field.
2. Take notice of service space as follows;
(Please give attention not to occupy service
space by letting ducts and pipes through)
In the following, Access door in service
space is a door for service. There fore, another
door is necessary to unload products.
3. Can't use singleness.
(MASTER BC CONTROLLER is necessary.)
<Accessories>
• Reducer.....Quantity for all connections
• Drain hose (VP-25 connection).......1pc
• Pipe cover for drain hose.................1pc
• Hose band.......................................1pc
• Tie band...........................................2pc
ø31
A
Band (accessory)
Drain hose (Accessory)
Unit : mm
CMB-P104,108V-GB
Note 1. Suspesion bolt (ø10), washer (M10) and
nut (M10) prepare in the field.
2. Take notice of service space as follows;
(Please give attention not to occupy service
space by letting ducts and pipes through)
• Pipe cover for drain hose...................................................1pc
In the following, Access door in service space
• Hose band..........................................................................1pc
is a door for service. There fore, another door
• Tie band.............................................................................1pc
is necessary to unload products.
362
CMB-P104,105,106,108, <Accessories>
• Refrigerant <Low pressure> conn. pipe (Large, Small).....2pc
• Refrigerant <High pressure> conn. pipe............................1pc
• Reducer (Large, Small)..................Quantity for all connection
1010,1013V-G
• Drain hose (VP-25 connection)..........................................1pc
Wide selection of indoor units
Ceiling cassette (4way air flow)
Ceiling suspended
PLFY-P VCM-E
PLFY-P VAM-E
PCFY-P VGM-E
Model P20
P25
P32
P40
P50
P63
P80 P100 P125
Capacity 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 14.0kW
Ceiling cassette (2way air flow)
Model
P40
P63
P100
P125
Capacity
4.5kW
7.1kW
11.2kW
14.0kW
Wall mounted
PLFY-P VLMD-E
Model P20
P25
P32
PKFY-P VAM-E
PKFY-P VGM-E
PKFY-P VFM-E
P40
P50
P63
P71
P80 P100 P125
Capacity 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW
Ceiling cassette (1way air flow)
Model
P20
P25
P32
P40
P50
P63
P100
Capacity 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 11.2kW
Floor standing
New
PFFY-P VLEM-E
PFFY-P VLRM-E
PMFY-P VBM-E
Model
P20
P25
P32
P40
Capacity
2.2kW
2.8kW
3.6kW
4.5kW
Ceiling concealed
Model
P20
Capacity 2.2kW
P25
P32
P40
P50
P63
2.8kW
3.6kW
4.5kW
5.6kW
7.1kW
Fresh Air Intake
PEFY-P VMH-E-F
New
PEFY-P VMR-E-L/R
PEFY-P VMM-E
PEFY-P VML-E
PFFY-P VKM-E
PEFY-P VMH-E
New
PEFY-P VMS-E
Model P20 P25 P32 P40 P50 P63 P71 P80 P100 P125 P140 P200 P250
Model
P80
P140
P200
P250
Capacity 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW
Capacity
9.0kW
16.0kW
22.4kW
28.0kW
26
INDOOR UNIT
Ceiling cassette type
PLFY-P VCM-E/VAM-E
4-way airflow
PLFY-P VCM-E
PLFY-P VAM-E
VCM
VAM
The new compact cassette VCM is suitable for 2x2 ceiling!
compact body to match with
2feets (600mm) x 2feets (600mm)
ceiling design (VCM)
570mm
Easy Installation
Only two panel sizes–perfectly suited to
various installation configurations
Only two panel sizes are available,650mm(255/8in.) for the compact VCM and 950mm(377/16in.) for the power cassette VAM. The VCM is
lightweight min.15kg(34lbs)(P20/P25)
PLFY-VCM Type
Superb Features
Drain water pipe lifted to 850mm(33-1/2in.)
(power cassette VAM)
First in the industry to offer 72 airflow
patterns (power cassette VAM)
The drain piping of the VAM can be
positioned anywhere up to 850mm(33-1/2in.)
from the ceiling's surface, allowing greater
freedom with long cross-piping and more
versatility with piping layouts
(VCM: 500mm(19-11/16in.)).
The 72 different airflow patterns provide the
best solution for varying room layouts and
air-conditioning requirements. For extra
versatility, you can also select from two-,
three- or four-way outlets. What's more, the
addition of separate motors to the individual
vanes enables manual control that-together
with remote control vane settings-make
possible highly customized and flexible
airflow patterns.
PLFY-VAM Type
850mm
(33-1/2in.)
650mm
(25-5/8in.)
(compact cassette VCM)
The new compact cassette VCM has a unit
height of only 208mm*1, to realize neat
installation in low-ceiling situations with very
limited space.
*:8-1/4in
Only
208mm*!
27
4-, 3-, or 2way outlet
selection
950mm
(37-7/16in.)
Unit height of only 208mm*1 great for
low-ceiling space situations
570mm
Handy corner-pocket design simplifies maintenance
and installation (power cassette VAM)
By using the handy corner pockets equipped
on four corners of the grille, maintenance
work such as drain pan cleaning and height
adjustment can be accomplished without
removing the grille. It is also easier to adjust
the ceiling height of the indoor unit during
installation.
Fixed airflow
direction per
vane
Motor
for the
vane
72 airflow patterns
*Optional air outlet shutter plate is
necessary for two-or three-way airflow
settings. The noise level may increase
during two-or three-way airflow setup.
*For VCM model, 2 or 3 way airflow is
not available.
INDOOR UNIT
Ceiling cassette type
)
PLFY-P VCM-E
PLFY-P VAM-E
-
+ %
% &
'
#
These units are ideal for maintaining constant
temperatures in environments that have
equipment such as refrigerate showcases.
Individual vane angle adjustment enables
precise airflow control to specific areas of the
store to reduce unnecessary air conditioning
of areas such as refrigerated showcases.
Remote control setting for two directions
' -
)
)
) -
*
) .
)
-
#
Mitsubishi Electric has developed a new airflow
control mechanism where a projection inside the
air passage distributes air evenly over the vane's
upper and lower surface while two additional
projections at the air outlet's exit adjust the angle
of the airflow. This helps to prevent indoor air
from rising, stopping it from hitting the surface
of the ceiling to reduce the likelihood of soiling
from smudging and condensation.
(
) *
) +
,
#
The airflow of the VAM power cassette is
powerful enough to warm atrium-type
ceilings up to 4.2 meter(13-13/16Ft) in height.
4-way high ceiling 2 (VAM)
4-way standard (VAM)
3.2m
(10-1/2Ft)
4.2m
(13-13/16Ft)
Fixed vane for two directions
Fixed
3.6m
(11-13/16Ft)
Smudging and the new
airflow control mechanism
Fixed
Outside
Inside
3-way standard (VAM)
Specifications according to ceiling height and number of vents
1
Standard
Top or bottom
airflow setting via
remote controller
Fixed
3
2
Grille
Vane
Fixed
Refrigerated
showcase not
affected by air
conditioning
1
2 3
A projection is created on the outside, where the airflow is
fastest. This diverts the airflow and distributes it evenly
over the upper and lower surfaces of the Vane.
The air outlet exit also has projections to prevent air from rising
within the room and stopping it from hitting the ceiling.
Wider airflow setting
reduces annoying drafts
30° horizontal
position
-+
. +. /
-
#
For easy connection to branch ducts,
knockout holes are designed to fit both round
and square ducts. Matching the shape of the
duct fringe provides more flexibility during
installation.
30°
70°
70° vertical
position
When cooled air is
expelled horizontally, it
tends to cling to the
surface of the ceiling. This
cools the surface down
and causes condensation,
which attracts dust from
the room's interior to soil
the ceiling's surface.
High ceiling 1 High ceiling 2
3.2
3.6
4.2
3.6
4.0
4.2
4.0
4.2
---
*VCM:2.7m(standard/4way only)
% --
*
.
-
#
When the air conditioner is not operating, the
vane shutter closes automatically to conceal
the air outlet and create an aesthetically
appealing flat surface.*
*This feature will not activate when the vane is set at
fixed position.
0
)
*
+
-
-
#
The unique suction mechanism prevents indoor
air from rising to eliminate condensation on the
vane and make bristles unnecessary.
During operation
When turned off
1
2
) )
. 3
-
4- #
!"# Indoor air quality is significantly enhanced by
the direct intake of fresh exterior air. An
optional multi-function casement is also
available (only for VAM) for the intake of a
larger volume of air.
!"#$ !"# 28
INDOOR UNIT
Ceiling cassette type
2-way airflow
(drain-up mechanism is built in)
PLFY-P VLMD-E
PLFY-P VLMD-E
Slim body of 290 mm* height. (*11- /
7 16in.)
Slim body - only 290mm height
The slimline body is highly suitable for installation in narrow ceiling
spaces and for replacing obsolete air-conditioning equipment in older
buildings. The main unit is only 290mm* height.
290mm
*
(*: 11-7/16in.)
Equipped with drain water lift-up
mechanism as standard
Terminal block on outside of main unit
makes wiring easier
The drain can be positioned anywhere up to 600mm* from the
ceiling's surface, providing greater freedom with long cross-piping
and allowing more versatility with piping layouts.(*: 23-5/8in.)
Drain height
max. 593mm(23-3/8in.)
Main unit height - 290mm(11-7/16in.)
Ceiling surface
Newly designed decorative panel with air flow
switching and swing functions as a standard feature
593
(unit: mm)
Compact unit and low noise level attained!
Fresh air directly taken in
Fresh air can be taken in to the main unit directly (optional accessories
needed.
29
INDOOR UNIT
Ceiling cassette type
! PMFY-P VBM-E
PMFY-P VBM-E
Unit body size has been standardized for all
models at 854mm for easier installation. Body
weight is also only 14kg for the main unit and
3kg for the panel, making this unit one of the
lightest in the industry.
The drain can be positioned anywhere up to 600mm* from the ceiling's surface.(*: 23-5/8in.)
max.
402
(15-7/8)
max.
600*
Newly developed airflow control technology
reduces noise level to only 27dB (P20VBM)
for industry-leading quiet operation.
230
(9-11/16)
198
(7-13/16)
unit: mm(in.)
30
INDOOR UNIT
Ceiling concealed
type
New
PEFY-P VMR-E-L/R
PEFY-P VMR-E-L/R
Problem solver for residential hotels, museums, libraries,
or hospitals where low noise is especially a must!
Inlet
Card Key
Switch
Noise measurement point
Noise measurement point
*According to the data measured in Mitsubishi Electric laboratory
Operable by card key switch
Prepared a contact for a card key. It’s possible
to operate / stop by taking a card key in and
out.
Enables to install for symmetric
design room
Both of Left piping / Right piping, control
box, are available.
It's selectable for layout of each room.
Plus easy maintenance from the access door
in the prefabricated bath.
*Seen from an anterior view, the pipe and
control box are on the right side of –R type.
31
Ultra low noise
Realizing the low level noise that is NC21 around a bed and N22 around a desk when the high
notch.
It contributes to create a quiet indoor environment.
*Outlet is elbow-constructed using a glass wool duct.
The noise level is changed by the room size or the setting condition of the unit.
Energy-saving by prevention of forgetting the switch off
Compact & Simple operation remote controller is available.
*This remote controller can operate only start / stop, Indoor temperature control and wind speed
control. Centralized remote controller must be used together.
Enables a prevention to forget the switch in a vacant room off by the centralized remote
controller like G-50.
INDOOR UNIT
Ceiling concealed
type
PEFY-P VMS-E
New
PEFY-P VMS-E
Increased design flexibility for the places where low noise
operation is especially needed from an ultra thin body.
Changeable static pressure
(4 stage 5-15-35-50Pa)
Ultra low height unit with 200mm high
Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.
Filter is attached as standard.
More than 20mm
Drain lift-up pump is attached
as standard.
More than 20mm
Changeable air flow rate
(3 stage low-middle-high)
Ceiling surface
Access door
Make the access door at the appointed position properly
unit: mm
for service maintenance.
Reduced noise thanks to the use of newly designed centrifugal fan and coil
Noise level table (Standard static pressure)
Capacity
Noise
Level
Fan
Speed
dB(A)
P20
P25
P32
High
27
27
30
Mid
25
25
28
Low
22
22
25
32
INDOOR UNIT
Ceiling concealed
type
PEFY-P VML-E
PEFY-P VML-E
Increased design flexibility for hotel and residential use.
Low static pressure (5Pa) meets
an application requiring direct air flow
Low height unit with 225mm* high
*: 8-7/8in.
Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.
Notes: Drain lift-up pump not applicable.
Changeable air flow rate
(3 stage low-middle-high)
Service space:500(19-11/16) or more
Hole pitch
100(3-15/16) or more
20(13/16) or more
245(9-11/16)+Drain
covering
configuration
225
height
(8-7/8)
Flexible installation by rear
or bottom return air inlet.
30(1-3/16)
Access door
20/25/32 Model
Filter is attached as standard.
Reduced noise thanks to the use of
newly designed centrifugal fan
Noise level table (Standard static pressure 220V)
Capacity
Noise
Level
Fan
Speed
dB(A)
P20
P25
P32
High
36
36
40
Mid
29
29
29
Low
25
25
25
Note: In the case of bottom inlet, the operating noise is
louder than in the case of rear inlet.
33
unit: mm(in.)
Drainage lines may be connected
on either the right or left side.
Perfect for use in hotels and other places
where line placement is a problem.
INDOOR UNIT
Ceiling concealed
type
PEFY-P VMM-E
PEFY-P VMM-E
Achieving creative air conditioning design
through a rich array of system materials.
Flexible installation for a variety of layouts
Long room
L-shaped rooms
Air outlet side compatible
with a variety of ducts (optional)
Multiple installation patterns for assorted applications and locations
Bottom intake (directly attached to panel)
Adjustable setting of external static pressure to meet
system configuration and installation conditions
Static pressure settings can be increased to
adjust to all kinds of ducts as well as
functional upgrade option (high performance
filter etc). An increase from the standard 50Pa
to 130* Pa is possible to cope with various
layout configurations.
Slim 295mm main unit with optional drain up
mechanism ensures up to 600 mm of lift
Max.
600
Max.
416
184
Bottom intake (using canvas duct)
Maintenance panel
with air intake
All-duct system
Ceiling chamber system (1)
A rear intake can
also be used
Square duct flange
Maintenance panel
Ceiling chamber system (2)
*For P100~P125.
Room with fixed
ceiling fixtures
A bottom intake can
also be used
Maintenance panel
Hanging ceiling installation
Square duct flange
System ceiling
295
34
INDOOR UNIT
Ceiling concealed
type
PEFY-P VMH-E
PEFY-P VMH-E
Increased design flexibility from sufficient external static pressure
allow authentic duct air- conditioning with an elegant interior layout.
One-side maintenance
Maximum external static pressure 200Pa
The additional external static pressure capacity provides flexibility for
duct extension, branching and air outlet configuration.
P40 P50 P63 P71 P80 P100 P125 P140 P200 P250
External
static
pressure
(Pa)
220V
50/100/200
230/240V
100/150/200
380V
110/220
400/415V
130/260
All maintenance to the unit, including
fan inspection and fan motor removal,
can be conducted from the inspection
opening on one side.
Drain up mechanism (option) ensures
up to 550mm* of lift
*: 21-11/16in.
The introduction of an upper drain mechanism allows the drain
connection to be raised as high as 550mm*, allowing more freedom in
piping layout design and reducing horizontal piping requirements.
Reduced noise thanks to the use of
newly designed centrifugal fan
Noise level table (Standard static pressure 220V)
Capacity
Noise
High
Level Fan
Speed Low
dB(A)
P40
P50
P63
P71
P80
P100 P125 P140
34
34
38
39
41
42
42
42
27
27
32
32
35
34
34
34
222mm
(8-3/4in.)
MAX.
550mm
(21-11/16in.) 328mm
(12-15/16in.)
35
INDOOR UNIT
Ceiling suspended
type
PCFY-P VGM-E
PCFY-P VGM-E
Seek and slim with stylishly curved lines, the PCFY series blends right
into any interior. It also features a single air outlet which allows the
auto vane to act as a shutter when the unit is turned off.
The most suitable airflow can be selected for ceilings up to 3.5m high,
enhancing air-conditioning efficiency and comfort.
Ceiling height
2.7m(8-7/8Ft)
3.5m(11-1/2Ft)
! The auto vane swings up and down automatically to distribute air more
evenly to every corner of the room.
Auto vane
Swing
The new direct suspension system eliminates the task of removing the
attachment fixture from the main unit, greatly shortening installation
time.
1. Leave attachment fixture
attached to main unit.
2. Suspend the attachment
fixture from the suspension bolts.
3. Simply tighten the nuts
to secure the unit.
Ceiling surface
Suspension
bolts
Attachment
fixture
Air outlet
*A one-touch suspension is also available: simply suspend
the main unit from the attachment fitting after securing
the latter to the ceiling.
36
INDOOR UNIT
Wall mounted
type
PKFY-P VAM
PKFY-P VAM-E
PKFY-P VGM-E
PKFY-P VFM-E
PKFY-P VGM
PKFY-P VAM-E
PKFY-P VGM-E
PKFY-P VFM-E
PKFY-P VFM
Elegant Design and Compact Dimensions Ideal for Offices,
Stores and Residential Uses.
Capacity range
Capacity P20 P25 P32 P40 P50 P63 P100
Quiet operation (PKFY-P VGM)
VAM
Among the quietest in the industry
VGM
Airflow passage configuration that assures quiet operations
VFM
Compact design with 990mm* width
(PKFY-P VGM)
Width reduced by 20% to a compact
990mm*. *: 39in.
Extra compactness has been achieved thanks
to a 20%(260mm(10-1/4in.))
reduction in which compared with previous
models.
Compact 295mm(11-5/8in.) high body fits
snugly in even limited spaces (PKFY-P VAM)
Lightweight 8.5kg(20lbs) unit easy to
transport and install (PKFY-P VAM)
Auto-flap shutter enhances
good looks
37
1
1. The unit incorporates a randon pitch cycling fan. By changing fan
intervals reduction in airflow. Optimal design of the airflow passage
gives a shorted fan diameter and allows a highly compact installation.
2. Thanks to a highly practical casing configuration, airflow
generated by the fan is distributed uniformly.
3. Due to careful positioning of the vertical vane axis, air is blown
evenly from the fan. This prevents mixing with secondary air,
and also suppresses condensation.
2
3
Front grille opens out - easy filter cleaning (PKFY-P VGM)
In room air conditioning style, the grille
opens out allowing the filter to be removed.
The filter and open grille can therefore be
thoroughly and easily cleaned.
Front power supply box for easier
wiring even after installation
The front power supply box allows electrical
wiring work to be done after the indoor unit
has been installed. For easier installation, all
the screws required for securing the indoor
unit to the wall are accessible from the front
of the unit.
Front grille
opens out
5-way piping provides more flexibility
in selecting installation sites
All piping including drainage can be
connected from the rear, right, base, and left
of the unit, providing much greater flexibility
out piping and selecting installation site.
INDOOR UNIT
Floor standing
type
New
PFFY-P VKM-E
PFFY-P VKM-E
For living rooms, bed rooms, or offices where a sophisticated
design is required. The latest Mitsubishi innovation – floor-standing
air-conditioner sophisticated in design, rich in function.
Quiet Operation
Mitsubishi Electric air conditioners have
always been some of the quietest model
available in the market. Our new floorstanding models are no exception.
It can create a silent and comfortable space
where the occupants would not even
recognize the existence
ONLY
of air conditioner
operation.
✻2.5kw class
27dB
Noise level Quiet passenger
Human
Subway car
interior
car interior
(40km/h)
Library interior
80dB
60dB
40dB
hearing limits
Sound of
rustling leaves (Extremely quiet)
10dB
Sophisticated Design
Optimum Air Distribution
From Mitsubishi
Electric, an
Deluxe look in
“Glossy Pure White” color
innovative new floorstanding airconditioner. Our
Sleek louvers look just like
pleasing mix of
flat panels
streamlined form and
diversified function.
Smart upper/lower air outlets
Engineered to keep
close when switched off
room walls free,
furnish comfy cooling
in summer, toasty heating in winter.
The “Glossy Pure White” colour ensures a deluxe look, the perfect
match for any room. Both upper and lower air outlets remain closed
when switched OFF, in a smart and striking image.
A superb new air-conditioner from Mitsubishi, providing a handsome
fit for your own distinctive interior.
Comfy room temperatures are realized by the optimum, powerful and
efficient air distribution through upper and lower air outlets.
The upper vane angle is remote controllable, with 5 air flow direction
levels (+Swing and Auto modes) and 4 wind power levels (+Auto
mode).
By setting the vane angle almost vertical, annoying direct wind can be
avoided for your better comfort.
Slim but Mighty
600 mm
The unit body is slim and
trim, the essence in
compact. An ideal size for
living rooms, bedrooms,
attics and more.
The removable and
200
washable front panel makes
700 mm
mm
cleaning a snap.
Easy and regular cleaning allows your air-conditioner stay beautiful
while keeping its energy-efficient operation always possible.
The air from both upper and lower air
outlets is optimally controlled and distributed evenly to every corner of the room.
In heating mode, the warm air is smartly
controlled to stay at the floor level: Your
feet do not feel chilled any more!
14 16 18 20 22 24 26 ˚C
38
INDOOR UNIT
Floor standing
type
PFFY-P VLEM-E
PFFY-P VLEM-E
The compact body of 220mm(7-7/8in.) in
depth can be easily installed in the perimeter
zone for effective air conditioning in the
perimeter zone.
Optimum dehumidification depending on
indoor temperature to prevent over-cooling.
Refreshing dehumidification can be attained.
INDOOR UNIT
Floor mounted
concealed type
PFFY-P VLRM-E
PFFY-P VLRM-E
The body is concealed in the pericover to pursue harmony with the interior.
The compact body of 220mm(7-7/8in.) in depth can be easily installed in the perimeter zone.
Optimum dehumidification depending on indoor temperature to prevent over-cooling. Refreshing
dehumidification can be attained.
39
INDOOR UNIT
Fresh Air
Intake Type
PEFY-P VMH-E-F
PEFY-P VMH-E-F
Fresh Air can be taken in with temperature control.
Ideal for Offices, Stores and Restaurant.
* Limits of capacity connectable to outdoor unit
The Fresh Air intake indoor unit
can be installed in any place.
Max. 110% of outdoor unit capacity, excepting heating at outdoor temperature of less than -5˚C(23˚F) (100%).
The Fresh Air intake indoor unit can take
Example
fresh outdoor air into any building in any
1. Nurcery home
place at any time.
Fresh Air intake
indoor unit
Office, Lobby, Workshop,
Rest room, nursery home,
Smoking corner,
Kitchen in restaurant
Fresh Air intake
indoor unit
2. Workshop
Passage
Exhaust
air
Fresh air
Air flow
Private room
Polluted air
Office
Private room
Workshop
Ventilating fan
Ventilating fan
Installing fresh Air intake indoor unit (Image)
Fresh Air intake indoor unit
Exhaust
air
EA
Supply air
Fresh
air
OA
< Note>
Fan remains of in operation during Thermo-OFF. Using this model with other
type of indoor unit is recommended for Cold Draft prevention because Cold Draft
might occur by using only this model that takes in fresh air.
40
INDOOR UNIT
Specifications & External Dimensions
For 50Hz
Area only
PLFY-P VCM-E
Specifications
PLFY-P20VCM-E
Power source
❇1
❇1
❇1
Heating capacity
❇1
Cooling
Power
consumption
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Height
Dimension ❇ 2
Width
Depth
Net weight ❇ 2
Heat exchanger
Type
Cooling capacity
Airflow rate ❇ 2
(Low-Mid-High)
Fan
External static
pressure
Type
Motor
Output
Air filter
Refrigerant
Gas(Flare)
pipe diameter
Liquid(Flare)
Drain pipe diameter
Noise level (Lo-Mid-Hi) ❇2 ❇3
PLFY-P25VCM-E
PLFY-P32VCM-E
PLFY-P40VCM-E
~ (Single phase), 220-230-240V 50Hz
2.2
2.8
3.6
4.5
7,500
9,600
12,300
15,400
5.0
2.5
3,2
4.0
8,500
10,900
13,600
17,100
0.06
0.05
0.06
0.05
0.06
0.06
0.05
0.05
0.28
0.28
0.23
0.23
0.28
0.28
0.23
0.23
Unit: Galvanized sheets with gray heat insulation, Panel: Munsell 0.70Y 8.59/0.97
Unit: 208(8-1/4"), Panel: 20(13/16")
Unit: 570(22-1/2"), Panel: 650(25-5/8")
Unit: 570(22-1/2"), Panel: 650(25-5/8")
Unit: 15.5<3>(35<7>)
Unit: 15.5<3>(35<7>)
Unit: 17<3>(38<7>)
Unit: 17<3>(38<7>)
Cross fin (Aluminum plate fin and copper tube)
Turbo fan × 1
kW
Btu/h
kW
Btu/h
kW
kW
A
A
mm(in.)
mm(in.)
mm(in.)
kg(lbs.)
m3/min
8-9-10
8-9-10
8-9-11
8-9-11
L/s
cfm
133-150-167
283-318-353
133-150-167
283-318-353
133-150-183
283-318-388
133-150-183
283-318-388
Pa
0 (direct blow)
Single phase induction motor
kW
0.011
0.015
0.020
PP Honey comb
ø 12.7(1/2")
mm(in)
ø 6.35(1/4")
mm(in)
O.D. ø32(1-1/4")
O.D. ø32(1-1/4")
O.D. ø32(1-1/4")
dB(A)
28-31-35
28-31-37
29-33-38
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇2 External dimension/ net weight are shown in<unit/panel> , and airflow rate/noise level are in (low-middle2-middle1-high).
❇3 It is measured in anechoic room.
0.020
O.D. ø32(1-1/4")
30-34-39
External Dimensions
PLFY-P20,25,32,40VCM-E
570
335
570
ø100
3-ø2.8hole
Burring hole
25
ø73.4
Cut out hole
56
Detail drawing of fresh air intake hole
57
15~37
87
31
420
530
Suspension bolt pitch
Suspension bolt pitch
576~620
Ceiling hole
15~37
Unit : mm
Fresh air intake
2
Drain pipe
VP-25 connection
(O.D.ø32)
199
352
335
576~620 Ceiling hole
202
230
15~37
17
15~37
Wiring entry
Suspension bolt M10 or W3/8
Ceiling surface
48
182
208
235
193
93
Ceiling surface
0
20
+5
Grille
Terminal block
27
38~58
0˚
12
12
0˚
118
121
66
1
650
Suspension bolt lower edge
301
Air outlet hole
Brand label
55 35
Grille
V/M
Drain hole
377
Auto vane
Air intake hole
301
Air outlet hole
650
V/M
Models
V/M
V/M
Air intake grille
Vane motor
35 55
377
Air intake hole
41
PLFY-P20VCM-E
PLFY-P25VCM-E
PLFY-P32VCM-E
PLFY-P40VCM-E
1
Refrigerant pipe
(6.35mm dia.)
flared connection
1/4F
2
Refrigerant pipe
(12.7mm dia.)
flared connection
1/2F
INDOOR UNIT
Specifications & External Dimensions
PLFY-P VAM-E
Specifications
PLFY-P32VAM-E
PLFY-P40VAM-E
Power source
❇1
❇1
Cooling capacity
❇2
❇2
❇1
Heating capacity
❇1
❇1
Cooling
Power
consumption
Heating
Cooling
Current
Heating
External finish(Munsel No.)
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
Dimension H x W x D ❇ 3
mm
in.
kg(lbs.)
❇3
Net weight
Heat exchanger
Type
Fan
Airflow rate
❇3
(Low-Mid2-Mid1-High)
4.5
15,400
4.7
4,000
5.0
4,300
17,100
PLFY-P100VAM-E
9.0
30,700
9.3
8,000
10.0
8,600
34,100
0.18
0.18
0.86
0.86
PLFY-P125VAM-E
11.2
38,200
11.6
10,000
12.5
10,800
42,700
0.30
0.30
1.43
1.43
14.0
47,800
14.5
12,500
16.0
13,800
54,600
0.34
0.34
1.64
1.64
298(30) x 840(950) x 840(950)
11-3/4"<1-3/16"> x 33-1/8"<37-7/16"> x 33-1/8"<37-7/16">
32<5>(71<12>)
11-12-13-14
12-13-14-16
14-15-16-18
16-18-20-22
19-22-25-27
21-24-27-29
183-200-217-233
388-424-459-494
200-217-233-267
424-459-494-565
233-250-267-300
494-530-565-636
267-300-333-367
565-636-706-777
317-367-417-450
671-777-883-953
350-400-450-483
742-848-953-1024
Pa
0
Single phase induction motor
kW
0.070
0.120
PP Honeycomb
mm(in.)
ø12.7
Liquid
mm(in.)
ø6.35 (1/4")
(Flare)
Drain pipe diameter
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4
5.6
19,100
5.8
5,000
6.3
5,400
21,500
L/s
cfm
Gas
(Flare)
PLFY-P80VAM-E
PLFY-P63VAM-E
~ 220-240V 50Hz / ~ 220V 60Hz
7.1
24,200
7.3
6,300
8.0
6,900
27,300
0.14
0.16
0.14
0.16
0.68
0.78
0.68
0.78
Panel : 0.70Y 8.59/0.97
258<30>x 840<950> x 840<950>
10-3/16"<1-3/16"> x 33-1/8"<37-7/16"> x 33-1/8"<37-7/16">
22<5>(49<12>)
24<5>(53<12>)
Cross fin (Aluminum plate fin and copper tube)
Turbo fan
3.6
12,300
3.7
3,150
4.0
3,400
13,600
0.12
0.12
0.59
0.59
m3/min
External static
pressure
Type
Motor
Output
Air filter
Refrigerant
pipe diameter
PLFY-P50VAM-E
dB(A)
ø 12.7(1/2") / ø 15.88(5/8")
(Compatible)
ø 6.35(1/4") / ø 9.52(3/8")
(Compatible)
(1/2")
27-28-29-31
27-28-30-32
ø 15.88 (5/8")/ ø 19.05(3/4") (Compatible)
ø 15.88(5/8")
ø 9.52 (3/8")
O.D. ø32 (VP-25)
28-29-31-33
35-38-41-43
33-36-39-41
30-32-35-37
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27 ˚C(80.6˚F) DB/19˚C(66.2˚F) WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F) DB,Outdoor 7˚C(44.6˚F) DB/6˚C(42.8˚F) WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB (WR2: water 20˚C(68˚F))
❇ 3 External dimension/ net weight are shown in <unit/panel> , and airflow rate/noise level are in (low-middle2-middle1-high).
❇ 4 It is measured in anechoic room.
External Dimensions
PLFY-P32,40,50,63,80,100,125VAM-E
20~45
159
20~45
810
Suspension bolt pitch
Fresh air intake
16
197
159
120˚
840
120˚
158
20~45
3 - ø2.8
Burring hole
ø125
Suspension bolt M10
or W3/8
ø 100
(Cut out hole)
1
Feeding hole
(Drain pump)
286
374
60
Branch
duct hole
159
89
Detail drawing of fresh air intake hole
98
192
ø 150
860~910
Ceiling hole
Terminal block
840
14 - ø 2.8
Burring hole
Suspension bolt pitch
605
Branch duct hole
350
ø 175
167
155
159
130
70˚
100
90 100 100 90
Unit : mm
Ceiling hole
860~910
20~45
Branch duct hole
(Cut out hole)
Drain pipe
VP-25connection
(O.D.ø 32)
2
B
Grille
Drain hole
135
Air intake grille
190
Ceiling surface
577
Air intake hole
30
Control wire entry
17
105
Power line entry
+5
0
140
Suspension bolt lower edge
50~70
170
A
Ceiling surface
PLFY-P63VAM-E
PLFY-P80VAM-E
PLFY-P100VAM-E
PLFY-P125VAM-E
A
B
ø 12.7
ø 6.35(R410A)
ø 12.7(R410A)
241
ø 9.52(R407C,R22) ø15.88(R407C,R22)
258
ø 15.88
ø 9.52
ø 15.88(R410A)
281
ø19.05(R407C,R22)
577
Air intake hole
➁ Gas Pipe
298
Auto vane
411
Air outlet hole
ø 6.35
M
77
PLFY-P50VAM-E
➀ Liquid Pipe
51
Models
PLFY-P32VAM-E
PLFY-P40VAM-E
M
950
High efficiency filter
& Fresh air intake casement (option)
17 +50
M
M
411
Air outlet hole
950
Vane motor
77
51
42
INDOOR UNIT
Specifications & External Dimensions
PLFY-P VLMD-E
Specifications
PLFY-P20VLMD-E
Power source
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling capacity
Heating capacity
Cooling
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Power
consumption
Dimension H x W x D
mm
in.
kg(lbs.)
❇ 3
❇ 3
Net weight
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
Motor
External static pressure
Type
Pa
Output
kW
PLFY-P40VLMD-E
11-7/16"<13/16"> x30-9/16"<42-9/16"> x 25"<28">
24 <6.5>(53<15>)
23 <6.5>(51<15>)
Cross fin
m 3/min
L/s
cfm
Airflow rate (Lo-Mid-Hi)
PLFY-P32VLMD-E
~ 220-240V 50Hz / ~ 220-230V 60Hz
2.2
2.8
3.6
4.5
7,500
9,600
12,300
15,400
2.3
2.9
3.7
4.7
2,500
3,150
4,000
2,000
2.5
3.2
4.0
5.0
2,200
2,800
3,400
4,300
8,500
10,900
13,600
17,100
0.072 / 0.075
0.072 / 0.075
0.072 / 0.075
0.081 / 0.085
0.065 / 0.069
0.065 / 0.069
0.065 / 0.069
0.074 / 0.079
0.36 / 0.37
0.36 / 0.37
0.36 / 0.37
0.40 / 0.42
0.30 / 0.32
0.30 / 0.32
0.30 / 0.32
0.34 / 0.37
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)
290<20> x 776<1,080> x 634<710>
Heat exchanger
Type
Fan
PLFY-P25VLMD-E
Turbo fan✕1
6.5-8.0-9.5
108-133-158
7.0-8.5-10.5
117-142-175
230-283-335
247-300-371
0
Single phase induction motor
0.015
PP honeycomb fabric (long life filter)
Air filter
Refrigerant
pipe diameter
Gas(Flare)
mm(in.)
ø 12.7(1/2")
Liquid(Flare)
mm(in.)
ø 6.35(1/4")
Unit drain pipe I.D.32 (1-1/4inch)
27-30-33
28-31-34
Drain pipe diameter
Noise level
(Lo-Mid-Hi)
dB(A)
220V,240V
230V
❇4
dB(A)
29-33-36
30-34-37
PLFY-P50VLMD-E PLFY-P63VLMD-E PLFY-P80VLMD-E PLFY-P100VLMD-E PLFY-P125VLMD-E
Power source
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling capacity
Heating capacity
Cooling
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Power
consumption
Dimension H x W x D
❇ 3
❇ 3
Net weight
Heat exchanger
Type
Fan
Motor
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
~ 220-240V 50Hz / ~ 220-230V 60Hz
11.2
7.1
9.0
5.6
19,100
24,200
30,700
38,200
5.8
7.3
9.3
11.6
6,300
8,000
10,000
5,000
12.5
8.0
10.0
6.3
5,400
6,900
8,600
10,800
21,500
27,300
34,100
42,700
0.101 / 0.105
0.147 / 0.156
0.157 / 0.186
0.082 / 0.086
0.094 / 0.099
0.140 / 0.150
0.150 / 0.180
0.075 / 0.080
0.72 / 0.74
0.75 / 0.88
0.49 / 0.51
0.41 / 0.43
0.43 / 0.46
0.66 / 0.69
0.69 / 0.83
0.35 / 0.38
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing
mm
290<20> x 946<1,250> x 634<710>
290<20> x 1,446<1,750> x 634<710> 290<20> x 1,708<2,010>x 606<710>
in.
11-7/16"<13/16"> x 37-1/4"<49-1/4"> x 25"< 28">
11-7/16"<13/16"> x 56-15/16"<68-15/16"> x 25"< 28"> 11-7/16"<13/16"> x 67-1/4"<79-3/16"> x 23-7/8"< 28">
kg(ibs.) 27 <7.5>(60<17>) 28 <7.5>(62<17>) 44 <12.5>(98<28>) 47 <12.5>(104<28>) 56 <13.0>(124<29>)
Cross fin
Airflow rate
(P50~P100:Lo-Mid-Hi)
(P125:Lo-Mid2-Mid1-Hi)
m 3/min
L/s
cfm
External static pressure
Type
Pa
Output
kW
Turbo fan✕1
10.0-13.0-15.5
9.0-11.0-12.5
150-183-208
167-217-258
318-388-441
353-459-547
0.020
Gas(Flare)
mm(in.)
ø 12.7(1/2")[R410A]
ø 15.88(5/8") [R22,R407C]
Liquid(Flare)
mm(in.)
ø 6.35(1/4")[R410A]
ø 9.52(3/8")[R22,R407C]
Drain pipe diameter
Noise level
(Lo-Mid-Hi)
Turbo fan✕2
15.5-18.5-22.0
17.5-21.0-25.0
258-308-367
292-350-417
547-653-777
0
Single phase induction motor
0.020 (at 240V)
0.030 (at 240V)
❇4
220V,240V
230V
dB(A)
dB(A)
31-34-37
32-35-38
Sirocco fan✕4
24.0-27.0-30.0-33.0
400-450-500-550
848-953-1,059-1,165
0.078✕2(at 240V)
Synthetic fiber unwoven
cloth filter (long life)
ø 15.88(5/8") [R410A]
ø 19.05(3/4") [R22,R407C]
ø 15.88(5/8")
ø 9.52(3/8")
Unit drain pipe I.D.32 (1-1/4inch)
36-39-42
33-36-39
32-37-39
34-37-40
33-38-40
37-41-43
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(97.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇ 3 The figure in < > indicates panel's
❇ 4 It is measured in anechoic room.
43
618-742-883
PP honeycomb fabric (long life filter)
Air filter
Refrigerant
pipe diameter
14.0
47,800
14.5
12,500
16.0
13,800
54,600
0.28 / 0.28
0.27 / 0.27
1.35 / 1.35
1.33 / 1.33
(0.7Y 8.59/0.97)
40-42-44-46
(Lo-Mid2-Mid1-Hi)
INDOOR UNIT
Specifications & External Dimensions
PLFY-P VLMD-E
External Dimensions
Unit : mm
146
70
H
670
ø12.7<R410A outdoor unit>
ø15.88<R407C,R22 outdoor unit>
ø6.35<R410A outdoor unit>
ø9.52<R407C,R22 outdoor unit>
Liquid pipe:HP
Model
63·80
Gas pipe:LP
Liquid pipe:HP
ø15.88
ø9.52
Model
100
Gas pipe:LP
ø15.88<R410A outdoor unit>
ø19.05<R407C,R22 outdoor unit>
ø9.52
Drain hose
VP-25<flexible joint> (accessory)
Liquid pipe:HP
Terminal bed(Power source)
Terminal bed(Transmission)
108
D(Lifting Bolt Pitch)
108
B
Terminal box
Branch duct Fx110 knock out hole
(both side)(Note:2)
68
D(Lifting bolt pitch)
574 (Lifting Bolt Pitch)
G-ø2.9 Mounting hole
4-ø2.9 Mounting hole
2
1
497
3
221
146
70
Control box
122
290
266
202
73
20
B
20
45
216
45
60
52
E
34
222
F
110
190
197
159
240
68
634
C
More Than 350
Gas pipe:LP
190
Model
50
48
Model
20·25·32·40
574
<flare>
Gas pipe:LP
ø12.7
Liquid pipe:HP
ø6.35
634
507
Note: 1.Use M10 screw for the lifing bolt (field supply).
2.It is available to connect the branch duct on right and left side both.
3.On Model :50, 100, you would use flare nut packed with the Indoor
Unit, when connnecting the Outdoor Unit for R407C, R22.
4.In order to increase the strength of the flare nut, the size of some
of them has been increased.
48
PLFY-P20, 25, 32, 40, 50, 63, 80, 100VLMD-E
20
20
20
670
Air filter
Drain hole
Water filling port
Fresh air intake 240x45 knock out hole
Standard center panel
A
300mm or less
Model
F
G H(Liquid) H(Gas)
E
D
C
B
A
PLFY-P20VLMD-E
PLFY-P25VLMD-E
CMP-40VLW-B 1080 1040 776 824 388
17
27
PLFY-P32VLMD-E
217.5✕2 6
=435
PLFY-P40VLMD-E
PLFY-P50VLMD-E
CMP-63VLW-B 1250 1210 946 994 473
PLFY-P63VLMD-E
22
29
PLFY-P80VLMD-E
188.5✕4
CMP-100VLW-B 1750 1710 1446 1494 723 =754
10
36
22
PLFY-P100VLMD-E
583mmMAX
710
3
Note: 1.Use M10 screw for the lifting bolt (field supply).
2.On this model, you would use flare nut packed
with the Indoor Unit, when connnecting the
Outdoor Unit for R407C, R22.
3.In order to increase the strength of theflare nut,
the size of some of them has been increased.
48
PLFY-P125VLMD-E
170mm ± 5mm(Actual Length)
2
606
670
574
A
A(Liquid) A(Gas)
22
36
Model
PLFY-P125VLMD-E
1
<flare>
ø15.88<R410A outdoor unit>
ø19.05<R407C,R22 outdoor unit>
ø9.52
48
Gas pipe:LP
Liquid pipe:HP
Drain hose VP-25<flexible joint> (accessory)
3
107
1756
107
Water filling port
1970
Fresh air intake ø150 knock out hole
1756(Lifting bolt pitch)
127
303
338~353
More than 350
290
155
192
235
90
1970(Ceiling opening)
20
20
45
Terminal box
222
Air filter
70
Control box
4-ø2.8Mounting hole
4-ø2.9Mounting hole
20
333
670(Ceiling opening)
Drain hole
20
ø224
255
38
2
˚
90˚
145
˚
2
181
ø17
1
3
Terminal bed
(Transmission)
856
45˚
Terminal bed
(Power source)
127
1708
90
574(Lifting bolt pitch)
68
606
476
70
178
106
68
Branch duct ø200 knock out hole (both side)
20
2010
300mm or less
710
600mm Max
170mm±5mm(Actual length)
3
Standard center panel
(CMP-125VLW-B)
44
INDOOR UNIT
Specifications & External Dimensions
PMFY-P VBM-E
Specifications
PMFY-P20VBM-E
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling
Heating
Cooling
Heating
Cooling capacity
Heating capacity
Power consumption
Current
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
External finish
❇3
Dimension H x W x D
Net weight ❇ 3
Heat exchanger
Type
mm(in.)
kg(lbs.)
Fan
m 3 /min
L/s
cfm
❇3
Airflow rate
(Low-Mid2-Mid1-High)
External static
pressure
Type
Output
Motor
Gas
0
kW
Single phase induction motor
0.028
PP Honeycomb fabric
mm(in.)
(Flare)
Liquid
PMFY-P40VBM-E
ø 12.7(1/2")
ø 6.35(1/4")
mm(in.)
(Flare)
Drain pipe diameter
Noise level (Low-Mid2-Mid1-High) ❇ 4
PMFY-P32VBM-E
Pa
Air filter
Refrigerant
pipe diameter
PMFY-P25VBM-E
~220-240V 50Hz / ~ 220V 60Hz
4.5
2.2
2.8
3.6
7,500
9,600
12,300
15,400
2.3
2.9
3.7
4.7
2,000
2,500
3,150
4,000
5.0
2.5
3.2
4.0
2,200
2,800
3,400
4,300
8,500
10,900
13,600
17,100
0.054
0.042
0.044
0.054
0.042
0.044
0.26
0.20
0.21
0.26
0.20
0.21
Panel : 0.98Y8.99/0.63
230<30> x 812<1,000> x 395<470> (9-1/16"<1-3/16" >x 32"<39-3/8"> x 15-9/16"<18-9/16">)
14 <3.0> (31<7>)
Cross fin (Aluminum plate fin and copper tube)
Line flow fan ✕ 1
6.5-7.2-8.0-8.7
7.7-8.7-9.7-10.7
7.3-8.0-8.6-9.3
108-120-133-145
122-133-143-155
128-145-162-178
230-254-283-307
258-283-304-328
272-307-343-378
Power source
O.D. ø25 (VP-20)
dB(A)
27-30-33-35
33-35-37-39
32-34-36-37
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇3 External dimension / net weight are shown in <panel>, and airflow rate/noise level are in (low-middle2-middle1-high).
❇4 It is measured in anechoic room.
External Dimensions
PMFY-P20,25,32,40VBM-E
Unit : mm
Top
1000 outer side of grille
960 seiling opening
811 suspension bolt pitch
759
20
20
17.5
28
45
PVC pipe:VP-20[OD ø25(1')]
Detail drawing of fresh air intake hole
247
69
17.5
4-ø2.8 Burring hole
ø100
28
45
OD ø12.7(1/2")
outer line of grille
Knock out
812
250
759
288.5
Terminal block for power supply
elect box
108
ø50
( 56)
Right side
drain pan
1000 outer side of grille
40
Installation space required around indoor unit
470
ceiling
panel
suspension bolt(M10 or W3/8)
Panel(grille):PMP-40BM
230
110
200
60
600
outer side of grille
200
Fresh air intake hole
Terminal biock for transmission
110
Front
235 or more
(10)
230
198
Drainage pipe
PVC pipe:VP-20[OD ø25]
Lower view
45
OD ø6.35(1/4")
Gas pipe
center of unit
ceiling panel
drain pan
same line
OD ø43
Liquid pipe
53
Air outlet(lower)
(96)
Left side
pipe cover
Drainage piping
43
20
ceiling opening
340 suspension bolt pitch
46
(20)
176
96
Refrigerant
pipe(liquid)
OD ø6.35
20
Refrigerant
piping
2
141
20
74.5
26
2
ø1
Refrigerant pipe(gas)
OD ø12.7
395
302
254
430
470
outer side of grille
20
74.5
26
mounting plate
30
Panel(grille):PMP-40BM
INDOOR UNIT
Specifications & External Dimensions
New
PEFY-P VMR-E-L/R
Specifications
PEFY-P20VMR-E-L/R
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling
Heating
Cooling
Heating
Cooling capacity
Heating capacity
Power consumption
Current
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
2.2
7,500
2.3
2,000
2.5
2,200
8,500
0.06/0.06
0.06/0.06
0.29/0.29
0.29/0.29
kW
A
A
External finish
mm(in.)
kg(lbs.)
Dimension H x W x D
Net weight ❇ 3
Heat exchanger
Type
Fan
Airflow rate
(Low-Mid-High)
m 3 /min
❇3
External static pressure
Motor
PEFY-P25VMR-E-L/R
3.6
12,300
3.7
3,150
4.0
3,400
13,600
0.07/0.08
0.07/0.08
0.34/0.38
0.34/0.38
4.8-5.8-7.9
4.8-5.8-9.3
Pa
Type
Output
PEFY-P32VMR-E-L/R
1-phase 220/230/240 V 50Hz 220/230V 60Hz
2.8
9,600
2.9
2,500
3.2
2,800
10,900
0.06/0.06
0.06/0.06
0.29/0.29
0.29/0.29
Galvanized
292 x 640 x 580
18 (40)
Cross fin (Aluminum fin and copper tube)
Sirocco fan ✕ 1
Power source
5
1-phase induction motor
kW
Air filter
Refrigerant
pipe diameter
Gas(Flare)
Liquid(Flare)
Drain pipe diameter
Noise level
(Low-Mid2-Mid1-High)
❇4
220V
230V
240V
0.018
PP Honeycomb fabric (washable)
mm(in.)
ø 6.35(1/4")
mm(in.)
ø 12.7(1/2")
O.D. 26(1-1/32)
0.023
20-25-30
21-26-32
22-27-30
dB(A)
20-25-33
21-26-35
22-27-33
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27˚C (81˚F) DB/19˚C (66˚F) WB, Outdoor 35˚C (95˚F) DB
Heating: Indoor 20˚C (68˚F) DB, Outdoor 7˚C (45˚F)DB/6˚C (43˚F) WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇3 The external static pressure is set to 100Pa (at 220V) / 150Pa (at 230, 240V) at factory shipment.
❇4 Measured in anechoic room. Noise levels of the unit with a rear air inlet. (Noise levels are higher for the unit with a
bottom air inlet.)
External Dimensions
PEFY-P20,25,32VMR-E-L/R
Unit : mm
Right side
Note 1. Use M10 screw for the suspension bolt (field supply).
50mm or below of clearance between the Indoor unit top and the end of the
suspension bolt will make maintenance of the Indoor heat exchanger easier.
2. Access door of 450mm x 450mm at the ceiling under the drain pan should be
designed for heat exchanger cleaning and maintenance.
3. This drawing shows the left piping specification. The symmetry shows the
right piping specification.
Model name: <Left piping> PEFY-P20 · 25 · 32VMR-E-L
<Right piping> PEFY-P20 · 25 · 32VMR-E-R
4. Period cleaning of drain pan will prevent water overflowing.
Gradient piping design is needed for water draining.
5. The inlet direction can be changed between rear inlet and bottom inlet.
Keep the inlet space between the ceiling and the unit in case of bottom
inlet.
15
Air outlet
100
62 25
Required space for service and maintenance
(Note 2)
23
Control box
Left side
Suspension bolt outlet
(Note 1)
439 (Suspension bolt pitch)
105
250
580 (In case of rear inlet)
30
15
500
150
28
50
Rear
air inlet
Make the access door at the appointed position properly
for service maintenance.
3
Bottom plate
Access door
113
148
Bottom air inlet
Insulation material
Ceiling surface
More than 20mm
2x2-ø3
Terminal bed (Power source)
Hose band
450
450
50~
25
1
100
2
Terminal bed (M-Net Transmission)
Drain pan
150
50~
300
25
570 (In case of bottom inlet)
275
300 (In case of bottom inlet)
292 (In case of rear inlet)
50 or below
Suspension bolt hole
More than 20mm
80
Air filter
622
50x9=450
480
Rear
air inlet
50
630
584 (Suspension bolt pitch)
530
2x10-ø3
Adhesion
Rigid vinyl drain pipe
<Pipe size>
Refrigerant pipe (gas) brazed
Insulation material
or drain pan
Urethane foam
Drain hose (accessory)
150
Do not leave space.
ø12.7·································➀
Refrigerant pipe (liquid) brazed
ø6.35·································➁
Drain pipe connection diameter
VP20(dia. 26mm) ·············➂
46
INDOOR UNIT
Specifications & External Dimensions
New
PEFY-P VMS-E
Specifications
PEFY-P20VMS-E PEFY-P25VMS-E PEFY-P32VMS-E PEFY-P40VMS-E PEFY-P50VMS-E PEFY-P63VMS-E
Power source
Cooling capacity
❇1
❇1
Heating capacity
Power input
Current
Temperature set range Remote controller
Fan ❇2 Type x Quantity
External static press
Motor type
Motor output
Airflow rate(Low-Mid-High)
External finish
External dimension
HxWxD
Net weight
R410A
Refrigerant piping Liquid
R407C,R22
diameter
Gas
R410A
R407C,R22
Drain piping diameter
Noise level (Low-Mid-High)
(mesured in anechoic room)
Air filter
Connectable outdoor unit
Heat exchanger
kW
kW
kW
A
˚C(˚F)
Pa
kW
m3/min
mm
In.
kg
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
1-phase 220-240V 50Hz 1-phase 220-230V 60Hz
3.6
4.5
5.6
7.1
5.0
6.3
8.0
4.0
0.08
0.08
0.06
0.09
0.07
0.11
0.09
0.13
0.11
0.14
0.12
0.06
0.39
0.39
0.28
0.44
0.33
0.53
0.42
0.63
0.52
0.68
0.57
0.28
19 to 30 (67 to 86) 17 to 28 (63 to 83) 19 to 30 (67 to 86) 17 to 28 (63 to 83) 19 to 30 (67 to 86) 17 to 28 (63 to 83) 19 to 30 (67 to 86) 17 to 28 (63 to 83) 19 to 30 (67 to 86) 17 to 28 (63 to 83) 19 to 30 (67 to 86) 17 to 28 (63 to 83)
Sirocco fan x 4
Sirocco fan x 3
5-15-35-50
DC brushless motor
0.096
12-14-16.5
6-7-8
7.5-8.5-10
8-9.5-11
9.5-11-13
Galvanized
200 x 1100 x 700
200 x 900 x 700
7-7/8 x 43-5/16 x 27-9/16
7-7/8 x 35-7/16 x 27-9/16
23
24
28
ø6.35(ø1/4) Brazed ø9.52(ø3/8) Brazed
ø6.35(ø1/4) Brazed
ø9.52(ø3/8) Brazed ø9.52(ø3/8) Brazed
ø6.35(ø1/4) Brazed
ø12.7(ø1/2) Brazed ø15.88(ø5/8) Brazed
ø12.7(ø1/2) Brazed
ø12.7(ø1/2) Brazed
ø15.88(ø5/8) Brazed ø15.88(ø5/8) Brazed
O.D. 32(1-9/32)
2.2
2.5
2.8
3.2
dB<A>
22-25-27
25-28-30
30-32-35
28-30-33
30-33-36
PP Honeycomb fabric (washable)
R410A, R407C, R22 CITY MULTI
Cross fin(Aluminium fin and copper tube)
Note: ❇ 1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.
<Cooling> Indoor : 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B.) Outdoor : 35˚CD.B. (95˚FD.B. )
<Heating> Indoor : 20˚CD.B. (68˚FD.B.) Outdoor : 7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)
Pipe length : 7.5m (24-9/16ft)
Height difference : 0m (0ft)
❇ 2.The external static pressure is set to 15 Pa at factory shipment.
External Dimensions
PEFY-P20,25,32,40,50,63VMS-E
Unit : mm
157.5
37 100
20
12
37
157.5
37 100
37
Access door
88
88
20
12
777
50
G
50
More than 20mm
More than 20mm
Ceiling surface Access door
Make the access door at the appointed position properly
for service maintenance.
Air filter
Less than 300mm
88
175mm -+ 5 mm
(Actual length)
20
12
700
677
Drain pipe Drainpump
(O.D.ø32)
270
24-ø2.9
Model:P63(Note3)
Drain hose (I.D.ø32)
<accessory>
48
102
170
200
10
116
Model
PEFY-P20,25,32,40VMS-E
70
270
Terminal bed(Power source)
Drain pipe(O.D.ø32)
(Spontaneous draining)
Terminal bed(Transmission)
A
B
C
D
E
F
G
900
952
998
860
9
800
1000
1100 1152 1198 1060
11
1000 1200
PEFY-P50VMS-E
PEFY-P63VMS-E
100
20
12
23
625(Suspension bolt pitch)
23
150(Duct) 23
100
25
20-ø2.9
Air filter
Suspension bolt hole
4-14 X 30 Slot
Knockout hole ø27
(Power source wiring)
Control box
Knockout hole ø27
(Transmission wiring)
90
49
2 X 2-ø2.9
1 Refrigerant piping
brazing connection (gas)
47
Air filter
88
100
20
30
100
57
25
10
2 X E-ø2.9
2 Refrigerant piping
brazing connection (liquid)
1060
100 X 9=900
860
100 X 7=700
Air
inlet
450 n 300
tha
re
Mo
Required space for service and maintenance
50~
4
150 50
100
Air
outlet
A
B (Suspension bolt pitch)
C
D (Duct)
100 X (E-1)=F
Note2
1Gas pipe
ø12.7
✻1
✻2
ø12.7
ø15.88
ø15.88
2 Liquid pipe
ø6.35
✻1
✻2
ø6.35
ø9.52
ø9.52
Note 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at
the bottom.
3. This chart indicates for PEFY-P20~50VMS-E models,
which has 3 fans. PEFY-P63VMS-E model have 4 fans.
4. In case of the inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side.
✻1 : R410A outdoor unit
✻2 : R407C,R22 outdoor unit
Less than 550mm
15
INDOOR UNIT
Specifications & External Dimensions
PEFY-P VML-E
Specifications
PEFY-P20VML-E
Power source
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling capacity
Heating capacity
Cooling
Heating
Cooling
Heating
Power consumption
(50/60Hz)
Current
2.2
7,500
2.3
2,000
2.5
2,200
8,500
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
External finish
Dimension H x W x D
Net weight
Heat exchanger
3
Motor
m /min
L/s
Airflow rate
(Lo-Mid-Hi)
80-97-132
170-205-279
cfm
Pa
External static pressure
Type
Output
PEFY-P32VML-E
225 x 720 x 550 (8-7/8" x 28-3/8" x 21-11/16")
18 (40)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan ✕ 1
4.8-5.8-7.9
mm(in.)
kg(lbs.)
Type
Fan
PEFY-P25VML-E
~ 220-240V 50Hz / 60Hz
2.8
9,600
2.9
2,500
3.2
2,800
10,900
0.05/0.06
0.05/0.06
0.24/0.28
0.24/0.28
Galvanizing
3.6
12,300
3.7
3,150
4.0
3,400
13,600
0.07/0.09
0.07/0.09
0.32/0.42
0.32/0.42
4.8-5.8-9.5
80-97-158
170-205-335
5
Single phase induction motor
0.023
PP Honeycomb fabric (washable)
kW
Air filter
mm(in.)
Gas(Brazing)
ø 12.7(1/2")
Refrigerant
pipe diameter
ø 6.35(1/4")
mm(in.)
Liquid(Brazing)
R1 (External thread)
Drain pipe diameter
Noise level (Lo-Mid-Hi)
dB(A)
25-29-36
❇5
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚(44.6˚F)CDB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(42.8˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇ 3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
❇ 4 The value are that at 240V.
❇ 5 It is measured in anechoic room.
0.032
25-29-40
External Dimensions
PEFY-P20,25,32VML-E
Unit : mm
The part air intake duct is attached. (✻3)
(When the air intake duct is used)
Note 1.Use M10 screw for the lifting bolt (field supply).
2.Keep the service space for the maintenance
from the bottom when the heat exchanger is
cleaned.
3.The direction of air intake can be changed from
the bottom to the rear by attaching the bottom
plate to the air intake side.
4.Drain Pan is changeable from right and left.
5.The dimension is changed, in case the optional
long-life filter is attached.
RearAir-Intake spec.:Depth is increased by
30mm(✻1)
BottomAir-Intake spec.:Height is increased
by 30mm(✻2)
Lifting bolt
14
80
Control box
459 (Lifting bolt pitch)
582
Refrigerant piping brazing connection
(gas ø12.7 copper tube):LP ··· 1
Refrigerant piping brazing connection
(liquid ø6.35 copper tube):HP ··· 2
Drain piping connection R1 (External thread) ··· 3
42.5
55
65.5
204.5
550 (✻1)
510
2
1
148
30
15
2✕3-ø3
540
14
Air filter
13.5
23
80
15
50✕11=550
720
Air outlet
50
Air inlet
16
710
664 (Lifting bolt pitch)
610
12-ø3
Air inlet
Air filter
Terminal bed
(Power source)
Terminal bed
(Transmission)
3
113
127
225 (✻2)
50 50
Bottom plate
In case of rear inlet
In case of bottom inlet
Air filter
Air inlet
Bottom plate
48
INDOOR UNIT
Specifications & External Dimensions
PEFY-P VMM-E
Specifications
PEFY-P20VMM-E PEFY-P25VMM-E PEFY-P32VMM-E PEFY-P40VMM-E PEFY-P50VMM-E PEFY-P63VMM-E
Power source
Cooling capacity
Heating capacity
Power consumption
(50Hz)
Current
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling
Heating
Cooling
Heating
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
2.2
7,500
2.3
2,000
2.5
2,200
8,500
~220-240V 50Hz
3.6
4.5
15,400
12,300
4.7
3.7
4,000
3,150
4.0
5.0
3,400
4,300
13,600
17,100
0.17
0.19
0.17
0.19
0.92
0.81
0.81
0.92
Galvanizing
2.8
9,600
2.9
2,500
3.2
2,800
10,900
0.15
0.15
0.73
0.73
External finish
Dimension H x W x D
mm(in.)
Net weight
Heat exchanger
Type
kg(lbs.)
m3/min
Fan
Airflow rate
(Lo-Mid-Hi)
External static pressure
Type
Output
Air filter
Motor
Gas
Refrigerant
pipe diameter
(Flare)
Liquid
(Flare)
Drain pipe diameter
Noise level (Lo-Mid-Hi)
❇3
L/s
cfm
Pa
295 x 815 x 700
(11-5/8 "x 32-1/8" x 27-9/16")
5.6
19,100
5.8
5,000
6.3
5,400
21,500
0.20
0.20
0.98
0.98
7.1
24,200
7.3
6,300
8.0
6,900
27,300
0.22
0.22
1.07
1.07
295 x 935 x 700
(11-5/8" x 36-13/16" x 27-9/16")
295 x 1,175 x 700
(11-5/8" x 46-5/16" x 27-9/16")
33(73)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan✕ 1
Sirocco fan✕ 2
6.0-7.2-8.5
100-120-142
212-254-300
kW
7.5-9.0-10.5
10.0-12.0-14.0
125-150-175
167-200-233
265-318-371
353-424-494
30/50/100
Single phase induction motor
0.075
PP Honeycomb fabric (washable)
mm(in.)
ø 12.7(1/2")
mm(in.)
ø 6.35(1/4")
dB(A)
12.0-14.5-17.0
200-242-283
424-512-600
27-30-32
ø 12.7(1/2")[R410A]
ø 15.88(5/8")[R22,R407C]
ø 6.35(1/4")[R410A]
ø 9.52(3/8")[R22,R407C]
Cooling capacity
Heating capacity
Power consumption
(50Hz)
Current
8.0
27,300
8.3
7,100
9.0
7,700
30,700
9.0
30,700
9.3
8,000
10.0
8,600
34,100
0.25
0.25
1.15
1.15
External finish
Dimension H x W x D
mm(in.)
Net weight
Heat exchanger
Type
kg(lbs.)
Fan
Airflow rate
(Lo-Hi)
External static pressure
Type
Output
Air filter
Motor
Gas
Refrigerant
pipe diameter
(Flare)
Liquid
(Flare)
Drain pipe diameter
Noise level (Lo-Mid-Hi)
❇3
m3/min
L/s
cfm
Pa
kW
mm(in.)
295 x 1,175 x 700
(11-5/8" x 46-5/16" x 27-9/16")
16.0
54,600
16.3
14,000
18.0
15,500
61,400
0.42
0.42
1.95
1.95
325 x 1,715 x 740
(12-13/16" x 67-9/16" x 29-3/16")
62(137)
65(144)
70(155)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan✕2
23.0-33.0
28.0-40.0
29.5-42.0
14.5-18.0-21.0
383-550
467-667
492-700
242-300-350
812-1165
989-1413
1042-1483
512-636-742
50/130
30/50/100
Single phase induction motor
0.280
0.200
0.078
PP Honeycomb fabric (washable)
ø 15.88(5/8") [R410A]
ø 15.88(5/8")
ø 19.05(3/4") [R22,R407C]
42(93)
mm(in.)
dB(A)
~220-240V 50Hz
14.0
11.2
38,200
47,800
11.6
14.5
12,500
10,000
16.0
12.5
10,800
13,800
42,700
54,600
0.29
0.40
0.29
0.40
1.34
1.90
1.34
1.90
Galvanizing
325 x 1,415 x 740
(12-13/16" x 55-3/4" x 29-3/16")
ø 9.52 (3/8")
32-36-39
R1 (External thread)
40-44
42-45
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB (WR2: water 20˚C(68˚F))
❇ 3 It is measured in anechoic room.
49
ø 15.88(5/8")
ø 9.52(3/8")
31-35-38
PEFY-P71VMM-E PEFY-P80VMM-E PEFY-P100VMM-E PEFY-P125VMM-E PEFY-P140VMM-E
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
13.5-16.2-19.0
225-270-317
477-572-671
0.078
R1 (External thread)
28-32-35
31-34-37
Power source
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling
Heating
Cooling
Heating
42(93)
27(60)
42-45
INDOOR UNIT
Specifications & External Dimensions
PEFY-P VMM-E
External Dimensions
Service space:500mm or more
1
282
288
256
176
Air inlet
355
365˜465
159
56
18
B
81
A
44 75
243
10
2
C
E
13
D
30
10-ø3(P20/25/32/40/50)
12-ø3(P63/71/80)
6
277
45 80
85
227
24
10
81
30
61
40
3.5
21
In case of rear inlet
640
4
179
30
81
Lifting bolt hole
13
35
P63,71,80
D
E
710 684
830 804
109
P50
C
-
B
(14X22)
H(Liquid) H(Gas)
F
G
17
27
6.35
12.7
17
27
6.35
12.7
✻1 6.35 ✻1 12.7 ✻1 22 ✻1 29
772 305
830 804
✻2 9.52 ✻2 15.88 ✻2 22 ✻2 29
9.52
15.88
1012 280 290 1070 1044
22
29
A
B
652 245
772 305
C
81
197
450
H
Refrigerant piping flare connection (liquid øF copper tube):HP
Refrigerant piping flare connection (gas øG copper tube) :LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Drain Pipe (Option)···Flexible joint VP-25(I.D.ø32) Set
Filter
Model
P20,25,32
P40
55
Access door
10-ø3(P20/25/32/40/50)
12-ø3(P63/71/80)
A
10
Note: 1. On Model :50, you would use flare nut packed
with the Indoor Unit, when connnecting the
Outdoor Unit for R407C, R22.
2. In order to increase the strength
of the flare nut, the size of some
of them has been increased.
1
2
3
4
5
6
7
50˜150 29
450
Unit : mm
10
PEFY-P20,25,32,40,50,63,71,80VMM-E
5
7
3.5
Air outlet
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter (field supply) near the air inlet grille.
In case of bottom inlet
10-ø3(P20/25/32/40/50)
12-ø3(P63/71/80)
7
10
Air outlet
40
15
10
176
256
81
C
B
81
A
Air inlet
PEFY-P100,125,140VMM-E
Service space:500mm or more
450
Access door
365˜465
323
308
2
44
282
319
279
181
Air inlet
13
E
75
D
B
81
13
30
243
6
307
45 122
113
1
30
10
40
In case of rear inlet
4
169
35
3
25
53
20
680
C
A
10
80
12-ø3
81
210
30
81
Lifting bolt hole
(14X22)
C
D
E
F(Liquid) F(Gas)
370 1310 1284
22
36
470 1610 1584
22
36
140
Model
A
B
P100·125 1252 360
P140
1552 460
5
7
3
Air outlet
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter (field supply) near the air inlet grille.
In case of bottom inlet
282
Air outlet
12-ø3
10
7
15
40
181
279
Air inlet
10
3
4
5
6
7
(liquid ø9.52 copper tube):HP
Refrigerant piping flare connection
(gas ø15.88<R410A outdoor unit> copper tube):LP
ø19.05<R407C,R22 outdoor unit>
Drain 25A (male screw)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option)···Flexible joint VP25(I.D. ø32)
Filter
30
2
B
375
1 Refrigerant piping flare connection
12-ø3
A
C
197
450
H
50˜150 29
55 81
10
Note: 1. On this model, you would use flare nut packed
with the Indoor Unit, when connnecting the
Outdoor Unit for R407C, R22.
2. In order to increase the strength
of the flare nut, the size of some
of them has been increased.
81
C
B
81
A
50
INDOOR UNIT
Specifications & External Dimensions
PEFY-P VMH-E
Specifications
Power source
Cooling capacity
Heating capacity
Power consumption
(50/60Hz)
Current
❇1
❇1
❇2
❇2
❇1
❇1
❇1
Cooling
Heating
Cooling
Heating
External finish
Dimension H x W x D
Net weight
Heat exchanger
Type
Fan
Airflow rate
(Lo-Hi)
External static 220V
pressure ❇ 3 230, 240V
Type
Motor
Output
❇4
Air filter (option)
Gas
(Flare)
Refrigerant
pipe diameter
Liquid
(Flare)
Drain pipe diameter
Noise level (Lo-Hi)
220V
❇ 5 230, 240V
PEFY-P40VMH-E PEFY-P50VMH-E PEFY-P63VMH-E PEFY-P71VMH-E PEFY-P80VMH-E PEFY-P100VMH-E PEFY-P125VMH-E PEFY-P140VMH-E
~ 220-240V 50Hz /60Hz
16.0
9.0
11.2
14.0
8.0
4.5
5.6
kW
7.1
BTU/h
15,400
19,100
24,200
27,300
30,700
38,200
47,800
54,600
kW
9.3
11.6
14.5
16.3
8.3
4.7
5.8
7.3
8,000
7,100
4,000
5,000
kcal/h
10,000
12,500
14,000
6,300
10.0
18.0
12.5
16.0
9.0
5.0
6.3
kW
8.0
kcal/h
4,300
5,400
10,800
13,800
15,500
6,900
8,600
7,700
34,100
BTU/h
17,100
21,500
27,300
30,700
42,700
54,600
61,400
kW
0.32/0.40
0.48/0.58
0.48/0.59
0.19/0.23
0.24/0.30
0.26/0.33
kW
0.19/0.23
0.24/0.30
0.26/0.33
0.32/0.40
0.48/0.58
0.48/0.59
A
0.88/1.06
1.12/1.38
1.20/1.51
1.47/1.83
2.34/2.66
2.35/2.70
A
0.88/1.06
1.12/1.38
1.20/1.51
1.47/1.83
2.34/2.66
2.35/2.70
Galvanizing
380 x 1,000 x 900
380 x 1,200 x 900
mm
380 x 750 x 900
15" x 39-3/8" x 35-7/16"
15" x 47-1/4" x 35-7/16"
15" x 29-9/16" x 35-7/16"
in.
kg(lbs.)
50(111)
45(100)
44(98)
70(155)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan ✕ 1
Sirocco fan ✕ 2
m3/min
10.0-14.0
28.0-40.0
13.5-19.0
18.0-25.0
15.5-22.0
26.5-38.0
L/s
167-233
225-317
258-367
300-417
442-633
467-667
353-494
477-671
547-777
636-883
936-1342
989-1413
cfm
Pa
50/100/200
Pa
100/150/200
Single phase induction motor
0.08
0.12
0.14
0.26
0.18
kW
Synthethic fiber unwoven cloth filter(long life)
1
ø 15.88 (5/8") [R410A]
mm(in.)
ø 12.7 (1/2") ø 12.7 5( /2") [R410A]
ø 15.88(5/8")
ø 15.88 ( /8") [R22,R407C]
ø 19.05 (3/4") [R22,R407C]
1/4") [R410A]
ø
6.35(
mm(in.)
ø 6.35 (1/4")
ø 9.52(3/8")
ø 9.52 (3/8")[R22,R407C]
32 (1-1/4 inch)
32 (1-1/4 inch)
35-41
dB(A)
27-34
32-38
32-39
34-42
38-43
dB(A)
31-37
36-41
35-41
38-44
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇ 3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
❇ 4 The value are that at 240V.
❇ 5 It is measured in anechoic room.
External Dimensions
Unit : mm
PEFY-P40,50,63,71,80, 100,125,140VMH-E
G-ø3
Air outlet
Air inlet
E
A
50x(J-1)=K
B (Lifting bolt pitch)
C
50x(G-1)=H
D
J-ø3
Less than 300mm
170mm±5mm
(Actual length)
50
50
Less than 550 mm
3
80
41 F
15
23
70
10
3
340
383
Lifting bolt
250
814 (Lifting bolt pitch)
904
Model:40~80 (Note3)
60
When installing the drain water lifting-up mech(option).
900
24
10
847
29
15
Drain hole
(option)
Control box
Terminal box
Terminal bed
(Transmission)
Keep duct-work length 850mm or more.
Drain hole
51
1
92
200
343
387
77
328
250
380
94
50 50 50 50
41 25
30
45
17
Terminal bed
(Power source)
130
50x5=250
50
340
2
Model
P40VMH-E
L
K
J
A
B
C
D
E
F G H
800 754 680 600 550 50 11 500 10 450 780
P50VMH-E
800 754 680 600 550 50 11 500 10 450 780
M
ø12.7
✻1 ø12.7
✻2 ø15.88
P63VMH-E
800 754 680 600 550 50 11 500 10 450 780 ø15.88
P71·80VMH-E 1050 1004 930 850 800 25 17 800 15 700 1030 ø15.88
✻1 ø15.88
P100·125
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
·140VMH-E
✻2 ø19.05
N
ø6.35
✻1 ø6.35
✻2 ø9.52
ø9.52
ø9.52
✻1 ø9.52
✻2 ø9.52
P(Liquid)
17
✻1 22
✻2 22
22
22
✻1 22
✻2 22
P(Gas)
27
✻1 29
✻2 29
29
29
✻1 36
✻2 36
✻1:R410A outdoor unit
✻2:R407C,R22 outdoor unit
Note : 1. Use M10 screw for the lifting bolt (field supply).
2. Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned.
3. This chart indicates for PEFY-P100·125·140VMH-E models, which have 2 fans.
PEFY-P40·50·63·71·80 models have 1 fan.
4. Make sure to install the air filter(field supply) on the air intake side.
In case field supplied air filter is used, attach it where the filter service is easily done.
5.On Model :50, 100, 125, 140, you would use flare nut packed with the Indoor Unit,
when connnecting the Outdoor Unit for R407C, R22.
6.In order to increase the strength of the flare nut, the size of some of them has been increased.
Refrigerant piping flare connection (gas M copper tube) : LP
··· ➀
Refrigerant piping flare connection (liquid N copper tube) : HP
··· ➁
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory) ··· ➂
P
INDOOR UNIT
Specifications & External Dimensions
PEFY-P VMH-E
Specifications
PEFY-P200VMH-E
PEFY-P250VMH-E
Power source
3N ~ 380-415V 50Hz / 60Hz
❇
❇
❇
❇
❇
❇
❇
Cooling capacity
Heating capacity
1
1
2
2
1
1
1
Cooling
Heating
Cooling
Heating
Power consumption
(50/60Hz)
Current
External finish
Dimension H x W x D
Net weight
Heat exchanger
Type
Fan
22.4
76,400
23.3
20,000
25.0
21,500
85,300
0.99/1.14
0.99/1.14
1.62/1.86
1.62/1.86
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
28.0
95,500
29.1
25,000
31.5
27,100
107,500
1.23/1.41
1.23/1.41
2.0/2.3
2.0/2.3
Galvanizing
470 x 1,250 x 1,120 (18-9/16" x 49-1/4" x 44-1/8")
100 (221)
Cross fin (Aluminum plate fin and copper tube)
mm(in.)
kg(lbs.)
Sirocco fan ✕ 2
m 3/min
L/s
cfm
Airflow rate
External static
pressure
❇5
Type
Motor
Output
Air filter (option)
380V
400, 415V
Pa
Pa
❇6
kW
58.0
967
2048
72.0
1200
2543
110/220
130/260
3-phase induction motor
0.76
1.08
Synthethic fiber unwoven cloth filter(long life)
Gas
ø 19.05 (3/4") [R410A]
ø 25.4 (1") [R22,R407C]
mm(in.)
(Brazing)
Refrigerant
pipe diameter
Liquid
mm(in.)
(Brazing)
ø 22.2 (7/8") [R410A]
ø 28.58 (1-1/8") [R22,R407C]
ø 9.52 (3/8") (R410A)
ø 12.7 (1/2") (R22,R407C)
32 (1-1/4 inch)
Drain pipe diameter
42(110Pa)/45(220Pa)
50(110Pa)/52(220Pa)
dB(A)
44(130Pa)/47(260Pa)
52(130Pa)/54(260Pa)
dB(A)
Note: ❇1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
❇ 3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
❇ 4 The value are that at 240V.
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 5 The external static pressure is set to 110Pa (at 380V) /130Pa (at 400, 415V) at factory shipment.
❇ 6 The value are that at 415V.
❇2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F)) ❇ 7 It is measured in anechoic room.
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB (WR2: water 20˚C(68˚F))
380V
400, 415V
❇7
Noise level
External Dimensions
PEFY-P200, 250VMH-E
Unit : mm
22-ø3
3
420
1100
50x20=1000
1326 (Lifting bolt pitch)
1372
50
100
15
10
Lifting bolt
1034 (Lifting bolt pitch)
1124
60
1120
1067
24
10
Note : 1. Use M10 screw for the lifting bolt
(field supply).
2. Keep the service space for the
maintenance from the bottom when
the heat exchanger is cleaned.
3. Make sure to install the air filter(field
supply)on the air intake side.
In case field supplied air filter is
used, attach it where the filter
service is easily done.
4.On this model, you would use pipe
packed with the Indoor Unit, when
connnecting the Outdoor Unit for
R407C, R22.
Model
A
P200VMH-E
✻1 ø19.05
✻1
ø9.52
✻2 ø25.4
✻2
ø12.7
P250VMH-E
✻1 ø22.2
✻1
ø9.52
✻2
ø12.7
✻2 ø28.58
✻1:R410A outdoor unit
✻2:R407C,R22 outdoor unit
B
Refrigerant piping brazing connection
(gas A copper tube) : LP
Refrigerant piping brazing connection
(liquid B copper tube) : HP
Drain hose 32mm(1-1/4inch)
<flexible joint 200mm>(accessory)
23
1250
Air outlet
Air inlet
102 25
50x21=1050
1100
21-ø3
340
····➀
····➁
····➂
29
15
Drain hole
(option)
Control box
Keep duct-work length 850mm or more.
Terminal bed
(Transmission)
Drain hole
2
1
95
20
105
170mm±5mm
(Actual Length)
3
Less than 550mm
Terminal bed
(Power source)
30
20
35
41
164
420
50x7= 350
44
327
50x6= 300
340
470
Less than 300mm
249
422
489
When installing the drain water lifting-up mech(option).
52
INDOOR UNIT
Specifications & External Dimensions
PCFY-P VGM-E
Specifications
PCFY-P40VGM-E
PCFY-P63VGM-E
Power source
❇
❇
❇
❇
❇
❇
❇
Cooling capacity
Heating capacity
1
1
2
2
1
1
1
Cooling
Heating
Cooling
Heating
Power
consumption
Current
4.5
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
15,400
4.7
4,000
5.0
4,300
17,100
0.10
0.10
0.46
0.46
kW
kW
A
A
External finish(Munsel No.)
Dimension H x W x D
mm
in.
Net weight
Heat exchanger
Type
Fan
Motor
kg(lbs.)
Airflow rate
(Lo-Mid2-Mid1-Hi)
❇3
External staticpressure
Type
Output
Air filter
Gas(Flare)
Refrigerant
pipe diameter
Liquid(Flare)
Drain pipe diameter
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4
m3/min
L/s
cfm
PCFY-P100VGM-E PCFY-P125VGM-E
~ 220-240V 50Hz / ~220V 60Hz
11.2
7.1
24,200
38,200
7.3
11.6
10,000
6,300
12.5
8.0
6,900
10,800
27,300
42,700
0.16
0.13
0.16
0.13
0.73
0.60
0.73
0.60
0.70Y 8.59/0.97
210 x 1,310 x 680
270 x 1,310 x 680
210 x 1,000 x 680
14.0
47,800
14.5
12,500
16.0
13,800
54,600
0.24
0.24
1.10
1.10
270 x 1,620 x 680
8-5/16" x 39-3/8" x 26-13/16" 8-5/16" x 51-5/8" x 26-13/16" 10-11/16" x 51-5/8" x 26-13/16" 10-11/16" x 63-13/16" x 26-13/16"
27(60)
43(95)
37(82)
34(75)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan ✕ 2
Sirocco fan ✕ 3
Sirocco fan ✕ 4
8-10-11-12
133-167-183-200
253-353-388-424
12-14-16-18
200-233-267-300
424-494-565-636
0.054
mm(in.)
mm(in.)
ø 6.35(1/4")
ø 12.7(1/2")
dB(A)
26-28-32-35
433-467-533-583
918-989-1130-1236
0
Single phase induction motor
0.150
0.090
0.070
PP Honeycomb (long life)
5
5
3
ø 15.88( /8") / ø 19.05( /4") (Compatible)
ø 15.88( /8")
ø 9.52(3/8")
I.D. ø26 (VP-25)
37-39-42-44
36-38-41-43
32-34-37-39
Pa
kW
18-20-23-25
300-333-383-417
636-706-812-883
29-33-36-38
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C (80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C (68˚F))
❇3 airflw rate/noise level are shown in (low-middle 2-middle 1-high).
❇4 It is measured in anechoic room.
External Dimensions
PCFY-P40,63,100,125VGM-E
140
320
80
150 18
Unit : mm
70
Model
40
63
Liquid
ø6.35
ø9.52
100,125
ø9.52
Gas
ø12.7
ø15.88
ø15.88(R410A)
ø 19.05(R407C,R22)
E
(Suspension bolt pitch)
70
16
G
F
81 96
Air outlet
B
A
182
I
J
High press.
Low press.
(Drainage)
254
506
680
56
229
87
H
D
Electrical box
161
Air intake
PCFY
PCFY
PCFY
PCFY
53
Model
-P40VGM-E
-P63VGM-E
-P100VGM-E
-P125VGM-E
C
A
1,000
1,310
1,310
1,620
B
904
1,214
1,214
1,524
C
918
1,228
1,228
1,535
D
983
1,290
1,290
1,600
90
E
933
1,240
1,240
1,547
F
210
210
270
270
G
180
180
207
207
H
157
157
217
217
I
201
201
198
198
J
241
241
245
245
INDOOR UNIT
Specifications & External Dimensions
PKFY-P VAM-E
PKFY-P VGM-E
Specifications
PKFY-P20VAM-E
PKFY-P25VAM-E PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E
~ 220-240V 50Hz ~ 220V 60Hz
3.6
4.5
2.2
2.8
5.6
7,500
9,600
12,300
15,400
19,100
2.3
2.9
3.7
4.7
5.8
3,150
4,000
2,000
2,500
5,000
4.0
5.0
2.5
3.2
6.3
2,200
2,800
3,400
4,300
5,400
8,500
10,900
13,600
17,100
21,500
0.04
0.07
0.04
0.07
0.20
0.32
0.20
0.32
Plastic 2.60Y 8.66/0.69
Plastic <PS,ABS> white 0.70Y 8.59/0.97
340 x 990 x 235 (13-7/16" x 39" x 6-5/16")
295 x 815 x 158 (11-5/8" x 32-1/8" x 6-1/4")
16(36)
8.5(19)
Cross fin (Aluminum plate fin and copper tube)
Line flow fan ✕ 1
9-10-11-12
8-9.5-10.5-11.5
4.9-5.2-5.6-5.9
82-87-93-98
133-158-175-192
150-167-183-200
173-184-198-208
283-335-371-406
318-353-388-424
Power source
❇
❇
❇
❇
❇
❇
❇
Cooling capacity
Heating capacity
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
1
1
2
2
1
1
1
Cooling
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Dimension H x W x D
Net weight
Heat exchanger
Type
Power
consumption
❇ 3
Airflow rate
(Lo-Mid2-Mid1-Hi)
Fan
Motor
mm(in.)
kg(lbs.)
m 3 /min
L/s
cfm
Pa
External static pressure
Type
Output
0
Single phase induction motor
0.030
0.017
kW
Air filter
Gas
mm(in.)
(Flare)
Refrigerant
pipe diameter
PP Honeycomb (long life)
ø 12.7(1/2")
Liquid
ø 6.35(1/4")
mm(in.)
(Flare)
ø 12.7(1/2") / ø 15.88(5/8")
(Compatible)
ø 6.35(1/4") / ø 9.52(3/8")
(Compatible)
Drain pipe diameter
I.D. ø16 (VP-16)
32-33-35-36
I.D. ø20 (VP-20)
33-36-38-41
dB(A)
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇ 3 Airflow rate/noise level are in (low-middle2-middle1-high).
❇ 4 It is measured in anechoic room.
34-37-40-43
External Dimensions
Front view
Left side
715 Air intake
340 Air intake
225
280 Air intake
80
Right side
13
295
Adress board
990
Lower side
660 (Total length of drain piping 760)
705 Air outlet
235
12-Louvers (manual)
160
40
60
80
110
50
450 Gas pipe
520 Liquid pipe
400
35
395
Service panel
(Power supply access)
Front view(to open the grille)
Filter grip
Terminal block for
remote control
280
5
Terminal block for
power supply
Installation board
37.4
31
Intake
direction
70
190
116
The address board is protected by
a plastic cover.
Remove the cover with a screwdriver
(one screw) to set the board.
158
Knock out hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
79
60
Knock out hole for
right piping
Refrigerant pipe.
Drain pipe.
Wiring hole
Address board
146
695 Outlet dimensions
60
235
Knock out hole for
left piping
Refrigerant pipe.
Drain pipe.Wiring hole.
MITSUBISHI PKFY-VAM
630 Intake dimensions
245
MITSUBISHI ELECTRIC
Auto vane
60
Remote control
terminal plate
Power terminal plate
70 21
53
70 21
247.5 Intake dimensions
2.5 60 150
Less than 15
233
340
815
21.5
Unit : mm
PKFY-P32,40,50VGM-E
245
13
783
198 Air intake
25.5
Intake dimensions
PKFY-P20, 25VAM-E
Liquid pipe
ø6.35
Gas pipe
ø12.7
481
(Left side piping
installation)
35
549
17˚
Outlet
angle
70.3
Address board
Outlet
Outlet
dimensions Terminal plate
direction
Rotary switch (pair No.)
Rotary switch (own address)
Drain pipe (O.D. ø20)
54
86
700 (Flexible hose total length 800)
153
(Right side piping
installation)
Liquid pipe
Gas pipe
Model
32,40
50
Liquid pipe
Gas pipe
ø6.35
ø12.7
ø 6.35(R410A) ø 12.7(R410A)
ø9.52(R407C,R22) ø15.88(R407C,R22)
Dip switch (switches functions)
54
INDOOR UNIT
Specifications & External Dimensions
PKFY-P VFM-E
Specifications
PKFY-P63VFM-E
Power source
❇1
❇1
❇2
❇1
Heating capacity
❇1
Cooling
Power
consumption
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Height
Dimension
Width
Depth
Net weight
Heat exchanger
Type
Airflow rate
❇3
Fan (Lo-Hi)
External static pressure
kW
BTU/h
kcal/h
kW
BTU/h
kW
kW
A
A
7.1
24,200
6,300
8.0
27,300
0.12
0.12
0.55
0.55
mm(in.)
mm(in.)
mm(in.)
kg(lbs.)
340(13-3/8)
1,400(55-1/8)
235(9-1/4)
24(53)
Cooling capacity
Motor
11.2
38,200
10,000
12.5
42,700
0.14
0.14
0.64
0.64
Plastic, white : <3.4Y7.7/0.8>
340(13-3/8)
1,680(66-1/8)
235(9-1/4)
28(62)
Cross fin (Aluminum plate fin and copper tube)
Line flow fan ✕ 2
m3/min
15-20
22-28
Pa
Type
Output
0
Single phase induction motor
kW
0.040
0.070
Air filter
PP Honeycomb (antibacterial)
Gas
Refrigerant
pipe diameter
PKFY-P100VFM-E
220-230-240V 50Hz / 220V 60Hz
(Flare)
Liquid
(Flare)
ø15.88(5/8)
mm(in.)
ø15.88(5/8) / ø19.05(3/4)
mm(in.)
ø9.52(3/8)
Drain pipe diameter
I.D. ø20 (VP-20)
Noise level (Lo-Hi)
dB(A)
❇3 ❇4
39-45
Note: 1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
❇1 Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DB
Heating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇2 Cooling Indoor: 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB, Outdoor: 35˚C(95˚F)DB
❇3 Airflow rate/noise level are in (low-high).
❇4 It is measured in anechoic room.
41-46
External Dimensions
PKFY-P100VFM-E
235 45
235
235 45
62.5
Unit : mm
235 45
235 45
235 45
235 45
235
Front
Less than 15
2
197
Knock out hole
for left piping
C
Less than 15
2
Bolt
42
58
Knock out hole
for left piping
A
235
340
197
C
Right side
1680
1370 (Air intake)
Left side
340
A
Knock out hole
for right piping
235
1400
1090 Air intake
Left side
13
235 45
Top
13
62.5
PKFY-P63VFM-E
42
58
Bolt
Drain hose
Drain hose
55(Gas pipe)
107
120(Liquid pipe)
1
1110 (Drain hose)
Lower side
Auto vanes
louvers(manual)
1120
552Air outlet
25
55 (Gas pipe)
120 (Liquid pipe) 102
111
1
Drain hose
Drain hose for
left-hand side piping
1110 (Drain hose)
183
Lower side
1400
240
240
694 Air outlet
552Air outlet
694 Air outlet
louvers(manual)
B
Auto vanes
Knock out hole for under-piping
Refrigerant pipe .Drain pipe
Knock out hole for under-piping
Refrigerant pipe .Drain pipe
Knock out hole for wiring
Unit center
990
37
74
245
285
19
91
74
Unit center
1270
84-ø6 hole
for tapping
screw
18
Drainage range on
right-hand side
285
19
900
91
180
12-ø6 hole
for tapping screw
280
314
184
30
80
280
60
240
610
32-ø12 hole
for bolt
30
225
55
90 Rear piping hole
Range for left rear piping hole
245
595
13X91=(1183)
18
60
184
30
66-ø6 hole
for tapping
screw
32
Wall fixture
10
30
29
18
37
98
Unit out line
455
Wall fixture
39
Drainage range on
left hand side
Drainage range on
right-hand side
10X91=(910)
900
18
C
30
37
65
100
39
37
74
32
Drainage range on
left hand side
B
10
30
29
98
100
4 39
39
4
37
74
A
30
39
100
C
30
37
65
100
4 39
B
4
Knock out hole for wiring
A
30
B
Under panel(Removable at
left-hand side piping)
Under panel(Removable at
left-hand side piping)
80
280
Drain hose for
left-hand side piping
111
183
41-ø12 hole
for bolt
295
Range for left rear piping hole
225
240
180
12-ø6 hole
for tapping screw
280
750
314
30
25
90 Rear piping hole
Range for left rear piping hole
INDOOR UNIT
Specifications & External Dimensions
New
PFFY-P VKM-E
Specifications
PFFY-P20VKM-E
PFFY-P25VKM-E
Power source
PFFY-P32VKM-E
PFFY-P40VKM-E
1-phase 220-240V 50Hz
Cooling capacity
❇1
kW
2.2
2.8
3.6
Heating capacity
❇1
kW
2.5
3.2
4.0
5.0
4.5
Power
Cooling
kW
0.025
0.025
0.025
0.028
consumption
Heating
kW
0.025
0.025
0.025
0.028
Current
Cooling
A
0.20
0.20
0.20
0.24
Heating
A
0.20
0.20
0.20
0.24
Height
mm
600
600
600
600
Width
mm
700
700
700
700
Depth
mm
200
200
200
200
kg
15
15
15
15
Dimension
Weight
Heat exchanger
Cross fin (Alminium plate fin and copper tube)
Line flow fan ✕ 2
Type
❇2
Airflow rate
m3/min
(Low-Mid-High-SHi)
Fan
6.1-7.0-8.0-9.1
6.1-7.0-8.0-9.1
5.9-6.8-7.6-8.7
8.0-9.0-9.5-10.7
External static
Pa
pressure
Motor
0
Type
DC motor
Output
0.03 ✕ 2
kW
Air filter
PP honeycomb fabric (Catechin Filter)
Refrigerant
Gas(Flare)
mm
pipe diameter
Liquid(Flare)
mm
❇2 ❇3
Noise level(Low-Mid-High-SHi)
12.7
6.35
dB(A)
35-38-42-44
28-32-35-38
28-32-35-38
27-31-34-37
Note: 1. Cooling/heating capacity indicates the maximum value at operation under the following condition.
❇1 Cooling Indoor: 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB, Outdoor: 35˚C(95˚F)DB
Heating Indoor: 20˚C(68˚F)DB, Outdoor: 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇2 Airflow rate/noise level are in (Low-Mid-High-SHi).
❇3 It is measured in anechoic room.
External Dimensions
PFFY-P20,25,32,40VKM-E
Unit : mm
131
131
7
4- 6 Hole
700
46.5
593
607
12
200
Air out
210
More than
100mm
Indoor unit
12
46.5
333
363
Installation plate
337
More than
100mm
More than
100mm
Air in
96
600
337
118
Gas pipe
12.7(flared)1/2
Liquid pipe
6.35(flared)1/4
11
508
155
454
12
60
205
165
125
128
45
35
72
110
19
drain
137
60
123
54
147
12
60
60
19
125
60
Air out
60
80
56
INDOOR UNIT
Specifications & External Dimensions
PFFY-P VLEM-E
PFFY-P VLRM-E
Specifications
PFFY-P20VLEM-E PFFY-P25VLEM-E PFFY-P32VLEM-E PFFY-P40VLEM-E PFFY-P50VLEM-E PFFY-P63VLEM-E
Power source
❇1
❇1
Cooling capacity
❇2
❇2
❇1
Heating capacity
❇1
❇1
Cooling
Power
consumption
Heating
Cooling
Current
Heating
External finish(Munsel No.)
kW
BTU/h
kW
kcal/h
kW
kcal/h
BTU/h
kW
kW
A
A
Dimension H x W x D
mm
in.
kg(lbs.)
Net weight
Heat exchanger
Type
Fan
❇3
Airflow rate
(Low-High)
External static
pressure
Type
Motor
Output
Air filter
Gas
Refrigerant
pipe diameter
(Flare)
Liquid
(Flare)
Drain pipe diameter
Noise level (Low-High) ❇3 ❇4 ❇5
m3/min
L/s
cfm
~ 220-240V 50Hz / ~ 208-230V 60Hz
3.6
4.5
5.6
7.1
12,300
15,400
19,100
24,200
3.7
4.7
5.8
7.3
3,150
4,000
5,000
6,300
4.0
5.0
6.3
8.0
4,300
5,400
6,900
3,400
17,100
21,500
27,300
13,600
0.065 / 0.075
0.06 / 0.07
0.085 / 0.09
0.1 / 0.11
0.065 / 0.075
0.06 / 0.07
0.085 / 0.09
0.1 / 0.11
0.32 / 0.33
0.29 / 0.30
0.40 / 0.41
0.46 / 0.47
0.32 / 0.33
0.29 / 0.30
0.40 / 0.41
0.46 / 0.47
Acrylic paint (5Y 8/1)
630 x 1,170 x 220
630 x 1,410 x 220
630 x 1,050 x 220
24-13/16" x 46-1/8" x 8-11/16"
24-13/16" x 55-9/16" x 8-11/16"
24-13/16" x 41-3/8" x 8-11/16"
23(51)
30(67)
25(56)
26(58)
32(71)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan✕ 2
Sirocco fan✕ 1
9.0-11.0
5.5-6.5
12.0-14.0
7.0-9.0
12.0-15.5
92-108
117-150
150-183
200-233
200-258
194-230
247-318
318-388
424-494
424-547
2.2
7,500
2.3
2,000
2.5
2,200
8,500
2.8
9,600
2.9
2,500
3.2
2,800
10,900
0.04 / 0.06
0.04 / 0.06
0.19 / 0.25
0.19 / 0.25
Pa
0
kW
Single phase induction motor
0.030
0.018
PP Honeycomb fabric (washable)
0.015
mm(in.)
mm(in.)
dB(A)
34-40
0.035
0.063
ø 12.7 (1/2")
ø 12.7 (1/2") [R410A]
ø 15.88 (5/8") [R22,R407C]
ø 15.88 (5/8")
ø 6.35 (1/4")
ø 6.35 (1/4") [R410A]
ø 9.52 (3/8") [R22,R407C]
ø 9.52 (3/8")
Accessary hose ø 27 (top end : ø 20)
38-43
35-40
40-46
PFFY-P20VLRM-E PFFY-P25VLRM-E PFFY-P32VLRM-E PFFY-P40VLRM-E PFFY-P50VLRM-E PFFY-P63VLRM-E
Power source
❇1
❇1
❇2
❇2
kW
BTU/h
kW
kcal/h
❇1
❇1
❇1
Cooling
Power
consumption
Heating
Cooling
Current
Heating
External finish(Munsel No.)
Dimension H x W x D
kW
kcal/h
BTU/h
kW
kW
A
A
Cooling capacity
Heating capacity
mm
in.
kg(lbs.)
Net weight
Heat exchanger
Type
Fan
❇3
Airflow rate
(Low-High)
External static
pressure
Type
Motor
Output
Air filter
Gas
Refrigerant
pipe diameter
(Flare)
Liquid
m3/min
L/s
cfm
~ 220-240V 50Hz / ~ 208-230V 60Hz
3.6
4.5
5.6
7.1
12,300
15,400
19,100
24,200
3.7
4.7
5.8
7.3
3,150
4,000
5,000
6,300
4.0
5.0
6.3
8.0
4,300
5,400
6,900
3,400
13,600
17,100
21,500
27,300
0.065 / 0.075
0.06 / 0.07
0.085 / 0.09
0.1 / 0.11
0.065 / 0.075
0.06 / 0.07
0.085 / 0.09
0.1 / 0.11
0.32 / 0.33
0.29 / 0.30
0.40 / 0.41
0.46 / 0.47
0.32 / 0.33
0.29 / 0.30
0.40 / 0.41
0.46 / 0.47
Galvanizing
639 x 1,006 x 220
639 x 1,246 x 220
639 x 886 x 220
25-3/16" x 39-5/8" x 8-11/16"
25-3/16" x 49-1/16" x 8-11/16"
25-3/16" x 34-15/16" x 8-11/16"
27(60)
25(56)
20(45)
21(47)
18.5(41)
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan✕ 2
Sirocco fan✕ 1
12.0-15.5
5.5-6.5
7.0-9.0
9.0-11.0
12.0-14.0
92-108
117-150
150-183
200-233
200-258
194-230
247-318
318-388
424-494
424-547
2.2
7,500
2.3
2,000
2.5
2,200
8,500
2.8
9,600
2.9
2,500
3.2
2,800
10,900
0.04 / 0.06
0.04 / 0.06
0.19 / 0.25
0.19 / 0.25
Pa
kW
mm(in.)
0
0.015
Single phase induction motor
0.030
0.035
0.018
PP Honeycomb fabric (washable)
ø 12.7 (1/2") [R410A]
ø 12.7 (1/2")
ø 15.88 (5/8")[R22,R407C]
(1/4")
ø 6.35
[R410A]
ø 9.52 (3/8") [R22,R407C]
Drain pipe diameter
Accessary hose ø 27 (top end : ø 20)
dB(A)
Noise level (Low-High) ❇3 ❇4 ❇5
38-43
35-40
34-40
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19˚C(66.2˚F)WB,Outdoor 35˚C(95˚F)DB
Heating : Indoor 20˚C(68˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚C(80.6˚F)DB/19.5˚C(67.1˚F)WB,Outdoor 35˚C(95˚F)DB (WR2: water 30˚C(80˚F))
Heating : Indoor 21˚C(69.8˚F)DB,Outdoor 7˚C(44.6˚F)DB/6˚C(42.8˚F)WB
(WR2: water 20˚C(68˚F))
❇ 3 Air flow rate/noise level are in ( Low-High)
❇ 4 Measured point : 1m51m, Power supply : AC240V/50Hz
·1dB(A) lower at AC230V/50Hz
·2dB(A) lower at AC220V/50Hz
·3dB(A) lower at 1.5m✕1.5m point
❇ 5 It is measured in anechoic room.
(Flare)
57
mm(in.)
ø 6.35 (1/4")
0.063
ø 15.88 (5/8")
ø 9.52 (3/8")
40-46
INDOOR UNIT
Specifications & External Dimensions
PFFY-P VLEM-E
PFFY-P VLRM-E
External Dimensions
PFFY-P20,25,32,40,50,63VLEM-E
Unit : mm
Air supply grille
(60)
Note: 1. On Model :50, you would use flare nut
packed with the Indoor Unit, when
connnecting the Outdoor Unit for R407C,
R22.
2. In order to increase the strength of the flare
nut, the size of some of them has been
120
Remote controller
can be built-in.
(Program timer can not be
built-in together)
40
G
Air outlet
C
A
220
80
B
170
2 ✕ 2-12 ✕16
Wall mounting hole
15
160
Refrigeant piping flare
connection(Liquid) F : HP
108
20
35
15
Refrigerant piping flare
connection(Gas) E : LP
35
Strainer
78
300
630
500
310
50
Drain pan
100
( 75 )
170
430
Hose(accessory)
OD ø 27(TOP ø 20)
Level adjusting screw
4 pcs.(attached)
Air
inlet
Air filter
6
10
45
90
D
170
B
220
2-12 ✕16
Floor mounting hole
21
25
10
220
B
640
640
760
760
C
600
600
720
720
D
610
610
730
730
E(Gas)
F(Liquid)
ø12.7
ø6.35
ø12.7
ø6.35
ø12.7
ø6.35
ø12.7
ø6.35
✻1 ø12.7 ✻1 ø6.35
PFFY-P50VLEM-E 1410 1000 960 970
✻2 ø15.88 ✻2 ø9.52
PFFY-P63VLEM-E 1410 1000 960 970
ø15.88
ø9.52
G(Liquid) G(Gas)
17
27
17
27
17
27
17
27
✻1 22 ✻1 29
✻2 22 ✻2 29
22
29
Piping
space
106
A
1050
1050
1170
1170
183.5
Dimensions
Model
PFFY-P20VLEM-E
PFFY-P25VLEM-E
PFFY-P32VLEM-E
PFFY-P40VLEM-E
✻1:R410A outdoor unit
✻2:R407C,R22 outdoor unit
PFFY-P20,25,32,40,50,63VLRM-E
15
B
132
Note: 1. On Model :50, you would use flare nut packed with the Indoor
Unit, when connnecting the Outdoor Unit for R407C, R22.
2. In order to increase the strength of the flare nut, the size of
some of them has been increased.
J
167
Air outlet
A
E
120
80
10
29
2- ø 4.7
Duct mounting hole
C
2 ✕ F - ø 4.7
Duct mounting hole
30 8
49
2 ✕ 2 - 12 ✕ 16
Wall mounting hole
Refrigerant piping flare
connection(Gas) G : LP
90
220
98
84
Refrigeant piping flare
connection(Liquid) H : HP
50
Drain pan
35
300
310
Strainer
Hose(accessory)
OD ø 27(TOP ø 20)
( 75 )
170
430
400
639
100
15
9
Air
inlet
76
Dimensions
Model
A
B
PFFY-P20VLRM-E 886 640
PFFY-P25VLRM-E 886 640
PFFY-P32VLRM-E 1006 760
PFFY-P40VLRM-E 1006 760
C
572
572
692
692
D
610
610
730
730
PFFY-P50VLRM-E 1246 1000 932
970
PFFY-P63VLRM-E 1246 1000 932
970
G(Gas)
ø12.7
ø12.7
ø12.7
ø12.7
ø12.7
✻1
720 7
✻2 ø15.88
ø15.88
720 7
E
360
360
480
480
F
4
4
5
5
H(Liquid)
ø6.35
ø6.35
ø6.35
ø6.35
ø6.35
✻1
✻2
ø9.52
ø9.52
Air filter
45
90
J(Liquid)
J(Gas)
17
27
17
27
17
27
17
27
✻1 22 ✻1 29
✻2 22 ✻2 29
22
29
D
B
15
2-12 ✕ 16
Floor mounting hole
106
Level adjusting screw
4 pcs.(attached)
✻1:R410A outdoor unit
✻2:R407C,R22 outdoor unit
58
INDOOR UNIT
Specifications & External Dimensions
PEFY-P
VMH-E-F
(Fresh Air Intake Type)
Specifications
PEFY-P80VMH-E-F
Power source
Cooling capacity
Heating capacity
kW
BTU/h
kW
BTU/h
kW
kW
A
A
Cooling
Heating
Cooling
Heating
Power consumption
(50/60Hz)
Current
PEFY-P140VMH-E-F
~ 220-240V 50Hz / ~ 208-230V 60Hz
❇1
❇1
❇1
❇1
9.0
30,700
8.5
29,000
0.16/0.21
0.16/0.21
0.67/0.91
0.67/0.91
16.0
54,600
15.1
51,500
0.29/0.33
0.29/0.33
1.24/1.48
1.24/1.48
External finish
Height
Width
Depth
Dimension
Galvanizing
380(15")
mm(in.)
mm(in.)
mm(in.)
kg(lbs.)
Net weight
Heat exchanger
Type
1000(39-3/8")
Sirocco fan✕ 1
9.0
150
18
35/85/170
40/115/190
50/130/210
80/170/220
3
m /min
L/s
cfm
Pa
Pa
Pa
Pa
208V
220V
230V
240V
External
static
pressure
(Low/Mid/High)
Type
Motor
Output
Air filter (option)
Refrigerant
pipe diameter
Drain pipe diameter
70(155")
Cross fin (Aluminum plate fin and copper tube)
Airflow rate
Fan
1200(47-1/4")
900(35-7/16")
50(111")
Gas(Flare)
Liquid(Flare)
kW
0.09
mm(in.)
mm(in.)
ø 15.88(5/8")
Sirocco fan✕ 2
18.0
300
636
35/85/170
50/115/190
60/130/220
100/170/240
Single phase induction motor
0.14
Synthetic fiber unwoven cloth filter(long life)
ø 15.88 (5/8") [R410A] / 19.05 (3/4") [R22,R407C]
ø 9.52(3/8")
32 (1-1/4 inch)
28/38/43
34/43/45
27/38/43
208, 220V
dB(A)
230, 240V
33/43/45
dB(A)
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 33˚C(91.4˚F)DB/28˚C(82.4˚F)WB,Outdoor 33˚C(91.4˚F)DB
Heating : Indoor 0˚C(32˚F)DB/-2.9˚C(26.8˚F)WB,Outdoor 0˚C(32˚F)DB/-2.9˚C(26.8˚F)WB
❇ 2 It is measured in anechoic room.
a ). The cooling and heating capacities are the maximum capacities that were obtained by operating in the above air conditions and with a refrigerant pipe of about 7.5m(24-5/8Ft).
b ). The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical information.
c ). The operating noise is the data that was obtained by measuring it 1.5m(4-15/16Ft) from the bottom of the unit in an anechoic room. (Noise meter A-scale value)
d ). The figure of Electrical characteristic indicates at 220V and at middle external static pressure.
e ). When the 100% fresh air indoor units are connected, the maximum connectable indoor units to 1 outdoor unit are as follows.
❇2
Noise level
Heat pump models
110%(100% in case of heating below-5˚C(23˚F)
Cooling only
110%
f ). Operational temp range is cooling : from 21˚C(61.8˚F)DB/15.5˚C (59.9˚F)WB to 43˚C(109.4˚F)DB/35˚C(95˚F)WB.
Heating : from -10˚C(14˚F)DB to 20˚C(68˚F)DB
✻Thermo off (Fan) operation automatically starts either when temperature is lower than 21˚C(69.8˚F)DB in cooling mode or when the temperature exceeds 20˚C(68˚F)DB in heating mode.
g ). As the room temp is sensed by the thermo in the remote controller or the one in the room, be sure to use ether remote controller or room thermo.
h ). Dry mode is Not available. Fan mode operation during the thermo off in Cooling/Heating mode.
i ). The fan would temporarily stops either with R2/WR2 system or in defrost.
j ). In any case, the air flow rate should be kept lower than 110% of the above chart.Please see “ Fan curves “ for the details.
k ). When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
l ). Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation. Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also
insulate rooms for dew condensation prevention as required.
m). Air filter must be installed in the air intake side.The filter should be attached where easy maintenance is possible in case of usage of field supply filters.
n). Long life filter cannot be used together with Hi-efficiency filter.
External Dimensions
PEFY-P80, 140VMH-E-F
Unit : mm
Required space for service and maintenance
625
G-ø3
100
~20
0
700 00
~2
150
450
50
E
Access door Ceiling surface
Make the access door at the appointed position
properly for service maintenance.
50
Less than 300mm
170mm±5mm (Actual length)
80 50
41F
15
340
Model:80(Note3)
23
3
383
814 (Lifting bolt pitch)
904
Lifting bolt
250
60
900
847
24
10
Less than 550mm
70
10
15
Note 1.Use M10 screw for the lifting bolt (field supply).
2.Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned.
3.This chart indicates for PEFY-P140VMH-E-F models, which have 2 fans.
PEFY-P80VMH-E-F model has 1 fan.
4.Make sure to install the air filter(field supply) on the air intake side.
In case field supplied air filter is used, attach it where the filter service is easily done.
5.On Model :140, you would use flare nut packed with the Indoor Unit,
when connnecting the Outdoor Unit for R407C, R22.
6.In order to increase the strength of the flare nut,
the size of some of them has been increased.
Keep duct-work length 850mm or more.
30
Terminal bed
(Transmission)
Drain hole
250
380
77
P
94
50 50 50 50
Terminal box
130
41 25
50
340
50x5=250
45
Terminal bed
(Power source)
328
2
17
3
When installing the drain
water lifting-up mech(option).
29
Drain hole
(option)
Control box
59
Note2
More than 20mm
Air outlet
50x(J-1)=K
B (Lifting bolt pitch)
A
D
C
50x(G-1)=H
Access door
Air inlet
L
50
450
More than 20mm
J-ø3
Refrigerant piping flare connection(gas M copper tube):LP
Refrigerant piping flare connection(liquid N copper tube):HP
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory)
1
92
200
343
387
D
850
F G
E
L
J K
H
800 25 17 800 15 700 1030
M
ø15.88
✻1 ø15.88
PEFY-P140VMH-E-F 1250 1204 1130 1050 1000 25 21 1000 19 900 1230
✻2 ø19.05
Model
PEFY-P80VMH-E-F
C
B
A
1050 1004 930
N
ø9.52
ø9.52
······ ➀
······ ➁
······ ➂
P(Liquid) P(Gas)
29
22
22
36
✻1:R410A outdoor unit
✻2:R407C,R22 outdoor unit
INDOOR UNIT
Specifications & External Dimensions
PEFY-P
VMH-E-F
(Fresh Air Intake Type)
Specifications
PEFY-P200VMH-E-F
PEFY-P250 VMH-E-F
Power source
3N~ 380-415V 50Hz / 60Hz
kW
BTU/h
kW
BTU/h
kW
kW
A
A
Cooling capacity
Heating capacity
Power consumption
(50/60Hz)
Current
Cooling
Heating
Cooling
Heating
22.4
76,400
21.2
72,300
0.34/0.42
0.34/0.42
0.58/0.74
0.58/0.74
28.0
95,500
26.5
90,400
0.39/0.50
0.39/0.50
0.68/0.86
0.68/0.86
External finish
Height
Width
Depth
Dimension
Galvanized
470 (18-9/16")
1250 (49-1/4")
1120 (44-1/8")
100 (221")
Cross fin
Sirocco fan ✕ 2
mm(in.)
mm(in.)
mm(in.)
kg(lbs.)
Net weight
Heat exchanger
Type
3
28
467
989
140/200
150/210
160/220
m /min
Airflow rate
L/s
cfm
Pa
Pa
Pa
Fan
External
static
pressure
Type
Motor
Output
Air filter (option)
Refrigerant
pipe diameter
380V
400V
415V
3-phase induction motor
0.23
Synthetic fiber unmoven cloth filter (long life type)
ø 19.05 (3/4") [R410A]
ø 22.2 (7/8") [R410A]
ø 25.4 (1") [R22,R407C]
ø 28.58 (1-1/8") [R22,R407C]
ø9.52 (3/8") [R410A]
ø9.52 (3/8") [R410A]
ø 12.7 (1/2") [R22,R407C]
ø 12.7 (1/2") [R22,R407C]
Unit drain pipe I.D 32 (1-1/4 inch)
39/42
40/44
40/43
40/45
40/44
41/46
kW
Gas
(Flare)
mm(in.)
Liquid
(Flare)
mm(in.)
380V
400V
415V
dB(A)
dB(A)
dB(A)
0.20
Drain pipe diameter
Noise level
35
583
1236
110/190
120/200
130/210
Note: 1. The cooling amd heating capacites are the maximum capacites that were obitained by operating in the above air conditions and with a refrigerant pipe of about 7.5m.
2 .The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical infomation.
3 .The operating noise is the data that was obitained by measuring it 1.5m from the the bottom of the unit in an anechoic room. (Noise meter A-scale value)
4 .The figure of Electrical characteristic , indicates at 220 Pa setting at 415V.
5 . When the 100% fresh air indoor units are connected, the maximum connectable indoor units to 1 outdoor unit are as follows.
Heat pump models
110%(100% in case of heating below-5˚C(23˚F))
6. Operational temp range is
Cooling only
110%
Cooling:from 21˚C(69.8˚F)DB/15.5˚C(59.9˚F)WB to 43˚C(109.4˚F)DB/35˚C(95˚F)WB
Heating: from -10˚C(14˚F)DB to 20˚C(68˚F)DB.
❇ Thermo off(Fan) operation automatically starts either when temperature is lower than 21˚C(69.8˚F)DB in cooling mode or when the temperature exceeds 20˚C(68˚F)DB in heating mode.
7. As the room temp in sensed by the thermo in the remote controller or the one in the room, be sure to use either remote controller or room thermo.
8. Autochangeover function or Dry mode is NOT available. Fan mode operation during the thermo off in Cooling/Heating mode.
9. The fan would temporaly stops either with R2/WR2 system or in defrost.
10. In any case, the air flow rate should be kept lower than 110% of the above chart. Please see "Fan curves" for the details.
11. When this nit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
12. Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation.
Please be careful when positioning indoor unit air outlet grilles, ie take the necessary precautions for cold air, and also insulate rooms for dew condensation prevention as required.
13. Air filter must be installed in the air intake side. The filter should be attached where easy maintenance in possible in case of usage of fild supply filters.
External Dimensions
PEFY-P200, 250VMH-E-F
Unit : mm
Required space for service and maintenance
22-ø3
22-ø3
730
200~
300
800 200
150~
1350
More than 20
1100
23
3
Lifting bolt
4-14X30
Access door
Ceiling surface
Make the access door at the appointed position properly maintenance.
78
+5
170-
When installing the drain water lifting-up
60
1034(Lifting bolt pitch)
340
Less than 300
1124
170mm+5mm (Actual length)
1120
1067
24
10
29
15
Drain hole
(option)
30
20
Keep duct-work length 850mm or more. Terminal bed
Drain hole
(Power source)
Terminal bed
(Transmission)
2
95
Model
20
3
105
35
41
164
420
50x7=350
44
327
50x6=300
340
470
Control box
Less than 550
420
Note2
More than 20
15
10
50
Access door
100 50
Air outlet
50
450
50x20=1000
1326(Lifting bolt pitch)
1372
Air outlet
102 25
1100
1250
50x21=1050
450
1
249
422
489
······
Refrigerant piping brazing connection(gas A copper tube):LP
Refrigerant piping brazing connection(liquid B copper tube):HP ······
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory) ······
A
B
PEFY-P200VMH-E-F ✻1 ø19.05 ✻1 ø9.52
✻2 ø25.4
✻2 ø12.7
✻1 ø9.52
PEFY-P250VMH-E-F ✻1 ø22.2
✻2 ø28.58 ✻2 ø12.7
✻1:R410A outdoor unit ✻2:The other outdoor unit
Note 1. Use M10 screw for the lifting bolt (field supply).
2.Keep the service space for maintenance from
the bottom
when the heat exchanger is cleaned.
3.Make sure to install the air filter (field supply) on
the air intake side.
In case field supplied air filter is used, attach it
where the filter service is easily done.
➀ 4.On this model, you would use pipe
➁ packed with the Indoor Unit, when connnecting
➂ the Outdoor Unit for R407C, R22.
60
The Ventilation System for Enhanced Air Quality - Lossnay
Combine with Lossnay Ventilation System Enhanced Air Quality.
Unified Control System Allows Greater Design Freedom.
Heat-Exchange Efficiency Obtainable Only with Lossnay.
The secret to the unmatched comfort provided Lossnay core is the crossflow, plate-fin structure off the heat-exchange unit. A diaphragm made of a
specially processed paper fully separates inducted and exhausted air
supplies, ensuring that only fresh air is introduced to the indoor environment.
The superior heat-transfer and moisture permeability of the special paper
assure highly effective total heat exchange (temperature and humidity) when
inducted ? and exhausted air supplies cross in the Lossnay core.
5.2
0
Stale hot air (exhaust)
Fresh cool air(outdoor)
Stale air exhaust
(dirty indoor air)
Lossnay Element
Construction & Principle
Fresh air exhaust
(fresh heating / cooling air)
EA
SA
20
Stale warm air (indoor air)
Outdoors
14.8
Indoors
OA
Fresh warm air (indoor supply air)
Fresh air induction
(fresh air)
LGH-15RX4
LGH-25RX4
LGH-35RX4
LGH-50RX4
LGH-65RX4
LGH-80RX4
LGH-100RX4
LGH-150RX4
LGH-200RX4
RA
Stale air induction
(dirty heating / cooling air)
[150m3/h Single phase 220-240V 50/60Hz]
[250m3/h Single phase 220-240V 50/60Hz]
[350m3/h Single phase 220-240V 50/60Hz]
[500m3/h Single phase 220-240V 50/60Hz]
[650m3/h Single phase 220-240V 50/60Hz]
[800m3/h Single phase 220-240V 50/60Hz]
[1000m3/h Single phase 220-240V 50/60Hz]
[1500m3/h Single phase 220-240V 50/60Hz]
[2000m3/h Single phase 220-240V 50/60Hz]
OA Processing Units
Ideal Indoor-Air Quality — For Your Comfort and Health
The OA (outdoor-air) Processing Unit creates an optimum indoor-air environment at an unparalleled rate of cost efficiency providing substantial
energy savings. Forced air ventilating and humidifying functions unique to this system keep indoor-air fresh and free of contaminants preventing
“sick building syndrome” and the spread of airborne viruses such as the flu. Another novel feature of the OA Processing Unit is the “Lossnay
core,” a heat-exchange unit that functions to transfer heat efficiently, cutting ventilation load by as much as 70%. This special combination of
functionality
and performance designed to ensure users ample comfort and year-round health cannot be found anywhere else on the market.
EA (Exhaust air)
Heat from the indoor air (both sensible
and latent) is recovered by the Lossnay
OA (Outdoor air)
Core and vented outside by the
Fresh, outdoor-air in a quantity exhaust fan.
required for ventilation is drawn
in by the supply fan.
Heat recovery unit
(Lossnay Core)
Temperature and humidity are
exchanged between the supply
air and the exhaust air.
OA Processing Units
The exhaust fan
High efficiency filters (Option)
The supply fan
RA (Return air)
The exhaust
fan draws in
contaminated
indoor-air.
Maintenance cover
Air filter
Prevents clogs in
the Lossnay Core.
DX Heat exchanger
Cools or heats the drawn
in outdoor-air.
SA (Supply air)
The processed, fresh
outdoor-air is vented
to the indoor rooms.
GUF-50RD(H)3 *1
Cooling Capacity
5.29 (DX coil:3.63, Lossnay:1.66)KW
Heating capacity
6.42 (DX coil:4.17, Lossnay:2.25)KW
500m3/h Single phase 220-240V 50Hz
GUF-100RD(H)3 *1
Cooling Capacity
10.81 (DX coil:7.32, Lossnay3.49)KW
Heating capacity
13.00 (DX coil:8.30, Lossnay:4.70)KW
1000m3/h Single phase 220-240V 50Hz
*1 H : Humidifying Type
61
INDOOR UNIT
Y
: PUHY
R2 : PURY
WY : PQHY
WR2 : PQRY
S
: PUMY
PLFY-VAM / VCM
PCFY-VGM
PLFY-VLMD
PKFY-VAM / VGM / VFM
PMFY-VBM
PFFY-VKM
PEFY-VMS
PFFY-VLRM / VLEM
PEFY-VMR
Fresh Air Intake type
PEFY-VML / VMM / VMH
LONWORKS
62
Integrated Communications Control with Mitsubishi's Unique Transmission Network(M-NET)
Model
No. of units controllable
(Groups (G) / units)
Local remote controller
Simple Wireless
Remote controller remote remote
controller controller
PAR-FL32MA
PAR-21MAA PAR-F27MEA PAC-SE/YT51CRA PAR-FA32MA
System controller
ON/OFF Group System Schedule
Centralized controller
remote remote remote
timer
controller controller controller
PAC-YT40ANRA PAC-SC30GRA PAC-SF44SRA PAC-YT34STA
G-50A
GB-50A
TG-2000A
50G/50units 50G/50units
1G/16units 1G/16units 1G/16units 1G/16units 16/50 8G/16units 50/50 50G/50U
2000G/2000units
G-50A browser GB-50A browser
Operation
Start / Stop
✕
Operation mode
Temperature setting
Permit / Prohibit direction
✕
✕
✕
✕
Fan speed
✕
Air flow direction
✕
*4
✕
✕
*4
✕
✕
*4
✕
✕
✕
✕
✕
✕
✕
✕
ON/OFF
Error flashing
✕
Error content
Monitoring
✕
✕
✕
✕
✕
✕
✕
Operation mode
✕
✕
✕
✕
Set temperature
✕
✕
✕
✕
✕
✕
✕
✕
Filter sign
Operating hour
✕
✕
✕
Indoor temperature (intake)
✕
✕
✕
✕
✕
✕
✕
✕
✕
Permit / Prohibit
Fan speed
✕
Air flow direction
*5
Weekly
Scheduling
Annual (Designated day setting)
✕
✕
✕
*5
8
Times of stops / Starts per week
56
*5
*5
✕
✕
✕
✕
✕
✕
✕
✕/
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
*5
✕
16
3/3
12
✕
12
12
*5
112
21/21
84
✕
84
84
✕
Times of stops / Starts per day
1/1
✕
5
10 *
✕
✕
1/1
✕
✕
✕
✕
✕ /336
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
5
10
1
✕
1
1
✕ /48
*5
✕
10
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
Minimum setting unit (minutes)
1
Error history
✕
Daily / Monthly reports
Electricity charges
✕ /30
✕
Set temperature range limit
✕
✕
✕
✕
Auto lock
✕
✕
✕
✕
✕/
✕/
*1
Group setting
✕
✕
✕
/✕
✕
✕
✕
✕
✕
✕/
*2
✕
/
✕
✕
✕
✕
✕
*2
*2
✕
✕
✕
/
✕
*2
✕
✕
*2
*2
✕
*2
✕
✕
✕
✕
✕
Revision of electricity charges
✕
✕
✕
✕
✕
/
Start / Stop
*3
/
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
–/
/
/
/
/
/
/
/
Fan speed
✕
✕
–/
/
✕
/
/
✕
/
/
Ventilation mode
✕
✕
–/✕
/✕
✕
/✕
/✕
✕
/✕
/✕
Status
✕
✕
–/
/
✕
/
/
/
/
Fan speed
✕
✕
–/
/
✕
/
/
✕
/
/
Ventilation mode
✕
✕
–/✕
/✕
✕
/✕
/✕
✕
/✕
/✕
: Each group / Batched
: Each group
: Block (City Multi indoor unit only)
✕ : Not available
: Batched handling (for maintenance)
: Batched only
– : Not used
63
✕
*2
Block setting
Ventilation
Ventilation
(group / interlocked) (group / interlocked)
Control and Others Recording
management
✕
✕
Auto off timer
Monitoring Operation
✕
✕
One day
Ventilation (group / interlocked)
✕
/
: G-50A license registration possible.
*1: For group operation, cross-over wring is required between indoor unit. *2: Installation possible at Initial setting tool.
*3: Interlock setting from local remote controller. *4: From schedule setting *5: When PAC-YT32PTA is connected.
Building Air conditioning
control system
HAND-HELD
REMOTE CONTROLLER
MA REMOTE CONTROLLER PAR-21MAA
High-quality pure-white color body
Dot liquid-crystal display is applied
Symbols, Japanese, Chinese, English, Germany,Spanish, Russian,
Italian, French display can be selected freely.
Connectable to all CITYMULTI indoor unit, and
automatically adjust its function with the indoor unit
connected
Limiting temperature setting range is possible
Help to avoid over-cooling or over-heating. Save energy.
Auto-stop timer is available
Help to avoid forgetting to stop the air conditioner.
Weekly scheduler is available
ON/OFF/Temperature setting 8 times per day, 1 week scheduling.
Grouping via cross-over wire directly
Usable as the local remote controller for system controller
(MELANS)
Combining ME remote controller and/or LOSSNAY remote
controller in a group is not possible.
LCD temperature setting and display in
1˚C /1˚F unit.
TM
Example of system configuration
M-NET
Non-polarized
2-wire
Non-polarized
2-wire
MA remote controller
MA remote controller
ME REMOTE CONTROLLER PAR-F27MEA
Example of system configuration
ME remote controller
ME remote controller
Easy to read, easy to operate icon display
Temperature selection
Room air temperature display
Outlet angle display
Displays the angle of blowing between 20˚ and 70˚. (Only for cassette
model PL and PK. Ceiling mounted models display the air volume
ratio.)
Auto-diagnosis display
A microcomputer constantly monitors operation to keep the units
running smoothly. Should problems occur, the temperature setting
display changes to an auto-diagnosis display that shows the
inspection mode and the unit address alternately.
Standardized remote controllers for all indoor units
All wiring is simply done with non-polarized two-wire signal
lines
Room thermometer is built into the remote controller
Daily timer
Repeated ON / OFF timer every day.
Auto OFF timer
0:30, 1:00, 1:30, 2:00...4:00 one touch timer.
Function lock
All functions or all functions except ON / OFF can be selected.
Limit setting of room temperature.
64
Building Air conditioning
control system
HAND-HELD
REMOTE CONTROLLER
SIMPLE MA REMOTE CONTROLLER PAC-YT51CRA
To simplify operation of the system, the range of controls has been
limited to START/STOP, room temperature and fan speed
The only wiring required is cross-over wiring based on two-wire
signal lines
Room temperature sensors are built-in. The indoor unit can be
replaced with body thermostats
Easy to read, easy to operate icon display
LCD temperature setting and display in
1˚C /1˚F unit.
Can operate all types of indoor units
Standardized remote controllers for all indoor units
*Since this system has no operation mode switching, test operation, selfdiagnosis or interlock setting functions, it should always be used in conjunction
with the PAR-21MAA or other centralized controller.
*Combining ME remote controller and/or LOSSNAY remote
controller in a group is not possible.
PAC-YT51CRA
WIRELESS REMOTE CONTROLLER PAR-FL32MA / PAR-FA32MA
• Wireless construction supports multi - systems in
buildings.
• No need to configure addresses for group operation.
• Lit LED keeps you informed of operation - blinking even
gives you the error code via the number of blinks.
• Can be used with the MA remote controller.
*When used in group configurations, wiring between indoor units is
required.
*Combining ME remote controller and/or LOSSNAY remote
controller in a group is not possible.
• LCD temperature setting and display in 1˚C /1˚F unit.
PAR-FL32MA
65
PAR-FA32MA
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
CENTRAL CONTROLLER G-50A/GB-50A
Up to 50 units of packaged air conditioners can freely be monitored
and operated!
Furthermore, it has enabled the Monitoring and Operation Via a
Web Browser on a Personal Computer connected to it using a LAN
or telephone line!
First in the industry
With Web Server
Functions!
G-50A (with display)
GB-50A
Simple and Flexible
This new generation controller is suitable for small to large systems
with simple to complex functions available.
Web Browser
Enables monitoring and operation of air conditioning units using a PC
with Microsoft® Internet Explorer.
Remote Access
Allows users to remotely monitor and operate the air conditioning
units using a PC connected to a telephone line.
Auto Alarm
In the case of any malfunction, necessary information will be sent to a
mobile phone and/or personal computer by e-mail.
Easy to Upgrade
Various new functions will be introduced gradually and can easily be
down loaded into any existing G-50A/GB-50A.
Example: Energy Monitoring
Demand Control
Annual Schedule
Example of display icons (air conditioner icons)
Operation
In timer operation
Stop
Lossnay on
Occurrence of
abnormality
Under energy-saving
control
Operation/
Occurrence of a filter sign
System Structure
Remote monitoring via a
Web browser
Web browser
City Multi
outdoor unit
G-50A
M-NET
Public telephone
line
Router
Ethernet
UP
Provider
POWER SUPPLY UNIT
MODEL
PAC-SC50KUA
POWER RATING
2.11kg
WEIGHT
SERIAL No.
MITSUBISHI ELECTRIC CORPORATION
Power supply unit
PAC-SC50KUA
City Multi
City Multi
outdoor unit
GB-50A
M-NET
Provider
UP
POWER SUPPLY UNIT
MODEL
PAC-SC50KUA
POWER RATING
WEIGHT
SERIAL No.
2.11kg
MITSUBISHI ELECTRIC CORPORATION
Power supply unit
PAC-SC50KUA
City Multi
* Microsoft is a trademark or trademark of Microsoft corporation.
66
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
GROUP REMOTE CONTROLLER PAC-SC30GRA
Up to 8 groups can be operated (maximum of 16 units). Just by
pressing switches, groups can be started and stopped
individually, or all groups can be started and stopped as a
batch.
Detailed settings and operations can also be made for each
individual group.
All the wiring is simply done with non-polarized two wire signal
lines. The connection is the same as the connection to the
master system controller.
It supports operation of groups that can extend beyond one
refrigerant system. Furthermore, it is possible to drive
interlocked systems that use ventilator equipment or drive
ventilator equipment in a stand-alone situation.
*With the group remote controller, you cannot control groups that
only contain the LOSSNAY remote controller.
*It is impossible to use the group remote controller to control K
control units.
*When connecting to signal cables for central control, it must use a
power supply unit for the signal cables.
System example
Connect to the centralized transmission line
Group remote
controller
UP
Power supply
unit
MA R/C
MA R/C
MA R/C
MA R/C
R/C:Remote Controller
Connect to the indoor/outdoor transmission line
67
R/C:Remote Controller
Group remote
controller
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
SYSTEM REMOTE CONTROLLER PAC-SF44SRA
50 groups/50 units of air conditioners can be controlled
Up to 50 groups/50 units of air conditioners can be operated with one remote
controller.
A general-purpose interface is available for control, so general devices can also be
turned ON and OFF.
Operation status displayed on easy-to-read LCD
The group currently operating can be seen at a glance with the operation status
display for each group.
Independent LOSSNAY operation is possible
LOSSNAY units can be grouped the same as the Central remote controller and
ON/OFF remote controller.
"Automatic ventilation", "Normal ventilation" and "Ventilation with heat
exchanger" can be switched from the system controller.
Simple remote controller limited to basic operations.
The only operations required for the air conditioner are "ON/OFF", "Operation
mode changeover", "Temperature setting" and "Prohibit operation by local remote
controller", so anyone can easilyoperate the unit.
Using collective control from the system remotecontroller, operation mode settings
using the local remote controllers can be prohibited.
(Operation mode limit function)
Schedule operation is available
Groups of air conditioners are available for operation at a set schedule using the
Schedule timer (PAC-YT34STA).
System example
System
remote
controller
UP
Power
supply
unit
MA R/C
LOSSNAY
PZ-52SF
MA R/C
LOSSNAY
LOSSNAY
PZ-52SF
R/C:Remote Controller
68
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
Schedule timer PAC-YT34STA
The weekly schedule of up to 50 groups/50 units can be
controlled with one schedule timer.
General-purpose devices can also be turned ON and OFF by
connecting a general-purpose interface.
The weekly schedule of up to ten patterns (no setting + nine
patterns) is available for setting.
"ON/OFF", "Operation Prohibit", "COOL/HEAT" and "Set
Temperature" can be scheduled with up to 16 settings in one
pattern.
It can be connected to the center control transmission line or to
the indoor/outdoor transmission line without the power supply
unit (PAC-SC50KUA). It is nonpolar 2-wire.
It can be interlocked with a building management system using
the external input/output managing function.
An error unit address and error code appear on the display.
(*) Use in combination with other system controllers.
System example
System
remote
controller
UP
Power supply
unit
LOSSNAY
ME R/C
Schedule timer
MA R/C
R/C:Remote Controller
69
Simple
ME R/C
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
ON/OFF remote controller PAC-YT40ANRA
16 groups/50 units can be controlled
Up to 16 groups/50 units can be operated with one ON/OFF remote controller.
A general-purpose interface is available for control, so general devices can also be
turned ON and OFF.
Just press a switch to start.
All of the units can be started and stopped by pressing the main switch, and each
unit in the group can be started and stopped with individual switches.
A general-purpose interface is available for control, so general devices can also be
turned ON and OFF.
LED flashing during failure.
If any error should occur in the air conditioner, its details can be confirmed easily
with the flashing LED. The LED also indicates whether each group is running or
stopped.
Interlock operation with external system possible.
It can be flexibly interlocked with a card reader, fire alarm system or building
management system, etc., using the incorporated external input/output function.
Flexible group setting.
The groups can be easily configured, so the group pattern can be freely set
according to the layout.
The ON/OFF remote controller can be connected at the indoor/outdoor
transmission line without the power supply unit.
System example
LOSSNAY
PAR-F27MEA
PZ-52SF
ON/OFF
remote
controller
PAR-21MAA
PAC-YT51CRA
R/C:Remote Controller
70
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
Integrated centralized control software TG-2000A
(1) Example of Basic System Configuration.
Single-phase 208/230V
M-NET
Charge
license
Input
G-50A
12VDC
Single-phase 208/230V
Web
monitor
license
UP
POWER SUPPLY UNIT
MODEL
PAC-SC50KUA
POWER RATING
WEIGHT
SERIAL No.
2.11kg
MITSUBISHI ELECTRIC CORPORATION
Power supply unit
PAC-SC50KUA
Schedule
license
3-phase 208/230V
(3-wire)
Indoor unit system
watt-hour meter
Compatible with TG-2000A Ver. 4.10 and higher
* The electric amount count software or separately
procured parts must be used with the designated PLC.
Indoor unit
watt-hour meter
power source
Outdoor unit system
watt-hour meter
Indoor unit system
watt-hour meter
Indoor unit
watt-hour meter
RS-485
Outdoor unit system
watt-hour meter
RS-232C
Converter
PLC (with electric amount count
software)
Central controller
personal computer
TG-2000A
Uninterruptive
power supply (UPS)
Uninterruptible
power supply (UPS)
Integrated
centralized control
software installation
Central control
personal computer
TG-2000A
Integrated centralized control
software installation
The TG-2000A can realize the following functions using
the G-50A/GB-50A option (license).
* Operation/monitor
* Annual/weekly schedule
* Charge
* Energy saving *1
* Peak cut *1
*1: Compatible with TG-2000A Ver. 4.10 and higher,
G-50A Ver. 2.51 or later.
Main features of TG-2000A
1 Up to 2000 indoor units (40 G-50A/GB-50A units) can be operated and monitored simultaneously.
2 The air-conditioner layout can be displayed on the screen, making control and operation easier.
3 The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be
saved in the weekly schedule.
4 Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment
5
6
7
8
71
percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment
function, and can be output as a CSV format file. * Power apportionment charging is not possible with the old model, A control or K control.
Charging without WHM
: The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
RS-485 WHM charging
: The RS-485 WHM value is automatically tabulated to calculate the air-conditioning charges.
PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the air-conditioning charges.
Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and
"performance save operation (60% to 90%)" functions.
Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count software.
Night set-back operation is possible with schedule settings. *1*4
General equipment can be operated and monitored. *2
General equipment can be schedule-controlled when using PAC-YG21CDA with PLC.
For details of PLC refer to Installation Manual of PAC-YG21CDA. *3
*1: Compatible with TG-2000A Ver. 4.10 and higher, G-50A Ver. 2.51 and higher.
*2: Compatible with TG-2000A Ver. 4.30 and higher, G-50A Ver. 2.51 and higher.
*3: Compatible with TG-2000A Ver. 4.60 and higher, G-50A Ver. 2.70 and higher.
*4: With Night Set-Back function,the CITY MULTI system can run at heating mode with target temperature set to 54 F/12 C
under schedule control. This function can protect the room from dropping down to extremely low temperature at mid-night.
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
LONWORKS (LMAP02)
CITY MULTITM can easily combine into a Building Management System (BMS) via the LonWorksTM and M-NET adapter
LMAP03-U. LonWorksTM is an opened transmission protocol widely used at BMS, and related equipment control.
CITY MULTITM is therefore compatible with large-scaled BMS management via LonWorksTM.
One LM ADAPTER unit can connect up to 50 Groups/50 indoor units.
Using a single LONWORKS adapter (LM ADAPTER), you can connect up to
a maximum of 50 indoor units.
Operation
Monitor
LMAP
LMAP 02
Protocol converter
between LON WORKS
and M-NET
L ON WORKS
Item
Request On/Off
Request Mode
Setpoint from network (Both cool and heat)
Request Fanspeed
Request Local Prohibit On/Off
Request Local Prohibit mode
Request Local Prohibit SetPoint
Request All Off
On/Off run state
Mode state
Setpoint state (both cool and heat)
FanSpeed state
Thermo On/Off state
Temperature state of indoor
Alarm state
Local Prohibit On/Off state
Local Prohibit mode state
Local Prohibit SetPoint state
M-NET
LMAP
CITY MULTI System
Example of System Configuration
CITY MULTI
System design made simple through integration of
various devices into a total control configuration.
Outdoor unit
Outdoor unit
208-230V
60Hz
LON WORKS
(78kdps)
M-NET
LMAP
Indoor units
Max. 50 indoor units
Indoor units
Indoor units
Indoor units
Indoor units
Lighting
Center
control device
Security
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
LON WORKS
The building management system is connected to the CITY MULTI air conditioning system using LON WORKS , which is widely used on
field networks, allowing for an open network and savings in construction to face.
LON, LON WORKS and the Echelon logo are trademarks of
Echelon Corporation registered in the United States and other countries.
72
Building Air conditioning
control system
CENTRALIZED
REMOTE CONTROLLER
BACnet TM interface(PAC-YG31CDA)
MITSUBISHI ELECTRIC's CITYMULTI can be easily connect to the building management system through BACnet. BACnet is the
appropriate transmission method and used in many of the backbone networks and also it is easy to combine with other equipment
corresponding to BACnet.
One BACnet interface software manages up to 500 Groups/500 Indoor units. (10 G-50A/GB-50A units).
(1) Example of Basic System Configuration.
Central
monitor
BACnet
BMS
TM
M-NET
LAN
G-50A
BACnetTM interface software
PAC-YG31CDA
UP
M-NET
PAC-SC50KUA
Power supply unit
G-50A
Web
Browser
(Optional)
TG-2000A
(Optional)
Operation
Monitor
73
Item
On/Off (state)
Operation mode (state)
Fan Speed (state)
Air direction (state)
Room Temp.
Filter Signal
Alam signal
Error Code
Communication State
On/Off (setup)
Operation mode (setup)
Fan Speed (setup)
Air direction (setup)
Set Temp.
Filter Signal
Prohibition of local operation (On/Off)
Prohibition of local operation (Mode)
Prohibition of local operation (filter reset)
Prohibition of local operation (Set temp.)
System Forced Off
WHM
WHM
CITY MULTI
OPTIONAL PARTS
R410A
OPTIONAL PARTS FOR OUTDOOR UNITS
For PU(H)Y, PURY series
Description
Model
Remarks
High static pressure motor
PAC-KBU04MT-F
~ 60Pa
Note: In case of using PAC-KBU04MT-F, when carrying out intensive install of the outdoor unit, please extend on installation interval to 20mm or more.
For PU(H)Y, PURY series
Description
Branch pipe (Joint)
Model
CMY-Y102S-G
200 or below
CMY-Y102L-G1
201-400
CMY-Y202-G1
CMY-Y302-G1
Branch pipe (Header)
Total capacity of indoor unit
401-650
The 1st branch of P450~P650
651 or above
The 1st branch of P700~P1250
CMY-Y104-G
For 4 branches
CMY-Y108-G
For 8 branches
CMY-Y1010-G
For 10 branches
Note : Indoor unit capacities
The capacity of an indoor unit is the same as the number used for its type identification.
For PUMY-P100, P125, P140YHM / PUMY-P100, P125, P140VHM
Description
Model
Branch Pipe (2 Branch)
CMY-Y62-G-E
Header
CMY-Y64-G-E
Header
CMY-Y68-G-E
Drain Socket
PAC-SG61DS-E
Centralized Drain Pan
PAC-SG64DP-E
Port Connector (ø9.52 → ø12.7 )
PAC-SG73RJ-E
Port Connector (ø15.88 → ø19.05)
PAC-SG75RJ-E
Air Protect Guide ( 2 pcs required )
PAC-SH63AG-E
OPTIONAL EQUIPMENT FOR BC CONTROLLER
BC Controller Model
CMB-P104V-G, GB
CMB-P105V-G
CMB-P106V-G
CMB-P108V-G, GA, GB
CMB-P1010V-G, GA
CMB-P1013V-G, GA
CMB-P1016V-G, GA
Junction pipe kit
CMY-R160-J
Branch pipe
CMY-Y102S-G
74
CITY MULTI
OPTIONAL PARTS
R410A
OPTIONAL PARTS FOR INDOOR UNITS
4-way cassette type (PLFY-VCM / VAM)
Description
Decoration panel
Multi-function casement
High-efficiency filter element
Air outlet shutter plate (1 set)
Model
SLP-2AA
PLP-6AA
PAC-SG03TM-E
PAC-SG01KF
PAC-SG06SP-E
2-way cassette type (PLFY-VLMD)
Description
Model
CMP-40VLW-B
CMP-63VLW-B
CMP-100VLW-B
CMP-125VLW-B
PAC-KH11OF
Decoration panel
OA duct flange
Applicable capacity
PLFY-VLMD-B
P20, P25, P32, P40
P50, P63
P80, P100
P125
P20, P25, P32, P40, P50, P63, P80, P100
Applicable capacity
VAM
–
P32, P40, P50, P63, P80, P100, P125
P32, P40, P50, P63, P80, P100, P125
P80, P100, P125
P32, P40, P50, P63, P80, P100, P125
VCM
P20, P25, P32, P40
–
–
–
–
1-way cassette type(PMFY-VBM)
Description
Model
Applicable capacity
Decoration panel
PMP-40BM
P20, P25, P32, P40
Ceiling concealed type (PEFY-VMH)
Description
Drain lift-up mechanism
Long life filter
Filter box
Model
PAC-KE04DM-F
PAC-KE32LAF-F
PAC-KE86LAF
PAC-KE88LAF
PAC-KE89LAF
PAC-KE85LAF
PAC-KE63TB-F
PAC-KE80TB-F
PAC-KE140TB-F
PAC-KE250TB-F
Applicable capacity
PEFY-VMH
P40~P250
–
P40, P50, P63
P71, P80
P100, P125, P140
P200, P250
P40, P50, P63
P71, P80
P100, P125, P140
P200, P250
Remarks
Standard Filter is attached
Necessary when long life filter is used
Ceiling concealed type (PEFY-VMM)
Description
Round shape duct flange
Drain lift-up mechanism
Model
Applicable capacity
PAC-KE32EDF-F
PAC-KE50EDF-F
PAC-KE80EDF-F
PAC-KE125EDF-F
PAC-KE140EDF-F
PAC-KE03DM-F
P20, P25, P32
P40, V50
P63, P71, P80
P100, P125
P140
P20, P25, P32, P40, P50, P63, P71, P80, P100, P125, P140
Ceiling suspended type (PCFY-VGM)
Description
High efficiency filter
Drain lift-up mechanism
Model
PAC-SE80KF-E
PAC-SE81KF-E
PAC-SE82KF-E
PAC-SE84DM-E
PAC-SE85DM-E
PAC-SE86DM-E
Applicable capacity
P40
P63, P100
P125
P40
P63
P100, P125
Fresh air intake type (PEFY-VMH-E-F)
Description
Long life filter
Filter box
Drain water lift-up kit
75
Model
PAC-KE88LAF
PAC-KE89LAF
PAC-KE85LAF
PAC-KE80TB-F
PAC-KE140TB-F
PAC-KE250TB-F
PAC-KE04DM-F
Applicable capacity
P80
P140
P200, P250
P80
P140
P200/P250
P80, P140, P200, P250
Single phase Multi Split system (5HP)
MSZ-FA series
MSZ-FA series
MSZ-GA series
Branch Box
SLZ series
MFZ series
PEAD series
PLA series
SEZ series
MXZ-8A140VA Single phase, 50Hz
Up to 8 indoor units
can be connected !
*MXZ-8A140VA can NOT be connected with City Multi indoor units.
The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series
9000 of the International Standard Organization (ISO) based on a review of Quality , management for
the production of refrigeration and air conditioning equipment.
FM 33568 / ISO 9001;2000
ISO Authorization System
The ISO 9000 series is a plant authorization system relating to quality management as stipulated by
the ISO. ISO 9001 certifies quality management based on the "design, development, production,
installation and auxiliary services" for products built at an authorized plant.
The Air Conditioning & Refrigeration Systems Works acquired environmental management system
standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO).
Certificate Number EC97J1227
http://Global.MitsubishiElectric.com/
MITSUBISHI ELECTRIC PRODUCTS ARE DISTRIBUTED BY...
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
http://Global.MitsubishiElectric.com
MEE05K437
New publication effective Jul. 2006
Specifications subject to change without notice